Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:34
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2023-10-16 08:34:38
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1256.95 | 601.32 | 601.32 |
Net Site Energy | 1256.95 | 601.32 | 601.32 |
Total Source Energy | 3636.81 | 1739.84 | 1739.84 |
Net Source Energy | 3636.81 | 1739.84 | 1739.84 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 165.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 200.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 496.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 103.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 61.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1091.83 | 165.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 165.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 200.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 496.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 100.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 103.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 61.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 165.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 200.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 496.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 100.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 103.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 61.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 285.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 175.14 | 79.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 522.33 | 79.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 285.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 175.14 | 79.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 522.33 | 79.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1091.828 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1091.828 | 100.00 |
Total On-Site and Utility Electric Sources | 1091.828 | 100.00 |
Total Electricity End Uses | 1091.828 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.33 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1433.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:34 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 20.1123 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 23.1025 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 20.9200 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 20.9200 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 20.9200 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 13.4438 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 17.2687 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 17.2687 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 20.1123 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 23.1025 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 20.9200 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 20.9200 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 20.9200 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 13.4438 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 13.5625 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 13.5625 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 13.5625 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 13.5625 | 6.19 | 4.3000 | |
Total | 2090.32 | 17.2687 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 17.2687 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 17.2687 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 08-JUL-15:09 | 12-FEB-09:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 200306.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 52877.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 30804.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8394.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5426.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 105561.21 | 200306.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 200306.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 52877.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 30804.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8394.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5426.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 179.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 635.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 318.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 328.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 196.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3457.82 | 179.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 85.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 303.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 752.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 152.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 156.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 93.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1654.21 | 85.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 85.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 303.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 752.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 152.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 156.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 93.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1654.21 | 85.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.18 |
SMSTORE1 DIRECT AIR | 1.15 |
SMSTORE2 DIRECT AIR | 1.14 |
SMSTORE3 DIRECT AIR | 1.13 |
SMSTORE4 DIRECT AIR | 1.13 |
LGSTORE2 DIRECT AIR | 2.01 |
SMSTORE5 DIRECT AIR | 1.02 |
SMSTORE6 DIRECT AIR | 1.02 |
SMSTORE7 DIRECT AIR | 1.01 |
SMSTORE8 DIRECT AIR | 1.17 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.18 | 2.18 | 2.18 | 2.18 | 2.18 | 2.18 | 1.00 | 1.00 | 2.18 |
PSZ-AC_2:2 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.00 | 1.000000 | 1.15 |
PSZ-AC_3:3 | 1.14 | 1.14 | 1.14 | 1.14 | 1.15 | 1.15 | 1.00 | 0.986819 | 1.15 |
PSZ-AC_4:4 | 1.13 | 1.13 | 1.13 | 1.13 | 1.15 | 1.15 | 1.00 | 0.977344 | 1.15 |
PSZ-AC_5:5 | 1.13 | 1.13 | 1.13 | 1.13 | 1.14 | 1.14 | 1.00 | 0.985421 | 1.14 |
PSZ-AC_6:6 | 2.01 | 2.01 | 2.01 | 2.01 | 2.01 | 2.01 | 1.00 | 1.00 | 2.01 |
PSZ-AC_7:7 | 1.02 | 1.02 | 1.02 | 1.02 | 1.04 | 1.04 | 1.00 | 0.978546 | 1.04 |
PSZ-AC_8:8 | 1.02 | 1.02 | 1.02 | 1.02 | 1.04 | 1.04 | 1.00 | 0.978850 | 1.04 |
PSZ-AC_9:9 | 1.01 | 1.01 | 1.01 | 1.01 | 1.04 | 1.04 | 1.00 | 0.974545 | 1.04 |
PSZ-AC_10:10 | 1.17 | 1.17 | 1.17 | 1.17 | 1.17 | 1.17 | 1.00 | 1.00 | 1.17 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.18 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.15 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.15 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.15 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.14 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.01 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.04 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.04 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.04 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.17 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.18 | 2332.70 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.15 | 1278.45 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.15 | 1273.51 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.15 | 1276.54 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.14 | 1265.73 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.01 | 2151.39 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1155.17 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1149.17 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1149.58 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.17 | 1294.75 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.18 | 2.18 | 2.18 | 1.44 | 49431.39 | 61206.57 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.15 | 1.15 | 1.15 | 0.762112 | 25837.55 | 32029.35 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.15 | 1.15 | 1.15 | 0.759166 | 25765.84 | 31596.82 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.15 | 1.15 | 1.15 | 0.760974 | 25811.78 | 31415.58 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 0.754529 | 25650.06 | 31408.75 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.01 | 2.01 | 2.01 | 1.33 | 46453.12 | 57470.83 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 0.688618 | 23988.56 | 29081.61 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 0.685046 | 23897.88 | 28971.81 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 0.685286 | 23904.63 | 28881.15 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.17 | 1.17 | 1.17 | 0.771827 | 26040.36 | 32354.90 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.18 | 1.09 | 1.45 | 49431.39 | 24715.69 | 0.730400 | 0.730400 |
PSZ-AC_2:2 COOLING COIL | 1.15 | 0.577357 | 0.769807 | 25837.55 | 12918.77 | 0.734990 | 0.734990 |
PSZ-AC_3:3 COOLING COIL | 1.15 | 0.575126 | 0.766833 | 25765.84 | 12882.92 | 0.734690 | 0.734690 |
PSZ-AC_4:4 COOLING COIL | 1.15 | 0.576495 | 0.768660 | 25811.78 | 12905.89 | 0.734860 | 0.734860 |
PSZ-AC_5:5 COOLING COIL | 1.14 | 0.571613 | 0.762153 | 25650.06 | 12825.03 | 0.734250 | 0.734250 |
PSZ-AC_6:6 COOLING COIL | 2.01 | 1.01 | 1.34 | 46453.12 | 23226.56 | 0.724410 | 0.724410 |
PSZ-AC_7:7 COOLING COIL | 1.04 | 0.521680 | 0.695573 | 23988.56 | 11994.28 | 0.725710 | 0.725710 |
PSZ-AC_8:8 COOLING COIL | 1.04 | 0.518974 | 0.691967 | 23897.88 | 11948.94 | 0.725330 | 0.725330 |
PSZ-AC_9:9 COOLING COIL | 1.04 | 0.519156 | 0.692207 | 23904.63 | 11952.32 | 0.725350 | 0.725350 |
PSZ-AC_10:10 COOLING COIL | 1.17 | 0.584717 | 0.779620 | 26040.36 | 13020.18 | 0.736310 | 0.736310 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 61206.57 |
PSZ-AC_2:2 HEATING COIL | 32029.35 |
PSZ-AC_3:3 HEATING COIL | 31596.82 |
PSZ-AC_4:4 HEATING COIL | 31415.58 |
PSZ-AC_5:5 HEATING COIL | 31408.75 |
PSZ-AC_6:6 HEATING COIL | 57470.83 |
PSZ-AC_7:7 HEATING COIL | 29081.61 |
PSZ-AC_8:8 HEATING COIL | 28971.81 |
PSZ-AC_9:9 HEATING COIL | 28881.15 |
PSZ-AC_10:10 HEATING COIL | 32354.90 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 20.112 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.412 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 23.103 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 27.403 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 20.920 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.220 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 20.920 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.220 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 20.920 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.220 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 4694.002 | 13.474 | 83.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4694.002 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 2312.850 | 6.639 | 41.117 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2312.850 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2367.672 | 13.592 | 84.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2367.672 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1656.630 | 9.510 | 58.904 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1656.630 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1281.630 | 7.358 | 45.570 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1281.630 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1281.630 | 7.358 | 45.570 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1281.630 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1281.630 | 7.358 | 45.570 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1281.630 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 4683.651 | 13.444 | 83.264 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4683.651 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6887 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.218 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
19 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
20 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
21 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
22 | 7 | -0.33074266E-12 | 0.10604805E-14 | -0.10376772E-12 | 0.10050050E-15 |
23 | 6 | 0.29711555E-07 | 0.19576406E-09 | 0.67975929E-08 | -0.14079383E-12 |
24 | 5 | -0.19537397E-03 | 0.16642354E-05 | -0.10041974E-03 | 0.67165186E-08 |
25 | 4 | 0.29828781 | 0.80514357E-03 | 0.10189302 | -0.34439683E-04 |
26 | 3 | -7.3878975 | 0.24810408E-01 | -2.3749899 | 0.29604922E-01 |
27 | 2 | 41.272027 | 0.87780140E-01 | 15.412956 | -0.33780550 |
28 | 1 | -80.852930 | 0.39442104E-01 | -29.274215 | 1.0851646 |
29 | 0 | 46.824337 | 0.79011109E-03 | 16.288086 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 35 | 1 | VerySmooth | 2.826 | 2.826 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.02458E-002 | 0.16139 | 0.61152 | 0.61152 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.11029 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 23861.75516 | 28634.10619 | 1.81666 | 2.18000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 34.40000 | 1.44733E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 22285.81304 | 26742.97565 | 0.99636 | 1.19563 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 12639.40954 | 15167.29144 | 0.96226 | 1.15471 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.32083 | 1.44731E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 10343.96251 | 12412.75501 | 0.46247 | 0.55496 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 12761.89184 | 15314.27021 | 0.94591 | 1.13509 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 29.17500 | 1.44637E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 10499.67828 | 12599.61393 | 0.46943 | 0.56332 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 12671.84857 | 15206.21828 | 0.93906 | 1.12687 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 29.17500 | 1.44637E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 10601.31162 | 12721.57394 | 0.47397 | 0.56877 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 12667.88550 | 15201.46260 | 0.93880 | 1.12656 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 29.17500 | 1.44637E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 10761.00665 | 12913.20798 | 0.48111 | 0.57734 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 22007.66909 | 26409.20290 | 1.67546 | 2.01055 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.24167 | 1.44730E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 20827.58067 | 24993.09681 | 0.93119 | 1.11743 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11503.33977 | 13804.00773 | 0.85081 | 1.02098 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 30.79000 | 1.44667E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 11084.45542 | 13301.34650 | 0.49557 | 0.59469 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11448.51722 | 13738.22067 | 0.84666 | 1.01600 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 30.79000 | 1.44667E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 11073.58130 | 13288.29755 | 0.49509 | 0.59411 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 11403.14008 | 13683.76809 | 0.84324 | 1.01188 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 30.79000 | 1.44667E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 11286.76185 | 13544.11421 | 0.50462 | 0.60554 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 12801.47217 | 15361.76660 | 0.97453 | 1.16943 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 33.92500 | 1.44724E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 13922.86943 | 16707.44331 | 0.62244 | 0.74693 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 33238.98 | 2.18000 | 2.18000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 39509.60 | 1.19563 | 1.19563 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 17454.95 | 1.15471 | 1.15471 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 18810.12 | 0.55496 | 0.55496 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 17392.84 | 1.15025 | 1.15025 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 18994.26 | 0.56332 | 0.56332 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 17426.88 | 1.15299 | 1.15299 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 19114.44 | 0.56877 | 0.56877 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 17300.99 | 1.14323 | 1.14323 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 19303.28 | 0.57734 | 0.57734 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 31038.02 | 2.01055 | 2.01055 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 37785.47 | 1.11743 | 1.11743 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 16007.33 | 1.04336 | 1.04336 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 19685.77 | 0.59469 | 0.59469 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 15937.27 | 1.03795 | 1.03795 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 19672.91 | 0.59411 | 0.59411 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 15940.68 | 1.03831 | 1.03831 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 19925.01 | 0.60554 | 0.60554 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 17533.81 | 1.16943 | 1.16943 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 23042.02 | 0.74693 | 0.74693 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.18000 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.15471 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.13509 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.12687 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.12656 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.01055 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02098 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.01600 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.01188 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.16943 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.18000 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.18000 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.18000 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.18000 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.18000 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.18000 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.15471 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.15471 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.15471 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.15471 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.15471 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.15471 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.13509 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.13509 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.13509 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.13509 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.15025 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.15025 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 0.98682 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.12687 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.12687 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.12687 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.12687 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.15299 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.15299 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 0.97734 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.12656 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.12656 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.12656 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.12656 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14323 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14323 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 0.98542 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.01055 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.01055 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.01055 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.01055 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.01055 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.01055 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02098 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02098 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02098 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02098 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04336 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04336 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.97855 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.01600 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.01600 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.01600 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.01600 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.03795 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.03795 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.97885 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.01188 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.01188 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.01188 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.01188 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.03831 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.03831 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.97454 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.16943 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.16943 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.16943 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.16943 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.16943 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.16943 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.18000 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.15471 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.15025 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.15299 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.14323 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.01055 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.04336 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.03795 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.03831 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.16943 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.18000 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.18000 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2332.69781 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.18000 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.18000 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.18000 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.43880 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.18000 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.09000 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.45333 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 49431.39000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 24715.69500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73040 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73040 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 49431.39000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 61206.56756 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 61206.56756 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.15471 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.15471 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1278.45247 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.15471 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.15471 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.15471 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76211 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.15471 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57736 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76981 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25837.55000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12918.77500 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73499 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73499 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25837.55000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32029.35274 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 32029.35274 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.15025 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.15025 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1273.51150 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.15025 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.15025 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.15025 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75917 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.15025 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57513 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76683 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25765.84000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12882.92000 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73469 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73469 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25765.84000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31596.81575 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 31596.81575 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.15299 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.15299 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1276.54352 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.15299 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.15299 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.15299 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76097 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.15299 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57650 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76866 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25811.78000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12905.89000 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73486 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73486 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25811.78000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31415.57906 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 31415.57906 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14323 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14323 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1265.73306 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14323 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14323 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14323 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75453 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14323 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57161 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76215 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25650.06000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12825.03000 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73425 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73425 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25650.06000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31408.75242 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 31408.75242 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.01055 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.01055 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2151.38877 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.01055 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.01055 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.01055 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.32697 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.01055 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.00528 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.34037 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 46453.12000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 23226.56000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72441 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72441 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 46453.12000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 57470.82799 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 57470.82799 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04336 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04336 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1155.16625 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04336 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04336 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04336 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68862 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04336 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52168 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69557 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23988.56000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11994.28000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72571 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72571 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23988.56000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29081.60693 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 29081.60693 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.03795 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.03795 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1149.17323 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.03795 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.03795 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.03795 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68505 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.03795 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51897 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69197 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23897.88000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11948.94000 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72533 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72533 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23897.88000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28971.80811 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 28971.80811 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.03831 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.03831 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1149.57711 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.03831 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.03831 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.03831 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68529 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.03831 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51916 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69221 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23904.63000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11952.31500 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72535 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72535 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23904.63000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28881.14804 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 28881.14804 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.16943 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.16943 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1294.75012 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.16943 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.16943 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.16943 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77183 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.16943 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58472 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.77962 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26040.36000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13020.18000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73631 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73631 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26040.36000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32354.89931 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 32354.89931 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 47714.5 | 11.61 | 11.61 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 24928.4 | 11.76 | 11.76 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 24860.2 | 11.76 | 11.76 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 24903.9 | 11.76 | 11.76 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 24749.9 | 11.76 | 11.76 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 44869.2 | 11.64 | 11.64 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 23166.6 | 11.81 | 11.81 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 23080.2 | 11.81 | 11.81 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 23086.7 | 11.81 | 11.81 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 25119.7 | 11.75 | 11.75 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 2.1514044304E-002 | 9.3593571979E-002 | Pass | Pass | 0.9241241185 | 8.7258898696 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 5.8280120765E-002 | 0.1136584052 | Pass | Pass | 0.1273997003 | 0.6813941707 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 2.3799868292E-002 | 9.2397042573E-002 | Pass | Pass | 0.2210308243 | 1.1826557745 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.1173337034E-002 | 0.1473203441 | Pass | Pass | 0.1276037263 | 0.3725792684 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.8765744916E-002 | 0.1863888629 | Pass | Pass | 0.3689195437 | 2.6689179903 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 3.8746194373E-002 | 0.2062214519 | Pass | Pass | 0.3665391959 | 1.1661817374 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 3.6936139994E-002 | 0.2063154571 | Pass | Pass | 0.1394121006 | 0.4079567136 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 3.6992254046E-002 | 0.2073264406 | Pass | Pass | 0.1517827774 | 0.6402920157 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.1061413993E-002 | 0.2184083763 | Pass | Pass | 0.1084820929 | 0.5582336633 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 5.6170461825E-002 | 0.2972372239 | Pass | Pass | 9.7734335870E-002 | 0.6728533485 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2867.05 | 36.31 | 0.00 | 98.02 | 1037.64 | 4039.03 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.826 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.826 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.826 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.826 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.826 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 13.4735 | 348.39 | 4694.00 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 83.90 | 0.0000 | Y | 73.93 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 6.6387 | 348.39 | 2312.85 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 42.32 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 13.5922 | 174.19 | 2367.67 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 85.39 | 0.0000 | Y | 37.95 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 9.5103 | 174.19 | 1656.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 30.31 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 30.25 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 7.3575 | 174.19 | 1281.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.76 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 30.25 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 7.3575 | 174.19 | 1281.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.76 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 30.25 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 7.3575 | 174.19 | 1281.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.76 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 13.4438 | 348.39 | 4683.65 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 54.16 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 8.6344 | 4180.64 | 36097.17 | 496.92 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 458.42 | AstronomicalClock | - | 41.77 | 41.77 | 3.59 | |
EXTERIOR_LIGHTS_B | 7264.83 | AstronomicalClock | - | 83.77 | 71.17 | 97.06 | |
Exterior Lighting Total | 7723.25 | 100.65 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 49431.39 | 36104.69 | 13326.70 | 0.73 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25837.55 | 18990.34 | 6847.21 | 0.73 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25765.84 | 18929.90 | 6835.94 | 0.73 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25811.78 | 18968.04 | 6843.74 | 0.73 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25650.06 | 18833.56 | 6816.50 | 0.73 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 46453.12 | 33651.10 | 12802.02 | 0.72 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23988.56 | 17408.74 | 6579.82 | 0.73 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23897.88 | 17333.85 | 6564.03 | 0.73 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23904.63 | 17339.22 | 6565.41 | 0.73 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26040.36 | 19173.78 | 6866.58 | 0.74 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 47714.5 | 11.61 | 11.61 | ||||
PSZ-AC_2:2 COOLING COIL | 24928.4 | 11.76 | 11.76 | ||||
PSZ-AC_3:3 COOLING COIL | 24860.2 | 11.76 | 11.76 | ||||
PSZ-AC_4:4 COOLING COIL | 24903.9 | 11.76 | 11.76 | ||||
PSZ-AC_5:5 COOLING COIL | 24749.9 | 11.76 | 11.76 | ||||
PSZ-AC_6:6 COOLING COIL | 44869.2 | 11.64 | 11.64 | ||||
PSZ-AC_7:7 COOLING COIL | 23166.6 | 11.81 | 11.81 | ||||
PSZ-AC_8:8 COOLING COIL | 23080.2 | 11.81 | 11.81 | ||||
PSZ-AC_9:9 COOLING COIL | 23086.7 | 11.81 | 11.81 | ||||
PSZ-AC_10:10 COOLING COIL | 25119.7 | 11.75 | 11.75 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 61206.57 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 32029.35 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 31596.82 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 31415.58 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 31408.75 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 57470.83 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 29081.61 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 28971.81 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 28881.15 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 32354.90 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.18 | 2332.70 | 1070.05 | 1.00 | 1.30 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.15 | 1278.45 | 1107.16 | 1.00 | 1.37 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.15 | 1273.51 | 1107.16 | 1.00 | 1.37 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.15 | 1276.54 | 1107.16 | 1.00 | 1.37 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1265.73 | 1107.16 | 1.00 | 1.37 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.01 | 2151.39 | 1070.05 | 1.00 | 1.31 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1155.17 | 1107.16 | 1.00 | 1.39 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1149.17 | 1107.16 | 1.00 | 1.39 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1149.58 | 1107.16 | 1.00 | 1.39 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.17 | 1294.75 | 1107.16 | 1.00 | 1.37 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 23861.76 | 28634.11 | 82.19 | 1.817 | 2.180 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 23.89 | 23.88 | 0.00971 | 34.40 | 0.01447 | 0.411 | 0.00 |
SMSTORE1 | 12639.41 | 15167.29 | 87.07 | 0.962 | 1.155 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.88 | 0.00967 | 34.32 | 0.01447 | 0.206 | 0.00 |
SMSTORE2 | 12761.89 | 15314.27 | 87.92 | 0.946 | 1.135 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00944 | 29.17 | 0.01446 | 0.206 | 0.00 |
SMSTORE3 | 12671.85 | 15206.22 | 87.30 | 0.939 | 1.127 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00944 | 29.17 | 0.01446 | 0.206 | 0.00 |
SMSTORE4 | 12667.89 | 15201.46 | 87.27 | 0.939 | 1.127 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00946 | 29.17 | 0.01446 | 0.206 | 0.00 |
LGSTORE2 | 22007.67 | 26409.20 | 75.80 | 1.675 | 2.011 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00976 | 34.24 | 0.01447 | 0.411 | 0.00 |
SMSTORE5 | 11503.34 | 13804.01 | 79.25 | 0.851 | 1.021 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00942 | 30.79 | 0.01447 | 0.206 | 0.00 |
SMSTORE6 | 11448.52 | 13738.22 | 78.87 | 0.847 | 1.016 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00943 | 30.79 | 0.01447 | 0.206 | 0.00 |
SMSTORE7 | 11403.14 | 13683.77 | 78.56 | 0.843 | 1.012 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00944 | 30.79 | 0.01447 | 0.206 | 0.00 |
SMSTORE8 | 12801.47 | 15361.77 | 88.19 | 0.975 | 1.169 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 23.89 | 23.88 | 0.00972 | 33.92 | 0.01447 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 22285.81 | 26742.98 | 76.76 | 0.996 | 1.196 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00669 | -6.30 | 0.00230 | 0.411 | 0.00 |
SMSTORE1 | 10343.96 | 12412.76 | 71.26 | 0.462 | 0.555 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00663 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE2 | 10499.68 | 12599.61 | 72.33 | 0.469 | 0.563 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00664 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE3 | 10601.31 | 12721.57 | 73.03 | 0.474 | 0.569 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00665 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE4 | 10761.01 | 12913.21 | 74.13 | 0.481 | 0.577 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00666 | -6.30 | 0.00230 | 0.206 | 0.00 |
LGSTORE2 | 20827.58 | 24993.10 | 71.74 | 0.931 | 1.117 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00674 | -6.30 | 0.00230 | 0.411 | 0.00 |
SMSTORE5 | 11084.46 | 13301.35 | 76.36 | 0.496 | 0.595 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00669 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE6 | 11073.58 | 13288.30 | 76.28 | 0.495 | 0.594 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00669 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE7 | 11286.76 | 13544.11 | 77.75 | 0.505 | 0.606 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00670 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE8 | 13922.87 | 16707.44 | 95.91 | 0.622 | 0.747 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00672 | -6.30 | 0.00230 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.18 | 2.18 | 1.20 | 1.20 | 2.1800 | 2.1800 | 2.1800 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.15 | 1.15 | 0.55 | 0.55 | 1.1547 | 1.1547 | 1.1547 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.15 | 1.15 | 0.56 | 0.56 | 1.1503 | 1.1351 | 1.1503 | 0.9868 | 1.0000 |
PSZ-AC_4:4 | 1.15 | 1.15 | 0.57 | 0.57 | 1.1530 | 1.1269 | 1.1530 | 0.9773 | 1.0000 |
PSZ-AC_5:5 | 1.14 | 1.14 | 0.58 | 0.58 | 1.1432 | 1.1266 | 1.1432 | 0.9854 | 1.0000 |
PSZ-AC_6:6 | 2.01 | 2.01 | 1.12 | 1.12 | 2.0106 | 2.0106 | 2.0106 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.04 | 1.04 | 0.59 | 0.59 | 1.0434 | 1.0210 | 1.0434 | 0.9785 | 1.0000 |
PSZ-AC_8:8 | 1.04 | 1.04 | 0.59 | 0.59 | 1.0379 | 1.0160 | 1.0379 | 0.9789 | 1.0000 |
PSZ-AC_9:9 | 1.04 | 1.04 | 0.61 | 0.61 | 1.0383 | 1.0119 | 1.0383 | 0.9745 | 1.0000 |
PSZ-AC_10:10 | 1.17 | 1.17 | 0.75 | 0.75 | 1.1694 | 1.1694 | 1.1694 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 49431.390 | 36104.687 | 2.180000 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24715.69 | 18508.94 | 1.453333 | 26.77 | 18.65 | 0.01060958 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 28.3128 | 23.88 | 0.00971062 | 50.6508 | 23861.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 61206.568 | 61206.568 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 61206.57 | 61206.57 | 2.179995 | 15.93 | 10.40 | 0.00586355 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 18.8752 | 21.11 | 0.00669319 | 41.5351 | 22285.81 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 25837.550 | 18990.341 | 1.154710 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 12918.77 | 9757.61 | 0.769807 | 26.69 | 18.56 | 0.01052786 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 26.7261 | 23.88 | 0.00967238 | 50.4541 | 12638.05 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 32029.353 | 32029.353 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32029.35 | 32029.35 | 1.154715 | 16.22 | 10.51 | 0.00585497 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 17.8173 | 21.11 | 0.00662617 | 41.1229 | 10343.96 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 25765.840 | 18929.905 | 1.150250 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 12882.92 | 9723.34 | 0.766833 | 26.70 | 18.57 | 0.01053498 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 26.8297 | 23.89 | 0.00967670 | 50.4763 | 12585.48 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 31596.816 | 31596.816 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31596.82 | 31596.82 | 1.150252 | 16.20 | 10.51 | 0.00586300 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 17.8865 | 21.11 | 0.00663959 | 41.2054 | 10499.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 25811.780 | 18968.045 | 1.152990 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 12905.89 | 9744.59 | 0.768660 | 26.69 | 18.56 | 0.01053110 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 26.7660 | 23.89 | 0.00967436 | 50.4642 | 12614.29 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 31415.579 | 31415.579 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31415.58 | 31415.58 | 1.152991 | 16.22 | 10.53 | 0.00587174 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 17.8440 | 21.11 | 0.00664799 | 41.2569 | 10601.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 25650.060 | 18833.557 | 1.143230 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 12825.03 | 9669.08 | 0.762153 | 26.71 | 18.58 | 0.01054556 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 26.9945 | 23.89 | 0.00968310 | 50.5091 | 12507.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 31408.752 | 31408.752 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31408.75 | 31408.75 | 1.143226 | 16.17 | 10.51 | 0.00587600 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 17.9964 | 21.11 | 0.00666127 | 41.3385 | 10761.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 46453.120 | 33651.105 | 2.010550 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23226.56 | 17205.75 | 1.340367 | 26.94 | 18.79 | 0.01072464 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 30.6990 | 23.89 | 0.00975956 | 50.9016 | 21998.89 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 57470.828 | 57470.828 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 57470.83 | 57470.83 | 2.010555 | 15.50 | 10.18 | 0.00582878 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 20.4659 | 21.11 | 0.00673739 | 41.8051 | 20827.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 23988.560 | 17408.738 | 1.043360 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 11994.28 | 8896.80 | 0.695573 | 26.89 | 18.76 | 0.01070692 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 29.5784 | 23.89 | 0.00978103 | 51.0120 | 11412.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 29081.607 | 29081.607 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29081.61 | 29081.61 | 1.043361 | 15.70 | 10.26 | 0.00582155 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 19.7189 | 21.11 | 0.00668706 | 41.4969 | 11084.46 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 23897.880 | 17333.849 | 1.037950 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 11948.94 | 8854.92 | 0.691967 | 26.90 | 18.77 | 0.01071637 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 29.7326 | 23.89 | 0.00978679 | 51.0416 | 11353.45 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 28971.808 | 28971.808 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28971.81 | 28971.81 | 1.037948 | 15.67 | 10.24 | 0.00581639 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 19.8217 | 21.11 | 0.00668626 | 41.4920 | 11073.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 23904.630 | 17339.223 | 1.038310 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 11952.32 | 8857.82 | 0.692207 | 26.90 | 18.77 | 0.01071591 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 29.7223 | 23.89 | 0.00978651 | 51.0402 | 11356.34 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 28881.148 | 28881.148 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28881.15 | 28881.15 | 1.038313 | 15.68 | 10.25 | 0.00582972 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 19.8148 | 21.11 | 0.00670251 | 41.5918 | 11286.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 26040.360 | 19173.777 | 1.169430 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 13020.18 | 9781.30 | 0.779620 | 26.58 | 18.55 | 0.01055870 | 12.80 | 11.77 | 0.00850000 | 33.92 | 0.01447239 | 23.42 | 26.3897 | 23.88 | 0.00972317 | 50.7154 | 12784.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 32354.899 | 32354.899 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32354.90 | 32354.90 | 1.169435 | 16.28 | 10.63 | 0.00593965 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 17.5931 | 21.10 | 0.00671715 | 41.6842 | 13922.87 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 49431.390 | 36104.687 | 2.180000 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5627 | 1004.8586 | 1.1610 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.179995 | 2.53092317 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 24715.69 | 18508.94 | 1.0000 | 1.68728591 | 1.453333 | 26.77 | 18.65 | 0.01060958 | 53960.7 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24715.69 | 34.40 | 0.01447326 | 23.54 | 0.41147883 | 28.3128 | 23.88 | 0.00971062 | 23.88 | 0.00971062 | 50.6508 | 23861.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 61206.568 | 61206.568 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.179995 | 2.53092317 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 61206.57 | 61206.57 | 1.0000 | 2.53092317 | 2.179995 | 15.93 | 10.40 | 0.00586355 | 30848.6 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61206.57 | -6.30 | 0.00229779 | -6.30 | 0.41147883 | 18.8752 | 21.11 | 0.00669319 | 21.11 | 0.00669319 | 41.5351 | 22285.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25837.550 | 18990.341 | 1.154710 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4108 | 1004.8586 | 1.1610 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.154715 | 1.34059667 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 12918.77 | 9757.61 | 1.0000 | 0.89372748 | 0.769807 | 26.69 | 18.56 | 0.01052786 | 53670.7 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12918.77 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 26.7261 | 23.89 | 0.00967238 | 23.88 | 0.00967238 | 50.4541 | 12638.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32029.353 | 32029.353 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.154715 | 1.34059667 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32029.35 | 32029.35 | 1.0000 | 1.34059667 | 1.154715 | 16.22 | 10.51 | 0.00585497 | 31121.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32029.35 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 17.8173 | 21.11 | 0.00662617 | 21.11 | 0.00662617 | 41.1229 | 10343.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25765.840 | 18929.905 | 1.150250 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4240 | 1004.8586 | 1.1610 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.150252 | 1.33541553 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 12882.92 | 9723.34 | 1.0000 | 0.89027551 | 0.766833 | 26.70 | 18.57 | 0.01053498 | 53696.9 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12882.92 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 26.8297 | 23.89 | 0.00967670 | 23.89 | 0.00967670 | 50.4763 | 12585.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31596.816 | 31596.816 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.150252 | 1.33541553 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31596.82 | 31596.82 | 1.0000 | 1.33541553 | 1.150252 | 16.20 | 10.51 | 0.00586300 | 31122.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31596.82 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 17.8865 | 21.11 | 0.00663959 | 21.11 | 0.00663959 | 41.2054 | 10499.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25811.780 | 18968.045 | 1.152990 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4168 | 1004.8586 | 1.1610 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.152991 | 1.33859494 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 12905.89 | 9744.59 | 1.0000 | 0.89239623 | 0.768660 | 26.69 | 18.56 | 0.01053110 | 53682.6 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12905.89 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 26.7660 | 23.89 | 0.00967436 | 23.89 | 0.00967436 | 50.4642 | 12614.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31415.579 | 31415.579 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.152991 | 1.33859494 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31415.58 | 31415.58 | 1.0000 | 1.33859494 | 1.152991 | 16.22 | 10.53 | 0.00587174 | 31156.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31415.58 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 17.8440 | 21.11 | 0.00664799 | 21.11 | 0.00664799 | 41.2569 | 10601.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25650.060 | 18833.557 | 1.143230 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4437 | 1004.8586 | 1.1610 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.143226 | 1.32725900 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 12825.03 | 9669.08 | 1.0000 | 0.88484214 | 0.762153 | 26.71 | 18.58 | 0.01054556 | 53735.8 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12825.03 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 26.9945 | 23.89 | 0.00968310 | 23.89 | 0.00968310 | 50.5091 | 12507.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31408.752 | 31408.752 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.143226 | 1.32725900 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31408.75 | 31408.75 | 1.0000 | 1.32725900 | 1.143226 | 16.17 | 10.51 | 0.00587600 | 31125.1 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31408.75 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 17.9964 | 21.11 | 0.00666127 | 21.11 | 0.00666127 | 41.3385 | 10761.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 46453.120 | 33651.105 | 2.010550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7766 | 1004.8586 | 1.1610 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.010555 | 2.33420705 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 23226.56 | 17205.75 | 1.0000 | 1.55613426 | 1.340367 | 26.94 | 18.79 | 0.01072464 | 54426.4 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23226.56 | 34.40 | 0.01447326 | 23.54 | 0.41147883 | 30.6990 | 23.89 | 0.00975956 | 23.89 | 0.00975956 | 50.9016 | 21998.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 57470.828 | 57470.828 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.010555 | 2.33420705 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 57470.83 | 57470.83 | 1.0000 | 2.33420705 | 2.010555 | 15.50 | 10.18 | 0.00582878 | 30318.3 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 57470.83 | -6.30 | 0.00229779 | -6.30 | 0.41147883 | 20.4659 | 21.11 | 0.00673739 | 21.11 | 0.00673739 | 41.8051 | 20827.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23988.560 | 17408.738 | 1.043360 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7436 | 1004.8586 | 1.1610 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.043361 | 1.21131764 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 11994.28 | 8896.80 | 1.0000 | 0.80754432 | 0.695573 | 26.89 | 18.76 | 0.01070692 | 54333.2 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11994.28 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 29.5784 | 23.89 | 0.00978103 | 23.89 | 0.00978103 | 51.0120 | 11412.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29081.607 | 29081.607 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.043361 | 1.21131764 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 29081.61 | 29081.61 | 1.0000 | 1.21131764 | 1.043361 | 15.70 | 10.26 | 0.00582155 | 30507.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29081.61 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 19.7189 | 21.11 | 0.00668706 | 21.11 | 0.00668706 | 41.4969 | 11084.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23897.880 | 17333.849 | 1.037950 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7612 | 1004.8586 | 1.1610 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.037948 | 1.20503331 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 11948.94 | 8854.92 | 1.0000 | 0.80335707 | 0.691967 | 26.90 | 18.77 | 0.01071637 | 54368.4 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11948.94 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 29.7326 | 23.89 | 0.00978679 | 23.89 | 0.00978679 | 51.0416 | 11353.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28971.808 | 28971.808 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.037948 | 1.20503331 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28971.81 | 28971.81 | 1.0000 | 1.20503331 | 1.037948 | 15.67 | 10.24 | 0.00581639 | 30466.1 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28971.81 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 19.8217 | 21.11 | 0.00668626 | 21.11 | 0.00668626 | 41.4920 | 11073.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23904.630 | 17339.223 | 1.038310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7603 | 1004.8586 | 1.1610 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.038313 | 1.20545683 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 11952.32 | 8857.82 | 1.0000 | 0.80363570 | 0.692207 | 26.90 | 18.77 | 0.01071591 | 54366.7 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11952.32 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 29.7223 | 23.89 | 0.00978651 | 23.89 | 0.00978651 | 51.0402 | 11356.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28881.148 | 28881.148 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.038313 | 1.20545683 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28881.15 | 28881.15 | 1.0000 | 1.20545683 | 1.038313 | 15.68 | 10.25 | 0.00582972 | 30501.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28881.15 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 19.8148 | 21.11 | 0.00670251 | 21.11 | 0.00670251 | 41.5918 | 11286.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26040.360 | 19173.777 | 1.169430 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4681 | 1004.8586 | 1.1610 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.169435 | 1.35768654 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 13020.18 | 9781.30 | 1.0000 | 0.90512053 | 0.779620 | 26.58 | 18.55 | 0.01055870 | 53640.0 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13020.18 | 33.92 | 0.01447239 | 23.42 | 0.20573941 | 26.3897 | 23.89 | 0.00972317 | 23.88 | 0.00972317 | 50.7154 | 12784.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32354.899 | 32354.899 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.169435 | 1.35768654 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32354.90 | 32354.90 | 1.0000 | 1.35768654 | 1.169435 | 16.28 | 10.63 | 0.00593965 | 31397.6 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32354.90 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 17.5931 | 21.11 | 0.00671715 | 21.10 | 0.00671715 | 41.6842 | 13922.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 2.18 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.15 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.15 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.15 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.14 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 2.01 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.04 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.04 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.04 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.17 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3288.33 | 2662.83 | 745.00 |
SMSTORE1 | 2998.33 | 2202.17 | 245.50 |
SMSTORE2 | 2432.00 | 1926.00 | 450.50 |
SMSTORE3 | 2444.50 | 1968.67 | 481.17 |
SMSTORE4 | 2431.00 | 2069.50 | 549.33 |
LGSTORE2 | 2220.17 | 2117.50 | 722.33 |
SMSTORE5 | 2177.50 | 2158.00 | 741.00 |
SMSTORE6 | 2182.00 | 2185.33 | 769.00 |
SMSTORE7 | 2210.50 | 2255.83 | 847.33 |
SMSTORE8 | 2378.83 | 2354.50 | 1058.33 |
Facility | 3862.17 | 3388.50 | 1433.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 2.17 | 0.00 | 0.33 | 0.00 |
SMSTORE1 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 2.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 9.67 | 0.00 | 0.00 | 0.00 |
Facility | 12.33 | 0.00 | 0.33 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 17.08 | 56.25 | 1805.20 | 0.982 | 0.227 | 0.000 | 0.000 |
SMSTORE1 | 8.54 | 28.12 | 902.60 | 0.862 | 0.241 | 0.000 | 0.000 |
SMSTORE2 | 7.18 | 28.12 | 902.60 | 1.033 | 0.314 | 0.000 | 0.000 |
SMSTORE3 | 7.18 | 28.12 | 902.60 | 1.030 | 0.314 | 0.000 | 0.000 |
SMSTORE4 | 7.18 | 28.12 | 902.60 | 1.017 | 0.314 | 0.000 | 0.000 |
LGSTORE2 | 24.93 | 56.25 | 1805.20 | 0.982 | 0.302 | 0.000 | 0.000 |
SMSTORE5 | 12.46 | 28.12 | 902.60 | 0.989 | 0.335 | 0.000 | 0.000 |
SMSTORE6 | 12.46 | 28.12 | 902.60 | 0.984 | 0.335 | 0.000 | 0.000 |
SMSTORE7 | 12.46 | 28.12 | 902.60 | 0.976 | 0.335 | 0.000 | 0.000 |
SMSTORE8 | 12.46 | 28.12 | 902.60 | 0.993 | 0.355 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 17.08 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.54 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.18 | 28.12 | 902.60 | 0.801 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.18 | 28.12 | 902.60 | 0.801 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.18 | 28.12 | 902.60 | 0.801 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.93 | 56.25 | 1805.20 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.46 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.46 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.46 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.46 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 17.08 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.54 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.18 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.18 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.18 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 121.95 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 10185752.64 | 0.00 | 10185752.64 | 2731052.24 | 12916804.87 | 12976396.34 | 3169.35 | 4421.96 | 1168.69 | 17.46 |
SMSTORE1 | 4464343.68 | 0.00 | 4464343.68 | 1359523.50 | 5823867.18 | 6488198.17 | 4406.16 | 3177.25 | 1176.59 | 21.46 |
SMSTORE2 | 4081125.07 | 0.00 | 4081125.07 | 1395493.01 | 5476618.08 | 6488198.17 | 4336.78 | 3551.92 | 871.30 | 96.10 |
SMSTORE3 | 4066400.34 | 0.00 | 4066400.34 | 1395493.01 | 5461893.35 | 6488198.17 | 4337.41 | 3572.50 | 850.09 | 91.96 |
SMSTORE4 | 4012839.29 | 0.00 | 4012839.29 | 1395493.01 | 5408332.29 | 6488198.17 | 4340.18 | 3623.33 | 796.49 | 85.62 |
LGSTORE2 | 7059283.25 | 0.00 | 7059283.25 | 2566144.11 | 9625427.37 | 12976396.34 | 4720.54 | 3345.92 | 693.55 | 49.58 |
SMSTORE5 | 3554268.20 | 0.00 | 3554268.20 | 1406000.65 | 4960268.85 | 6488198.17 | 4720.41 | 3355.94 | 683.64 | 50.03 |
SMSTORE6 | 3537000.77 | 0.00 | 3537000.77 | 1406000.65 | 4943001.42 | 6488198.17 | 4720.19 | 3372.92 | 666.89 | 47.37 |
SMSTORE7 | 3503618.51 | 0.00 | 3503618.51 | 1406000.65 | 4909619.16 | 6488198.17 | 4722.33 | 3415.67 | 622.00 | 37.92 |
SMSTORE8 | 3563555.30 | 0.00 | 3563555.30 | 1733578.79 | 5297134.10 | 6488198.17 | 4721.96 | 3452.25 | 585.79 | 23.40 |
Total Facility | 48028187.05 | 0.00 | 48028187.05 | 16794779.62 | 64822966.67 | 77858378.04 | 4729.49 | 5075.29 | 1547.05 | 174.80 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4835 | 0.0000 | 0.4835 | 0.1116 | 0.5951 | 0.4115 | 254.89 | 4421.62 | 1163.49 |
SMSTORE1 | 0.2120 | 0.0000 | 0.2120 | 0.0593 | 0.2713 | 0.2057 | 1488.78 | 3177.08 | 1174.13 |
SMSTORE2 | 0.2542 | 0.0000 | 0.2542 | 0.0773 | 0.3315 | 0.2057 | 0.00 | 3551.25 | 843.75 |
SMSTORE3 | 0.2533 | 0.0000 | 0.2533 | 0.0773 | 0.3307 | 0.2057 | 0.00 | 3571.83 | 823.17 |
SMSTORE4 | 0.2503 | 0.0000 | 0.2503 | 0.0773 | 0.3276 | 0.2057 | 0.00 | 3623.00 | 772.00 |
LGSTORE2 | 0.4833 | 0.0000 | 0.4833 | 0.1485 | 0.6318 | 0.4115 | 0.00 | 3345.75 | 684.25 |
SMSTORE5 | 0.2433 | 0.0000 | 0.2433 | 0.0824 | 0.3258 | 0.2057 | 0.00 | 3355.94 | 674.06 |
SMSTORE6 | 0.2422 | 0.0000 | 0.2422 | 0.0824 | 0.3246 | 0.2057 | 0.00 | 3372.67 | 657.33 |
SMSTORE7 | 0.2402 | 0.0000 | 0.2402 | 0.0824 | 0.3226 | 0.2057 | 0.00 | 3415.67 | 614.33 |
SMSTORE8 | 0.2445 | 0.0000 | 0.2445 | 0.0873 | 0.3318 | 0.2057 | 0.00 | 3452.08 | 577.92 |
Total Facility | 2.9067 | 0.0000 | 2.9067 | 0.8860 | 3.7927 | 2.4689 | 1595.16 | 5073.38 | 1518.90 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 13729192.91 | 0.00 | 13729192.91 | 12976396.34 | 3162.26 | 0.17 | 5597.57 | 17.46 |
PSZ-AC_2:2 | 6017379.46 | 0.00 | 6017379.46 | 6488198.17 | 4325.63 | 4.75 | 4429.62 | 21.46 |
PSZ-AC_3:3 | 5500865.35 | 0.00 | 5500865.35 | 6488198.17 | 4326.01 | 1.33 | 4432.65 | 96.10 |
PSZ-AC_4:4 | 5481018.53 | 0.00 | 5481018.53 | 6488198.17 | 4327.88 | 0.53 | 4431.59 | 91.96 |
PSZ-AC_5:5 | 5408823.60 | 0.00 | 5408823.60 | 6488198.17 | 4331.62 | 0.83 | 4427.54 | 85.62 |
PSZ-AC_6:6 | 9515082.82 | 0.00 | 9515082.82 | 12976396.34 | 4716.09 | 0.50 | 4043.41 | 49.58 |
PSZ-AC_7:7 | 4790727.89 | 0.00 | 4790727.89 | 6488198.17 | 4715.66 | 0.00 | 4044.34 | 49.61 |
PSZ-AC_8:8 | 4767449.75 | 0.00 | 4767449.75 | 6488198.17 | 4715.99 | 0.50 | 4043.51 | 47.21 |
PSZ-AC_9:9 | 4722438.64 | 0.00 | 4722438.64 | 6488198.17 | 4719.14 | 0.17 | 4040.69 | 37.92 |
PSZ-AC_10:10 | 4803188.66 | 0.00 | 4803188.66 | 6488198.17 | 4719.96 | 0.17 | 4039.88 | 23.40 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6517 | 0.0000 | 0.6517 | 0.4115 | 249.22 | 0.00 | 5590.78 |
PSZ-AC_2:2 | 0.2857 | 0.0000 | 0.2857 | 0.2057 | 1410.67 | 4.75 | 4424.58 |
PSZ-AC_3:3 | 0.3426 | 0.0000 | 0.3426 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3415 | 0.0000 | 0.3415 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3373 | 0.0000 | 0.3373 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.6514 | 0.0000 | 0.6514 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3280 | 0.0000 | 0.3280 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3265 | 0.0000 | 0.3265 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3237 | 0.0000 | 0.3237 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.3295 | 0.0000 | 0.3295 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5044.89 | 595.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4458.41 | 877.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4046.22 | 444.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4061.20 | 425.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4090.75 | 389.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3792.66 | 286.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3791.27 | 288.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3799.52 | 277.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3819.54 | 248.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3815.71 | 237.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.6542 | 0.8748 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.3036 | 0.3686 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3303 | 0.4818 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3297 | 0.4809 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3264 | 0.4806 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6366 | 0.8892 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3200 | 0.4536 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3187 | 0.4542 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3163 | 0.4583 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3202 | 0.4937 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 759 |
Defaulted Fields | 823 |
Fields with Defaults | 2681 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1091.83 | 3274.06 | 01-JAN-08:00 | 105561.21 | 08-JUL-15:10 |
Electricity:Building | 625.08 | 2063.06 | 01-JAN-00:10 | 38863.50 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 142.50 | 391.26 | 01-JAN-00:10 | 7378.51 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 625.08 | 2063.06 | 01-JAN-00:10 | 38863.50 | 01-JAN-11:10 |
InteriorLights:Electricity | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 116.25 | 317.63 | 01-JAN-00:10 | 6035.26 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 116.25 | 317.63 | 01-JAN-00:10 | 6035.26 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 81.39 | 223.36 | 01-JAN-00:10 | 4215.80 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 68.27 | 186.54 | 01-JAN-00:10 | 3544.17 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 68.27 | 186.54 | 01-JAN-00:10 | 3544.17 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 59.43 | 204.26 | 01-JAN-00:10 | 3853.00 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 59.43 | 204.26 | 01-JAN-00:10 | 3853.00 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 59.43 | 204.26 | 01-JAN-00:10 | 3853.00 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 73.33 | 274.94 | 01-JAN-00:10 | 5168.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 54.16 | 201.30 | 01-JAN-00:10 | 3825.14 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 54.16 | 201.30 | 01-JAN-00:10 | 3825.14 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1091.83 | 3274.06 | 01-JAN-08:00 | 105561.21 | 08-JUL-15:10 |
ElectricityPurchased:Plant | 1091.83 | 3274.06 | 01-JAN-08:00 | 105561.21 | 08-JUL-15:10 |
Cogeneration:ElectricityPurchased | 1091.83 | 3274.06 | 01-JAN-08:00 | 105561.21 | 08-JUL-15:10 |
General:Cogeneration:ElectricityPurchased | 1091.83 | 3274.06 | 01-JAN-08:00 | 105561.21 | 08-JUL-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1091.83 | 3274.06 | 01-JAN-08:00 | 105561.21 | 08-JUL-15:10 |
ElectricityNet:Plant | 1091.83 | 3274.06 | 01-JAN-08:00 | 105561.21 | 08-JUL-15:10 |
Cogeneration:ElectricityNet | 1091.83 | 3274.06 | 01-JAN-08:00 | 105561.21 | 08-JUL-15:10 |
General:Cogeneration:ElectricityNet | 1091.83 | 3274.06 | 01-JAN-08:00 | 105561.21 | 08-JUL-15:10 |
Electricity:HVAC | 304.14 | 0.00 | 01-JAN-00:10 | 62182.34 | 08-JUL-14:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 200.54 | 0.00 | 01-JAN-00:10 | 53565.67 | 08-JUL-14:00 |
General:Cooling:Electricity | 200.54 | 0.00 | 01-JAN-00:10 | 53565.67 | 08-JUL-14:00 |
Fans:Electricity | 103.60 | 0.00 | 01-JAN-00:10 | 9506.54 | 12-FEB-09:10 |
General:Fans:Electricity | 103.60 | 0.00 | 01-JAN-00:10 | 9506.54 | 12-FEB-09:10 |
ExteriorLights:Electricity | 100.65 | 0.00 | 01-JAN-07:50 | 7723.25 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 100.65 | 0.00 | 01-JAN-07:50 | 7723.25 | 01-JAN-06:10 |
Electricity:Plant | 61.96 | 1211.00 | 02-JAN-07:10 | 11827.30 | 27-MAR-13:40 |
WaterSystems:Electricity | 61.96 | 1211.00 | 02-JAN-07:10 | 11827.30 | 27-MAR-13:40 |
Water Heater:WaterSystems:Electricity | 61.96 | 1211.00 | 02-JAN-07:10 | 11827.30 | 27-MAR-13:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 165.13 | 0.00 | 01-JAN-00:10 | 200306.64 | 12-FEB-09:10 |
NaturalGas:HVAC | 165.13 | 0.00 | 01-JAN-00:10 | 200306.64 | 12-FEB-09:10 |
Heating:NaturalGas | 165.13 | 0.00 | 01-JAN-00:10 | 200306.64 | 12-FEB-09:10 |
General:Heating:NaturalGas | 165.13 | 0.00 | 01-JAN-00:10 | 200306.64 | 12-FEB-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1553.52 | 0.00 | 01-JAN-00:10 | 301393.53 | 08-JUL-14:00 |
EnergyTransfer:Building | 617.35 | 0.00 | 01-JAN-00:10 | 140990.68 | 13-FEB-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 131.99 | 0.00 | 01-JAN-00:10 | 30285.50 | 12-FEB-08:10 |
Heating:EnergyTransfer | 41.56 | 0.00 | 01-JAN-00:10 | 140985.42 | 13-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 5.40 | 0.00 | 01-JAN-00:10 | 30285.50 | 12-FEB-08:10 |
General:Heating:EnergyTransfer | 41.56 | 0.00 | 01-JAN-00:10 | 140985.42 | 13-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 5.40 | 0.00 | 01-JAN-00:10 | 30285.50 | 12-FEB-08:10 |
Cooling:EnergyTransfer | 575.79 | 0.00 | 01-JAN-00:10 | 100905.68 | 08-JUL-15:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 126.59 | 0.00 | 01-JAN-00:10 | 17350.83 | 08-JUL-16:10 |
General:Cooling:EnergyTransfer | 575.79 | 0.00 | 01-JAN-00:10 | 100905.68 | 08-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 126.59 | 0.00 | 01-JAN-00:10 | 17350.83 | 08-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 72.04 | 0.00 | 01-JAN-00:10 | 10314.92 | 11-OCT-20:20 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 1.32 | 0.00 | 01-JAN-00:10 | 10238.88 | 12-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 1.32 | 0.00 | 01-JAN-00:10 | 10238.88 | 12-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 70.71 | 0.00 | 01-JAN-00:10 | 10314.92 | 11-OCT-20:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 70.71 | 0.00 | 01-JAN-00:10 | 10314.92 | 11-OCT-20:20 |
EnergyTransfer:Zone:SMSTORE2 | 53.44 | 0.00 | 01-JAN-00:10 | 12397.91 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 2.20 | 0.00 | 01-JAN-00:10 | 12397.91 | 12-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 2.20 | 0.00 | 01-JAN-00:10 | 12397.91 | 12-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 51.24 | 0.00 | 01-JAN-00:10 | 8835.12 | 08-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 51.24 | 0.00 | 01-JAN-00:10 | 8835.12 | 08-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 52.95 | 0.00 | 01-JAN-00:10 | 13067.43 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 2.49 | 0.00 | 01-JAN-00:10 | 13067.43 | 12-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 2.49 | 0.00 | 01-JAN-00:10 | 13067.43 | 12-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 50.46 | 0.00 | 01-JAN-00:10 | 8869.92 | 08-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 50.46 | 0.00 | 01-JAN-00:10 | 8869.92 | 08-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 50.90 | 0.00 | 01-JAN-00:10 | 13794.03 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 2.98 | 0.00 | 01-JAN-00:10 | 13794.03 | 12-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 2.98 | 0.00 | 01-JAN-00:10 | 13794.03 | 12-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 47.92 | 0.00 | 01-JAN-00:10 | 8715.08 | 08-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 47.92 | 0.00 | 01-JAN-00:10 | 8715.08 | 08-JUL-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 83.22 | 0.00 | 01-JAN-00:10 | 29039.83 | 12-FEB-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 6.39 | 0.00 | 01-JAN-00:10 | 29039.83 | 12-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 6.39 | 0.00 | 01-JAN-00:10 | 29039.83 | 12-FEB-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 76.84 | 0.00 | 01-JAN-00:10 | 15858.05 | 08-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 76.84 | 0.00 | 01-JAN-00:10 | 15858.05 | 08-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE5 | 42.73 | 0.00 | 01-JAN-00:10 | 15168.47 | 12-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 3.72 | 0.00 | 01-JAN-00:10 | 15168.47 | 12-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 3.72 | 0.00 | 01-JAN-00:10 | 15168.47 | 12-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 39.01 | 0.00 | 01-JAN-00:10 | 8283.61 | 08-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 39.01 | 0.00 | 01-JAN-00:10 | 8283.61 | 08-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE6 | 42.21 | 0.00 | 01-JAN-00:10 | 15376.60 | 12-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 3.90 | 0.00 | 01-JAN-00:10 | 15376.60 | 12-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 3.90 | 0.00 | 01-JAN-00:10 | 15376.60 | 12-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 38.31 | 0.00 | 01-JAN-00:10 | 8238.29 | 08-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 38.31 | 0.00 | 01-JAN-00:10 | 8238.29 | 08-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE7 | 41.51 | 0.00 | 01-JAN-00:10 | 16354.18 | 12-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 4.68 | 0.00 | 01-JAN-00:10 | 16354.18 | 12-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 4.68 | 0.00 | 01-JAN-00:10 | 16354.18 | 12-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 36.83 | 0.00 | 01-JAN-00:10 | 8260.13 | 08-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 36.83 | 0.00 | 01-JAN-00:10 | 8260.13 | 08-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 46.36 | 0.00 | 01-JAN-00:10 | 18878.76 | 12-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 8.48 | 0.00 | 01-JAN-00:10 | 18878.76 | 12-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 8.48 | 0.00 | 01-JAN-00:10 | 18878.76 | 12-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 37.88 | 0.00 | 01-JAN-00:10 | 9374.04 | 08-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 37.88 | 0.00 | 01-JAN-00:10 | 9374.04 | 08-JUL-14:10 |
EnergyTransfer:HVAC | 936.17 | 0.00 | 01-JAN-00:10 | 201100.20 | 08-JUL-14:00 |
HeatingCoils:EnergyTransfer | 132.10 | 0.00 | 01-JAN-00:10 | 160245.31 | 12-FEB-09:10 |
CoolingCoils:EnergyTransfer | 804.07 | 0.00 | 01-JAN-00:10 | 201100.20 | 08-JUL-14:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 5.401 | -126.590 | 0.000 | 0.000 | 24.238 | 116.248 | 26.249 | 16.797 | 0.000 | 5.321 | 0.000 | 0.000 | -8.901 | 0.000 | -19.290 | -39.471 |
SMSTORE1 | 0.000 | 0.000 | 1.321 | -70.713 | 0.000 | 0.000 | 11.980 | 68.266 | 13.125 | 8.316 | 0.000 | 2.882 | 0.000 | 0.000 | -4.688 | 0.000 | -9.189 | -21.299 |
SMSTORE2 | 0.000 | 0.000 | 2.199 | -51.241 | 0.000 | 0.000 | 7.271 | 49.007 | 10.421 | 8.281 | 0.000 | 2.821 | 0.000 | 0.000 | -4.676 | 0.000 | -9.459 | -14.623 |
SMSTORE3 | 0.000 | 0.000 | 2.487 | -50.459 | 0.000 | 0.000 | 7.280 | 49.007 | 10.421 | 8.293 | 0.000 | 2.821 | 0.000 | 0.000 | -4.628 | 0.000 | -9.400 | -15.822 |
SMSTORE4 | 0.000 | 0.000 | 2.984 | -47.917 | 0.000 | 0.000 | 7.296 | 49.007 | 10.421 | 8.320 | 0.000 | 2.822 | 0.003 | 0.000 | -4.553 | 0.000 | -9.307 | -19.072 |
LGSTORE2 | 0.000 | 0.000 | 6.385 | -76.835 | 0.000 | 0.000 | 25.127 | 54.161 | 19.173 | 16.784 | 0.000 | 5.095 | 0.003 | 0.000 | -8.711 | 0.000 | -17.086 | -24.092 |
SMSTORE5 | 0.000 | 0.000 | 3.725 | -39.004 | 0.000 | 0.000 | 12.571 | 27.807 | 9.586 | 8.385 | 0.000 | 2.833 | 0.001 | 0.000 | -4.341 | 0.000 | -9.232 | -12.328 |
SMSTORE6 | 0.000 | 0.000 | 3.904 | -38.307 | 0.000 | 0.000 | 12.580 | 27.807 | 9.586 | 8.397 | 0.000 | 2.833 | 0.001 | 0.000 | -4.316 | 0.000 | -9.201 | -13.283 |
SMSTORE7 | 0.000 | 0.000 | 4.676 | -36.832 | 0.000 | 0.000 | 12.604 | 27.807 | 9.586 | 8.422 | 0.000 | 2.834 | 0.000 | 0.000 | -4.243 | 0.000 | -9.110 | -15.742 |
SMSTORE8 | 0.000 | 0.000 | 8.483 | -37.877 | 0.000 | 0.000 | 12.641 | 27.807 | 9.586 | 8.462 | 0.000 | 2.966 | 0.001 | 0.000 | -3.987 | 0.000 | -12.074 | -16.006 |
Total Facility | 0.000 | 0.000 | 41.563 | -575.778 | 0.000 | 0.000 | 133.587 | 496.921 | 128.154 | 100.456 | 0.000 | 33.228 | 0.009 | 0.000 | -53.043 | 0.000 | -113.347 | -191.740 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 26-AUG-07:02 | 0.00 | 0.00 | 0.00 | -36019.56 | 0.00 | 0.00 | 0.00 | 317.63 | 73.64 | 0.00 | 0.00 | 0.00 | 35767.39 | 0.00 | -55.97 | 0.00 | -83.13 | 0.00 |
SMSTORE1 | 26-AUG-07:02 | 0.00 | 0.00 | 0.00 | -20635.90 | 0.00 | 0.00 | 0.00 | 186.54 | 36.82 | 0.00 | 0.00 | 0.00 | 20488.10 | 0.00 | -31.89 | 0.00 | -43.67 | 0.00 |
SMSTORE2 | 05-JUN-06:02 | 0.00 | 0.00 | 0.00 | -19362.87 | 0.00 | 0.00 | 0.00 | 167.44 | 36.82 | 0.00 | 0.00 | 0.00 | 19289.01 | 0.00 | -121.88 | 0.00 | -8.52 | 0.00 |
SMSTORE3 | 05-JUN-06:02 | 0.00 | 0.00 | 0.00 | -19453.00 | 0.00 | 0.00 | 0.00 | 167.44 | 36.82 | 0.00 | 0.00 | 0.00 | 19380.28 | 0.00 | -122.94 | 0.00 | -8.60 | 0.00 |
SMSTORE4 | 05-JUN-06:02 | 0.00 | 0.00 | 0.00 | -19189.69 | 0.00 | 0.00 | 0.00 | 167.44 | 36.82 | 0.00 | 0.00 | 0.00 | 19114.59 | 0.00 | -120.76 | 0.00 | -8.41 | 0.00 |
LGSTORE2 | 26-AUG-07:02 | 0.00 | 0.00 | 0.00 | -34168.64 | 0.00 | 0.00 | 0.00 | 201.30 | 73.64 | 0.00 | 0.00 | 0.00 | 34022.94 | 0.00 | -53.07 | 0.00 | -76.17 | 0.00 |
SMSTORE5 | 26-AUG-07:02 | 0.00 | 0.00 | 0.00 | -17576.35 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 0.00 | 0.00 | 0.00 | 17500.23 | 0.00 | -24.29 | 0.00 | -39.77 | 0.00 |
SMSTORE6 | 26-AUG-07:02 | 0.00 | 0.00 | 0.00 | -17486.69 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 0.00 | 0.00 | 0.00 | 17409.12 | 0.00 | -23.49 | 0.00 | -39.12 | 0.00 |
SMSTORE7 | 16-SEP-07:02 | 0.00 | 0.00 | 0.00 | -16758.47 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 0.00 | 0.00 | 0.00 | 16696.72 | 0.00 | -36.65 | 0.00 | -41.78 | 0.00 |
SMSTORE8 | 09-SEP-07:02 | 0.00 | 0.00 | 0.00 | -17302.19 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 0.00 | 0.00 | 0.00 | 17218.37 | 0.00 | -28.99 | 0.00 | -27.37 | 0.00 |
Total Facility | 26-AUG-07:02 | 0.00 | 0.00 | 0.00 | -163056.06 | 0.00 | 0.00 | 295.52 | 6142.12 | 1450.75 | 0.00 | 0.00 | 0.00 | 155908.44 | 0.00 | -267.32 | 0.00 | -473.45 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 12-FEB-08:61 | 0.00 | 0.00 | 61272.55 | 0.00 | 0.00 | 0.00 | 282.54 | 317.63 | 74.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -547.36 | 0.00 | -1766.47 | -59633.52 |
SMSTORE1 | 12-FEB-08:61 | 0.00 | 0.00 | 32056.17 | 0.00 | 0.00 | 0.00 | 133.19 | 186.54 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -316.85 | 0.00 | -890.03 | -31206.32 |
SMSTORE2 | 12-FEB-08:61 | 0.00 | 0.00 | 31650.79 | 0.00 | 0.00 | 0.00 | 0.00 | 167.44 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -301.88 | 0.00 | -871.74 | -30681.91 |
SMSTORE3 | 12-FEB-08:61 | 0.00 | 0.00 | 31477.20 | 0.00 | 0.00 | 0.00 | 0.00 | 167.44 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -294.93 | 0.00 | -863.50 | -30523.52 |
SMSTORE4 | 12-FEB-08:61 | 0.00 | 0.00 | 31470.98 | 0.00 | 0.00 | 0.00 | 0.00 | 167.44 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -288.67 | 0.00 | -855.72 | -30531.34 |
LGSTORE2 | 13-FEB-08:61 | 0.00 | 0.00 | 57668.08 | 0.00 | 0.00 | 0.00 | 0.00 | 201.30 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -253.93 | 0.00 | -1249.86 | -56439.24 |
SMSTORE5 | 12-FEB-09:12 | 0.00 | 0.00 | 29271.45 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 531.09 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -855.99 | -29086.72 |
SMSTORE6 | 12-FEB-09:12 | 0.00 | 0.00 | 29180.47 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 532.57 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -854.43 | -28998.79 |
SMSTORE7 | 12-FEB-09:12 | 0.00 | 0.00 | 29154.84 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 538.56 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -848.67 | -28984.91 |
SMSTORE8 | 12-FEB-09:12 | 0.00 | 0.00 | 32667.91 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 558.27 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1044.04 | -32322.32 |
Total Facility | 13-FEB-08:61 | 0.00 | 0.00 | 284183.27 | 0.00 | 0.00 | 0.00 | 755.56 | 6142.12 | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1783.98 | 0.00 | -8884.58 | -281864.63 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.1800 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.1800 | 0.1888 | 1.0000 | Not calculated | 0.4115 | 0.1888 | ||
PSZ-AC_2:2 | 1.1547 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1547 | 0.1782 | 1.0000 | Not calculated | 0.2057 | 0.1782 | ||
PSZ-AC_3:3 | 1.1351 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1503 | 0.1789 | 1.0000 | Not calculated | 0.2057 | 0.1789 | ||
PSZ-AC_4:4 | 1.1269 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1530 | 0.1784 | 1.0000 | Not calculated | 0.2057 | 0.1784 | ||
PSZ-AC_5:5 | 1.1266 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1432 | 0.1800 | 1.0000 | Not calculated | 0.2057 | 0.1800 | ||
PSZ-AC_6:6 | 2.0106 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0106 | 0.2047 | 1.0000 | Not calculated | 0.4115 | 0.2047 | ||
PSZ-AC_7:7 | 1.0210 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0434 | 0.1972 | 1.0000 | Not calculated | 0.2057 | 0.1972 | ||
PSZ-AC_8:8 | 1.0160 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0379 | 0.1982 | 1.0000 | Not calculated | 0.2057 | 0.1982 | ||
PSZ-AC_9:9 | 1.0119 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0383 | 0.1981 | 1.0000 | Not calculated | 0.2057 | 0.1981 | ||
PSZ-AC_10:10 | 1.1694 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1694 | 0.1759 | 1.0000 | Not calculated | 0.2057 | 0.1759 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.1800 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.1800 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1888 | ||
PSZ-AC_2:2 | 1.1547 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1547 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1782 | ||
PSZ-AC_3:3 | 1.1351 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1351 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1813 | ||
PSZ-AC_4:4 | 1.1269 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1269 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1826 | ||
PSZ-AC_5:5 | 1.1266 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1266 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1826 | ||
PSZ-AC_6:6 | 2.0106 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0106 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2047 | ||
PSZ-AC_7:7 | 1.0210 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0210 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2015 | ||
PSZ-AC_8:8 | 1.0160 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0160 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2025 | ||
PSZ-AC_9:9 | 1.0119 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0119 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2033 | ||
PSZ-AC_10:10 | 1.1694 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1694 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1759 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1800 | 2.1800 | 2.1800 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1547 | 1.1547 | 1.1547 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1351 | 1.1351 | 1.1351 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1269 | 1.1269 | 1.1269 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1266 | 1.1266 | 1.1266 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0106 | 2.0106 | 2.0106 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0210 | 1.0210 | 1.0210 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0160 | 1.0160 | 1.0160 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0119 | 1.0119 | 1.0119 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1694 | 1.1694 | 1.1694 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.1800 | 2.1800 | 2.1800 | 2.1800 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1547 | 1.1547 | 1.1547 | 1.1547 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1351 | 1.1503 | 1.1351 | 1.1351 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1269 | 1.1530 | 1.1269 | 1.1269 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1266 | 1.1432 | 1.1266 | 1.1266 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.0106 | 2.0106 | 2.0106 | 2.0106 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0210 | 1.0434 | 1.0210 | 1.0210 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0160 | 1.0379 | 1.0160 | 1.0160 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0119 | 1.0383 | 1.0119 | 1.0119 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.1694 | 1.1694 | 1.1694 | 1.1694 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1800 | 2.1800 | 2.1800 | No | 0.4115 | 0.3442 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1547 | 1.1547 | 1.1547 | No | 0.2057 | 0.3707 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1351 | 1.1351 | 1.1351 | No | 0.2057 | 0.3652 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1269 | 1.1269 | 1.1269 | No | 0.2057 | 0.3617 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1266 | 1.1266 | 1.1266 | No | 0.2057 | 0.3564 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0106 | 2.0106 | 2.0106 | No | 0.4115 | 0.3682 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0210 | 1.0210 | 1.0210 | No | 0.2057 | 0.3460 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0160 | 1.0160 | 1.0160 | No | 0.2057 | 0.3463 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0119 | 1.0119 | 1.0119 | No | 0.2057 | 0.3398 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1694 | 1.1694 | 1.1694 | No | 0.2057 | 0.2754 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.1800 | 2.1800 | 2.1800 | 2.1800 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1547 | 1.1547 | 1.1547 | 1.1547 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1351 | 1.1351 | 1.1351 | 1.1351 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1269 | 1.1269 | 1.1269 | 1.1269 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1266 | 1.1266 | 1.1266 | 1.1266 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.0106 | 2.0106 | 2.0106 | 2.0106 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0210 | 1.0210 | 1.0210 | 1.0210 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0160 | 1.0160 | 1.0160 | 1.0160 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0119 | 1.0119 | 1.0119 | 1.0119 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.1694 | 1.1694 | 1.1694 | 1.1694 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.33 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 165.13 | 200306.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 200.54 | 53565.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 496.92 | 30804.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 100.65 | 7723.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 103.60 | 9506.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 61.96 | 11827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 1091.83 |
Natural Gas | 0.00 | 165.13 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1256.95 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 237.73 |
Space Heating | 0.00 |
Space Cooling | 95.94 |
Fans (All) | 49.56 |
Service Water Heating | 29.64 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 522.33 |
Subtotal | 522.33 |
Natural Gas [MJ/m2] | |
Space Heating | 79.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 79.00 |
Subtotal | 79.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 39.53 |
Space Heating | 13.14 |
Space Cooling | 15.95 |
Fans (All) | 8.24 |
Service Water Heating | 4.93 |
Receptacle Equipment | 10.20 |
Miscellaneous | 8.01 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8397.33 | 362.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8346.17 | 413.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8451.67 | 308.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8614.33 | 145.67 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8631.00 | 129.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8636.17 | 123.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8643.33 | 116.67 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8612.50 | 147.50 | 0.00 | 0.00 | 0.00 |
Min | 8346.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 413.83 | 0.00 | 0.00 | 0.00 |
Average | 8585.25 | 174.75 | 0.00 | 0.00 | 0.00 |
Sum | 85852.50 | 1747.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25427.67 | 47.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25427.67 | 47.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25429.83 | 45.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93096.00 | 115.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45855.50 | 56.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45856.00 | 56.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45857.00 | 55.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45849.50 | 62.50 | 0.00 | 0.00 | 0.00 |
Min | 25427.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93096.00 | 115.00 | 0.00 | 0.00 | 0.00 |
Average | 48561.72 | 48.48 | 0.00 | 0.00 | 0.00 |
Sum | 485617.17 | 484.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 7766.00 | 994.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8533.83 | 226.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 7073.67 | 1686.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 7078.83 | 1681.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 7093.33 | 1666.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 7101.33 | 1658.67 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 7127.17 | 1632.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 7131.33 | 1628.67 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 7160.50 | 1599.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 7106.33 | 1653.67 | 0.00 | 0.00 | 0.00 |
Min | 7073.67 | 226.17 | 0.00 | 0.00 | 0.00 |
Max | 8533.83 | 1686.33 | 0.00 | 0.00 | 0.00 |
Average | 7317.23 | 1442.77 | 0.00 | 0.00 | 0.00 |
Sum | 73172.33 | 14427.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 86619.50 | 2421.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43079.33 | 697.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 24693.67 | 781.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 24683.67 | 791.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 24601.17 | 873.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 87669.83 | 5541.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 43100.83 | 2811.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 43015.33 | 2896.67 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 42903.17 | 3008.83 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 42960.50 | 2951.50 | 0.00 | 0.00 | 0.00 |
Min | 24601.17 | 697.67 | 0.00 | 0.00 | 0.00 |
Max | 87669.83 | 5541.17 | 0.00 | 0.00 | 0.00 |
Average | 46332.70 | 2277.50 | 0.00 | 0.00 | 0.00 |
Sum | 463327.00 | 22775.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:38
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243560E+10 | 10510.09 | 27-JAN-00:02 | -3.9 | -6.1 | 0.109784E+10 | 1540.28 | 20-JAN-13:00 | -3.9 | -6.1 |
February | 0.354977E+10 | 11062.19 | 03-FEB-00:02 | -5.1 | -7.2 | 0.108001E+10 | 1685.85 | 26-FEB-17:19 | 23.53 | 11.91 |
March | 0.691568E+10 | 11683.19 | 30-MAR-16:10 | 27.62 | 17.53 | 0.130936E+10 | 1685.97 | 11-MAR-13:00 | 27.62 | 17.53 |
April | 0.885930E+10 | 11617.29 | 17-APR-16:10 | 28.80 | 16.45 | 0.133871E+10 | 1685.96 | 14-APR-12:20 | 28.80 | 16.45 |
May | 0.124356E+11 | 18059.40 | 31-MAY-07:03 | 19.50 | 18.65 | 0.140059E+10 | 1686.02 | 21-MAY-17:10 | 19.50 | 18.65 |
June | 0.163288E+11 | 33624.02 | 15-JUN-07:02 | 22.20 | 18.87 | 0.135460E+10 | 1686.06 | 30-JUN-12:00 | 31.10 | 23.42 |
July | 0.184075E+11 | 34155.26 | 17-JUL-07:01 | 22.07 | 19.58 | 0.141285E+10 | 1686.06 | 04-JUL-16:10 | 22.07 | 19.58 |
August | 0.193955E+11 | 36027.15 | 26-AUG-07:02 | 22.30 | 17.92 | 0.139422E+10 | 1686.05 | 27-AUG-12:00 | 31.70 | 22.73 |
September | 0.149642E+11 | 35392.20 | 16-SEP-07:02 | 22.20 | 20.70 | 0.136515E+10 | 1686.07 | 09-SEP-12:30 | 22.20 | 20.70 |
October | 0.109451E+11 | 29264.92 | 19-OCT-07:02 | 19.40 | 19.12 | 0.137761E+10 | 1686.04 | 09-OCT-17:49 | 19.40 | 19.12 |
November | 0.743860E+10 | 10616.86 | 05-NOV-16:07 | 24.03 | 17.90 | 0.127025E+10 | 1685.89 | 19-NOV-13:39 | 20.77 | 17.82 |
December | 0.491632E+10 | 7920.15 | 01-DEC-00:03 | 1.80 | 1.51 | 0.113786E+10 | 1685.81 | 10-DEC-18:00 | 15.00 | 7.40 |
Annual Sum or Average | 0.126592E+12 | 0.155391E+11 | ||||||||
Minimum of Months | 0.243560E+10 | 7920.15 | -5.1 | -7.2 | 0.108001E+10 | 1540.28 | -3.9 | -6.1 | ||
Maximum of Months | 0.193955E+11 | 36027.15 | 28.80 | 20.70 | 0.141285E+10 | 1686.07 | 31.70 | 23.42 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138316E+10 | 3743.92 | 26-JAN-16:03 | 2.20 | -2.7 | 0.576793E+09 | 842.90 | 29-JAN-18:00 | 13.30 | 5.45 |
February | 0.212933E+10 | 17947.30 | 28-FEB-22:15 | 18.37 | 10.65 | 0.559993E+09 | 842.90 | 19-FEB-17:40 | 18.37 | 10.65 |
March | 0.412724E+10 | 19874.84 | 12-MAR-17:55 | 16.10 | 7.37 | 0.673505E+09 | 842.95 | 11-MAR-13:00 | 16.10 | 7.37 |
April | 0.541826E+10 | 18296.88 | 09-APR-18:35 | 18.50 | 10.55 | 0.673868E+09 | 842.95 | 14-APR-12:09 | 26.20 | 16.07 |
May | 0.728686E+10 | 16842.01 | 13-MAY-20:46 | 17.95 | 11.51 | 0.699577E+09 | 842.99 | 05-MAY-12:39 | 17.95 | 11.51 |
June | 0.899519E+10 | 19579.16 | 15-JUN-07:02 | 22.20 | 18.87 | 0.676482E+09 | 843.01 | 30-JUN-12:30 | 30.85 | 23.58 |
July | 0.992995E+10 | 20032.60 | 17-JUL-07:01 | 22.07 | 19.58 | 0.706375E+09 | 843.02 | 16-JUL-16:10 | 22.07 | 19.58 |
August | 0.103175E+11 | 20638.04 | 26-AUG-07:02 | 22.30 | 17.92 | 0.697107E+09 | 843.02 | 27-AUG-12:00 | 31.70 | 22.73 |
September | 0.824009E+10 | 20273.08 | 16-SEP-07:02 | 22.20 | 20.70 | 0.682058E+09 | 843.02 | 08-SEP-12:39 | 22.20 | 20.70 |
October | 0.616929E+10 | 18265.76 | 11-OCT-20:01 | 17.93 | 10.36 | 0.696396E+09 | 843.16 | 08-OCT-17:30 | 17.93 | 10.36 |
November | 0.422679E+10 | 12817.76 | 03-NOV-20:30 | 18.60 | 16.28 | 0.652505E+09 | 842.91 | 19-NOV-13:20 | 19.83 | 17.29 |
December | 0.249112E+10 | 14336.85 | 12-DEC-21:55 | 18.30 | 14.62 | 0.612974E+09 | 842.90 | 10-DEC-18:00 | 18.30 | 14.62 |
Annual Sum or Average | 0.707148E+11 | 0.790763E+10 | ||||||||
Minimum of Months | 0.138316E+10 | 3743.92 | 2.20 | -2.7 | 0.559993E+09 | 842.90 | 13.30 | 5.45 | ||
Maximum of Months | 0.103175E+11 | 20638.04 | 22.30 | 20.70 | 0.706375E+09 | 843.16 | 31.70 | 23.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.874103E+09 | 3679.85 | 17-JAN-10:23 | 2.50 | 2.15 | 0.327701E+09 | 702.42 | 31-JAN-17:19 | 19.23 | 13.32 |
February | 0.142242E+10 | 4767.05 | 01-FEB-08:61 | -0.6 | -1.9 | 0.323781E+09 | 842.90 | 25-FEB-13:00 | 20.00 | 9.28 |
March | 0.295725E+10 | 6093.32 | 30-MAR-16:10 | 27.62 | 17.53 | 0.404851E+09 | 842.96 | 11-MAR-13:00 | 27.62 | 17.53 |
April | 0.370025E+10 | 6110.78 | 17-APR-16:10 | 28.80 | 16.45 | 0.404766E+09 | 842.93 | 08-APR-12:09 | 28.80 | 16.45 |
May | 0.514886E+10 | 15843.20 | 19-MAY-06:03 | 16.57 | 15.54 | 0.425606E+09 | 842.98 | 06-MAY-12:30 | 16.57 | 15.54 |
June | 0.668937E+10 | 19368.02 | 05-JUN-06:02 | 19.60 | 16.99 | 0.417301E+09 | 842.97 | 24-JUN-12:09 | 31.28 | 23.73 |
July | 0.733266E+10 | 18720.72 | 03-JUL-06:02 | 18.68 | 16.73 | 0.420592E+09 | 842.95 | 01-JUL-12:09 | 18.68 | 16.73 |
August | 0.787535E+10 | 19030.02 | 26-AUG-06:02 | 21.78 | 17.46 | 0.432216E+09 | 843.01 | 05-AUG-12:00 | 21.78 | 17.46 |
September | 0.595678E+10 | 19323.79 | 25-SEP-06:02 | 19.40 | 16.66 | 0.410838E+09 | 842.99 | 09-SEP-12:09 | 19.40 | 16.66 |
October | 0.433723E+10 | 15680.57 | 11-OCT-06:03 | 17.70 | 16.28 | 0.411214E+09 | 842.94 | 14-OCT-12:39 | 20.73 | 13.29 |
November | 0.301308E+10 | 7177.13 | 04-NOV-06:03 | 16.10 | 15.07 | 0.378395E+09 | 842.90 | 18-NOV-13:00 | 21.10 | 10.33 |
December | 0.193515E+10 | 4086.23 | 07-DEC-08:61 | 1.88 | 1.59 | 0.342182E+09 | 716.48 | 16-DEC-13:00 | 14.40 | 10.24 |
Annual Sum or Average | 0.512425E+11 | 0.469944E+10 | ||||||||
Minimum of Months | 0.874103E+09 | 3679.85 | -0.6 | -1.9 | 0.323781E+09 | 702.42 | 14.40 | 9.28 | ||
Maximum of Months | 0.787535E+10 | 19368.02 | 28.80 | 17.53 | 0.432216E+09 | 843.01 | 31.28 | 23.73 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.745949E+09 | 3504.09 | 13-JAN-17:13 | 3.30 | -0.9 | 0.326808E+09 | 702.42 | 31-JAN-17:19 | 19.23 | 13.32 |
February | 0.130352E+10 | 4706.04 | 01-FEB-08:61 | -0.6 | -1.9 | 0.322349E+09 | 842.90 | 25-FEB-13:00 | 20.00 | 9.28 |
March | 0.282579E+10 | 6020.40 | 30-MAR-16:10 | 27.62 | 17.53 | 0.402944E+09 | 842.96 | 11-MAR-13:00 | 27.62 | 17.53 |
April | 0.362501E+10 | 6088.94 | 17-APR-16:10 | 28.80 | 16.45 | 0.404347E+09 | 842.93 | 08-APR-12:09 | 28.80 | 16.45 |
May | 0.510879E+10 | 15955.20 | 19-MAY-06:03 | 16.57 | 15.54 | 0.425578E+09 | 842.98 | 06-MAY-12:30 | 16.57 | 15.54 |
June | 0.670717E+10 | 19458.18 | 05-JUN-06:02 | 19.60 | 16.99 | 0.417299E+09 | 842.97 | 24-JUN-12:09 | 31.28 | 23.73 |
July | 0.737042E+10 | 18809.80 | 03-JUL-06:02 | 18.68 | 16.73 | 0.420593E+09 | 842.95 | 01-JUL-12:09 | 18.68 | 16.73 |
August | 0.791303E+10 | 19095.86 | 26-AUG-06:02 | 21.78 | 17.46 | 0.432216E+09 | 843.01 | 05-AUG-12:00 | 21.78 | 17.46 |
September | 0.595381E+10 | 19384.64 | 25-SEP-06:02 | 19.40 | 16.66 | 0.410832E+09 | 842.99 | 09-SEP-12:09 | 19.40 | 16.66 |
October | 0.426586E+10 | 15570.97 | 11-OCT-06:03 | 17.70 | 16.28 | 0.410286E+09 | 842.94 | 14-OCT-12:39 | 20.73 | 13.29 |
November | 0.286956E+10 | 6400.67 | 04-NOV-06:03 | 16.10 | 15.07 | 0.376764E+09 | 842.90 | 18-NOV-13:00 | 21.10 | 10.33 |
December | 0.177165E+10 | 4031.60 | 15-DEC-08:62 | 2.88 | 0.94 | 0.339751E+09 | 707.59 | 16-DEC-13:00 | 14.40 | 10.24 |
Annual Sum or Average | 0.504606E+11 | 0.468977E+10 | ||||||||
Minimum of Months | 0.745949E+09 | 3504.09 | -0.6 | -1.9 | 0.322349E+09 | 702.42 | 14.40 | 9.28 | ||
Maximum of Months | 0.791303E+10 | 19458.18 | 28.80 | 17.53 | 0.432216E+09 | 843.01 | 31.28 | 23.73 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.594324E+09 | 4402.04 | 09-JAN-19:42 | -0.4 | -1.6 | 0.325645E+09 | 702.41 | 31-JAN-18:10 | 18.72 | 13.14 |
February | 0.113458E+10 | 4645.82 | 01-FEB-08:61 | -0.6 | -1.9 | 0.319802E+09 | 842.90 | 25-FEB-13:00 | 20.00 | 9.28 |
March | 0.257952E+10 | 5800.99 | 30-MAR-16:10 | 27.62 | 17.53 | 0.399369E+09 | 842.96 | 11-MAR-13:00 | 27.62 | 17.53 |
April | 0.338697E+10 | 5920.72 | 17-APR-16:10 | 28.80 | 16.45 | 0.403066E+09 | 842.93 | 08-APR-12:09 | 28.80 | 16.45 |
May | 0.486368E+10 | 14138.33 | 19-MAY-06:03 | 16.57 | 15.54 | 0.425443E+09 | 842.98 | 06-MAY-12:30 | 16.57 | 15.54 |
June | 0.649710E+10 | 19194.81 | 05-JUN-06:02 | 19.60 | 16.99 | 0.417256E+09 | 842.96 | 03-JUN-12:09 | 19.60 | 16.99 |
July | 0.717514E+10 | 18553.93 | 03-JUL-06:02 | 18.68 | 16.73 | 0.420557E+09 | 842.99 | 01-JUL-12:20 | 18.68 | 16.73 |
August | 0.771539E+10 | 18812.90 | 26-AUG-06:02 | 21.78 | 17.46 | 0.432179E+09 | 843.00 | 05-AUG-12:00 | 21.78 | 17.46 |
September | 0.574852E+10 | 19114.58 | 25-SEP-06:02 | 19.40 | 16.66 | 0.410781E+09 | 842.98 | 09-SEP-12:09 | 19.40 | 16.66 |
October | 0.405443E+10 | 14897.63 | 18-OCT-06:02 | 19.90 | 19.90 | 0.408496E+09 | 842.94 | 14-OCT-12:50 | 19.90 | 19.90 |
November | 0.262094E+10 | 4515.57 | 05-NOV-14:00 | 23.30 | 18.52 | 0.374171E+09 | 842.90 | 18-NOV-13:00 | 21.10 | 10.33 |
December | 0.154827E+10 | 3965.05 | 15-DEC-08:62 | 2.88 | 0.94 | 0.336802E+09 | 702.45 | 12-DEC-18:30 | 2.88 | 0.94 |
Annual Sum or Average | 0.479189E+11 | 0.467356E+10 | ||||||||
Minimum of Months | 0.594324E+09 | 3965.05 | -0.6 | -1.9 | 0.319802E+09 | 702.41 | 2.88 | 0.94 | ||
Maximum of Months | 0.771539E+10 | 19194.81 | 28.80 | 19.90 | 0.432179E+09 | 843.00 | 28.80 | 19.90 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.641981E+09 | 7240.86 | 04-JAN-20:03 | 3.22 | 0.59 | 0.110638E+10 | 1948.65 | 31-JAN-17:40 | 19.07 | 13.27 |
February | 0.154158E+10 | 6346.86 | 28-FEB-15:30 | 24.15 | 13.12 | 0.108054E+10 | 2247.80 | 25-FEB-15:00 | 24.15 | 13.12 |
March | 0.388675E+10 | 9832.06 | 30-MAR-15:00 | 27.80 | 17.08 | 0.134517E+10 | 2247.80 | 04-MAR-15:09 | 27.80 | 17.08 |
April | 0.525254E+10 | 10346.81 | 17-APR-15:00 | 28.90 | 16.41 | 0.137495E+10 | 2247.84 | 15-APR-14:00 | 28.90 | 16.41 |
May | 0.777955E+10 | 20861.93 | 30-MAY-07:03 | 22.07 | 19.14 | 0.145602E+10 | 2248.00 | 06-MAY-14:09 | 22.07 | 19.14 |
June | 0.108665E+11 | 32433.29 | 05-JUN-07:03 | 21.05 | 17.87 | 0.143019E+10 | 2248.04 | 24-JUN-14:20 | 32.40 | 22.04 |
July | 0.120442E+11 | 32401.28 | 25-JUL-07:02 | 21.20 | 18.27 | 0.143899E+10 | 2247.92 | 01-JUL-14:09 | 21.20 | 18.27 |
August | 0.130328E+11 | 34175.17 | 26-AUG-07:02 | 22.30 | 17.92 | 0.148069E+10 | 2247.93 | 26-AUG-14:09 | 32.52 | 20.65 |
September | 0.944110E+10 | 32904.12 | 16-SEP-07:02 | 22.20 | 20.70 | 0.140976E+10 | 2248.01 | 09-SEP-14:50 | 22.20 | 20.70 |
October | 0.641306E+10 | 27062.84 | 19-OCT-07:02 | 19.40 | 19.12 | 0.138401E+10 | 2247.91 | 21-OCT-14:20 | 21.47 | 13.33 |
November | 0.382178E+10 | 8126.38 | 05-NOV-15:00 | 23.90 | 18.46 | 0.126025E+10 | 2247.80 | 18-NOV-15:00 | 21.10 | 9.81 |
December | 0.211455E+10 | 6613.86 | 14-DEC-09:03 | 6.20 | 4.89 | 0.114111E+10 | 1994.97 | 12-DEC-17:40 | 6.20 | 4.89 |
Annual Sum or Average | 0.768364E+11 | 0.159081E+11 | ||||||||
Minimum of Months | 0.641981E+09 | 6346.86 | 3.22 | 0.59 | 0.108054E+10 | 1948.65 | 6.20 | 4.89 | ||
Maximum of Months | 0.130328E+11 | 34175.17 | 28.90 | 20.70 | 0.148069E+10 | 2248.04 | 32.52 | 22.04 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.289643E+09 | 3583.96 | 04-JAN-20:03 | 3.22 | 0.59 | 0.552595E+09 | 967.82 | 31-JAN-15:39 | 20.37 | 13.40 |
February | 0.728332E+09 | 4456.14 | 02-FEB-10:32 | -0.4 | -2.3 | 0.539011E+09 | 1123.87 | 25-FEB-15:00 | 20.60 | 9.33 |
March | 0.188116E+10 | 5069.00 | 30-MAR-15:00 | 27.80 | 17.08 | 0.670280E+09 | 1123.87 | 04-MAR-15:09 | 27.80 | 17.08 |
April | 0.262534E+10 | 5381.47 | 17-APR-15:00 | 28.90 | 16.41 | 0.686558E+09 | 1123.89 | 15-APR-14:00 | 28.90 | 16.41 |
May | 0.396892E+10 | 10053.57 | 30-MAY-07:03 | 22.07 | 19.14 | 0.727925E+09 | 1123.97 | 06-MAY-14:09 | 22.07 | 19.14 |
June | 0.560546E+10 | 16289.35 | 15-JUN-07:02 | 22.20 | 18.87 | 0.715059E+09 | 1123.99 | 24-JUN-14:20 | 32.40 | 22.04 |
July | 0.622817E+10 | 16672.85 | 25-JUL-07:02 | 21.20 | 18.27 | 0.719443E+09 | 1123.93 | 01-JUL-14:09 | 21.20 | 18.27 |
August | 0.673921E+10 | 17579.79 | 26-AUG-07:02 | 22.30 | 17.92 | 0.740305E+09 | 1123.94 | 26-AUG-14:09 | 32.52 | 20.65 |
September | 0.485776E+10 | 16922.55 | 16-SEP-07:02 | 22.20 | 20.70 | 0.704851E+09 | 1123.97 | 09-SEP-14:50 | 22.20 | 20.70 |
October | 0.323000E+10 | 13897.70 | 19-OCT-07:02 | 19.40 | 19.12 | 0.691327E+09 | 1123.92 | 21-OCT-14:20 | 21.47 | 13.33 |
November | 0.185463E+10 | 4191.77 | 05-NOV-15:00 | 23.90 | 18.46 | 0.629003E+09 | 1123.87 | 18-NOV-15:39 | 21.10 | 9.92 |
December | 0.996594E+09 | 3251.96 | 14-DEC-09:03 | 6.20 | 4.89 | 0.569817E+09 | 997.45 | 12-DEC-17:40 | 6.20 | 4.89 |
Annual Sum or Average | 0.390052E+11 | 0.794618E+10 | ||||||||
Minimum of Months | 0.289643E+09 | 3251.96 | -0.4 | -2.3 | 0.539011E+09 | 967.82 | 6.20 | 4.89 | ||
Maximum of Months | 0.673921E+10 | 17579.79 | 28.90 | 20.70 | 0.740305E+09 | 1123.99 | 32.52 | 22.04 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267715E+09 | 4600.11 | 26-JAN-19:42 | -1.0 | -4.5 | 0.552083E+09 | 961.39 | 31-JAN-15:39 | 20.37 | 13.40 |
February | 0.696522E+09 | 4939.78 | 03-FEB-11:23 | -2.5 | -5.7 | 0.537782E+09 | 1123.87 | 25-FEB-15:00 | 20.60 | 9.33 |
March | 0.180604E+10 | 4977.71 | 30-MAR-15:00 | 27.80 | 17.08 | 0.667759E+09 | 1123.87 | 04-MAR-15:09 | 27.80 | 17.08 |
April | 0.254371E+10 | 5303.56 | 17-APR-15:00 | 28.90 | 16.41 | 0.685281E+09 | 1123.89 | 15-APR-14:00 | 28.90 | 16.41 |
May | 0.388659E+10 | 9353.35 | 30-MAY-07:03 | 22.07 | 19.14 | 0.727807E+09 | 1123.97 | 06-MAY-14:09 | 22.07 | 19.14 |
June | 0.554386E+10 | 16199.48 | 15-JUN-07:02 | 22.20 | 18.87 | 0.715050E+09 | 1123.99 | 24-JUN-14:20 | 32.40 | 22.04 |
July | 0.617070E+10 | 16586.06 | 25-JUL-07:02 | 21.20 | 18.27 | 0.719434E+09 | 1123.93 | 01-JUL-14:09 | 21.20 | 18.27 |
August | 0.668193E+10 | 17490.11 | 26-AUG-07:02 | 22.30 | 17.92 | 0.740300E+09 | 1123.93 | 26-AUG-14:09 | 32.52 | 20.65 |
September | 0.480290E+10 | 16831.58 | 16-SEP-07:02 | 22.20 | 20.70 | 0.704833E+09 | 1123.97 | 09-SEP-14:50 | 22.20 | 20.70 |
October | 0.316666E+10 | 13802.59 | 19-OCT-07:02 | 19.40 | 19.12 | 0.690262E+09 | 1123.92 | 21-OCT-14:20 | 21.47 | 13.33 |
November | 0.179253E+10 | 4120.57 | 05-NOV-15:00 | 23.90 | 18.46 | 0.627401E+09 | 1123.87 | 18-NOV-15:50 | 21.10 | 9.87 |
December | 0.948591E+09 | 3234.71 | 14-DEC-09:03 | 6.20 | 4.89 | 0.568898E+09 | 997.46 | 12-DEC-17:30 | 6.20 | 4.89 |
Annual Sum or Average | 0.383077E+11 | 0.793689E+10 | ||||||||
Minimum of Months | 0.267715E+09 | 3234.71 | -2.5 | -5.7 | 0.537782E+09 | 961.39 | 6.20 | 4.89 | ||
Maximum of Months | 0.668193E+10 | 17490.11 | 28.90 | 20.70 | 0.740300E+09 | 1123.99 | 32.52 | 22.04 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.209911E+09 | 4813.79 | 26-JAN-11:23 | -1.9 | -5.3 | 0.550671E+09 | 945.82 | 31-JAN-15:39 | 20.37 | 13.40 |
February | 0.593685E+09 | 2882.04 | 28-FEB-15:30 | 24.15 | 13.12 | 0.534750E+09 | 1123.87 | 25-FEB-15:00 | 24.15 | 13.12 |
March | 0.161234E+10 | 4772.85 | 30-MAR-15:00 | 27.80 | 17.08 | 0.661525E+09 | 1123.87 | 04-MAR-15:20 | 27.80 | 17.08 |
April | 0.233077E+10 | 5114.07 | 17-APR-15:00 | 28.90 | 16.41 | 0.681582E+09 | 1123.89 | 15-APR-14:00 | 28.90 | 16.41 |
May | 0.368293E+10 | 6783.25 | 30-MAY-07:03 | 22.07 | 19.14 | 0.727338E+09 | 1123.97 | 06-MAY-14:09 | 22.07 | 19.14 |
June | 0.545543E+10 | 16125.02 | 15-JUN-07:02 | 22.20 | 18.87 | 0.715032E+09 | 1123.98 | 24-JUN-14:20 | 32.40 | 22.04 |
July | 0.612144E+10 | 16523.03 | 25-JUL-07:02 | 21.20 | 18.27 | 0.719422E+09 | 1123.93 | 01-JUL-14:09 | 21.20 | 18.27 |
August | 0.665230E+10 | 16749.60 | 26-AUG-07:02 | 22.30 | 17.92 | 0.740296E+09 | 1123.93 | 26-AUG-14:09 | 32.52 | 20.65 |
September | 0.472425E+10 | 16762.42 | 16-SEP-07:02 | 22.20 | 20.70 | 0.704774E+09 | 1123.97 | 09-SEP-14:50 | 22.20 | 20.70 |
October | 0.302347E+10 | 13695.68 | 19-OCT-07:02 | 19.40 | 19.12 | 0.687450E+09 | 1123.92 | 21-OCT-14:30 | 21.65 | 13.37 |
November | 0.162802E+10 | 3958.38 | 05-NOV-15:00 | 23.90 | 18.46 | 0.623472E+09 | 1123.87 | 18-NOV-15:50 | 21.10 | 9.87 |
December | 0.798803E+09 | 3171.48 | 14-DEC-09:03 | 6.20 | 4.89 | 0.566651E+09 | 997.45 | 12-DEC-17:30 | 6.20 | 4.89 |
Annual Sum or Average | 0.368334E+11 | 0.791296E+10 | ||||||||
Minimum of Months | 0.209911E+09 | 2882.04 | -1.9 | -5.3 | 0.534750E+09 | 945.82 | 6.20 | 4.89 | ||
Maximum of Months | 0.665230E+10 | 16762.42 | 28.90 | 20.70 | 0.740296E+09 | 1123.98 | 32.52 | 22.04 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105352E+09 | 2016.80 | 21-JAN-15:35 | 9.60 | 4.99 | 0.548748E+09 | 926.30 | 31-JAN-15:39 | 20.37 | 13.40 |
February | 0.431256E+09 | 2716.25 | 28-FEB-15:30 | 24.15 | 13.12 | 0.530388E+09 | 1123.87 | 25-FEB-15:30 | 24.15 | 13.12 |
March | 0.120989E+10 | 4799.53 | 30-MAR-14:50 | 27.80 | 17.21 | 0.652590E+09 | 1123.87 | 04-MAR-15:39 | 27.80 | 17.21 |
April | 0.206250E+10 | 5151.47 | 17-APR-14:30 | 28.90 | 16.52 | 0.674489E+09 | 1123.88 | 15-APR-14:00 | 28.90 | 16.52 |
May | 0.368283E+10 | 6440.60 | 30-MAY-14:30 | 30.60 | 21.24 | 0.726165E+09 | 1123.98 | 06-MAY-14:09 | 30.60 | 21.24 |
June | 0.599658E+10 | 16077.10 | 15-JUN-07:02 | 22.20 | 18.87 | 0.715062E+09 | 1123.97 | 24-JUN-14:09 | 32.30 | 22.07 |
July | 0.688807E+10 | 16636.59 | 17-JUL-07:01 | 22.07 | 19.58 | 0.719514E+09 | 1123.93 | 01-JUL-14:09 | 22.07 | 19.58 |
August | 0.752974E+10 | 15827.62 | 10-AUG-07:02 | 25.37 | 23.14 | 0.740395E+09 | 1124.01 | 12-AUG-14:30 | 30.85 | 23.40 |
September | 0.515994E+10 | 17307.47 | 09-SEP-07:02 | 22.67 | 20.24 | 0.704598E+09 | 1123.98 | 09-SEP-14:00 | 23.90 | 21.59 |
October | 0.298554E+10 | 10494.98 | 19-OCT-07:02 | 19.40 | 19.12 | 0.682631E+09 | 1123.91 | 14-OCT-14:20 | 19.40 | 19.12 |
November | 0.134296E+10 | 3923.25 | 05-NOV-15:00 | 23.90 | 18.46 | 0.617895E+09 | 1123.87 | 18-NOV-15:00 | 21.10 | 9.81 |
December | 0.483932E+09 | 3099.93 | 01-DEC-19:53 | 5.00 | 0.51 | 0.563534E+09 | 997.45 | 12-DEC-17:10 | 21.42 | 16.03 |
Annual Sum or Average | 0.378786E+11 | 0.787601E+10 | ||||||||
Minimum of Months | 0.105352E+09 | 2016.80 | 5.00 | 0.51 | 0.530388E+09 | 926.30 | 19.40 | 9.81 | ||
Maximum of Months | 0.752974E+10 | 17307.47 | 30.60 | 23.14 | 0.740395E+09 | 1124.01 | 32.30 | 23.40 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253278E+10 | 61265.23 | 27-JAN-08:61 | -6.4 |
February | 0.154231E+10 | 61272.51 | 12-FEB-08:61 | -11.9 |
March | 0.175535E+09 | 61192.83 | 18-MAR-07:01 | 2.30 |
April | 0.101264E+09 | 61205.80 | 06-APR-07:01 | 2.25 |
May | 34032186.69 | 1449.84 | 31-MAY-07:05 | 19.50 |
June | 27755034.11 | 1795.06 | 16-JUN-07:05 | 21.88 |
July | 27042934.13 | 1809.79 | 25-JUL-07:04 | 21.20 |
August | 26712504.55 | 1871.70 | 26-AUG-07:04 | 22.30 |
September | 28036050.68 | 1892.53 | 16-SEP-07:04 | 22.20 |
October | 67203153.56 | 12088.63 | 26-OCT-07:01 | 2.57 |
November | 0.157344E+09 | 61207.30 | 22-NOV-08:61 | -2.2 |
December | 0.680624E+09 | 61250.52 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.540064E+10 | |||
Minimum of Months | 26712504.55 | 1449.84 | -11.9 | |
Maximum of Months | 0.253278E+10 | 61272.51 | 22.30 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.645883E+09 | 32048.36 | 27-JAN-08:61 | -6.4 |
February | 0.348460E+09 | 32056.15 | 12-FEB-08:61 | -11.9 |
March | 45492428.39 | 7564.94 | 23-MAR-07:01 | 6.20 |
April | 26451275.14 | 736.26 | 06-APR-08:10 | 5.37 |
May | 16710660.10 | 972.22 | 31-MAY-07:05 | 19.50 |
June | 15140899.27 | 1107.96 | 16-JUN-07:05 | 21.88 |
July | 14164616.74 | 1060.86 | 30-JUL-07:05 | 21.78 |
August | 13254237.36 | 1090.41 | 26-AUG-07:04 | 22.30 |
September | 15763235.66 | 1108.03 | 16-SEP-07:04 | 22.20 |
October | 24771087.63 | 1080.93 | 18-OCT-07:05 | 19.50 |
November | 46329879.76 | 31086.70 | 22-NOV-08:61 | -2.2 |
December | 0.108260E+09 | 32035.74 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.132068E+10 | |||
Minimum of Months | 13254237.36 | 736.26 | -11.9 | |
Maximum of Months | 0.645883E+09 | 32056.15 | 22.30 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.930146E+09 | 31624.04 | 08-JAN-08:61 | -4.4 |
February | 0.526493E+09 | 31650.79 | 12-FEB-08:61 | -11.9 |
March | 48732166.94 | 5555.08 | 19-MAR-07:03 | 1.57 |
April | 30235138.16 | 2360.14 | 06-APR-07:05 | 2.25 |
May | 35798006.25 | 1653.06 | 29-MAY-16:02 | 30.00 |
June | 86342464.82 | 2410.23 | 25-JUN-16:02 | 33.22 |
July | 0.107928E+09 | 2725.34 | 08-JUL-17:02 | 34.40 |
August | 93825426.66 | 2291.03 | 06-AUG-16:02 | 32.70 |
September | 41626460.47 | 1644.74 | 03-SEP-16:02 | 30.00 |
October | 25089585.66 | 1033.80 | 09-OCT-16:03 | 27.62 |
November | 53185345.64 | 20598.52 | 22-NOV-07:02 | -3.2 |
December | 0.219472E+09 | 31353.69 | 03-DEC-08:61 | -3.4 |
Annual Sum or Average | 0.219887E+10 | |||
Minimum of Months | 25089585.66 | 1033.80 | -11.9 | |
Maximum of Months | 0.930146E+09 | 31650.79 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106390E+10 | 31450.39 | 08-JAN-08:61 | -4.4 |
February | 0.598189E+09 | 31477.20 | 12-FEB-08:61 | -11.9 |
March | 55051302.91 | 9115.78 | 19-MAR-07:03 | 1.57 |
April | 32271335.68 | 1841.30 | 07-APR-07:04 | 3.53 |
May | 36483653.44 | 1656.00 | 29-MAY-16:02 | 30.00 |
June | 86457828.70 | 2410.26 | 25-JUN-16:02 | 33.22 |
July | 0.107608E+09 | 2725.25 | 08-JUL-17:02 | 34.40 |
August | 93369486.69 | 2291.32 | 06-AUG-16:02 | 32.70 |
September | 41666349.44 | 1646.74 | 03-SEP-16:02 | 30.00 |
October | 27570850.81 | 1672.23 | 26-OCT-07:07 | 2.57 |
November | 61740953.24 | 23344.43 | 22-NOV-07:02 | -3.2 |
December | 0.282282E+09 | 31180.97 | 03-DEC-08:61 | -3.4 |
Annual Sum or Average | 0.248659E+10 | |||
Minimum of Months | 27570850.81 | 1646.74 | -11.9 | |
Maximum of Months | 0.106390E+10 | 31477.20 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129253E+10 | 31444.38 | 08-JAN-08:61 | -4.4 |
February | 0.727977E+09 | 31470.98 | 12-FEB-08:61 | -11.9 |
March | 69837481.89 | 13081.70 | 19-MAR-07:03 | 1.57 |
April | 38114349.40 | 2469.64 | 06-APR-07:03 | 2.25 |
May | 39748890.59 | 1662.26 | 29-MAY-16:02 | 30.00 |
June | 87114339.19 | 2414.47 | 25-JUN-16:02 | 33.22 |
July | 0.109069E+09 | 2729.40 | 08-JUL-17:02 | 34.40 |
August | 95608243.54 | 2295.24 | 06-AUG-16:02 | 32.70 |
September | 42403366.60 | 1652.29 | 03-SEP-16:02 | 30.00 |
October | 32621786.47 | 1995.55 | 26-OCT-07:06 | 2.57 |
November | 72345435.74 | 26487.37 | 22-NOV-07:02 | -3.2 |
December | 0.376082E+09 | 31177.34 | 03-DEC-08:61 | -3.4 |
Annual Sum or Average | 0.298345E+10 | |||
Minimum of Months | 32621786.47 | 1652.29 | -11.9 | |
Maximum of Months | 0.129253E+10 | 31470.98 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.289140E+10 | 57654.12 | 28-JAN-08:61 | -4.0 |
February | 0.161878E+10 | 57668.08 | 13-FEB-08:61 | -5.2 |
March | 0.200044E+09 | 57613.04 | 20-MAR-07:01 | 5.10 |
April | 96537154.67 | 51847.73 | 07-APR-07:01 | 3.53 |
May | 60196700.44 | 3331.08 | 29-MAY-16:02 | 30.00 |
June | 93285402.93 | 4834.24 | 25-JUN-16:02 | 33.22 |
July | 0.112615E+09 | 5457.16 | 08-JUL-17:02 | 34.40 |
August | 84958806.85 | 4594.12 | 06-AUG-16:02 | 32.70 |
September | 58403064.90 | 3313.84 | 03-SEP-16:02 | 30.00 |
October | 77384985.76 | 16355.71 | 26-OCT-07:01 | 2.57 |
November | 0.161924E+09 | 57610.28 | 22-NOV-08:61 | -2.2 |
December | 0.929743E+09 | 57646.53 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.638527E+10 | |||
Minimum of Months | 58403064.90 | 3313.84 | -5.2 | |
Maximum of Months | 0.289140E+10 | 57668.08 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168963E+10 | 29206.91 | 27-JAN-08:61 | -6.4 |
February | 0.953041E+09 | 29271.46 | 12-FEB-09:12 | -9.8 |
March | 0.121276E+09 | 29184.11 | 20-MAR-07:01 | 5.10 |
April | 56242813.45 | 28177.98 | 07-APR-07:01 | 3.53 |
May | 32821862.16 | 1678.73 | 29-MAY-16:02 | 30.00 |
June | 48728592.78 | 2428.37 | 25-JUN-16:02 | 33.22 |
July | 57292380.58 | 2744.78 | 08-JUL-17:02 | 34.40 |
August | 43161209.11 | 2308.53 | 06-AUG-16:02 | 32.70 |
September | 30654584.19 | 1669.03 | 03-SEP-16:02 | 30.00 |
October | 43387505.67 | 9661.68 | 26-OCT-07:01 | 2.57 |
November | 92197443.73 | 29183.85 | 22-NOV-08:61 | -2.2 |
December | 0.556487E+09 | 29202.80 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.372492E+10 | |||
Minimum of Months | 30654584.19 | 1669.03 | -9.8 | |
Maximum of Months | 0.168963E+10 | 29271.46 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175534E+10 | 29100.27 | 27-JAN-08:61 | -6.4 |
February | 0.100169E+10 | 29180.48 | 12-FEB-09:12 | -9.8 |
March | 0.133182E+09 | 29077.30 | 20-MAR-07:01 | 5.10 |
April | 58695564.47 | 29074.87 | 06-APR-07:01 | 2.25 |
May | 33475831.20 | 1680.60 | 29-MAY-16:02 | 30.00 |
June | 49426394.88 | 2429.39 | 25-JUN-16:02 | 33.22 |
July | 57612846.01 | 2745.51 | 08-JUL-17:02 | 34.40 |
August | 43281084.17 | 2309.37 | 06-AUG-16:02 | 32.70 |
September | 30700072.48 | 1670.24 | 03-SEP-16:02 | 30.00 |
October | 45326904.65 | 12216.57 | 26-OCT-07:01 | 2.57 |
November | 0.100320E+09 | 29077.36 | 22-NOV-08:61 | -2.2 |
December | 0.594735E+09 | 29096.13 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.390379E+10 | |||
Minimum of Months | 30700072.48 | 1670.24 | -9.8 | |
Maximum of Months | 0.175534E+10 | 29180.48 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207679E+10 | 29015.05 | 27-JAN-08:61 | -6.4 |
February | 0.119180E+10 | 29154.85 | 12-FEB-09:12 | -9.8 |
March | 0.189660E+09 | 28993.14 | 20-MAR-07:01 | 5.10 |
April | 73891553.65 | 28990.16 | 06-APR-07:01 | 2.25 |
May | 37148967.51 | 1687.05 | 29-MAY-16:02 | 30.00 |
June | 51146027.63 | 2430.65 | 25-JUN-16:02 | 33.22 |
July | 58001668.14 | 2745.10 | 08-JUL-17:02 | 34.40 |
August | 43020548.18 | 2309.60 | 06-AUG-16:02 | 32.70 |
September | 31212962.58 | 1673.06 | 03-SEP-16:02 | 30.00 |
October | 53687806.90 | 20168.20 | 26-OCT-07:01 | 2.57 |
November | 0.125345E+09 | 28991.24 | 22-NOV-08:61 | -2.2 |
December | 0.743882E+09 | 29011.20 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.467558E+10 | |||
Minimum of Months | 31212962.58 | 1673.06 | -9.8 | |
Maximum of Months | 0.207679E+10 | 29154.85 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.358144E+10 | 32458.50 | 14-JAN-08:61 | -6.4 |
February | 0.223087E+10 | 32667.91 | 12-FEB-09:12 | -9.8 |
March | 0.473083E+09 | 32350.42 | 20-MAR-07:01 | 5.10 |
April | 0.161020E+09 | 32342.11 | 06-APR-07:01 | 2.25 |
May | 54920136.31 | 1703.51 | 29-MAY-16:02 | 30.00 |
June | 53240199.97 | 2421.99 | 25-JUN-16:02 | 33.22 |
July | 59237765.42 | 2726.78 | 08-JUL-17:02 | 34.40 |
August | 42360833.32 | 2291.78 | 06-AUG-16:02 | 32.70 |
September | 39002868.04 | 1673.55 | 03-SEP-16:02 | 30.00 |
October | 95177383.97 | 31835.56 | 26-OCT-07:01 | 2.57 |
November | 0.281244E+09 | 32341.25 | 22-NOV-08:61 | -2.2 |
December | 0.141081E+10 | 32371.23 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.848241E+10 | |||
Minimum of Months | 39002868.04 | 1673.55 | -9.8 | |
Maximum of Months | 0.358144E+10 | 32667.91 | 34.40 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.986629E+10 | 6035.26 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.891946E+10 | 6035.26 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.987658E+10 | 6035.26 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.956097E+10 | 6035.26 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.986629E+10 | 6035.26 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.956097E+10 | 6035.26 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.987658E+10 | 6035.26 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.986629E+10 | 6035.26 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.957126E+10 | 6035.26 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.986629E+10 | 6035.26 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.953010E+10 | 6035.26 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.988687E+10 | 6035.26 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.116248E+12 | 0.262491E+11 | ||||
Minimum of Months | 0.891946E+10 | 6035.26 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.988687E+10 | 6035.26 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.579394E+10 | 3544.17 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.523792E+10 | 3544.17 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.579999E+10 | 3544.17 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.561464E+10 | 3544.17 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.579394E+10 | 3544.17 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.561464E+10 | 3544.17 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.579999E+10 | 3544.17 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.579394E+10 | 3544.17 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.562069E+10 | 3544.17 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.579394E+10 | 3544.17 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.559651E+10 | 3544.17 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.580603E+10 | 3544.17 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.682662E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.523792E+10 | 3544.17 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.580603E+10 | 3544.17 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.413753E+10 | 3181.37 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.374692E+10 | 3181.37 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.422433E+10 | 3181.37 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.401456E+10 | 3181.37 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.418093E+10 | 3181.37 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.407966E+10 | 3181.37 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.411583E+10 | 3181.37 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.422433E+10 | 3181.37 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.401456E+10 | 3181.37 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.413753E+10 | 3181.37 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.401456E+10 | 3181.37 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.411583E+10 | 3181.37 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.490066E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.374692E+10 | 3181.37 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.422433E+10 | 3181.37 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.413753E+10 | 3181.37 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.374692E+10 | 3181.37 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.422433E+10 | 3181.37 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.401456E+10 | 3181.37 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.418093E+10 | 3181.37 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.407966E+10 | 3181.37 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.411583E+10 | 3181.37 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.422433E+10 | 3181.37 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.401456E+10 | 3181.37 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.413753E+10 | 3181.37 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.401456E+10 | 3181.37 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.411583E+10 | 3181.37 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.490066E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.374692E+10 | 3181.37 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.422433E+10 | 3181.37 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.413753E+10 | 3181.37 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.374692E+10 | 3181.37 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.422433E+10 | 3181.37 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.401456E+10 | 3181.37 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.418093E+10 | 3181.37 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.407966E+10 | 3181.37 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.411583E+10 | 3181.37 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.422433E+10 | 3181.37 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.401456E+10 | 3181.37 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.413753E+10 | 3181.37 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.401456E+10 | 3181.37 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.411583E+10 | 3181.37 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.490066E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.374692E+10 | 3181.37 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.422433E+10 | 3181.37 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.457032E+10 | 3825.14 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.413982E+10 | 3825.14 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.467469E+10 | 3825.14 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.443552E+10 | 3825.14 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.462251E+10 | 3825.14 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.451379E+10 | 3825.14 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.454423E+10 | 3825.14 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.467469E+10 | 3825.14 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.443552E+10 | 3825.14 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.457032E+10 | 3825.14 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.443552E+10 | 3825.14 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.454423E+10 | 3825.14 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.541612E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.413982E+10 | 3825.14 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.467469E+10 | 3825.14 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.986629E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459484E+10 |
February | 0.305697E+10 | 0.891946E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4234202.28 | 0.328306E+10 |
March | 0.335708E+10 | 0.987658E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36075593.52 | 0.207237E+10 |
April | 0.327081E+10 | 0.956097E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198145E+09 | 0.102238E+10 |
May | 0.336680E+10 | 0.986629E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469920E+09 | 0.492662E+09 |
June | 0.325380E+10 | 0.956097E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119474E+10 | 0.179102E+09 |
July | 0.339353E+10 | 0.987658E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139098E+10 | 0.159240E+09 |
August | 0.334857E+10 | 0.986629E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136669E+10 | 77014994.63 |
September | 0.327932E+10 | 0.957126E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551617E+09 | 0.312436E+09 |
October | 0.338624E+10 | 0.986629E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107570E+09 | 0.143220E+10 |
November | 0.327446E+10 | 0.953010E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 654806.52 | 0.222466E+10 |
December | 0.340325E+10 | 0.988687E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344046E+10 |
Annual Sum or Average | 0.397770E+11 | 0.116248E+12 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532064E+10 | 0.192904E+11 |
Minimum of Months | 0.305697E+10 | 0.891946E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77014994.63 |
Maximum of Months | 0.340325E+10 | 0.988687E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139098E+10 | 0.459484E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.579394E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225118E+10 |
February | 0.152844E+10 | 0.523792E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.61 | 0.156916E+10 |
March | 0.167849E+10 | 0.579999E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19334282.18 | 0.100982E+10 |
April | 0.163536E+10 | 0.561464E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108511E+09 | 0.469925E+09 |
May | 0.168335E+10 | 0.579394E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256191E+09 | 0.199060E+09 |
June | 0.162685E+10 | 0.561464E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643965E+09 | 59943976.01 |
July | 0.169671E+10 | 0.579999E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753634E+09 | 62928023.03 |
August | 0.167424E+10 | 0.579394E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738950E+09 | 25066830.93 |
September | 0.163961E+10 | 0.562069E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300514E+09 | 0.130797E+09 |
October | 0.169307E+10 | 0.579394E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58608981.32 | 0.672130E+09 |
November | 0.163718E+10 | 0.559651E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 356330.70 | 0.106394E+10 |
December | 0.170157E+10 | 0.580603E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167527E+10 |
Annual Sum or Average | 0.198880E+11 | 0.682662E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288235E+10 | 0.918921E+10 |
Minimum of Months | 0.152844E+10 | 0.523792E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25066830.93 |
Maximum of Months | 0.170157E+10 | 0.580603E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753634E+09 | 0.225118E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229905E+10 |
February | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.61 | 0.161066E+10 |
March | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19305621.35 | 0.103226E+10 |
April | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105798E+09 | 0.494013E+09 |
May | 0.102058E+10 | 0.418093E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249978E+09 | 0.218566E+09 |
June | 0.998711E+09 | 0.407966E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632796E+09 | 69063609.72 |
July | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737821E+09 | 70311267.21 |
August | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726800E+09 | 31393380.76 |
September | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290694E+09 | 0.144466E+09 |
October | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55604771.36 | 0.697192E+09 |
November | 0.973196E+09 | 0.401456E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343473.34 | 0.108736E+10 |
December | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170445E+10 |
Annual Sum or Average | 0.119700E+11 | 0.490066E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282142E+10 | 0.945878E+10 |
Minimum of Months | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31393380.76 |
Maximum of Months | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737821E+09 | 0.229905E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229000E+10 |
February | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.61 | 0.160051E+10 |
March | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19305774.19 | 0.102171E+10 |
April | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105803E+09 | 0.491260E+09 |
May | 0.102058E+10 | 0.418093E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249985E+09 | 0.218113E+09 |
June | 0.998711E+09 | 0.407966E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632704E+09 | 69452087.35 |
July | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737555E+09 | 70772241.75 |
August | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726603E+09 | 31984825.02 |
September | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290689E+09 | 0.144501E+09 |
October | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55617037.72 | 0.692655E+09 |
November | 0.973196E+09 | 0.401456E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343473.16 | 0.107856E+10 |
December | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169001E+10 |
Annual Sum or Average | 0.119700E+11 | 0.490066E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282089E+10 | 0.939952E+10 |
Minimum of Months | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31984825.02 |
Maximum of Months | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737555E+09 | 0.229000E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228083E+10 |
February | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.61 | 0.158652E+10 |
March | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19306261.50 | 0.100413E+10 |
April | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105828E+09 | 0.484192E+09 |
May | 0.102058E+10 | 0.418093E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250099E+09 | 0.215643E+09 |
June | 0.998711E+09 | 0.407966E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633001E+09 | 67732229.27 |
July | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738074E+09 | 69448075.38 |
August | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727005E+09 | 30513149.05 |
September | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290850E+09 | 0.142988E+09 |
October | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55659134.31 | 0.683757E+09 |
November | 0.973196E+09 | 0.401456E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343472.87 | 0.106613E+10 |
December | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167475E+10 |
Annual Sum or Average | 0.119700E+11 | 0.490066E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282245E+10 | 0.930664E+10 |
Minimum of Months | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30513149.05 |
Maximum of Months | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738074E+09 | 0.228083E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.457032E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418701E+10 |
February | 0.313522E+10 | 0.413982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4108877.92 | 0.290770E+10 |
March | 0.355148E+10 | 0.467469E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34825600.82 | 0.181506E+10 |
April | 0.338259E+10 | 0.443552E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190392E+09 | 0.886505E+09 |
May | 0.349753E+10 | 0.462251E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450541E+09 | 0.409921E+09 |
June | 0.343071E+10 | 0.451379E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114300E+10 | 0.134257E+09 |
July | 0.344942E+10 | 0.454423E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133289E+10 | 0.133378E+09 |
August | 0.355148E+10 | 0.467469E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131333E+10 | 59193011.37 |
September | 0.338259E+10 | 0.443552E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524467E+09 | 0.270545E+09 |
October | 0.344359E+10 | 0.457032E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100392E+09 | 0.125427E+10 |
November | 0.331698E+10 | 0.443552E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 617736.89 | 0.194954E+10 |
December | 0.344942E+10 | 0.454423E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307911E+10 |
Annual Sum or Average | 0.410346E+11 | 0.541612E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509457E+10 | 0.170865E+11 |
Minimum of Months | 0.313522E+10 | 0.413982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59193011.37 |
Maximum of Months | 0.355148E+10 | 0.467469E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133289E+10 | 0.418701E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228321E+10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.62 | 0.157493E+10 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19328175.44 | 0.977371E+09 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105978E+09 | 0.473630E+09 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250676E+09 | 0.215494E+09 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635100E+09 | 67628112.68 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741189E+09 | 69386709.49 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730069E+09 | 29142409.04 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291838E+09 | 0.143218E+09 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55842242.83 | 0.675140E+09 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343471.96 | 0.105350E+10 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166941E+10 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283265E+10 | 0.923206E+10 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29142409.04 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741189E+09 | 0.228321E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228066E+10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.63 | 0.157057E+10 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19328568.55 | 0.970261E+09 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105997E+09 | 0.469836E+09 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250728E+09 | 0.214494E+09 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635200E+09 | 67198467.39 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741337E+09 | 69064386.37 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730178E+09 | 28844112.79 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291890E+09 | 0.142840E+09 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55859290.19 | 0.672102E+09 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343471.90 | 0.104900E+10 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166586E+10 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283314E+10 | 0.920073E+10 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28844112.79 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741337E+09 | 0.228066E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227102E+10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.85 | 0.155769E+10 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19329047.97 | 0.951587E+09 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106053E+09 | 0.458347E+09 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250864E+09 | 0.210936E+09 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635345E+09 | 65994766.27 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741461E+09 | 68268752.29 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730241E+09 | 28212529.18 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291967E+09 | 0.141745E+09 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55897771.74 | 0.663700E+09 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343471.92 | 0.103722E+10 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165508E+10 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283378E+10 | 0.910980E+10 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28212529.18 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741461E+09 | 0.227102E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284696E+10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2407322.81 | 0.203869E+10 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20564972.67 | 0.123526E+10 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109289E+09 | 0.630485E+09 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259981E+09 | 0.334990E+09 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670387E+09 | 0.135805E+09 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776496E+09 | 0.116232E+09 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766096E+09 | 62558129.34 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302321E+09 | 0.222638E+09 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57898036.48 | 0.906347E+09 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 357227.06 | 0.137618E+10 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216748E+10 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296580E+10 | 0.120736E+11 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62558129.34 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776496E+09 | 0.284696E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 6035.26 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8886.97 | 07-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 6035.26 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 340.89 | 28-FEB-15:00 | 9043.12 | 11-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 6035.26 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.89 | 30-MAR-16:00 | 5360.18 | 22-MAR-11:10 |
April | 4050.04 | 01-APR-12:09 | 6035.26 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1440.81 | 12-APR-14:00 | 4408.09 | 05-APR-11:05 |
May | 4050.04 | 05-MAY-12:09 | 6035.26 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.05 | 19-MAY-16:00 | 1965.57 | 10-MAY-11:10 |
June | 4050.04 | 02-JUN-12:09 | 6035.26 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3040.49 | 06-JUN-15:00 | 781.62 | 07-JUN-11:10 |
July | 4050.04 | 01-JUL-12:09 | 6035.26 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3502.57 | 08-JUL-15:00 | 1533.81 | 28-JUL-17:00 |
August | 4050.04 | 04-AUG-12:09 | 6035.26 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3186.20 | 01-AUG-17:00 | 327.81 | 31-AUG-17:00 |
September | 4050.04 | 01-SEP-12:09 | 6035.26 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2205.52 | 07-SEP-15:00 | 2035.78 | 28-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 6035.26 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1728.25 | 10-OCT-16:00 | 3917.03 | 25-OCT-11:10 |
November | 4050.04 | 03-NOV-12:09 | 6035.26 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 151.55 | 19-NOV-15:00 | 5549.45 | 20-NOV-12:05 |
December | 4050.04 | 01-DEC-13:09 | 6035.26 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6436.76 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.81 | |||||
Maximum of Months | 4050.04 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3502.57 | 9043.12 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3544.17 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 3544.17 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 3544.17 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.98 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 3544.17 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.33 | 12-APR-14:00 | 2482.78 | 05-APR-11:05 |
May | 2024.96 | 05-MAY-12:09 | 3544.17 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.37 | 19-MAY-16:00 | 1076.40 | 10-MAY-11:10 |
June | 2024.96 | 02-JUN-12:09 | 3544.17 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.25 | 06-JUN-15:00 | 422.30 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 3544.17 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2024.96 | 04-AUG-12:09 | 3544.17 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2024.96 | 01-SEP-12:09 | 3544.17 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.34 | 07-SEP-15:00 | 1101.59 | 28-SEP-17:00 |
October | 2024.96 | 01-OCT-12:09 | 3544.17 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.78 | 10-OCT-16:00 | 2238.51 | 25-OCT-11:10 |
November | 2024.96 | 03-NOV-12:09 | 3544.17 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 3058.63 | 20-NOV-12:05 |
December | 2024.96 | 01-DEC-13:09 | 3544.17 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.39 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3544.17 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2024.96 | 3544.17 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3181.37 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 3181.37 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3181.37 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.98 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 3181.37 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.33 | 12-APR-14:00 | 2476.56 | 05-APR-11:05 |
May | 2024.96 | 06-MAY-12:09 | 3181.37 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.37 | 19-MAY-16:00 | 1076.40 | 10-MAY-11:10 |
June | 2024.96 | 03-JUN-12:09 | 3181.37 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.28 | 06-JUN-15:00 | 422.30 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 3181.37 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 3181.37 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 3181.37 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.12 | 07-SEP-15:00 | 1101.59 | 28-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 3181.37 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.77 | 10-OCT-16:00 | 2210.94 | 25-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 3181.37 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 3017.30 | 20-NOV-12:05 |
December | 2024.96 | 02-DEC-13:09 | 3181.37 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.39 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3181.37 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 3181.37 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3181.37 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.98 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 3181.37 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.33 | 12-APR-14:00 | 2466.97 | 05-APR-11:05 |
May | 2024.96 | 06-MAY-12:09 | 3181.37 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.37 | 19-MAY-16:00 | 1076.40 | 10-MAY-11:10 |
June | 2024.96 | 03-JUN-12:09 | 3181.37 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.29 | 06-JUN-15:00 | 422.30 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 3181.37 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 3181.37 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 3181.37 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.13 | 07-SEP-15:00 | 1101.59 | 28-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 3181.37 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.77 | 10-OCT-16:00 | 2192.91 | 25-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 3181.37 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 2990.35 | 20-NOV-12:05 |
December | 2024.96 | 02-DEC-13:09 | 3181.37 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.39 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3181.37 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 3181.37 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3181.37 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.97 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 3181.37 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.33 | 12-APR-14:00 | 2432.65 | 05-APR-11:05 |
May | 2024.96 | 06-MAY-12:09 | 3181.37 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.37 | 19-MAY-16:00 | 1076.40 | 10-MAY-11:10 |
June | 2024.96 | 03-JUN-12:09 | 3181.37 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.31 | 06-JUN-15:00 | 422.30 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 3181.37 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 3181.37 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 3181.37 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.14 | 07-SEP-15:00 | 1101.59 | 28-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 3181.37 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.76 | 10-OCT-16:00 | 2156.19 | 25-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 3181.37 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 2977.32 | 20-NOV-12:05 |
December | 2024.96 | 02-DEC-13:09 | 3181.37 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.39 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3825.14 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8548.36 | 07-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 3825.14 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 326.02 | 28-FEB-15:00 | 8665.12 | 11-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3825.14 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1118.14 | 30-MAR-16:00 | 5188.45 | 22-MAR-11:10 |
April | 5400.05 | 01-APR-14:09 | 3825.14 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1418.31 | 12-APR-14:00 | 4233.50 | 05-APR-11:05 |
May | 5400.05 | 06-MAY-14:09 | 3825.14 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1889.19 | 19-MAY-16:00 | 1925.83 | 10-MAY-11:10 |
June | 5400.05 | 03-JUN-14:09 | 3825.14 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2937.13 | 06-JUN-15:00 | 760.15 | 07-JUN-11:10 |
July | 5400.05 | 01-JUL-14:09 | 3825.14 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3470.21 | 08-JUL-15:00 | 1487.64 | 28-JUL-17:00 |
August | 5400.05 | 05-AUG-14:09 | 3825.14 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3102.80 | 01-AUG-17:00 | 319.23 | 31-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 3825.14 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2166.53 | 07-SEP-15:00 | 1982.46 | 28-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 3825.14 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1701.26 | 10-OCT-16:00 | 3756.50 | 25-OCT-11:10 |
November | 5400.05 | 04-NOV-14:09 | 3825.14 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 146.40 | 19-NOV-15:00 | 5361.03 | 20-NOV-12:05 |
December | 5400.05 | 02-DEC-15:09 | 3825.14 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6294.04 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.23 | |||||
Maximum of Months | 5400.05 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3470.21 | 8665.12 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.95 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.31 | 12-APR-14:00 | 2342.33 | 05-APR-11:05 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.36 | 19-MAY-16:00 | 1065.70 | 10-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.17 | 06-JUN-15:00 | 422.30 | 07-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.34 | 07-SEP-15:00 | 1101.59 | 28-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.77 | 10-OCT-16:00 | 2080.87 | 25-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 2975.51 | 20-NOV-12:05 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.39 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.95 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.31 | 12-APR-14:00 | 2324.34 | 05-APR-11:05 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.36 | 19-MAY-16:00 | 1063.58 | 10-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.17 | 06-JUN-15:00 | 422.30 | 07-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.34 | 07-SEP-15:00 | 1101.59 | 28-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.77 | 10-OCT-16:00 | 2068.82 | 25-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 2975.51 | 20-NOV-12:05 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.39 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.95 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.30 | 12-APR-14:00 | 2277.19 | 05-APR-11:05 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.36 | 19-MAY-16:00 | 1049.35 | 10-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.18 | 06-JUN-15:00 | 422.30 | 07-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.34 | 07-SEP-15:00 | 1101.59 | 28-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.77 | 10-OCT-16:00 | 2044.22 | 25-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 2975.51 | 20-NOV-12:05 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.39 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5080.22 | 07-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 195.56 | 28-FEB-15:00 | 5181.70 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 655.64 | 30-MAR-16:00 | 3052.26 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.78 | 12-APR-14:00 | 2434.73 | 05-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.19 | 19-MAY-16:00 | 1086.91 | 10-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1733.42 | 06-JUN-15:00 | 480.78 | 07-JUN-07:00 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1965.31 | 08-JUL-15:00 | 872.35 | 28-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1807.51 | 01-AUG-17:00 | 202.03 | 25-AUG-05:00 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1244.32 | 07-SEP-15:00 | 1154.90 | 28-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 973.71 | 10-OCT-16:00 | 2168.30 | 25-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.40 | 19-NOV-15:00 | 3163.92 | 20-NOV-12:05 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3642.11 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.03 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1965.31 | 5181.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10510.09 | 27-JAN-00:02 | 1687.52 | 1588.13 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.02 |
February | 11062.19 | 03-FEB-00:02 | 1687.52 | 1588.13 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.32 |
March | 11683.19 | 30-MAR-16:10 | 3375.03 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1098.35 | 0.00 |
April | 11617.29 | 17-APR-16:10 | 3375.03 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1374.08 | 0.00 |
May | 18059.40 | 31-MAY-07:03 | 1350.01 | 1270.50 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.79 |
June | 33624.02 | 15-JUN-07:02 | 1687.52 | 1588.13 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.07 |
July | 34155.26 | 17-JUL-07:01 | 2362.52 | 2223.38 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.28 |
August | 36027.15 | 26-AUG-07:02 | 0.00 | 1588.13 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.13 |
September | 35392.20 | 16-SEP-07:02 | 0.00 | 1588.13 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.01 |
October | 29264.92 | 19-OCT-07:02 | 1687.52 | 1588.13 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.52 |
November | 10616.86 | 05-NOV-16:07 | 12150.11 | 18105.77 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 38.86 | 0.00 |
December | 7920.15 | 01-DEC-00:03 | 1012.51 | 952.88 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7920.15 | 0.00 | 952.88 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36027.15 | 12150.11 | 18105.77 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 1374.08 | 489.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3743.92 | 26-JAN-16:03 | 2531.20 | 10632.52 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3269.33 |
February | 17947.30 | 28-FEB-22:15 | 8099.84 | 28353.40 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.86 |
March | 19874.84 | 12-MAR-17:55 | 12149.77 | 21265.05 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.13 |
April | 18296.88 | 09-APR-18:35 | 10799.79 | 28353.40 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.28 |
May | 16842.01 | 13-MAY-20:46 | 5062.40 | 17720.87 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.90 |
June | 19579.16 | 15-JUN-07:02 | 843.73 | 932.68 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.27 |
July | 20032.60 | 17-JUL-07:01 | 1181.23 | 1305.75 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.83 |
August | 20638.04 | 26-AUG-07:02 | 0.00 | 932.68 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.67 |
September | 20273.08 | 16-SEP-07:02 | 0.00 | 932.68 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.58 |
October | 18265.76 | 11-OCT-20:01 | 9112.33 | 31897.57 | 6044.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.16 |
November | 12817.76 | 03-NOV-20:30 | 6074.88 | 21265.05 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.19 |
December | 14336.85 | 12-DEC-21:55 | 6074.88 | 21265.05 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3743.92 | 0.00 | 932.68 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.56 | |
Maximum of Months | 20638.04 | 12149.77 | 31897.57 | 6044.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3269.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3679.85 | 17-JAN-10:23 | 1012.48 | 9544.12 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 513.68 |
February | 4767.05 | 01-FEB-08:61 | 1687.47 | 16744.07 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 657.71 |
March | 6093.32 | 30-MAR-16:10 | 1687.47 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 591.83 | 0.00 |
April | 6110.78 | 17-APR-16:10 | 1687.47 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 758.69 | 0.00 |
May | 15843.20 | 19-MAY-06:03 | 0.00 | 669.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.31 |
June | 19368.02 | 05-JUN-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 |
July | 18720.72 | 03-JUL-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.15 |
August | 19030.02 | 26-AUG-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.96 |
September | 19323.79 | 25-SEP-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15680.57 | 11-OCT-06:03 | 0.00 | 669.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.02 |
November | 7177.13 | 04-NOV-06:03 | 0.00 | 502.32 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.20 |
December | 4086.23 | 07-DEC-08:61 | 1518.72 | 15069.67 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3679.85 | 0.00 | 502.32 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19368.02 | 1687.47 | 16744.07 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 758.69 | 657.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3504.09 | 13-JAN-17:13 | 5062.40 | 9544.12 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3050.23 |
February | 4706.04 | 01-FEB-08:61 | 1687.47 | 16744.07 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.26 |
March | 6020.40 | 30-MAR-16:10 | 1687.47 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 591.83 | 0.00 |
April | 6088.94 | 17-APR-16:10 | 1687.47 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 758.69 | 0.00 |
May | 15955.20 | 19-MAY-06:03 | 0.00 | 669.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.31 |
June | 19458.18 | 05-JUN-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.60 |
July | 18809.80 | 03-JUL-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.23 |
August | 19095.86 | 26-AUG-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 |
September | 19384.64 | 25-SEP-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15570.97 | 11-OCT-06:03 | 0.00 | 669.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.02 |
November | 6400.67 | 04-NOV-06:03 | 0.00 | 502.32 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.19 |
December | 4031.60 | 15-DEC-08:62 | 1012.48 | 10046.44 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3504.09 | 0.00 | 502.32 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19458.18 | 5062.40 | 16744.07 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 758.69 | 3050.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4402.04 | 09-JAN-19:42 | 2699.95 | 12725.50 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526.24 |
February | 4645.82 | 01-FEB-08:61 | 1687.47 | 16744.07 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 642.06 |
March | 5800.99 | 30-MAR-16:10 | 1687.47 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 591.82 | 0.00 |
April | 5920.72 | 17-APR-16:10 | 1687.47 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 758.69 | 0.00 |
May | 14138.33 | 19-MAY-06:03 | 0.00 | 669.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 |
June | 19194.81 | 05-JUN-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.41 |
July | 18553.93 | 03-JUL-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.05 |
August | 18812.90 | 26-AUG-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 |
September | 19114.58 | 25-SEP-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14897.63 | 18-OCT-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.26 |
November | 4515.57 | 05-NOV-14:00 | 1012.48 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.17 |
December | 3965.05 | 15-DEC-08:62 | 1012.48 | 10046.44 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3965.05 | 0.00 | 669.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19194.81 | 2699.95 | 16744.07 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 758.69 | 642.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7240.86 | 04-JAN-20:03 | 2227.52 | 6039.66 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.59 |
February | 6346.86 | 28-FEB-15:30 | 4657.54 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 74.17 | 0.00 |
March | 9832.06 | 30-MAR-15:00 | 4657.54 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1114.80 | 0.00 |
April | 10346.81 | 17-APR-15:00 | 4657.54 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1399.71 | 0.00 |
May | 20861.93 | 30-MAY-07:03 | 0.00 | 805.21 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.81 |
June | 32433.29 | 05-JUN-07:03 | 0.00 | 805.21 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.37 |
July | 32401.28 | 25-JUL-07:02 | 0.00 | 1006.52 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.11 |
August | 34175.17 | 26-AUG-07:02 | 0.00 | 1006.52 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.17 |
September | 32904.12 | 16-SEP-07:02 | 0.00 | 1006.52 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.50 |
October | 27062.84 | 19-OCT-07:02 | 0.00 | 1006.52 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.32 |
November | 8126.38 | 05-NOV-15:00 | 4657.54 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 | 0.00 |
December | 6613.86 | 14-DEC-09:03 | 2227.52 | 6039.66 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 759.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6346.86 | 0.00 | 805.21 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34175.17 | 4657.54 | 6039.66 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 1399.71 | 759.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3583.96 | 04-JAN-20:03 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.34 |
February | 4456.14 | 02-FEB-10:32 | 1484.97 | 7855.30 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.20 |
March | 5069.00 | 30-MAR-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 619.27 | 0.00 |
April | 5381.47 | 17-APR-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 779.19 | 0.00 |
May | 10053.57 | 30-MAY-07:03 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.36 |
June | 16289.35 | 15-JUN-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.36 |
July | 16672.85 | 25-JUL-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.16 |
August | 17579.79 | 26-AUG-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.77 |
September | 16922.55 | 16-SEP-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.44 |
October | 13897.70 | 19-OCT-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.04 |
November | 4191.77 | 05-NOV-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 0.00 |
December | 3251.96 | 14-DEC-09:03 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3251.96 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17579.79 | 2328.71 | 7855.30 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 779.19 | 598.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4600.11 | 26-JAN-19:42 | 3509.93 | 7855.30 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.24 |
February | 4939.78 | 03-FEB-11:23 | 5804.89 | 7855.30 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 660.13 |
March | 4977.71 | 30-MAR-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 619.27 | 0.00 |
April | 5303.56 | 17-APR-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 779.19 | 0.00 |
May | 9353.35 | 30-MAY-07:03 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 |
June | 16199.48 | 15-JUN-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.65 |
July | 16586.06 | 25-JUL-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.48 |
August | 17490.11 | 26-AUG-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.12 |
September | 16831.58 | 16-SEP-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.78 |
October | 13802.59 | 19-OCT-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.30 |
November | 4120.57 | 05-NOV-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 0.00 |
December | 3234.71 | 14-DEC-09:03 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3234.71 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17490.11 | 5804.89 | 7855.30 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 779.19 | 660.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4813.79 | 26-JAN-11:23 | 5804.89 | 7855.30 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 649.99 |
February | 2882.04 | 28-FEB-15:30 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 41.15 | 0.00 |
March | 4772.85 | 30-MAR-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 619.27 | 0.00 |
April | 5114.07 | 17-APR-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 779.18 | 0.00 |
May | 6783.25 | 30-MAY-07:03 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.86 |
June | 16125.02 | 15-JUN-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.42 |
July | 16523.03 | 25-JUL-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.44 |
August | 16749.60 | 26-AUG-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.21 |
September | 16762.42 | 16-SEP-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.78 |
October | 13695.68 | 19-OCT-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.08 |
November | 3958.38 | 05-NOV-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 0.00 |
December | 3171.48 | 14-DEC-09:03 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2882.04 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16762.42 | 5804.89 | 7855.30 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 779.18 | 649.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2016.80 | 21-JAN-15:35 | 5399.90 | 3927.65 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1971.66 |
February | 2716.25 | 28-FEB-15:30 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 44.00 | 0.00 |
March | 4799.53 | 30-MAR-14:50 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 650.23 | 0.00 |
April | 5151.47 | 17-APR-14:30 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 790.12 | 0.00 |
May | 6440.60 | 30-MAY-14:30 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.03 | 0.00 |
June | 16077.10 | 15-JUN-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.81 |
July | 16636.59 | 17-JUL-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.15 |
August | 15827.62 | 10-AUG-07:02 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 15.72 | 0.00 |
September | 17307.47 | 09-SEP-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.37 |
October | 10494.98 | 19-OCT-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.55 |
November | 3923.25 | 05-NOV-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 0.00 |
December | 3099.93 | 01-DEC-19:53 | 2632.45 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2016.80 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17307.47 | 5399.90 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.03 | 1971.66 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.783616E+11 | 65138.51 | 09-JAN-18:00 | 0.768093E+11 | 177174.00 | 09-JAN-08:09 |
February | 0.706428E+11 | 64573.66 | 28-FEB-14:00 | 0.431550E+11 | 200306.64 | 12-FEB-09:09 |
March | 0.796220E+11 | 77162.92 | 30-MAR-14:09 | 0.592377E+10 | 76160.58 | 19-MAR-08:09 |
April | 0.820369E+11 | 73676.93 | 19-APR-14:39 | 0.791119E+09 | 51616.43 | 07-APR-07:10 |
May | 0.948776E+11 | 82722.69 | 30-MAY-13:39 | 897633.18 | 450.29 | 11-MAY-08:20 |
June | 0.107773E+12 | 97062.31 | 23-JUN-12:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.116249E+12 | 105561.21 | 08-JUL-15:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.121810E+12 | 102541.07 | 02-AUG-12:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.100471E+12 | 94725.79 | 06-SEP-13:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.860489E+11 | 83293.47 | 10-OCT-15:00 | 0.745038E+09 | 39380.13 | 26-OCT-08:09 |
November | 0.762553E+11 | 72072.05 | 05-NOV-13:50 | 0.664062E+10 | 96915.05 | 22-NOV-08:09 |
December | 0.776790E+11 | 61532.83 | 12-DEC-13:00 | 0.310605E+11 | 130590.68 | 18-DEC-08:09 |
Annual Sum or Average | 0.109183E+13 | 0.165126E+12 | ||||
Minimum of Months | 0.706428E+11 | 61532.83 | 0.00 | 0.00 | ||
Maximum of Months | 0.121810E+12 | 105561.21 | 0.768093E+11 | 200306.64 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.420288E+11 | 0.102541E+11 | 0.108325E+11 | 0.00 | 0.974604E+10 | 0.00 | 0.00 | 1600432.58 | 0.00 | 0.00 | 0.00 | 0.549851E+10 | 0.00 |
February | 0.380395E+11 | 0.866418E+10 | 0.980803E+10 | 0.00 | 0.838549E+10 | 0.00 | 0.00 | 0.786080E+09 | 0.00 | 0.00 | 0.00 | 0.495947E+10 | 0.00 |
March | 0.426243E+11 | 0.872495E+10 | 0.110075E+11 | 0.00 | 0.866691E+10 | 0.00 | 0.00 | 0.314588E+10 | 0.00 | 0.00 | 0.00 | 0.545255E+10 | 0.00 |
April | 0.407637E+11 | 0.757710E+10 | 0.105079E+11 | 0.00 | 0.816808E+10 | 0.00 | 0.00 | 0.987672E+10 | 0.00 | 0.00 | 0.00 | 0.514346E+10 | 0.00 |
May | 0.423184E+11 | 0.707526E+10 | 0.109147E+11 | 0.00 | 0.845677E+10 | 0.00 | 0.00 | 0.209052E+11 | 0.00 | 0.00 | 0.00 | 0.520723E+10 | 0.00 |
June | 0.411980E+11 | 0.651592E+10 | 0.106386E+11 | 0.00 | 0.837758E+10 | 0.00 | 0.00 | 0.360887E+11 | 0.00 | 0.00 | 0.00 | 0.495474E+10 | 0.00 |
July | 0.419004E+11 | 0.685746E+10 | 0.107945E+11 | 0.00 | 0.883617E+10 | 0.00 | 0.00 | 0.428378E+11 | 0.00 | 0.00 | 0.00 | 0.502281E+10 | 0.00 |
August | 0.426079E+11 | 0.748768E+10 | 0.110006E+11 | 0.00 | 0.912664E+10 | 0.00 | 0.00 | 0.465328E+11 | 0.00 | 0.00 | 0.00 | 0.505468E+10 | 0.00 |
September | 0.407800E+11 | 0.806830E+10 | 0.105148E+11 | 0.00 | 0.822966E+10 | 0.00 | 0.00 | 0.279538E+11 | 0.00 | 0.00 | 0.00 | 0.492408E+10 | 0.00 |
October | 0.420288E+11 | 0.923468E+10 | 0.108325E+11 | 0.00 | 0.844803E+10 | 0.00 | 0.00 | 0.103221E+11 | 0.00 | 0.00 | 0.00 | 0.518286E+10 | 0.00 |
November | 0.407147E+11 | 0.972262E+10 | 0.104978E+11 | 0.00 | 0.828597E+10 | 0.00 | 0.00 | 0.189855E+10 | 0.00 | 0.00 | 0.00 | 0.513565E+10 | 0.00 |
December | 0.419167E+11 | 0.104673E+11 | 0.108050E+11 | 0.00 | 0.887001E+10 | 0.00 | 0.00 | 0.194707E+09 | 0.00 | 0.00 | 0.00 | 0.542529E+10 | 0.00 |
Annual Sum or Average | 0.496921E+12 | 0.100650E+12 | 0.128154E+12 | 0.00 | 0.103597E+12 | 0.00 | 0.00 | 0.200544E+12 | 0.00 | 0.00 | 0.00 | 0.619613E+11 | 0.00 |
Minimum of Months | 0.380395E+11 | 0.651592E+10 | 0.980803E+10 | 0.00 | 0.816808E+10 | 0.00 | 0.00 | 1600432.58 | 0.00 | 0.00 | 0.00 | 0.492408E+10 | 0.00 |
Maximum of Months | 0.426243E+11 | 0.104673E+11 | 0.110075E+11 | 0.00 | 0.974604E+10 | 0.00 | 0.00 | 0.465328E+11 | 0.00 | 0.00 | 0.00 | 0.549851E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.768093E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.431550E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.592377E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.791119E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 897633.18 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.745038E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.664062E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.310605E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.165126E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.768093E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30804.00 | 01-JAN-11:09 | 7723.25 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 9067.50 | 09-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30804.00 | 01-FEB-10:09 | 7723.25 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 9506.54 | 12-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 30804.00 | 01-MAR-10:09 | 7723.25 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 7168.86 | 19-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 30804.00 | 01-APR-09:09 | 7723.25 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 6705.68 | 07-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 30804.00 | 01-MAY-09:09 | 7723.25 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 6085.84 | 30-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 30804.00 | 01-JUN-09:09 | 7723.25 | 01-JUN-05:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 7529.87 | 26-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 30804.00 | 01-JUL-09:09 | 7723.25 | 01-JUL-05:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 8616.67 | 08-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 30804.00 | 01-AUG-09:09 | 7723.25 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 8065.88 | 19-AUG-13:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 30804.00 | 01-SEP-09:09 | 7723.25 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 7162.60 | 06-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 30804.00 | 01-OCT-10:09 | 7723.25 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 6896.55 | 19-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30804.00 | 01-NOV-09:09 | 7723.25 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7560.93 | 22-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30804.00 | 01-DEC-10:09 | 7723.25 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 8195.86 | 18-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30804.00 | 7723.25 | 8059.50 | 0.00 | 6085.84 | 0.00 | 0.00 | |||||
Maximum of Months | 30804.00 | 7723.25 | 8059.50 | 0.00 | 9506.54 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 317.44 | 31-JAN-23:10 | 0.00 | 0.00 | 0.00 | 11578.78 | 09-JAN-18:00 | 0.00 |
February | 14260.34 | 28-FEB-15:09 | 0.00 | 0.00 | 0.00 | 9718.99 | 08-FEB-13:20 | 0.00 |
March | 25027.79 | 30-MAR-14:09 | 0.00 | 0.00 | 0.00 | 11827.30 | 27-MAR-13:39 | 0.00 |
April | 24433.00 | 17-APR-14:20 | 0.00 | 0.00 | 0.00 | 9683.78 | 05-APR-11:00 | 0.00 |
May | 34172.73 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 7959.00 | 18-MAY-13:20 | 0.00 |
June | 43910.67 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 9653.88 | 23-JUN-14:39 | 0.00 |
July | 53565.67 | 08-JUL-13:00 | 0.00 | 0.00 | 0.00 | 7555.67 | 15-JUL-12:30 | 0.00 |
August | 49491.79 | 19-AUG-13:00 | 0.00 | 0.00 | 0.00 | 9106.76 | 29-AUG-15:50 | 0.00 |
September | 43828.47 | 06-SEP-12:00 | 0.00 | 0.00 | 0.00 | 9150.97 | 14-SEP-14:09 | 0.00 |
October | 33833.16 | 10-OCT-14:09 | 0.00 | 0.00 | 0.00 | 9682.20 | 05-OCT-12:20 | 0.00 |
November | 21331.36 | 05-NOV-14:00 | 0.00 | 0.00 | 0.00 | 9742.34 | 15-NOV-13:50 | 0.00 |
December | 11479.21 | 12-DEC-13:00 | 0.00 | 0.00 | 0.00 | 9475.59 | 30-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 317.44 | 0.00 | 0.00 | 0.00 | 7555.67 | 0.00 | ||
Maximum of Months | 53565.67 | 0.00 | 0.00 | 0.00 | 11827.30 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 65138.51 | 09-JAN-18:00 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 6972.99 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 64573.66 | 28-FEB-14:00 | 30804.00 | 8059.50 | 0.00 | 0.00 | 5730.80 | 0.00 | 0.00 | 13911.51 | 0.00 |
March | 77162.92 | 30-MAR-14:09 | 30804.00 | 8059.50 | 0.00 | 0.00 | 5730.80 | 0.00 | 0.00 | 25027.79 | 0.00 |
April | 73676.93 | 19-APR-14:39 | 30804.00 | 8059.50 | 0.00 | 0.00 | 5730.80 | 0.00 | 0.00 | 23045.34 | 0.00 |
May | 82722.69 | 30-MAY-13:39 | 30804.00 | 8059.50 | 0.00 | 0.00 | 5730.80 | 0.00 | 0.00 | 32682.66 | 0.00 |
June | 97062.31 | 23-JUN-12:50 | 30804.00 | 8059.50 | 0.00 | 0.00 | 6980.93 | 0.00 | 0.00 | 43658.92 | 0.00 |
July | 105561.21 | 08-JUL-15:09 | 30804.00 | 8059.50 | 0.00 | 0.00 | 8394.04 | 0.00 | 0.00 | 52877.15 | 0.00 |
August | 102541.07 | 02-AUG-12:50 | 30804.00 | 8059.50 | 0.00 | 0.00 | 7818.79 | 0.00 | 0.00 | 48303.87 | 0.00 |
September | 94725.79 | 06-SEP-13:39 | 30804.00 | 8059.50 | 0.00 | 0.00 | 7035.98 | 0.00 | 0.00 | 43269.17 | 0.00 |
October | 83293.47 | 10-OCT-15:00 | 30804.00 | 8059.50 | 0.00 | 0.00 | 5730.80 | 0.00 | 0.00 | 33269.69 | 0.00 |
November | 72072.05 | 05-NOV-13:50 | 30804.00 | 8059.50 | 0.00 | 0.00 | 5730.80 | 0.00 | 0.00 | 19948.88 | 0.00 |
December | 61532.83 | 12-DEC-13:00 | 30804.00 | 8059.50 | 0.00 | 0.00 | 5730.80 | 0.00 | 0.00 | 11479.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 61532.83 | 30804.00 | 8059.50 | 0.00 | 0.00 | 5730.80 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 105561.21 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 8394.04 | 0.00 | 0.00 | 52877.15 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 177174.00 | 09-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 200306.64 | 12-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 76160.58 | 19-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 51616.43 | 07-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 450.29 | 11-MAY-08:20 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 39380.13 | 26-OCT-08:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 96915.05 | 22-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 130590.68 | 18-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 200306.64 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
February | 1.00 | 20.43 | 0.33 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
December | 0.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Annual Sum or Average | 2.17 | 20.47 | 0.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.51 | 0.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
February | 0.17 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
February | 0.33 | 20.19 | 0.00 | 20.19 | 0.00 | 20.19 | 0.00 | 20.19 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
February | 0.33 | 20.19 | 0.00 | 20.19 | 0.00 | 20.19 | 0.00 | 20.19 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
February | 0.50 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
February | 0.83 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.17 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
February | 3.67 | 17.54 | 0.00 | 17.54 | 0.00 | 17.54 | 0.00 | 17.54 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.33 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Annual Sum or Average | 9.67 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.67 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.29 | 198.00 | 21.24 | 198.00 | 21.20 |
February | 401.50 | 21.77 | 122.00 | 21.60 | 122.00 | 21.49 |
March | 338.17 | 22.47 | 77.83 | 22.69 | 7.17 | 22.66 |
April | 166.67 | 22.92 | 209.00 | 23.43 | 19.50 | 23.43 |
May | 85.83 | 23.72 | 397.33 | 23.86 | 63.33 | 23.86 |
June | 24.83 | 23.88 | 429.17 | 23.89 | 19.67 | 23.89 |
July | 72.17 | 23.89 | 494.33 | 23.89 | 72.17 | 23.89 |
August | 71.00 | 23.89 | 497.00 | 23.89 | 71.00 | 23.89 |
September | 51.67 | 23.87 | 461.83 | 23.89 | 50.17 | 23.89 |
October | 183.00 | 22.91 | 222.67 | 23.45 | 42.33 | 23.49 |
November | 308.33 | 22.39 | 98.17 | 22.70 | 19.33 | 22.70 |
December | 463.67 | 21.40 | 81.00 | 21.48 | 60.33 | 21.46 |
Annual Sum or Average | 2662.83 | 22.17 | 3288.33 | 22.93 | 745.00 | 22.87 |
Minimum of Months | 24.83 | 21.29 | 77.83 | 21.24 | 7.17 | 21.20 |
Maximum of Months | 496.00 | 23.89 | 497.00 | 23.89 | 198.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 476.67 | 21.73 | 62.83 | 21.68 | 62.67 | 21.64 |
February | 363.83 | 22.14 | 46.83 | 22.14 | 30.00 | 22.07 |
March | 300.83 | 23.02 | 81.00 | 23.20 | 0.00 | 23.20 |
April | 117.00 | 23.27 | 210.33 | 23.67 | 2.33 | 23.67 |
May | 32.83 | 23.69 | 369.67 | 23.87 | 16.50 | 23.87 |
June | 7.17 | 23.48 | 419.33 | 23.88 | 2.00 | 23.88 |
July | 39.00 | 23.89 | 493.67 | 23.89 | 39.00 | 23.89 |
August | 29.17 | 23.89 | 496.33 | 23.89 | 29.17 | 23.89 |
September | 22.67 | 23.88 | 446.33 | 23.89 | 22.33 | 23.89 |
October | 113.17 | 23.20 | 228.67 | 23.66 | 21.50 | 23.67 |
November | 246.17 | 22.82 | 100.67 | 23.12 | 5.83 | 23.12 |
December | 453.67 | 22.20 | 42.67 | 22.30 | 14.17 | 22.30 |
Annual Sum or Average | 2202.17 | 22.47 | 2998.33 | 23.24 | 245.50 | 23.22 |
Minimum of Months | 7.17 | 21.73 | 42.67 | 21.68 | 0.00 | 21.64 |
Maximum of Months | 476.67 | 23.89 | 496.33 | 23.89 | 62.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 367.17 | 21.33 | 97.00 | 21.29 | 97.00 | 21.27 |
February | 293.67 | 21.83 | 54.00 | 21.74 | 51.50 | 21.65 |
March | 234.83 | 22.54 | 76.83 | 22.88 | 2.00 | 22.87 |
April | 99.83 | 22.99 | 177.50 | 23.67 | 8.00 | 23.67 |
May | 46.83 | 23.83 | 312.83 | 24.02 | 35.33 | 24.02 |
June | 21.50 | 25.07 | 332.83 | 24.16 | 18.83 | 24.22 |
July | 68.33 | 24.72 | 369.00 | 24.21 | 68.33 | 24.28 |
August | 65.83 | 24.80 | 379.00 | 24.21 | 65.83 | 24.29 |
September | 42.33 | 24.42 | 351.17 | 24.09 | 41.17 | 24.12 |
October | 128.50 | 23.00 | 173.83 | 23.60 | 30.33 | 23.64 |
November | 214.67 | 22.40 | 68.50 | 22.77 | 8.17 | 22.78 |
December | 342.50 | 21.55 | 39.50 | 21.66 | 24.00 | 21.67 |
Annual Sum or Average | 1926.00 | 22.32 | 2432.00 | 23.18 | 450.50 | 23.19 |
Minimum of Months | 21.50 | 21.33 | 39.50 | 21.29 | 2.00 | 21.27 |
Maximum of Months | 367.17 | 25.07 | 379.00 | 24.21 | 97.00 | 24.29 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.33 | 110.17 | 21.29 | 110.17 | 21.26 |
February | 301.00 | 21.82 | 62.67 | 21.71 | 61.00 | 21.63 |
March | 242.00 | 22.49 | 74.67 | 22.83 | 2.50 | 22.81 |
April | 104.33 | 22.97 | 171.83 | 23.64 | 8.50 | 23.65 |
May | 47.67 | 23.83 | 311.67 | 24.02 | 35.67 | 24.02 |
June | 21.17 | 25.11 | 332.83 | 24.16 | 18.67 | 24.22 |
July | 67.67 | 24.73 | 369.00 | 24.21 | 67.67 | 24.28 |
August | 64.00 | 24.83 | 379.00 | 24.21 | 64.00 | 24.29 |
September | 42.17 | 24.42 | 351.17 | 24.09 | 41.00 | 24.12 |
October | 136.33 | 22.96 | 170.67 | 23.56 | 31.17 | 23.60 |
November | 226.67 | 22.40 | 66.50 | 22.73 | 11.33 | 22.75 |
December | 344.67 | 21.50 | 44.33 | 21.61 | 29.50 | 21.62 |
Annual Sum or Average | 1968.67 | 22.30 | 2444.50 | 23.15 | 481.17 | 23.14 |
Minimum of Months | 21.17 | 21.33 | 44.33 | 21.29 | 2.50 | 21.26 |
Maximum of Months | 371.00 | 25.11 | 379.00 | 24.21 | 110.17 | 24.29 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.30 | 125.83 | 21.26 | 125.83 | 21.23 |
February | 314.67 | 21.82 | 69.83 | 21.69 | 69.83 | 21.60 |
March | 255.67 | 22.41 | 69.83 | 22.71 | 4.17 | 22.69 |
April | 117.83 | 22.94 | 157.33 | 23.57 | 9.17 | 23.58 |
May | 56.17 | 23.82 | 304.83 | 24.01 | 42.17 | 24.01 |
June | 23.17 | 24.83 | 331.33 | 24.15 | 19.83 | 24.19 |
July | 71.83 | 24.66 | 369.00 | 24.20 | 71.83 | 24.26 |
August | 74.17 | 24.66 | 379.00 | 24.19 | 74.17 | 24.26 |
September | 48.50 | 24.32 | 349.83 | 24.08 | 46.67 | 24.11 |
October | 149.67 | 22.90 | 159.50 | 23.48 | 34.00 | 23.53 |
November | 240.00 | 22.35 | 64.83 | 22.65 | 14.00 | 22.67 |
December | 346.83 | 21.44 | 49.83 | 21.53 | 37.67 | 21.54 |
Annual Sum or Average | 2069.50 | 22.29 | 2431.00 | 23.09 | 549.33 | 23.08 |
Minimum of Months | 23.17 | 21.30 | 49.83 | 21.26 | 4.17 | 21.23 |
Maximum of Months | 371.00 | 24.83 | 379.00 | 24.20 | 125.83 | 24.26 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.26 | 170.50 | 21.22 | 170.50 | 21.19 |
February | 302.33 | 21.80 | 92.83 | 21.64 | 92.83 | 21.54 |
March | 259.33 | 22.34 | 47.33 | 22.53 | 5.33 | 22.51 |
April | 135.00 | 22.99 | 111.83 | 23.42 | 11.17 | 23.44 |
May | 66.83 | 23.78 | 262.50 | 23.91 | 51.83 | 23.91 |
June | 33.33 | 24.23 | 299.00 | 23.99 | 30.83 | 24.01 |
July | 84.83 | 24.21 | 338.00 | 24.03 | 84.83 | 24.06 |
August | 94.50 | 24.09 | 348.00 | 23.99 | 94.50 | 24.01 |
September | 72.50 | 24.08 | 314.17 | 23.98 | 71.17 | 24.00 |
October | 149.33 | 22.76 | 133.33 | 23.32 | 36.50 | 23.38 |
November | 253.67 | 22.37 | 44.83 | 22.56 | 16.67 | 22.59 |
December | 325.83 | 21.40 | 57.83 | 21.43 | 56.17 | 21.44 |
Annual Sum or Average | 2117.50 | 22.31 | 2220.17 | 22.94 | 722.33 | 22.92 |
Minimum of Months | 33.33 | 21.26 | 44.83 | 21.22 | 5.33 | 21.19 |
Maximum of Months | 340.00 | 24.23 | 348.00 | 24.03 | 170.50 | 24.06 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.25 | 173.17 | 21.21 | 173.17 | 21.19 |
February | 303.50 | 21.79 | 94.67 | 21.63 | 94.67 | 21.53 |
March | 262.67 | 22.32 | 38.17 | 22.47 | 6.00 | 22.44 |
April | 144.50 | 23.02 | 94.33 | 23.38 | 13.83 | 23.40 |
May | 71.33 | 23.77 | 256.50 | 23.91 | 53.17 | 23.91 |
June | 35.33 | 24.17 | 295.00 | 23.98 | 32.00 | 24.00 |
July | 85.33 | 24.21 | 338.00 | 24.03 | 85.33 | 24.06 |
August | 96.17 | 24.08 | 347.83 | 23.98 | 96.17 | 24.00 |
September | 73.67 | 24.07 | 306.83 | 23.98 | 71.67 | 23.99 |
October | 153.00 | 22.78 | 128.17 | 23.31 | 36.50 | 23.38 |
November | 265.33 | 22.42 | 42.67 | 22.58 | 17.17 | 22.61 |
December | 327.17 | 21.40 | 62.17 | 21.42 | 61.33 | 21.43 |
Annual Sum or Average | 2158.00 | 22.32 | 2177.50 | 22.93 | 741.00 | 22.90 |
Minimum of Months | 35.33 | 21.25 | 38.17 | 21.21 | 6.00 | 21.19 |
Maximum of Months | 340.00 | 24.21 | 347.83 | 24.03 | 173.17 | 24.06 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.25 | 182.17 | 21.20 | 182.17 | 21.18 |
February | 304.83 | 21.78 | 98.50 | 21.61 | 98.50 | 21.51 |
March | 266.00 | 22.29 | 35.83 | 22.42 | 7.00 | 22.39 |
April | 150.33 | 23.00 | 91.33 | 23.35 | 15.33 | 23.36 |
May | 73.67 | 23.75 | 254.00 | 23.90 | 54.67 | 23.90 |
June | 36.67 | 24.16 | 294.50 | 23.98 | 32.83 | 24.00 |
July | 87.50 | 24.20 | 338.00 | 24.03 | 87.50 | 24.06 |
August | 99.00 | 24.07 | 347.83 | 23.98 | 99.00 | 24.00 |
September | 74.50 | 24.06 | 305.33 | 23.97 | 72.33 | 23.99 |
October | 155.17 | 22.75 | 126.83 | 23.29 | 36.50 | 23.35 |
November | 269.50 | 22.40 | 41.33 | 22.56 | 17.50 | 22.59 |
December | 328.17 | 21.39 | 66.33 | 21.41 | 65.67 | 21.42 |
Annual Sum or Average | 2185.33 | 22.31 | 2182.00 | 22.91 | 769.00 | 22.88 |
Minimum of Months | 36.67 | 21.25 | 35.83 | 21.20 | 7.00 | 21.18 |
Maximum of Months | 340.00 | 24.20 | 347.83 | 24.03 | 182.17 | 24.06 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.23 | 206.33 | 21.19 | 206.33 | 21.17 |
February | 307.00 | 21.74 | 111.50 | 21.57 | 111.50 | 21.47 |
March | 276.17 | 22.22 | 32.83 | 22.30 | 10.83 | 22.26 |
April | 171.33 | 22.95 | 78.83 | 23.24 | 19.00 | 23.26 |
May | 81.67 | 23.70 | 250.83 | 23.88 | 57.50 | 23.88 |
June | 40.50 | 24.13 | 294.33 | 23.98 | 36.17 | 24.00 |
July | 90.33 | 24.19 | 338.00 | 24.02 | 90.33 | 24.05 |
August | 102.00 | 24.07 | 347.67 | 23.98 | 102.00 | 24.00 |
September | 78.33 | 24.05 | 304.00 | 23.97 | 75.67 | 23.99 |
October | 160.17 | 22.68 | 123.17 | 23.23 | 36.83 | 23.29 |
November | 278.67 | 22.36 | 41.83 | 22.51 | 20.17 | 22.53 |
December | 329.67 | 21.37 | 81.17 | 21.38 | 81.00 | 21.38 |
Annual Sum or Average | 2255.83 | 22.30 | 2210.50 | 22.86 | 847.33 | 22.82 |
Minimum of Months | 40.50 | 21.23 | 32.83 | 21.19 | 10.83 | 21.17 |
Maximum of Months | 340.00 | 24.19 | 347.67 | 24.02 | 206.33 | 24.05 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.20 | 261.33 | 21.16 | 261.33 | 21.15 |
February | 308.00 | 21.67 | 147.50 | 21.49 | 147.50 | 21.39 |
March | 296.67 | 22.15 | 41.50 | 22.13 | 29.33 | 22.05 |
April | 204.17 | 22.83 | 70.50 | 23.07 | 33.67 | 23.10 |
May | 93.83 | 23.56 | 246.00 | 23.82 | 60.17 | 23.81 |
June | 48.67 | 24.13 | 298.83 | 23.99 | 44.67 | 24.01 |
July | 86.00 | 24.23 | 338.00 | 24.03 | 86.00 | 24.07 |
August | 104.50 | 24.09 | 348.00 | 23.99 | 104.50 | 24.01 |
September | 85.33 | 24.02 | 309.50 | 23.97 | 78.17 | 23.99 |
October | 170.33 | 22.55 | 125.33 | 23.12 | 38.50 | 23.19 |
November | 286.33 | 22.27 | 48.33 | 22.37 | 30.50 | 22.37 |
December | 330.67 | 21.34 | 144.00 | 21.31 | 144.00 | 21.30 |
Annual Sum or Average | 2354.50 | 22.26 | 2378.83 | 22.76 | 1058.33 | 22.69 |
Minimum of Months | 48.67 | 21.20 | 41.50 | 21.16 | 29.33 | 21.15 |
Maximum of Months | 340.00 | 24.23 | 348.00 | 24.03 | 261.33 | 24.07 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.29338 | 24.77893 | -0.4585 | 10.59661 |
February | 448.00000 | 21.98670 | 27.59131 | -0.2496 | 9.03788 |
March | 497.00000 | 22.92041 | 33.17398 | 0.07247 | 7.05267 |
April | 479.00000 | 23.54392 | 41.81356 | 0.30571 | 8.16401 |
May | 496.00000 | 23.85980 | 50.04239 | -0.3971 | 8.71010 |
June | 481.00000 | 23.88873 | 52.05353 | -0.2991 | 7.11256 |
July | 495.00000 | 23.88996 | 58.18472 | -0.2284 | 6.19045 |
August | 497.00000 | 23.89048 | 58.40332 | -0.2090 | 6.01064 |
September | 479.00000 | 23.88622 | 54.22420 | -0.3004 | 7.07022 |
October | 496.00000 | 23.52212 | 45.08426 | 0.35661 | 8.69641 |
November | 480.00000 | 22.91797 | 33.97747 | 0.09495 | 7.39690 |
December | 496.00000 | 21.56126 | 29.86740 | -0.3009 | 8.54623 |
Annual Sum or Average | 5840.00000 | 23.10070 | 42.51929 | -0.1345 | 7.87723 |
Minimum of Months | 448.00000 | 21.29338 | 24.77893 | -0.4585 | 6.01064 |
Maximum of Months | 497.00000 | 23.89048 | 58.40332 | 0.35661 | 10.59661 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.80801 | 26.55901 | -0.3004 | 8.33496 |
February | 448.00000 | 22.46309 | 28.14311 | -0.1078 | 7.71982 |
March | 497.00000 | 23.35559 | 32.25992 | 0.18281 | 6.89834 |
April | 479.00000 | 23.71868 | 40.01359 | 0.35246 | 8.19309 |
May | 496.00000 | 23.86612 | 46.98508 | -0.4020 | 8.67042 |
June | 481.00000 | 23.87447 | 49.70640 | -0.3253 | 7.46538 |
July | 495.00000 | 23.88928 | 55.18038 | -0.2623 | 6.55982 |
August | 497.00000 | 23.89075 | 55.61743 | -0.2469 | 6.39565 |
September | 479.00000 | 23.87958 | 51.47445 | -0.3262 | 7.40842 |
October | 496.00000 | 23.71197 | 43.43611 | 0.39410 | 8.75472 |
November | 480.00000 | 23.33210 | 33.14426 | 0.19167 | 7.21239 |
December | 496.00000 | 22.33949 | 30.76507 | -0.1119 | 6.89773 |
Annual Sum or Average | 5840.00000 | 23.34736 | 41.18491 | -0.0805 | 7.54057 |
Minimum of Months | 448.00000 | 21.80801 | 26.55901 | -0.4020 | 6.39565 |
Maximum of Months | 497.00000 | 23.89075 | 55.61743 | 0.39410 | 8.75472 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.35427 | 24.49724 | -0.4119 | 9.62277 |
February | 336.00000 | 22.08946 | 26.72370 | -0.2009 | 8.35799 |
March | 379.00000 | 23.07938 | 33.01778 | 0.12704 | 7.13365 |
April | 360.00000 | 23.71874 | 40.13023 | 0.34764 | 8.51318 |
May | 375.00000 | 24.00164 | 49.43978 | -0.3539 | 8.14084 |
June | 366.00000 | 24.08332 | 51.82172 | -0.2557 | 6.98958 |
July | 369.00000 | 24.11108 | 58.09650 | -0.1827 | 6.33035 |
August | 379.00000 | 24.10608 | 58.25986 | -0.1695 | 6.19822 |
September | 360.00000 | 24.04302 | 53.86309 | -0.2684 | 6.95907 |
October | 371.00000 | 23.63437 | 44.01268 | 0.37775 | 8.97935 |
November | 360.00000 | 23.01800 | 32.70854 | 0.12183 | 7.33140 |
December | 369.00000 | 21.71938 | 29.03946 | -0.2466 | 7.90406 |
Annual Sum or Average | 4395.00000 | 23.25447 | 41.92561 | -0.0930 | 7.69858 |
Minimum of Months | 336.00000 | 21.35427 | 24.49724 | -0.4119 | 6.19822 |
Maximum of Months | 379.00000 | 24.11108 | 58.25986 | 0.37775 | 9.62277 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.33122 | 24.55491 | -0.4286 | 9.84017 |
February | 336.00000 | 22.04001 | 26.85151 | -0.2215 | 8.44859 |
March | 379.00000 | 23.02148 | 33.15794 | 0.10822 | 7.12600 |
April | 360.00000 | 23.70046 | 40.20520 | 0.34055 | 8.45684 |
May | 375.00000 | 23.99903 | 49.48233 | -0.3564 | 8.18293 |
June | 366.00000 | 24.08323 | 51.79784 | -0.2551 | 6.98319 |
July | 369.00000 | 24.11126 | 58.04687 | -0.1814 | 6.32286 |
August | 379.00000 | 24.10627 | 58.20400 | -0.1683 | 6.19161 |
September | 360.00000 | 24.04234 | 53.86703 | -0.2687 | 6.96282 |
October | 371.00000 | 23.60426 | 44.12331 | 0.36837 | 8.92032 |
November | 360.00000 | 22.96105 | 32.91981 | 0.10332 | 7.32268 |
December | 369.00000 | 21.65998 | 29.14551 | -0.2693 | 8.12400 |
Annual Sum or Average | 4395.00000 | 23.22980 | 41.98701 | -0.1024 | 7.73352 |
Minimum of Months | 336.00000 | 21.33122 | 24.55491 | -0.4286 | 6.19161 |
Maximum of Months | 379.00000 | 24.11126 | 58.20400 | 0.36837 | 9.84017 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.30119 | 24.63387 | -0.4494 | 10.13651 |
February | 336.00000 | 21.95574 | 27.05113 | -0.2528 | 8.60101 |
March | 379.00000 | 22.91246 | 33.43376 | 0.07511 | 7.10771 |
April | 360.00000 | 23.64609 | 40.42529 | 0.32122 | 8.29385 |
May | 375.00000 | 23.98681 | 49.77667 | -0.3675 | 8.37562 |
June | 366.00000 | 24.07809 | 52.04325 | -0.2621 | 7.04536 |
July | 369.00000 | 24.10684 | 58.34028 | -0.1869 | 6.34060 |
August | 379.00000 | 24.10189 | 58.53391 | -0.1734 | 6.20100 |
September | 360.00000 | 24.03631 | 54.13773 | -0.2758 | 7.03604 |
October | 371.00000 | 23.54278 | 44.41507 | 0.34950 | 8.78186 |
November | 360.00000 | 22.86804 | 33.18087 | 0.07419 | 7.28823 |
December | 369.00000 | 21.58706 | 29.27306 | -0.2966 | 8.39590 |
Annual Sum or Average | 4395.00000 | 23.18533 | 42.22828 | -0.1202 | 7.79349 |
Minimum of Months | 336.00000 | 21.30119 | 24.63387 | -0.4494 | 6.20100 |
Maximum of Months | 379.00000 | 24.10684 | 58.53391 | 0.34950 | 10.13651 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.25976 | 26.21333 | -0.4977 | 10.94791 |
February | 308.00000 | 21.83896 | 28.70794 | -0.3130 | 9.09590 |
March | 348.00000 | 22.73305 | 35.18387 | 0.01450 | 7.00271 |
April | 330.00000 | 23.53841 | 41.92087 | 0.28047 | 7.84221 |
May | 344.00000 | 23.90560 | 51.09703 | -0.4110 | 8.99239 |
June | 336.00000 | 23.95256 | 53.50723 | -0.3056 | 7.32911 |
July | 338.00000 | 23.98219 | 60.07882 | -0.2248 | 6.41457 |
August | 348.00000 | 23.95800 | 60.01555 | -0.2164 | 6.26159 |
September | 330.00000 | 23.94489 | 55.62642 | -0.3130 | 7.37606 |
October | 340.00000 | 23.42021 | 46.00897 | 0.31129 | 8.43855 |
November | 330.00000 | 22.72197 | 34.76163 | 0.02039 | 7.21023 |
December | 338.00000 | 21.48762 | 30.92161 | -0.3477 | 8.98416 |
Annual Sum or Average | 4030.00000 | 23.07052 | 43.79725 | -0.1666 | 7.98289 |
Minimum of Months | 308.00000 | 21.25976 | 26.21333 | -0.4977 | 6.26159 |
Maximum of Months | 348.00000 | 23.98219 | 60.07882 | 0.31129 | 10.94791 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.25322 | 26.12879 | -0.5011 | 10.98030 |
February | 308.00000 | 21.82157 | 28.65384 | -0.3224 | 9.12898 |
March | 348.00000 | 22.70562 | 35.16773 | -0.0027 | 7.00518 |
April | 330.00000 | 23.52485 | 41.92260 | 0.26526 | 7.69332 |
May | 344.00000 | 23.90322 | 51.11059 | -0.4310 | 9.34094 |
June | 336.00000 | 23.95151 | 53.50595 | -0.3298 | 7.63708 |
July | 338.00000 | 23.98053 | 60.10474 | -0.2504 | 6.65172 |
August | 348.00000 | 23.95682 | 60.03935 | -0.2430 | 6.50316 |
September | 330.00000 | 23.94431 | 55.67474 | -0.3341 | 7.64746 |
October | 340.00000 | 23.41531 | 45.98367 | 0.29754 | 8.26410 |
November | 330.00000 | 22.71052 | 34.72499 | 0.00741 | 7.19842 |
December | 338.00000 | 21.47984 | 30.84168 | -0.3563 | 9.08688 |
Annual Sum or Average | 4030.00000 | 23.06258 | 43.78213 | -0.1832 | 8.08750 |
Minimum of Months | 308.00000 | 21.25322 | 26.12879 | -0.5011 | 6.50316 |
Maximum of Months | 348.00000 | 23.98053 | 60.10474 | 0.29754 | 10.98030 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.24586 | 26.14678 | -0.5071 | 11.08294 |
February | 308.00000 | 21.79873 | 28.70124 | -0.3322 | 9.21245 |
March | 348.00000 | 22.66496 | 35.27286 | -0.0166 | 7.03771 |
April | 330.00000 | 23.49850 | 42.02979 | 0.25494 | 7.63547 |
May | 344.00000 | 23.89883 | 51.22579 | -0.4366 | 9.46087 |
June | 336.00000 | 23.95101 | 53.56845 | -0.3327 | 7.67785 |
July | 338.00000 | 23.98000 | 60.18174 | -0.2530 | 6.67511 |
August | 348.00000 | 23.95651 | 60.11065 | -0.2453 | 6.52471 |
September | 330.00000 | 23.94336 | 55.74128 | -0.3369 | 7.68769 |
October | 340.00000 | 23.39592 | 46.07330 | 0.29047 | 8.22622 |
November | 330.00000 | 22.67996 | 34.80850 | -0.0032 | 7.21087 |
December | 338.00000 | 21.46657 | 30.87045 | -0.3637 | 9.17781 |
Annual Sum or Average | 4030.00000 | 23.04873 | 43.85505 | -0.1900 | 8.12682 |
Minimum of Months | 308.00000 | 21.24586 | 26.14678 | -0.5071 | 6.52471 |
Maximum of Months | 348.00000 | 23.98000 | 60.18174 | 0.29047 | 11.08294 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.22527 | 26.19731 | -0.5260 | 11.44935 |
February | 308.00000 | 21.74448 | 28.81630 | -0.3573 | 9.49966 |
March | 348.00000 | 22.56308 | 35.53323 | -0.0496 | 7.15863 |
April | 330.00000 | 23.41902 | 42.36540 | 0.22789 | 7.51518 |
May | 344.00000 | 23.88247 | 51.49888 | -0.4496 | 9.77798 |
June | 336.00000 | 23.94999 | 53.69683 | -0.3337 | 7.69856 |
July | 338.00000 | 23.97932 | 60.33159 | -0.2516 | 6.66066 |
August | 348.00000 | 23.95632 | 60.18094 | -0.2434 | 6.50577 |
September | 330.00000 | 23.94053 | 55.87953 | -0.3381 | 7.71687 |
October | 340.00000 | 23.34248 | 46.31146 | 0.27449 | 8.17669 |
November | 330.00000 | 22.60472 | 35.00913 | -0.0274 | 7.26832 |
December | 338.00000 | 21.43515 | 30.93788 | -0.3827 | 9.44455 |
Annual Sum or Average | 4030.00000 | 23.01245 | 44.02422 | -0.2045 | 8.23151 |
Minimum of Months | 308.00000 | 21.22527 | 26.19731 | -0.5260 | 6.50577 |
Maximum of Months | 348.00000 | 23.97932 | 60.33159 | 0.27449 | 11.44935 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.19764 | 26.09319 | -0.5886 | 12.94339 |
February | 308.00000 | 21.66607 | 28.73261 | -0.4223 | 10.63255 |
March | 348.00000 | 22.40420 | 35.86772 | -0.1179 | 7.58168 |
April | 330.00000 | 23.25597 | 43.02036 | 0.16959 | 7.38192 |
May | 344.00000 | 23.83791 | 51.93921 | -0.4710 | 10.48691 |
June | 336.00000 | 23.95203 | 53.83266 | -0.3048 | 7.37342 |
July | 338.00000 | 23.98422 | 60.11835 | -0.2137 | 6.36551 |
August | 348.00000 | 23.96159 | 59.94604 | -0.2016 | 6.16932 |
September | 330.00000 | 23.93476 | 55.87364 | -0.3173 | 7.55166 |
October | 340.00000 | 23.24385 | 46.58869 | 0.24884 | 8.33374 |
November | 330.00000 | 22.49224 | 35.11778 | -0.0724 | 7.54486 |
December | 338.00000 | 21.39193 | 30.80464 | -0.4336 | 10.35313 |
Annual Sum or Average | 4030.00000 | 22.95265 | 44.12293 | -0.2265 | 8.54793 |
Minimum of Months | 308.00000 | 21.19764 | 26.09319 | -0.5886 | 6.16932 |
Maximum of Months | 348.00000 | 23.98422 | 60.11835 | 0.24884 | 12.94339 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.588003E+09 | 0.161123E+09 | 38.25 | 0.587408E+09 | 595095.94 | 0.00 | 0.47 | 26-FEB-15:10 | 0.00 | 01-FEB-00:10 | 9301.89 | 26-FEB-15:10 | 9301.89 | 26-FEB-15:10 | 75.97 | 28-FEB-20:00 | 2537.28 | 26-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.247140E+10 | 0.661699E+09 | 114.86 | 0.198814E+10 | 0.483268E+09 | 0.00 | 0.74 | 30-MAR-16:10 | 0.00 | 01-MAR-00:10 | 16606.73 | 30-MAR-14:00 | 14426.23 | 30-MAR-16:10 | 3716.14 | 30-MAR-12:10 | 4343.57 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.745557E+10 | 0.199242E+10 | 264.31 | 0.611345E+10 | 0.134212E+10 | 0.00 | 0.72 | 17-APR-16:10 | 0.00 | 01-APR-00:10 | 15575.01 | 23-APR-17:00 | 14933.56 | 17-APR-16:10 | 5209.37 | 23-APR-13:00 | 4214.74 | 17-APR-16:10 | 0.00 | 01-APR-00:10 |
May | 0.167097E+11 | 0.432587E+10 | 425.83 | 0.123633E+11 | 0.434640E+10 | 0.00 | 1.00 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 29225.56 | 31-MAY-07:03 | 19757.70 | 30-MAY-07:03 | 15433.89 | 31-MAY-07:03 | 6255.52 | 31-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.289943E+11 | 0.735613E+10 | 474.19 | 0.204364E+11 | 0.855787E+10 | 0.00 | 1.00 | 04-JUN-07:03 | 0.00 | 01-JUN-00:10 | 54000.16 | 23-JUN-07:03 | 38448.20 | 15-JUN-07:02 | 22530.20 | 23-JUN-07:03 | 11622.37 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.357032E+11 | 0.893016E+10 | 494.56 | 0.234968E+11 | 0.122065E+11 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 54744.59 | 27-JUL-07:02 | 38923.74 | 25-JUL-07:02 | 25001.57 | 28-JUL-07:03 | 11825.90 | 07-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.388736E+11 | 0.957237E+10 | 498.14 | 0.248796E+11 | 0.139940E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 54898.65 | 20-AUG-07:01 | 41053.07 | 26-AUG-07:02 | 30231.49 | 23-AUG-07:02 | 11920.85 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.236323E+11 | 0.586765E+10 | 439.89 | 0.158714E+11 | 0.776084E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 54482.29 | 17-SEP-07:02 | 40389.67 | 16-SEP-07:02 | 25374.51 | 28-SEP-07:02 | 11605.10 | 17-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.873691E+10 | 0.219939E+10 | 249.21 | 0.615115E+10 | 0.258576E+10 | 0.00 | 1.00 | 18-OCT-07:03 | 0.00 | 01-OCT-00:10 | 53444.82 | 19-OCT-07:02 | 23573.11 | 18-OCT-07:03 | 30392.96 | 19-OCT-07:02 | 11341.64 | 19-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.176259E+10 | 0.465386E+09 | 103.96 | 0.127724E+10 | 0.485345E+09 | 0.00 | 0.69 | 05-NOV-16:07 | 0.00 | 01-NOV-00:10 | 15809.01 | 05-NOV-16:07 | 11605.98 | 05-NOV-16:03 | 5190.45 | 05-NOV-13:00 | 3920.76 | 05-NOV-16:07 | 0.00 | 01-NOV-00:10 |
December | 0.160611E+09 | 43998147.00 | 16.42 | 0.113326E+09 | 47284829.71 | 0.00 | 0.40 | 12-DEC-14:20 | 0.00 | 01-DEC-00:03 | 8386.43 | 12-DEC-14:10 | 6051.95 | 12-DEC-14:40 | 2537.70 | 12-DEC-14:00 | 2226.01 | 12-DEC-14:10 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.165088E+12 | 0.415762E+11 | 3119.62 | 0.113278E+12 | 0.518099E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.388736E+11 | 0.957237E+10 | 498.14 | 0.248796E+11 | 0.139940E+11 | 0.00 | 1.00 | 0.00 | 54898.65 | 41053.07 | 30392.96 | 11920.85 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 5621128.85 | 1567024.26 | 4.08 | 4873262.75 | 747866.11 | 0.00 | 0.12 | 31-JAN-23:10 | 0.00 | 01-JAN-00:10 | 1151.14 | 31-JAN-23:10 | 967.19 | 31-JAN-23:10 | 280.07 | 19-JAN-23:50 | 317.44 | 31-JAN-23:10 | 0.00 | 01-JAN-00:10 |
February | 0.521118E+09 | 0.132557E+09 | 48.27 | 0.513416E+09 | 7702127.76 | 0.00 | 1.00 | 19-FEB-18:02 | 0.00 | 01-FEB-00:10 | 25603.56 | 19-FEB-18:08 | 24314.78 | 26-FEB-18:31 | 7308.74 | 19-FEB-18:08 | 5452.45 | 19-FEB-18:08 | 0.00 | 01-FEB-00:10 |
March | 0.187695E+10 | 0.477473E+09 | 144.51 | 0.153824E+10 | 0.338709E+09 | 0.00 | 1.00 | 04-MAR-19:01 | 0.00 | 01-MAR-00:10 | 25736.90 | 04-MAR-19:36 | 24314.78 | 12-MAR-17:35 | 7266.35 | 11-MAR-23:18 | 5572.88 | 11-MAR-19:07 | 0.00 | 01-MAR-00:10 |
April | 0.528308E+10 | 0.133922E+10 | 285.41 | 0.435976E+10 | 0.923324E+09 | 0.00 | 1.00 | 08-APR-18:01 | 0.00 | 01-APR-00:10 | 26850.43 | 22-APR-18:02 | 24368.52 | 08-APR-18:09 | 12008.73 | 22-APR-18:02 | 5683.39 | 22-APR-18:02 | 0.00 | 01-APR-00:10 |
May | 0.997748E+10 | 0.251393E+10 | 449.83 | 0.758598E+10 | 0.239150E+10 | 0.00 | 1.00 | 04-MAY-21:22 | 0.00 | 01-MAY-00:10 | 26945.93 | 24-MAY-20:02 | 24799.67 | 13-MAY-18:17 | 12706.17 | 24-MAY-20:02 | 5786.25 | 14-MAY-17:38 | 0.00 | 01-MAY-00:10 |
June | 0.152450E+11 | 0.380565E+10 | 469.47 | 0.111304E+11 | 0.411461E+10 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 27238.13 | 27-JUN-07:02 | 24555.29 | 10-JUN-19:22 | 6952.04 | 27-JUN-07:02 | 5881.66 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.182154E+11 | 0.451124E+10 | 496.27 | 0.123755E+11 | 0.583985E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 27651.91 | 27-JUL-07:02 | 22549.39 | 04-JUL-07:02 | 14588.81 | 28-JUL-20:17 | 5980.45 | 07-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.194594E+11 | 0.475434E+10 | 499.72 | 0.129202E+11 | 0.653919E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 27777.78 | 20-AUG-07:01 | 23594.74 | 26-AUG-07:02 | 9363.31 | 25-AUG-07:03 | 6051.41 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.126578E+11 | 0.309408E+10 | 447.25 | 0.883263E+10 | 0.382521E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 27582.85 | 17-SEP-07:02 | 23215.67 | 16-SEP-07:02 | 14003.98 | 21-SEP-20:02 | 5889.72 | 17-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.521530E+10 | 0.127854E+10 | 259.31 | 0.382017E+10 | 0.139513E+10 | 0.00 | 1.00 | 02-OCT-21:42 | 0.00 | 01-OCT-00:10 | 27666.32 | 19-OCT-07:02 | 23370.86 | 11-OCT-20:01 | 14579.84 | 19-OCT-07:02 | 5795.02 | 19-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.138068E+10 | 0.349431E+09 | 127.01 | 0.101419E+10 | 0.366484E+09 | 0.00 | 1.00 | 02-NOV-20:02 | 0.00 | 01-NOV-00:10 | 26610.65 | 04-NOV-18:02 | 15539.88 | 03-NOV-20:30 | 11509.01 | 04-NOV-18:58 | 5644.38 | 04-NOV-18:02 | 0.00 | 01-NOV-00:10 |
December | 0.175904E+09 | 45206658.94 | 25.69 | 0.123676E+09 | 52227924.96 | 0.00 | 1.00 | 12-DEC-21:02 | 0.00 | 01-DEC-00:03 | 25653.25 | 12-DEC-21:08 | 17638.70 | 12-DEC-21:55 | 8242.69 | 12-DEC-21:08 | 5462.93 | 12-DEC-21:08 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.900137E+11 | 0.223032E+11 | 3256.83 | 0.642190E+11 | 0.257947E+11 | 0.00 | ||||||||||||||
Minimum of Months | 5621128.85 | 1567024.26 | 4.08 | 4873262.75 | 747866.11 | 0.00 | 0.12 | 0.00 | 1151.14 | 967.19 | 280.07 | 317.44 | 0.00 | |||||||
Maximum of Months | 0.194594E+11 | 0.475434E+10 | 499.72 | 0.129202E+11 | 0.653919E+10 | 0.00 | 1.00 | 0.00 | 27777.78 | 24799.67 | 14588.81 | 6051.41 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 118138.76 | 33408.28 | 0.50 | 107366.31 | 10772.44 | 0.00 | 0.02 | 31-JAN-15:00 | 0.00 | 01-JAN-00:10 | 141.15 | 31-JAN-15:00 | 128.67 | 31-JAN-15:00 | 12.48 | 31-JAN-15:00 | 39.89 | 31-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.306594E+09 | 82249347.19 | 35.67 | 0.306465E+09 | 129618.64 | 0.00 | 0.48 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 5056.45 | 28-FEB-15:10 | 5056.45 | 28-FEB-15:10 | 24.96 | 22-FEB-14:40 | 1344.20 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.112339E+10 | 0.294451E+09 | 99.50 | 0.908183E+09 | 0.215208E+09 | 0.00 | 0.75 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 | 8810.80 | 30-MAR-14:00 | 7508.09 | 30-MAR-16:10 | 1990.57 | 30-MAR-12:10 | 2257.94 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.333020E+10 | 0.872119E+09 | 214.00 | 0.279955E+10 | 0.530644E+09 | 0.00 | 0.72 | 17-APR-16:10 | 0.00 | 01-APR-00:10 | 8114.37 | 17-APR-14:00 | 7812.23 | 17-APR-16:10 | 2693.48 | 04-APR-14:00 | 2165.40 | 17-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.692075E+10 | 0.175828E+10 | 328.35 | 0.518947E+10 | 0.173128E+10 | 0.00 | 1.00 | 19-MAY-06:03 | 0.00 | 01-MAY-00:10 | 26646.68 | 31-MAY-06:03 | 13257.17 | 30-MAY-06:03 | 13856.96 | 31-MAY-06:03 | 5588.86 | 31-MAY-06:03 | 0.00 | 01-MAY-00:10 |
June | 0.118725E+11 | 0.295499E+10 | 352.91 | 0.841940E+10 | 0.345315E+10 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 28272.44 | 23-JUN-06:02 | 19305.24 | 12-JUN-06:02 | 15480.18 | 19-JUN-06:02 | 5957.78 | 26-JUN-06:01 | 0.00 | 01-JUN-00:10 |
July | 0.142260E+11 | 0.349039E+10 | 363.58 | 0.937004E+10 | 0.485597E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 28817.36 | 27-JUL-06:02 | 20047.94 | 04-JUL-07:02 | 16362.44 | 31-JUL-06:02 | 6003.08 | 07-JUL-06:01 | 0.00 | 01-JUL-00:05 |
August | 0.156637E+11 | 0.379023E+10 | 375.22 | 0.100930E+11 | 0.557065E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 29236.75 | 21-AUG-06:02 | 19678.13 | 27-AUG-07:02 | 15710.47 | 23-AUG-06:03 | 6038.27 | 09-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.940103E+10 | 0.229519E+10 | 329.57 | 0.639594E+10 | 0.300509E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 29158.95 | 17-SEP-07:02 | 21144.60 | 16-SEP-06:02 | 15863.29 | 03-SEP-07:02 | 5967.60 | 17-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.351520E+10 | 0.871538E+09 | 200.58 | 0.251875E+10 | 0.996446E+09 | 0.00 | 1.00 | 02-OCT-06:03 | 0.00 | 01-OCT-00:10 | 28175.65 | 19-OCT-06:02 | 12320.80 | 18-OCT-06:02 | 16516.21 | 19-OCT-06:02 | 5837.63 | 19-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.744404E+09 | 0.194540E+09 | 93.89 | 0.563339E+09 | 0.181065E+09 | 0.00 | 0.64 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 | 7643.52 | 05-NOV-14:00 | 5317.20 | 05-NOV-15:00 | 2554.24 | 05-NOV-13:20 | 1861.99 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 92830444.39 | 24944187.44 | 18.50 | 65114796.56 | 27715647.83 | 0.00 | 0.43 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 4707.56 | 12-DEC-14:00 | 3304.84 | 12-DEC-14:00 | 1402.73 | 12-DEC-14:00 | 1217.82 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.671968E+11 | 0.166290E+11 | 2412.27 | 0.466294E+11 | 0.205674E+11 | 0.00 | ||||||||||||||
Minimum of Months | 118138.76 | 33408.28 | 0.50 | 107366.31 | 10772.44 | 0.00 | 0.02 | 0.00 | 141.15 | 128.67 | 12.48 | 39.89 | 0.00 | |||||||
Maximum of Months | 0.156637E+11 | 0.379023E+10 | 375.22 | 0.100930E+11 | 0.557065E+10 | 0.00 | 1.00 | 0.00 | 29236.75 | 21144.60 | 16516.21 | 6038.27 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.15 | 0.04 | 0.17 | 0.13 | 0.02 | 0.00 | 0.00 | 31-JAN-16:10 | 0.00 | 01-JAN-00:10 | 0.00 | 31-JAN-16:10 | 0.00 | 31-JAN-16:10 | 0.00 | 31-JAN-16:10 | 0.00 | 31-JAN-16:10 | 0.00 | 01-JAN-00:10 |
February | 0.281938E+09 | 75947258.63 | 33.83 | 0.281867E+09 | 71439.80 | 0.00 | 0.47 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 4913.93 | 28-FEB-15:10 | 4913.93 | 28-FEB-15:10 | 17.19 | 28-FEB-20:00 | 1311.07 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.107207E+10 | 0.281735E+09 | 96.08 | 0.866084E+09 | 0.205988E+09 | 0.00 | 0.74 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 | 8724.20 | 30-MAR-14:00 | 7436.44 | 30-MAR-16:10 | 1973.29 | 30-MAR-12:10 | 2240.50 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.327125E+10 | 0.858173E+09 | 212.08 | 0.274992E+10 | 0.521329E+09 | 0.00 | 0.71 | 17-APR-16:10 | 0.00 | 01-APR-00:10 | 8095.11 | 17-APR-14:00 | 7791.62 | 17-APR-16:10 | 2656.80 | 04-APR-14:00 | 2161.86 | 17-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.687765E+10 | 0.174908E+10 | 327.51 | 0.515674E+10 | 0.172091E+10 | 0.00 | 1.00 | 19-MAY-06:03 | 0.00 | 01-MAY-00:10 | 26582.71 | 31-MAY-06:03 | 13289.48 | 30-MAY-06:03 | 13826.67 | 31-MAY-06:03 | 5575.47 | 31-MAY-06:03 | 0.00 | 01-MAY-00:10 |
June | 0.118954E+11 | 0.296083E+10 | 352.91 | 0.843794E+10 | 0.345749E+10 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 28327.58 | 23-JUN-06:02 | 19389.26 | 12-JUN-06:02 | 15499.79 | 19-JUN-06:02 | 5969.18 | 26-JUN-06:01 | 0.00 | 01-JUN-00:10 |
July | 0.142745E+11 | 0.350174E+10 | 363.77 | 0.940956E+10 | 0.486497E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 28872.42 | 27-JUL-06:02 | 20114.79 | 04-JUL-07:02 | 16387.80 | 31-JUL-06:02 | 6014.28 | 07-JUL-06:01 | 0.00 | 01-JUL-00:05 |
August | 0.157145E+11 | 0.380191E+10 | 375.25 | 0.101328E+11 | 0.558169E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 29298.17 | 21-AUG-06:02 | 19756.37 | 27-AUG-07:02 | 15730.80 | 23-AUG-06:03 | 6049.18 | 09-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.939911E+10 | 0.229545E+10 | 328.91 | 0.639550E+10 | 0.300361E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 29210.85 | 17-SEP-07:02 | 21192.25 | 16-SEP-06:02 | 15894.22 | 03-SEP-07:02 | 5978.24 | 17-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.347065E+10 | 0.861425E+09 | 198.75 | 0.248369E+10 | 0.986955E+09 | 0.00 | 1.00 | 02-OCT-06:03 | 0.00 | 01-OCT-00:10 | 28226.07 | 19-OCT-06:02 | 12335.00 | 18-OCT-06:02 | 16551.88 | 19-OCT-06:02 | 5848.05 | 19-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.664965E+09 | 0.174564E+09 | 89.72 | 0.502454E+09 | 0.162511E+09 | 0.00 | 0.63 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 | 7521.47 | 05-NOV-14:00 | 5226.15 | 05-NOV-15:00 | 2515.52 | 05-NOV-13:20 | 1837.32 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 73505839.28 | 19832554.66 | 16.67 | 51762830.84 | 21743008.44 | 0.00 | 0.39 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 4337.05 | 12-DEC-14:00 | 3040.41 | 12-DEC-14:00 | 1296.64 | 12-DEC-14:00 | 1131.58 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.669956E+11 | 0.165807E+11 | 2395.66 | 0.464683E+11 | 0.205273E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.15 | 0.04 | 0.17 | 0.13 | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.157145E+11 | 0.380191E+10 | 375.25 | 0.101328E+11 | 0.558169E+10 | 0.00 | 1.00 | 0.00 | 29298.17 | 21192.25 | 16551.88 | 6049.18 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.244300E+09 | 66230143.69 | 31.08 | 0.244273E+09 | 27418.65 | 0.00 | 0.45 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 4609.96 | 28-FEB-15:10 | 4609.96 | 28-FEB-15:10 | 15.03 | 28-FEB-20:00 | 1238.13 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.967002E+09 | 0.255395E+09 | 87.17 | 0.781002E+09 | 0.186000E+09 | 0.00 | 0.72 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 | 8455.52 | 30-MAR-14:00 | 7212.80 | 30-MAR-16:10 | 1933.50 | 30-MAR-12:10 | 2181.09 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.308099E+10 | 0.811851E+09 | 203.08 | 0.258971E+10 | 0.491284E+09 | 0.00 | 0.71 | 17-APR-16:10 | 0.00 | 01-APR-00:10 | 7902.23 | 17-APR-14:00 | 7619.10 | 17-APR-16:10 | 2565.55 | 04-APR-14:00 | 2116.94 | 17-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.659675E+10 | 0.168305E+10 | 321.68 | 0.493928E+10 | 0.165747E+10 | 0.00 | 1.00 | 19-MAY-06:03 | 0.00 | 01-MAY-00:10 | 23461.80 | 31-MAY-06:03 | 11621.86 | 30-MAY-06:03 | 12293.63 | 31-MAY-06:03 | 4922.71 | 31-MAY-06:03 | 0.00 | 01-MAY-00:10 |
June | 0.116377E+11 | 0.290147E+10 | 352.67 | 0.822803E+10 | 0.340963E+10 | 0.00 | 1.00 | 04-JUN-07:03 | 0.00 | 01-JUN-00:10 | 28135.56 | 23-JUN-06:02 | 19123.26 | 12-JUN-06:02 | 15440.73 | 19-JUN-06:02 | 5930.86 | 26-JUN-06:01 | 0.00 | 01-JUN-00:10 |
July | 0.140126E+11 | 0.344134E+10 | 363.41 | 0.920829E+10 | 0.480430E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 28679.46 | 27-JUL-06:02 | 19827.59 | 04-JUL-07:02 | 16324.91 | 31-JUL-06:02 | 5975.82 | 07-JUL-06:01 | 0.00 | 01-JUL-00:05 |
August | 0.154375E+11 | 0.373786E+10 | 374.91 | 0.991477E+10 | 0.552274E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 29104.06 | 21-AUG-06:02 | 19495.78 | 27-AUG-07:02 | 15673.92 | 23-AUG-06:03 | 6011.02 | 09-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.915496E+10 | 0.224030E+10 | 327.27 | 0.620973E+10 | 0.294523E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 29016.36 | 17-SEP-07:02 | 20886.44 | 16-SEP-06:02 | 15841.15 | 03-SEP-07:02 | 5940.66 | 17-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.331451E+10 | 0.824816E+09 | 192.83 | 0.236152E+10 | 0.952992E+09 | 0.00 | 1.00 | 11-OCT-06:03 | 0.00 | 01-OCT-00:10 | 28046.00 | 19-OCT-06:02 | 12202.76 | 18-OCT-06:02 | 16499.82 | 19-OCT-06:02 | 5811.14 | 19-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.564274E+09 | 0.148805E+09 | 80.89 | 0.424950E+09 | 0.139325E+09 | 0.00 | 0.61 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 | 7218.77 | 05-NOV-14:00 | 5009.30 | 05-NOV-15:00 | 2422.08 | 05-NOV-13:20 | 1772.57 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 52051288.83 | 14103761.89 | 13.67 | 37059593.94 | 14991694.89 | 0.00 | 0.35 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 3829.76 | 12-DEC-14:00 | 2677.85 | 12-DEC-14:00 | 1151.91 | 12-DEC-14:00 | 1010.25 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.650626E+11 | 0.161252E+11 | 2348.66 | 0.449386E+11 | 0.201240E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.154375E+11 | 0.373786E+10 | 374.91 | 0.991477E+10 | 0.552274E+10 | 0.00 | 1.00 | 0.00 | 29104.06 | 20886.44 | 16499.82 | 6011.02 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.357942E+09 | 99696293.12 | 27.00 | 0.357857E+09 | 85722.52 | 0.00 | 0.44 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 8060.65 | 28-FEB-15:10 | 8060.65 | 28-FEB-15:10 | 22.22 | 28-FEB-19:40 | 2211.51 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.157138E+10 | 0.425811E+09 | 77.92 | 0.123978E+10 | 0.331599E+09 | 0.00 | 0.72 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 15289.31 | 30-MAR-14:10 | 12582.04 | 30-MAR-15:00 | 3754.35 | 30-MAR-12:10 | 4011.85 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.518366E+10 | 0.139933E+10 | 191.83 | 0.425291E+10 | 0.930750E+09 | 0.00 | 0.72 | 17-APR-14:40 | 0.00 | 01-APR-00:10 | 14644.38 | 17-APR-14:30 | 13632.71 | 17-APR-15:00 | 4943.38 | 04-APR-14:10 | 3975.30 | 17-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.115131E+11 | 0.300123E+10 | 311.22 | 0.841678E+10 | 0.309634E+10 | 0.00 | 1.00 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 35179.79 | 30-MAY-07:03 | 23688.80 | 30-MAY-07:03 | 16797.94 | 31-MAY-07:03 | 7617.00 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.209191E+11 | 0.530650E+10 | 344.83 | 0.144591E+11 | 0.645999E+10 | 0.00 | 1.00 | 04-JUN-08:62 | 0.00 | 01-JUN-00:10 | 50953.16 | 26-JUN-07:02 | 37347.85 | 05-JUN-07:03 | 27781.69 | 18-JUN-08:62 | 10953.76 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.248903E+11 | 0.621951E+10 | 349.15 | 0.160221E+11 | 0.886820E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 51627.81 | 31-JUL-07:02 | 36755.38 | 25-JUL-07:02 | 30979.88 | 31-JUL-07:02 | 11245.59 | 16-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.277221E+11 | 0.682921E+10 | 363.80 | 0.173921E+11 | 0.103301E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 52758.65 | 20-AUG-08:62 | 38690.63 | 26-AUG-07:02 | 28406.38 | 23-AUG-07:02 | 11172.39 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.160961E+11 | 0.400807E+10 | 314.42 | 0.106376E+11 | 0.545853E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 52581.30 | 17-SEP-08:62 | 37341.72 | 16-SEP-07:02 | 28829.23 | 03-SEP-08:62 | 11013.51 | 17-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.569833E+10 | 0.144457E+10 | 177.73 | 0.392568E+10 | 0.177264E+10 | 0.00 | 1.00 | 18-OCT-07:03 | 0.00 | 01-OCT-00:10 | 50203.34 | 19-OCT-07:02 | 21536.80 | 19-OCT-07:02 | 28666.53 | 19-OCT-07:02 | 10656.07 | 19-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.791326E+09 | 0.213512E+09 | 63.75 | 0.589996E+09 | 0.201330E+09 | 0.00 | 0.62 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 13354.51 | 05-NOV-15:00 | 8977.79 | 05-NOV-15:00 | 4541.62 | 05-NOV-14:10 | 3352.80 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 66549769.69 | 18441217.42 | 7.00 | 47249876.93 | 19299892.76 | 0.00 | 0.31 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 6106.49 | 12-DEC-14:00 | 4182.99 | 12-DEC-14:00 | 1923.51 | 12-DEC-14:00 | 1656.58 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.114810E+12 | 0.289659E+11 | 2228.65 | 0.773411E+11 | 0.374688E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.277221E+11 | 0.682921E+10 | 363.80 | 0.173921E+11 | 0.103301E+11 | 0.00 | 1.00 | 0.00 | 52758.65 | 38690.63 | 30979.88 | 11245.59 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.175027E+09 | 47973374.44 | 26.00 | 0.174997E+09 | 30420.51 | 0.00 | 0.43 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 4120.65 | 28-FEB-15:10 | 4120.65 | 28-FEB-15:10 | 9.31 | 28-FEB-19:40 | 1111.99 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.781096E+09 | 0.208232E+09 | 75.33 | 0.618313E+09 | 0.162783E+09 | 0.00 | 0.72 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 7834.31 | 30-MAR-14:10 | 6475.78 | 30-MAR-15:00 | 1903.45 | 30-MAR-12:10 | 2022.63 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.262477E+10 | 0.696957E+09 | 188.75 | 0.216008E+10 | 0.464682E+09 | 0.00 | 0.72 | 17-APR-14:50 | 0.00 | 01-APR-00:10 | 7559.74 | 17-APR-14:30 | 7056.27 | 17-APR-15:00 | 2510.47 | 04-APR-14:10 | 2016.70 | 17-APR-14:40 | 0.00 | 01-APR-00:10 |
May | 0.588749E+10 | 0.150907E+10 | 309.64 | 0.431625E+10 | 0.157123E+10 | 0.00 | 1.00 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 17012.65 | 30-MAY-07:03 | 11430.66 | 30-MAY-07:03 | 7794.34 | 31-MAY-07:03 | 3619.42 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.107390E+11 | 0.267997E+10 | 344.31 | 0.744127E+10 | 0.329777E+10 | 0.00 | 1.00 | 04-JUN-08:62 | 0.00 | 01-JUN-00:10 | 26322.31 | 26-JUN-07:02 | 18740.69 | 05-JUN-07:03 | 14339.54 | 18-JUN-08:62 | 5557.96 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.127872E+11 | 0.314401E+10 | 351.43 | 0.825620E+10 | 0.453097E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 26668.37 | 31-JUL-07:02 | 19004.51 | 25-JUL-07:02 | 15999.20 | 31-JUL-07:02 | 5705.60 | 16-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.142430E+11 | 0.345283E+10 | 365.40 | 0.896389E+10 | 0.527909E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 27251.83 | 20-AUG-08:62 | 19997.46 | 26-AUG-07:02 | 14648.13 | 23-AUG-07:02 | 5667.46 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.826307E+10 | 0.202292E+10 | 313.72 | 0.547819E+10 | 0.278489E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 27155.91 | 17-SEP-08:62 | 19302.84 | 16-SEP-07:02 | 14875.63 | 03-SEP-08:62 | 5587.73 | 17-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.291388E+10 | 0.725953E+09 | 175.56 | 0.201248E+10 | 0.901396E+09 | 0.00 | 1.00 | 18-OCT-07:03 | 0.00 | 01-OCT-00:10 | 25924.32 | 19-OCT-07:02 | 11145.63 | 19-OCT-07:02 | 14778.70 | 19-OCT-07:02 | 5406.29 | 19-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.385362E+09 | 0.102211E+09 | 61.33 | 0.287887E+09 | 97475672.72 | 0.00 | 0.62 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 6891.78 | 05-NOV-15:00 | 4649.05 | 05-NOV-15:00 | 2321.04 | 05-NOV-14:10 | 1700.14 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 30798954.36 | 8404197.95 | 6.17 | 21957724.15 | 8841230.21 | 0.00 | 0.30 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 2966.89 | 12-DEC-14:00 | 2036.14 | 12-DEC-14:00 | 930.75 | 12-DEC-14:00 | 794.42 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.588307E+11 | 0.145985E+11 | 2217.64 | 0.397315E+11 | 0.190992E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.142430E+11 | 0.345283E+10 | 365.40 | 0.896389E+10 | 0.527909E+10 | 0.00 | 1.00 | 0.00 | 27251.83 | 19997.46 | 15999.20 | 5705.60 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.165088E+09 | 45355872.97 | 25.33 | 0.165061E+09 | 26904.03 | 0.00 | 0.42 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 4018.13 | 28-FEB-15:10 | 4018.13 | 28-FEB-15:10 | 8.49 | 28-FEB-19:40 | 1086.79 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.749063E+09 | 0.200062E+09 | 73.25 | 0.592367E+09 | 0.156696E+09 | 0.00 | 0.71 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 7721.71 | 30-MAR-14:10 | 6382.17 | 30-MAR-15:00 | 1877.51 | 30-MAR-12:10 | 1997.23 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.255441E+10 | 0.679499E+09 | 185.75 | 0.210165E+10 | 0.452752E+09 | 0.00 | 0.71 | 17-APR-14:50 | 0.00 | 01-APR-00:10 | 7479.37 | 17-APR-14:40 | 6975.99 | 17-APR-15:00 | 2461.66 | 04-APR-14:10 | 1997.71 | 17-APR-14:40 | 0.00 | 01-APR-00:10 |
May | 0.578911E+10 | 0.148520E+10 | 306.67 | 0.423904E+10 | 0.155006E+10 | 0.00 | 1.00 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 15852.17 | 30-MAY-07:03 | 10591.07 | 30-MAY-07:03 | 7250.41 | 31-MAY-07:03 | 3373.71 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.106633E+11 | 0.266155E+10 | 343.38 | 0.737734E+10 | 0.328594E+10 | 0.00 | 1.00 | 04-JUN-08:62 | 0.00 | 01-JUN-00:10 | 26218.95 | 26-JUN-07:02 | 18501.73 | 15-JUN-07:02 | 14297.02 | 18-JUN-08:62 | 5536.73 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.127110E+11 | 0.312538E+10 | 351.09 | 0.819629E+10 | 0.451473E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 26566.39 | 31-JUL-07:02 | 18899.31 | 25-JUL-07:02 | 15949.53 | 31-JUL-07:02 | 5683.95 | 16-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.141675E+11 | 0.343452E+10 | 365.03 | 0.890284E+10 | 0.526467E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 27145.74 | 20-AUG-08:62 | 19889.29 | 26-AUG-07:02 | 14605.06 | 23-AUG-07:02 | 5645.86 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.819843E+10 | 0.200759E+10 | 313.70 | 0.542693E+10 | 0.277150E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 27050.79 | 17-SEP-08:62 | 19194.52 | 16-SEP-07:02 | 14830.22 | 03-SEP-08:62 | 5566.60 | 17-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.286931E+10 | 0.715324E+09 | 173.14 | 0.197733E+10 | 0.891975E+09 | 0.00 | 1.00 | 18-OCT-07:03 | 0.00 | 01-OCT-00:10 | 25826.44 | 19-OCT-07:02 | 11088.97 | 19-OCT-07:02 | 14737.47 | 19-OCT-07:02 | 5385.86 | 19-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.363482E+09 | 96513850.21 | 59.75 | 0.270714E+09 | 92768760.23 | 0.00 | 0.62 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 6798.22 | 05-NOV-15:00 | 4575.56 | 05-NOV-15:00 | 2296.16 | 05-NOV-14:10 | 1679.51 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 28588303.39 | 7818080.18 | 5.33 | 20365386.95 | 8222916.44 | 0.00 | 0.29 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 2832.16 | 12-DEC-14:00 | 1941.00 | 12-DEC-14:00 | 891.16 | 12-DEC-14:00 | 760.69 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.582593E+11 | 0.144588E+11 | 2202.43 | 0.392699E+11 | 0.189894E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.141675E+11 | 0.343452E+10 | 365.03 | 0.890284E+10 | 0.526467E+10 | 0.00 | 1.00 | 0.00 | 27145.74 | 19889.29 | 15949.53 | 5683.95 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.143840E+09 | 39745194.79 | 23.58 | 0.143825E+09 | 14958.24 | 0.00 | 0.40 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 3783.79 | 28-FEB-15:10 | 3783.79 | 28-FEB-15:10 | 5.53 | 28-FEB-19:30 | 1029.79 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.674287E+09 | 0.181049E+09 | 67.25 | 0.533110E+09 | 0.141177E+09 | 0.00 | 0.69 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 7482.17 | 30-MAR-14:10 | 6177.76 | 30-MAR-15:00 | 1809.60 | 30-MAR-12:20 | 1945.77 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.236970E+10 | 0.634129E+09 | 178.00 | 0.195516E+10 | 0.414542E+09 | 0.00 | 0.70 | 17-APR-14:50 | 0.00 | 01-APR-00:10 | 7279.57 | 17-APR-14:40 | 6786.82 | 17-APR-15:00 | 2312.28 | 04-APR-14:10 | 1953.65 | 17-APR-14:40 | 0.00 | 01-APR-00:10 |
May | 0.555747E+10 | 0.143078E+10 | 297.92 | 0.406753E+10 | 0.148994E+10 | 0.00 | 0.94 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 11627.27 | 30-MAY-07:03 | 8092.66 | 30-MAY-15:00 | 5065.67 | 31-MAY-07:03 | 2774.19 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.105532E+11 | 0.263664E+10 | 342.46 | 0.729136E+10 | 0.326187E+10 | 0.00 | 1.00 | 04-JUN-08:62 | 0.00 | 01-JUN-00:10 | 26211.44 | 26-JUN-07:02 | 18411.39 | 15-JUN-07:02 | 14309.08 | 19-JUN-07:03 | 5537.46 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.126282E+11 | 0.310643E+10 | 349.16 | 0.814287E+10 | 0.448529E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 26569.83 | 31-JUL-07:02 | 18829.62 | 25-JUL-07:02 | 15985.67 | 31-JUL-07:02 | 5685.22 | 16-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.141262E+11 | 0.342582E+10 | 365.54 | 0.887340E+10 | 0.525275E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 27145.06 | 20-AUG-08:62 | 19002.99 | 26-AUG-07:02 | 14628.29 | 23-AUG-07:02 | 5646.83 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.810884E+10 | 0.198744E+10 | 311.69 | 0.536345E+10 | 0.274540E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 27047.50 | 17-SEP-08:62 | 19109.16 | 16-SEP-07:02 | 14863.25 | 03-SEP-08:62 | 5568.13 | 17-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.277040E+10 | 0.692096E+09 | 168.95 | 0.190243E+10 | 0.867968E+09 | 0.00 | 1.00 | 18-OCT-07:03 | 0.00 | 01-OCT-00:10 | 25832.68 | 19-OCT-07:02 | 11057.98 | 19-OCT-07:02 | 14774.70 | 19-OCT-07:02 | 5387.28 | 19-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.313150E+09 | 83383097.77 | 53.92 | 0.231603E+09 | 81547409.16 | 0.00 | 0.60 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 6581.97 | 05-NOV-15:00 | 4413.85 | 05-NOV-15:00 | 2229.16 | 05-NOV-14:10 | 1633.88 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 24196633.37 | 6659954.95 | 4.50 | 17237338.81 | 6959294.56 | 0.00 | 0.26 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 2529.32 | 12-DEC-14:00 | 1731.31 | 12-DEC-14:00 | 798.01 | 12-DEC-14:00 | 684.56 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.572694E+11 | 0.142242E+11 | 2162.97 | 0.385220E+11 | 0.187475E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.141262E+11 | 0.342582E+10 | 365.54 | 0.887340E+10 | 0.525275E+10 | 0.00 | 1.00 | 0.00 | 27145.06 | 19109.16 | 15985.67 | 5685.22 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.126289E+09 | 35202930.50 | 20.17 | 0.126289E+09 | 0.00 | 0.00 | 0.37 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 3740.62 | 28-FEB-15:10 | 3740.62 | 28-FEB-15:10 | 0.00 | 28-FEB-15:10 | 1027.81 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.588765E+09 | 0.159968E+09 | 57.00 | 0.472128E+09 | 0.116638E+09 | 0.00 | 0.65 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 7579.35 | 30-MAR-14:10 | 6263.49 | 30-MAR-14:50 | 1805.51 | 30-MAR-12:30 | 1995.37 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.218745E+10 | 0.593025E+09 | 163.75 | 0.185204E+10 | 0.335413E+09 | 0.00 | 0.65 | 17-APR-14:10 | 0.00 | 01-APR-00:10 | 7380.96 | 17-APR-14:10 | 6883.14 | 17-APR-14:30 | 2066.29 | 04-APR-15:00 | 2004.27 | 17-APR-14:10 | 0.00 | 01-APR-00:10 |
May | 0.558443E+10 | 0.144872E+10 | 277.83 | 0.415529E+10 | 0.142914E+10 | 0.00 | 0.91 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 | 11703.71 | 30-MAY-15:00 | 8592.85 | 30-MAY-14:30 | 4123.13 | 31-MAY-13:00 | 2930.60 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.112617E+11 | 0.282494E+10 | 342.60 | 0.789163E+10 | 0.337007E+10 | 0.00 | 1.00 | 05-JUN-07:03 | 0.00 | 01-JUN-00:10 | 28918.67 | 26-JUN-07:02 | 18579.83 | 15-JUN-07:02 | 13154.09 | 27-JUN-07:02 | 6049.15 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.136521E+11 | 0.336758E+10 | 341.64 | 0.898467E+10 | 0.466744E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 29179.32 | 27-JUL-07:02 | 19000.50 | 18-JUL-07:02 | 16723.33 | 31-JUL-07:02 | 6197.16 | 16-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.153445E+11 | 0.373375E+10 | 365.57 | 0.982655E+10 | 0.551799E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 29890.44 | 20-AUG-08:62 | 18141.80 | 10-AUG-07:02 | 16736.66 | 20-AUG-08:03 | 6186.22 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.868866E+10 | 0.213513E+10 | 303.17 | 0.587568E+10 | 0.281298E+10 | 0.00 | 1.00 | 02-SEP-07:02 | 0.00 | 01-SEP-00:05 | 29431.68 | 17-SEP-08:62 | 19964.23 | 09-SEP-07:02 | 16161.96 | 17-SEP-08:62 | 6065.44 | 17-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.282480E+10 | 0.708406E+09 | 158.37 | 0.196630E+10 | 0.858494E+09 | 0.00 | 1.00 | 19-OCT-07:02 | 0.00 | 01-OCT-00:10 | 19519.95 | 19-OCT-07:02 | 8725.66 | 10-OCT-14:10 | 11596.21 | 19-OCT-07:02 | 4067.33 | 19-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.261995E+09 | 70201749.64 | 44.00 | 0.193130E+09 | 68865615.47 | 0.00 | 0.56 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 6556.81 | 05-NOV-15:00 | 4437.48 | 05-NOV-15:00 | 2185.96 | 05-NOV-14:10 | 1648.49 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 19068966.76 | 5298381.46 | 4.33 | 13793501.04 | 5275465.73 | 0.00 | 0.21 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 2265.28 | 12-DEC-14:00 | 1569.18 | 12-DEC-14:00 | 696.09 | 12-DEC-14:00 | 620.17 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.605398E+11 | 0.150822E+11 | 2078.42 | 0.413575E+11 | 0.191823E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.153445E+11 | 0.373375E+10 | 365.57 | 0.982655E+10 | 0.551799E+10 | 0.00 | 1.00 | 0.00 | 29890.44 | 19964.23 | 16736.66 | 6197.16 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 86.77 | 86.25 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 88.36 | 73.98 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 86.91 | 51.00 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.31 | 42.50 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.63 | 28.15 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 68.22 | 17.69 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 73.07 | 12.40 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 88.17 | 10.51 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.62 | 24.29 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.36 | 49.54 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 97.96 | 63.18 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 91.42 | 73.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.14 | 44.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.63 | 10.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.36 | 86.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 86.77 | 86.25 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 88.36 | 73.98 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 86.91 | 51.00 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.31 | 42.50 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.63 | 28.15 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 68.22 | 17.69 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 73.07 | 12.40 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 88.17 | 10.51 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.62 | 24.29 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.36 | 49.54 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 97.96 | 63.18 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 91.42 | 73.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.14 | 44.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.63 | 10.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.36 | 86.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 86.77 | 86.25 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 88.36 | 73.98 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 86.91 | 51.00 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.31 | 42.50 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.63 | 28.15 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 68.22 | 17.69 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 73.07 | 12.40 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 88.17 | 10.51 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.62 | 24.29 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.36 | 49.54 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 97.96 | 63.18 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 91.42 | 73.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.14 | 44.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.63 | 10.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.36 | 86.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 86.77 | 86.25 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 88.36 | 73.98 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 86.91 | 51.00 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.31 | 42.50 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.63 | 28.15 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 68.22 | 17.69 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 73.07 | 12.40 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 88.17 | 10.51 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.62 | 24.29 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.36 | 49.54 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 97.96 | 63.18 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 91.42 | 73.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.14 | 44.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.63 | 10.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.36 | 86.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.00 | 62.05 | 26.95 | 104.84 | 102.09 | 0.00 | 0.00 | 0.00 |
February | 83.07 | 55.68 | 27.39 | 106.67 | 87.59 | 0.00 | 0.00 | 0.00 |
March | 74.71 | 38.93 | 35.77 | 104.84 | 60.55 | 0.00 | 0.00 | 0.00 |
April | 55.95 | 18.21 | 37.74 | 87.07 | 50.51 | 0.00 | 0.00 | 0.00 |
May | 45.21 | 5.25 | 39.95 | 74.05 | 33.53 | 0.00 | 0.00 | 0.00 |
June | 41.80 | 2.33 | 39.47 | 81.66 | 21.16 | 0.00 | 0.00 | 0.00 |
July | 42.26 | 3.15 | 39.11 | 87.43 | 14.84 | 0.00 | 0.00 | 0.00 |
August | 50.45 | 9.42 | 41.03 | 105.56 | 12.62 | 0.00 | 0.00 | 0.00 |
September | 55.48 | 20.64 | 34.85 | 97.97 | 29.01 | 0.00 | 0.00 | 0.00 |
October | 80.44 | 52.11 | 28.33 | 121.99 | 58.89 | 0.00 | 0.00 | 0.00 |
November | 86.53 | 57.42 | 29.11 | 118.04 | 75.05 | 0.00 | 0.00 | 0.00 |
December | 87.73 | 61.72 | 26.01 | 110.38 | 87.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.98 | 32.13 | 33.84 | 100.03 | 52.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.80 | 2.33 | 26.01 | 74.05 | 12.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.00 | 62.05 | 41.03 | 121.99 | 102.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.00 | 62.05 | 26.95 | 104.84 | 102.09 | 0.00 | 0.00 | 0.00 |
February | 83.07 | 55.68 | 27.39 | 106.67 | 87.59 | 0.00 | 0.00 | 0.00 |
March | 74.71 | 38.93 | 35.77 | 104.84 | 60.55 | 0.00 | 0.00 | 0.00 |
April | 55.95 | 18.21 | 37.74 | 87.07 | 50.51 | 0.00 | 0.00 | 0.00 |
May | 45.21 | 5.25 | 39.95 | 74.05 | 33.53 | 0.00 | 0.00 | 0.00 |
June | 41.80 | 2.33 | 39.47 | 81.66 | 21.16 | 0.00 | 0.00 | 0.00 |
July | 42.26 | 3.15 | 39.11 | 87.43 | 14.84 | 0.00 | 0.00 | 0.00 |
August | 50.45 | 9.42 | 41.03 | 105.56 | 12.62 | 0.00 | 0.00 | 0.00 |
September | 55.48 | 20.64 | 34.85 | 97.97 | 29.01 | 0.00 | 0.00 | 0.00 |
October | 80.44 | 52.11 | 28.33 | 121.99 | 58.89 | 0.00 | 0.00 | 0.00 |
November | 86.53 | 57.42 | 29.11 | 118.04 | 75.05 | 0.00 | 0.00 | 0.00 |
December | 87.73 | 61.72 | 26.01 | 110.38 | 87.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.98 | 32.13 | 33.84 | 100.03 | 52.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.80 | 2.33 | 26.01 | 74.05 | 12.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.00 | 62.05 | 41.03 | 121.99 | 102.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 85.24 | 91.72 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 86.75 | 78.98 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 85.12 | 54.45 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 71.11 | 44.71 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.16 | 29.20 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 68.25 | 18.09 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 73.27 | 12.70 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 88.46 | 10.64 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.54 | 24.62 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 100.60 | 51.30 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 96.58 | 66.24 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 89.74 | 79.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 82.31 | 46.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.16 | 10.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 100.60 | 91.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 85.24 | 91.72 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 86.75 | 78.98 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 85.12 | 54.45 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 71.11 | 44.71 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.16 | 29.20 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 68.25 | 18.09 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 73.27 | 12.70 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 88.46 | 10.64 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.54 | 24.62 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 100.60 | 51.30 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 96.58 | 66.24 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 89.74 | 79.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 82.31 | 46.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.16 | 10.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 100.60 | 91.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.00 | 62.05 | 26.95 | 103.05 | 108.47 | 0.00 | 0.00 | 0.00 |
February | 83.07 | 55.68 | 27.39 | 104.79 | 93.43 | 0.00 | 0.00 | 0.00 |
March | 74.71 | 38.93 | 35.77 | 102.75 | 64.60 | 0.00 | 0.00 | 0.00 |
April | 55.95 | 18.21 | 37.74 | 85.66 | 53.10 | 0.00 | 0.00 | 0.00 |
May | 45.21 | 5.25 | 39.95 | 73.49 | 34.75 | 0.00 | 0.00 | 0.00 |
June | 41.80 | 2.33 | 39.47 | 81.70 | 21.62 | 0.00 | 0.00 | 0.00 |
July | 42.26 | 3.15 | 39.11 | 87.67 | 15.19 | 0.00 | 0.00 | 0.00 |
August | 50.45 | 9.42 | 41.03 | 105.91 | 12.78 | 0.00 | 0.00 | 0.00 |
September | 55.48 | 20.64 | 34.85 | 97.90 | 29.40 | 0.00 | 0.00 | 0.00 |
October | 80.44 | 52.11 | 28.33 | 121.12 | 60.94 | 0.00 | 0.00 | 0.00 |
November | 86.53 | 57.42 | 29.11 | 116.43 | 78.61 | 0.00 | 0.00 | 0.00 |
December | 87.73 | 61.72 | 26.01 | 108.40 | 93.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.98 | 32.13 | 33.84 | 99.07 | 55.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.80 | 2.33 | 26.01 | 73.49 | 12.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.00 | 62.05 | 41.03 | 121.12 | 108.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 85.62 | 88.56 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 87.08 | 76.81 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 85.38 | 53.70 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 70.96 | 45.25 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 60.82 | 30.46 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.50 | 19.97 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.98 | 14.51 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.43 | 12.56 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.16 | 26.37 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 100.55 | 51.74 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 96.95 | 65.29 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 90.23 | 76.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 82.13 | 46.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 60.82 | 12.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 100.55 | 88.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 85.62 | 88.56 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 87.08 | 76.81 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 85.38 | 53.70 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 70.96 | 45.25 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 60.82 | 30.46 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.50 | 19.97 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.98 | 14.51 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.43 | 12.56 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.16 | 26.37 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 100.55 | 51.74 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 96.95 | 65.29 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 90.23 | 76.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 82.13 | 46.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 60.82 | 12.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 100.55 | 88.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 102.95 | 104.18 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 104.61 | 90.38 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 102.50 | 63.35 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 85.02 | 53.43 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 72.69 | 36.02 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.40 | 23.70 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 85.71 | 17.23 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 104.17 | 14.96 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 96.92 | 31.27 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 120.40 | 61.10 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 116.24 | 77.07 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 108.41 | 89.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 98.32 | 55.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 72.69 | 14.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 120.40 | 104.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 85.87 | 87.27 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 87.35 | 75.62 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 85.66 | 52.89 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 71.08 | 44.89 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 60.85 | 30.36 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.48 | 20.07 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.92 | 14.67 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.39 | 12.74 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.16 | 26.40 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 100.65 | 51.32 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 97.22 | 64.46 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 90.53 | 74.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 82.25 | 46.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 60.85 | 12.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 100.65 | 87.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 85.87 | 87.27 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 87.35 | 75.62 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 85.66 | 52.89 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 71.08 | 44.89 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 60.85 | 30.36 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.48 | 20.07 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.92 | 14.67 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.39 | 12.74 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.16 | 26.40 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 100.65 | 51.32 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 97.22 | 64.46 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 90.53 | 74.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 82.25 | 46.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 60.85 | 12.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 100.65 | 87.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 103.24 | 102.67 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 104.93 | 88.97 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 102.83 | 62.40 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 85.16 | 53.00 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 72.73 | 35.90 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.37 | 23.82 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 85.64 | 17.43 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 104.12 | 15.17 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 96.91 | 31.31 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 120.52 | 60.61 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 116.56 | 76.08 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 108.77 | 88.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 98.47 | 54.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 72.73 | 15.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 120.52 | 102.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 86.16 | 86.18 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 87.74 | 74.34 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 86.14 | 51.81 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 71.40 | 44.15 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.04 | 29.88 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.63 | 19.70 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 72.07 | 14.33 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.52 | 12.40 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.28 | 26.01 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 100.88 | 50.59 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 97.63 | 63.46 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 90.88 | 73.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 82.52 | 45.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.04 | 12.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 100.88 | 86.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 86.16 | 86.18 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 87.74 | 74.34 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 86.14 | 51.81 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 71.40 | 44.15 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.04 | 29.88 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.63 | 19.70 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 72.07 | 14.33 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.52 | 12.40 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.28 | 26.01 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 100.88 | 50.59 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 97.63 | 63.46 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 90.88 | 73.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 82.52 | 45.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.04 | 12.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 100.88 | 86.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 103.60 | 101.38 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 105.40 | 87.47 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 103.41 | 61.13 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 85.54 | 52.14 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 72.96 | 35.35 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.55 | 23.38 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 85.81 | 17.03 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 104.27 | 14.77 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 97.06 | 30.84 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 120.79 | 59.74 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 117.04 | 74.90 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 109.19 | 87.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 98.79 | 53.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 72.96 | 14.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 120.79 | 101.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 87.33 | 82.94 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 88.96 | 71.01 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 87.44 | 49.27 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.33 | 42.19 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.50 | 28.45 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.80 | 18.47 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 72.23 | 13.31 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.66 | 11.36 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.52 | 24.85 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.55 | 48.79 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 98.70 | 61.11 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 92.03 | 71.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.24 | 43.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.50 | 11.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.55 | 82.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 87.33 | 82.94 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 88.96 | 71.01 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 87.44 | 49.27 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.33 | 42.19 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.50 | 28.45 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.80 | 18.47 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 72.23 | 13.31 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.66 | 11.36 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.52 | 24.85 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.55 | 48.79 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 98.70 | 61.11 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 92.03 | 71.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.24 | 43.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.50 | 11.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.55 | 82.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 87.33 | 82.94 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 88.96 | 71.01 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 87.44 | 49.27 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.33 | 42.19 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.50 | 28.45 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.80 | 18.47 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 72.23 | 13.31 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.66 | 11.36 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.52 | 24.85 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.55 | 48.79 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 98.70 | 61.11 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 92.03 | 71.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.24 | 43.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.50 | 11.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.55 | 82.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 87.33 | 82.94 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 88.96 | 71.01 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 87.44 | 49.27 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.33 | 42.19 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.50 | 28.45 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.80 | 18.47 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 72.23 | 13.31 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.66 | 11.36 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.52 | 24.85 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.55 | 48.79 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 98.70 | 61.11 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 92.03 | 71.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.24 | 43.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.50 | 11.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.55 | 82.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 104.94 | 97.62 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 106.81 | 83.60 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 104.91 | 58.18 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 86.62 | 49.85 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 73.50 | 33.67 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.75 | 21.93 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 86.00 | 15.81 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 104.43 | 13.54 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 97.34 | 29.47 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 121.56 | 57.65 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 118.27 | 72.17 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 110.51 | 83.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 99.62 | 51.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 73.50 | 13.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 121.56 | 97.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 104.94 | 97.62 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 106.81 | 83.60 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 104.91 | 58.18 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 86.62 | 49.85 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 73.50 | 33.67 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.75 | 21.93 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 86.00 | 15.81 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 104.43 | 13.54 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 97.34 | 29.47 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 121.56 | 57.65 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 118.27 | 72.17 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 110.51 | 83.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 99.62 | 51.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 73.50 | 13.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 121.56 | 97.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 86.93 | 83.32 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 88.66 | 71.17 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 87.27 | 49.08 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.25 | 41.99 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.52 | 28.22 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 68.00 | 18.14 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 72.47 | 12.97 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.87 | 10.97 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.54 | 24.53 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.38 | 48.62 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 98.51 | 61.03 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 91.70 | 71.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.16 | 43.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.52 | 10.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.38 | 83.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 86.93 | 83.32 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 88.66 | 71.17 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 87.27 | 49.08 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.25 | 41.99 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.52 | 28.22 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 68.00 | 18.14 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 72.47 | 12.97 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.87 | 10.97 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.54 | 24.53 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.38 | 48.62 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 98.51 | 61.03 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 91.70 | 71.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.16 | 43.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.52 | 10.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.38 | 83.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 104.53 | 98.01 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 106.51 | 83.74 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 104.76 | 57.92 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 86.56 | 49.60 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 73.54 | 33.39 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.99 | 21.55 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 86.29 | 15.41 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 104.69 | 13.08 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 97.38 | 29.10 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 121.40 | 57.43 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 118.10 | 72.04 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 110.17 | 83.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 99.56 | 51.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 73.54 | 13.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 121.40 | 98.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 87.02 | 82.99 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 88.80 | 70.76 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 87.50 | 48.62 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.43 | 41.64 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.63 | 28.03 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 68.07 | 18.03 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 72.53 | 12.87 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.93 | 10.88 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.59 | 24.42 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.48 | 48.35 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 98.67 | 60.67 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 91.81 | 70.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.28 | 43.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.63 | 10.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.48 | 82.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 87.02 | 82.99 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 88.80 | 70.76 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 87.50 | 48.62 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.43 | 41.64 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.63 | 28.03 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 68.07 | 18.03 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 72.53 | 12.87 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.93 | 10.88 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.59 | 24.42 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.48 | 48.35 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 98.67 | 60.67 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 91.81 | 70.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.28 | 43.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.63 | 10.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.48 | 82.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 104.64 | 97.63 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 106.68 | 83.26 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 105.03 | 57.39 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 86.78 | 49.18 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 73.67 | 33.17 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 81.08 | 21.42 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 86.37 | 15.30 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 104.76 | 12.97 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 97.45 | 28.96 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 121.52 | 57.11 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 118.29 | 71.62 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 110.31 | 83.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 99.70 | 50.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 73.67 | 12.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 121.52 | 97.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 87.34 | 81.69 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 89.18 | 69.41 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 88.03 | 47.36 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.92 | 40.58 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.88 | 27.48 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 68.13 | 17.85 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 72.54 | 12.77 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.91 | 10.82 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.63 | 24.23 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.70 | 47.67 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 99.05 | 59.74 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 92.14 | 69.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.52 | 42.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.88 | 10.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.70 | 81.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 87.34 | 81.69 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 89.18 | 69.41 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 88.03 | 47.36 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.92 | 40.58 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.88 | 27.48 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 68.13 | 17.85 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 72.54 | 12.77 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.91 | 10.82 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.63 | 24.23 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 101.70 | 47.67 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 99.05 | 59.74 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 92.14 | 69.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.52 | 42.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.88 | 10.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 101.70 | 81.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 105.02 | 96.09 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 107.13 | 81.67 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 105.66 | 55.91 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 87.36 | 47.94 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 73.98 | 32.52 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 81.15 | 21.20 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 86.38 | 15.18 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 104.74 | 12.91 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 97.49 | 28.75 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 121.79 | 56.31 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 118.75 | 70.52 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 110.70 | 82.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 100.00 | 49.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 73.98 | 12.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 121.79 | 96.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 88.37 | 76.37 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.15 | 64.45 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.21 | 43.20 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 74.01 | 36.89 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.37 | 25.37 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.78 | 17.18 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.91 | 12.55 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.18 | 10.89 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.33 | 23.71 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.02 | 45.52 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 99.84 | 56.77 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.08 | 65.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.92 | 39.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.37 | 10.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.02 | 76.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 88.37 | 76.37 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.15 | 64.45 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.21 | 43.20 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 74.01 | 36.89 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.37 | 25.37 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.78 | 17.18 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.91 | 12.55 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 87.18 | 10.89 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.33 | 23.71 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.02 | 45.52 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 99.84 | 56.77 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.08 | 65.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.92 | 39.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.37 | 10.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.02 | 76.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 106.27 | 89.83 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 108.31 | 75.84 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 107.07 | 51.02 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 88.67 | 43.61 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 74.57 | 30.05 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.73 | 20.42 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 85.62 | 14.92 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 103.87 | 12.99 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 97.12 | 28.14 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 122.17 | 53.78 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 119.69 | 67.04 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 111.84 | 77.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 100.47 | 46.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 74.57 | 12.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 122.17 | 89.83 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.232407E+09 | 0.231008E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.213760E+09 | 0.178972E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.232766E+09 | 0.136594E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.187431E+09 | 0.110149E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.165079E+09 | 75405463.52 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.176817E+09 | 45863092.62 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.195702E+09 | 33221316.37 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.236143E+09 | 28161867.26 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211560E+09 | 62968600.49 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.271491E+09 | 0.132699E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.253922E+09 | 0.163775E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.244872E+09 | 0.197370E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.262195E+10 | 0.139619E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.165079E+09 | 28161867.26 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.271491E+09 | 0.231008E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.232407E+09 | 0.231008E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.213760E+09 | 0.178972E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.232766E+09 | 0.136594E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.187431E+09 | 0.110149E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.165079E+09 | 75405463.52 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.176817E+09 | 45863092.62 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.195702E+09 | 33221316.37 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.236143E+09 | 28161867.26 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211560E+09 | 62968600.49 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.271491E+09 | 0.132699E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.253922E+09 | 0.163775E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.244872E+09 | 0.197370E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.262195E+10 | 0.139619E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.165079E+09 | 28161867.26 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.271491E+09 | 0.231008E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.232407E+09 | 0.231008E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.213760E+09 | 0.178972E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.232766E+09 | 0.136594E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.187431E+09 | 0.110149E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.165079E+09 | 75405463.52 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.176817E+09 | 45863092.62 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.195702E+09 | 33221316.37 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.236143E+09 | 28161867.26 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211560E+09 | 62968600.49 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.271491E+09 | 0.132699E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.253922E+09 | 0.163775E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.244872E+09 | 0.197370E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.262195E+10 | 0.139619E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.165079E+09 | 28161867.26 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.271491E+09 | 0.231008E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.232407E+09 | 0.231008E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.213760E+09 | 0.178972E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.232766E+09 | 0.136594E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.187431E+09 | 0.110149E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.165079E+09 | 75405463.52 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.176817E+09 | 45863092.62 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.195702E+09 | 33221316.37 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.236143E+09 | 28161867.26 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211560E+09 | 62968600.49 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.271491E+09 | 0.132699E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.253922E+09 | 0.163775E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.244872E+09 | 0.197370E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.262195E+10 | 0.139619E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.165079E+09 | 28161867.26 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.271491E+09 | 0.231008E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238381E+09 | 0.166199E+09 | 72182703.48 | 0.280815E+09 | 0.273432E+09 |
February | 0.200958E+09 | 0.134708E+09 | 66250453.20 | 0.258060E+09 | 0.211886E+09 |
March | 0.200093E+09 | 0.104277E+09 | 95816550.87 | 0.280795E+09 | 0.162186E+09 |
April | 0.145023E+09 | 47207941.68 | 97814586.08 | 0.225682E+09 | 0.130910E+09 |
May | 0.121078E+09 | 14072550.26 | 0.107005E+09 | 0.198324E+09 | 89803039.26 |
June | 0.108338E+09 | 6028589.92 | 0.102310E+09 | 0.211670E+09 | 54843007.04 |
July | 0.113179E+09 | 8439246.37 | 0.104739E+09 | 0.234159E+09 | 39746652.91 |
August | 0.135127E+09 | 25242249.26 | 0.109885E+09 | 0.282725E+09 | 33811168.71 |
September | 0.143813E+09 | 53490937.69 | 90322032.85 | 0.253930E+09 | 75199345.45 |
October | 0.215437E+09 | 0.139561E+09 | 75876831.16 | 0.326738E+09 | 0.157738E+09 |
November | 0.224295E+09 | 0.148839E+09 | 75456648.77 | 0.305952E+09 | 0.194522E+09 |
December | 0.234978E+09 | 0.165309E+09 | 69669240.16 | 0.295643E+09 | 0.233936E+09 |
Annual Sum or Average | 0.208070E+10 | 0.101337E+10 | 0.106733E+10 | 0.315449E+10 | 0.165801E+10 |
Minimum of Months | 0.108338E+09 | 6028589.92 | 66250453.20 | 0.198324E+09 | 33811168.71 |
Maximum of Months | 0.238381E+09 | 0.166199E+09 | 0.109885E+09 | 0.326738E+09 | 0.273432E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238381E+09 | 0.166199E+09 | 72182703.48 | 0.280815E+09 | 0.273432E+09 |
February | 0.200958E+09 | 0.134708E+09 | 66250453.20 | 0.258060E+09 | 0.211886E+09 |
March | 0.200093E+09 | 0.104277E+09 | 95816550.87 | 0.280795E+09 | 0.162186E+09 |
April | 0.145023E+09 | 47207941.68 | 97814586.08 | 0.225682E+09 | 0.130910E+09 |
May | 0.121078E+09 | 14072550.26 | 0.107005E+09 | 0.198324E+09 | 89803039.26 |
June | 0.108338E+09 | 6028589.92 | 0.102310E+09 | 0.211670E+09 | 54843007.04 |
July | 0.113179E+09 | 8439246.37 | 0.104739E+09 | 0.234159E+09 | 39746652.91 |
August | 0.135127E+09 | 25242249.26 | 0.109885E+09 | 0.282725E+09 | 33811168.71 |
September | 0.143813E+09 | 53490937.69 | 90322032.85 | 0.253930E+09 | 75199345.45 |
October | 0.215437E+09 | 0.139561E+09 | 75876831.16 | 0.326738E+09 | 0.157738E+09 |
November | 0.224295E+09 | 0.148839E+09 | 75456648.77 | 0.305952E+09 | 0.194522E+09 |
December | 0.234978E+09 | 0.165309E+09 | 69669240.16 | 0.295643E+09 | 0.233936E+09 |
Annual Sum or Average | 0.208070E+10 | 0.101337E+10 | 0.106733E+10 | 0.315449E+10 | 0.165801E+10 |
Minimum of Months | 0.108338E+09 | 6028589.92 | 66250453.20 | 0.198324E+09 | 33811168.71 |
Maximum of Months | 0.238381E+09 | 0.166199E+09 | 0.109885E+09 | 0.326738E+09 | 0.273432E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.228301E+09 | 0.245658E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.209863E+09 | 0.191070E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.227974E+09 | 0.145851E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.184322E+09 | 0.115882E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.163818E+09 | 78202523.43 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.176892E+09 | 46892199.56 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.196247E+09 | 34024905.12 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.236923E+09 | 28507337.99 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211362E+09 | 63821016.32 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.269445E+09 | 0.137409E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.250338E+09 | 0.171692E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.240351E+09 | 0.212169E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.259584E+10 | 0.147118E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.163818E+09 | 28507337.99 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.269445E+09 | 0.245658E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.228301E+09 | 0.245658E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.209863E+09 | 0.191070E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.227974E+09 | 0.145851E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.184322E+09 | 0.115882E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.163818E+09 | 78202523.43 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.176892E+09 | 46892199.56 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.196247E+09 | 34024905.12 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.236923E+09 | 28507337.99 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211362E+09 | 63821016.32 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.269445E+09 | 0.137409E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.250338E+09 | 0.171692E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.240351E+09 | 0.212169E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.259584E+10 | 0.147118E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.163818E+09 | 28507337.99 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.269445E+09 | 0.245658E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238381E+09 | 0.166199E+09 | 72182703.48 | 0.276007E+09 | 0.290537E+09 |
February | 0.200958E+09 | 0.134708E+09 | 66250453.20 | 0.253503E+09 | 0.226028E+09 |
March | 0.200093E+09 | 0.104277E+09 | 95816550.87 | 0.275206E+09 | 0.173029E+09 |
April | 0.145023E+09 | 47207941.68 | 97814586.08 | 0.222037E+09 | 0.137626E+09 |
May | 0.121078E+09 | 14072550.26 | 0.107005E+09 | 0.196849E+09 | 93080359.98 |
June | 0.108338E+09 | 6028589.92 | 0.102310E+09 | 0.211765E+09 | 56051704.31 |
July | 0.113179E+09 | 8439246.37 | 0.104739E+09 | 0.234813E+09 | 40690974.17 |
August | 0.135127E+09 | 25242249.26 | 0.109885E+09 | 0.283682E+09 | 34219537.60 |
September | 0.143813E+09 | 53490937.69 | 90322032.85 | 0.253747E+09 | 76194689.88 |
October | 0.215437E+09 | 0.139561E+09 | 75876831.16 | 0.324404E+09 | 0.163224E+09 |
November | 0.224295E+09 | 0.148839E+09 | 75456648.77 | 0.301789E+09 | 0.203766E+09 |
December | 0.234978E+09 | 0.165309E+09 | 69669240.16 | 0.290352E+09 | 0.251179E+09 |
Annual Sum or Average | 0.208070E+10 | 0.101337E+10 | 0.106733E+10 | 0.312415E+10 | 0.174563E+10 |
Minimum of Months | 0.108338E+09 | 6028589.92 | 66250453.20 | 0.196849E+09 | 34219537.60 |
Maximum of Months | 0.238381E+09 | 0.166199E+09 | 0.109885E+09 | 0.324404E+09 | 0.290537E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.229327E+09 | 0.237188E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.210660E+09 | 0.185822E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.228671E+09 | 0.143822E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.183937E+09 | 0.117290E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.162887E+09 | 81579454.14 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174967E+09 | 51754882.03 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.192783E+09 | 38858536.37 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.234178E+09 | 33632531.12 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210371E+09 | 68356864.22 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.269313E+09 | 0.138568E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.251300E+09 | 0.169241E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.241677E+09 | 0.204205E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.259007E+10 | 0.147032E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.162887E+09 | 33632531.12 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.269313E+09 | 0.237188E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.229327E+09 | 0.237188E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.210660E+09 | 0.185822E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.228671E+09 | 0.143822E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.183937E+09 | 0.117290E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.162887E+09 | 81579454.14 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174967E+09 | 51754882.03 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.192783E+09 | 38858536.37 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.234178E+09 | 33632531.12 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210371E+09 | 68356864.22 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.269313E+09 | 0.138568E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.251300E+09 | 0.169241E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.241677E+09 | 0.204205E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.259007E+10 | 0.147032E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.162887E+09 | 33632531.12 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.269313E+09 | 0.237188E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.275736E+09 | 0.279046E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.253073E+09 | 0.218651E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.274528E+09 | 0.169688E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.220380E+09 | 0.138487E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.194694E+09 | 96485696.59 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.208385E+09 | 61421934.55 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.229560E+09 | 46149103.52 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.279002E+09 | 40064701.57 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.251209E+09 | 81058885.94 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.322486E+09 | 0.163645E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.301284E+09 | 0.199756E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.290357E+09 | 0.240521E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.310069E+10 | 0.173497E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.194694E+09 | 40064701.57 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.322486E+09 | 0.279046E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.229984E+09 | 0.233757E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.211306E+09 | 0.182929E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.229431E+09 | 0.141653E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.184239E+09 | 0.116348E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.162984E+09 | 81306411.31 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174904E+09 | 52030099.09 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.192640E+09 | 39304136.16 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.234063E+09 | 34122068.72 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210366E+09 | 68429593.32 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.269576E+09 | 0.137456E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.252001E+09 | 0.167068E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.242476E+09 | 0.200811E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.259397E+10 | 0.145521E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.162984E+09 | 34122068.72 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.269576E+09 | 0.233757E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.229984E+09 | 0.233757E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.211306E+09 | 0.182929E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.229431E+09 | 0.141653E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.184239E+09 | 0.116348E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.162984E+09 | 81306411.31 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174904E+09 | 52030099.09 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.192640E+09 | 39304136.16 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.234063E+09 | 34122068.72 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210366E+09 | 68429593.32 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.269576E+09 | 0.137456E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.252001E+09 | 0.167068E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.242476E+09 | 0.200811E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.259397E+10 | 0.145521E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.162984E+09 | 34122068.72 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.269576E+09 | 0.233757E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.276529E+09 | 0.275000E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.253849E+09 | 0.215244E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.275432E+09 | 0.167135E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.220742E+09 | 0.137379E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.194811E+09 | 96164226.93 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.208311E+09 | 61747530.89 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.229391E+09 | 46674686.38 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.278864E+09 | 40642323.69 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.251203E+09 | 81144740.51 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.322801E+09 | 0.162335E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.302121E+09 | 0.197195E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.291319E+09 | 0.236526E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.310537E+10 | 0.171719E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.194811E+09 | 40642323.69 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.322801E+09 | 0.275000E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.230782E+09 | 0.230825E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.212253E+09 | 0.179839E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.230726E+09 | 0.138755E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.185060E+09 | 0.114436E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.163495E+09 | 80037717.71 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.175296E+09 | 51058894.62 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.193020E+09 | 38394143.17 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.234415E+09 | 33207118.67 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210685E+09 | 67407109.70 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.270191E+09 | 0.135488E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.253049E+09 | 0.164478E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.243426E+09 | 0.197875E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.260240E+10 | 0.143180E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.163495E+09 | 33207118.67 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.270191E+09 | 0.230825E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.230782E+09 | 0.230825E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.212253E+09 | 0.179839E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.230726E+09 | 0.138755E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.185060E+09 | 0.114436E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.163495E+09 | 80037717.71 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.175296E+09 | 51058894.62 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.193020E+09 | 38394143.17 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.234415E+09 | 33207118.67 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210685E+09 | 67407109.70 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.270191E+09 | 0.135488E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.253049E+09 | 0.164478E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.243426E+09 | 0.197875E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.260240E+10 | 0.143180E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.163495E+09 | 33207118.67 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.270191E+09 | 0.230825E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.277490E+09 | 0.271546E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.254983E+09 | 0.211611E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.276975E+09 | 0.163734E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.221722E+09 | 0.135135E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.195425E+09 | 94676175.67 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.208780E+09 | 60608325.78 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.229844E+09 | 45606575.24 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.279284E+09 | 39567736.49 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.251586E+09 | 79942988.17 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.323537E+09 | 0.160019E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.303373E+09 | 0.194149E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.292458E+09 | 0.233072E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.311546E+10 | 0.168967E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.195425E+09 | 39567736.49 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.323537E+09 | 0.271546E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.233899E+09 | 0.222135E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.215215E+09 | 0.171778E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.234212E+09 | 0.131977E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.187471E+09 | 0.109350E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.164718E+09 | 76203812.16 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.175742E+09 | 47878566.59 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.193452E+09 | 35644645.85 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.234788E+09 | 30427971.42 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211307E+09 | 64403444.35 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.271999E+09 | 0.130669E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.255825E+09 | 0.158407E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.246492E+09 | 0.190511E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.262512E+10 | 0.136939E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.164718E+09 | 30427971.42 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.271999E+09 | 0.222135E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.233899E+09 | 0.222135E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.215215E+09 | 0.171778E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.234212E+09 | 0.131977E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.187471E+09 | 0.109350E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.164718E+09 | 76203812.16 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.175742E+09 | 47878566.59 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.193452E+09 | 35644645.85 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.234788E+09 | 30427971.42 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211307E+09 | 64403444.35 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.271999E+09 | 0.130669E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.255825E+09 | 0.158407E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.246492E+09 | 0.190511E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.262512E+10 | 0.136939E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.164718E+09 | 30427971.42 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.271999E+09 | 0.222135E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.233899E+09 | 0.222135E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.215215E+09 | 0.171778E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.234212E+09 | 0.131977E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.187471E+09 | 0.109350E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.164718E+09 | 76203812.16 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.175742E+09 | 47878566.59 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.193452E+09 | 35644645.85 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.234788E+09 | 30427971.42 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211307E+09 | 64403444.35 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.271999E+09 | 0.130669E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.255825E+09 | 0.158407E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.246492E+09 | 0.190511E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.262512E+10 | 0.136939E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.164718E+09 | 30427971.42 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.271999E+09 | 0.222135E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.233899E+09 | 0.222135E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.215215E+09 | 0.171778E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.234212E+09 | 0.131977E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.187471E+09 | 0.109350E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.164718E+09 | 76203812.16 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.175742E+09 | 47878566.59 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.193452E+09 | 35644645.85 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.234788E+09 | 30427971.42 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211307E+09 | 64403444.35 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.271999E+09 | 0.130669E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.255825E+09 | 0.158407E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.246492E+09 | 0.190511E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.262512E+10 | 0.136939E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.164718E+09 | 30427971.42 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.271999E+09 | 0.222135E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.281080E+09 | 0.261478E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.258397E+09 | 0.202252E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.280999E+09 | 0.155840E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.224520E+09 | 0.129205E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.196856E+09 | 90188784.71 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.209315E+09 | 56854975.61 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.230350E+09 | 42346047.61 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.279704E+09 | 36260363.53 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.252296E+09 | 76397044.08 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.325593E+09 | 0.154407E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.306567E+09 | 0.187072E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.295980E+09 | 0.224536E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.314166E+10 | 0.161684E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.196856E+09 | 36260363.53 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.325593E+09 | 0.261478E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.281080E+09 | 0.261478E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.258397E+09 | 0.202252E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.280999E+09 | 0.155840E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.224520E+09 | 0.129205E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.196856E+09 | 90188784.71 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.209315E+09 | 56854975.61 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.230350E+09 | 42346047.61 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.279704E+09 | 36260363.53 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.252296E+09 | 76397044.08 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.325593E+09 | 0.154407E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.306567E+09 | 0.187072E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.295980E+09 | 0.224536E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.314166E+10 | 0.161684E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.196856E+09 | 36260363.53 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.325593E+09 | 0.261478E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.232828E+09 | 0.223153E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.214492E+09 | 0.172174E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.233757E+09 | 0.131446E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.187265E+09 | 0.108851E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.164771E+09 | 75584200.86 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.176250E+09 | 47026831.61 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.194098E+09 | 34729349.91 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.235345E+09 | 29374451.50 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211351E+09 | 63590093.15 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.271532E+09 | 0.130222E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.255332E+09 | 0.158188E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.245602E+09 | 0.190836E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.262262E+10 | 0.136518E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.164771E+09 | 29374451.50 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.271532E+09 | 0.223153E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.232828E+09 | 0.223153E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.214492E+09 | 0.172174E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.233757E+09 | 0.131446E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.187265E+09 | 0.108851E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.164771E+09 | 75584200.86 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.176250E+09 | 47026831.61 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.194098E+09 | 34729349.91 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.235345E+09 | 29374451.50 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211351E+09 | 63590093.15 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.271532E+09 | 0.130222E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.255332E+09 | 0.158188E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.245602E+09 | 0.190836E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.262262E+10 | 0.136518E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.164771E+09 | 29374451.50 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.271532E+09 | 0.223153E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.279965E+09 | 0.262511E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.257670E+09 | 0.202592E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.280601E+09 | 0.155146E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.224368E+09 | 0.128565E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.196981E+09 | 89434396.33 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.209933E+09 | 55851601.48 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.231131E+09 | 41267170.39 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.280397E+09 | 35025263.15 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.252414E+09 | 75423497.15 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.325164E+09 | 0.153810E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.306113E+09 | 0.186730E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.295081E+09 | 0.224784E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.313982E+10 | 0.161114E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.196981E+09 | 35025263.15 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.325164E+09 | 0.262511E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.233081E+09 | 0.222281E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.214835E+09 | 0.171175E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.234351E+09 | 0.130223E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.187745E+09 | 0.107927E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.165061E+09 | 75071589.53 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.176435E+09 | 46745015.62 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.194277E+09 | 34476575.21 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.235505E+09 | 29134580.21 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211487E+09 | 63296048.46 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.271801E+09 | 0.129509E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.255751E+09 | 0.157268E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.245910E+09 | 0.189936E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.262624E+10 | 0.135704E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.165061E+09 | 29134580.21 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.271801E+09 | 0.222281E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.233081E+09 | 0.222281E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.214835E+09 | 0.171175E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.234351E+09 | 0.130223E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.187745E+09 | 0.107927E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.165061E+09 | 75071589.53 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.176435E+09 | 46745015.62 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.194277E+09 | 34476575.21 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.235505E+09 | 29134580.21 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211487E+09 | 63296048.46 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.271801E+09 | 0.129509E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.255751E+09 | 0.157268E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.245910E+09 | 0.189936E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.262624E+10 | 0.135704E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.165061E+09 | 29134580.21 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.271801E+09 | 0.222281E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.280270E+09 | 0.261481E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.258083E+09 | 0.201416E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.281310E+09 | 0.153707E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.224944E+09 | 0.127480E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.197330E+09 | 88831255.73 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.210156E+09 | 55519455.72 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.231345E+09 | 40968336.93 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.280588E+09 | 34742037.70 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.252578E+09 | 75075362.62 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.325487E+09 | 0.152970E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.306613E+09 | 0.185644E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.295451E+09 | 0.223723E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.314415E+10 | 0.160156E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.197330E+09 | 34742037.70 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.325487E+09 | 0.261481E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.233924E+09 | 0.218787E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.215745E+09 | 0.167916E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.235771E+09 | 0.126853E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.189000E+09 | 0.105190E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.165740E+09 | 73601984.78 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.176591E+09 | 46256493.30 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.194297E+09 | 34203301.32 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.235452E+09 | 28988937.31 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211582E+09 | 62815964.49 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.272402E+09 | 0.127692E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.256749E+09 | 0.154845E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.246778E+09 | 0.186981E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.263403E+10 | 0.133413E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.165740E+09 | 28988937.31 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.272402E+09 | 0.218787E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.233924E+09 | 0.218787E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.215745E+09 | 0.167916E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.235771E+09 | 0.126853E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.189000E+09 | 0.105190E+09 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.165740E+09 | 73601984.78 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.176591E+09 | 46256493.30 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.194297E+09 | 34203301.32 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.235452E+09 | 28988937.31 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211582E+09 | 62815964.49 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.272402E+09 | 0.127692E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.256749E+09 | 0.154845E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.246778E+09 | 0.186981E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.263403E+10 | 0.133413E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.165740E+09 | 28988937.31 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.272402E+09 | 0.218787E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.281285E+09 | 0.257363E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.259178E+09 | 0.197585E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.283004E+09 | 0.149750E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.226444E+09 | 0.124271E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.198143E+09 | 87108211.54 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.210342E+09 | 54950373.19 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.231367E+09 | 40653640.58 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.280524E+09 | 34577842.47 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.252693E+09 | 74515730.04 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.326202E+09 | 0.150834E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.307804E+09 | 0.182794E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.296497E+09 | 0.220248E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.315348E+10 | 0.157465E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.198143E+09 | 34577842.47 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.326202E+09 | 0.257363E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.236698E+09 | 0.204548E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.218098E+09 | 0.155910E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.238928E+09 | 0.115701E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.191837E+09 | 95626165.74 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.167065E+09 | 67952987.96 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.175689E+09 | 44538249.01 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.192601E+09 | 33610876.80 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.233511E+09 | 29160781.19 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210798E+09 | 61463567.80 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.273260E+09 | 0.121919E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.258785E+09 | 0.147156E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.249311E+09 | 0.175826E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.264658E+10 | 0.125341E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.167065E+09 | 29160781.19 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.273260E+09 | 0.204548E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.236698E+09 | 0.204548E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.218098E+09 | 0.155910E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.238928E+09 | 0.115701E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.191837E+09 | 95626165.74 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.167065E+09 | 67952987.96 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.175689E+09 | 44538249.01 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.192601E+09 | 33610876.80 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.233511E+09 | 29160781.19 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210798E+09 | 61463567.80 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.273260E+09 | 0.121919E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.258785E+09 | 0.147156E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.249311E+09 | 0.175826E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.264658E+10 | 0.125341E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.167065E+09 | 29160781.19 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.273260E+09 | 0.204548E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.284637E+09 | 0.240600E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.262024E+09 | 0.183479E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.286787E+09 | 0.136660E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.229830E+09 | 0.113043E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.199726E+09 | 80474695.31 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.209254E+09 | 52935637.35 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.229336E+09 | 39966481.21 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.278198E+09 | 34790179.99 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.251747E+09 | 72933947.00 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.327225E+09 | 0.144053E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.310243E+09 | 0.173760E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.299561E+09 | 0.207152E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.316857E+10 | 0.147985E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.199726E+09 | 34790179.99 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.327225E+09 | 0.240600E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 556.77 | 549.17 | 474.14 | 330.57 | 143.57 | 0.00 | 0.00 |
February | 566.78 | 471.09 | 442.53 | 296.64 | 145.89 | 0.00 | 0.00 |
March | 557.29 | 325.10 | 397.99 | 207.41 | 190.58 | 0.00 | 0.00 |
April | 463.38 | 270.99 | 298.07 | 97.03 | 201.04 | 0.00 | 0.00 |
May | 394.63 | 179.67 | 240.83 | 27.99 | 212.83 | 0.00 | 0.00 |
June | 436.19 | 113.09 | 222.67 | 12.39 | 210.28 | 0.00 | 0.00 |
July | 467.12 | 79.29 | 225.11 | 16.79 | 208.33 | 0.00 | 0.00 |
August | 563.78 | 67.30 | 268.77 | 50.21 | 218.56 | 0.00 | 0.00 |
September | 522.41 | 155.20 | 295.58 | 109.94 | 185.64 | 0.00 | 0.00 |
October | 649.43 | 315.96 | 428.51 | 277.59 | 150.92 | 0.00 | 0.00 |
November | 627.93 | 402.83 | 461.00 | 305.91 | 155.09 | 0.00 | 0.00 |
December | 586.46 | 469.44 | 467.37 | 328.80 | 138.57 | 0.00 | 0.00 |
Annual Sum or Average | 532.62 | 282.24 | 351.49 | 171.19 | 180.30 | 0.00 | 0.00 |
Minimum of Months | 394.63 | 67.30 | 222.67 | 12.39 | 138.57 | 0.00 | 0.00 |
Maximum of Months | 649.43 | 549.17 | 474.14 | 330.57 | 218.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 273.52 | 291.91 | 237.07 | 165.29 | 71.79 | 0.00 | 0.00 |
February | 278.28 | 251.39 | 221.27 | 148.32 | 72.95 | 0.00 | 0.00 |
March | 272.98 | 173.51 | 198.99 | 103.70 | 95.29 | 0.00 | 0.00 |
April | 227.89 | 142.51 | 149.03 | 48.51 | 100.52 | 0.00 | 0.00 |
May | 195.82 | 93.15 | 120.41 | 14.00 | 106.42 | 0.00 | 0.00 |
June | 218.19 | 57.81 | 111.33 | 6.20 | 105.14 | 0.00 | 0.00 |
July | 234.21 | 40.60 | 112.56 | 8.39 | 104.16 | 0.00 | 0.00 |
August | 282.83 | 34.06 | 134.38 | 25.10 | 109.28 | 0.00 | 0.00 |
September | 260.98 | 78.64 | 147.79 | 54.97 | 92.82 | 0.00 | 0.00 |
October | 322.32 | 163.55 | 214.25 | 138.79 | 75.46 | 0.00 | 0.00 |
November | 309.59 | 211.09 | 230.50 | 152.95 | 77.54 | 0.00 | 0.00 |
December | 287.88 | 252.21 | 233.69 | 164.40 | 69.29 | 0.00 | 0.00 |
Annual Sum or Average | 263.69 | 148.65 | 175.75 | 85.59 | 90.15 | 0.00 | 0.00 |
Minimum of Months | 195.82 | 34.06 | 111.33 | 6.20 | 69.29 | 0.00 | 0.00 |
Maximum of Months | 322.32 | 291.91 | 237.07 | 165.29 | 109.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 274.19 | 281.29 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 278.77 | 244.00 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 273.25 | 170.75 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 226.95 | 143.93 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 194.32 | 96.94 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 215.40 | 63.63 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 229.66 | 46.25 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 279.03 | 40.07 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 259.24 | 84.02 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 321.50 | 164.57 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 310.14 | 207.65 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 288.87 | 242.28 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 262.58 | 148.26 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 194.32 | 40.07 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 321.50 | 281.29 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 274.98 | 277.22 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 279.62 | 240.20 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 274.15 | 168.18 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 227.32 | 142.78 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 194.44 | 96.62 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 215.32 | 63.97 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 229.49 | 46.77 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 278.89 | 40.65 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 259.23 | 84.11 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 321.82 | 163.25 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 311.00 | 204.99 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 289.83 | 238.26 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 262.98 | 146.74 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 194.44 | 40.65 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 321.82 | 277.22 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 275.93 | 273.74 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 280.87 | 236.15 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 275.70 | 164.74 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 228.33 | 140.43 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 195.05 | 95.11 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 215.81 | 62.78 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 229.94 | 45.70 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 279.31 | 39.57 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 259.63 | 82.85 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 322.55 | 160.91 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 312.30 | 201.81 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 290.96 | 234.77 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 263.83 | 144.38 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 195.05 | 39.57 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 322.55 | 273.74 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 559.20 | 526.99 | 473.17 | 329.89 | 143.28 | 0.00 | 0.00 |
February | 569.47 | 451.23 | 441.63 | 296.03 | 145.59 | 0.00 | 0.00 |
March | 559.60 | 313.47 | 397.17 | 206.98 | 190.19 | 0.00 | 0.00 |
April | 462.55 | 268.44 | 297.45 | 96.83 | 200.63 | 0.00 | 0.00 |
May | 392.99 | 181.15 | 240.33 | 27.93 | 212.40 | 0.00 | 0.00 |
June | 432.71 | 117.76 | 222.21 | 12.37 | 209.85 | 0.00 | 0.00 |
July | 460.91 | 84.85 | 224.65 | 16.75 | 207.90 | 0.00 | 0.00 |
August | 559.50 | 72.52 | 268.22 | 50.10 | 218.11 | 0.00 | 0.00 |
September | 520.76 | 158.34 | 294.97 | 109.71 | 185.26 | 0.00 | 0.00 |
October | 649.34 | 310.44 | 427.63 | 277.02 | 150.61 | 0.00 | 0.00 |
November | 631.34 | 388.80 | 460.05 | 305.28 | 154.77 | 0.00 | 0.00 |
December | 589.13 | 452.17 | 466.41 | 328.13 | 138.29 | 0.00 | 0.00 |
Annual Sum or Average | 532.21 | 276.23 | 350.77 | 170.84 | 179.93 | 0.00 | 0.00 |
Minimum of Months | 392.99 | 72.52 | 222.21 | 12.37 | 138.29 | 0.00 | 0.00 |
Maximum of Months | 649.34 | 526.99 | 473.17 | 329.89 | 218.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 278.38 | 264.64 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 283.83 | 226.08 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 279.31 | 156.08 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 231.06 | 133.59 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 196.58 | 89.83 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 216.99 | 57.83 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 231.23 | 41.34 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 280.42 | 35.01 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 260.46 | 78.16 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 324.16 | 154.66 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 315.11 | 194.10 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 293.56 | 226.42 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 265.89 | 137.67 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 196.58 | 35.01 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 324.16 | 264.64 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 278.68 | 263.61 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 284.29 | 224.77 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 280.02 | 154.63 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 231.65 | 132.46 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 196.93 | 89.22 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 217.22 | 57.49 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 231.44 | 41.04 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 280.61 | 34.73 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 260.63 | 77.80 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 324.48 | 153.82 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 315.63 | 192.97 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 293.93 | 225.35 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 266.25 | 136.85 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 196.93 | 34.73 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 324.48 | 263.61 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 279.69 | 259.46 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 285.49 | 220.49 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 281.71 | 150.63 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 233.20 | 129.11 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 197.74 | 87.48 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 217.41 | 56.89 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 231.47 | 40.72 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 280.55 | 34.56 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 260.75 | 77.22 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 325.20 | 151.66 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 316.86 | 190.00 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 294.97 | 221.85 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 267.04 | 134.54 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 197.74 | 34.56 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 325.20 | 259.46 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 283.02 | 242.57 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 288.62 | 204.74 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 285.48 | 137.42 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 236.69 | 117.40 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 199.32 | 80.79 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 216.29 | 54.79 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 229.44 | 40.02 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 278.23 | 34.76 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 259.78 | 75.56 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 326.22 | 144.82 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 319.37 | 180.58 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 298.01 | 208.63 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 268.32 | 126.42 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 199.32 | 34.76 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 326.22 | 242.57 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.149125E+10 | 0.147089E+10 | 0.126994E+10 | 0.885401E+09 | 0.384543E+09 | 0.00 | 0.00 |
February | 0.137115E+10 | 0.113965E+10 | 0.107058E+10 | 0.717638E+09 | 0.352940E+09 | 0.00 | 0.00 |
March | 0.149265E+10 | 0.870747E+09 | 0.106597E+10 | 0.555521E+09 | 0.510449E+09 | 0.00 | 0.00 |
April | 0.120108E+10 | 0.702415E+09 | 0.772587E+09 | 0.251494E+09 | 0.521094E+09 | 0.00 | 0.00 |
May | 0.105696E+10 | 0.481227E+09 | 0.645026E+09 | 74969553.42 | 0.570057E+09 | 0.00 | 0.00 |
June | 0.113061E+10 | 0.293138E+09 | 0.577156E+09 | 32116473.97 | 0.545040E+09 | 0.00 | 0.00 |
July | 0.125113E+10 | 0.212376E+09 | 0.602944E+09 | 44958910.78 | 0.557985E+09 | 0.00 | 0.00 |
August | 0.151002E+10 | 0.180266E+09 | 0.719872E+09 | 0.134475E+09 | 0.585397E+09 | 0.00 | 0.00 |
September | 0.135410E+10 | 0.402272E+09 | 0.766144E+09 | 0.284966E+09 | 0.481178E+09 | 0.00 | 0.00 |
October | 0.173944E+10 | 0.846273E+09 | 0.114771E+10 | 0.743490E+09 | 0.404223E+09 | 0.00 | 0.00 |
November | 0.162759E+10 | 0.104414E+10 | 0.119490E+10 | 0.792917E+09 | 0.401985E+09 | 0.00 | 0.00 |
December | 0.157077E+10 | 0.125735E+10 | 0.125181E+10 | 0.880660E+09 | 0.371153E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.167968E+11 | 0.890074E+10 | 0.110846E+11 | 0.539860E+10 | 0.568604E+10 | 0.00 | 0.00 |
Minimum of Months | 0.105696E+10 | 0.180266E+09 | 0.577156E+09 | 32116473.97 | 0.352940E+09 | 0.00 | 0.00 |
Maximum of Months | 0.173944E+10 | 0.147089E+10 | 0.126994E+10 | 0.885401E+09 | 0.585397E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.732607E+09 | 0.781851E+09 | 0.634972E+09 | 0.442700E+09 | 0.192272E+09 | 0.00 | 0.00 |
February | 0.673225E+09 | 0.608163E+09 | 0.535289E+09 | 0.358819E+09 | 0.176470E+09 | 0.00 | 0.00 |
March | 0.731152E+09 | 0.464728E+09 | 0.532985E+09 | 0.277760E+09 | 0.255225E+09 | 0.00 | 0.00 |
April | 0.590680E+09 | 0.369389E+09 | 0.386294E+09 | 0.125747E+09 | 0.260547E+09 | 0.00 | 0.00 |
May | 0.524485E+09 | 0.249485E+09 | 0.322513E+09 | 37484776.71 | 0.285028E+09 | 0.00 | 0.00 |
June | 0.565548E+09 | 0.149836E+09 | 0.288578E+09 | 16058236.99 | 0.272520E+09 | 0.00 | 0.00 |
July | 0.627304E+09 | 0.108739E+09 | 0.301472E+09 | 22479455.39 | 0.278992E+09 | 0.00 | 0.00 |
August | 0.757527E+09 | 91232929.52 | 0.359936E+09 | 67237285.33 | 0.292699E+09 | 0.00 | 0.00 |
September | 0.676471E+09 | 0.203836E+09 | 0.383072E+09 | 0.142483E+09 | 0.240589E+09 | 0.00 | 0.00 |
October | 0.863293E+09 | 0.438040E+09 | 0.573857E+09 | 0.371745E+09 | 0.202112E+09 | 0.00 | 0.00 |
November | 0.802465E+09 | 0.547150E+09 | 0.597451E+09 | 0.396458E+09 | 0.200992E+09 | 0.00 | 0.00 |
December | 0.771053E+09 | 0.675516E+09 | 0.625907E+09 | 0.440330E+09 | 0.185577E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.831581E+10 | 0.468797E+10 | 0.554232E+10 | 0.269930E+10 | 0.284302E+10 | 0.00 | 0.00 |
Minimum of Months | 0.524485E+09 | 91232929.52 | 0.288578E+09 | 16058236.99 | 0.176470E+09 | 0.00 | 0.00 |
Maximum of Months | 0.863293E+09 | 0.781851E+09 | 0.634972E+09 | 0.442700E+09 | 0.292699E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.734385E+09 | 0.753417E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.674389E+09 | 0.590291E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.731870E+09 | 0.457331E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.588253E+09 | 0.373066E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.520468E+09 | 0.259644E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.558318E+09 | 0.164932E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.615127E+09 | 0.123865E+09 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.747358E+09 | 0.107329E+09 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.671951E+09 | 0.217772E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.861112E+09 | 0.440780E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.803883E+09 | 0.538238E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.773704E+09 | 0.648924E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.828082E+10 | 0.467559E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.520468E+09 | 0.107329E+09 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.861112E+09 | 0.753417E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.736494E+09 | 0.742510E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.676455E+09 | 0.581096E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.734293E+09 | 0.450441E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.589220E+09 | 0.370076E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.520779E+09 | 0.258777E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.558119E+09 | 0.165807E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.614670E+09 | 0.125282E+09 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.746989E+09 | 0.108886E+09 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.671935E+09 | 0.218004E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.861953E+09 | 0.437247E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.806122E+09 | 0.531329E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.776268E+09 | 0.638144E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.829330E+10 | 0.462760E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.520779E+09 | 0.108886E+09 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.861953E+09 | 0.742510E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.739048E+09 | 0.733192E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.679488E+09 | 0.571289E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.738427E+09 | 0.441242E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.591842E+09 | 0.364006E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.522415E+09 | 0.254751E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.559371E+09 | 0.162726E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.615884E+09 | 0.122394E+09 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.748114E+09 | 0.105982E+09 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.672955E+09 | 0.214757E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.863917E+09 | 0.430994E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.809469E+09 | 0.523103E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.779307E+09 | 0.628820E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.832024E+10 | 0.455326E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.522415E+09 | 0.105982E+09 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.863917E+09 | 0.733192E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.149775E+10 | 0.141149E+10 | 0.126734E+10 | 0.883584E+09 | 0.383754E+09 | 0.00 | 0.00 |
February | 0.137765E+10 | 0.109161E+10 | 0.106838E+10 | 0.716166E+09 | 0.352216E+09 | 0.00 | 0.00 |
March | 0.149884E+10 | 0.839585E+09 | 0.106378E+10 | 0.554381E+09 | 0.509402E+09 | 0.00 | 0.00 |
April | 0.119892E+10 | 0.695806E+09 | 0.771002E+09 | 0.250978E+09 | 0.520025E+09 | 0.00 | 0.00 |
May | 0.105258E+10 | 0.485192E+09 | 0.643703E+09 | 74815755.05 | 0.568887E+09 | 0.00 | 0.00 |
June | 0.112160E+10 | 0.305223E+09 | 0.575972E+09 | 32050587.74 | 0.543922E+09 | 0.00 | 0.00 |
July | 0.123451E+10 | 0.227270E+09 | 0.601707E+09 | 44866678.58 | 0.556840E+09 | 0.00 | 0.00 |
August | 0.149856E+10 | 0.194231E+09 | 0.718395E+09 | 0.134199E+09 | 0.584196E+09 | 0.00 | 0.00 |
September | 0.134982E+10 | 0.410407E+09 | 0.764572E+09 | 0.284381E+09 | 0.480191E+09 | 0.00 | 0.00 |
October | 0.173918E+10 | 0.831491E+09 | 0.114536E+10 | 0.741965E+09 | 0.403394E+09 | 0.00 | 0.00 |
November | 0.163643E+10 | 0.100777E+10 | 0.119245E+10 | 0.791290E+09 | 0.401160E+09 | 0.00 | 0.00 |
December | 0.157792E+10 | 0.121111E+10 | 0.124925E+10 | 0.878853E+09 | 0.370392E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.167838E+11 | 0.871119E+10 | 0.110619E+11 | 0.538753E+10 | 0.567438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.105258E+10 | 0.194231E+09 | 0.575972E+09 | 32050587.74 | 0.352216E+09 | 0.00 | 0.00 |
Maximum of Months | 0.173918E+10 | 0.141149E+10 | 0.126734E+10 | 0.883584E+09 | 0.584196E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.745617E+09 | 0.708814E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.686650E+09 | 0.546937E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.748113E+09 | 0.418037E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.598895E+09 | 0.346264E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.526523E+09 | 0.240602E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.562433E+09 | 0.149905E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.619325E+09 | 0.110725E+09 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.751087E+09 | 93773330.32 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.675115E+09 | 0.202603E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.868227E+09 | 0.414253E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.816776E+09 | 0.503105E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.786280E+09 | 0.606451E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.838504E+10 | 0.434147E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.526523E+09 | 93773330.32 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.868227E+09 | 0.708814E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.746429E+09 | 0.706040E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.687750E+09 | 0.543761E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.750011E+09 | 0.414153E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.600432E+09 | 0.343332E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.527451E+09 | 0.238974E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.563025E+09 | 0.149009E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.619898E+09 | 0.109921E+09 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.751597E+09 | 93010633.65 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.675552E+09 | 0.201667E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.869089E+09 | 0.411988E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.818114E+09 | 0.500178E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.787266E+09 | 0.603591E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.839661E+10 | 0.431562E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.527451E+09 | 93010633.65 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.869089E+09 | 0.706040E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.749131E+09 | 0.694935E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.690664E+09 | 0.533412E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.754544E+09 | 0.403455E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.604442E+09 | 0.334651E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.529623E+09 | 0.234312E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.563524E+09 | 0.147463E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.619960E+09 | 0.109060E+09 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.751427E+09 | 92554946.58 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.675857E+09 | 0.200147E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.871006E+09 | 0.406217E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.821302E+09 | 0.492483E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.790049E+09 | 0.594207E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.842153E+10 | 0.424290E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.529623E+09 | 92554946.58 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.871006E+09 | 0.694935E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.758030E+09 | 0.649695E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.698218E+09 | 0.495296E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.764641E+09 | 0.368060E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.613503E+09 | 0.304294E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.533856E+09 | 0.216380E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.560632E+09 | 0.142012E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.614537E+09 | 0.107188E+09 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.745219E+09 | 93110502.14 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.673343E+09 | 0.195860E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.873744E+09 | 0.387891E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.827811E+09 | 0.468072E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.798180E+09 | 0.558800E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.846171E+10 | 0.398666E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.533856E+09 | 93110502.14 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.873744E+09 | 0.649695E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.345847E+09 | -222159611.4 | 0.00 | 0.00 | 744.00 | 0.00 | -123686915.8 | 58.99 | 0.00 | 0.00 |
February | 0.311554E+09 | -202136034.2 | 0.00 | 0.00 | 672.00 | 0.00 | -109418142.2 | 58.99 | 0.00 | 0.00 |
March | 0.336977E+09 | -219835470.7 | 0.00 | 0.00 | 744.00 | 0.00 | -117141552.9 | 58.99 | 0.00 | 0.00 |
April | 0.307670E+09 | -196552552.9 | 0.00 | 0.00 | 720.00 | 0.00 | -111117588.8 | 58.99 | 0.00 | 0.00 |
May | 0.300022E+09 | -186949343.4 | 0.00 | 0.00 | 744.00 | 0.00 | -113072897.5 | 58.99 | 0.00 | 0.00 |
June | 0.276865E+09 | -168315669.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108549146.9 | 58.99 | 0.00 | 0.00 |
July | 0.273352E+09 | -161582778.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111769278.9 | 58.99 | 0.00 | 0.00 |
August | 0.275934E+09 | -164393916.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111539917.3 | 58.99 | 0.00 | 0.00 |
September | 0.273383E+09 | -164887485.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108495186.3 | 58.99 | 0.00 | 0.00 |
October | 0.296916E+09 | -182730757.4 | 0.00 | 0.00 | 744.00 | 0.00 | -114185006.5 | 58.99 | 0.00 | 0.00 |
November | 0.305223E+09 | -192113591.4 | 0.00 | 0.00 | 720.00 | 0.00 | -113109868.6 | 58.99 | 0.00 | 0.00 |
December | 0.335675E+09 | -213743459.7 | 0.00 | 0.00 | 744.00 | 0.00 | -121931892.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.363942E+10 | -0.227540E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.136402E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.273352E+09 | -222159611.4 | 0.00 | 0.00 | 672.00 | 0.00 | -123686915.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.345847E+09 | -161582778.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108495186.3 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.343471E+09 | -222155614.5 | 0.00 | 0.00 | 744.00 | 0.00 | -121315193.7 | 58.99 | 0.00 | 0.00 |
February | 0.309517E+09 | -202137551.8 | 0.00 | 0.00 | 672.00 | 0.00 | -107378954.6 | 58.99 | 0.00 | 0.00 |
March | 0.335035E+09 | -219834383.9 | 0.00 | 0.00 | 744.00 | 0.00 | -115200285.2 | 58.99 | 0.00 | 0.00 |
April | 0.306568E+09 | -196557022.8 | 0.00 | 0.00 | 720.00 | 0.00 | -110011001.1 | 58.99 | 0.00 | 0.00 |
May | 0.299540E+09 | -186947657.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112592355.6 | 58.99 | 0.00 | 0.00 |
June | 0.276649E+09 | -168313604.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108335303.6 | 58.99 | 0.00 | 0.00 |
July | 0.273150E+09 | -161574132.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111575891.4 | 58.99 | 0.00 | 0.00 |
August | 0.275792E+09 | -164389963.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111402493.8 | 58.99 | 0.00 | 0.00 |
September | 0.273208E+09 | -164888064.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108320381.8 | 58.99 | 0.00 | 0.00 |
October | 0.295962E+09 | -182724614.5 | 0.00 | 0.00 | 744.00 | 0.00 | -113237150.9 | 58.99 | 0.00 | 0.00 |
November | 0.303551E+09 | -192110420.0 | 0.00 | 0.00 | 720.00 | 0.00 | -111440122.5 | 58.99 | 0.00 | 0.00 |
December | 0.332746E+09 | -213742554.4 | 0.00 | 0.00 | 744.00 | 0.00 | -119003708.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.362519E+10 | -0.227538E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.134981E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.273150E+09 | -222155614.5 | 0.00 | 0.00 | 672.00 | 0.00 | -121315193.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.343471E+09 | -161574132.3 | 0.00 | 0.00 | 744.00 | 0.00 | -107378954.6 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.318555E+09 | -195354187.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123200983.1 | 58.99 | 0.00 | 0.00 |
February | 0.286468E+09 | -177899157.3 | 0.00 | 0.00 | 672.00 | 0.00 | -108569133.1 | 58.99 | 0.00 | 0.00 |
March | 0.311873E+09 | -196189251.2 | 0.00 | 0.00 | 744.00 | 0.00 | -115683983.0 | 58.99 | 0.00 | 0.00 |
April | 0.282359E+09 | -172900938.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109458249.9 | 58.98 | 0.00 | 0.00 |
May | 0.277253E+09 | -165862745.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111389796.0 | 58.98 | 0.00 | 0.00 |
June | 0.256464E+09 | -149901616.4 | 0.00 | 0.00 | 720.00 | 0.00 | -106562430.7 | 58.99 | 0.00 | 0.00 |
July | 0.250692E+09 | -141281589.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109410361.5 | 58.98 | 0.00 | 0.00 |
August | 0.256195E+09 | -146826242.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109368532.5 | 58.99 | 0.00 | 0.00 |
September | 0.251779E+09 | -144941442.3 | 0.00 | 0.00 | 720.00 | 0.00 | -106837850.5 | 58.99 | 0.00 | 0.00 |
October | 0.273543E+09 | -160707583.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112835802.7 | 59.00 | 0.00 | 0.00 |
November | 0.281660E+09 | -169609244.8 | 0.00 | 0.00 | 720.00 | 0.00 | -112050278.8 | 58.99 | 0.00 | 0.00 |
December | 0.307515E+09 | -186566582.7 | 0.00 | 0.00 | 744.00 | 0.00 | -120948771.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.335436E+10 | -0.200804E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.134632E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.250692E+09 | -196189251.2 | 0.00 | 0.00 | 672.00 | 0.00 | -123200983.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.318555E+09 | -141281589.1 | 0.00 | 0.00 | 744.00 | 0.00 | -106562430.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.319048E+09 | -195341985.5 | 0.00 | 0.00 | 744.00 | 0.00 | -123705794.5 | 59.00 | 0.00 | 0.00 |
February | 0.286911E+09 | -177904415.8 | 0.00 | 0.00 | 672.00 | 0.00 | -109006771.7 | 58.99 | 0.00 | 0.00 |
March | 0.312270E+09 | -196194239.6 | 0.00 | 0.00 | 744.00 | 0.00 | -116075878.3 | 58.99 | 0.00 | 0.00 |
April | 0.282523E+09 | -172890647.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109632304.1 | 58.98 | 0.00 | 0.00 |
May | 0.277291E+09 | -165854732.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111436722.8 | 58.98 | 0.00 | 0.00 |
June | 0.256418E+09 | -149895237.0 | 0.00 | 0.00 | 720.00 | 0.00 | -106522786.7 | 58.99 | 0.00 | 0.00 |
July | 0.250607E+09 | -141246999.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109359768.3 | 58.99 | 0.00 | 0.00 |
August | 0.256105E+09 | -146819644.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109285487.6 | 59.00 | 0.00 | 0.00 |
September | 0.251762E+09 | -144930640.1 | 0.00 | 0.00 | 720.00 | 0.00 | -106831561.3 | 58.99 | 0.00 | 0.00 |
October | 0.273726E+09 | -160718024.2 | 0.00 | 0.00 | 744.00 | 0.00 | -113008072.8 | 58.99 | 0.00 | 0.00 |
November | 0.282034E+09 | -169625722.9 | 0.00 | 0.00 | 720.00 | 0.00 | -112408298.0 | 58.99 | 0.00 | 0.00 |
December | 0.308058E+09 | -186564228.0 | 0.00 | 0.00 | 744.00 | 0.00 | -121493749.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.335675E+10 | -0.200799E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.134877E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.250607E+09 | -196194239.6 | 0.00 | 0.00 | 672.00 | 0.00 | -123705794.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.319048E+09 | -141246999.1 | 0.00 | 0.00 | 744.00 | 0.00 | -106522786.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.310058E+09 | -184644410.1 | 0.00 | 0.00 | 744.00 | 0.00 | -125413714.7 | 58.99 | 0.00 | 0.00 |
February | 0.279077E+09 | -168240990.5 | 0.00 | 0.00 | 672.00 | 0.00 | -110835656.8 | 58.99 | 0.00 | 0.00 |
March | 0.303626E+09 | -185656905.0 | 0.00 | 0.00 | 744.00 | 0.00 | -117969174.5 | 58.98 | 0.00 | 0.00 |
April | 0.274618E+09 | -163588914.9 | 0.00 | 0.00 | 720.00 | 0.00 | -111028677.6 | 58.99 | 0.00 | 0.00 |
May | 0.269268E+09 | -156833191.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112434913.6 | 58.99 | 0.00 | 0.00 |
June | 0.249207E+09 | -141813919.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107393157.6 | 58.99 | 0.00 | 0.00 |
July | 0.243751E+09 | -133598423.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110152084.4 | 58.99 | 0.00 | 0.00 |
August | 0.249016E+09 | -138935390.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110080412.2 | 58.99 | 0.00 | 0.00 |
September | 0.244720E+09 | -137165571.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107554093.4 | 58.99 | 0.00 | 0.00 |
October | 0.266131E+09 | -151907600.3 | 0.00 | 0.00 | 744.00 | 0.00 | -114223518.7 | 58.99 | 0.00 | 0.00 |
November | 0.274249E+09 | -160209700.7 | 0.00 | 0.00 | 720.00 | 0.00 | -114039258.3 | 58.99 | 0.00 | 0.00 |
December | 0.299610E+09 | -176440844.9 | 0.00 | 0.00 | 744.00 | 0.00 | -123169553.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.326333E+10 | -0.189904E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.136429E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.243751E+09 | -185656905.0 | 0.00 | 0.00 | 672.00 | 0.00 | -125413714.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.310058E+09 | -133598423.8 | 0.00 | 0.00 | 744.00 | 0.00 | -107393157.6 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.310044E+09 | -184643302.3 | 0.00 | 0.00 | 744.00 | 0.00 | -125400940.6 | 58.99 | 0.00 | 0.00 |
February | 0.279128E+09 | -168242326.4 | 0.00 | 0.00 | 672.00 | 0.00 | -110885864.3 | 58.99 | 0.00 | 0.00 |
March | 0.303764E+09 | -185654538.6 | 0.00 | 0.00 | 744.00 | 0.00 | -118109033.6 | 58.98 | 0.00 | 0.00 |
April | 0.274729E+09 | -163580906.3 | 0.00 | 0.00 | 720.00 | 0.00 | -111147634.4 | 59.00 | 0.00 | 0.00 |
May | 0.269356E+09 | -156831477.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112524873.2 | 58.99 | 0.00 | 0.00 |
June | 0.249334E+09 | -141804286.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107529990.3 | 59.00 | 0.00 | 0.00 |
July | 0.243879E+09 | -133576377.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110302205.3 | 58.99 | 0.00 | 0.00 |
August | 0.249174E+09 | -138944386.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110229678.4 | 58.99 | 0.00 | 0.00 |
September | 0.244826E+09 | -137194229.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107631675.5 | 58.98 | 0.00 | 0.00 |
October | 0.266220E+09 | -151911922.5 | 0.00 | 0.00 | 744.00 | 0.00 | -114308280.3 | 58.99 | 0.00 | 0.00 |
November | 0.274342E+09 | -160199972.5 | 0.00 | 0.00 | 720.00 | 0.00 | -114142105.5 | 58.99 | 0.00 | 0.00 |
December | 0.299655E+09 | -176433170.0 | 0.00 | 0.00 | 744.00 | 0.00 | -123221854.0 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.326445E+10 | -0.189902E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.136543E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.243879E+09 | -185654538.6 | 0.00 | 0.00 | 672.00 | 0.00 | -125400940.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.310044E+09 | -133576377.8 | 0.00 | 0.00 | 744.00 | 0.00 | -107529990.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.310168E+09 | -184644823.7 | 0.00 | 0.00 | 744.00 | 0.00 | -125523445.4 | 58.99 | 0.00 | 0.00 |
February | 0.279282E+09 | -168236203.9 | 0.00 | 0.00 | 672.00 | 0.00 | -111045636.4 | 58.99 | 0.00 | 0.00 |
March | 0.304016E+09 | -185611752.9 | 0.00 | 0.00 | 744.00 | 0.00 | -118404323.1 | 59.00 | 0.00 | 0.00 |
April | 0.274887E+09 | -163595780.9 | 0.00 | 0.00 | 720.00 | 0.00 | -111291582.8 | 58.99 | 0.00 | 0.00 |
May | 0.269451E+09 | -156840506.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112610532.3 | 58.99 | 0.00 | 0.00 |
June | 0.249377E+09 | -141816420.3 | 0.00 | 0.00 | 720.00 | 0.00 | -107560594.7 | 58.99 | 0.00 | 0.00 |
July | 0.243936E+09 | -133600466.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110335665.4 | 58.99 | 0.00 | 0.00 |
August | 0.249210E+09 | -138934029.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110276008.3 | 58.99 | 0.00 | 0.00 |
September | 0.244875E+09 | -137169295.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107705232.1 | 58.99 | 0.00 | 0.00 |
October | 0.266343E+09 | -151905505.0 | 0.00 | 0.00 | 744.00 | 0.00 | -114437755.5 | 58.99 | 0.00 | 0.00 |
November | 0.274512E+09 | -160201538.3 | 0.00 | 0.00 | 720.00 | 0.00 | -114310306.6 | 58.99 | 0.00 | 0.00 |
December | 0.299788E+09 | -176435749.2 | 0.00 | 0.00 | 744.00 | 0.00 | -123352606.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.326585E+10 | -0.189899E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.136685E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.243936E+09 | -185611752.9 | 0.00 | 0.00 | 672.00 | 0.00 | -125523445.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.310168E+09 | -133600466.2 | 0.00 | 0.00 | 744.00 | 0.00 | -107560594.7 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 290.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 369.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 407.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 411.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 411.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 390.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 293.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 285.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4071.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 411.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.112934E+11 | 61206.57 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.641934E+10 | 61206.57 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.701349E+09 | 61206.57 | 18-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108721E+09 | 61206.57 | 06-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 41047069.53 | 11369.30 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.833643E+09 | 61206.57 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.433670E+10 | 61206.57 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.112934E+11 | 61206.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.327507E+10 | 32029.35 | 04-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184119E+10 | 32029.35 | 03-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118722E+09 | 7107.51 | 23-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8376944.87 | 3909.59 | 06-APR-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1237211.51 | 775.41 | 26-OCT-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114902E+09 | 31071.29 | 22-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.840233E+09 | 32029.35 | 02-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.619972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.327507E+10 | 32029.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.431252E+10 | 31596.82 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.237453E+10 | 31596.82 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207121E+09 | 5267.72 | 19-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23162493.88 | 6246.79 | 06-APR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10174886.70 | 4108.30 | 26-OCT-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.244866E+09 | 21009.58 | 22-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147120E+10 | 31596.82 | 03-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.864358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.431252E+10 | 31596.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.455364E+10 | 31415.58 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249723E+10 | 31415.58 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.242993E+09 | 9013.74 | 19-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 26446451.43 | 5444.28 | 07-APR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14896428.82 | 5507.61 | 26-OCT-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.288585E+09 | 23930.51 | 22-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164894E+10 | 31415.58 | 03-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.927273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.455364E+10 | 31415.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.491612E+10 | 31408.75 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.270782E+10 | 31408.75 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.309211E+09 | 13218.16 | 19-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35688188.38 | 6342.44 | 06-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24529661.49 | 5828.79 | 26-OCT-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.362645E+09 | 27282.14 | 22-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191021E+10 | 31408.75 | 03-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.491612E+10 | 31408.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.991206E+10 | 57470.83 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.547401E+10 | 57470.83 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.751235E+09 | 57470.83 | 18-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 74821067.53 | 51750.58 | 07-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101144E+09 | 15742.26 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.944369E+09 | 57470.83 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.419822E+10 | 57470.83 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.991206E+10 | 57470.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.517492E+10 | 29081.61 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.286854E+10 | 29081.61 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.401558E+09 | 29081.61 | 18-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40287025.46 | 28153.15 | 07-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 55033969.73 | 9350.93 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.491652E+09 | 29081.61 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219851E+10 | 29081.61 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.517492E+10 | 29081.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.526190E+10 | 28971.81 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.292966E+10 | 28971.81 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.435089E+09 | 28971.81 | 18-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 45666688.10 | 28971.81 | 06-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 65044486.68 | 11964.20 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.519782E+09 | 28971.81 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227697E+10 | 28971.81 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.526190E+10 | 28971.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.562702E+10 | 28881.15 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317171E+10 | 28881.15 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.555952E+09 | 28881.15 | 18-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 68842789.35 | 28881.15 | 06-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 94278150.10 | 20142.75 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.609676E+09 | 28881.15 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.254912E+10 | 28881.15 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.562702E+10 | 28881.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.712075E+10 | 32354.90 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.423995E+10 | 32354.90 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101578E+10 | 32354.90 | 03-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.200882E+09 | 32354.90 | 06-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 718106.54 | 662.99 | 11-MAY-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.188645E+09 | 32354.90 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.902372E+09 | 32354.90 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.341830E+10 | 32354.90 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.712075E+10 | 32354.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.588003E+09 | 0.587408E+09 | 9301.89 | 26-FEB-15:10 | 9301.89 | 0.00 |
March | 0.00 | 0.00 | 0.247140E+10 | 0.198814E+10 | 16606.73 | 30-MAR-14:00 | 13702.25 | 0.00 |
April | 0.00 | 0.00 | 0.745557E+10 | 0.611345E+10 | 15575.01 | 23-APR-17:00 | 11086.49 | 0.00 |
May | 0.00 | 0.00 | 0.167097E+11 | 0.123633E+11 | 29225.56 | 31-MAY-07:03 | 13791.67 | 0.00 |
June | 0.00 | 0.00 | 0.289943E+11 | 0.204364E+11 | 54000.16 | 23-JUN-07:03 | 31469.96 | 0.00 |
July | 0.00 | 0.00 | 0.357032E+11 | 0.234968E+11 | 54744.59 | 27-JUL-07:02 | 29860.59 | 0.00 |
August | 0.00 | 0.00 | 0.388736E+11 | 0.248796E+11 | 54898.65 | 20-AUG-07:01 | 30565.31 | 0.00 |
September | 0.00 | 0.00 | 0.236323E+11 | 0.158714E+11 | 54482.29 | 17-SEP-07:02 | 30835.62 | 0.00 |
October | 0.00 | 0.00 | 0.873691E+10 | 0.615115E+10 | 53444.82 | 19-OCT-07:02 | 23051.86 | 0.00 |
November | 0.00 | 0.00 | 0.176259E+10 | 0.127724E+10 | 15809.01 | 05-NOV-16:07 | 11605.91 | 0.00 |
December | 0.00 | 0.00 | 0.160611E+09 | 0.113326E+09 | 8386.43 | 12-DEC-14:10 | 5915.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.165088E+12 | 0.113278E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.388736E+11 | 0.248796E+11 | 54898.65 | 31469.96 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 5621128.85 | 4873262.75 | 1151.14 | 31-JAN-23:10 | 967.19 | 0.00 |
February | 0.00 | 0.00 | 0.521118E+09 | 0.513416E+09 | 25603.56 | 19-FEB-18:08 | 18294.82 | 0.00 |
March | 0.00 | 0.00 | 0.187695E+10 | 0.153824E+10 | 25736.90 | 04-MAR-19:36 | 19675.03 | 0.00 |
April | 0.00 | 0.00 | 0.528308E+10 | 0.435976E+10 | 26850.43 | 22-APR-18:02 | 14841.70 | 0.00 |
May | 0.00 | 0.00 | 0.997748E+10 | 0.758598E+10 | 26945.93 | 24-MAY-20:02 | 14239.75 | 0.00 |
June | 0.00 | 0.00 | 0.152450E+11 | 0.111304E+11 | 27238.13 | 27-JUN-07:02 | 20286.09 | 0.00 |
July | 0.00 | 0.00 | 0.182154E+11 | 0.123755E+11 | 27651.91 | 27-JUL-07:02 | 19249.11 | 0.00 |
August | 0.00 | 0.00 | 0.194594E+11 | 0.129202E+11 | 27777.78 | 20-AUG-07:01 | 19187.00 | 0.00 |
September | 0.00 | 0.00 | 0.126578E+11 | 0.883263E+10 | 27582.85 | 17-SEP-07:02 | 19342.84 | 0.00 |
October | 0.00 | 0.00 | 0.521530E+10 | 0.382017E+10 | 27666.32 | 19-OCT-07:02 | 13086.48 | 0.00 |
November | 0.00 | 0.00 | 0.138068E+10 | 0.101419E+10 | 26610.65 | 04-NOV-18:02 | 15237.80 | 0.00 |
December | 0.00 | 0.00 | 0.175904E+09 | 0.123676E+09 | 25653.25 | 12-DEC-21:08 | 17410.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.900137E+11 | 0.642190E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 5621128.85 | 4873262.75 | 1151.14 | 967.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.194594E+11 | 0.129202E+11 | 27777.78 | 20286.09 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 118138.76 | 107366.31 | 141.15 | 31-JAN-15:00 | 128.67 | 0.00 |
February | 0.00 | 0.00 | 0.306594E+09 | 0.306465E+09 | 5056.45 | 28-FEB-15:10 | 5056.45 | 0.00 |
March | 0.00 | 0.00 | 0.112339E+10 | 0.908183E+09 | 8810.80 | 30-MAR-14:00 | 7362.21 | 0.00 |
April | 0.00 | 0.00 | 0.333020E+10 | 0.279955E+10 | 8114.37 | 17-APR-14:00 | 7632.90 | 0.00 |
May | 0.00 | 0.00 | 0.692075E+10 | 0.518947E+10 | 26646.68 | 31-MAY-06:03 | 12789.72 | 0.00 |
June | 0.00 | 0.00 | 0.118725E+11 | 0.841940E+10 | 28272.44 | 23-JUN-06:02 | 16859.71 | 0.00 |
July | 0.00 | 0.00 | 0.142260E+11 | 0.937004E+10 | 28817.36 | 27-JUL-06:02 | 15356.64 | 0.00 |
August | 0.00 | 0.00 | 0.156637E+11 | 0.100930E+11 | 29236.75 | 21-AUG-06:02 | 14445.46 | 0.00 |
September | 0.00 | 0.00 | 0.940103E+10 | 0.639594E+10 | 29158.95 | 17-SEP-07:02 | 14141.18 | 0.00 |
October | 0.00 | 0.00 | 0.351520E+10 | 0.251875E+10 | 28175.65 | 19-OCT-06:02 | 11659.44 | 0.00 |
November | 0.00 | 0.00 | 0.744404E+09 | 0.563339E+09 | 7643.52 | 05-NOV-14:00 | 5194.97 | 0.00 |
December | 0.00 | 0.00 | 92830444.39 | 65114796.56 | 4707.56 | 12-DEC-14:00 | 3304.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.671968E+11 | 0.466294E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 118138.76 | 107366.31 | 141.15 | 128.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.156637E+11 | 0.100930E+11 | 29236.75 | 16859.71 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.15 | 0.13 | 0.00 | 31-JAN-16:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.281938E+09 | 0.281867E+09 | 4913.93 | 28-FEB-15:10 | 4913.93 | 0.00 |
March | 0.00 | 0.00 | 0.107207E+10 | 0.866084E+09 | 8724.20 | 30-MAR-14:00 | 7284.73 | 0.00 |
April | 0.00 | 0.00 | 0.327125E+10 | 0.274992E+10 | 8095.11 | 17-APR-14:00 | 7614.77 | 0.00 |
May | 0.00 | 0.00 | 0.687765E+10 | 0.515674E+10 | 26582.71 | 31-MAY-06:03 | 12756.04 | 0.00 |
June | 0.00 | 0.00 | 0.118954E+11 | 0.843794E+10 | 28327.58 | 23-JUN-06:02 | 16915.86 | 0.00 |
July | 0.00 | 0.00 | 0.142745E+11 | 0.940956E+10 | 28872.42 | 27-JUL-06:02 | 15402.01 | 0.00 |
August | 0.00 | 0.00 | 0.157145E+11 | 0.101328E+11 | 29298.17 | 21-AUG-06:02 | 14547.20 | 0.00 |
September | 0.00 | 0.00 | 0.939911E+10 | 0.639550E+10 | 29210.85 | 17-SEP-07:02 | 14160.67 | 0.00 |
October | 0.00 | 0.00 | 0.347065E+10 | 0.248369E+10 | 28226.07 | 19-OCT-06:02 | 11674.19 | 0.00 |
November | 0.00 | 0.00 | 0.664965E+09 | 0.502454E+09 | 7521.47 | 05-NOV-14:00 | 5102.55 | 0.00 |
December | 0.00 | 0.00 | 73505839.28 | 51762830.84 | 4337.05 | 12-DEC-14:00 | 3040.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.669956E+11 | 0.464683E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.15 | 0.13 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.157145E+11 | 0.101328E+11 | 29298.17 | 16915.86 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.244300E+09 | 0.244273E+09 | 4609.96 | 28-FEB-15:10 | 4609.96 | 0.00 |
March | 0.00 | 0.00 | 0.967002E+09 | 0.781002E+09 | 8455.52 | 30-MAR-14:00 | 7040.28 | 0.00 |
April | 0.00 | 0.00 | 0.308099E+10 | 0.258971E+10 | 7902.23 | 17-APR-14:00 | 7426.46 | 0.00 |
May | 0.00 | 0.00 | 0.659675E+10 | 0.493928E+10 | 23461.80 | 31-MAY-06:03 | 11168.17 | 0.00 |
June | 0.00 | 0.00 | 0.116377E+11 | 0.822803E+10 | 28135.56 | 23-JUN-06:02 | 16638.71 | 0.00 |
July | 0.00 | 0.00 | 0.140126E+11 | 0.920829E+10 | 28679.46 | 27-JUL-06:02 | 15136.94 | 0.00 |
August | 0.00 | 0.00 | 0.154375E+11 | 0.991477E+10 | 29104.06 | 21-AUG-06:02 | 14334.28 | 0.00 |
September | 0.00 | 0.00 | 0.915496E+10 | 0.620973E+10 | 29016.36 | 17-SEP-07:02 | 13899.39 | 0.00 |
October | 0.00 | 0.00 | 0.331451E+10 | 0.236152E+10 | 28046.00 | 19-OCT-06:02 | 11546.18 | 0.00 |
November | 0.00 | 0.00 | 0.564274E+09 | 0.424950E+09 | 7218.77 | 05-NOV-14:00 | 4870.75 | 0.00 |
December | 0.00 | 0.00 | 52051288.83 | 37059593.94 | 3829.76 | 12-DEC-14:00 | 2677.85 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.650626E+11 | 0.449386E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.154375E+11 | 0.991477E+10 | 29104.06 | 16638.71 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.357942E+09 | 0.357857E+09 | 8060.65 | 28-FEB-15:10 | 8060.65 | 0.00 |
March | 0.00 | 0.00 | 0.157138E+10 | 0.123978E+10 | 15289.31 | 30-MAR-14:10 | 12478.47 | 0.00 |
April | 0.00 | 0.00 | 0.518366E+10 | 0.425291E+10 | 14644.38 | 17-APR-14:30 | 13587.03 | 0.00 |
May | 0.00 | 0.00 | 0.115131E+11 | 0.841678E+10 | 35179.79 | 30-MAY-07:03 | 23688.80 | 0.00 |
June | 0.00 | 0.00 | 0.209191E+11 | 0.144591E+11 | 50953.16 | 26-JUN-07:02 | 30832.66 | 0.00 |
July | 0.00 | 0.00 | 0.248903E+11 | 0.160221E+11 | 51627.81 | 31-JUL-07:02 | 20647.94 | 0.00 |
August | 0.00 | 0.00 | 0.277221E+11 | 0.173921E+11 | 52758.65 | 20-AUG-08:62 | 25459.53 | 0.00 |
September | 0.00 | 0.00 | 0.160961E+11 | 0.106376E+11 | 52581.30 | 17-SEP-08:62 | 24133.05 | 0.00 |
October | 0.00 | 0.00 | 0.569833E+10 | 0.392568E+10 | 50203.34 | 19-OCT-07:02 | 21536.80 | 0.00 |
November | 0.00 | 0.00 | 0.791326E+09 | 0.589996E+09 | 13354.51 | 05-NOV-15:00 | 8977.79 | 0.00 |
December | 0.00 | 0.00 | 66549769.69 | 47249876.93 | 6106.49 | 12-DEC-14:00 | 4182.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.114810E+12 | 0.773411E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.277221E+11 | 0.173921E+11 | 52758.65 | 30832.66 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.175027E+09 | 0.174997E+09 | 4120.65 | 28-FEB-15:10 | 4120.65 | 0.00 |
March | 0.00 | 0.00 | 0.781096E+09 | 0.618313E+09 | 7834.31 | 30-MAR-14:10 | 6404.30 | 0.00 |
April | 0.00 | 0.00 | 0.262477E+10 | 0.216008E+10 | 7559.74 | 17-APR-14:30 | 7026.70 | 0.00 |
May | 0.00 | 0.00 | 0.588749E+10 | 0.431625E+10 | 17012.65 | 30-MAY-07:03 | 11430.66 | 0.00 |
June | 0.00 | 0.00 | 0.107390E+11 | 0.744127E+10 | 26322.31 | 26-JUN-07:02 | 15910.40 | 0.00 |
July | 0.00 | 0.00 | 0.127872E+11 | 0.825620E+10 | 26668.37 | 31-JUL-07:02 | 10669.17 | 0.00 |
August | 0.00 | 0.00 | 0.142430E+11 | 0.896389E+10 | 27251.83 | 20-AUG-08:62 | 13104.33 | 0.00 |
September | 0.00 | 0.00 | 0.826307E+10 | 0.547819E+10 | 27155.91 | 17-SEP-08:62 | 12441.68 | 0.00 |
October | 0.00 | 0.00 | 0.291388E+10 | 0.201248E+10 | 25924.32 | 19-OCT-07:02 | 11145.63 | 0.00 |
November | 0.00 | 0.00 | 0.385362E+09 | 0.287887E+09 | 6891.78 | 05-NOV-15:00 | 4649.05 | 0.00 |
December | 0.00 | 0.00 | 30798954.36 | 21957724.15 | 2966.89 | 12-DEC-14:00 | 2036.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.588307E+11 | 0.397315E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.142430E+11 | 0.896389E+10 | 27251.83 | 15910.40 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.165088E+09 | 0.165061E+09 | 4018.13 | 28-FEB-15:10 | 4018.13 | 0.00 |
March | 0.00 | 0.00 | 0.749063E+09 | 0.592367E+09 | 7721.71 | 30-MAR-14:10 | 6301.69 | 0.00 |
April | 0.00 | 0.00 | 0.255441E+10 | 0.210165E+10 | 7479.37 | 17-APR-14:40 | 6960.65 | 0.00 |
May | 0.00 | 0.00 | 0.578911E+10 | 0.423904E+10 | 15852.17 | 30-MAY-07:03 | 10591.07 | 0.00 |
June | 0.00 | 0.00 | 0.106633E+11 | 0.737734E+10 | 26218.95 | 26-JUN-07:02 | 15818.86 | 0.00 |
July | 0.00 | 0.00 | 0.127110E+11 | 0.819629E+10 | 26566.39 | 31-JUL-07:02 | 10616.86 | 0.00 |
August | 0.00 | 0.00 | 0.141675E+11 | 0.890284E+10 | 27145.74 | 20-AUG-08:62 | 13024.76 | 0.00 |
September | 0.00 | 0.00 | 0.819843E+10 | 0.542693E+10 | 27050.79 | 17-SEP-08:62 | 12356.26 | 0.00 |
October | 0.00 | 0.00 | 0.286931E+10 | 0.197733E+10 | 25826.44 | 19-OCT-07:02 | 11088.97 | 0.00 |
November | 0.00 | 0.00 | 0.363482E+09 | 0.270714E+09 | 6798.22 | 05-NOV-15:00 | 4575.56 | 0.00 |
December | 0.00 | 0.00 | 28588303.39 | 20365386.95 | 2832.16 | 12-DEC-14:00 | 1941.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.582593E+11 | 0.392699E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.141675E+11 | 0.890284E+10 | 27145.74 | 15818.86 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.143840E+09 | 0.143825E+09 | 3783.79 | 28-FEB-15:10 | 3783.79 | 0.00 |
March | 0.00 | 0.00 | 0.674287E+09 | 0.533110E+09 | 7482.17 | 30-MAR-14:10 | 6090.88 | 0.00 |
April | 0.00 | 0.00 | 0.236970E+10 | 0.195516E+10 | 7279.57 | 17-APR-14:40 | 6769.73 | 0.00 |
May | 0.00 | 0.00 | 0.555747E+10 | 0.406753E+10 | 11627.27 | 30-MAY-07:03 | 7626.41 | 0.00 |
June | 0.00 | 0.00 | 0.105532E+11 | 0.729136E+10 | 26211.44 | 26-JUN-07:02 | 15729.76 | 0.00 |
July | 0.00 | 0.00 | 0.126282E+11 | 0.814287E+10 | 26569.83 | 31-JUL-07:02 | 10584.16 | 0.00 |
August | 0.00 | 0.00 | 0.141262E+11 | 0.887340E+10 | 27145.06 | 20-AUG-08:62 | 12978.54 | 0.00 |
September | 0.00 | 0.00 | 0.810884E+10 | 0.536345E+10 | 27047.50 | 17-SEP-08:62 | 12251.59 | 0.00 |
October | 0.00 | 0.00 | 0.277040E+10 | 0.190243E+10 | 25832.68 | 19-OCT-07:02 | 11057.98 | 0.00 |
November | 0.00 | 0.00 | 0.313150E+09 | 0.231603E+09 | 6581.97 | 05-NOV-15:00 | 4413.85 | 0.00 |
December | 0.00 | 0.00 | 24196633.37 | 17237338.81 | 2529.32 | 12-DEC-14:00 | 1731.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.572694E+11 | 0.385220E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.141262E+11 | 0.887340E+10 | 27145.06 | 15729.76 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.126289E+09 | 0.126289E+09 | 3740.62 | 28-FEB-15:10 | 3740.62 | 0.00 |
March | 0.00 | 0.00 | 0.588765E+09 | 0.472128E+09 | 7579.35 | 30-MAR-14:10 | 6223.36 | 0.00 |
April | 0.00 | 0.00 | 0.218745E+10 | 0.185204E+10 | 7380.96 | 17-APR-14:10 | 6872.53 | 0.00 |
May | 0.00 | 0.00 | 0.558443E+10 | 0.415529E+10 | 11703.71 | 30-MAY-15:00 | 8575.88 | 0.00 |
June | 0.00 | 0.00 | 0.112617E+11 | 0.789163E+10 | 28918.67 | 26-JUN-07:02 | 15836.76 | 0.00 |
July | 0.00 | 0.00 | 0.136521E+11 | 0.898467E+10 | 29179.32 | 27-JUL-07:02 | 13983.45 | 0.00 |
August | 0.00 | 0.00 | 0.153445E+11 | 0.982655E+10 | 29890.44 | 20-AUG-08:62 | 13179.87 | 0.00 |
September | 0.00 | 0.00 | 0.868866E+10 | 0.587568E+10 | 29431.68 | 17-SEP-08:62 | 13269.72 | 0.00 |
October | 0.00 | 0.00 | 0.282480E+10 | 0.196630E+10 | 19519.95 | 19-OCT-07:02 | 7923.74 | 0.00 |
November | 0.00 | 0.00 | 0.261995E+09 | 0.193130E+09 | 6556.81 | 05-NOV-15:00 | 4437.48 | 0.00 |
December | 0.00 | 0.00 | 19068966.76 | 13793501.04 | 2265.28 | 12-DEC-14:00 | 1569.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.605398E+11 | 0.413575E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.153445E+11 | 0.982655E+10 | 29890.44 | 15836.76 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.195239E+10 | 0.41 | 2332.70 | 02-JAN-08:61 | 0.91 |
February | 0.167927E+10 | 0.40 | 2332.70 | 01-FEB-08:61 | 0.91 |
March | 0.171573E+10 | 0.38 | 2332.70 | 18-MAR-07:01 | 0.91 |
April | 0.164172E+10 | 0.37 | 2332.70 | 06-APR-07:01 | 0.91 |
May | 0.169302E+10 | 0.37 | 1092.18 | 31-MAY-07:03 | 0.60 |
June | 0.166710E+10 | 0.37 | 2332.70 | 12-JUN-07:02 | 0.90 |
July | 0.177059E+10 | 0.38 | 2332.70 | 01-JUL-07:02 | 0.89 |
August | 0.179707E+10 | 0.38 | 2332.70 | 01-AUG-07:02 | 0.90 |
September | 0.165485E+10 | 0.37 | 2332.70 | 02-SEP-07:02 | 0.90 |
October | 0.169430E+10 | 0.37 | 2332.70 | 18-OCT-07:03 | 0.89 |
November | 0.165498E+10 | 0.37 | 2332.70 | 21-NOV-08:61 | 0.91 |
December | 0.179913E+10 | 0.39 | 2332.70 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.207202E+11 | 0.38 | |||
Minimum of Months | 0.164172E+10 | 0.37 | 1092.18 | 0.60 | |
Maximum of Months | 0.195239E+10 | 0.41 | 2332.70 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.786749E+09 | 0.33 | 1278.45 | 04-JAN-08:61 | 0.94 |
February | 0.743296E+09 | 0.35 | 1278.45 | 03-FEB-08:61 | 0.94 |
March | 0.839681E+09 | 0.38 | 681.60 | 23-MAR-07:01 | 0.68 |
April | 0.794158E+09 | 0.37 | 605.01 | 06-APR-08:10 | 0.64 |
May | 0.805942E+09 | 0.38 | 977.02 | 31-MAY-07:03 | 0.82 |
June | 0.803714E+09 | 0.38 | 1278.45 | 12-JUN-07:02 | 0.93 |
July | 0.868219E+09 | 0.39 | 1278.45 | 01-JUL-07:02 | 0.93 |
August | 0.886458E+09 | 0.39 | 1278.45 | 01-AUG-07:02 | 0.93 |
September | 0.800472E+09 | 0.38 | 1278.45 | 02-SEP-07:02 | 0.93 |
October | 0.843955E+09 | 0.38 | 1278.45 | 18-OCT-07:03 | 0.93 |
November | 0.807803E+09 | 0.37 | 1255.51 | 22-NOV-08:61 | 0.94 |
December | 0.740765E+09 | 0.33 | 1278.45 | 02-DEC-08:61 | 0.94 |
Annual Sum or Average | 0.972121E+10 | 0.37 | |||
Minimum of Months | 0.740765E+09 | 0.33 | 605.01 | 0.64 | |
Maximum of Months | 0.886458E+09 | 0.39 | 1278.45 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.841500E+09 | 0.34 | 1273.51 | 02-JAN-07:01 | 0.94 |
February | 0.724947E+09 | 0.33 | 1273.51 | 03-FEB-07:01 | 0.95 |
March | 0.756890E+09 | 0.31 | 636.79 | 19-MAR-07:03 | 0.66 |
April | 0.715764E+09 | 0.31 | 660.47 | 06-APR-07:05 | 0.67 |
May | 0.744790E+09 | 0.31 | 1225.73 | 31-MAY-06:03 | 0.91 |
June | 0.735886E+09 | 0.31 | 1273.51 | 05-JUN-06:02 | 0.93 |
July | 0.768684E+09 | 0.31 | 1273.51 | 01-JUL-06:02 | 0.93 |
August | 0.796938E+09 | 0.32 | 1273.51 | 01-AUG-06:02 | 0.93 |
September | 0.720985E+09 | 0.31 | 1273.51 | 01-SEP-06:02 | 0.93 |
October | 0.737727E+09 | 0.31 | 1273.51 | 18-OCT-06:02 | 0.92 |
November | 0.721126E+09 | 0.31 | 1017.48 | 22-NOV-07:02 | 0.85 |
December | 0.769121E+09 | 0.32 | 1273.51 | 03-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.903436E+10 | 0.31 | |||
Minimum of Months | 0.715764E+09 | 0.31 | 636.79 | 0.66 | |
Maximum of Months | 0.841500E+09 | 0.34 | 1273.51 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.849985E+09 | 0.34 | 1276.54 | 02-JAN-07:01 | 0.94 |
February | 0.729997E+09 | 0.33 | 1276.54 | 03-FEB-07:01 | 0.95 |
March | 0.759596E+09 | 0.32 | 730.38 | 19-MAR-07:03 | 0.71 |
April | 0.717552E+09 | 0.31 | 643.35 | 07-APR-07:04 | 0.66 |
May | 0.746563E+09 | 0.31 | 1222.46 | 31-MAY-06:03 | 0.91 |
June | 0.737525E+09 | 0.31 | 1276.54 | 05-JUN-06:02 | 0.93 |
July | 0.770606E+09 | 0.31 | 1276.54 | 01-JUL-06:02 | 0.93 |
August | 0.798839E+09 | 0.32 | 1276.54 | 01-AUG-06:02 | 0.93 |
September | 0.722637E+09 | 0.31 | 1276.54 | 01-SEP-06:02 | 0.93 |
October | 0.739586E+09 | 0.31 | 1276.54 | 18-OCT-06:02 | 0.92 |
November | 0.723943E+09 | 0.31 | 1094.05 | 22-NOV-07:02 | 0.88 |
December | 0.775491E+09 | 0.32 | 1276.54 | 03-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.907232E+10 | 0.31 | |||
Minimum of Months | 0.717552E+09 | 0.31 | 643.35 | 0.66 | |
Maximum of Months | 0.849985E+09 | 0.34 | 1276.54 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.851576E+09 | 0.34 | 1265.73 | 02-JAN-07:01 | 0.94 |
February | 0.728920E+09 | 0.33 | 1265.73 | 03-FEB-07:01 | 0.95 |
March | 0.754765E+09 | 0.32 | 825.90 | 19-MAR-07:03 | 0.77 |
April | 0.711699E+09 | 0.31 | 659.65 | 06-APR-07:03 | 0.67 |
May | 0.740173E+09 | 0.31 | 1049.18 | 31-MAY-06:03 | 0.85 |
June | 0.729978E+09 | 0.31 | 1265.73 | 05-JUN-06:02 | 0.93 |
July | 0.761775E+09 | 0.31 | 1265.73 | 01-JUL-06:02 | 0.93 |
August | 0.789142E+09 | 0.32 | 1265.73 | 01-AUG-06:02 | 0.93 |
September | 0.715909E+09 | 0.31 | 1265.73 | 01-SEP-06:02 | 0.93 |
October | 0.733531E+09 | 0.31 | 1265.73 | 18-OCT-06:02 | 0.92 |
November | 0.719604E+09 | 0.31 | 1165.95 | 22-NOV-07:02 | 0.91 |
December | 0.775250E+09 | 0.32 | 1265.73 | 03-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.901232E+10 | 0.32 | |||
Minimum of Months | 0.711699E+09 | 0.31 | 659.65 | 0.67 | |
Maximum of Months | 0.851576E+09 | 0.34 | 1265.73 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137199E+10 | 0.31 | 2151.39 | 01-JAN-09:01 | 0.91 |
February | 0.116388E+10 | 0.30 | 2151.39 | 01-FEB-08:61 | 0.91 |
March | 0.119102E+10 | 0.28 | 2151.39 | 18-MAR-07:01 | 0.91 |
April | 0.111696E+10 | 0.27 | 2022.91 | 07-APR-07:01 | 0.89 |
May | 0.116189E+10 | 0.28 | 1419.88 | 30-MAY-07:03 | 0.73 |
June | 0.115613E+10 | 0.28 | 2151.39 | 05-JUN-07:03 | 0.90 |
July | 0.121499E+10 | 0.28 | 2151.39 | 01-JUL-07:02 | 0.90 |
August | 0.126560E+10 | 0.29 | 2151.39 | 01-AUG-07:02 | 0.90 |
September | 0.112687E+10 | 0.27 | 2151.39 | 02-SEP-07:02 | 0.90 |
October | 0.115193E+10 | 0.27 | 2151.39 | 19-OCT-07:02 | 0.89 |
November | 0.113649E+10 | 0.28 | 2151.39 | 21-NOV-08:61 | 0.91 |
December | 0.123746E+10 | 0.29 | 2151.39 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.142952E+11 | 0.28 | |||
Minimum of Months | 0.111696E+10 | 0.27 | 1419.88 | 0.73 | |
Maximum of Months | 0.137199E+10 | 0.31 | 2151.39 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.740469E+09 | 0.32 | 1155.17 | 01-JAN-09:01 | 0.94 |
February | 0.627281E+09 | 0.31 | 1155.17 | 01-FEB-08:61 | 0.94 |
March | 0.640014E+09 | 0.29 | 1155.17 | 18-MAR-07:01 | 0.94 |
April | 0.599798E+09 | 0.28 | 1133.04 | 07-APR-07:01 | 0.93 |
May | 0.623843E+09 | 0.28 | 699.46 | 30-MAY-07:03 | 0.72 |
June | 0.620820E+09 | 0.29 | 1155.17 | 12-JUN-07:02 | 0.93 |
July | 0.652486E+09 | 0.29 | 1155.17 | 01-JUL-07:02 | 0.93 |
August | 0.679274E+09 | 0.30 | 1155.17 | 01-AUG-07:02 | 0.93 |
September | 0.605013E+09 | 0.28 | 1155.17 | 02-SEP-07:02 | 0.93 |
October | 0.618593E+09 | 0.28 | 1155.17 | 19-OCT-07:02 | 0.92 |
November | 0.610556E+09 | 0.29 | 1155.17 | 21-NOV-08:61 | 0.94 |
December | 0.666206E+09 | 0.30 | 1155.17 | 01-DEC-08:61 | 0.94 |
Annual Sum or Average | 0.768435E+10 | 0.29 | |||
Minimum of Months | 0.599798E+09 | 0.28 | 699.46 | 0.72 | |
Maximum of Months | 0.740469E+09 | 0.32 | 1155.17 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.739163E+09 | 0.32 | 1149.17 | 01-JAN-09:01 | 0.94 |
February | 0.625739E+09 | 0.31 | 1149.17 | 01-FEB-08:61 | 0.94 |
March | 0.637528E+09 | 0.29 | 1149.17 | 18-MAR-07:01 | 0.94 |
April | 0.596818E+09 | 0.28 | 1149.17 | 06-APR-07:01 | 0.94 |
May | 0.620589E+09 | 0.28 | 636.58 | 30-MAY-07:03 | 0.69 |
June | 0.617399E+09 | 0.29 | 1149.17 | 12-JUN-07:02 | 0.93 |
July | 0.648918E+09 | 0.29 | 1149.17 | 01-JUL-07:02 | 0.93 |
August | 0.675533E+09 | 0.30 | 1149.17 | 01-AUG-07:02 | 0.93 |
September | 0.601830E+09 | 0.28 | 1149.17 | 02-SEP-07:02 | 0.93 |
October | 0.615619E+09 | 0.28 | 1149.17 | 19-OCT-07:02 | 0.92 |
November | 0.608102E+09 | 0.29 | 1149.17 | 21-NOV-08:61 | 0.94 |
December | 0.664815E+09 | 0.30 | 1149.17 | 01-DEC-08:61 | 0.94 |
Annual Sum or Average | 0.765205E+10 | 0.29 | |||
Minimum of Months | 0.596818E+09 | 0.28 | 636.58 | 0.69 | |
Maximum of Months | 0.739163E+09 | 0.32 | 1149.17 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.748536E+09 | 0.32 | 1149.58 | 01-JAN-09:01 | 0.94 |
February | 0.631959E+09 | 0.31 | 1149.58 | 01-FEB-08:61 | 0.94 |
March | 0.640671E+09 | 0.29 | 1149.58 | 18-MAR-07:01 | 0.94 |
April | 0.597585E+09 | 0.28 | 1149.58 | 06-APR-07:01 | 0.94 |
May | 0.620772E+09 | 0.28 | 459.83 | 25-MAY-11:10 | 0.56 |
June | 0.616780E+09 | 0.29 | 1149.58 | 12-JUN-07:02 | 0.93 |
July | 0.648697E+09 | 0.29 | 1149.58 | 01-JUL-07:02 | 0.93 |
August | 0.675425E+09 | 0.30 | 1149.58 | 01-AUG-07:02 | 0.93 |
September | 0.601992E+09 | 0.28 | 1149.58 | 03-SEP-08:62 | 0.92 |
October | 0.616516E+09 | 0.28 | 1149.58 | 19-OCT-07:02 | 0.92 |
November | 0.610501E+09 | 0.29 | 1149.58 | 21-NOV-08:61 | 0.94 |
December | 0.671718E+09 | 0.30 | 1149.58 | 01-DEC-08:61 | 0.94 |
Annual Sum or Average | 0.768115E+10 | 0.29 | |||
Minimum of Months | 0.597585E+09 | 0.28 | 459.83 | 0.56 | |
Maximum of Months | 0.748536E+09 | 0.32 | 1149.58 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.863679E+09 | 0.34 | 1294.75 | 01-JAN-09:01 | 0.94 |
February | 0.730197E+09 | 0.33 | 1294.75 | 01-FEB-08:61 | 0.94 |
March | 0.731012E+09 | 0.30 | 1294.75 | 03-MAR-08:61 | 0.94 |
April | 0.676022E+09 | 0.28 | 1294.75 | 06-APR-07:01 | 0.94 |
May | 0.699182E+09 | 0.28 | 533.82 | 11-MAY-07:05 | 0.58 |
June | 0.692247E+09 | 0.29 | 1294.75 | 12-JUN-07:02 | 0.93 |
July | 0.731204E+09 | 0.29 | 1294.75 | 04-JUL-08:62 | 0.93 |
August | 0.762370E+09 | 0.30 | 1294.75 | 01-AUG-07:02 | 0.93 |
September | 0.679096E+09 | 0.28 | 1294.75 | 05-SEP-07:02 | 0.92 |
October | 0.696273E+09 | 0.28 | 1294.75 | 26-OCT-07:01 | 0.94 |
November | 0.692865E+09 | 0.29 | 1294.75 | 21-NOV-08:61 | 0.94 |
December | 0.770053E+09 | 0.30 | 1294.75 | 01-DEC-08:61 | 0.94 |
Annual Sum or Average | 0.872420E+10 | 0.30 | |||
Minimum of Months | 0.676022E+09 | 0.28 | 533.82 | 0.58 | |
Maximum of Months | 0.863679E+09 | 0.34 | 1294.75 | 0.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.195239E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.184040E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.237743E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.363414E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.601889E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.902323E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.107008E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.113694E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.752250E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.389369E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.212036E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.184313E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.622963E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.184040E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.113694E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.788316E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.875853E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.131715E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.213338E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.331987E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.460936E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.537946E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.564080E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.389455E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.212249E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.115723E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.785971E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.320244E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.785971E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.564080E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.841534E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.807196E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.105134E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.158788E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.250307E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.369088E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.425907E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.458717E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.301617E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.160927E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.915666E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.794065E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.256633E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.794065E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.458717E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.849985E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.805944E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.104133E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.157572E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.249564E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.369835E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.427235E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.460075E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.301809E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.160101E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.898507E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.795323E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.256530E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.795323E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.460075E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.851576E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.795150E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.101016E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.152355E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.242322E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.363144E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.420312E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.452700E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.295621E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.155835E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.868410E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.789353E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.251375E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.789353E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.452700E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.137199E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.126357E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.161683E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.251629E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.416312E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.646263E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.743450E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.809481E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.513494E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.259650E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.135000E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.125590E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.432611E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.125590E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.809481E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.740469E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.675255E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.848246E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.129676E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.213291E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.330079E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.379650E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.413211E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.262793E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.134455E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.712767E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.674610E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.222829E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.674610E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.413211E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.739163E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.671095E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.837590E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.127632E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.210579E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.327895E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.377429E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.411005E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.260942E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.133094E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.704616E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.672633E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.221109E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.671095E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.411005E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.748536E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.671704E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.821720E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.123171E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.205156E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.325342E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.375513E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.410124E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.258943E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.130861E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.693884E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.678378E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.219053E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.671704E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.410124E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.863679E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.765400E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.890980E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.126905E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.214791E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.351719E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.409878E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.449612E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.281423E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.140468E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.763066E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.775351E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.238064E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.763066E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.449612E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.195239E+10 | 0.00 | 0.112934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167927E+10 | 0.588003E+09 | 0.641934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171573E+10 | 0.247140E+10 | 0.701349E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164172E+10 | 0.745557E+10 | 0.108721E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169302E+10 | 0.167097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166710E+10 | 0.289943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.177059E+10 | 0.357032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179707E+10 | 0.388736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165485E+10 | 0.236323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169430E+10 | 0.873691E+10 | 41047069.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165498E+10 | 0.176259E+10 | 0.833643E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179913E+10 | 0.160611E+09 | 0.433670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207202E+11 | 0.165088E+12 | 0.237342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.164172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.195239E+10 | 0.388736E+11 | 0.112934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.786749E+09 | 5621128.85 | 0.327507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.743296E+09 | 0.486975E+09 | 0.184119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.839681E+09 | 0.180836E+10 | 0.118722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.794158E+09 | 0.508635E+10 | 8376944.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.805942E+09 | 0.987728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.803714E+09 | 0.151514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.868219E+09 | 0.182075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.886458E+09 | 0.194594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.800472E+09 | 0.125938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.843955E+09 | 0.513150E+10 | 1237211.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.807803E+09 | 0.135125E+10 | 0.114902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.740765E+09 | 0.168942E+09 | 0.840233E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.972121E+10 | 0.893283E+11 | 0.619972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.740765E+09 | 5621128.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.886458E+09 | 0.194594E+11 | 0.327507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.841500E+09 | 118138.76 | 0.431252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.724947E+09 | 0.306594E+09 | 0.237453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.756890E+09 | 0.112339E+10 | 0.207121E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.715764E+09 | 0.333020E+10 | 23162493.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.744790E+09 | 0.692075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.735886E+09 | 0.118725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.768684E+09 | 0.142260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.796938E+09 | 0.156637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.720985E+09 | 0.940103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.737727E+09 | 0.351520E+10 | 10174886.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.721126E+09 | 0.744404E+09 | 0.244866E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.769121E+09 | 92830444.39 | 0.147120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.903436E+10 | 0.671968E+11 | 0.864358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.715764E+09 | 118138.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.841500E+09 | 0.156637E+11 | 0.431252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.849985E+09 | 0.15 | 0.455364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.729997E+09 | 0.281938E+09 | 0.249723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.759596E+09 | 0.107207E+10 | 0.242993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.717552E+09 | 0.327125E+10 | 26446451.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.746563E+09 | 0.687765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.737525E+09 | 0.118954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.770606E+09 | 0.142745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.798839E+09 | 0.157145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.722637E+09 | 0.939911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.739586E+09 | 0.347065E+10 | 14896428.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.723943E+09 | 0.664965E+09 | 0.288585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.775491E+09 | 73505839.28 | 0.164894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.907232E+10 | 0.669956E+11 | 0.927273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.717552E+09 | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.849985E+09 | 0.157145E+11 | 0.455364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.851576E+09 | 0.00 | 0.491612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.728920E+09 | 0.244300E+09 | 0.270782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.754765E+09 | 0.967002E+09 | 0.309211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.711699E+09 | 0.308099E+10 | 35688188.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.740173E+09 | 0.659675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.729978E+09 | 0.116377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.761775E+09 | 0.140126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.789142E+09 | 0.154375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.715909E+09 | 0.915496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.733531E+09 | 0.331451E+10 | 24529661.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.719604E+09 | 0.564274E+09 | 0.362645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.775250E+09 | 52051288.83 | 0.191021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.901232E+10 | 0.650626E+11 | 0.102662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.711699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.851576E+09 | 0.154375E+11 | 0.491612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137199E+10 | 0.00 | 0.991206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116388E+10 | 0.357942E+09 | 0.547401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119102E+10 | 0.157138E+10 | 0.751235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111696E+10 | 0.518366E+10 | 74821067.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116189E+10 | 0.115131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.115613E+10 | 0.209191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121499E+10 | 0.248903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.126560E+10 | 0.277221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112687E+10 | 0.160961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115193E+10 | 0.569833E+10 | 0.101144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113649E+10 | 0.791326E+09 | 0.944369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123746E+10 | 66549769.69 | 0.419822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142952E+11 | 0.114810E+12 | 0.214559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137199E+10 | 0.277221E+11 | 0.991206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.740469E+09 | 0.00 | 0.517492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.627281E+09 | 0.175027E+09 | 0.286854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.640014E+09 | 0.781096E+09 | 0.401558E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.599798E+09 | 0.262477E+10 | 40287025.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.623843E+09 | 0.588749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.620820E+09 | 0.107390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.652486E+09 | 0.127872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.679274E+09 | 0.142430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.605013E+09 | 0.826307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.618593E+09 | 0.291388E+10 | 55033969.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.610556E+09 | 0.385362E+09 | 0.491652E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.666206E+09 | 30798954.36 | 0.219851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.768435E+10 | 0.588307E+11 | 0.112305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.599798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.740469E+09 | 0.142430E+11 | 0.517492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.739163E+09 | 0.00 | 0.526190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.625739E+09 | 0.165088E+09 | 0.292966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.637528E+09 | 0.749063E+09 | 0.435089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.596818E+09 | 0.255441E+10 | 45666688.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.620589E+09 | 0.578911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.617399E+09 | 0.106633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.648918E+09 | 0.127110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.675533E+09 | 0.141675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.601830E+09 | 0.819843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.615619E+09 | 0.286931E+10 | 65044486.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.608102E+09 | 0.363482E+09 | 0.519782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.664815E+09 | 28588303.39 | 0.227697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.765205E+10 | 0.582593E+11 | 0.115341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.596818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.739163E+09 | 0.141675E+11 | 0.526190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.748536E+09 | 0.00 | 0.562702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.631959E+09 | 0.143840E+09 | 0.317171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.640671E+09 | 0.674287E+09 | 0.555952E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.597585E+09 | 0.236970E+10 | 68842789.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.620772E+09 | 0.555747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.616780E+09 | 0.105532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.648697E+09 | 0.126282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.675425E+09 | 0.141262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.601992E+09 | 0.810884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.616516E+09 | 0.277040E+10 | 94278150.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.610501E+09 | 0.313150E+09 | 0.609676E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.671718E+09 | 24196633.37 | 0.254912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.768115E+10 | 0.572694E+11 | 0.126766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.597585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.748536E+09 | 0.141262E+11 | 0.562702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.863679E+09 | 0.00 | 0.712075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.730197E+09 | 0.126289E+09 | 0.423995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.731012E+09 | 0.588765E+09 | 0.101578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.676022E+09 | 0.218745E+10 | 0.200882E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.699182E+09 | 0.558443E+10 | 718106.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.692247E+09 | 0.112617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.731204E+09 | 0.136521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.762370E+09 | 0.153445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.679096E+09 | 0.868866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.696273E+09 | 0.282480E+10 | 0.188645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.692865E+09 | 0.261995E+09 | 0.902372E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.770053E+09 | 19068966.76 | 0.341830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.872420E+10 | 0.605398E+11 | 0.170874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.676022E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.863679E+09 | 0.153445E+11 | 0.712075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.195239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167927E+10 | 0.00 | 0.00 | 0.00 | 0.161123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171573E+10 | 0.00 | 0.00 | 0.00 | 0.661699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164172E+10 | 0.00 | 0.00 | 0.00 | 0.199242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169302E+10 | 0.00 | 0.00 | 0.00 | 0.432587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166710E+10 | 0.00 | 0.00 | 0.00 | 0.735613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.177059E+10 | 0.00 | 0.00 | 0.00 | 0.893016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179707E+10 | 0.00 | 0.00 | 0.00 | 0.957237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165485E+10 | 0.00 | 0.00 | 0.00 | 0.586765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169430E+10 | 0.00 | 0.00 | 0.00 | 0.219939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165498E+10 | 0.00 | 0.00 | 0.00 | 0.465386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179913E+10 | 0.00 | 0.00 | 0.00 | 43998147.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207202E+11 | 0.00 | 0.00 | 0.00 | 0.415762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.164172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.195239E+10 | 0.00 | 0.00 | 0.00 | 0.957237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.786749E+09 | 0.00 | 0.00 | 0.00 | 1567024.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.743296E+09 | 0.00 | 0.00 | 0.00 | 0.132557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.839681E+09 | 0.00 | 0.00 | 0.00 | 0.477473E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.794158E+09 | 0.00 | 0.00 | 0.00 | 0.133922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.805942E+09 | 0.00 | 0.00 | 0.00 | 0.251393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.803714E+09 | 0.00 | 0.00 | 0.00 | 0.380565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.868219E+09 | 0.00 | 0.00 | 0.00 | 0.451124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.886458E+09 | 0.00 | 0.00 | 0.00 | 0.475434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.800472E+09 | 0.00 | 0.00 | 0.00 | 0.309408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.843955E+09 | 0.00 | 0.00 | 0.00 | 0.127854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.807803E+09 | 0.00 | 0.00 | 0.00 | 0.349431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.740765E+09 | 0.00 | 0.00 | 0.00 | 45206658.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.972121E+10 | 0.00 | 0.00 | 0.00 | 0.223032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.740765E+09 | 0.00 | 0.00 | 0.00 | 1567024.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.886458E+09 | 0.00 | 0.00 | 0.00 | 0.475434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.841500E+09 | 0.00 | 0.00 | 0.00 | 33408.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.724947E+09 | 0.00 | 0.00 | 0.00 | 82249347.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.756890E+09 | 0.00 | 0.00 | 0.00 | 0.294451E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.715764E+09 | 0.00 | 0.00 | 0.00 | 0.872119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.744790E+09 | 0.00 | 0.00 | 0.00 | 0.175828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.735886E+09 | 0.00 | 0.00 | 0.00 | 0.295499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.768684E+09 | 0.00 | 0.00 | 0.00 | 0.349039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.796938E+09 | 0.00 | 0.00 | 0.00 | 0.379023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.720985E+09 | 0.00 | 0.00 | 0.00 | 0.229519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.737727E+09 | 0.00 | 0.00 | 0.00 | 0.871538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.721126E+09 | 0.00 | 0.00 | 0.00 | 0.194540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.769121E+09 | 0.00 | 0.00 | 0.00 | 24944187.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.903436E+10 | 0.00 | 0.00 | 0.00 | 0.166290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.715764E+09 | 0.00 | 0.00 | 0.00 | 33408.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.841500E+09 | 0.00 | 0.00 | 0.00 | 0.379023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.849985E+09 | 0.00 | 0.00 | 0.00 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.729997E+09 | 0.00 | 0.00 | 0.00 | 75947258.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.759596E+09 | 0.00 | 0.00 | 0.00 | 0.281735E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.717552E+09 | 0.00 | 0.00 | 0.00 | 0.858173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.746563E+09 | 0.00 | 0.00 | 0.00 | 0.174908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.737525E+09 | 0.00 | 0.00 | 0.00 | 0.296083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.770606E+09 | 0.00 | 0.00 | 0.00 | 0.350174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.798839E+09 | 0.00 | 0.00 | 0.00 | 0.380191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.722637E+09 | 0.00 | 0.00 | 0.00 | 0.229545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.739586E+09 | 0.00 | 0.00 | 0.00 | 0.861425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.723943E+09 | 0.00 | 0.00 | 0.00 | 0.174564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.775491E+09 | 0.00 | 0.00 | 0.00 | 19832554.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.907232E+10 | 0.00 | 0.00 | 0.00 | 0.165807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.717552E+09 | 0.00 | 0.00 | 0.00 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.849985E+09 | 0.00 | 0.00 | 0.00 | 0.380191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.851576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.728920E+09 | 0.00 | 0.00 | 0.00 | 66230143.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.754765E+09 | 0.00 | 0.00 | 0.00 | 0.255395E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.711699E+09 | 0.00 | 0.00 | 0.00 | 0.811851E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.740173E+09 | 0.00 | 0.00 | 0.00 | 0.168305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.729978E+09 | 0.00 | 0.00 | 0.00 | 0.290147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.761775E+09 | 0.00 | 0.00 | 0.00 | 0.344134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.789142E+09 | 0.00 | 0.00 | 0.00 | 0.373786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.715909E+09 | 0.00 | 0.00 | 0.00 | 0.224030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.733531E+09 | 0.00 | 0.00 | 0.00 | 0.824816E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.719604E+09 | 0.00 | 0.00 | 0.00 | 0.148805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.775250E+09 | 0.00 | 0.00 | 0.00 | 14103761.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.901232E+10 | 0.00 | 0.00 | 0.00 | 0.161252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.711699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.851576E+09 | 0.00 | 0.00 | 0.00 | 0.373786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.137199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116388E+10 | 0.00 | 0.00 | 0.00 | 99696293.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119102E+10 | 0.00 | 0.00 | 0.00 | 0.425811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111696E+10 | 0.00 | 0.00 | 0.00 | 0.139933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116189E+10 | 0.00 | 0.00 | 0.00 | 0.300123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.115613E+10 | 0.00 | 0.00 | 0.00 | 0.530650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121499E+10 | 0.00 | 0.00 | 0.00 | 0.621951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.126560E+10 | 0.00 | 0.00 | 0.00 | 0.682921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112687E+10 | 0.00 | 0.00 | 0.00 | 0.400807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115193E+10 | 0.00 | 0.00 | 0.00 | 0.144457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113649E+10 | 0.00 | 0.00 | 0.00 | 0.213512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123746E+10 | 0.00 | 0.00 | 0.00 | 18441217.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142952E+11 | 0.00 | 0.00 | 0.00 | 0.289659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137199E+10 | 0.00 | 0.00 | 0.00 | 0.682921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.740469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.627281E+09 | 0.00 | 0.00 | 0.00 | 47973374.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.640014E+09 | 0.00 | 0.00 | 0.00 | 0.208232E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.599798E+09 | 0.00 | 0.00 | 0.00 | 0.696957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.623843E+09 | 0.00 | 0.00 | 0.00 | 0.150907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.620820E+09 | 0.00 | 0.00 | 0.00 | 0.267997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.652486E+09 | 0.00 | 0.00 | 0.00 | 0.314401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.679274E+09 | 0.00 | 0.00 | 0.00 | 0.345283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.605013E+09 | 0.00 | 0.00 | 0.00 | 0.202292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.618593E+09 | 0.00 | 0.00 | 0.00 | 0.725953E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.610556E+09 | 0.00 | 0.00 | 0.00 | 0.102211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.666206E+09 | 0.00 | 0.00 | 0.00 | 8404197.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.768435E+10 | 0.00 | 0.00 | 0.00 | 0.145985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.599798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.740469E+09 | 0.00 | 0.00 | 0.00 | 0.345283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.739163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.625739E+09 | 0.00 | 0.00 | 0.00 | 45355872.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.637528E+09 | 0.00 | 0.00 | 0.00 | 0.200062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.596818E+09 | 0.00 | 0.00 | 0.00 | 0.679499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.620589E+09 | 0.00 | 0.00 | 0.00 | 0.148520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.617399E+09 | 0.00 | 0.00 | 0.00 | 0.266155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.648918E+09 | 0.00 | 0.00 | 0.00 | 0.312538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.675533E+09 | 0.00 | 0.00 | 0.00 | 0.343452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.601830E+09 | 0.00 | 0.00 | 0.00 | 0.200759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.615619E+09 | 0.00 | 0.00 | 0.00 | 0.715324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.608102E+09 | 0.00 | 0.00 | 0.00 | 96513850.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.664815E+09 | 0.00 | 0.00 | 0.00 | 7818080.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.765205E+10 | 0.00 | 0.00 | 0.00 | 0.144588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.596818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.739163E+09 | 0.00 | 0.00 | 0.00 | 0.343452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.748536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.631959E+09 | 0.00 | 0.00 | 0.00 | 39745194.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.640671E+09 | 0.00 | 0.00 | 0.00 | 0.181049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.597585E+09 | 0.00 | 0.00 | 0.00 | 0.634129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.620772E+09 | 0.00 | 0.00 | 0.00 | 0.143078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.616780E+09 | 0.00 | 0.00 | 0.00 | 0.263664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.648697E+09 | 0.00 | 0.00 | 0.00 | 0.310643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.675425E+09 | 0.00 | 0.00 | 0.00 | 0.342582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.601992E+09 | 0.00 | 0.00 | 0.00 | 0.198744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.616516E+09 | 0.00 | 0.00 | 0.00 | 0.692096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.610501E+09 | 0.00 | 0.00 | 0.00 | 83383097.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.671718E+09 | 0.00 | 0.00 | 0.00 | 6659954.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.768115E+10 | 0.00 | 0.00 | 0.00 | 0.142242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.597585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.748536E+09 | 0.00 | 0.00 | 0.00 | 0.342582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.863679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.730197E+09 | 0.00 | 0.00 | 0.00 | 35202930.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.731012E+09 | 0.00 | 0.00 | 0.00 | 0.159968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.676022E+09 | 0.00 | 0.00 | 0.00 | 0.593025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.699182E+09 | 0.00 | 0.00 | 0.00 | 0.144872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.692247E+09 | 0.00 | 0.00 | 0.00 | 0.282494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.731204E+09 | 0.00 | 0.00 | 0.00 | 0.336758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.762370E+09 | 0.00 | 0.00 | 0.00 | 0.373375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.679096E+09 | 0.00 | 0.00 | 0.00 | 0.213513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.696273E+09 | 0.00 | 0.00 | 0.00 | 0.708406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.692865E+09 | 0.00 | 0.00 | 0.00 | 70201749.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.770053E+09 | 0.00 | 0.00 | 0.00 | 5298381.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.872420E+10 | 0.00 | 0.00 | 0.00 | 0.150822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.676022E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.863679E+09 | 0.00 | 0.00 | 0.00 | 0.373375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.786875E+10 | 0.00 | 0.00 | 128445.52 | 0.00 | 0.590981E+10 | 0.175727E+09 | 0.00 | 0.53 |
February | 0.517508E+10 | 1255963.96 | 0.00 | 2792583.04 | 0.00 | 0.372473E+10 | 0.142951E+10 | 0.00 | 0.62 |
March | 0.422988E+10 | 0.178134E+09 | 0.00 | 6298025.89 | 0.00 | 0.279737E+09 | 0.345585E+10 | 0.00 | 0.71 |
April | 0.163398E+10 | 0.582661E+09 | 0.00 | 9586682.41 | 1705458.71 | 42219850.98 | 0.319377E+10 | 0.00 | 0.78 |
May | 0.157626E+09 | 0.279178E+10 | 0.00 | 6602738.50 | 0.00 | 0.00 | 0.205758E+10 | 0.00 | 0.75 |
June | 3180135.11 | 0.855457E+10 | 0.00 | 3612925.89 | 0.00 | 0.00 | 0.508030E+09 | 0.00 | 0.61 |
July | 20886.24 | 0.121067E+11 | 0.00 | 973149.75 | 0.00 | 0.00 | 0.355561E+09 | 0.00 | 0.57 |
August | 0.00 | 0.135762E+11 | 0.00 | 178870.96 | 0.00 | 0.00 | 16325904.34 | 0.00 | 0.54 |
September | 23917342.22 | 0.601964E+10 | 0.00 | 5346779.87 | 0.00 | 0.00 | 0.171374E+10 | 0.00 | 0.68 |
October | 0.244805E+10 | 0.133411E+10 | 0.00 | 10635562.04 | 0.00 | 3150879.81 | 0.445434E+10 | 0.00 | 0.79 |
November | 0.481592E+10 | 50556498.30 | 0.00 | 6792693.50 | 1563872.80 | 0.113757E+09 | 0.418699E+10 | 0.00 | 0.73 |
December | 0.895135E+10 | 0.00 | 0.00 | 1149116.15 | 0.00 | 0.137810E+10 | 0.740367E+09 | 0.00 | 0.56 |
Annual Sum or Average | 0.353078E+11 | 0.451957E+11 | 0.00 | 54097573.51 | 3269331.51 | 0.114515E+11 | 0.222878E+11 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 128445.52 | 0.00 | 0.00 | 16325904.34 | 0.00 | 0.53 |
Maximum of Months | 0.895135E+10 | 0.135762E+11 | 0.00 | 10635562.04 | 1705458.71 | 0.590981E+10 | 0.445434E+10 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.320300E+10 | 0.00 | 0.00 | 291338.95 | 0.00 | 0.168362E+10 | 0.297530E+09 | 0.00 | 0.40 |
February | 0.199242E+10 | 681768.93 | 0.00 | 2212595.74 | 0.00 | 0.101321E+10 | 0.127515E+10 | 0.00 | 0.56 |
March | 0.145390E+10 | 97061739.80 | 0.00 | 4182970.42 | 0.00 | 3741548.70 | 0.245356E+10 | 0.00 | 0.69 |
April | 0.461643E+09 | 0.324922E+09 | 0.00 | 4454431.40 | 0.00 | 827903.81 | 0.169213E+10 | 0.00 | 0.71 |
May | 27504953.51 | 0.147547E+10 | 0.00 | 2735086.44 | 0.00 | 0.00 | 0.785052E+09 | 0.00 | 0.61 |
June | 449946.87 | 0.396613E+10 | 0.00 | 1257250.03 | 0.00 | 0.00 | 0.189202E+09 | 0.00 | 0.50 |
July | 0.00 | 0.547381E+10 | 0.00 | 335189.77 | 0.00 | 0.00 | 76471457.03 | 0.00 | 0.46 |
August | 0.00 | 0.608331E+10 | 0.00 | 17901.82 | 0.00 | 0.00 | 83792.65 | 0.00 | 0.45 |
September | 3017585.17 | 0.277419E+10 | 0.00 | 2261843.45 | 0.00 | 0.00 | 0.680171E+09 | 0.00 | 0.58 |
October | 0.693601E+09 | 0.668068E+09 | 0.00 | 5913011.89 | 0.00 | 0.00 | 0.274879E+10 | 0.00 | 0.76 |
November | 0.147530E+10 | 30960843.52 | 0.00 | 4855191.26 | 773276.71 | 8251468.26 | 0.285195E+10 | 0.00 | 0.73 |
December | 0.343304E+10 | 0.00 | 0.00 | 1009345.30 | 0.00 | 0.109992E+09 | 0.665988E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.127439E+11 | 0.208946E+11 | 0.00 | 29526156.48 | 773276.71 | 0.281965E+10 | 0.137161E+11 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 17901.82 | 0.00 | 0.00 | 83792.65 | 0.00 | 0.40 |
Maximum of Months | 0.343304E+10 | 0.608331E+10 | 0.00 | 5913011.89 | 773276.71 | 0.168362E+10 | 0.285195E+10 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.278455E+10 | 0.00 | 0.00 | 64231.55 | 0.00 | 0.243374E+10 | 74821159.12 | 0.00 | 0.42 |
February | 0.197121E+10 | 803164.88 | 0.00 | 928872.58 | 0.00 | 0.142117E+10 | 0.504272E+09 | 0.00 | 0.49 |
March | 0.183512E+10 | 77457078.27 | 0.00 | 1954703.11 | 3509857.55 | 38796068.46 | 0.127395E+10 | 0.00 | 0.58 |
April | 0.727762E+09 | 0.270286E+09 | 0.00 | 2055573.16 | 10719292.38 | 3041989.85 | 0.102960E+10 | 0.00 | 0.60 |
May | 0.111384E+09 | 0.115245E+10 | 0.00 | 2290905.15 | 49736653.75 | 0.00 | 0.800211E+09 | 0.00 | 0.62 |
June | 6590558.13 | 0.335536E+10 | 0.00 | 972299.90 | 0.195027E+09 | 0.00 | 0.197874E+09 | 0.00 | 0.49 |
July | 4395728.13 | 0.446755E+10 | 0.00 | 710314.14 | 0.286631E+09 | 0.00 | 78432711.47 | 0.00 | 0.44 |
August | 66710.75 | 0.501729E+10 | 0.00 | 265196.75 | 0.323990E+09 | 0.00 | 20463320.55 | 0.00 | 0.44 |
September | 47493894.17 | 0.220538E+10 | 0.00 | 1849406.43 | 0.128482E+09 | 0.00 | 0.600552E+09 | 0.00 | 0.55 |
October | 0.108626E+10 | 0.502063E+09 | 0.00 | 3376711.68 | 32777960.51 | 393987.70 | 0.158840E+10 | 0.00 | 0.64 |
November | 0.192950E+10 | 14372755.43 | 0.00 | 2506937.20 | 4919778.66 | 35688306.25 | 0.153881E+10 | 0.00 | 0.61 |
December | 0.326147E+10 | 0.00 | 0.00 | 418693.24 | 0.00 | 0.557228E+09 | 0.257507E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.137658E+11 | 0.170630E+11 | 0.00 | 17393844.90 | 0.103579E+10 | 0.449006E+10 | 0.796489E+10 | 0.00 | 0.53 |
Minimum of Months | 66710.75 | 0.00 | 0.00 | 64231.55 | 0.00 | 0.00 | 20463320.55 | 0.00 | 0.42 |
Maximum of Months | 0.326147E+10 | 0.501729E+10 | 0.00 | 3376711.68 | 0.323990E+09 | 0.243374E+10 | 0.158840E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.254662E+10 | 0.00 | 0.00 | 47539.12 | 0.00 | 0.267481E+10 | 57399187.98 | 0.00 | 0.41 |
February | 0.193398E+10 | 805223.58 | 0.00 | 804431.13 | 0.00 | 0.148127E+10 | 0.440560E+09 | 0.00 | 0.49 |
March | 0.185270E+10 | 75757133.17 | 0.00 | 1796134.57 | 3435018.32 | 52752629.66 | 0.118781E+10 | 0.00 | 0.57 |
April | 0.739712E+09 | 0.266933E+09 | 0.00 | 1976264.77 | 10559948.90 | 3314852.04 | 0.996529E+09 | 0.00 | 0.60 |
May | 0.115293E+09 | 0.114860E+10 | 0.00 | 2255383.41 | 49559794.72 | 0.00 | 0.793837E+09 | 0.00 | 0.62 |
June | 6557432.55 | 0.335926E+10 | 0.00 | 983480.61 | 0.194953E+09 | 0.00 | 0.198430E+09 | 0.00 | 0.49 |
July | 4405932.95 | 0.447573E+10 | 0.00 | 730627.76 | 0.286550E+09 | 0.00 | 79103354.59 | 0.00 | 0.44 |
August | 142879.55 | 0.502649E+10 | 0.00 | 273250.92 | 0.323940E+09 | 0.00 | 20569573.23 | 0.00 | 0.44 |
September | 47568140.00 | 0.220600E+10 | 0.00 | 1850482.79 | 0.128350E+09 | 0.00 | 0.600903E+09 | 0.00 | 0.55 |
October | 0.111267E+10 | 0.498982E+09 | 0.00 | 3275447.45 | 32590893.33 | 1740963.38 | 0.153129E+10 | 0.00 | 0.64 |
November | 0.195153E+10 | 11795088.70 | 0.00 | 2379878.76 | 5316682.53 | 53386090.51 | 0.146249E+10 | 0.00 | 0.61 |
December | 0.308844E+10 | 0.00 | 0.00 | 368253.84 | 0.00 | 0.722078E+09 | 0.240112E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.133996E+11 | 0.170704E+11 | 0.00 | 16741175.13 | 0.103526E+10 | 0.498935E+10 | 0.760903E+10 | 0.00 | 0.52 |
Minimum of Months | 142879.55 | 0.00 | 0.00 | 47539.12 | 0.00 | 0.00 | 20569573.23 | 0.00 | 0.41 |
Maximum of Months | 0.308844E+10 | 0.502649E+10 | 0.00 | 3275447.45 | 0.323940E+09 | 0.267481E+10 | 0.153129E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.216763E+10 | 0.00 | 0.00 | 30366.17 | 0.00 | 0.305463E+10 | 38041447.75 | 0.00 | 0.41 |
February | 0.181888E+10 | 799134.85 | 0.00 | 611144.25 | 0.00 | 0.165133E+10 | 0.331256E+09 | 0.00 | 0.48 |
March | 0.185250E+10 | 72351733.30 | 0.00 | 1486669.72 | 3307218.21 | 0.137145E+09 | 0.996267E+09 | 0.00 | 0.56 |
April | 0.804103E+09 | 0.257967E+09 | 0.00 | 1699436.88 | 10213194.98 | 5028546.31 | 0.860459E+09 | 0.00 | 0.58 |
May | 0.131264E+09 | 0.111899E+10 | 0.00 | 2091821.96 | 48998411.73 | 0.00 | 0.761879E+09 | 0.00 | 0.61 |
June | 15682199.09 | 0.332545E+10 | 0.00 | 919359.22 | 0.194376E+09 | 0.00 | 0.184827E+09 | 0.00 | 0.49 |
July | 4586484.11 | 0.443483E+10 | 0.00 | 688370.67 | 0.285639E+09 | 0.00 | 80720961.13 | 0.00 | 0.44 |
August | 13897.90 | 0.497740E+10 | 0.00 | 280293.73 | 0.322903E+09 | 0.00 | 23824345.08 | 0.00 | 0.44 |
September | 51941143.36 | 0.217364E+10 | 0.00 | 1715444.44 | 0.127545E+09 | 0.00 | 0.584167E+09 | 0.00 | 0.54 |
October | 0.114874E+10 | 0.484911E+09 | 0.00 | 2996478.53 | 32111615.88 | 1738901.94 | 0.141421E+10 | 0.00 | 0.63 |
November | 0.199780E+10 | 10340538.07 | 0.00 | 2044316.10 | 5776504.49 | 71111167.58 | 0.129977E+10 | 0.00 | 0.59 |
December | 0.292249E+10 | 0.00 | 0.00 | 297769.16 | 0.00 | 0.877650E+09 | 0.212441E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.129156E+11 | 0.168567E+11 | 0.00 | 14861470.83 | 0.103087E+10 | 0.579863E+10 | 0.678786E+10 | 0.00 | 0.52 |
Minimum of Months | 13897.90 | 0.00 | 0.00 | 30366.17 | 0.00 | 0.00 | 23824345.08 | 0.00 | 0.41 |
Maximum of Months | 0.292249E+10 | 0.497740E+10 | 0.00 | 2996478.53 | 0.322903E+09 | 0.305463E+10 | 0.141421E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.294302E+10 | 0.00 | 0.00 | 6729.08 | 0.00 | 0.676247E+10 | 13363021.41 | 0.00 | 0.38 |
February | 0.280889E+10 | 109781.86 | 0.00 | 845719.57 | 0.00 | 0.363800E+10 | 0.457552E+09 | 0.00 | 0.43 |
March | 0.336588E+10 | 0.111515E+09 | 0.00 | 2036393.36 | 0.00 | 0.325638E+09 | 0.147657E+10 | 0.00 | 0.48 |
April | 0.138952E+10 | 0.358220E+09 | 0.00 | 2698320.33 | 12755576.80 | 15431420.74 | 0.129787E+10 | 0.00 | 0.52 |
May | 0.131737E+09 | 0.200801E+10 | 0.00 | 3020768.81 | 39240496.29 | 0.00 | 0.119487E+10 | 0.00 | 0.52 |
June | 2133910.59 | 0.639024E+10 | 0.00 | 1095429.70 | 0.105266E+09 | 0.00 | 0.259254E+09 | 0.00 | 0.43 |
July | 230331.76 | 0.842906E+10 | 0.00 | 1034962.55 | 0.194655E+09 | 0.00 | 0.253107E+09 | 0.00 | 0.41 |
August | 150233.60 | 0.956813E+10 | 0.00 | 175775.67 | 0.143796E+09 | 0.00 | 11730411.59 | 0.00 | 0.40 |
September | 47092712.43 | 0.400822E+10 | 0.00 | 2379100.34 | 0.102117E+09 | 0.00 | 0.941256E+09 | 0.00 | 0.47 |
October | 0.192028E+10 | 0.876086E+09 | 0.00 | 4557092.87 | 18618716.58 | 1275724.75 | 0.240430E+10 | 0.00 | 0.53 |
November | 0.374939E+10 | 9648488.55 | 0.00 | 2716572.59 | 11569729.98 | 0.112302E+09 | 0.203911E+10 | 0.00 | 0.50 |
December | 0.499702E+10 | 0.00 | 20079.57 | 347426.58 | 0.00 | 0.194499E+10 | 0.335050E+09 | 608.62 | 0.39 |
Annual Sum or Average | 0.213554E+11 | 0.317592E+11 | 20079.57 | 20914291.44 | 0.628019E+09 | 0.128001E+11 | 0.106840E+11 | 608.62 | 0.45 |
Minimum of Months | 150233.60 | 0.00 | 0.00 | 6729.08 | 0.00 | 0.00 | 11730411.59 | 0.00 | 0.38 |
Maximum of Months | 0.499702E+10 | 0.956813E+10 | 20079.57 | 4557092.87 | 0.194655E+09 | 0.676247E+10 | 0.240430E+10 | 608.62 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134857E+10 | 0.00 | 0.00 | 997.79 | 0.00 | 0.349236E+10 | 3517811.68 | 0.00 | 0.38 |
February | 0.133141E+10 | 61748.37 | 0.00 | 402564.11 | 0.00 | 0.188760E+10 | 0.216071E+09 | 0.00 | 0.43 |
March | 0.166721E+10 | 56010882.84 | 0.00 | 953904.23 | 0.00 | 0.188956E+09 | 0.705327E+09 | 0.00 | 0.48 |
April | 0.705510E+09 | 0.179308E+09 | 0.00 | 1322448.48 | 6495916.82 | 15531255.35 | 0.625882E+09 | 0.00 | 0.53 |
May | 68975924.86 | 0.100229E+10 | 0.00 | 1490763.23 | 19621909.43 | 0.00 | 0.604849E+09 | 0.00 | 0.53 |
June | 4464127.06 | 0.319530E+10 | 0.00 | 544318.15 | 52662603.85 | 0.00 | 0.127505E+09 | 0.00 | 0.44 |
July | 116623.03 | 0.421360E+10 | 0.00 | 510111.77 | 96975553.87 | 0.00 | 0.133986E+09 | 0.00 | 0.41 |
August | 0.00 | 0.478174E+10 | 0.00 | 81322.05 | 71572528.47 | 0.00 | 6408057.49 | 0.00 | 0.40 |
September | 24575589.19 | 0.199859E+10 | 0.00 | 1205603.10 | 50679017.32 | 0.00 | 0.482661E+09 | 0.00 | 0.48 |
October | 0.956868E+09 | 0.437155E+09 | 0.00 | 2285380.05 | 9248594.26 | 3088359.11 | 0.121148E+10 | 0.00 | 0.54 |
November | 0.185292E+10 | 4697793.07 | 0.00 | 1315493.07 | 5881150.46 | 82088921.42 | 0.100750E+10 | 0.00 | 0.50 |
December | 0.235051E+10 | 0.00 | 7512.38 | 160106.63 | 0.00 | 0.110747E+10 | 0.164534E+09 | 473.42 | 0.39 |
Annual Sum or Average | 0.103111E+11 | 0.158688E+11 | 7512.38 | 10273012.67 | 0.313137E+09 | 0.677710E+10 | 0.528973E+10 | 473.42 | 0.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 997.79 | 0.00 | 0.00 | 3517811.68 | 0.00 | 0.38 |
Maximum of Months | 0.235051E+10 | 0.478174E+10 | 7512.38 | 2285380.05 | 96975553.87 | 0.349236E+10 | 0.121148E+10 | 473.42 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357406E+10 | 0.00 | 0.00 | 0.38 |
February | 0.128706E+10 | 59083.94 | 0.00 | 372820.72 | 0.00 | 0.193147E+10 | 0.204513E+09 | 0.00 | 0.43 |
March | 0.168385E+10 | 54955096.89 | 0.00 | 874642.27 | 0.00 | 0.195631E+09 | 0.652857E+09 | 0.00 | 0.48 |
April | 0.713523E+09 | 0.175853E+09 | 0.00 | 1251163.97 | 6941256.69 | 18967925.82 | 0.594572E+09 | 0.00 | 0.52 |
May | 76204747.40 | 0.990465E+09 | 0.00 | 1445740.00 | 19583813.64 | 0.00 | 0.592419E+09 | 0.00 | 0.53 |
June | 4815668.86 | 0.318674E+10 | 0.00 | 532979.75 | 52672001.34 | 0.00 | 0.125516E+09 | 0.00 | 0.43 |
July | 116573.32 | 0.420358E+10 | 0.00 | 499251.87 | 96884732.09 | 0.00 | 0.134774E+09 | 0.00 | 0.41 |
August | 0.00 | 0.477122E+10 | 0.00 | 78828.48 | 71540545.85 | 0.00 | 6469325.57 | 0.00 | 0.40 |
September | 26363416.48 | 0.199111E+10 | 0.00 | 1182450.03 | 50578587.93 | 0.00 | 0.476540E+09 | 0.00 | 0.48 |
October | 0.953487E+09 | 0.433687E+09 | 0.00 | 2211134.78 | 9207135.73 | 7207340.60 | 0.118948E+10 | 0.00 | 0.54 |
November | 0.186215E+10 | 4419693.98 | 0.00 | 1237062.99 | 6102371.09 | 92743945.56 | 0.961575E+09 | 0.00 | 0.50 |
December | 0.228850E+10 | 0.00 | 7603.83 | 143412.04 | 0.00 | 0.117263E+10 | 0.153270E+09 | 559.00 | 0.39 |
Annual Sum or Average | 0.101640E+11 | 0.158121E+11 | 7603.83 | 9829486.90 | 0.313510E+09 | 0.699271E+10 | 0.509199E+10 | 559.00 | 0.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.228850E+10 | 0.477122E+10 | 7603.83 | 2211134.78 | 96884732.09 | 0.357406E+10 | 0.118948E+10 | 559.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.937422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389753E+10 | 0.00 | 0.00 | 0.38 |
February | 0.107324E+10 | 59833.17 | 0.00 | 311393.21 | 0.00 | 0.214585E+10 | 0.177441E+09 | 0.00 | 0.42 |
March | 0.166999E+10 | 52069511.37 | 0.00 | 704393.99 | 30812.99 | 0.249372E+09 | 0.547836E+09 | 0.00 | 0.47 |
April | 0.736937E+09 | 0.165085E+09 | 0.00 | 1072215.28 | 8002274.84 | 21578125.80 | 0.522289E+09 | 0.00 | 0.51 |
May | 0.102752E+09 | 0.966186E+09 | 0.00 | 1287920.57 | 19659649.34 | 0.00 | 0.549831E+09 | 0.00 | 0.52 |
June | 7968608.83 | 0.316925E+10 | 0.00 | 502233.68 | 52650547.24 | 0.00 | 0.118574E+09 | 0.00 | 0.43 |
July | 114882.16 | 0.418838E+10 | 0.00 | 483892.33 | 96730297.16 | 0.00 | 0.147041E+09 | 0.00 | 0.41 |
August | 0.00 | 0.476054E+10 | 0.00 | 70328.24 | 71575979.89 | 0.00 | 6712134.44 | 0.00 | 0.40 |
September | 33621372.28 | 0.197660E+10 | 0.00 | 1112779.11 | 50410037.27 | 0.00 | 0.459374E+09 | 0.00 | 0.48 |
October | 0.967539E+09 | 0.423941E+09 | 0.00 | 2025017.60 | 9061147.98 | 23548930.28 | 0.111600E+10 | 0.00 | 0.53 |
November | 0.184469E+10 | 3783048.61 | 0.00 | 1057547.56 | 6891771.63 | 0.160073E+09 | 0.856474E+09 | 0.00 | 0.49 |
December | 0.210677E+10 | 0.00 | 7700.07 | 108853.94 | 0.00 | 0.136870E+10 | 0.119839E+09 | 879.44 | 0.39 |
Annual Sum or Average | 0.948104E+10 | 0.157059E+11 | 7700.07 | 8736575.50 | 0.315013E+09 | 0.786666E+10 | 0.462141E+10 | 879.44 | 0.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.210677E+10 | 0.476054E+10 | 7700.07 | 2025017.60 | 96730297.16 | 0.389753E+10 | 0.111600E+10 | 879.44 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.347170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445597E+10 | 0.00 | 0.00 | 0.38 |
February | 0.652773E+09 | 122029.65 | 0.00 | 248836.48 | 0.00 | 0.253333E+10 | 0.153684E+09 | 0.00 | 0.43 |
March | 0.151468E+10 | 47377718.71 | 0.00 | 477889.39 | 202217.86 | 0.448733E+09 | 0.416330E+09 | 0.00 | 0.47 |
April | 0.731320E+09 | 0.144856E+09 | 0.00 | 894616.79 | 10348662.93 | 55646297.46 | 0.458525E+09 | 0.00 | 0.53 |
May | 0.119033E+09 | 0.940774E+09 | 0.00 | 1161261.77 | 19903420.42 | 0.00 | 0.538746E+09 | 0.00 | 0.53 |
June | 10745747.52 | 0.313799E+10 | 0.00 | 540202.34 | 52049848.89 | 0.00 | 0.120318E+09 | 0.00 | 0.44 |
July | 6132240.17 | 0.421758E+10 | 0.00 | 433139.41 | 96243967.07 | 0.00 | 0.169453E+09 | 0.00 | 0.41 |
August | 6820.05 | 0.478226E+10 | 0.00 | 147221.16 | 71346058.36 | 0.00 | 13915681.86 | 0.00 | 0.40 |
September | 47792872.55 | 0.198271E+10 | 0.00 | 1118012.50 | 49686087.78 | 0.00 | 0.441723E+09 | 0.00 | 0.48 |
October | 0.951151E+09 | 0.413701E+09 | 0.00 | 1994105.25 | 8688049.94 | 75174212.98 | 0.110550E+10 | 0.00 | 0.56 |
November | 0.158262E+10 | 2971171.88 | 0.00 | 899982.12 | 4594194.92 | 0.451258E+09 | 0.776730E+09 | 0.00 | 0.50 |
December | 0.145529E+10 | 0.00 | 0.00 | 79229.52 | 0.00 | 0.200196E+10 | 90042445.69 | 0.00 | 0.39 |
Annual Sum or Average | 0.741871E+10 | 0.156703E+11 | 0.00 | 7994496.71 | 0.313063E+09 | 0.100221E+11 | 0.428497E+10 | 0.00 | 0.46 |
Minimum of Months | 6820.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.158262E+10 | 0.478226E+10 | 0.00 | 1994105.25 | 96243967.07 | 0.445597E+10 | 0.110550E+10 | 0.00 | 0.56 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:34:38
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.149767E+12 | 0.295785E+11 | 0.00 | 0.662066E+11 | 0.153692E+11 |
February | 0.158893E+12 | 0.210503E+11 | 0.00 | 0.478760E+11 | 0.123272E+11 |
March | 0.253907E+12 | 0.132546E+11 | 0.00 | 0.355064E+11 | 0.162060E+11 |
April | 0.301380E+12 | 0.487847E+10 | 0.00 | 0.173814E+11 | 0.473760E+11 |
May | 0.343297E+12 | -0.380086E+10 | 0.00 | -0.408057E+10 | 0.102319E+12 |
June | 0.341562E+12 | -0.160292E+11 | 0.00 | -0.404167E+11 | 0.179870E+12 |
July | 0.330860E+12 | -0.216844E+11 | 0.00 | -0.560663E+11 | 0.215938E+12 |
August | 0.304741E+12 | -0.242896E+11 | 0.00 | -0.645940E+11 | 0.237285E+12 |
September | 0.226396E+12 | -0.959294E+10 | 0.00 | -0.206599E+11 | 0.141554E+12 |
October | 0.203468E+12 | 0.621438E+10 | 0.00 | 0.249605E+11 | 0.518003E+11 |
November | 0.134467E+12 | 0.142835E+11 | 0.00 | 0.413506E+11 | 0.104589E+11 |
December | 0.118315E+12 | 0.224475E+11 | 0.00 | 0.505605E+11 | 0.713091E+10 |
Annual Sum or Average | 0.286705E+13 | 0.363102E+11 | 0.00 | 0.980245E+11 | 0.103764E+13 |
Minimum of Months | 0.118315E+12 | -0.242896E+11 | 0.00 | -0.645940E+11 | 0.713091E+10 |