Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:34
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 08:34:27
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1614.45 | 772.35 | 772.35 |
Net Site Energy | 1614.45 | 772.35 | 772.35 |
Total Source Energy | 3775.36 | 1806.12 | 1806.12 |
Net Source Energy | 3775.36 | 1806.12 | 1806.12 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 642.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 73.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 496.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 107.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 65.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 972.30 | 642.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 642.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 73.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 496.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 100.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 107.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 65.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 642.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 73.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 496.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 100.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 107.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 65.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 285.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 117.94 | 307.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 465.14 | 307.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 285.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 117.94 | 307.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 465.14 | 307.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 972.297 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 972.297 | 100.00 |
Total On-Site and Utility Electric Sources | 972.297 | 100.00 |
Total Electricity End Uses | 972.297 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 3.67 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2384.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:34 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 20.1123 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 23.1025 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 20.9200 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 20.9200 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 20.9200 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 13.4438 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 17.2687 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 17.2687 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 20.1123 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 23.1025 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 20.9200 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 20.9200 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 20.9200 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 13.4438 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 13.5625 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 13.5625 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 13.5625 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 13.5625 | 6.19 | 4.3000 | |
Total | 2090.32 | 17.2687 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 17.2687 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 17.2687 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-JUL-13:00 | 06-FEB-12:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 241918.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 37700.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 30804.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6755.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 9698.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 93017.47 | 241918.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 241918.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 37700.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 30804.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6755.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 9698.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 696.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 233.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 318.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 340.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 206.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3079.26 | 696.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 333.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 111.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 752.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 152.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 163.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1473.11 | 333.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 333.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 111.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 752.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 152.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 163.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1473.11 | 333.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.05 |
SMSTORE1 DIRECT AIR | 1.10 |
SMSTORE2 DIRECT AIR | 1.21 |
SMSTORE3 DIRECT AIR | 1.20 |
SMSTORE4 DIRECT AIR | 1.20 |
LGSTORE2 DIRECT AIR | 1.88 |
SMSTORE5 DIRECT AIR | 1.01 |
SMSTORE6 DIRECT AIR | 1.01 |
SMSTORE7 DIRECT AIR | 0.998651 |
SMSTORE8 DIRECT AIR | 1.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 1.00 | 1.00 | 2.05 |
PSZ-AC_2:2 | 1.10 | 1.10 | 1.10 | 1.10 | 1.11 | 1.11 | 1.00 | 0.996303 | 1.11 |
PSZ-AC_3:3 | 1.21 | 1.21 | 1.21 | 1.21 | 1.21 | 1.21 | 1.00 | 1.00 | 1.21 |
PSZ-AC_4:4 | 1.20 | 1.20 | 1.20 | 1.20 | 1.20 | 1.20 | 1.00 | 1.00 | 1.20 |
PSZ-AC_5:5 | 1.20 | 1.20 | 1.20 | 1.20 | 1.20 | 1.20 | 1.00 | 1.00 | 1.20 |
PSZ-AC_6:6 | 1.88 | 1.88 | 1.88 | 1.88 | 1.93 | 1.93 | 1.00 | 0.973010 | 1.93 |
PSZ-AC_7:7 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.00 | 1.00 | 1.01 |
PSZ-AC_8:8 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.00 | 1.00 | 1.01 |
PSZ-AC_9:9 | 0.998651 | 0.998651 | 0.998651 | 0.998651 | 0.999457 | 0.999457 | 1.00 | 0.999193 | 0.999457 |
PSZ-AC_10:10 | 1.05 | 1.05 | 1.05 | 1.05 | 1.06 | 1.06 | 1.00 | 0.990411 | 1.06 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.05 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.11 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.21 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.20 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.20 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.93 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.01 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.01 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 0.999457 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.06 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.05 | 2193.57 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.11 | 1226.41 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.21 | 1336.93 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.20 | 1328.26 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.20 | 1328.14 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.93 | 2068.19 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.01 | 1120.51 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.01 | 1114.05 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.999457 | 1106.56 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1168.43 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.05 | 2.05 | 2.05 | 1.35 | 43197.06 | 63847.93 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.11 | 1.11 | 1.11 | 0.731087 | 22941.31 | 33675.94 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.21 | 1.21 | 1.21 | 0.796972 | 22535.29 | 35992.16 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.20 | 1.20 | 1.20 | 0.791805 | 22395.25 | 35817.68 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.20 | 1.20 | 1.20 | 0.791734 | 22432.00 | 35815.28 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.93 | 1.93 | 1.93 | 1.28 | 41156.14 | 60072.26 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.01 | 1.01 | 1.01 | 0.667957 | 21484.38 | 31635.26 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.01 | 1.01 | 1.01 | 0.664108 | 21392.25 | 31505.27 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.999457 | 0.999457 | 0.999457 | 0.659642 | 21270.04 | 31336.48 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 0.696524 | 22122.80 | 32375.69 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.05 | 1.02 | 1.37 | 43197.06 | 21598.53 | 0.755820 | 0.755820 |
PSZ-AC_2:2 COOLING COIL | 1.11 | 0.553854 | 0.738473 | 22941.31 | 11470.66 | 0.762860 | 0.762860 |
PSZ-AC_3:3 COOLING COIL | 1.21 | 0.603766 | 0.805020 | 22535.29 | 11267.65 | 0.800110 | 0.800110 |
PSZ-AC_4:4 COOLING COIL | 1.20 | 0.599852 | 0.799800 | 22395.25 | 11197.62 | 0.800020 | 0.800020 |
PSZ-AC_5:5 COOLING COIL | 1.20 | 0.599799 | 0.799733 | 22432.00 | 11216.00 | 0.800460 | 0.800460 |
PSZ-AC_6:6 COOLING COIL | 1.93 | 0.966401 | 1.29 | 41156.14 | 20578.07 | 0.752810 | 0.752810 |
PSZ-AC_7:7 COOLING COIL | 1.01 | 0.506028 | 0.674707 | 21484.38 | 10742.19 | 0.753690 | 0.753690 |
PSZ-AC_8:8 COOLING COIL | 1.01 | 0.503112 | 0.670813 | 21392.25 | 10696.12 | 0.753270 | 0.753270 |
PSZ-AC_9:9 COOLING COIL | 0.999460 | 0.499729 | 0.666307 | 21270.04 | 10635.02 | 0.752970 | 0.752970 |
PSZ-AC_10:10 COOLING COIL | 1.06 | 0.527670 | 0.703560 | 22122.80 | 11061.40 | 0.758320 | 0.758320 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 63847.93 |
PSZ-AC_2:2 HEATING COIL | 33675.94 |
PSZ-AC_3:3 HEATING COIL | 35992.16 |
PSZ-AC_4:4 HEATING COIL | 35817.68 |
PSZ-AC_5:5 HEATING COIL | 35815.28 |
PSZ-AC_6:6 HEATING COIL | 60072.26 |
PSZ-AC_7:7 HEATING COIL | 31635.26 |
PSZ-AC_8:8 HEATING COIL | 31505.27 |
PSZ-AC_9:9 HEATING COIL | 31336.48 |
PSZ-AC_10:10 HEATING COIL | 32375.69 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 20.112 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.412 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 23.103 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 27.403 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 20.920 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.220 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 20.920 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.220 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 20.920 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.220 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 4694.002 | 13.474 | 83.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4694.002 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 2312.850 | 6.639 | 41.117 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2312.850 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2367.672 | 13.592 | 84.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2367.672 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1656.630 | 9.510 | 58.904 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1656.630 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1281.630 | 7.358 | 45.570 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1281.630 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1281.630 | 7.358 | 45.570 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1281.630 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1281.630 | 7.358 | 45.570 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1281.630 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 4683.651 | 13.444 | 83.264 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4683.651 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5398 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1408 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2031 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.619 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.024 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.847 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.34329049E-12 | 0.74065570E-15 | -0.11060681E-12 | 0.10726285E-15 |
23 | 6 | 0.31458623E-07 | 0.15582808E-09 | 0.71832143E-08 | -0.15023289E-12 |
24 | 5 | -0.20415818E-03 | 0.13111101E-05 | -0.10480723E-03 | 0.70917048E-08 |
25 | 4 | 0.30843928 | 0.62847427E-03 | 0.10555000 | -0.35885187E-04 |
26 | 3 | -7.5886440 | 0.19208290E-01 | -2.4345797 | 0.30589548E-01 |
27 | 2 | 41.933758 | 0.67466625E-01 | 15.656649 | -0.34517733 |
28 | 1 | -81.359657 | 0.30121645E-01 | -29.492494 | 1.0959638 |
29 | 0 | 46.824334 | 0.59962785E-03 | 16.283006 | |
30 | 7 | -0.30155247E-08 | -0.19705740E-14 | 0.18469307E-14 | -0.46079768E-16 |
31 | 6 | 0.40551627E-05 | 0.26926011E-08 | 0.31944497E-02 | -0.26797721E-04 |
32 | 5 | -0.28496186E-03 | 0.15923452E-05 | -0.22398486 | 0.19584477E-02 |
33 | 4 | 0.65115693E-02 | 0.72427529E-04 | 4.8338806 | -0.45306652E-01 |
34 | 3 | -0.57046066E-01 | 0.57554694E-03 | -38.045903 | 0.39892442 |
35 | 2 | 0.20237164 | 0.95689144E-03 | 116.53161 | -1.4185768 |
36 | 1 | -0.29197338 | 0.29127682E-03 | -143.93536 | 2.0495010 |
37 | 0 | 0.14232195 | 0.70641069E-05 | 60.838472 | |
38 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
39 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
40 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
41 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
42 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
43 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
44 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
45 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
46 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
47 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
48 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
49 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
50 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
51 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
52 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
53 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
54 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521549E-14 | -0.37274185E-16 |
55 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
56 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
57 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
58 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
59 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
60 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
61 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
62 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521548E-14 | -0.37274183E-16 |
63 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
64 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
65 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
66 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
67 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
68 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
69 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
70 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
71 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
72 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
73 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
74 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
75 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
76 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
77 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
78 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274181E-16 |
79 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
80 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
81 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
82 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
83 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
84 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
85 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
86 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
87 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
88 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
89 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
90 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
91 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
92 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
93 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
94 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
95 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
96 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
97 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
98 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
99 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
100 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
101 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
102 | 7 | -0.20778300E-08 | -0.65167512E-15 | 0.79548166E-14 | -0.12010680E-15 |
103 | 6 | 0.57088823E-05 | 0.38884884E-08 | 0.31895855E-02 | -0.26756916E-04 |
104 | 5 | -0.40892418E-03 | 0.23023551E-05 | -0.22370841 | 0.19560076E-02 |
105 | 4 | 0.93961169E-02 | 0.10478953E-03 | 4.8292766 | -0.45262394E-01 |
106 | 3 | -0.82481111E-01 | 0.83319714E-03 | -38.019897 | 0.39863696 |
107 | 2 | 0.29283299 | 0.13859693E-02 | 116.48099 | -1.4178998 |
108 | 1 | -0.42263540 | 0.42218679E-03 | -143.90557 | 2.0490113 |
109 | 0 | 0.20604930 | 0.10232106E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 35 | 1 | VerySmooth | 2.375 | 2.375 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.05070E-002 | 0.31435 | 0.47518 | 0.47518 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12234 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 22689.89497 | 27227.87396 | 1.70832 | 2.04998 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.30000 | 1.33670E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 28074.96949 | 33689.96339 | 1.24125 | 1.48950 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 12552.17160 | 15062.60592 | 0.91968 | 1.10361 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 13263.20036 | 15915.84043 | 0.58640 | 0.70369 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 13700.45606 | 16440.54727 | 1.00628 | 1.20753 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18500 | 1.33579E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 13409.25647 | 16091.10776 | 0.59286 | 0.71143 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 13613.84418 | 16336.61301 | 0.99975 | 1.19970 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18500 | 1.33579E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 13484.73743 | 16181.68491 | 0.59620 | 0.71544 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 13611.82293 | 16334.18752 | 0.99966 | 1.19960 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18500 | 1.33579E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 13626.40133 | 16351.68160 | 0.60246 | 0.72296 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 21474.21734 | 25769.06081 | 1.56720 | 1.88064 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 26094.30072 | 31313.16087 | 1.15372 | 1.38447 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11532.93054 | 13839.51665 | 0.84338 | 1.01206 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 13956.63669 | 16747.96403 | 0.61706 | 0.74048 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11468.04041 | 13761.64849 | 0.83852 | 1.00622 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 13943.53662 | 16732.24394 | 0.61649 | 0.73978 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 11383.65490 | 13660.38588 | 0.83221 | 0.99865 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 14151.21150 | 16981.45380 | 0.62567 | 0.75080 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 11899.37240 | 14279.24688 | 0.87102 | 1.04522 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 17343.26413 | 20811.91695 | 0.76675 | 0.92010 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 29920.44 | 2.04998 | 2.04998 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 51355.43 | 1.48950 | 1.48950 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 16026.17 | 1.10771 | 1.10771 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 24762.21 | 0.70369 | 0.70369 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 16166.82 | 1.20753 | 1.20753 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 24934.92 | 0.71143 | 0.71143 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 16064.04 | 1.19970 | 1.19970 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 25024.18 | 0.71544 | 0.71544 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 16061.95 | 1.19960 | 1.19960 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 25191.70 | 0.72296 | 0.72296 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 28334.98 | 1.93280 | 1.93280 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 49013.59 | 1.38447 | 1.38447 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 14577.78 | 1.01206 | 1.01206 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 25582.22 | 0.74048 | 0.74048 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 14497.29 | 1.00622 | 1.00622 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 25566.73 | 0.73978 | 0.73978 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 14442.41 | 0.99946 | 0.99946 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 25812.31 | 0.75080 | 0.75080 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 15200.26 | 1.05534 | 1.05534 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 29586.68 | 0.92010 | 0.92010 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.04998 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.10361 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.20753 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.19970 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.19960 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.88064 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.01206 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00622 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99865 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04522 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.04998 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.04998 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.04998 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.04998 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.04998 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.04998 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.10361 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.10361 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.10361 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.10361 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.10771 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.10771 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.99630 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.20753 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.20753 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.20753 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20753 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.20753 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.20753 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.19970 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.19970 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.19970 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.19970 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.19970 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.19970 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.19960 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.19960 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.19960 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.19960 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.19960 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.19960 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.88064 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.88064 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.88064 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.88064 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.93280 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.93280 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 0.97301 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.01206 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.01206 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.01206 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.01206 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.01206 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.01206 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00622 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00622 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00622 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00622 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00622 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00622 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99865 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99865 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99865 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99865 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.99946 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.99946 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.99919 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04522 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04522 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04522 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04522 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05534 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05534 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 0.99041 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.04998 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.10771 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.20753 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.19970 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.19960 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.93280 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.01206 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.00622 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.99946 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.05534 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.04998 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.04998 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2193.57383 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.04998 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.04998 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.04998 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.35299 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.04998 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.02499 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.36665 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 43197.06000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21598.53000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75582 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75582 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 43197.06000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 63847.93479 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 63847.93479 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.10771 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.10771 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1226.40758 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.10771 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.10771 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.10771 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.73109 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.10771 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55385 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.73847 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22941.31000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11470.65500 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76286 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76286 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22941.31000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33675.94314 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 33675.94314 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.20753 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.20753 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1336.93057 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.20753 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.20753 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.20753 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.79697 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.20753 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.60377 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.80502 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22535.29000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11267.64500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80011 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80011 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22535.29000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35992.16313 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 35992.16313 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.19970 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.19970 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1328.26312 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.19970 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.19970 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.19970 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.79180 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.19970 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.59985 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.79980 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22395.25000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11197.62500 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80002 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80002 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22395.25000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35817.67571 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 35817.67571 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.19960 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.19960 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1328.14459 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.19960 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.19960 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.19960 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.79173 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.19960 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.59980 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.79973 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22432.00000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11216.00000 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80046 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80046 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22432.00000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35815.28159 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 35815.28159 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.93280 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.93280 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2068.18980 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.93280 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.93280 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.93280 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.27565 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.93280 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.96640 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.28853 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 41156.14000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20578.07000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75281 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75281 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 41156.14000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 60072.25546 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 60072.25546 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.01206 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.01206 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1120.50664 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.01206 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.01206 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.01206 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.66796 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.01206 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50603 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67471 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21484.38000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10742.19000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75369 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75369 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21484.38000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31635.26118 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 31635.26118 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00622 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00622 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1114.04956 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00622 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00622 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00622 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.66411 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00622 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50311 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67081 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21392.25000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10696.12500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75327 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75327 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21392.25000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31505.27254 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 31505.27254 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.99946 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.99946 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1106.55773 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.99946 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.99946 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.99946 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65964 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.99946 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49973 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66631 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21270.04000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10635.02000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75297 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75297 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21270.04000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31336.48378 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 31336.48378 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05534 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05534 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1168.42899 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05534 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05534 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05534 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69652 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05534 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52767 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70356 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22122.80000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11061.40000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75832 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75832 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22122.80000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32375.68627 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 32375.68627 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 41584.7 | 11.47 | 11.47 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 22070.3 | 11.60 | 11.60 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 21587.3 | 11.38 | 11.38 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 21453.4 | 11.38 | 11.38 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 21490.2 | 11.39 | 11.39 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 39635.6 | 11.49 | 11.49 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 20688.2 | 11.65 | 11.65 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 20600.7 | 11.65 | 11.65 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 20483.8 | 11.66 | 11.66 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 21292.8 | 11.63 | 11.63 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.141 | 0.136 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.203 | 0.194 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 3.8937990077E-002 | 0.2216011684 | Pass | Pass | 0.1457173084 | 0.7234554056 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 4.7221149093E-002 | 0.1430537808 | Pass | Pass | 0.2304540241 | 1.2987470479 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 4.1414574231E-002 | 0.2306095696 | Pass | Pass | 8.9883379711E-002 | 0.4407303276 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 4.7533087575E-002 | 0.2553461834 | Pass | Pass | 9.5344398597E-002 | 0.6415739806 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 5.2508753164E-002 | 0.2793795362 | Pass | Pass | 9.5872253543E-002 | 0.7060489700 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 6.5211574581E-002 | 0.3325730019 | Pass | Pass | 2.9236174461E-002 | 9.7534933177E-002 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 6.4858469450E-002 | 0.3348846580 | Pass | Pass | 2.7449023183E-002 | 8.7125083571E-002 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 6.6090883344E-002 | 0.3399779956 | Pass | Pass | 2.7361890826E-002 | 8.7329804058E-002 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 7.1396985831E-002 | 0.3680853095 | Pass | Pass | 2.6552465645E-002 | 8.6631777237E-002 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 0.1028705656 | 0.4148345021 | Pass | Pass | 5.6602919231E-002 | 0.3462736383 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3990.85 | 264.18 | 0.00 | 601.12 | 502.59 | 5358.76 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.197 | 0.203 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.375 | 0.401 | 0.442 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.375 | 0.401 | 0.442 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.375 | 0.401 | 0.442 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.375 | 0.401 | 0.442 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.375 | 0.401 | 0.442 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.375 | 0.401 | 0.442 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.375 | 0.401 | 0.442 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.375 | 0.401 | 0.442 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.375 | 0.401 | 0.442 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.375 | 0.401 | 0.442 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.375 | 0.401 | 0.442 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.375 | 0.401 | 0.442 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.375 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.375 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.992 | 2.839 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.992 | 2.839 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 13.4735 | 348.39 | 4694.00 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 83.90 | 0.0000 | Y | 73.93 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 6.6387 | 348.39 | 2312.85 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 42.32 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 13.5922 | 174.19 | 2367.67 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 85.39 | 0.0000 | Y | 37.95 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 9.5103 | 174.19 | 1656.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 30.31 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 30.25 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 7.3575 | 174.19 | 1281.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.76 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 30.25 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 7.3575 | 174.19 | 1281.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.76 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 30.25 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 7.3575 | 174.19 | 1281.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.76 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 13.4438 | 348.39 | 4683.65 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 54.16 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 8.6344 | 4180.64 | 36097.17 | 496.92 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 458.42 | AstronomicalClock | - | 42.04 | 42.04 | 3.62 | |
EXTERIOR_LIGHTS_B | 7264.83 | AstronomicalClock | - | 83.67 | 71.18 | 97.07 | |
Exterior Lighting Total | 7723.25 | 100.69 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 43197.06 | 32649.20 | 10547.86 | 0.76 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22941.31 | 17501.01 | 5440.30 | 0.76 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22535.29 | 18030.71 | 4504.58 | 0.80 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22395.25 | 17916.65 | 4478.60 | 0.80 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22432.00 | 17955.92 | 4476.08 | 0.80 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 41156.14 | 30982.75 | 10173.39 | 0.75 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21484.38 | 16192.56 | 5291.82 | 0.75 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21392.25 | 16114.14 | 5278.11 | 0.75 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21270.04 | 16015.70 | 5254.34 | 0.75 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22122.80 | 16776.16 | 5346.64 | 0.76 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 41584.7 | 11.47 | 11.47 | ||||
PSZ-AC_2:2 COOLING COIL | 22070.3 | 11.60 | 11.60 | ||||
PSZ-AC_3:3 COOLING COIL | 21587.3 | 11.38 | 11.38 | ||||
PSZ-AC_4:4 COOLING COIL | 21453.4 | 11.38 | 11.38 | ||||
PSZ-AC_5:5 COOLING COIL | 21490.2 | 11.39 | 11.39 | ||||
PSZ-AC_6:6 COOLING COIL | 39635.6 | 11.49 | 11.49 | ||||
PSZ-AC_7:7 COOLING COIL | 20688.2 | 11.65 | 11.65 | ||||
PSZ-AC_8:8 COOLING COIL | 20600.7 | 11.65 | 11.65 | ||||
PSZ-AC_9:9 COOLING COIL | 20483.8 | 11.66 | 11.66 | ||||
PSZ-AC_10:10 COOLING COIL | 21292.8 | 11.63 | 11.63 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 63847.93 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 33675.94 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 35992.16 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 35817.68 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 35815.28 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 60072.26 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 31635.26 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 31505.27 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 31336.48 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 32375.69 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.05 | 2193.57 | 1070.05 | 1.00 | 1.31 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.11 | 1226.41 | 1107.16 | 1.00 | 1.38 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.21 | 1336.93 | 1107.16 | 1.00 | 1.36 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.20 | 1328.26 | 1107.16 | 1.00 | 1.36 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.20 | 1328.14 | 1107.16 | 1.00 | 1.36 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.93 | 2068.19 | 1070.05 | 1.00 | 1.32 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.01 | 1120.51 | 1107.16 | 1.00 | 1.40 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.01 | 1114.05 | 1107.16 | 1.00 | 1.40 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1106.56 | 1107.16 | 1.00 | 1.40 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1168.43 | 1107.16 | 1.00 | 1.39 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 22689.89 | 27227.87 | 78.15 | 1.708 | 2.050 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 23.89 | 23.89 | 0.00966 | 30.30 | 0.01337 | 0.411 | 0.00 |
SMSTORE1 | 12552.17 | 15062.61 | 86.47 | 0.920 | 1.104 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00925 | 26.77 | 0.01336 | 0.206 | 0.00 |
SMSTORE2 | 13700.46 | 16440.55 | 94.38 | 1.006 | 1.208 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00933 | 25.18 | 0.01336 | 0.206 | 0.00 |
SMSTORE3 | 13613.84 | 16336.61 | 93.78 | 1.000 | 1.200 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00933 | 25.18 | 0.01336 | 0.206 | 0.00 |
SMSTORE4 | 13611.82 | 16334.19 | 93.77 | 1.000 | 1.200 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00935 | 25.18 | 0.01336 | 0.206 | 0.00 |
LGSTORE2 | 21474.22 | 25769.06 | 73.97 | 1.567 | 1.881 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00949 | 26.77 | 0.01336 | 0.411 | 0.00 |
SMSTORE5 | 11532.93 | 13839.52 | 79.45 | 0.843 | 1.012 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00940 | 26.77 | 0.01336 | 0.206 | 0.00 |
SMSTORE6 | 11468.04 | 13761.65 | 79.00 | 0.839 | 1.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00942 | 26.77 | 0.01336 | 0.206 | 0.00 |
SMSTORE7 | 11383.65 | 13660.39 | 78.42 | 0.832 | 0.999 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00944 | 26.77 | 0.01336 | 0.206 | 0.00 |
SMSTORE8 | 11899.37 | 14279.25 | 81.97 | 0.871 | 1.045 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00949 | 26.77 | 0.01336 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 28074.97 | 33689.96 | 96.70 | 1.241 | 1.489 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00656 | -16.30 | 0.00092 | 0.411 | 0.00 |
SMSTORE1 | 13263.20 | 15915.84 | 91.37 | 0.586 | 0.704 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00649 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE2 | 13409.26 | 16091.11 | 92.38 | 0.593 | 0.711 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00650 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE3 | 13484.74 | 16181.68 | 92.90 | 0.596 | 0.715 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00650 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE4 | 13626.40 | 16351.68 | 93.87 | 0.602 | 0.723 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00651 | -16.30 | 0.00092 | 0.206 | 0.00 |
LGSTORE2 | 26094.30 | 31313.16 | 89.88 | 1.154 | 1.384 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00659 | -16.30 | 0.00092 | 0.411 | 0.00 |
SMSTORE5 | 13956.64 | 16747.96 | 96.15 | 0.617 | 0.740 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00654 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE6 | 13943.54 | 16732.24 | 96.06 | 0.616 | 0.740 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00654 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE7 | 14151.21 | 16981.45 | 97.49 | 0.626 | 0.751 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00655 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE8 | 17343.26 | 20811.92 | 119.48 | 0.767 | 0.920 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00659 | -16.30 | 0.00092 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.05 | 2.05 | 1.49 | 1.49 | 2.0500 | 2.0500 | 2.0500 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.11 | 1.11 | 0.70 | 0.70 | 1.1077 | 1.1036 | 1.1077 | 0.9963 | 1.0000 |
PSZ-AC_3:3 | 1.21 | 1.21 | 0.71 | 0.71 | 1.2075 | 1.2075 | 1.2075 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.20 | 1.20 | 0.72 | 0.72 | 1.1997 | 1.1997 | 1.1997 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.20 | 1.20 | 0.72 | 0.72 | 1.1996 | 1.1996 | 1.1996 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.93 | 1.93 | 1.38 | 1.38 | 1.9328 | 1.8806 | 1.9328 | 0.9730 | 1.0000 |
PSZ-AC_7:7 | 1.01 | 1.01 | 0.74 | 0.74 | 1.0121 | 1.0121 | 1.0121 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.01 | 1.01 | 0.74 | 0.74 | 1.0062 | 1.0062 | 1.0062 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.00 | 1.00 | 0.75 | 0.75 | 0.9995 | 0.9987 | 0.9995 | 0.9992 | 1.0000 |
PSZ-AC_10:10 | 1.06 | 1.06 | 0.92 | 0.92 | 1.0553 | 1.0452 | 1.0553 | 0.9904 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 43197.060 | 32649.202 | 2.049980 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21598.53 | 16354.15 | 1.366653 | 26.06 | 18.38 | 0.01040626 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 30.1085 | 23.89 | 0.00966273 | 50.9655 | 22689.89 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 63847.935 | 63847.935 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 63847.93 | 63847.93 | 2.049978 | 13.60 | 9.00 | 0.00542745 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 20.0723 | 21.10 | 0.00655838 | 41.1660 | 28074.97 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 22941.310 | 17501.008 | 1.107710 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 11470.66 | 8801.07 | 0.738473 | 26.00 | 18.28 | 0.01029547 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 27.8601 | 23.89 | 0.00959392 | 50.6076 | 12247.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 33675.943 | 33675.943 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 33675.94 | 33675.94 | 1.107707 | 14.16 | 9.28 | 0.00545335 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 18.5734 | 21.10 | 0.00648647 | 40.7187 | 13263.20 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 22535.290 | 18030.711 | 1.207530 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11267.65 | 8845.16 | 0.805020 | 25.07 | 17.75 | 0.01002041 | 12.80 | 11.87 | 0.00850000 | 25.18 | 0.01335791 | 20.33 | 25.5571 | 23.89 | 0.00933498 | 49.2618 | 12210.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 35992.163 | 35992.163 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35992.16 | 35992.16 | 1.207533 | 14.73 | 9.63 | 0.00554833 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 17.0380 | 21.10 | 0.00649802 | 40.7904 | 13409.26 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 22395.250 | 17916.648 | 1.199700 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11197.62 | 8788.57 | 0.799800 | 25.07 | 17.76 | 0.01002187 | 12.80 | 11.87 | 0.00850000 | 25.18 | 0.01335791 | 20.33 | 25.7239 | 23.89 | 0.00933135 | 49.2426 | 12241.59 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 35817.676 | 35817.676 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35817.68 | 35817.68 | 1.199704 | 14.69 | 9.61 | 0.00554695 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 17.1492 | 21.10 | 0.00650382 | 40.8265 | 13484.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 22432.000 | 17955.919 | 1.199600 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11216.00 | 8786.73 | 0.799733 | 25.07 | 17.77 | 0.01003491 | 12.80 | 11.87 | 0.00850000 | 25.18 | 0.01335791 | 20.33 | 25.7260 | 23.89 | 0.00934701 | 49.3245 | 12135.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 35815.282 | 35815.282 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35815.28 | 35815.28 | 1.199597 | 14.69 | 9.62 | 0.00555594 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 17.1507 | 21.10 | 0.00651478 | 40.8946 | 13626.40 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 41156.140 | 30982.754 | 1.932800 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 20578.07 | 15484.68 | 1.288533 | 26.14 | 18.46 | 0.01046589 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 31.9339 | 23.89 | 0.00967910 | 51.0499 | 21348.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 60072.255 | 60072.255 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 60072.26 | 60072.26 | 1.932802 | 13.14 | 8.74 | 0.00538327 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 21.2892 | 21.10 | 0.00658937 | 41.3568 | 26094.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 21484.380 | 16192.562 | 1.012060 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 10742.19 | 8092.14 | 0.674707 | 26.13 | 18.45 | 0.01045565 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 30.4932 | 23.89 | 0.00969745 | 51.1453 | 11021.28 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 31635.261 | 31635.261 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31635.26 | 31635.26 | 1.012056 | 13.50 | 8.92 | 0.00539810 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 20.3289 | 21.10 | 0.00653969 | 41.0493 | 13956.64 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 21392.250 | 16114.140 | 1.006220 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 10696.12 | 8048.65 | 0.670813 | 26.14 | 18.46 | 0.01046538 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 30.6701 | 23.89 | 0.00970378 | 51.1782 | 10953.15 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 31505.273 | 31505.273 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31505.27 | 31505.27 | 1.006224 | 13.46 | 8.89 | 0.00539074 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 20.4467 | 21.10 | 0.00653875 | 41.0434 | 13943.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 21270.040 | 16015.702 | 0.999460 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 10635.02 | 7996.68 | 0.666307 | 26.15 | 18.46 | 0.01047206 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 30.8776 | 23.89 | 0.00970813 | 51.2007 | 10906.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 31336.484 | 31336.484 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31336.48 | 31336.48 | 0.999457 | 13.41 | 8.87 | 0.00539489 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 20.5851 | 21.10 | 0.00655377 | 41.1368 | 14151.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 22122.800 | 16776.162 | 1.055340 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 11061.40 | 8335.82 | 0.703560 | 25.97 | 18.37 | 0.01043171 | 12.80 | 11.87 | 0.00850000 | 29.84 | 0.01336614 | 21.70 | 29.2426 | 23.89 | 0.00971823 | 51.2538 | 11623.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 32375.686 | 32375.686 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32375.69 | 32375.69 | 1.055340 | 13.81 | 9.16 | 0.00548448 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 19.4951 | 21.10 | 0.00658882 | 41.3575 | 17343.26 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 43197.060 | 32649.202 | 2.049980 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1847 | 1004.8586 | 1.1739 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.049978 | 2.40652158 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | Sensible | 21598.53 | 16354.15 | 1.0000 | 1.60434894 | 1.366653 | 26.06 | 18.38 | 0.01040626 | 52718.7 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21598.53 | 30.30 | 0.01336696 | 21.83 | 0.41147883 | 30.1085 | 23.89 | 0.00966273 | 23.89 | 0.00966273 | 50.9655 | 22689.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 63847.935 | 63847.935 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.049978 | 2.40652158 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 63847.93 | 63847.93 | 1.0000 | 2.40652158 | 2.049978 | 13.60 | 9.00 | 0.00542745 | 27373.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 63847.93 | -16.30 | 0.00092409 | -16.30 | 0.41147883 | 20.0723 | 21.11 | 0.00655838 | 21.10 | 0.00655838 | 41.1660 | 28074.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22941.310 | 17501.008 | 1.107710 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9788 | 1004.8586 | 1.1739 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.107707 | 1.30036539 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 11470.66 | 8801.07 | 1.0000 | 0.86691254 | 0.738473 | 26.00 | 18.28 | 0.01029547 | 52371.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11470.66 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 27.8601 | 23.89 | 0.00959392 | 23.89 | 0.00959392 | 50.6076 | 12247.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33675.943 | 33675.943 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.107707 | 1.30036539 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 33675.94 | 33675.94 | 1.0000 | 1.30036539 | 1.107707 | 14.16 | 9.28 | 0.00545335 | 28008.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33675.94 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 18.5734 | 21.11 | 0.00648647 | 21.10 | 0.00648647 | 40.7187 | 13263.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22535.290 | 18030.711 | 1.207530 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4674 | 1004.8586 | 1.1739 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.207533 | 1.41755341 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 11267.65 | 8845.16 | 1.0000 | 0.94503336 | 0.805020 | 25.07 | 17.75 | 0.01002041 | 50719.9 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11267.65 | 25.18 | 0.01335791 | 20.33 | 0.20573941 | 25.5571 | 23.94 | 0.00933498 | 23.89 | 0.00933498 | 49.2618 | 12210.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35992.163 | 35992.163 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.207533 | 1.41755341 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 35992.16 | 35992.16 | 1.0000 | 1.41755341 | 1.207533 | 14.73 | 9.63 | 0.00554833 | 28831.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35992.16 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 17.0380 | 21.11 | 0.00649802 | 21.10 | 0.00649802 | 40.7904 | 13409.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22395.250 | 17916.648 | 1.199700 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4702 | 1004.8586 | 1.1739 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.199704 | 1.40836327 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 11197.62 | 8788.57 | 1.0000 | 0.93890547 | 0.799800 | 25.07 | 17.76 | 0.01002187 | 50725.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11197.62 | 25.18 | 0.01335791 | 20.33 | 0.20573941 | 25.7239 | 23.94 | 0.00933135 | 23.89 | 0.00933135 | 49.2426 | 12241.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35817.676 | 35817.676 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.199704 | 1.40836327 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 35817.68 | 35817.68 | 1.0000 | 1.40836327 | 1.199704 | 14.69 | 9.61 | 0.00554695 | 28786.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35817.68 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 17.1492 | 21.11 | 0.00650382 | 21.10 | 0.00650382 | 40.8265 | 13484.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22432.000 | 17955.919 | 1.199600 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4944 | 1004.8586 | 1.1739 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.199597 | 1.40823759 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 11216.00 | 8786.73 | 1.0000 | 0.93882720 | 0.799733 | 25.07 | 17.77 | 0.01003491 | 50757.8 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11216.00 | 25.18 | 0.01335791 | 20.33 | 0.20573941 | 25.7260 | 23.94 | 0.00934701 | 23.89 | 0.00934701 | 49.3245 | 12135.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35815.282 | 35815.282 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.199597 | 1.40823759 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 35815.28 | 35815.28 | 1.0000 | 1.40823759 | 1.199597 | 14.69 | 9.62 | 0.00555594 | 28808.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35815.28 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 17.1507 | 21.11 | 0.00651478 | 21.10 | 0.00651478 | 40.8946 | 13626.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 41156.140 | 30982.754 | 1.932800 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2956 | 1004.8586 | 1.1739 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.932802 | 2.26896552 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 20578.07 | 15484.68 | 1.0000 | 1.51264190 | 1.288533 | 26.14 | 18.46 | 0.01046589 | 52953.7 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20578.07 | 30.30 | 0.01336696 | 21.83 | 0.41147883 | 31.9339 | 23.89 | 0.00967910 | 23.89 | 0.00967910 | 51.0499 | 21348.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 60072.255 | 60072.255 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.932802 | 2.26896552 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 60072.26 | 60072.26 | 1.0000 | 2.26896552 | 1.932802 | 13.14 | 8.74 | 0.00538327 | 26800.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 60072.26 | -16.30 | 0.00092409 | -16.30 | 0.41147883 | 21.2892 | 21.11 | 0.00658937 | 21.10 | 0.00658937 | 41.3568 | 26094.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21484.380 | 16192.562 | 1.012060 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2765 | 1004.8586 | 1.1739 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.012056 | 1.18807816 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | Sensible | 10742.19 | 8092.14 | 1.0000 | 0.79205524 | 0.674707 | 26.13 | 18.45 | 0.01045565 | 52915.0 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10742.19 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 30.4932 | 23.89 | 0.00969745 | 23.89 | 0.00969745 | 51.1453 | 11021.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31635.261 | 31635.261 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.012056 | 1.18807816 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31635.26 | 31635.26 | 1.0000 | 1.18807816 | 1.012056 | 13.50 | 8.92 | 0.00539810 | 27202.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31635.26 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 20.3289 | 21.11 | 0.00653969 | 21.10 | 0.00653969 | 41.0493 | 13956.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21392.250 | 16114.140 | 1.006220 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2946 | 1004.8586 | 1.1739 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.006224 | 1.18123168 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | Sensible | 10696.12 | 8048.65 | 1.0000 | 0.78748475 | 0.670813 | 26.14 | 18.46 | 0.01046538 | 52948.3 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10696.12 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 30.6701 | 23.89 | 0.00970378 | 23.89 | 0.00970378 | 51.1782 | 10953.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31505.273 | 31505.273 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.006224 | 1.18123168 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31505.27 | 31505.27 | 1.0000 | 1.18123168 | 1.006224 | 13.46 | 8.89 | 0.00539074 | 27139.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31505.27 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 20.4467 | 21.11 | 0.00653875 | 21.10 | 0.00653875 | 41.0434 | 13943.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21270.040 | 16015.702 | 0.999460 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3070 | 1004.8586 | 1.1739 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.999457 | 1.17328806 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 10635.02 | 7996.68 | 1.0000 | 0.78219426 | 0.666307 | 26.15 | 18.46 | 0.01047206 | 52971.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10635.02 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 30.8776 | 23.89 | 0.00970813 | 23.89 | 0.00970813 | 51.2007 | 10906.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31336.484 | 31336.484 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.999457 | 1.17328806 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31336.48 | 31336.48 | 1.0000 | 1.17328806 | 0.999457 | 13.41 | 8.87 | 0.00539489 | 27097.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31336.48 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 20.5851 | 21.11 | 0.00655377 | 21.10 | 0.00655377 | 41.1368 | 14151.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22122.800 | 16776.162 | 1.055340 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2320 | 1004.8586 | 1.1739 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.055340 | 1.23889043 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 11061.40 | 8335.82 | 1.0000 | 0.82592689 | 0.703560 | 25.97 | 18.37 | 0.01043171 | 52688.8 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11061.40 | 29.84 | 0.01336614 | 21.70 | 0.20573941 | 29.2426 | 23.89 | 0.00971823 | 23.89 | 0.00971823 | 51.2538 | 11623.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32375.686 | 32375.686 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.055340 | 1.23889043 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 32375.69 | 32375.69 | 1.0000 | 1.23889043 | 1.055340 | 13.81 | 9.16 | 0.00548448 | 27736.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32375.69 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 19.4951 | 21.10 | 0.00658882 | 21.10 | 0.00658882 | 41.3575 | 17343.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.05 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.11 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.21 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.20 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.20 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.93 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.01 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.01 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.00 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.06 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3028.83 | 3848.17 | 1605.00 |
SMSTORE1 | 2297.17 | 3494.33 | 723.00 |
SMSTORE2 | 2112.17 | 2821.00 | 968.17 |
SMSTORE3 | 2164.67 | 2852.67 | 1047.00 |
SMSTORE4 | 2201.00 | 2914.33 | 1144.33 |
LGSTORE2 | 2176.17 | 2777.50 | 1307.33 |
SMSTORE5 | 2127.00 | 2817.17 | 1324.83 |
SMSTORE6 | 2138.00 | 2840.00 | 1354.83 |
SMSTORE7 | 2206.67 | 2909.17 | 1460.00 |
SMSTORE8 | 2446.00 | 3024.17 | 1766.50 |
Facility | 3871.17 | 4359.67 | 2384.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 11.17 | 0.00 | 3.67 | 0.00 |
SMSTORE1 | 0.83 | 0.00 | 0.17 | 0.00 |
SMSTORE2 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 1.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 7.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 6.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 6.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 9.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 40.00 | 0.00 | 0.00 | 0.00 |
Facility | 48.50 | 0.00 | 3.67 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 1.036 | 0.241 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.917 | 0.252 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 1.119 | 0.328 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 1.111 | 0.328 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 1.100 | 0.328 | 0.000 | 0.000 |
LGSTORE2 | 24.80 | 56.25 | 1805.20 | 1.017 | 0.316 | 0.000 | 0.000 |
SMSTORE5 | 12.40 | 28.12 | 902.60 | 1.030 | 0.350 | 0.000 | 0.000 |
SMSTORE6 | 12.40 | 28.12 | 902.60 | 1.024 | 0.350 | 0.000 | 0.000 |
SMSTORE7 | 12.40 | 28.12 | 902.60 | 1.013 | 0.350 | 0.000 | 0.000 |
SMSTORE8 | 12.40 | 28.12 | 902.60 | 1.013 | 0.377 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.80 | 56.25 | 1805.20 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.40 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.40 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.40 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.40 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.80 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 121.06 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 10784852.01 | 0.00 | 10784852.01 | 2993858.48 | 13778710.49 | 12976396.34 | 3143.94 | 4092.08 | 1523.97 | 25.40 |
SMSTORE1 | 4776698.30 | 0.00 | 4776698.30 | 1454836.47 | 6231534.77 | 6488198.17 | 4287.48 | 2918.81 | 1553.71 | 28.32 |
SMSTORE2 | 4460676.39 | 0.00 | 4460676.39 | 1502250.16 | 5962926.55 | 6488198.17 | 4317.25 | 3318.08 | 1124.67 | 112.35 |
SMSTORE3 | 4429917.30 | 0.00 | 4429917.30 | 1502250.16 | 5932167.46 | 6488198.17 | 4317.43 | 3347.00 | 1095.57 | 108.65 |
SMSTORE4 | 4377291.31 | 0.00 | 4377291.31 | 1502250.16 | 5879541.46 | 6488198.17 | 4320.47 | 3393.83 | 1045.70 | 99.34 |
LGSTORE2 | 7412164.49 | 0.00 | 7412164.49 | 2777494.96 | 10189659.46 | 12976396.34 | 4691.70 | 3158.17 | 910.13 | 83.10 |
SMSTORE5 | 3752220.10 | 0.00 | 3752220.10 | 1515968.53 | 5268188.64 | 6488198.17 | 4692.16 | 3166.92 | 900.92 | 81.75 |
SMSTORE6 | 3729779.37 | 0.00 | 3729779.37 | 1515968.53 | 5245747.90 | 6488198.17 | 4693.23 | 3184.33 | 882.44 | 78.43 |
SMSTORE7 | 3683254.13 | 0.00 | 3683254.13 | 1515968.53 | 5199222.66 | 6488198.17 | 4696.44 | 3222.33 | 841.23 | 70.36 |
SMSTORE8 | 3668513.30 | 0.00 | 3668513.30 | 1946294.26 | 5614807.56 | 6488198.17 | 4705.90 | 3287.83 | 766.27 | 55.29 |
Total Facility | 51075366.71 | 0.00 | 51075366.71 | 18227140.23 | 69302506.94 | 77858378.04 | 4708.16 | 4646.89 | 1840.30 | 217.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.5110 | 0.0000 | 0.5110 | 0.1189 | 0.6299 | 0.4115 | 236.02 | 4091.58 | 1512.39 |
SMSTORE1 | 0.2259 | 0.0000 | 0.2259 | 0.0623 | 0.2882 | 0.2057 | 1382.74 | 2918.81 | 1538.45 |
SMSTORE2 | 0.2758 | 0.0000 | 0.2758 | 0.0811 | 0.3568 | 0.2057 | 0.00 | 3317.67 | 1077.33 |
SMSTORE3 | 0.2739 | 0.0000 | 0.2739 | 0.0811 | 0.3550 | 0.2057 | 0.00 | 3345.92 | 1049.08 |
SMSTORE4 | 0.2710 | 0.0000 | 0.2710 | 0.0811 | 0.3521 | 0.2057 | 0.00 | 3393.17 | 1001.83 |
LGSTORE2 | 0.5017 | 0.0000 | 0.5017 | 0.1559 | 0.6576 | 0.4115 | 0.00 | 3157.67 | 872.33 |
SMSTORE5 | 0.2539 | 0.0000 | 0.2539 | 0.0864 | 0.3403 | 0.2057 | 0.00 | 3166.92 | 863.08 |
SMSTORE6 | 0.2526 | 0.0000 | 0.2526 | 0.0864 | 0.3390 | 0.2057 | 0.00 | 3184.00 | 846.00 |
SMSTORE7 | 0.2498 | 0.0000 | 0.2498 | 0.0864 | 0.3362 | 0.2057 | 0.00 | 3222.00 | 808.00 |
SMSTORE8 | 0.2498 | 0.0000 | 0.2498 | 0.0931 | 0.3429 | 0.2057 | 0.00 | 3287.33 | 742.67 |
Total Facility | 3.0654 | 0.0000 | 3.0654 | 0.9327 | 3.9981 | 2.4689 | 1482.91 | 4643.23 | 1801.16 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 14863039.80 | 0.00 | 14863039.80 | 12976396.34 | 3135.83 | 0.67 | 5623.51 | 25.40 |
PSZ-AC_2:2 | 6582908.79 | 0.00 | 6582908.79 | 6488198.17 | 4215.96 | 3.67 | 4540.37 | 28.32 |
PSZ-AC_3:3 | 6147398.52 | 0.00 | 6147398.52 | 6488198.17 | 4305.48 | 0.83 | 4453.68 | 112.35 |
PSZ-AC_4:4 | 6105010.63 | 0.00 | 6105010.63 | 6488198.17 | 4306.78 | 0.83 | 4452.38 | 108.49 |
PSZ-AC_5:5 | 6032484.19 | 0.00 | 6032484.19 | 6488198.17 | 4310.94 | 0.50 | 4448.56 | 99.34 |
PSZ-AC_6:6 | 10215052.59 | 0.00 | 10215052.59 | 12976396.34 | 4685.15 | 0.50 | 4074.35 | 83.10 |
PSZ-AC_7:7 | 5171093.00 | 0.00 | 5171093.00 | 6488198.17 | 4684.71 | 0.17 | 4075.12 | 81.41 |
PSZ-AC_8:8 | 5140165.68 | 0.00 | 5140165.68 | 6488198.17 | 4685.78 | 0.42 | 4073.80 | 78.09 |
PSZ-AC_9:9 | 5076035.51 | 0.00 | 5076035.51 | 6488198.17 | 4690.19 | 0.17 | 4069.64 | 70.20 |
PSZ-AC_10:10 | 5055659.11 | 0.00 | 5055659.11 | 6488198.17 | 4701.32 | 0.41 | 4058.27 | 55.12 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.7042 | 0.0000 | 0.7042 | 0.4115 | 230.66 | 0.58 | 5608.76 |
PSZ-AC_2:2 | 0.3113 | 0.0000 | 0.3113 | 0.2057 | 1312.75 | 3.67 | 4523.58 |
PSZ-AC_3:3 | 0.3800 | 0.0000 | 0.3800 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3775 | 0.0000 | 0.3775 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3735 | 0.0000 | 0.3735 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.6915 | 0.0000 | 0.6915 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3499 | 0.0000 | 0.3499 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3481 | 0.0000 | 0.3481 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3443 | 0.0000 | 0.3443 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.3443 | 0.0000 | 0.3443 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5114.69 | 553.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4063.53 | 898.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4029.20 | 478.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4053.95 | 449.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4069.34 | 425.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3819.02 | 294.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3811.17 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3818.85 | 289.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3823.52 | 276.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3824.26 | 260.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.7147 | 0.8656 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.3682 | 0.3698 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3675 | 0.5113 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3656 | 0.5119 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3617 | 0.5145 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6791 | 0.8961 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3429 | 0.4620 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3415 | 0.4575 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3379 | 0.4547 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3374 | 0.4669 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 759 |
Defaulted Fields | 823 |
Fields with Defaults | 2681 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 972.30 | 3274.06 | 01-JAN-08:00 | 93017.47 | 21-JUL-14:00 |
Electricity:Building | 625.08 | 2063.06 | 01-JAN-00:10 | 38863.50 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 142.50 | 391.26 | 01-JAN-00:10 | 7378.51 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 625.08 | 2063.06 | 01-JAN-00:10 | 38863.50 | 01-JAN-11:10 |
InteriorLights:Electricity | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 116.25 | 317.63 | 01-JAN-00:10 | 6035.26 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 116.25 | 317.63 | 01-JAN-00:10 | 6035.26 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 81.39 | 223.36 | 01-JAN-00:10 | 4215.80 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 68.27 | 186.54 | 01-JAN-00:10 | 3544.17 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 68.27 | 186.54 | 01-JAN-00:10 | 3544.17 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 59.43 | 204.26 | 01-JAN-00:10 | 3853.00 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 59.43 | 204.26 | 01-JAN-00:10 | 3853.00 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 59.43 | 204.26 | 01-JAN-00:10 | 3853.00 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 73.33 | 274.94 | 01-JAN-00:10 | 5168.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 54.16 | 201.30 | 01-JAN-00:10 | 3825.14 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 54.16 | 201.30 | 01-JAN-00:10 | 3825.14 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 972.30 | 3274.06 | 01-JAN-08:00 | 93017.47 | 21-JUL-14:00 |
ElectricityPurchased:Plant | 972.30 | 3274.06 | 01-JAN-08:00 | 93017.47 | 21-JUL-14:00 |
Cogeneration:ElectricityPurchased | 972.30 | 3274.06 | 01-JAN-08:00 | 93017.47 | 21-JUL-14:00 |
General:Cogeneration:ElectricityPurchased | 972.30 | 3274.06 | 01-JAN-08:00 | 93017.47 | 21-JUL-14:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 972.30 | 3274.06 | 01-JAN-08:00 | 93017.47 | 21-JUL-14:00 |
ElectricityNet:Plant | 972.30 | 3274.06 | 01-JAN-08:00 | 93017.47 | 21-JUL-14:00 |
Cogeneration:ElectricityNet | 972.30 | 3274.06 | 01-JAN-08:00 | 93017.47 | 21-JUL-14:00 |
General:Cogeneration:ElectricityNet | 972.30 | 3274.06 | 01-JAN-08:00 | 93017.47 | 21-JUL-14:00 |
Electricity:HVAC | 181.48 | 0.00 | 01-JAN-00:10 | 46487.47 | 15-JUL-14:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 73.81 | 0.00 | 01-JAN-00:10 | 39264.14 | 15-JUL-14:00 |
General:Cooling:Electricity | 73.81 | 0.00 | 01-JAN-00:10 | 39264.14 | 15-JUL-14:00 |
Fans:Electricity | 107.67 | 0.00 | 01-JAN-00:10 | 9732.09 | 06-FEB-12:10 |
General:Fans:Electricity | 107.67 | 0.00 | 01-JAN-00:10 | 9732.09 | 06-FEB-12:10 |
ExteriorLights:Electricity | 100.69 | 0.00 | 01-JAN-08:00 | 7723.25 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 100.69 | 0.00 | 01-JAN-08:00 | 7723.25 | 01-JAN-06:10 |
Electricity:Plant | 65.06 | 1211.00 | 06-JAN-00:20 | 12753.28 | 08-JAN-14:00 |
WaterSystems:Electricity | 65.06 | 1211.00 | 06-JAN-00:20 | 12753.28 | 08-JAN-14:00 |
Water Heater:WaterSystems:Electricity | 65.06 | 1211.00 | 06-JAN-00:20 | 12753.28 | 08-JAN-14:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 642.16 | 0.00 | 01-JAN-00:10 | 241918.43 | 06-FEB-12:10 |
NaturalGas:HVAC | 642.16 | 0.00 | 01-JAN-00:10 | 241918.43 | 06-FEB-12:10 |
Heating:NaturalGas | 642.16 | 0.00 | 01-JAN-00:10 | 241918.43 | 06-FEB-12:10 |
General:Heating:NaturalGas | 642.16 | 0.00 | 01-JAN-00:10 | 241918.43 | 06-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1339.41 | 0.00 | 01-JAN-00:10 | 362291.35 | 07-FEB-08:10 |
EnergyTransfer:Building | 525.33 | 0.00 | 01-JAN-00:10 | 169679.21 | 07-FEB-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 105.94 | 0.00 | 01-JAN-00:10 | 34086.18 | 07-FEB-08:10 |
Heating:EnergyTransfer | 167.45 | 0.00 | 01-JAN-00:10 | 169679.21 | 07-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 24.62 | 0.00 | 01-JAN-00:10 | 34086.18 | 07-FEB-08:10 |
General:Heating:EnergyTransfer | 167.45 | 0.00 | 01-JAN-00:10 | 169679.21 | 07-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 24.62 | 0.00 | 01-JAN-00:10 | 34086.18 | 07-FEB-08:10 |
Cooling:EnergyTransfer | 357.88 | 0.00 | 01-JAN-00:10 | 88815.63 | 21-JUL-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 81.32 | 0.00 | 01-JAN-00:10 | 14913.92 | 21-JUL-13:00 |
General:Cooling:EnergyTransfer | 357.88 | 0.00 | 01-JAN-00:10 | 88815.63 | 21-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 81.32 | 0.00 | 01-JAN-00:10 | 14913.92 | 21-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE1 | 53.96 | 0.00 | 01-JAN-00:10 | 13490.63 | 07-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 7.27 | 0.00 | 01-JAN-00:10 | 13490.63 | 07-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 7.27 | 0.00 | 01-JAN-00:10 | 13490.63 | 07-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 46.69 | 0.00 | 01-JAN-00:10 | 9833.16 | 27-AUG-17:30 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 46.69 | 0.00 | 01-JAN-00:10 | 9833.16 | 27-AUG-17:30 |
EnergyTransfer:Zone:SMSTORE2 | 42.94 | 0.00 | 01-JAN-00:10 | 14502.11 | 07-FEB-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 9.54 | 0.00 | 01-JAN-00:10 | 14498.56 | 07-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 9.54 | 0.00 | 01-JAN-00:10 | 14498.56 | 07-FEB-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 33.40 | 0.00 | 01-JAN-00:10 | 7797.91 | 21-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 33.40 | 0.00 | 01-JAN-00:10 | 7797.91 | 21-JUL-13:40 |
EnergyTransfer:Zone:SMSTORE3 | 42.95 | 0.00 | 01-JAN-00:10 | 15565.98 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 10.51 | 0.00 | 01-JAN-00:10 | 15565.98 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 10.51 | 0.00 | 01-JAN-00:10 | 15565.98 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 32.44 | 0.00 | 01-JAN-00:10 | 7806.57 | 21-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 32.44 | 0.00 | 01-JAN-00:10 | 7806.57 | 21-JUL-13:40 |
EnergyTransfer:Zone:SMSTORE4 | 42.28 | 0.00 | 01-JAN-00:10 | 16480.28 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 12.02 | 0.00 | 01-JAN-00:10 | 16480.28 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 12.02 | 0.00 | 01-JAN-00:10 | 16480.28 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 30.26 | 0.00 | 01-JAN-00:10 | 7663.04 | 21-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 30.26 | 0.00 | 01-JAN-00:10 | 7663.04 | 21-JUL-13:40 |
EnergyTransfer:Zone:LGSTORE2 | 72.91 | 0.00 | 01-JAN-00:10 | 33103.07 | 07-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 25.88 | 0.00 | 01-JAN-00:10 | 33103.07 | 07-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 25.88 | 0.00 | 01-JAN-00:10 | 33103.07 | 07-FEB-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 47.04 | 0.00 | 01-JAN-00:10 | 13730.12 | 21-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 47.04 | 0.00 | 01-JAN-00:10 | 13730.12 | 21-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE5 | 38.33 | 0.00 | 01-JAN-00:10 | 16912.53 | 07-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 14.84 | 0.00 | 01-JAN-00:10 | 16912.53 | 07-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 14.84 | 0.00 | 01-JAN-00:10 | 16912.53 | 07-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 23.48 | 0.00 | 01-JAN-00:10 | 7115.30 | 21-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 23.48 | 0.00 | 01-JAN-00:10 | 7115.30 | 21-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE6 | 38.14 | 0.00 | 01-JAN-00:10 | 16945.03 | 13-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 15.30 | 0.00 | 01-JAN-00:10 | 16945.03 | 13-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 15.30 | 0.00 | 01-JAN-00:10 | 16945.03 | 13-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 22.85 | 0.00 | 01-JAN-00:10 | 7058.86 | 21-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 22.85 | 0.00 | 01-JAN-00:10 | 7058.86 | 21-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE7 | 38.78 | 0.00 | 01-JAN-00:10 | 17472.94 | 21-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 17.48 | 0.00 | 01-JAN-00:10 | 17472.94 | 21-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 17.48 | 0.00 | 01-JAN-00:10 | 17472.94 | 21-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 21.31 | 0.00 | 01-JAN-00:10 | 7012.57 | 21-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 21.31 | 0.00 | 01-JAN-00:10 | 7012.57 | 21-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE8 | 49.10 | 0.00 | 01-JAN-00:10 | 20587.87 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 30.00 | 0.00 | 01-JAN-00:10 | 20587.87 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 30.00 | 0.00 | 01-JAN-00:10 | 20587.87 | 06-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 19.10 | 0.00 | 01-JAN-00:10 | 7651.62 | 21-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 19.10 | 0.00 | 01-JAN-00:10 | 7651.62 | 21-JUL-13:00 |
EnergyTransfer:HVAC | 814.07 | 0.00 | 01-JAN-00:10 | 193534.74 | 06-FEB-12:10 |
HeatingCoils:EnergyTransfer | 513.73 | 0.00 | 01-JAN-00:10 | 193534.74 | 06-FEB-12:10 |
CoolingCoils:EnergyTransfer | 300.35 | 0.00 | 01-JAN-00:10 | 166030.30 | 20-JUL-14:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 24.619 | -81.319 | 0.000 | 0.000 | 25.354 | 116.248 | 26.249 | 19.828 | 0.000 | 1.057 | 0.000 | 0.000 | -11.901 | 0.000 | -44.584 | -75.550 |
SMSTORE1 | 0.000 | 0.000 | 7.270 | -46.692 | 0.000 | 0.000 | 12.477 | 68.266 | 13.125 | 9.798 | 0.000 | 0.566 | 0.000 | 0.000 | -6.284 | 0.000 | -21.489 | -37.036 |
SMSTORE2 | 0.000 | 0.000 | 9.544 | -33.398 | 0.000 | 0.000 | 7.600 | 49.007 | 10.421 | 9.789 | 0.000 | 0.551 | 0.000 | 0.000 | -6.178 | 0.000 | -22.192 | -25.144 |
SMSTORE3 | 0.000 | 0.000 | 10.506 | -32.440 | 0.000 | 0.000 | 7.609 | 49.007 | 10.421 | 9.805 | 0.000 | 0.551 | 0.001 | 0.000 | -6.108 | 0.000 | -22.109 | -27.241 |
SMSTORE4 | 0.000 | 0.000 | 12.021 | -30.261 | 0.000 | 0.000 | 7.623 | 49.007 | 10.421 | 9.832 | 0.000 | 0.551 | 0.003 | 0.000 | -6.032 | 0.000 | -22.003 | -31.158 |
LGSTORE2 | 0.000 | 0.000 | 25.879 | -47.035 | 0.000 | 0.000 | 26.248 | 54.161 | 19.173 | 19.821 | 0.000 | 0.996 | 0.002 | 0.000 | -11.622 | 0.000 | -40.446 | -47.175 |
SMSTORE5 | 0.000 | 0.000 | 14.845 | -23.483 | 0.000 | 0.000 | 13.132 | 27.807 | 9.586 | 9.891 | 0.000 | 0.553 | 0.000 | 0.000 | -5.820 | 0.000 | -21.972 | -24.539 |
SMSTORE6 | 0.000 | 0.000 | 15.296 | -22.846 | 0.000 | 0.000 | 13.142 | 27.807 | 9.586 | 9.904 | 0.000 | 0.553 | 0.001 | 0.000 | -5.792 | 0.000 | -21.931 | -25.719 |
SMSTORE7 | 0.000 | 0.000 | 17.475 | -21.306 | 0.000 | 0.000 | 13.167 | 27.807 | 9.586 | 9.936 | 0.000 | 0.553 | 0.001 | 0.000 | -5.698 | 0.000 | -21.805 | -29.716 |
SMSTORE8 | 0.000 | 0.000 | 29.999 | -19.097 | 0.000 | 0.000 | 13.214 | 27.807 | 9.586 | 10.028 | 0.000 | 0.589 | 0.002 | 0.000 | -5.338 | 0.000 | -28.118 | -38.669 |
Total Facility | 0.000 | 0.000 | 167.453 | -357.879 | 0.000 | 0.000 | 139.566 | 496.921 | 128.154 | 118.632 | 0.000 | 6.522 | 0.011 | 0.000 | -70.774 | 0.000 | -266.649 | -361.946 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-AUG-07:02 | 0.00 | 0.00 | 0.00 | -36957.92 | 0.00 | 0.00 | 178.40 | 317.63 | 74.62 | 282.32 | 0.00 | 0.00 | 36299.61 | 0.00 | -0.00 | 0.00 | -194.66 | 0.00 |
SMSTORE1 | 06-AUG-07:02 | 0.00 | 0.00 | 0.00 | -20356.57 | 0.00 | 0.00 | 86.98 | 186.54 | 37.31 | 135.57 | 0.00 | 0.00 | 20012.36 | 0.00 | -0.00 | 0.00 | -102.19 | 0.00 |
SMSTORE2 | 06-AUG-07:02 | 0.00 | 0.00 | 0.00 | -20875.69 | 0.00 | 0.00 | 0.00 | 167.44 | 37.31 | 131.51 | 0.00 | 0.00 | 20644.98 | 0.00 | -0.00 | 0.00 | -105.56 | 0.00 |
SMSTORE3 | 06-AUG-07:02 | 0.00 | 0.00 | 0.00 | -20785.74 | 0.00 | 0.00 | 0.00 | 167.44 | 37.31 | 130.93 | 0.00 | 0.00 | 20556.40 | 0.00 | -0.00 | 0.00 | -106.34 | 0.00 |
SMSTORE4 | 06-AUG-07:02 | 0.00 | 0.00 | 0.00 | -20664.02 | 0.00 | 0.00 | 0.00 | 167.44 | 37.31 | 133.06 | 0.00 | 0.00 | 20429.49 | 0.00 | -0.00 | 0.00 | -103.28 | 0.00 |
LGSTORE2 | 11-AUG-07:02 | 0.00 | 0.00 | 0.00 | -33569.34 | 0.00 | 0.00 | 0.00 | 201.30 | 73.64 | 254.80 | 0.00 | 0.00 | 33298.00 | 0.00 | -0.00 | 0.00 | -258.39 | 0.00 |
SMSTORE5 | 11-AUG-07:02 | 0.00 | 0.00 | 0.00 | -17404.55 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 129.06 | 0.00 | 0.00 | 17274.40 | 0.00 | -0.00 | 0.00 | -139.09 | 0.00 |
SMSTORE6 | 11-AUG-07:02 | 0.00 | 0.00 | 0.00 | -17277.12 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 129.97 | 0.00 | 0.00 | 17145.13 | 0.00 | -0.00 | 0.00 | -138.15 | 0.00 |
SMSTORE7 | 11-AUG-07:02 | 0.00 | 0.00 | 0.00 | -17061.62 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 131.78 | 0.00 | 0.00 | 16925.34 | 0.00 | -0.00 | 0.00 | -135.68 | 0.00 |
SMSTORE8 | 07-AUG-07:02 | 0.00 | 0.00 | 0.00 | -14415.31 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 131.11 | 0.00 | 0.00 | 14238.24 | 0.00 | -0.00 | 0.00 | -94.21 | 0.00 |
Total Facility | 11-AUG-07:02 | 0.00 | 0.00 | 0.00 | -156864.01 | 0.00 | 0.00 | 295.52 | 6142.12 | 1450.75 | 1589.10 | 0.00 | 0.00 | 149044.69 | 0.00 | 0.00 | 0.00 | -1658.17 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 07-MAR-08:61 | 0.00 | 0.00 | 63842.66 | 0.00 | 0.00 | 0.00 | 274.82 | 317.63 | 74.62 | 547.75 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1599.19 | -63458.29 |
SMSTORE1 | 07-MAR-08:61 | 0.00 | 0.00 | 33650.52 | 0.00 | 0.00 | 0.00 | 129.99 | 186.54 | 37.31 | 238.76 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -836.12 | -33407.00 |
SMSTORE2 | 10-DEC-08:61 | 0.00 | 0.00 | 35862.50 | 0.00 | 0.00 | 0.00 | 0.00 | 167.44 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -123.90 | 0.00 | -882.70 | -35060.65 |
SMSTORE3 | 10-DEC-08:61 | 0.00 | 0.00 | 35696.66 | 0.00 | 0.00 | 0.00 | 0.00 | 167.44 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -117.06 | 0.00 | -873.87 | -34910.49 |
SMSTORE4 | 10-DEC-08:61 | 0.00 | 0.00 | 35695.54 | 0.00 | 0.00 | 0.00 | 0.00 | 167.44 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -110.85 | 0.00 | -865.44 | -34924.01 |
LGSTORE2 | 06-FEB-08:61 | 0.00 | 0.00 | 60266.11 | 0.00 | 0.00 | 0.00 | 0.00 | 201.30 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1113.76 | 0.00 | -1827.39 | -57599.90 |
SMSTORE5 | 07-FEB-08:61 | 0.00 | 0.00 | 31697.79 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -85.18 | 0.00 | -1037.83 | -30714.95 |
SMSTORE6 | 06-FEB-08:61 | 0.00 | 0.00 | 31601.09 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -559.75 | 0.00 | -992.17 | -30189.35 |
SMSTORE7 | 10-JAN-08:12 | 0.00 | 0.00 | 31481.99 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 203.29 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -843.62 | -30981.84 |
SMSTORE8 | 24-JAN-08:12 | 0.00 | 0.00 | 32678.80 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -139.86 | 0.00 | -1306.53 | -31372.58 |
Total Facility | 06-FEB-08:61 | 0.00 | 0.00 | 304430.62 | 0.00 | 0.00 | 0.00 | 772.57 | 6142.12 | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6953.63 | 0.00 | -12767.66 | -293076.26 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0500 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0500 | 0.2007 | 1.0000 | Not calculated | 0.4115 | 0.2007 | ||
PSZ-AC_2:2 | 1.1036 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1077 | 0.1857 | 1.0000 | Not calculated | 0.2057 | 0.1857 | ||
PSZ-AC_3:3 | 1.2075 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2075 | 0.1704 | 1.0000 | Not calculated | 0.2057 | 0.1704 | ||
PSZ-AC_4:4 | 1.1997 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1997 | 0.1715 | 1.0000 | Not calculated | 0.2057 | 0.1715 | ||
PSZ-AC_5:5 | 1.1996 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1996 | 0.1715 | 1.0000 | Not calculated | 0.2057 | 0.1715 | ||
PSZ-AC_6:6 | 1.8806 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9328 | 0.2129 | 1.0000 | Not calculated | 0.4115 | 0.2129 | ||
PSZ-AC_7:7 | 1.0121 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0121 | 0.2033 | 1.0000 | Not calculated | 0.2057 | 0.2033 | ||
PSZ-AC_8:8 | 1.0062 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0062 | 0.2045 | 1.0000 | Not calculated | 0.2057 | 0.2045 | ||
PSZ-AC_9:9 | 0.9987 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9995 | 0.2059 | 1.0000 | Not calculated | 0.2057 | 0.2059 | ||
PSZ-AC_10:10 | 1.0452 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0553 | 0.1950 | 1.0000 | Not calculated | 0.2057 | 0.1950 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0500 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0500 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2007 | ||
PSZ-AC_2:2 | 1.1036 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1036 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1864 | ||
PSZ-AC_3:3 | 1.2075 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2075 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1704 | ||
PSZ-AC_4:4 | 1.1997 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1997 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1715 | ||
PSZ-AC_5:5 | 1.1996 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1996 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1715 | ||
PSZ-AC_6:6 | 1.8806 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8806 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2188 | ||
PSZ-AC_7:7 | 1.0121 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0121 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2033 | ||
PSZ-AC_8:8 | 1.0062 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0062 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2045 | ||
PSZ-AC_9:9 | 0.9987 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9987 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2060 | ||
PSZ-AC_10:10 | 1.0452 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0452 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1968 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0500 | 2.0500 | 2.0500 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1036 | 1.1036 | 1.1036 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2075 | 1.2075 | 1.2075 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1997 | 1.1997 | 1.1997 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1996 | 1.1996 | 1.1996 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8806 | 1.8806 | 1.8806 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0121 | 1.0121 | 1.0121 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0062 | 1.0062 | 1.0062 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9987 | 0.9987 | 0.9987 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0452 | 1.0452 | 1.0452 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0500 | 2.0500 | 2.0500 | 2.0500 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1036 | 1.1077 | 1.1036 | 1.1036 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.2075 | 1.2075 | 1.2075 | 1.2075 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1997 | 1.1997 | 1.1997 | 1.1997 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1996 | 1.1996 | 1.1996 | 1.1996 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8806 | 1.9328 | 1.8806 | 1.8806 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0121 | 1.0121 | 1.0121 | 1.0121 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0062 | 1.0062 | 1.0062 | 1.0062 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9987 | 0.9995 | 0.9987 | 0.9987 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0452 | 1.0553 | 1.0452 | 1.0452 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0500 | 2.0500 | 2.0500 | No | 0.4115 | 0.2763 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1036 | 1.1036 | 1.1036 | No | 0.2057 | 0.2924 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2075 | 1.2075 | 1.2075 | No | 0.2057 | 0.2892 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1997 | 1.1997 | 1.1997 | No | 0.2057 | 0.2876 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1996 | 1.1996 | 1.1996 | No | 0.2057 | 0.2846 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8806 | 1.8806 | 1.8806 | No | 0.4115 | 0.2972 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0121 | 1.0121 | 1.0121 | No | 0.2057 | 0.2778 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0062 | 1.0062 | 1.0062 | No | 0.2057 | 0.2781 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9987 | 0.9987 | 0.9987 | No | 0.2057 | 0.2740 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0452 | 1.0452 | 1.0452 | No | 0.2057 | 0.2236 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0500 | 2.0500 | 2.0500 | 2.0500 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1036 | 1.1036 | 1.1036 | 1.1036 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.2075 | 1.2075 | 1.2075 | 1.2075 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1997 | 1.1997 | 1.1997 | 1.1997 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1996 | 1.1996 | 1.1996 | 1.1996 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8806 | 1.8806 | 1.8806 | 1.8806 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0121 | 1.0121 | 1.0121 | 1.0121 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0062 | 1.0062 | 1.0062 | 1.0062 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9987 | 0.9987 | 0.9987 | 0.9987 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0452 | 1.0452 | 1.0452 | 1.0452 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 3.67 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 3.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 642.16 | 241918.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 73.81 | 39264.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 496.92 | 30804.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 100.69 | 7723.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 107.67 | 9732.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 65.06 | 12753.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 972.30 |
Natural Gas | 0.00 | 642.16 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1614.45 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 237.73 |
Space Heating | 0.00 |
Space Cooling | 35.31 |
Fans (All) | 51.51 |
Service Water Heating | 31.12 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 465.14 |
Subtotal | 465.14 |
Natural Gas [MJ/m2] | |
Space Heating | 307.21 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 307.21 |
Subtotal | 307.21 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 30.78 |
Space Heating | 39.78 |
Space Cooling | 4.57 |
Fans (All) | 6.67 |
Service Water Heating | 4.03 |
Receptacle Equipment | 7.94 |
Miscellaneous | 6.24 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8719.00 | 41.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8715.50 | 44.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8730.67 | 29.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8748.00 | 12.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8751.00 | 9.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8751.67 | 8.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8752.67 | 7.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
Min | 8715.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 44.50 | 0.00 | 0.00 | 0.00 |
Average | 8743.98 | 16.02 | 0.00 | 0.00 | 0.00 |
Sum | 87439.83 | 160.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25468.33 | 6.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25468.33 | 6.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25469.33 | 5.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93191.00 | 20.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45903.50 | 8.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45903.50 | 8.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45904.00 | 8.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45904.50 | 7.50 | 0.00 | 0.00 | 0.00 |
Min | 25468.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93191.00 | 20.00 | 0.00 | 0.00 | 0.00 |
Average | 48603.05 | 7.15 | 0.00 | 0.00 | 0.00 |
Sum | 486030.50 | 71.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8262.67 | 497.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8548.50 | 211.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8032.00 | 728.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8031.83 | 728.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8040.33 | 719.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8077.83 | 682.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8081.67 | 678.33 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8083.17 | 676.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8084.00 | 676.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8094.50 | 665.50 | 0.00 | 0.00 | 0.00 |
Min | 8031.83 | 211.50 | 0.00 | 0.00 | 0.00 |
Max | 8548.50 | 728.17 | 0.00 | 0.00 | 0.00 |
Average | 8133.65 | 626.35 | 0.00 | 0.00 | 0.00 |
Sum | 81336.50 | 6263.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 87005.83 | 2035.17 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43165.00 | 612.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 24659.33 | 815.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 24657.33 | 817.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 24601.83 | 873.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 89821.50 | 3389.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 44208.33 | 1703.67 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 44171.00 | 1741.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 44083.00 | 1829.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 43879.50 | 2032.50 | 0.00 | 0.00 | 0.00 |
Min | 24601.83 | 612.00 | 0.00 | 0.00 | 0.00 |
Max | 89821.50 | 3389.50 | 0.00 | 0.00 | 0.00 |
Average | 47025.27 | 1584.93 | 0.00 | 0.00 | 0.00 |
Sum | 470252.67 | 15849.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:27
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.702390E+09 | 13618.69 | 06-JAN-00:02 | -10.0 | -10.7 | 0.106503E+10 | 1275.40 | 29-JAN-18:00 | -6.7 | -7.2 |
February | 0.634541E+09 | 13636.00 | 11-FEB-00:02 | -10.0 | -10.7 | 0.961309E+09 | 1275.40 | 20-FEB-18:00 | -1.1 | -2.5 |
March | 0.270736E+10 | 13369.64 | 04-MAR-00:02 | -9.4 | -10.8 | 0.108950E+10 | 1512.58 | 12-MAR-17:49 | 13.58 | 11.60 |
April | 0.461904E+10 | 7991.26 | 13-APR-23:03 | 1.78 | 0.76 | 0.111055E+10 | 1685.87 | 08-APR-12:00 | 1.78 | 0.76 |
May | 0.746710E+10 | 8623.23 | 14-MAY-15:00 | 26.10 | 17.84 | 0.133426E+10 | 1685.91 | 13-MAY-12:00 | 26.10 | 17.84 |
June | 0.117593E+11 | 28176.65 | 12-JUN-07:03 | 24.08 | 18.79 | 0.135012E+10 | 1686.00 | 02-JUN-12:50 | 24.08 | 18.79 |
July | 0.152992E+11 | 31803.37 | 26-JUL-07:02 | 20.87 | 17.48 | 0.141275E+10 | 1686.00 | 23-JUL-12:00 | 20.87 | 17.48 |
August | 0.148945E+11 | 36965.53 | 06-AUG-07:02 | 20.28 | 15.40 | 0.139378E+10 | 1686.02 | 13-AUG-16:00 | 27.20 | 22.46 |
September | 0.112286E+11 | 28440.26 | 17-SEP-07:02 | 22.12 | 19.56 | 0.135613E+10 | 1685.97 | 09-SEP-12:00 | 22.12 | 19.56 |
October | 0.716994E+10 | 8552.63 | 11-OCT-17:10 | 21.23 | 14.34 | 0.121492E+10 | 1685.94 | 22-OCT-12:00 | 21.70 | 14.82 |
November | 0.382089E+10 | 9699.60 | 24-NOV-00:03 | -1.8 | -2.5 | 0.106421E+10 | 1685.83 | 05-NOV-12:09 | -1.8 | -2.5 |
December | 0.101724E+10 | 13310.49 | 29-DEC-00:02 | -9.4 | -10.3 | 0.107037E+10 | 1275.40 | 10-DEC-18:00 | -9.4 | -10.3 |
Annual Sum or Average | 0.813201E+11 | 0.144229E+11 | ||||||||
Minimum of Months | 0.634541E+09 | 7991.26 | -10.0 | -10.8 | 0.961309E+09 | 1275.40 | -9.4 | -10.3 | ||
Maximum of Months | 0.152992E+11 | 36965.53 | 26.10 | 19.56 | 0.141275E+10 | 1686.02 | 27.20 | 22.46 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.403351E+09 | 5829.21 | 23-JAN-10:52 | -6.1 | -8.0 | 0.548549E+09 | 775.31 | 15-JAN-18:00 | -6.1 | -8.0 |
February | 0.343910E+09 | 6017.81 | 10-FEB-10:32 | -6.9 | -8.0 | 0.493501E+09 | 760.95 | 19-FEB-18:00 | 2.20 | 1.05 |
March | 0.158356E+10 | 14098.65 | 15-MAR-20:57 | 18.90 | 13.76 | 0.570531E+09 | 842.90 | 12-MAR-17:00 | 18.90 | 13.76 |
April | 0.254958E+10 | 4011.61 | 10-APR-17:20 | 2.80 | 2.22 | 0.594939E+09 | 842.92 | 08-APR-12:00 | 2.80 | 2.22 |
May | 0.453828E+10 | 17565.20 | 21-MAY-18:29 | 16.15 | 9.62 | 0.688068E+09 | 842.97 | 14-MAY-16:10 | 16.15 | 9.62 |
June | 0.698049E+10 | 17194.85 | 03-JUN-18:06 | 17.80 | 10.05 | 0.674298E+09 | 843.13 | 25-JUN-17:00 | 26.70 | 18.35 |
July | 0.874853E+10 | 17675.08 | 26-JUL-07:02 | 20.87 | 17.48 | 0.704328E+09 | 843.09 | 30-JUL-17:00 | 24.40 | 20.25 |
August | 0.846214E+10 | 20358.98 | 06-AUG-07:02 | 20.28 | 15.40 | 0.694911E+09 | 843.01 | 13-AUG-12:39 | 29.63 | 22.57 |
September | 0.659417E+10 | 16726.76 | 10-SEP-17:32 | 16.10 | 10.54 | 0.679512E+09 | 842.96 | 09-SEP-12:00 | 16.10 | 10.54 |
October | 0.388144E+10 | 13850.30 | 22-OCT-21:13 | 18.70 | 13.93 | 0.642587E+09 | 842.95 | 22-OCT-12:00 | 18.70 | 13.93 |
November | 0.210322E+10 | 4618.63 | 05-NOV-17:10 | 11.52 | 10.00 | 0.565658E+09 | 842.90 | 05-NOV-17:00 | 10.60 | 9.36 |
December | 0.504026E+09 | 5839.18 | 08-DEC-11:22 | -6.1 | -7.0 | 0.553961E+09 | 766.35 | 24-DEC-18:40 | 4.63 | 2.63 |
Annual Sum or Average | 0.466927E+11 | 0.741084E+10 | ||||||||
Minimum of Months | 0.343910E+09 | 4011.61 | -6.9 | -8.0 | 0.493501E+09 | 760.95 | -6.1 | -8.0 | ||
Maximum of Months | 0.874853E+10 | 20358.98 | 20.87 | 17.48 | 0.704328E+09 | 843.13 | 29.63 | 22.57 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153473E+09 | 1882.78 | 11-JAN-18:10 | 10.27 | 9.38 | 0.317181E+09 | 637.68 | 07-JAN-13:20 | 10.27 | 9.38 |
February | 0.160812E+09 | 6471.25 | 21-FEB-18:22 | -9.2 | -10.2 | 0.288167E+09 | 637.68 | 04-FEB-13:09 | -9.2 | -10.2 |
March | 0.112223E+10 | 5220.68 | 24-MAR-09:13 | -3.7 | -5.5 | 0.338053E+09 | 702.45 | 14-MAR-16:30 | -3.7 | -5.5 |
April | 0.193618E+10 | 4053.69 | 24-APR-07:01 | 3.17 | 1.61 | 0.339236E+09 | 842.91 | 08-APR-12:00 | 3.17 | 1.61 |
May | 0.317487E+10 | 4740.06 | 27-MAY-13:00 | 21.70 | 12.35 | 0.411056E+09 | 842.93 | 13-MAY-12:00 | 21.70 | 12.35 |
June | 0.498269E+10 | 17877.33 | 26-JUN-06:02 | 20.50 | 17.42 | 0.415616E+09 | 842.95 | 17-JUN-12:09 | 20.50 | 17.42 |
July | 0.628682E+10 | 18723.17 | 05-JUL-06:02 | 18.98 | 16.76 | 0.420002E+09 | 842.97 | 01-JUL-12:50 | 18.98 | 16.76 |
August | 0.627468E+10 | 20879.09 | 06-AUG-07:02 | 20.28 | 15.40 | 0.431432E+09 | 842.95 | 12-AUG-12:09 | 23.40 | 16.43 |
September | 0.464571E+10 | 16531.45 | 15-SEP-06:03 | 18.30 | 16.87 | 0.408360E+09 | 842.94 | 09-SEP-12:00 | 18.30 | 16.87 |
October | 0.288717E+10 | 4442.88 | 11-OCT-16:10 | 21.70 | 14.52 | 0.366623E+09 | 842.89 | 21-OCT-12:09 | 18.98 | 11.78 |
November | 0.152169E+10 | 4054.80 | 07-NOV-08:61 | 2.20 | 0.89 | 0.317795E+09 | 773.79 | 04-NOV-12:00 | 2.20 | 0.89 |
December | 0.251644E+09 | 5135.60 | 25-DEC-11:23 | -3.6 | -4.3 | 0.316832E+09 | 637.68 | 02-DEC-13:00 | -3.6 | -4.3 |
Annual Sum or Average | 0.333980E+11 | 0.437035E+10 | ||||||||
Minimum of Months | 0.153473E+09 | 1882.78 | -9.2 | -10.2 | 0.288167E+09 | 637.68 | -9.2 | -10.2 | ||
Maximum of Months | 0.628682E+10 | 20879.09 | 21.70 | 17.42 | 0.431432E+09 | 842.97 | 23.40 | 17.42 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120627E+09 | 5631.52 | 04-JAN-11:43 | -5.8 | -7.9 | 0.317181E+09 | 637.68 | 07-JAN-13:30 | -0.9 | -2.9 |
February | 0.127601E+09 | 5964.37 | 25-FEB-11:02 | -6.9 | -8.5 | 0.288144E+09 | 637.68 | 11-FEB-13:50 | -6.9 | -8.5 |
March | 0.100157E+10 | 5853.76 | 07-MAR-20:35 | -6.7 | -7.9 | 0.337556E+09 | 702.45 | 14-MAR-17:00 | 21.10 | 15.63 |
April | 0.178065E+10 | 3978.66 | 24-APR-07:01 | 3.17 | 1.61 | 0.336828E+09 | 842.91 | 08-APR-12:00 | 3.17 | 1.61 |
May | 0.304180E+10 | 4657.23 | 27-MAY-13:00 | 21.70 | 12.35 | 0.408680E+09 | 842.92 | 13-MAY-12:00 | 21.70 | 12.35 |
June | 0.494264E+10 | 17780.10 | 26-JUN-06:02 | 20.50 | 17.42 | 0.415558E+09 | 842.95 | 17-JUN-12:09 | 20.50 | 17.42 |
July | 0.629160E+10 | 18650.42 | 05-JUL-06:02 | 18.98 | 16.76 | 0.419997E+09 | 842.97 | 01-JUL-12:50 | 18.98 | 16.76 |
August | 0.627455E+10 | 20789.12 | 06-AUG-07:02 | 20.28 | 15.40 | 0.431423E+09 | 842.95 | 12-AUG-12:09 | 23.40 | 16.43 |
September | 0.459034E+10 | 16459.00 | 15-SEP-06:03 | 18.30 | 16.87 | 0.408162E+09 | 842.94 | 09-SEP-12:00 | 18.30 | 16.87 |
October | 0.270932E+10 | 4202.30 | 11-OCT-16:10 | 21.70 | 14.52 | 0.364353E+09 | 842.89 | 21-OCT-12:20 | 19.07 | 11.85 |
November | 0.134951E+10 | 4003.18 | 07-NOV-08:61 | 2.20 | 0.89 | 0.316471E+09 | 764.60 | 04-NOV-12:00 | 2.20 | 0.89 |
December | 0.210476E+09 | 5915.05 | 06-DEC-19:42 | -6.7 | -7.4 | 0.316817E+09 | 637.68 | 02-DEC-13:30 | -6.7 | -7.4 |
Annual Sum or Average | 0.324407E+11 | 0.436117E+10 | ||||||||
Minimum of Months | 0.120627E+09 | 3978.66 | -6.9 | -8.5 | 0.288144E+09 | 637.68 | -6.9 | -8.5 | ||
Maximum of Months | 0.629160E+10 | 20789.12 | 21.70 | 17.42 | 0.431423E+09 | 842.97 | 23.40 | 17.42 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 72122142.58 | 5698.75 | 28-JAN-11:32 | -5.8 | -7.3 | 0.317181E+09 | 637.68 | 07-JAN-13:09 | -5.8 | -7.3 |
February | 77890323.85 | 5076.38 | 16-FEB-20:12 | -3.3 | -4.3 | 0.288114E+09 | 637.68 | 04-FEB-13:20 | -3.3 | -4.3 |
March | 0.828859E+09 | 4124.37 | 18-MAR-07:01 | 1.78 | 0.50 | 0.336725E+09 | 702.44 | 14-MAR-17:49 | 1.78 | 0.50 |
April | 0.155077E+10 | 3875.51 | 24-APR-07:01 | 3.17 | 1.61 | 0.333342E+09 | 842.91 | 08-APR-12:00 | 3.17 | 1.61 |
May | 0.278123E+10 | 4396.97 | 27-MAY-13:00 | 21.70 | 12.35 | 0.404336E+09 | 842.92 | 13-MAY-12:00 | 21.70 | 12.35 |
June | 0.471148E+10 | 17641.05 | 26-JUN-06:02 | 20.50 | 17.42 | 0.415260E+09 | 842.96 | 17-JUN-12:09 | 20.50 | 17.42 |
July | 0.608256E+10 | 18523.15 | 05-JUL-06:02 | 18.98 | 16.76 | 0.419958E+09 | 842.97 | 01-JUL-12:50 | 18.98 | 16.76 |
August | 0.605722E+10 | 20667.40 | 06-AUG-07:02 | 20.28 | 15.40 | 0.431367E+09 | 842.95 | 12-AUG-12:09 | 23.40 | 16.43 |
September | 0.437319E+10 | 15523.95 | 17-SEP-07:02 | 22.12 | 19.56 | 0.407584E+09 | 842.94 | 09-SEP-12:00 | 22.12 | 19.56 |
October | 0.245406E+10 | 4115.89 | 24-OCT-07:02 | 1.78 | 0.45 | 0.360923E+09 | 842.89 | 21-OCT-12:50 | 1.78 | 0.45 |
November | 0.113161E+10 | 3784.84 | 28-NOV-08:61 | 3.12 | 2.18 | 0.314934E+09 | 751.55 | 04-NOV-12:00 | 3.12 | 2.18 |
December | 0.140650E+09 | 3985.60 | 02-DEC-18:43 | 1.20 | 0.85 | 0.316803E+09 | 637.68 | 02-DEC-13:39 | 1.20 | 0.85 |
Annual Sum or Average | 0.302617E+11 | 0.434653E+10 | ||||||||
Minimum of Months | 72122142.58 | 3784.84 | -5.8 | -7.3 | 0.288114E+09 | 637.68 | -5.8 | -7.3 | ||
Maximum of Months | 0.608256E+10 | 20667.40 | 22.12 | 19.56 | 0.431367E+09 | 842.97 | 23.40 | 19.56 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11765037.49 | 1193.25 | 21-JAN-12:00 | -0.6 | -3.2 | 0.108442E+10 | 1700.53 | 14-JAN-15:39 | -0.6 | -3.2 |
February | 20620118.21 | 1538.29 | 18-FEB-12:00 | 1.10 | 0.02 | 0.987309E+09 | 1700.53 | 04-FEB-15:39 | 1.10 | 0.02 |
March | 0.982251E+09 | 11737.16 | 03-MAR-18:12 | -5.8 | -7.6 | 0.115183E+10 | 1995.04 | 15-MAR-16:00 | 25.00 | 15.95 |
April | 0.219850E+10 | 7572.88 | 10-APR-16:43 | 2.88 | 2.37 | 0.112269E+10 | 2247.83 | 08-APR-14:09 | 2.88 | 2.37 |
May | 0.430886E+10 | 7233.75 | 27-MAY-14:20 | 21.70 | 12.29 | 0.134929E+10 | 2247.90 | 13-MAY-14:39 | 21.70 | 12.29 |
June | 0.753599E+10 | 27542.91 | 26-JUN-07:03 | 20.28 | 17.94 | 0.142201E+10 | 2247.99 | 17-JUN-14:09 | 20.28 | 17.94 |
July | 0.100432E+11 | 31091.29 | 05-JUL-07:03 | 19.50 | 16.90 | 0.143769E+10 | 2247.99 | 01-JUL-14:09 | 19.50 | 16.90 |
August | 0.997198E+10 | 33581.42 | 11-AUG-07:02 | 18.40 | 15.63 | 0.147919E+10 | 2247.96 | 26-AUG-14:09 | 25.37 | 21.59 |
September | 0.694710E+10 | 26614.76 | 17-SEP-08:62 | 21.70 | 19.45 | 0.139443E+10 | 2247.97 | 09-SEP-14:20 | 21.70 | 19.45 |
October | 0.364990E+10 | 6821.35 | 24-OCT-11:03 | 4.50 | 1.98 | 0.120602E+10 | 2247.74 | 21-OCT-14:09 | 4.50 | 1.98 |
November | 0.130553E+10 | 7841.73 | 21-NOV-20:43 | 2.20 | 0.16 | 0.106525E+10 | 2112.46 | 04-NOV-14:00 | 2.20 | 0.16 |
December | 59922053.57 | 2969.76 | 16-DEC-12:00 | 4.40 | 1.70 | 0.108625E+10 | 1700.53 | 02-DEC-15:39 | 4.40 | 1.70 |
Annual Sum or Average | 0.470357E+11 | 0.147864E+11 | ||||||||
Minimum of Months | 11765037.49 | 1193.25 | -5.8 | -7.6 | 0.987309E+09 | 1700.53 | -0.6 | -3.2 | ||
Maximum of Months | 0.100432E+11 | 33581.42 | 21.70 | 19.45 | 0.147919E+10 | 2247.99 | 25.37 | 21.59 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8004022.56 | 3999.80 | 18-JAN-18:23 | 1.70 | 1.02 | 0.542193E+09 | 850.24 | 07-JAN-15:09 | 1.70 | 1.02 |
February | 8726690.18 | 1587.69 | 22-FEB-17:15 | 12.07 | 5.77 | 0.493639E+09 | 850.24 | 11-FEB-15:09 | 12.07 | 5.77 |
March | 0.464145E+09 | 5905.63 | 04-MAR-11:52 | -6.1 | -7.8 | 0.575616E+09 | 997.49 | 15-MAR-16:00 | 25.00 | 15.95 |
April | 0.101701E+10 | 3860.50 | 17-APR-10:03 | 2.30 | 0.10 | 0.559559E+09 | 1123.87 | 08-APR-14:09 | 2.30 | 0.10 |
May | 0.206538E+10 | 3619.77 | 27-MAY-14:30 | 21.70 | 12.26 | 0.671235E+09 | 1123.92 | 13-MAY-14:50 | 21.70 | 12.26 |
June | 0.380160E+10 | 13188.12 | 26-JUN-07:03 | 20.28 | 17.94 | 0.710773E+09 | 1123.96 | 17-JUN-14:39 | 20.28 | 17.94 |
July | 0.514214E+10 | 15828.36 | 26-JUL-07:02 | 20.87 | 17.48 | 0.718808E+09 | 1123.96 | 01-JUL-14:20 | 20.87 | 17.48 |
August | 0.509904E+10 | 17411.03 | 11-AUG-07:02 | 18.40 | 15.63 | 0.739560E+09 | 1123.95 | 26-AUG-14:09 | 25.37 | 21.59 |
September | 0.350631E+10 | 13795.40 | 17-SEP-08:62 | 21.70 | 19.45 | 0.696875E+09 | 1123.95 | 09-SEP-14:09 | 21.70 | 19.45 |
October | 0.173882E+10 | 3813.97 | 24-OCT-08:23 | 2.50 | 0.66 | 0.601378E+09 | 1123.84 | 21-OCT-14:09 | 2.50 | 0.66 |
November | 0.606023E+09 | 4191.16 | 29-NOV-20:53 | 1.10 | -1.2 | 0.532034E+09 | 1046.48 | 04-NOV-14:00 | 1.10 | -1.2 |
December | 26529618.48 | 3834.69 | 23-DEC-11:13 | 2.40 | -0.9 | 0.543111E+09 | 850.24 | 02-DEC-15:00 | 2.40 | -0.9 |
Annual Sum or Average | 0.234837E+11 | 0.738478E+10 | ||||||||
Minimum of Months | 8004022.56 | 1587.69 | -6.1 | -7.8 | 0.493639E+09 | 850.24 | 1.10 | -1.2 | ||
Maximum of Months | 0.514214E+10 | 17411.03 | 21.70 | 19.45 | 0.739560E+09 | 1123.96 | 25.37 | 21.59 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4432858.28 | 3398.38 | 14-JAN-11:23 | 4.40 | 3.15 | 0.542193E+09 | 850.24 | 07-JAN-15:50 | 4.40 | 3.15 |
February | 6863413.77 | 623.69 | 18-FEB-12:00 | 1.10 | 0.02 | 0.493640E+09 | 850.24 | 04-FEB-15:30 | 1.10 | 0.02 |
March | 0.429887E+09 | 4449.56 | 01-MAR-19:23 | 0.00 | -2.1 | 0.575228E+09 | 997.49 | 15-MAR-16:40 | 25.00 | 15.95 |
April | 0.958501E+09 | 3590.44 | 15-APR-17:13 | 3.50 | 2.60 | 0.557783E+09 | 1123.87 | 08-APR-14:09 | 3.50 | 2.60 |
May | 0.197010E+10 | 3477.27 | 27-MAY-14:30 | 21.70 | 12.26 | 0.666972E+09 | 1123.91 | 13-MAY-14:50 | 21.70 | 12.26 |
June | 0.370740E+10 | 12403.10 | 26-JUN-07:03 | 20.28 | 17.94 | 0.710392E+09 | 1123.91 | 10-JUN-14:09 | 20.28 | 17.94 |
July | 0.506431E+10 | 15707.82 | 26-JUL-07:02 | 20.87 | 17.48 | 0.718796E+09 | 1123.96 | 01-JUL-14:30 | 20.87 | 17.48 |
August | 0.502290E+10 | 17283.55 | 11-AUG-07:02 | 18.40 | 15.63 | 0.739510E+09 | 1123.95 | 26-AUG-14:09 | 25.37 | 21.59 |
September | 0.343337E+10 | 13690.48 | 17-SEP-08:62 | 21.70 | 19.45 | 0.696184E+09 | 1123.95 | 09-SEP-14:09 | 21.70 | 19.45 |
October | 0.166588E+10 | 3260.94 | 14-OCT-08:63 | 6.10 | 5.58 | 0.599029E+09 | 1123.85 | 21-OCT-14:09 | 19.40 | 12.06 |
November | 0.562057E+09 | 4149.82 | 29-NOV-20:33 | 1.30 | -1.0 | 0.531522E+09 | 1040.97 | 04-NOV-14:00 | 1.30 | -1.0 |
December | 20391239.47 | 1411.31 | 16-DEC-12:00 | 4.40 | 1.70 | 0.543112E+09 | 850.24 | 02-DEC-15:39 | 4.40 | 1.70 |
Annual Sum or Average | 0.228461E+11 | 0.737436E+10 | ||||||||
Minimum of Months | 4432858.28 | 623.69 | 0.00 | -2.1 | 0.493640E+09 | 850.24 | 1.10 | -1.0 | ||
Maximum of Months | 0.506431E+10 | 17283.55 | 21.70 | 19.45 | 0.739510E+09 | 1123.96 | 25.37 | 21.59 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1478417.98 | 2826.62 | 11-JAN-18:43 | 6.93 | 6.10 | 0.542193E+09 | 850.24 | 07-JAN-15:20 | 6.93 | 6.10 |
February | 2920073.81 | 366.37 | 18-FEB-12:00 | 1.10 | 0.02 | 0.493640E+09 | 850.24 | 04-FEB-15:39 | 1.10 | 0.02 |
March | 0.341060E+09 | 4133.53 | 02-MAR-19:23 | 1.40 | -0.2 | 0.574165E+09 | 998.13 | 14-MAR-12:09 | 24.08 | 17.61 |
April | 0.782585E+09 | 3504.17 | 13-APR-09:53 | 3.90 | 1.83 | 0.553716E+09 | 1123.85 | 08-APR-14:20 | 3.90 | 1.83 |
May | 0.175128E+10 | 3154.57 | 27-MAY-14:30 | 21.70 | 12.26 | 0.656748E+09 | 1123.91 | 13-MAY-14:00 | 21.70 | 12.26 |
June | 0.347246E+10 | 10747.14 | 18-JUN-08:62 | 24.50 | 21.64 | 0.709176E+09 | 1123.91 | 10-JUN-14:20 | 24.50 | 21.64 |
July | 0.490212E+10 | 15234.60 | 26-JUL-07:02 | 20.87 | 17.48 | 0.718767E+09 | 1123.97 | 01-JUL-14:30 | 20.87 | 17.48 |
August | 0.486440E+10 | 17067.98 | 11-AUG-07:02 | 18.40 | 15.63 | 0.739330E+09 | 1123.96 | 26-AUG-14:09 | 25.37 | 21.59 |
September | 0.325417E+10 | 13492.50 | 17-SEP-08:62 | 21.70 | 19.45 | 0.694265E+09 | 1123.95 | 09-SEP-14:09 | 21.70 | 19.45 |
October | 0.147855E+10 | 3186.49 | 14-OCT-08:63 | 6.10 | 5.58 | 0.593978E+09 | 1123.85 | 21-OCT-14:09 | 19.40 | 12.06 |
November | 0.443176E+09 | 4052.75 | 22-NOV-11:33 | 1.50 | -0.8 | 0.530217E+09 | 1024.88 | 04-NOV-14:00 | 1.50 | -0.8 |
December | 12057572.69 | 3002.15 | 01-DEC-20:23 | 6.10 | 3.97 | 0.543104E+09 | 850.24 | 09-DEC-15:09 | -5.8 | -5.8 |
Annual Sum or Average | 0.213063E+11 | 0.734930E+10 | ||||||||
Minimum of Months | 1478417.98 | 366.37 | 1.10 | -0.8 | 0.493640E+09 | 850.24 | -5.8 | -5.8 | ||
Maximum of Months | 0.490212E+10 | 17067.98 | 24.50 | 21.64 | 0.739330E+09 | 1123.97 | 25.37 | 21.64 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -1.0 | -1.6 | 0.542193E+09 | 850.24 | 21-JAN-15:30 | -1.1 | -3.2 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.3 | -4.7 | 0.493640E+09 | 850.24 | 04-FEB-15:30 | -5.6 | -7.1 |
March | 0.170566E+09 | 3263.97 | 17-MAR-19:33 | 4.80 | 2.71 | 0.572259E+09 | 997.47 | 15-MAR-12:00 | 4.80 | 2.71 |
April | 0.434740E+09 | 3344.16 | 13-APR-18:23 | 4.45 | 2.33 | 0.547561E+09 | 1123.86 | 08-APR-14:50 | 4.45 | 2.33 |
May | 0.131913E+10 | 2706.53 | 27-MAY-14:10 | 21.70 | 12.32 | 0.637412E+09 | 1123.90 | 13-MAY-14:00 | 21.70 | 12.32 |
June | 0.317220E+10 | 7508.26 | 18-JUN-08:62 | 24.50 | 21.64 | 0.705603E+09 | 1123.90 | 10-JUN-14:20 | 24.50 | 21.64 |
July | 0.487541E+10 | 12224.98 | 19-JUL-07:02 | 22.20 | 20.31 | 0.718748E+09 | 1123.95 | 08-JUL-14:30 | 22.20 | 20.31 |
August | 0.483586E+10 | 14420.14 | 07-AUG-07:02 | 21.20 | 18.87 | 0.738701E+09 | 1123.97 | 26-AUG-14:09 | 25.37 | 21.59 |
September | 0.303221E+10 | 13565.70 | 17-SEP-08:62 | 21.70 | 19.45 | 0.689460E+09 | 1123.96 | 09-SEP-14:09 | 21.70 | 19.45 |
October | 0.106232E+10 | 2729.90 | 11-OCT-15:00 | 22.20 | 14.61 | 0.586334E+09 | 1123.85 | 21-OCT-14:09 | 19.40 | 12.06 |
November | 0.194355E+09 | 3222.07 | 07-NOV-18:13 | 5.00 | 2.83 | 0.528082E+09 | 991.47 | 04-NOV-14:00 | 5.00 | 2.83 |
December | 840678.51 | 538.42 | 16-DEC-12:00 | 4.40 | 1.70 | 0.543112E+09 | 850.24 | 02-DEC-15:00 | 4.40 | 1.70 |
Annual Sum or Average | 0.190976E+11 | 0.730311E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 0.493640E+09 | 850.24 | -5.6 | -7.1 | ||
Maximum of Months | 0.487541E+10 | 14420.14 | 24.50 | 21.64 | 0.738701E+09 | 1123.97 | 25.37 | 21.64 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.694410E+10 | 63821.38 | 30-JAN-08:61 | -10.5 |
February | 0.680694E+10 | 63832.46 | 07-FEB-08:61 | -15.6 |
March | 0.282793E+10 | 63842.65 | 07-MAR-08:61 | -10.8 |
April | 0.749120E+09 | 63788.98 | 17-APR-07:01 | -2.9 |
May | 80934930.06 | 22304.33 | 01-MAY-07:01 | 6.05 |
June | 32671180.89 | 1709.92 | 12-JUN-07:05 | 24.08 |
July | 26665154.78 | 1676.07 | 26-JUL-07:04 | 20.87 |
August | 29138364.11 | 1715.12 | 11-AUG-07:04 | 18.40 |
September | 33246229.93 | 1671.92 | 14-SEP-07:05 | 20.60 |
October | 0.165015E+09 | 63788.70 | 17-OCT-07:01 | -2.4 |
November | 0.885858E+09 | 63795.21 | 22-NOV-08:61 | 1.10 |
December | 0.603693E+10 | 63832.98 | 11-DEC-08:61 | -14.8 |
Annual Sum or Average | 0.246185E+11 | |||
Minimum of Months | 26665154.78 | 1671.92 | -15.6 | |
Maximum of Months | 0.694410E+10 | 63842.65 | 24.08 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.220744E+10 | 33636.82 | 10-JAN-08:61 | -9.9 |
February | 0.216694E+10 | 33634.07 | 10-FEB-08:61 | -9.7 |
March | 0.628447E+09 | 33650.55 | 07-MAR-08:61 | -10.8 |
April | 0.117266E+09 | 33614.51 | 17-APR-07:01 | -2.9 |
May | 29926830.31 | 650.05 | 24-MAY-07:10 | 16.52 |
June | 13747550.20 | 1047.71 | 26-JUN-07:05 | 20.28 |
July | 15165186.00 | 1058.54 | 05-JUL-07:05 | 19.50 |
August | 16598747.39 | 1032.03 | 10-AUG-07:05 | 20.28 |
September | 13242810.47 | 992.29 | 15-SEP-07:05 | 18.40 |
October | 41554282.57 | 12974.81 | 30-OCT-07:01 | 0.87 |
November | 0.135182E+09 | 33612.38 | 24-NOV-08:61 | -2.6 |
December | 0.188420E+10 | 33642.96 | 11-DEC-08:61 | -14.8 |
Annual Sum or Average | 0.726972E+10 | |||
Minimum of Months | 13242810.47 | 650.05 | -14.8 | |
Maximum of Months | 0.220744E+10 | 33650.55 | 20.28 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.279069E+10 | 35845.32 | 29-JAN-08:61 | -8.1 |
February | 0.269700E+10 | 35860.78 | 05-FEB-08:61 | -13.0 |
March | 0.934032E+09 | 35862.48 | 05-MAR-08:61 | -9.7 |
April | 0.209326E+09 | 35811.59 | 16-APR-07:01 | -3.7 |
May | 33883688.67 | 696.76 | 24-MAY-06:10 | 18.03 |
June | 20823499.87 | 1395.61 | 17-JUN-17:03 | 28.80 |
July | 31346943.24 | 1655.83 | 16-JUL-16:02 | 30.03 |
August | 28605316.06 | 1434.36 | 13-AUG-16:02 | 29.03 |
September | 14087695.39 | 1098.75 | 15-SEP-06:05 | 18.30 |
October | 55589869.61 | 17807.23 | 30-OCT-06:02 | -0.4 |
November | 0.295603E+09 | 35234.27 | 24-NOV-07:01 | -3.2 |
December | 0.243295E+10 | 35862.51 | 10-DEC-08:61 | -13.0 |
Annual Sum or Average | 0.954395E+10 | |||
Minimum of Months | 14087695.39 | 696.76 | -13.0 | |
Maximum of Months | 0.279069E+10 | 35862.51 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304678E+10 | 35679.68 | 29-JAN-08:61 | -8.1 |
February | 0.291025E+10 | 35694.84 | 05-FEB-08:61 | -13.0 |
March | 0.105415E+10 | 35696.51 | 05-MAR-08:61 | -9.7 |
April | 0.257082E+09 | 35646.31 | 16-APR-07:01 | -3.7 |
May | 39428361.24 | 2489.15 | 01-MAY-06:05 | 2.35 |
June | 21019022.19 | 1397.09 | 17-JUN-17:03 | 28.80 |
July | 31019973.04 | 1655.89 | 16-JUL-16:02 | 30.03 |
August | 28262577.76 | 1434.39 | 13-AUG-16:02 | 29.03 |
September | 14479190.82 | 1090.52 | 15-SEP-06:05 | 18.30 |
October | 66827605.37 | 23490.43 | 30-OCT-06:02 | -0.4 |
November | 0.376163E+09 | 35075.49 | 24-NOV-07:01 | -3.2 |
December | 0.266043E+10 | 35696.67 | 10-DEC-08:61 | -13.0 |
Annual Sum or Average | 0.105059E+11 | |||
Minimum of Months | 14479190.82 | 1090.52 | -13.0 | |
Maximum of Months | 0.304678E+10 | 35696.67 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.343643E+10 | 35678.58 | 29-JAN-08:61 | -8.1 |
February | 0.325464E+10 | 35693.57 | 05-FEB-08:61 | -13.0 |
March | 0.126559E+10 | 35695.27 | 05-MAR-08:61 | -9.7 |
April | 0.327444E+09 | 35644.87 | 16-APR-07:01 | -3.7 |
May | 45825097.79 | 4652.49 | 01-MAY-06:05 | 2.35 |
June | 21941237.14 | 1406.79 | 17-JUN-17:03 | 28.80 |
July | 32592188.11 | 1662.53 | 16-JUL-16:02 | 30.03 |
August | 28751934.36 | 1441.14 | 13-AUG-16:02 | 29.03 |
September | 15802850.27 | 1023.16 | 15-SEP-06:05 | 18.30 |
October | 86100626.51 | 27902.53 | 30-OCT-06:02 | -0.4 |
November | 0.500031E+09 | 35074.88 | 24-NOV-07:01 | -3.2 |
December | 0.300536E+10 | 35695.55 | 10-DEC-08:61 | -13.0 |
Annual Sum or Average | 0.120205E+11 | |||
Minimum of Months | 15802850.27 | 1023.16 | -13.0 | |
Maximum of Months | 0.343643E+10 | 35695.55 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.730819E+10 | 60177.63 | 10-JAN-08:61 | -9.9 |
February | 0.682305E+10 | 60266.12 | 06-FEB-08:61 | -15.0 |
March | 0.281105E+10 | 60198.14 | 07-MAR-08:61 | -10.8 |
April | 0.808595E+09 | 60148.26 | 17-APR-07:01 | -2.9 |
May | 97883887.09 | 59874.42 | 01-MAY-07:01 | 6.05 |
June | 43393321.80 | 2797.46 | 17-JUN-17:03 | 28.80 |
July | 41100466.73 | 3314.26 | 16-JUL-16:02 | 30.03 |
August | 41557854.58 | 2863.45 | 13-AUG-16:02 | 29.03 |
September | 35654572.30 | 1565.03 | 14-SEP-07:05 | 20.60 |
October | 0.240762E+09 | 60145.54 | 17-OCT-07:01 | -2.4 |
November | 0.122966E+10 | 60146.55 | 22-NOV-08:61 | 1.10 |
December | 0.639783E+10 | 60193.33 | 11-DEC-08:61 | -14.8 |
Annual Sum or Average | 0.258787E+11 | |||
Minimum of Months | 35654572.30 | 1565.03 | -15.0 | |
Maximum of Months | 0.730819E+10 | 60266.12 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.412586E+10 | 31679.63 | 10-JAN-08:61 | -9.9 |
February | 0.385224E+10 | 31697.79 | 07-FEB-08:61 | -15.6 |
March | 0.168232E+10 | 31690.85 | 07-MAR-08:61 | -10.8 |
April | 0.498776E+09 | 31661.71 | 17-APR-07:01 | -2.9 |
May | 57762553.60 | 31509.05 | 01-MAY-07:01 | 6.05 |
June | 24797305.98 | 1418.12 | 17-JUN-17:03 | 28.80 |
July | 22360837.70 | 1670.51 | 16-JUL-16:02 | 30.03 |
August | 21980595.74 | 1446.07 | 13-AUG-16:02 | 29.03 |
September | 20356581.65 | 805.56 | 16-SEP-07:05 | 21.88 |
October | 0.144163E+09 | 31660.09 | 17-OCT-07:01 | -2.4 |
November | 0.760946E+09 | 31659.14 | 22-NOV-08:61 | 1.10 |
December | 0.363327E+10 | 31687.49 | 11-DEC-08:61 | -14.8 |
Annual Sum or Average | 0.148448E+11 | |||
Minimum of Months | 20356581.65 | 805.56 | -15.6 | |
Maximum of Months | 0.412586E+10 | 31697.79 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.421498E+10 | 31553.74 | 10-JAN-08:61 | -9.9 |
February | 0.392776E+10 | 31601.09 | 06-FEB-08:61 | -15.0 |
March | 0.175992E+10 | 31564.88 | 07-MAR-08:61 | -10.8 |
April | 0.547076E+09 | 31535.47 | 17-APR-07:01 | -2.9 |
May | 64337436.78 | 31386.60 | 01-MAY-07:01 | 6.05 |
June | 26849243.65 | 1420.83 | 17-JUN-17:03 | 28.80 |
July | 22361675.94 | 1672.10 | 16-JUL-16:02 | 30.03 |
August | 22116946.90 | 1447.62 | 13-AUG-16:02 | 29.03 |
September | 21522129.05 | 786.20 | 16-SEP-07:05 | 21.88 |
October | 0.159406E+09 | 31534.20 | 17-OCT-07:01 | -2.4 |
November | 0.811345E+09 | 31533.28 | 22-NOV-08:61 | 1.10 |
December | 0.371806E+10 | 31561.50 | 11-DEC-08:61 | -14.8 |
Annual Sum or Average | 0.152957E+11 | |||
Minimum of Months | 21522129.05 | 786.20 | -15.0 | |
Maximum of Months | 0.421498E+10 | 31601.09 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.468561E+10 | 31482.00 | 10-JAN-08:12 | -9.8 |
February | 0.434690E+10 | 31460.55 | 14-FEB-08:12 | -9.4 |
March | 0.212147E+10 | 31402.30 | 07-MAR-08:61 | -10.8 |
April | 0.733062E+09 | 31376.16 | 17-APR-07:01 | -2.9 |
May | 89971942.77 | 31229.52 | 01-MAY-07:01 | 6.05 |
June | 31305449.62 | 1428.53 | 17-JUN-17:03 | 28.80 |
July | 21700360.98 | 1674.59 | 16-JUL-16:02 | 30.03 |
August | 22028268.61 | 1450.90 | 13-AUG-16:02 | 29.03 |
September | 26963362.06 | 725.87 | 16-SEP-07:05 | 21.88 |
October | 0.217113E+09 | 31373.10 | 17-OCT-07:01 | -2.4 |
November | 0.102572E+10 | 31373.78 | 22-NOV-08:61 | 1.10 |
December | 0.415319E+10 | 31400.30 | 11-DEC-08:13 | -14.6 |
Annual Sum or Average | 0.174750E+11 | |||
Minimum of Months | 21700360.98 | 725.87 | -14.6 | |
Maximum of Months | 0.468561E+10 | 31482.00 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.755841E+10 | 32678.81 | 24-JAN-08:12 | -12.0 |
February | 0.720663E+10 | 32646.88 | 14-FEB-08:12 | -9.4 |
March | 0.399247E+10 | 32511.59 | 06-MAR-08:61 | -9.2 |
April | 0.164106E+10 | 32376.43 | 17-APR-07:01 | -2.9 |
May | 0.244202E+09 | 32225.55 | 01-MAY-07:01 | 6.05 |
June | 37483291.85 | 1942.93 | 14-JUN-07:05 | 10.18 |
July | 21330339.04 | 1672.80 | 16-JUL-16:02 | 30.03 |
August | 22816583.91 | 1451.94 | 13-AUG-16:02 | 29.03 |
September | 44750316.45 | 16000.99 | 30-SEP-07:03 | 8.17 |
October | 0.502658E+09 | 32381.19 | 17-OCT-07:01 | -2.4 |
November | 0.200146E+10 | 32386.48 | 22-NOV-08:61 | 1.10 |
December | 0.672558E+10 | 32561.51 | 11-DEC-08:13 | -14.6 |
Annual Sum or Average | 0.299989E+11 | |||
Minimum of Months | 21330339.04 | 1451.94 | -14.6 | |
Maximum of Months | 0.755841E+10 | 32678.81 | 30.03 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.986629E+10 | 6035.26 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.891946E+10 | 6035.26 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.987658E+10 | 6035.26 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.956097E+10 | 6035.26 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.986629E+10 | 6035.26 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.956097E+10 | 6035.26 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.987658E+10 | 6035.26 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.986629E+10 | 6035.26 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.957126E+10 | 6035.26 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.986629E+10 | 6035.26 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.953010E+10 | 6035.26 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.988687E+10 | 6035.26 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.116248E+12 | 0.262491E+11 | ||||
Minimum of Months | 0.891946E+10 | 6035.26 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.988687E+10 | 6035.26 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.579394E+10 | 3544.17 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.523792E+10 | 3544.17 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.579999E+10 | 3544.17 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.561464E+10 | 3544.17 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.579394E+10 | 3544.17 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.561464E+10 | 3544.17 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.579999E+10 | 3544.17 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.579394E+10 | 3544.17 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.562069E+10 | 3544.17 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.579394E+10 | 3544.17 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.559651E+10 | 3544.17 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.580603E+10 | 3544.17 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.682662E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.523792E+10 | 3544.17 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.580603E+10 | 3544.17 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.413753E+10 | 3181.37 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.374692E+10 | 3181.37 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.422433E+10 | 3181.37 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.401456E+10 | 3181.37 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.418093E+10 | 3181.37 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.407966E+10 | 3181.37 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.411583E+10 | 3181.37 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.422433E+10 | 3181.37 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.401456E+10 | 3181.37 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.413753E+10 | 3181.37 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.401456E+10 | 3181.37 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.411583E+10 | 3181.37 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.490066E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.374692E+10 | 3181.37 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.422433E+10 | 3181.37 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.413753E+10 | 3181.37 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.374692E+10 | 3181.37 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.422433E+10 | 3181.37 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.401456E+10 | 3181.37 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.418093E+10 | 3181.37 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.407966E+10 | 3181.37 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.411583E+10 | 3181.37 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.422433E+10 | 3181.37 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.401456E+10 | 3181.37 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.413753E+10 | 3181.37 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.401456E+10 | 3181.37 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.411583E+10 | 3181.37 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.490066E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.374692E+10 | 3181.37 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.422433E+10 | 3181.37 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.413753E+10 | 3181.37 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.374692E+10 | 3181.37 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.422433E+10 | 3181.37 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.401456E+10 | 3181.37 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.418093E+10 | 3181.37 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.407966E+10 | 3181.37 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.411583E+10 | 3181.37 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.422433E+10 | 3181.37 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.401456E+10 | 3181.37 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.413753E+10 | 3181.37 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.401456E+10 | 3181.37 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.411583E+10 | 3181.37 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.490066E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.374692E+10 | 3181.37 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.422433E+10 | 3181.37 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.457032E+10 | 3825.14 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.413982E+10 | 3825.14 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.467469E+10 | 3825.14 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.443552E+10 | 3825.14 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.462251E+10 | 3825.14 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.451379E+10 | 3825.14 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.454423E+10 | 3825.14 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.467469E+10 | 3825.14 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.443552E+10 | 3825.14 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.457032E+10 | 3825.14 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.443552E+10 | 3825.14 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.454423E+10 | 3825.14 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.541612E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.413982E+10 | 3825.14 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.467469E+10 | 3825.14 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.986629E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772034E+10 |
February | 0.305697E+10 | 0.891946E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748508E+10 |
March | 0.335708E+10 | 0.987658E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11413652.53 | 0.530620E+10 |
April | 0.327081E+10 | 0.956097E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357003E+10 |
May | 0.336680E+10 | 0.986629E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10366331.92 | 0.207648E+10 |
June | 0.325380E+10 | 0.956097E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184213E+09 | 0.105989E+10 |
July | 0.339353E+10 | 0.987658E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443262E+09 | 0.375325E+09 |
August | 0.334857E+10 | 0.986629E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372450E+09 | 0.553321E+09 |
September | 0.327932E+10 | 0.957126E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35643433.85 | 0.135516E+10 |
October | 0.338624E+10 | 0.986629E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319427E+10 |
November | 0.327446E+10 | 0.953010E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431019E+10 |
December | 0.340325E+10 | 0.988687E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.757756E+10 |
Annual Sum or Average | 0.397770E+11 | 0.116248E+12 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105735E+10 | 0.445839E+11 |
Minimum of Months | 0.305697E+10 | 0.891946E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375325E+09 |
Maximum of Months | 0.340325E+10 | 0.988687E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443262E+09 | 0.772034E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.579394E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372415E+10 |
February | 0.152844E+10 | 0.523792E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355622E+10 |
March | 0.167849E+10 | 0.579999E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6181579.52 | 0.259434E+10 |
April | 0.163536E+10 | 0.561464E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175401E+10 |
May | 0.168335E+10 | 0.579394E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5590654.23 | 0.103903E+10 |
June | 0.162685E+10 | 0.561464E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97849470.90 | 0.480823E+09 |
July | 0.169671E+10 | 0.579999E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236682E+09 | 0.148626E+09 |
August | 0.167424E+10 | 0.579394E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200314E+09 | 0.232787E+09 |
September | 0.163961E+10 | 0.562069E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19255074.44 | 0.646091E+09 |
October | 0.169307E+10 | 0.579394E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158613E+10 |
November | 0.163718E+10 | 0.559651E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209975E+10 |
December | 0.170157E+10 | 0.580603E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362723E+10 |
Annual Sum or Average | 0.198880E+11 | 0.682662E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565873E+09 | 0.214892E+11 |
Minimum of Months | 0.152844E+10 | 0.523792E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148626E+09 |
Maximum of Months | 0.170157E+10 | 0.580603E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236682E+09 | 0.372415E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383570E+10 |
February | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366930E+10 |
March | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6182281.89 | 0.266071E+10 |
April | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180713E+10 |
May | 0.102058E+10 | 0.418093E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5590616.85 | 0.107383E+10 |
June | 0.998711E+09 | 0.407966E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94421730.67 | 0.509483E+09 |
July | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230575E+09 | 0.175517E+09 |
August | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195405E+09 | 0.260093E+09 |
September | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19076235.79 | 0.677800E+09 |
October | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161992E+10 |
November | 0.973196E+09 | 0.401456E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214644E+10 |
December | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375625E+10 |
Annual Sum or Average | 0.119700E+11 | 0.490066E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551251E+09 | 0.221922E+11 |
Minimum of Months | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175517E+09 |
Maximum of Months | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230575E+09 | 0.383570E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382745E+10 |
February | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366098E+10 |
March | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6182281.01 | 0.265362E+10 |
April | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179353E+10 |
May | 0.102058E+10 | 0.418093E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5590823.22 | 0.106222E+10 |
June | 0.998711E+09 | 0.407966E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94430276.67 | 0.508838E+09 |
July | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230543E+09 | 0.175791E+09 |
August | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195407E+09 | 0.260285E+09 |
September | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19076459.96 | 0.676395E+09 |
October | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160729E+10 |
November | 0.973196E+09 | 0.401456E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213501E+10 |
December | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374758E+10 |
Annual Sum or Average | 0.119700E+11 | 0.490066E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551230E+09 | 0.221090E+11 |
Minimum of Months | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175791E+09 |
Maximum of Months | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230543E+09 | 0.382745E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382046E+10 |
February | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365410E+10 |
March | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6182289.83 | 0.264598E+10 |
April | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177653E+10 |
May | 0.102058E+10 | 0.418093E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5591760.98 | 0.104251E+10 |
June | 0.998711E+09 | 0.407966E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94479079.79 | 0.505288E+09 |
July | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230688E+09 | 0.173453E+09 |
August | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195460E+09 | 0.258097E+09 |
September | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19077190.41 | 0.672316E+09 |
October | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159062E+10 |
November | 0.973196E+09 | 0.401456E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212383E+10 |
December | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374024E+10 |
Annual Sum or Average | 0.119700E+11 | 0.490066E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551479E+09 | 0.220034E+11 |
Minimum of Months | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173453E+09 |
Maximum of Months | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230688E+09 | 0.382046E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.457032E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704157E+10 |
February | 0.313522E+10 | 0.413982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675897E+10 |
March | 0.355148E+10 | 0.467469E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11123444.75 | 0.486306E+10 |
April | 0.338259E+10 | 0.443552E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324130E+10 |
May | 0.349753E+10 | 0.462251E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10070363.03 | 0.186008E+10 |
June | 0.343071E+10 | 0.451379E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170802E+09 | 0.936755E+09 |
July | 0.344942E+10 | 0.454423E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416941E+09 | 0.327859E+09 |
August | 0.355148E+10 | 0.467469E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352534E+09 | 0.485618E+09 |
September | 0.338259E+10 | 0.443552E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34335697.88 | 0.123642E+10 |
October | 0.344359E+10 | 0.457032E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288578E+10 |
November | 0.331698E+10 | 0.443552E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390091E+10 |
December | 0.344942E+10 | 0.454423E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690737E+10 |
Annual Sum or Average | 0.410346E+11 | 0.541612E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.995807E+09 | 0.404457E+11 |
Minimum of Months | 0.313522E+10 | 0.413982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327859E+09 |
Maximum of Months | 0.355148E+10 | 0.467469E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416941E+09 | 0.704157E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383810E+10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367545E+10 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6181552.89 | 0.265214E+10 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175657E+10 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593735.79 | 0.100183E+10 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94758691.37 | 0.502802E+09 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231472E+09 | 0.171246E+09 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195875E+09 | 0.257098E+09 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19079234.98 | 0.669375E+09 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156709E+10 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212194E+10 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375827E+10 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552960E+09 | 0.219719E+11 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171246E+09 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231472E+09 | 0.383810E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383629E+10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367381E+10 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6181785.06 | 0.264946E+10 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175048E+10 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593735.57 | 0.990608E+09 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94790413.08 | 0.500883E+09 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231530E+09 | 0.170467E+09 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195907E+09 | 0.256348E+09 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19079614.21 | 0.667146E+09 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156036E+10 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211883E+10 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375626E+10 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553082E+09 | 0.219309E+11 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170467E+09 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231530E+09 | 0.383629E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382664E+10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366511E+10 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6181835.89 | 0.263933E+10 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173391E+10 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593735.13 | 0.962743E+09 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94872882.58 | 0.494684E+09 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231657E+09 | 0.168138E+09 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195976E+09 | 0.254099E+09 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19080105.03 | 0.660535E+09 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154456E+10 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210868E+10 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374616E+10 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553362E+09 | 0.218046E+11 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168138E+09 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231657E+09 | 0.382664E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488788E+10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481018E+10 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6484579.44 | 0.330721E+10 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222390E+10 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5893499.99 | 0.118816E+10 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102374E+09 | 0.676694E+09 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247902E+09 | 0.276034E+09 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206781E+09 | 0.392672E+09 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19999164.20 | 0.858782E+09 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194990E+10 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268898E+10 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485794E+10 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589434E+09 | 0.281183E+11 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276034E+09 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247902E+09 | 0.488788E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 6035.26 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 11393.74 | 31-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 6035.26 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 12700.39 | 06-FEB-17:00 |
March | 4050.04 | 03-MAR-13:09 | 6035.26 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 659.71 | 15-MAR-14:00 | 10040.83 | 06-MAR-18:00 |
April | 4050.04 | 01-APR-12:09 | 6035.26 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 8058.18 | 16-APR-11:10 |
May | 4050.04 | 05-MAY-12:09 | 6035.26 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 675.61 | 14-MAY-15:00 | 3955.51 | 11-MAY-15:00 |
June | 4050.04 | 02-JUN-12:09 | 6035.26 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2026.26 | 27-JUN-13:00 | 4054.70 | 13-JUN-11:10 |
July | 4050.04 | 01-JUL-12:09 | 6035.26 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2263.15 | 21-JUL-14:00 | 1647.48 | 02-JUL-11:10 |
August | 4050.04 | 04-AUG-12:09 | 6035.26 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1958.00 | 10-AUG-14:00 | 2795.78 | 31-AUG-11:10 |
September | 4050.04 | 01-SEP-12:09 | 6035.26 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1007.76 | 16-SEP-13:00 | 3620.52 | 28-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 6035.26 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5309.52 | 23-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 6035.26 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6512.23 | 22-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 6035.26 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 11348.04 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1647.48 | |||||
Maximum of Months | 4050.04 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2263.15 | 12700.39 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3544.17 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 3544.17 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6778.27 | 06-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 3544.17 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.16 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 3544.17 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 3544.17 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 358.90 | 14-MAY-15:00 | 2226.14 | 11-MAY-15:00 |
June | 2024.96 | 02-JUN-12:09 | 3544.17 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2293.24 | 13-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 3544.17 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.53 | 02-JUL-11:10 |
August | 2024.96 | 04-AUG-12:09 | 3544.17 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1061.96 | 10-AUG-14:00 | 1552.23 | 31-AUG-11:10 |
September | 2024.96 | 01-SEP-12:09 | 3544.17 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.90 | 16-SEP-13:00 | 2066.45 | 28-SEP-16:30 |
October | 2024.96 | 01-OCT-12:09 | 3544.17 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2024.96 | 03-NOV-12:09 | 3544.17 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 3544.17 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3544.17 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.53 | |||||
Maximum of Months | 2024.96 | 3544.17 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3181.37 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 3181.37 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6778.27 | 06-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3181.37 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.19 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 3181.37 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 3181.37 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 358.92 | 14-MAY-15:00 | 2201.13 | 11-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 3181.37 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2302.54 | 13-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 3181.37 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.61 | 02-JUL-11:10 |
August | 2024.96 | 05-AUG-12:09 | 3181.37 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.04 | 10-AUG-14:00 | 1550.70 | 31-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 3181.37 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.90 | 16-SEP-13:00 | 2053.49 | 28-SEP-16:30 |
October | 2024.96 | 07-OCT-12:09 | 3181.37 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 3181.37 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 3181.37 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.61 | |||||
Maximum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3181.37 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 3181.37 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6778.27 | 06-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3181.37 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.19 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 3181.37 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 3181.37 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 358.92 | 14-MAY-15:00 | 2179.59 | 11-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 3181.37 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2300.61 | 13-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 3181.37 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.61 | 02-JUL-11:10 |
August | 2024.96 | 05-AUG-12:09 | 3181.37 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.02 | 10-AUG-14:00 | 1549.39 | 31-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 3181.37 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.90 | 16-SEP-13:00 | 2045.77 | 28-SEP-16:30 |
October | 2024.96 | 07-OCT-12:09 | 3181.37 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 3181.37 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 3181.37 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.61 | |||||
Maximum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3181.37 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 3181.37 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6778.27 | 06-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3181.37 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.19 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 3181.37 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 3181.37 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 358.91 | 14-MAY-15:00 | 2136.63 | 11-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 3181.37 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2277.89 | 13-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 3181.37 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.59 | 02-JUL-11:10 |
August | 2024.96 | 05-AUG-12:09 | 3181.37 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.05 | 10-AUG-14:00 | 1543.18 | 31-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 3181.37 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.89 | 16-SEP-13:00 | 2024.47 | 28-SEP-16:30 |
October | 2024.96 | 07-OCT-12:09 | 3181.37 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 3181.37 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 3181.37 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.59 | |||||
Maximum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3825.14 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 11118.18 | 31-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 3825.14 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 12216.69 | 06-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3825.14 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 641.12 | 15-MAR-14:00 | 9818.19 | 06-MAR-18:00 |
April | 5400.05 | 01-APR-14:09 | 3825.14 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 7828.71 | 16-APR-11:10 |
May | 5400.05 | 06-MAY-14:09 | 3825.14 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 647.63 | 14-MAY-15:00 | 3797.45 | 11-MAY-15:00 |
June | 5400.05 | 03-JUN-14:09 | 3825.14 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1949.06 | 27-JUN-13:00 | 3978.01 | 13-JUN-11:10 |
July | 5400.05 | 01-JUL-14:09 | 3825.14 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2212.96 | 21-JUL-14:00 | 1609.17 | 02-JUL-11:10 |
August | 5400.05 | 05-AUG-14:09 | 3825.14 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1910.76 | 10-AUG-14:00 | 2737.39 | 31-AUG-11:10 |
September | 5400.05 | 02-SEP-14:09 | 3825.14 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 971.23 | 16-SEP-13:00 | 3505.82 | 28-SEP-16:30 |
October | 5400.05 | 07-OCT-14:09 | 3825.14 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5204.75 | 23-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 3825.14 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6438.11 | 22-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 3825.14 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 11218.88 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1609.17 | |||||
Maximum of Months | 5400.05 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2212.96 | 12216.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6778.27 | 06-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.14 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2206.59 | 13-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.51 | 02-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.05 | 10-AUG-14:00 | 1518.61 | 31-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.87 | 16-SEP-13:00 | 1949.82 | 28-SEP-16:20 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.51 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6778.27 | 06-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.14 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2196.24 | 13-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.51 | 02-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.05 | 10-AUG-14:00 | 1510.56 | 31-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.87 | 16-SEP-13:00 | 1939.69 | 28-SEP-16:20 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.51 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6778.27 | 06-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.14 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2163.44 | 13-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.51 | 02-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.05 | 10-AUG-14:00 | 1496.07 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.86 | 16-SEP-13:00 | 1908.73 | 28-SEP-16:20 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.51 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6455.29 | 31-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 7285.77 | 06-FEB-17:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 374.72 | 15-MAR-14:00 | 5681.40 | 06-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4578.11 | 16-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 387.28 | 14-MAY-15:00 | 2263.84 | 11-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1158.31 | 27-JUN-13:00 | 2159.42 | 13-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1284.48 | 15-JUL-15:00 | 932.70 | 02-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1109.39 | 10-AUG-14:00 | 1578.18 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 575.37 | 16-SEP-13:00 | 1877.92 | 28-SEP-16:30 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3011.82 | 23-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3659.14 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6376.32 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 932.70 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1284.48 | 7285.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13618.69 | 06-JAN-00:02 | 2025.02 | 1905.75 | 4477.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.62 |
February | 13636.00 | 11-FEB-00:02 | 2025.02 | 19058.65 | 4477.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.20 |
March | 13369.64 | 04-MAR-00:02 | 2025.02 | 19058.65 | 4477.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.40 |
April | 7991.26 | 13-APR-23:03 | 1012.51 | 952.88 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.91 |
May | 8623.23 | 14-MAY-15:00 | 2700.03 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 675.61 | 0.00 |
June | 28176.65 | 12-JUN-07:03 | 1350.01 | 1270.50 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 6.19 | 0.00 |
July | 31803.37 | 26-JUL-07:02 | 1687.52 | 1588.13 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.80 |
August | 36965.53 | 06-AUG-07:02 | 2025.02 | 1905.75 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.66 |
September | 28440.26 | 17-SEP-07:02 | 2025.02 | 1905.75 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.53 |
October | 8552.63 | 11-OCT-17:10 | 3375.03 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.64 |
November | 9699.60 | 24-NOV-00:03 | 1350.01 | 1270.50 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.99 |
December | 13310.49 | 29-DEC-00:02 | 2025.02 | 1905.75 | 4477.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 622.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7991.26 | 1012.51 | 952.88 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36965.53 | 3375.03 | 19058.65 | 4477.50 | 0.00 | 0.00 | 0.00 | 0.00 | 675.61 | 622.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5829.21 | 23-JAN-10:52 | 1687.47 | 17720.87 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 795.79 |
February | 6017.81 | 10-FEB-10:32 | 1687.47 | 17720.87 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 734.11 |
March | 14098.65 | 15-MAR-20:57 | 7087.36 | 24809.22 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.98 |
April | 4011.61 | 10-APR-17:20 | 1687.47 | 3544.17 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.91 |
May | 17565.20 | 21-MAY-18:29 | 9449.82 | 24809.22 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.91 |
June | 17194.85 | 03-JUN-18:06 | 13499.74 | 28353.40 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.22 |
July | 17675.08 | 26-JUL-07:02 | 843.73 | 932.68 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.83 |
August | 20358.98 | 06-AUG-07:02 | 1012.48 | 1119.21 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.19 |
September | 16726.76 | 10-SEP-17:32 | 10124.81 | 17720.87 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.85 |
October | 13850.30 | 22-OCT-21:13 | 4724.91 | 24809.22 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.03 |
November | 4618.63 | 05-NOV-17:10 | 6074.88 | 10632.52 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.82 |
December | 5839.18 | 08-DEC-11:22 | 1687.47 | 17720.87 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 759.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4011.61 | 843.73 | 932.68 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.98 | |
Maximum of Months | 20358.98 | 13499.74 | 28353.40 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 795.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1882.78 | 11-JAN-18:10 | 1687.47 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.67 |
February | 6471.25 | 21-FEB-18:22 | 8437.34 | 15906.87 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1010.88 |
March | 5220.68 | 24-MAR-09:13 | 1349.97 | 12725.50 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.17 |
April | 4053.69 | 24-APR-07:01 | 1518.72 | 15069.67 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.76 |
May | 4740.06 | 27-MAY-13:00 | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.05 |
June | 17877.33 | 26-JUN-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 |
July | 18723.17 | 05-JUL-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 |
August | 20879.09 | 06-AUG-07:02 | 0.00 | 1004.64 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.56 |
September | 16531.45 | 15-SEP-06:03 | 0.00 | 669.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.43 |
October | 4442.88 | 11-OCT-16:10 | 1687.47 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.78 |
November | 4054.80 | 07-NOV-08:61 | 1687.47 | 16744.07 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 536.84 |
December | 5135.60 | 25-DEC-11:23 | 2699.95 | 12725.50 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 728.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1882.78 | 0.00 | 669.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.43 | |
Maximum of Months | 20879.09 | 8437.34 | 16744.07 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1010.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5631.52 | 04-JAN-11:43 | 1349.97 | 12725.50 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 782.55 |
February | 5964.37 | 25-FEB-11:02 | 3374.94 | 15906.87 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.16 |
March | 5853.76 | 07-MAR-20:35 | 674.99 | 6697.63 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.58 |
April | 3978.66 | 24-APR-07:01 | 1518.72 | 15069.67 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.38 |
May | 4657.23 | 27-MAY-13:00 | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.05 |
June | 17780.10 | 26-JUN-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 |
July | 18650.42 | 05-JUL-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.97 |
August | 20789.12 | 06-AUG-07:02 | 0.00 | 1004.64 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.34 |
September | 16459.00 | 15-SEP-06:03 | 0.00 | 669.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.43 |
October | 4202.30 | 11-OCT-16:10 | 1687.47 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.78 |
November | 4003.18 | 07-NOV-08:61 | 1687.47 | 16744.07 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.29 |
December | 5915.05 | 06-DEC-19:42 | 3374.94 | 15906.87 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 782.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3978.66 | 0.00 | 669.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.43 | |
Maximum of Months | 20789.12 | 3374.94 | 16744.07 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5698.75 | 28-JAN-11:32 | 3374.94 | 15906.87 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 802.42 |
February | 5076.38 | 16-FEB-20:12 | 674.99 | 6697.63 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.92 |
March | 4124.37 | 18-MAR-07:01 | 1687.47 | 16744.07 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.94 |
April | 3875.51 | 24-APR-07:01 | 1518.72 | 15069.67 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.53 |
May | 4396.97 | 27-MAY-13:00 | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.05 |
June | 17641.05 | 26-JUN-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.23 |
July | 18523.15 | 05-JUL-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.53 |
August | 20667.40 | 06-AUG-07:02 | 0.00 | 1004.64 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.28 |
September | 15523.95 | 17-SEP-07:02 | 0.00 | 1004.64 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.09 |
October | 4115.89 | 24-OCT-07:02 | 1012.48 | 10046.44 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.50 |
November | 3784.84 | 28-NOV-08:61 | 1518.72 | 15069.67 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.24 |
December | 3985.60 | 02-DEC-18:43 | 506.24 | 5023.22 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3784.84 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.23 | |
Maximum of Months | 20667.40 | 3374.94 | 16744.07 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 802.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1193.25 | 21-JAN-12:00 | 3915.04 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1160.69 |
February | 1538.29 | 18-FEB-12:00 | 3915.04 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1016.78 |
March | 11737.16 | 03-MAR-18:12 | 11475.11 | 19125.69 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1497.39 |
April | 7572.88 | 10-APR-16:43 | 14377.64 | 11475.41 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5630.98 |
May | 7233.75 | 27-MAY-14:20 | 5400.05 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 649.90 |
June | 27542.91 | 26-JUN-07:03 | 0.00 | 805.21 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.57 |
July | 31091.29 | 05-JUL-07:03 | 0.00 | 805.21 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.36 |
August | 33581.42 | 11-AUG-07:02 | 0.00 | 1006.52 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.39 |
September | 26614.76 | 17-SEP-08:62 | 0.00 | 1006.52 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.14 |
October | 6821.35 | 24-OCT-11:03 | 9315.09 | 11475.41 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5084.08 |
November | 7841.73 | 21-NOV-20:43 | 2227.52 | 6039.66 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.70 |
December | 2969.76 | 16-DEC-12:00 | 3915.04 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1193.25 | 0.00 | 805.21 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.14 | |
Maximum of Months | 33581.42 | 14377.64 | 19125.69 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5630.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3999.80 | 18-JAN-18:23 | 3442.43 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.23 |
February | 1587.69 | 22-FEB-17:15 | 4792.41 | 3927.65 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.43 |
March | 5905.63 | 04-MAR-11:52 | 9787.31 | 9819.13 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 736.16 |
April | 3860.50 | 17-APR-10:03 | 4353.67 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.11 |
May | 3619.77 | 27-MAY-14:30 | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.90 |
June | 13188.12 | 26-JUN-07:03 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.64 |
July | 15828.36 | 26-JUL-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.88 |
August | 17411.03 | 11-AUG-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.09 |
September | 13795.40 | 17-SEP-08:62 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.21 |
October | 3813.97 | 24-OCT-08:23 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.11 |
November | 4191.16 | 29-NOV-20:53 | 1484.97 | 4134.37 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.12 |
December | 3834.69 | 23-DEC-11:13 | 5872.39 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1587.69 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.12 | |
Maximum of Months | 17411.03 | 9787.31 | 9819.13 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3398.38 | 14-JAN-11:23 | 5872.39 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.60 |
February | 623.69 | 18-FEB-12:00 | 1957.46 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.94 |
March | 4449.56 | 01-MAR-19:23 | 3509.93 | 7855.30 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 629.78 |
April | 3590.44 | 15-APR-17:13 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.84 |
May | 3477.27 | 27-MAY-14:30 | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.90 |
June | 12403.10 | 26-JUN-07:03 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.42 |
July | 15707.82 | 26-JUL-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.92 |
August | 17283.55 | 11-AUG-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.15 |
September | 13690.48 | 17-SEP-08:62 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.25 |
October | 3260.94 | 14-OCT-08:63 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.59 |
November | 4149.82 | 29-NOV-20:33 | 1484.97 | 4134.37 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.35 |
December | 1411.31 | 16-DEC-12:00 | 1957.46 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 623.69 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.35 | |
Maximum of Months | 17283.55 | 5872.39 | 7855.30 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 629.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2826.62 | 11-JAN-18:43 | 3442.43 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.70 |
February | 366.37 | 18-FEB-12:00 | 1957.46 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.94 |
March | 4133.53 | 02-MAR-19:23 | 3509.93 | 7855.30 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.07 |
April | 3504.17 | 13-APR-09:53 | 1113.73 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.66 |
May | 3154.57 | 27-MAY-14:30 | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.90 |
June | 10747.14 | 18-JUN-08:62 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 9.68 | 0.00 |
July | 15234.60 | 26-JUL-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.75 |
August | 17067.98 | 11-AUG-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.68 |
September | 13492.50 | 17-SEP-08:62 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.43 |
October | 3186.49 | 14-OCT-08:63 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.70 |
November | 4052.75 | 22-NOV-11:33 | 4353.67 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.91 |
December | 3002.15 | 01-DEC-20:23 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 366.37 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17067.98 | 4353.67 | 7855.30 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 9.68 | 554.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 206.72 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 665.22 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 206.72 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 851.04 |
March | 3263.97 | 17-MAR-19:33 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.04 |
April | 3344.16 | 13-APR-18:23 | 2632.45 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 513.09 |
May | 2706.53 | 27-MAY-14:10 | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.34 |
June | 7508.26 | 18-JUN-08:62 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 19.92 | 0.00 |
July | 12224.98 | 19-JUL-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.89 |
August | 14420.14 | 07-AUG-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.21 |
September | 13565.70 | 17-SEP-08:62 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.13 |
October | 2729.90 | 11-OCT-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.14 |
November | 3222.07 | 07-NOV-18:13 | 3442.43 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 572.88 |
December | 538.42 | 16-DEC-12:00 | 1957.46 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 206.72 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14420.14 | 3442.43 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 19.92 | 851.04 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.803517E+11 | 64938.68 | 18-JAN-18:30 | 0.159090E+12 | 214499.55 | 24-JAN-08:09 |
February | 0.719529E+11 | 62981.55 | 02-FEB-17:30 | 0.148885E+12 | 241918.43 | 06-FEB-12:09 |
March | 0.784939E+11 | 69026.14 | 15-MAR-14:39 | 0.876419E+11 | 191358.49 | 06-MAR-08:09 |
April | 0.724845E+11 | 60245.58 | 04-APR-18:40 | 0.334180E+11 | 138655.32 | 17-APR-07:10 |
May | 0.754413E+11 | 67621.21 | 10-MAY-14:09 | 0.162134E+10 | 45840.57 | 01-MAY-07:10 |
June | 0.843511E+11 | 88735.73 | 27-JUN-12:50 | 1888146.86 | 1049.31 | 14-JUN-07:10 |
July | 0.992851E+11 | 93017.47 | 21-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.963586E+11 | 88524.95 | 13-AUG-14:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.812374E+11 | 80474.95 | 16-SEP-13:20 | 32417726.03 | 5112.03 | 30-SEP-07:10 |
October | 0.765757E+11 | 61962.61 | 11-OCT-15:20 | 0.142624E+11 | 90866.14 | 30-OCT-07:10 |
November | 0.755854E+11 | 62190.77 | 29-NOV-18:40 | 0.514035E+11 | 125325.44 | 24-NOV-08:09 |
December | 0.801789E+11 | 61947.82 | 28-DEC-17:00 | 0.145801E+12 | 222187.55 | 11-DEC-08:09 |
Annual Sum or Average | 0.972297E+12 | 0.642158E+12 | ||||
Minimum of Months | 0.719529E+11 | 60245.58 | 0.00 | 0.00 | ||
Maximum of Months | 0.992851E+11 | 93017.47 | 0.159090E+12 | 241918.43 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.420288E+11 | 0.109724E+11 | 0.108325E+11 | 0.00 | 0.108110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570705E+10 | 0.00 |
February | 0.380395E+11 | 0.903490E+10 | 0.980803E+10 | 0.00 | 0.987731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519307E+10 | 0.00 |
March | 0.426243E+11 | 0.879445E+10 | 0.110075E+11 | 0.00 | 0.973786E+10 | 0.00 | 0.00 | 0.582934E+09 | 0.00 | 0.00 | 0.00 | 0.574696E+10 | 0.00 |
April | 0.407637E+11 | 0.728979E+10 | 0.105079E+11 | 0.00 | 0.845492E+10 | 0.00 | 0.00 | 16806237.87 | 0.00 | 0.00 | 0.00 | 0.545141E+10 | 0.00 |
May | 0.423184E+11 | 0.650168E+10 | 0.109147E+11 | 0.00 | 0.833029E+10 | 0.00 | 0.00 | 0.185870E+10 | 0.00 | 0.00 | 0.00 | 0.551750E+10 | 0.00 |
June | 0.411980E+11 | 0.582775E+10 | 0.106386E+11 | 0.00 | 0.809872E+10 | 0.00 | 0.00 | 0.133414E+11 | 0.00 | 0.00 | 0.00 | 0.524664E+10 | 0.00 |
July | 0.419004E+11 | 0.617742E+10 | 0.107945E+11 | 0.00 | 0.826865E+10 | 0.00 | 0.00 | 0.268450E+11 | 0.00 | 0.00 | 0.00 | 0.529910E+10 | 0.00 |
August | 0.426079E+11 | 0.705209E+10 | 0.110006E+11 | 0.00 | 0.837524E+10 | 0.00 | 0.00 | 0.219984E+11 | 0.00 | 0.00 | 0.00 | 0.532436E+10 | 0.00 |
September | 0.407800E+11 | 0.798488E+10 | 0.105148E+11 | 0.00 | 0.801631E+10 | 0.00 | 0.00 | 0.878624E+10 | 0.00 | 0.00 | 0.00 | 0.515527E+10 | 0.00 |
October | 0.420288E+11 | 0.950345E+10 | 0.108325E+11 | 0.00 | 0.841268E+10 | 0.00 | 0.00 | 0.377857E+09 | 0.00 | 0.00 | 0.00 | 0.542049E+10 | 0.00 |
November | 0.407147E+11 | 0.102833E+11 | 0.104978E+11 | 0.00 | 0.873457E+10 | 0.00 | 0.00 | 781592.80 | 0.00 | 0.00 | 0.00 | 0.535428E+10 | 0.00 |
December | 0.419167E+11 | 0.112644E+11 | 0.108050E+11 | 0.00 | 0.105535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563933E+10 | 0.00 |
Annual Sum or Average | 0.496921E+12 | 0.100686E+12 | 0.128154E+12 | 0.00 | 0.107671E+12 | 0.00 | 0.00 | 0.738081E+11 | 0.00 | 0.00 | 0.00 | 0.650554E+11 | 0.00 |
Minimum of Months | 0.380395E+11 | 0.582775E+10 | 0.980803E+10 | 0.00 | 0.801631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515527E+10 | 0.00 |
Maximum of Months | 0.426243E+11 | 0.112644E+11 | 0.110075E+11 | 0.00 | 0.108110E+11 | 0.00 | 0.00 | 0.268450E+11 | 0.00 | 0.00 | 0.00 | 0.574696E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.159090E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.148885E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.876419E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.334180E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.162134E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1888146.86 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 32417726.03 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.142624E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.514035E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.145801E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.642158E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.159090E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30804.00 | 01-JAN-11:09 | 7723.25 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 9255.81 | 24-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30804.00 | 01-FEB-10:09 | 7723.25 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 9732.09 | 06-FEB-12:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 30804.00 | 01-MAR-10:09 | 7723.25 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 8861.39 | 06-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 30804.00 | 01-APR-09:09 | 7723.25 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 7963.80 | 17-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 30804.00 | 01-MAY-09:09 | 7723.25 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 6380.95 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 30804.00 | 01-JUN-09:09 | 7723.25 | 01-JUN-19:49 | 8059.50 | 01-JUN-09:09 | 0.00 | 7137.62 | 27-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 30804.00 | 01-JUL-09:09 | 7723.25 | 01-JUL-19:00 | 8059.50 | 01-JUL-09:09 | 0.00 | 7778.01 | 21-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 30804.00 | 01-AUG-09:09 | 7723.25 | 01-AUG-19:40 | 8059.50 | 01-AUG-09:09 | 0.00 | 7487.42 | 14-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 30804.00 | 01-SEP-09:09 | 7723.25 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 6794.57 | 16-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 30804.00 | 01-OCT-10:09 | 7723.25 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 7149.46 | 30-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30804.00 | 01-NOV-09:09 | 7723.25 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7737.17 | 24-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30804.00 | 01-DEC-10:09 | 7723.25 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 9390.43 | 11-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30804.00 | 7723.25 | 8059.50 | 0.00 | 6380.95 | 0.00 | 0.00 | |||||
Maximum of Months | 30804.00 | 7723.25 | 8059.50 | 0.00 | 9732.09 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 12753.28 | 08-JAN-13:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 10887.88 | 08-FEB-13:50 | 0.00 |
March | 15298.69 | 15-MAR-14:09 | 0.00 | 0.00 | 0.00 | 11803.60 | 30-MAR-18:49 | 0.00 |
April | 2649.82 | 08-APR-12:00 | 0.00 | 0.00 | 0.00 | 8829.72 | 04-APR-11:39 | 0.00 |
May | 18737.87 | 14-MAY-14:00 | 0.00 | 0.00 | 0.00 | 8668.94 | 26-MAY-17:49 | 0.00 |
June | 38893.76 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 9711.35 | 01-JUN-13:09 | 0.00 |
July | 39264.14 | 15-JUL-13:00 | 0.00 | 0.00 | 0.00 | 9699.37 | 17-JUL-13:00 | 0.00 |
August | 37668.58 | 13-AUG-14:00 | 0.00 | 0.00 | 0.00 | 7579.61 | 04-AUG-12:00 | 0.00 |
September | 28754.42 | 16-SEP-13:00 | 0.00 | 0.00 | 0.00 | 7579.16 | 29-SEP-13:50 | 0.00 |
October | 10651.15 | 11-OCT-14:00 | 0.00 | 0.00 | 0.00 | 9703.97 | 07-OCT-13:20 | 0.00 |
November | 250.54 | 05-NOV-22:00 | 0.00 | 0.00 | 0.00 | 9592.45 | 29-NOV-14:09 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 10639.79 | 30-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7579.16 | 0.00 | ||
Maximum of Months | 39264.14 | 0.00 | 0.00 | 0.00 | 12753.28 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 64938.68 | 18-JAN-18:30 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 6535.95 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 62981.55 | 02-FEB-17:30 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 7890.25 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 69026.14 | 15-MAR-14:39 | 30804.00 | 8059.50 | 0.00 | 0.00 | 5596.42 | 0.00 | 0.00 | 14855.90 | 0.00 |
April | 60245.58 | 04-APR-18:40 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 6459.51 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 67621.21 | 10-MAY-14:09 | 30804.00 | 8059.50 | 0.00 | 0.00 | 5596.42 | 0.00 | 0.00 | 17428.49 | 0.00 |
June | 88735.73 | 27-JUN-12:50 | 30804.00 | 8059.50 | 0.00 | 0.00 | 6990.50 | 0.00 | 0.00 | 38260.02 | 0.00 |
July | 93017.47 | 21-JUL-13:00 | 30804.00 | 8059.50 | 0.00 | 0.00 | 6755.03 | 0.00 | 0.00 | 37700.26 | 0.00 |
August | 88524.95 | 13-AUG-14:39 | 30804.00 | 8059.50 | 0.00 | 0.00 | 6829.85 | 0.00 | 0.00 | 37407.66 | 0.00 |
September | 80474.95 | 16-SEP-13:20 | 30804.00 | 8059.50 | 0.00 | 0.00 | 5596.42 | 0.00 | 0.00 | 28439.03 | 0.00 |
October | 61962.61 | 11-OCT-15:20 | 30804.00 | 8059.50 | 0.00 | 0.00 | 5596.42 | 0.00 | 0.00 | 9950.66 | 0.00 |
November | 62190.77 | 29-NOV-18:40 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 6365.10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 61947.82 | 28-DEC-17:00 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 8661.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 60245.58 | 30804.00 | 8059.50 | 0.00 | 0.00 | 5596.42 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 93017.47 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 8661.67 | 0.00 | 0.00 | 38260.02 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 214499.55 | 24-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 241918.43 | 06-FEB-12:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 191358.49 | 06-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 138655.32 | 17-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 45840.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1049.31 | 14-JUN-07:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 5112.03 | 30-SEP-07:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 90866.14 | 30-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 125325.44 | 24-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 222187.55 | 11-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 241918.43 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 20.44 | 1.17 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
February | 3.67 | 20.31 | 1.33 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
March | 1.17 | 20.53 | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
April | 0.33 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
December | 2.50 | 20.42 | 1.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Annual Sum or Average | 11.17 | 20.41 | 3.67 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 20.55 | 1.33 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.83 | 20.50 | 0.17 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 20.50 | 0.17 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.50 | 0.17 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.67 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Annual Sum or Average | 1.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
February | 2.50 | 19.94 | 0.00 | 19.94 | 0.00 | 19.94 | 0.00 | 19.94 |
March | 0.50 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Annual Sum or Average | 7.00 | 20.22 | 0.00 | 20.22 | 0.00 | 20.22 | 0.00 | 20.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
February | 2.33 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
March | 0.33 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.17 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
Annual Sum or Average | 6.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
February | 2.50 | 19.95 | 0.00 | 19.95 | 0.00 | 19.95 | 0.00 | 19.95 |
March | 0.50 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
Annual Sum or Average | 6.83 | 20.22 | 0.00 | 20.22 | 0.00 | 20.22 | 0.00 | 20.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
February | 3.33 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 |
March | 1.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.67 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 |
Annual Sum or Average | 9.33 | 20.12 | 0.00 | 20.12 | 0.00 | 20.12 | 0.00 | 20.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.50 | 17.76 | 0.00 | 17.76 | 0.00 | 17.76 | 0.00 | 17.76 |
February | 16.00 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 |
March | 4.67 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
April | 1.17 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
December | 8.33 | 17.64 | 0.00 | 17.64 | 0.00 | 17.64 | 0.00 | 17.64 |
Annual Sum or Average | 40.00 | 17.38 | 0.00 | 17.38 | 0.00 | 17.38 | 0.00 | 17.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.06 | 410.00 | 21.05 | 410.00 | 21.05 |
February | 448.00 | 21.05 | 375.67 | 21.04 | 375.67 | 21.04 |
March | 470.17 | 21.18 | 183.83 | 21.13 | 182.33 | 21.11 |
April | 463.50 | 21.55 | 37.67 | 21.50 | 37.67 | 21.47 |
May | 281.50 | 22.61 | 58.33 | 22.83 | 0.00 | 22.83 |
June | 95.17 | 23.54 | 309.00 | 23.81 | 49.17 | 23.82 |
July | 94.33 | 23.89 | 478.33 | 23.89 | 94.33 | 23.89 |
August | 58.67 | 23.86 | 456.33 | 23.89 | 54.83 | 23.89 |
September | 90.67 | 23.35 | 310.00 | 23.77 | 30.67 | 23.78 |
October | 378.67 | 21.73 | 46.50 | 21.92 | 7.17 | 21.91 |
November | 475.50 | 21.31 | 39.50 | 21.27 | 39.50 | 21.24 |
December | 496.00 | 21.05 | 323.67 | 21.04 | 323.67 | 21.04 |
Annual Sum or Average | 3848.17 | 21.57 | 3028.83 | 22.02 | 1605.00 | 21.91 |
Minimum of Months | 58.67 | 21.05 | 37.67 | 21.04 | 0.00 | 21.04 |
Maximum of Months | 496.00 | 23.89 | 478.33 | 23.89 | 410.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.38 | 218.83 | 21.30 | 218.83 | 21.26 |
February | 448.00 | 21.35 | 172.00 | 21.28 | 172.00 | 21.25 |
March | 456.83 | 21.66 | 61.50 | 21.67 | 46.83 | 21.63 |
April | 438.33 | 22.25 | 4.83 | 22.24 | 4.83 | 22.23 |
May | 199.17 | 23.26 | 86.17 | 23.45 | 0.00 | 23.45 |
June | 50.17 | 23.70 | 304.67 | 23.84 | 27.67 | 23.84 |
July | 58.17 | 23.89 | 469.83 | 23.86 | 58.17 | 23.86 |
August | 25.83 | 23.89 | 439.67 | 23.87 | 25.83 | 23.87 |
September | 40.00 | 23.59 | 315.50 | 23.84 | 16.33 | 23.84 |
October | 327.83 | 22.39 | 71.67 | 22.66 | 0.00 | 22.66 |
November | 458.00 | 21.91 | 2.83 | 21.91 | 2.83 | 21.90 |
December | 496.00 | 21.43 | 149.67 | 21.36 | 149.67 | 21.31 |
Annual Sum or Average | 3494.33 | 21.92 | 2297.17 | 22.41 | 723.00 | 22.32 |
Minimum of Months | 25.83 | 21.35 | 2.83 | 21.28 | 0.00 | 21.25 |
Maximum of Months | 496.00 | 23.89 | 469.83 | 23.87 | 218.83 | 23.87 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 262.17 | 21.11 | 262.17 | 21.11 |
February | 336.00 | 21.11 | 222.67 | 21.11 | 222.67 | 21.11 |
March | 351.00 | 21.23 | 85.67 | 21.28 | 75.00 | 21.25 |
April | 344.33 | 21.71 | 10.33 | 21.70 | 10.33 | 21.68 |
May | 177.50 | 22.89 | 61.17 | 23.17 | 0.00 | 23.17 |
June | 64.83 | 23.78 | 250.50 | 23.98 | 42.00 | 23.99 |
July | 84.17 | 24.12 | 361.00 | 24.06 | 84.17 | 24.07 |
August | 42.33 | 24.22 | 362.00 | 24.05 | 41.50 | 24.07 |
September | 57.00 | 23.56 | 256.33 | 23.91 | 27.00 | 23.92 |
October | 269.00 | 21.83 | 38.50 | 22.08 | 1.50 | 22.08 |
November | 354.83 | 21.37 | 11.50 | 21.36 | 11.50 | 21.35 |
December | 369.00 | 21.11 | 190.33 | 21.11 | 190.33 | 21.11 |
Annual Sum or Average | 2821.00 | 21.66 | 2112.17 | 22.21 | 968.17 | 22.13 |
Minimum of Months | 42.33 | 21.11 | 10.33 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 371.00 | 24.22 | 362.00 | 24.06 | 262.17 | 24.07 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 280.33 | 21.11 | 280.33 | 21.11 |
February | 336.00 | 21.11 | 244.50 | 21.11 | 244.50 | 21.11 |
March | 353.33 | 21.23 | 92.83 | 21.24 | 87.50 | 21.22 |
April | 347.50 | 21.67 | 12.67 | 21.65 | 12.67 | 21.63 |
May | 185.17 | 22.79 | 58.00 | 23.07 | 0.00 | 23.07 |
June | 66.17 | 23.77 | 249.17 | 23.98 | 42.00 | 23.99 |
July | 84.17 | 24.12 | 360.67 | 24.06 | 84.17 | 24.07 |
August | 41.33 | 24.23 | 361.50 | 24.05 | 40.50 | 24.07 |
September | 61.50 | 23.52 | 252.50 | 23.90 | 27.00 | 23.91 |
October | 281.50 | 21.83 | 26.67 | 21.99 | 2.50 | 21.98 |
November | 356.00 | 21.33 | 15.83 | 21.32 | 15.83 | 21.32 |
December | 369.00 | 21.11 | 210.00 | 21.11 | 210.00 | 21.11 |
Annual Sum or Average | 2852.67 | 21.65 | 2164.67 | 22.18 | 1047.00 | 22.09 |
Minimum of Months | 41.33 | 21.11 | 12.67 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 371.00 | 24.23 | 361.50 | 24.06 | 280.33 | 24.07 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 299.83 | 21.11 | 299.83 | 21.11 |
February | 336.00 | 21.11 | 263.33 | 21.11 | 263.33 | 21.11 |
March | 357.67 | 21.24 | 108.33 | 21.22 | 105.67 | 21.20 |
April | 352.00 | 21.60 | 16.83 | 21.58 | 16.83 | 21.56 |
May | 202.50 | 22.63 | 48.83 | 22.89 | 0.00 | 22.89 |
June | 74.67 | 23.72 | 243.50 | 23.96 | 45.33 | 23.97 |
July | 85.83 | 24.11 | 356.50 | 24.06 | 85.83 | 24.07 |
August | 46.67 | 24.18 | 357.67 | 24.04 | 45.33 | 24.06 |
September | 69.50 | 23.44 | 239.17 | 23.86 | 28.17 | 23.88 |
October | 292.17 | 21.78 | 16.33 | 21.86 | 3.33 | 21.85 |
November | 357.33 | 21.30 | 22.33 | 21.29 | 22.33 | 21.28 |
December | 369.00 | 21.11 | 228.33 | 21.11 | 228.33 | 21.11 |
Annual Sum or Average | 2914.33 | 21.64 | 2201.00 | 22.13 | 1144.33 | 22.04 |
Minimum of Months | 46.67 | 21.11 | 16.33 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 371.00 | 24.18 | 357.67 | 24.06 | 299.83 | 24.07 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 314.33 | 21.11 | 314.33 | 21.11 |
February | 308.00 | 21.11 | 295.00 | 21.11 | 295.00 | 21.11 |
March | 335.17 | 21.25 | 147.00 | 21.20 | 147.00 | 21.18 |
April | 328.83 | 21.48 | 27.67 | 21.45 | 27.67 | 21.43 |
May | 230.17 | 22.45 | 20.33 | 22.57 | 3.00 | 22.58 |
June | 84.00 | 23.60 | 205.17 | 23.84 | 44.33 | 23.85 |
July | 73.17 | 23.99 | 322.33 | 23.96 | 73.17 | 23.96 |
August | 44.00 | 23.96 | 310.83 | 23.94 | 41.67 | 23.95 |
September | 71.00 | 23.24 | 194.33 | 23.73 | 29.17 | 23.75 |
October | 295.17 | 21.72 | 11.00 | 21.76 | 3.83 | 21.76 |
November | 330.00 | 21.25 | 47.00 | 21.23 | 47.00 | 21.22 |
December | 338.00 | 21.11 | 281.17 | 21.11 | 281.17 | 21.11 |
Annual Sum or Average | 2777.50 | 21.61 | 2176.17 | 22.00 | 1307.33 | 21.90 |
Minimum of Months | 44.00 | 21.11 | 11.00 | 21.11 | 3.00 | 21.11 |
Maximum of Months | 340.00 | 23.99 | 322.33 | 23.96 | 314.33 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 314.33 | 21.11 | 314.33 | 21.11 |
February | 308.00 | 21.11 | 294.67 | 21.11 | 294.67 | 21.11 |
March | 336.67 | 21.25 | 151.50 | 21.21 | 151.50 | 21.19 |
April | 330.00 | 21.47 | 31.33 | 21.44 | 31.33 | 21.41 |
May | 244.00 | 22.47 | 16.17 | 22.54 | 3.50 | 22.55 |
June | 92.33 | 23.61 | 186.50 | 23.83 | 45.67 | 23.85 |
July | 73.50 | 23.99 | 319.00 | 23.96 | 73.50 | 23.96 |
August | 46.33 | 23.94 | 294.67 | 23.94 | 43.67 | 23.94 |
September | 78.33 | 23.28 | 175.67 | 23.72 | 29.83 | 23.74 |
October | 300.00 | 21.73 | 11.00 | 21.77 | 4.67 | 21.76 |
November | 330.00 | 21.24 | 50.67 | 21.22 | 50.67 | 21.21 |
December | 338.00 | 21.11 | 281.50 | 21.11 | 281.50 | 21.11 |
Annual Sum or Average | 2817.17 | 21.63 | 2127.00 | 21.98 | 1324.83 | 21.88 |
Minimum of Months | 46.33 | 21.11 | 11.00 | 21.11 | 3.50 | 21.11 |
Maximum of Months | 340.00 | 23.99 | 319.00 | 23.96 | 314.33 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 315.33 | 21.11 | 315.33 | 21.11 |
February | 308.00 | 21.11 | 298.83 | 21.11 | 298.83 | 21.11 |
March | 337.83 | 21.26 | 157.67 | 21.21 | 157.67 | 21.19 |
April | 330.00 | 21.44 | 34.33 | 21.41 | 34.33 | 21.38 |
May | 253.50 | 22.42 | 13.33 | 22.47 | 4.33 | 22.48 |
June | 96.33 | 23.59 | 181.67 | 23.82 | 47.00 | 23.84 |
July | 74.00 | 23.99 | 318.33 | 23.96 | 74.00 | 23.96 |
August | 48.00 | 23.94 | 293.17 | 23.94 | 45.17 | 23.94 |
September | 81.00 | 23.25 | 171.50 | 23.70 | 30.50 | 23.72 |
October | 303.33 | 21.71 | 11.50 | 21.74 | 5.33 | 21.73 |
November | 330.00 | 21.23 | 58.33 | 21.22 | 58.33 | 21.20 |
December | 338.00 | 21.11 | 284.00 | 21.11 | 284.00 | 21.11 |
Annual Sum or Average | 2840.00 | 21.63 | 2138.00 | 21.96 | 1354.83 | 21.87 |
Minimum of Months | 48.00 | 21.11 | 11.50 | 21.11 | 4.33 | 21.11 |
Maximum of Months | 340.00 | 23.99 | 318.33 | 23.96 | 315.33 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 320.17 | 21.11 | 320.17 | 21.11 |
February | 308.00 | 21.11 | 303.00 | 21.11 | 303.00 | 21.11 |
March | 341.50 | 21.27 | 180.50 | 21.21 | 180.50 | 21.19 |
April | 330.00 | 21.38 | 49.67 | 21.35 | 49.67 | 21.32 |
May | 288.50 | 22.38 | 9.00 | 22.39 | 6.50 | 22.38 |
June | 104.50 | 23.52 | 177.17 | 23.78 | 49.67 | 23.80 |
July | 77.00 | 23.98 | 317.33 | 23.95 | 76.67 | 23.96 |
August | 53.50 | 23.91 | 288.50 | 23.93 | 48.50 | 23.94 |
September | 87.83 | 23.15 | 163.00 | 23.64 | 32.00 | 23.67 |
October | 310.33 | 21.67 | 13.33 | 21.69 | 8.33 | 21.67 |
November | 330.00 | 21.22 | 83.17 | 21.19 | 83.17 | 21.18 |
December | 338.00 | 21.11 | 301.83 | 21.11 | 301.83 | 21.11 |
Annual Sum or Average | 2909.17 | 21.63 | 2206.67 | 21.93 | 1460.00 | 21.84 |
Minimum of Months | 53.50 | 21.11 | 9.00 | 21.11 | 6.50 | 21.11 |
Maximum of Months | 341.50 | 23.98 | 320.17 | 23.95 | 320.17 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 334.33 | 21.11 | 334.33 | 21.11 |
February | 308.00 | 21.11 | 308.00 | 21.11 | 308.00 | 21.11 |
March | 345.33 | 21.26 | 255.00 | 21.20 | 255.00 | 21.17 |
April | 330.00 | 21.29 | 110.67 | 21.25 | 110.67 | 21.22 |
May | 325.17 | 22.21 | 14.67 | 22.17 | 14.67 | 22.13 |
June | 127.17 | 23.35 | 160.17 | 23.68 | 56.00 | 23.71 |
July | 83.67 | 23.97 | 315.33 | 23.95 | 82.33 | 23.96 |
August | 69.83 | 23.83 | 280.17 | 23.92 | 57.50 | 23.92 |
September | 107.33 | 22.94 | 149.17 | 23.51 | 32.67 | 23.55 |
October | 319.67 | 21.59 | 27.17 | 21.58 | 24.00 | 21.55 |
November | 330.00 | 21.19 | 166.00 | 21.16 | 166.00 | 21.15 |
December | 338.00 | 21.11 | 325.33 | 21.11 | 325.33 | 21.11 |
Annual Sum or Average | 3024.17 | 21.63 | 2446.00 | 21.86 | 1766.50 | 21.77 |
Minimum of Months | 69.83 | 21.11 | 14.67 | 21.11 | 14.67 | 21.11 |
Maximum of Months | 345.33 | 23.97 | 334.33 | 23.95 | 334.33 | 23.96 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.05911 | 16.65885 | -0.6362 | 13.79377 |
February | 448.00000 | 21.04955 | 16.61092 | -0.6426 | 13.96255 |
March | 497.00000 | 21.32232 | 25.65897 | -0.4325 | 10.49700 |
April | 479.00000 | 21.62092 | 31.33174 | -0.2772 | 7.80451 |
May | 496.00000 | 23.15264 | 35.92797 | -0.8078 | 20.86188 |
June | 481.00000 | 23.81651 | 46.22948 | -0.4253 | 9.41245 |
July | 495.00000 | 23.88832 | 55.29948 | -0.2886 | 6.88652 |
August | 497.00000 | 23.88228 | 50.26510 | -0.3315 | 7.48925 |
September | 479.00000 | 23.77729 | 46.29085 | -0.4434 | 9.78808 |
October | 496.00000 | 22.23057 | 36.18612 | -0.0525 | 7.19858 |
November | 480.00000 | 21.32978 | 29.29238 | -0.3662 | 8.61459 |
December | 496.00000 | 21.05253 | 20.17894 | -0.5955 | 12.75551 |
Annual Sum or Average | 5840.00000 | 22.35596 | 34.25809 | -0.4407 | 10.74981 |
Minimum of Months | 448.00000 | 21.04955 | 16.61092 | -0.8078 | 6.88652 |
Maximum of Months | 497.00000 | 23.88832 | 55.29948 | -0.0525 | 20.86188 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.37924 | 19.00181 | -0.4899 | 10.46898 |
February | 448.00000 | 21.34977 | 18.64907 | -0.5005 | 10.61134 |
March | 497.00000 | 21.83624 | 26.99945 | -0.2710 | 8.25182 |
April | 479.00000 | 22.39097 | 31.92630 | -0.0816 | 6.56595 |
May | 496.00000 | 23.62534 | 35.03094 | -0.6360 | 14.44122 |
June | 481.00000 | 23.82932 | 44.92675 | -0.4142 | 8.95599 |
July | 495.00000 | 23.84286 | 52.96964 | -0.3134 | 7.23409 |
August | 497.00000 | 23.84802 | 48.68014 | -0.3484 | 7.72083 |
September | 479.00000 | 23.83487 | 45.21708 | -0.4192 | 8.98942 |
October | 496.00000 | 22.88514 | 36.14430 | 0.10048 | 6.86216 |
November | 480.00000 | 21.99939 | 30.43283 | -0.1932 | 6.99638 |
December | 496.00000 | 21.43486 | 22.20521 | -0.4470 | 9.71354 |
Annual Sum or Average | 5840.00000 | 22.69534 | 34.43464 | -0.3338 | 8.89851 |
Minimum of Months | 448.00000 | 21.34977 | 18.64907 | -0.6360 | 6.56595 |
Maximum of Months | 497.00000 | 23.84802 | 52.96964 | 0.10048 | 14.44122 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10994 | 15.91066 | -0.5789 | 12.18772 |
February | 336.00000 | 21.11095 | 15.87830 | -0.5790 | 12.18357 |
March | 379.00000 | 21.42630 | 24.76650 | -0.3687 | 9.40125 |
April | 360.00000 | 21.80676 | 30.20917 | -0.2112 | 7.17421 |
May | 375.00000 | 23.42982 | 34.67421 | -0.6997 | 16.90464 |
June | 366.00000 | 23.95138 | 45.76101 | -0.3768 | 8.57899 |
July | 369.00000 | 24.04616 | 55.30680 | -0.2407 | 6.58090 |
August | 379.00000 | 24.01971 | 50.02353 | -0.2906 | 7.11527 |
September | 360.00000 | 23.88169 | 45.72942 | -0.4044 | 9.00435 |
October | 371.00000 | 22.38779 | 35.20942 | -0.0059 | 7.04149 |
November | 360.00000 | 21.40098 | 28.96437 | -0.3255 | 7.99440 |
December | 369.00000 | 21.11149 | 19.67761 | -0.5416 | 11.33246 |
Annual Sum or Average | 4395.00000 | 22.48526 | 33.63635 | -0.3843 | 9.61978 |
Minimum of Months | 336.00000 | 21.10994 | 15.87830 | -0.6997 | 6.58090 |
Maximum of Months | 379.00000 | 24.04616 | 55.30680 | -0.0059 | 16.90464 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10969 | 15.91124 | -0.5922 | 12.51645 |
February | 336.00000 | 21.11037 | 15.87938 | -0.5912 | 12.48842 |
March | 379.00000 | 21.41126 | 24.80725 | -0.3821 | 9.57721 |
April | 360.00000 | 21.74235 | 30.32456 | -0.2346 | 7.31125 |
May | 375.00000 | 23.35562 | 34.82174 | -0.7318 | 18.08871 |
June | 366.00000 | 23.94755 | 45.77578 | -0.3799 | 8.63923 |
July | 369.00000 | 24.04561 | 55.28399 | -0.2408 | 6.57978 |
August | 379.00000 | 24.01875 | 50.01337 | -0.2910 | 7.11955 |
September | 360.00000 | 23.87240 | 45.76749 | -0.4100 | 9.13321 |
October | 371.00000 | 22.31974 | 35.36554 | -0.0287 | 7.05125 |
November | 360.00000 | 21.36163 | 29.04707 | -0.3448 | 8.19043 |
December | 369.00000 | 21.11062 | 19.68010 | -0.5541 | 11.62394 |
Annual Sum or Average | 4395.00000 | 22.46204 | 33.68375 | -0.3975 | 9.85546 |
Minimum of Months | 336.00000 | 21.10969 | 15.87938 | -0.7318 | 6.57978 |
Maximum of Months | 379.00000 | 24.04561 | 55.28399 | -0.0287 | 18.08871 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10977 | 15.91123 | -0.6091 | 12.95030 |
February | 336.00000 | 21.11001 | 15.87967 | -0.6077 | 12.91158 |
March | 379.00000 | 21.38644 | 24.87300 | -0.4013 | 9.83148 |
April | 360.00000 | 21.65170 | 30.48420 | -0.2659 | 7.50338 |
May | 375.00000 | 23.21926 | 35.09677 | -0.7883 | 20.18831 |
June | 366.00000 | 23.93082 | 45.95265 | -0.3926 | 8.89217 |
July | 369.00000 | 24.04082 | 55.51367 | -0.2476 | 6.63906 |
August | 379.00000 | 24.01281 | 50.17425 | -0.2988 | 7.21191 |
September | 360.00000 | 23.84561 | 45.94944 | -0.4256 | 9.49709 |
October | 371.00000 | 22.21724 | 35.60970 | -0.0605 | 7.03885 |
November | 360.00000 | 21.31764 | 29.14118 | -0.3669 | 8.43671 |
December | 369.00000 | 21.11001 | 19.68215 | -0.5706 | 12.02049 |
Annual Sum or Average | 4395.00000 | 22.42401 | 33.81727 | -0.4187 | 10.25748 |
Minimum of Months | 336.00000 | 21.10977 | 15.87967 | -0.7883 | 6.63906 |
Maximum of Months | 379.00000 | 24.04082 | 55.51367 | -0.0605 | 20.18831 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 17.35774 | -0.6587 | 14.26138 |
February | 308.00000 | 21.11000 | 17.28645 | -0.6568 | 14.20142 |
March | 348.00000 | 21.34209 | 26.49046 | -0.4485 | 10.55508 |
April | 330.00000 | 21.48929 | 32.27072 | -0.3268 | 8.00251 |
May | 344.00000 | 22.92304 | 36.90448 | -0.9089 | 24.71958 |
June | 336.00000 | 23.84210 | 46.76794 | -0.4402 | 9.71641 |
July | 338.00000 | 23.94678 | 55.65150 | -0.2924 | 7.01473 |
August | 348.00000 | 23.92251 | 50.56855 | -0.3420 | 7.69877 |
September | 330.00000 | 23.75449 | 47.02002 | -0.4723 | 10.48070 |
October | 340.00000 | 22.00423 | 37.51836 | -0.1255 | 7.06687 |
November | 330.00000 | 21.24963 | 30.71728 | -0.4170 | 9.12680 |
December | 338.00000 | 21.11000 | 21.06912 | -0.6198 | 13.24530 |
Annual Sum or Average | 4030.00000 | 22.32786 | 35.09728 | -0.4750 | 11.34130 |
Minimum of Months | 308.00000 | 21.11000 | 17.28645 | -0.9089 | 7.01473 |
Maximum of Months | 348.00000 | 23.94678 | 55.65150 | -0.1255 | 24.71958 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10982 | 17.26235 | -0.6550 | 14.15351 |
February | 308.00000 | 21.10993 | 17.18990 | -0.6536 | 14.10757 |
March | 348.00000 | 21.33855 | 26.40698 | -0.4541 | 10.62751 |
April | 330.00000 | 21.46766 | 32.21414 | -0.3414 | 8.15095 |
May | 344.00000 | 22.87504 | 36.91267 | -0.9436 | 26.07429 |
June | 336.00000 | 23.83852 | 46.77796 | -0.4628 | 10.15005 |
July | 338.00000 | 23.94577 | 55.70951 | -0.3164 | 7.31155 |
August | 348.00000 | 23.92209 | 50.57785 | -0.3653 | 8.03235 |
September | 330.00000 | 23.75213 | 47.00931 | -0.4926 | 10.89257 |
October | 340.00000 | 21.98372 | 37.47743 | -0.1416 | 7.10553 |
November | 330.00000 | 21.24243 | 30.63811 | -0.4247 | 9.23279 |
December | 338.00000 | 21.10988 | 20.97225 | -0.6176 | 13.17842 |
Annual Sum or Average | 4030.00000 | 22.31872 | 35.05827 | -0.4884 | 11.58898 |
Minimum of Months | 308.00000 | 21.10982 | 17.18990 | -0.9436 | 7.10553 |
Maximum of Months | 348.00000 | 23.94577 | 55.70951 | -0.1416 | 26.07429 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10995 | 17.26231 | -0.6588 | 14.25821 |
February | 308.00000 | 21.11000 | 17.19010 | -0.6572 | 14.20601 |
March | 348.00000 | 21.33277 | 26.42646 | -0.4610 | 10.74258 |
April | 330.00000 | 21.44114 | 32.25934 | -0.3529 | 8.27881 |
May | 344.00000 | 22.80148 | 37.08085 | -0.9753 | 27.36364 |
June | 336.00000 | 23.82876 | 46.87125 | -0.4710 | 10.35383 |
July | 338.00000 | 23.94507 | 55.79214 | -0.3200 | 7.35930 |
August | 348.00000 | 23.92063 | 50.63667 | -0.3692 | 8.09492 |
September | 330.00000 | 23.73828 | 47.09012 | -0.5011 | 11.13087 |
October | 340.00000 | 21.94496 | 37.57978 | -0.1546 | 7.13326 |
November | 330.00000 | 21.23487 | 30.65598 | -0.4315 | 9.33707 |
December | 338.00000 | 21.11000 | 20.97232 | -0.6216 | 13.28177 |
Annual Sum or Average | 4030.00000 | 22.30378 | 35.11453 | -0.4973 | 11.80126 |
Minimum of Months | 308.00000 | 21.10995 | 17.19010 | -0.9753 | 7.13326 |
Maximum of Months | 348.00000 | 23.94507 | 55.79214 | -0.1546 | 27.36364 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10995 | 17.26256 | -0.6746 | 14.70407 |
February | 308.00000 | 21.11000 | 17.19030 | -0.6721 | 14.62676 |
March | 348.00000 | 21.31552 | 26.48363 | -0.4829 | 11.15309 |
April | 330.00000 | 21.38105 | 32.36248 | -0.3822 | 8.65431 |
May | 344.00000 | 22.62451 | 37.49992 | -1.0477 | 30.39494 |
June | 336.00000 | 23.79650 | 47.13773 | -0.4910 | 10.90954 |
July | 338.00000 | 23.94336 | 55.98319 | -0.3243 | 7.41979 |
August | 348.00000 | 23.91576 | 50.78230 | -0.3747 | 8.19611 |
September | 330.00000 | 23.69699 | 47.31803 | -0.5213 | 11.76175 |
October | 340.00000 | 21.86101 | 37.80025 | -0.1827 | 7.24564 |
November | 330.00000 | 21.21551 | 30.70183 | -0.4503 | 9.64991 |
December | 338.00000 | 21.10982 | 20.97286 | -0.6370 | 13.69527 |
Annual Sum or Average | 4030.00000 | 22.26695 | 35.25560 | -0.5196 | 12.37757 |
Minimum of Months | 308.00000 | 21.10982 | 17.19030 | -1.0477 | 7.24564 |
Maximum of Months | 348.00000 | 23.94336 | 55.98319 | -0.1827 | 30.39494 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 17.06089 | -0.7487 | 16.96503 |
February | 308.00000 | 21.11000 | 17.02319 | -0.7441 | 16.80471 |
March | 348.00000 | 21.28466 | 26.39912 | -0.5615 | 12.94295 |
April | 330.00000 | 21.29115 | 32.30167 | -0.4602 | 9.98559 |
May | 344.00000 | 22.29808 | 38.19361 | -1.1978 | 37.14188 |
June | 336.00000 | 23.70595 | 47.63503 | -0.5417 | 12.51551 |
July | 338.00000 | 23.94216 | 56.38183 | -0.3233 | 7.42489 |
August | 348.00000 | 23.89920 | 51.09093 | -0.3790 | 8.37630 |
September | 330.00000 | 23.58844 | 47.71628 | -0.5694 | 13.48126 |
October | 340.00000 | 21.73031 | 37.96311 | -0.2427 | 7.77671 |
November | 330.00000 | 21.18592 | 30.60311 | -0.5110 | 10.87032 |
December | 338.00000 | 21.11000 | 20.80811 | -0.7069 | 15.71306 |
Annual Sum or Average | 4030.00000 | 22.19766 | 35.39875 | -0.5817 | 14.17892 |
Minimum of Months | 308.00000 | 21.11000 | 17.02319 | -1.1978 | 7.42489 |
Maximum of Months | 348.00000 | 23.94216 | 56.38183 | -0.2427 | 37.14188 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.414220E+09 | 0.112914E+09 | 18.92 | 0.352793E+09 | 61426946.13 | 0.00 | 0.56 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 | 10321.59 | 15-MAR-14:00 | 9575.19 | 15-MAR-14:00 | 1950.27 | 14-MAR-13:10 | 2783.08 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 |
April | 9078712.51 | 2562683.56 | 2.17 | 8080589.72 | 998122.78 | 0.00 | 0.13 | 08-APR-13:00 | 0.00 | 01-APR-00:05 | 2140.57 | 08-APR-13:00 | 1946.35 | 08-APR-13:00 | 194.22 | 08-APR-13:00 | 598.16 | 08-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.137505E+10 | 0.367192E+09 | 92.40 | 0.122822E+10 | 0.146825E+09 | 0.00 | 0.67 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 13242.15 | 14-MAY-15:00 | 10580.98 | 14-MAY-15:00 | 3126.08 | 14-MAY-16:10 | 3413.37 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.109417E+11 | 0.274101E+10 | 343.84 | 0.796279E+10 | 0.297890E+10 | 0.00 | 1.00 | 02-JUN-07:03 | 0.00 | 01-JUN-00:10 | 47651.47 | 18-JUN-07:02 | 31172.61 | 12-JUN-07:03 | 23610.64 | 18-JUN-07:02 | 10204.06 | 27-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.226993E+11 | 0.554534E+10 | 481.94 | 0.152232E+11 | 0.747610E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:05 | 48700.86 | 21-JUL-07:01 | 29324.25 | 20-JUL-07:02 | 26505.66 | 29-JUL-07:03 | 10493.95 | 21-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.178479E+11 | 0.444952E+10 | 448.28 | 0.133464E+11 | 0.450154E+10 | 0.00 | 1.00 | 05-AUG-07:03 | 0.00 | 01-AUG-00:10 | 47637.15 | 14-AUG-07:02 | 32736.75 | 06-AUG-07:02 | 23068.10 | 15-AUG-07:03 | 10199.40 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.720017E+10 | 0.181367E+10 | 277.18 | 0.505303E+10 | 0.214714E+10 | 0.00 | 1.00 | 14-SEP-07:03 | 0.00 | 01-SEP-00:10 | 46478.84 | 16-SEP-07:03 | 26430.48 | 17-SEP-07:02 | 22173.91 | 14-SEP-07:03 | 9969.28 | 17-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.344458E+09 | 92679333.81 | 32.58 | 0.295888E+09 | 48569668.56 | 0.00 | 0.45 | 11-OCT-16:10 | 0.00 | 01-OCT-00:10 | 8024.18 | 11-OCT-16:10 | 6942.44 | 11-OCT-16:10 | 1119.22 | 11-OCT-17:10 | 2079.58 | 11-OCT-16:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.608319E+11 | 0.151249E+11 | 1697.31 | 0.434704E+11 | 0.173615E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.226993E+11 | 0.554534E+10 | 481.94 | 0.152232E+11 | 0.747610E+10 | 0.00 | 1.00 | 0.00 | 48700.86 | 32736.75 | 26505.66 | 10493.95 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.297240E+09 | 77226684.34 | 22.24 | 0.254056E+09 | 43184582.92 | 0.00 | 1.00 | 15-MAR-20:01 | 0.00 | 01-MAR-00:05 | 22565.06 | 15-MAR-20:01 | 18953.74 | 15-MAR-20:09 | 4455.91 | 15-MAR-20:57 | 4804.93 | 15-MAR-20:01 | 0.00 | 01-MAR-00:05 |
April | 24808776.17 | 6717661.09 | 9.42 | 22597293.08 | 2211483.09 | 0.00 | 0.37 | 30-APR-17:20 | 0.00 | 01-APR-00:05 | 3491.47 | 30-APR-17:20 | 2839.66 | 30-APR-17:20 | 651.82 | 30-APR-17:20 | 900.67 | 30-APR-17:20 | 0.00 | 01-APR-00:05 |
May | 0.124765E+10 | 0.310444E+09 | 117.13 | 0.111980E+10 | 0.127853E+09 | 0.00 | 1.00 | 13-MAY-18:02 | 0.00 | 01-MAY-00:10 | 23191.84 | 14-MAY-17:45 | 21805.76 | 23-MAY-22:56 | 9534.95 | 14-MAY-17:20 | 4933.49 | 14-MAY-17:45 | 0.00 | 01-MAY-00:10 |
June | 0.720047E+10 | 0.172196E+10 | 341.54 | 0.534540E+10 | 0.185507E+10 | 0.00 | 1.00 | 01-JUN-20:02 | 0.00 | 01-JUN-00:10 | 25161.68 | 18-JUN-07:02 | 21950.35 | 10-JUN-18:56 | 12787.80 | 27-JUN-20:45 | 5314.68 | 18-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.137676E+11 | 0.323193E+10 | 449.40 | 0.944818E+10 | 0.431945E+10 | 0.00 | 1.00 | 01-JUL-18:02 | 0.00 | 01-JUL-00:05 | 25067.56 | 17-JUL-07:02 | 19939.49 | 06-JUL-20:01 | 12946.34 | 28-JUL-20:03 | 5463.38 | 21-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.109234E+11 | 0.261432E+10 | 422.43 | 0.825141E+10 | 0.267196E+10 | 0.00 | 1.00 | 01-AUG-20:02 | 0.00 | 01-AUG-00:10 | 24975.71 | 15-AUG-07:02 | 21251.26 | 03-AUG-20:02 | 13215.26 | 28-AUG-20:03 | 5277.00 | 15-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.483762E+10 | 0.116246E+10 | 284.05 | 0.345091E+10 | 0.138671E+10 | 0.00 | 1.00 | 02-SEP-18:02 | 0.00 | 01-SEP-00:10 | 24926.93 | 15-SEP-20:03 | 19826.40 | 07-SEP-20:01 | 12901.16 | 15-SEP-20:03 | 5229.89 | 15-SEP-20:03 | 0.00 | 01-SEP-00:10 |
October | 0.333693E+09 | 84418403.49 | 51.85 | 0.283416E+09 | 50276913.74 | 0.00 | 1.00 | 22-OCT-17:02 | 0.00 | 01-OCT-00:10 | 22556.02 | 22-OCT-18:54 | 18589.05 | 22-OCT-17:08 | 5867.67 | 22-OCT-18:54 | 4802.94 | 22-OCT-18:54 | 0.00 | 01-OCT-00:10 |
November | 2805434.49 | 781592.80 | 3.25 | 2588465.32 | 216969.17 | 0.00 | 0.17 | 27-NOV-21:20 | 0.00 | 01-NOV-00:10 | 1482.46 | 27-NOV-21:20 | 1323.81 | 27-NOV-21:20 | 158.64 | 27-NOV-21:20 | 402.30 | 27-NOV-21:20 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.386353E+11 | 0.921025E+10 | 1701.31 | 0.281784E+11 | 0.104569E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.137676E+11 | 0.323193E+10 | 449.40 | 0.944818E+10 | 0.431945E+10 | 0.00 | 1.00 | 0.00 | 25161.68 | 21950.35 | 13215.26 | 5463.38 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.220207E+09 | 58671647.83 | 18.50 | 0.197401E+09 | 22805696.85 | 0.00 | 0.57 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 | 5458.86 | 15-MAR-14:00 | 5328.38 | 15-MAR-14:00 | 940.86 | 14-MAR-13:00 | 1443.12 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 |
April | 8763342.26 | 2404849.60 | 4.00 | 8216814.09 | 546528.18 | 0.00 | 0.19 | 08-APR-13:00 | 0.00 | 01-APR-00:05 | 1596.68 | 08-APR-13:00 | 1536.32 | 08-APR-13:00 | 99.66 | 08-APR-14:00 | 432.20 | 08-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.712931E+09 | 0.185756E+09 | 84.50 | 0.656959E+09 | 55971623.43 | 0.00 | 0.65 | 10-MAY-14:00 | 0.00 | 01-MAY-00:10 | 6606.91 | 10-MAY-14:00 | 5635.45 | 10-MAY-14:00 | 1317.88 | 14-MAY-12:50 | 1686.97 | 10-MAY-14:00 | 0.00 | 01-MAY-00:10 |
June | 0.453246E+10 | 0.111478E+10 | 262.15 | 0.347595E+10 | 0.105651E+10 | 0.00 | 1.00 | 02-JUN-06:03 | 0.00 | 01-JUN-00:10 | 24925.17 | 18-JUN-07:02 | 16923.23 | 12-JUN-06:03 | 11947.01 | 18-JUN-07:02 | 5230.93 | 18-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.908168E+10 | 0.217700E+10 | 351.67 | 0.642305E+10 | 0.265863E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:05 | 25424.25 | 21-JUL-06:01 | 17228.26 | 15-JUL-06:02 | 13489.44 | 29-JUL-06:03 | 5350.77 | 21-JUL-06:03 | 0.00 | 01-JUL-00:05 |
August | 0.733473E+10 | 0.179563E+10 | 337.42 | 0.581554E+10 | 0.151919E+10 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 25174.41 | 14-AUG-06:02 | 18156.83 | 06-AUG-07:02 | 13550.72 | 14-AUG-06:03 | 5212.44 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.302990E+10 | 0.748125E+09 | 230.57 | 0.224608E+10 | 0.783825E+09 | 0.00 | 1.00 | 09-SEP-06:03 | 0.00 | 01-SEP-00:10 | 24348.01 | 16-SEP-06:03 | 14368.27 | 17-SEP-07:02 | 11619.12 | 14-SEP-06:02 | 5114.42 | 17-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.144616E+09 | 38321664.54 | 30.50 | 0.133476E+09 | 11140127.38 | 0.00 | 0.43 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3930.87 | 11-OCT-15:00 | 3774.03 | 11-OCT-13:00 | 416.10 | 13-OCT-06:10 | 1015.54 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.250653E+11 | 0.612069E+10 | 1319.31 | 0.189567E+11 | 0.610862E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.908168E+10 | 0.217700E+10 | 351.67 | 0.642305E+10 | 0.265863E+10 | 0.00 | 1.00 | 0.00 | 25424.25 | 18156.83 | 13550.72 | 5350.77 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.206283E+09 | 55220060.44 | 18.17 | 0.185107E+09 | 21175445.69 | 0.00 | 0.55 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 | 5250.87 | 15-MAR-14:00 | 5124.03 | 15-MAR-14:00 | 889.97 | 14-MAR-13:00 | 1394.45 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 |
April | 7135148.42 | 1965869.01 | 2.50 | 6695886.47 | 439261.95 | 0.00 | 0.17 | 08-APR-13:00 | 0.00 | 01-APR-00:05 | 1413.42 | 08-APR-13:00 | 1359.60 | 08-APR-13:00 | 84.86 | 08-APR-14:00 | 384.56 | 08-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.676006E+09 | 0.176637E+09 | 82.08 | 0.623441E+09 | 52564739.90 | 0.00 | 0.63 | 10-MAY-14:00 | 0.00 | 01-MAY-00:10 | 6367.09 | 14-MAY-14:50 | 5412.14 | 10-MAY-14:00 | 1257.95 | 14-MAY-14:00 | 1631.97 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.450726E+10 | 0.110802E+10 | 260.65 | 0.345395E+10 | 0.105331E+10 | 0.00 | 1.00 | 02-JUN-06:03 | 0.00 | 01-JUN-00:10 | 24769.90 | 18-JUN-07:02 | 16811.29 | 12-JUN-06:03 | 11879.11 | 18-JUN-07:02 | 5198.41 | 18-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.909136E+10 | 0.217713E+10 | 351.82 | 0.642843E+10 | 0.266293E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:05 | 25272.47 | 21-JUL-06:01 | 17124.15 | 15-JUL-06:02 | 13405.77 | 29-JUL-06:03 | 5317.52 | 21-JUL-06:03 | 0.00 | 01-JUL-00:05 |
August | 0.734118E+10 | 0.179545E+10 | 337.89 | 0.581955E+10 | 0.152163E+10 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 25019.60 | 14-AUG-06:02 | 18049.19 | 06-AUG-07:02 | 13458.24 | 14-AUG-06:03 | 5180.10 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.299738E+10 | 0.739924E+09 | 229.91 | 0.222048E+10 | 0.776893E+09 | 0.00 | 1.00 | 09-SEP-06:03 | 0.00 | 01-SEP-00:10 | 24196.60 | 16-SEP-06:03 | 14278.70 | 17-SEP-07:02 | 11553.93 | 14-SEP-06:02 | 5082.66 | 17-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.124045E+09 | 32987330.72 | 26.75 | 0.114868E+09 | 9176968.90 | 0.00 | 0.40 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3659.36 | 11-OCT-15:00 | 3490.77 | 11-OCT-13:00 | 339.66 | 13-OCT-06:10 | 951.80 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.249507E+11 | 0.608734E+10 | 1309.76 | 0.188525E+11 | 0.609812E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.909136E+10 | 0.217713E+10 | 351.82 | 0.642843E+10 | 0.266293E+10 | 0.00 | 1.00 | 0.00 | 25272.47 | 18049.19 | 13458.24 | 5317.52 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.186632E+09 | 50360014.44 | 17.42 | 0.167798E+09 | 18833950.11 | 0.00 | 0.52 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 | 4943.06 | 15-MAR-14:00 | 4825.11 | 15-MAR-14:00 | 820.18 | 14-MAR-13:00 | 1323.63 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 |
April | 4248092.96 | 1180234.29 | 2.00 | 4000073.28 | 248019.69 | 0.00 | 0.13 | 08-APR-13:00 | 0.00 | 01-APR-00:05 | 1051.69 | 08-APR-13:00 | 1012.20 | 08-APR-13:00 | 54.10 | 08-APR-14:00 | 289.25 | 08-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.599018E+09 | 0.157655E+09 | 74.33 | 0.552670E+09 | 46347264.10 | 0.00 | 0.60 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5974.69 | 14-MAY-15:00 | 5006.12 | 10-MAY-14:00 | 1188.45 | 14-MAY-14:00 | 1546.85 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.430954E+10 | 0.106331E+10 | 252.77 | 0.329975E+10 | 0.100978E+10 | 0.00 | 1.00 | 02-JUN-06:03 | 0.00 | 01-JUN-00:10 | 24804.64 | 18-JUN-07:02 | 15669.80 | 12-JUN-06:03 | 11942.39 | 18-JUN-07:02 | 5206.68 | 18-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.882016E+10 | 0.212033E+10 | 350.36 | 0.623484E+10 | 0.258531E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:05 | 25297.00 | 21-JUL-06:01 | 17115.06 | 15-JUL-06:02 | 13473.64 | 29-JUL-06:03 | 5326.25 | 21-JUL-06:03 | 0.00 | 01-JUL-00:05 |
August | 0.711029E+10 | 0.174600E+10 | 335.81 | 0.564096E+10 | 0.146933E+10 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 25055.82 | 14-AUG-06:02 | 18052.48 | 06-AUG-07:02 | 13511.71 | 14-AUG-06:03 | 5188.44 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.282418E+10 | 0.699712E+09 | 220.90 | 0.208935E+10 | 0.734829E+09 | 0.00 | 1.00 | 09-SEP-06:03 | 0.00 | 01-SEP-00:10 | 24233.84 | 16-SEP-06:03 | 14268.84 | 17-SEP-07:02 | 11615.84 | 14-SEP-06:02 | 5090.52 | 17-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 97730093.82 | 26128699.50 | 19.75 | 91077043.23 | 6653050.58 | 0.00 | 0.36 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3281.41 | 11-OCT-15:00 | 3102.76 | 11-OCT-13:00 | 294.35 | 11-OCT-17:10 | 862.55 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.239518E+11 | 0.586467E+10 | 1273.35 | 0.180805E+11 | 0.587134E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.882016E+10 | 0.212033E+10 | 350.36 | 0.623484E+10 | 0.258531E+10 | 0.00 | 1.00 | 0.00 | 25297.00 | 18052.48 | 13511.71 | 5326.25 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.300908E+09 | 83172475.13 | 15.42 | 0.252811E+09 | 48097432.66 | 0.00 | 0.51 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 8923.35 | 15-MAR-14:10 | 8127.55 | 15-MAR-14:10 | 1839.01 | 14-MAR-13:00 | 2432.68 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 5024661.94 | 1430753.64 | 1.83 | 4404656.42 | 620005.52 | 0.00 | 0.07 | 08-APR-13:30 | 0.00 | 01-APR-00:05 | 1078.51 | 08-APR-13:30 | 948.88 | 08-APR-13:30 | 132.39 | 08-APR-13:40 | 306.30 | 08-APR-13:30 | 0.00 | 01-APR-00:05 |
May | 0.953625E+09 | 0.257563E+09 | 64.67 | 0.848593E+09 | 0.105032E+09 | 0.00 | 0.61 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 11330.95 | 14-MAY-15:00 | 8828.83 | 14-MAY-15:00 | 2695.00 | 14-MAY-14:10 | 2967.20 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.767489E+10 | 0.193056E+10 | 242.54 | 0.557759E+10 | 0.209729E+10 | 0.00 | 1.00 | 02-JUN-07:03 | 0.00 | 01-JUN-00:10 | 45562.96 | 18-JUN-08:62 | 30193.06 | 12-JUN-07:03 | 21381.89 | 27-JUN-07:03 | 9820.70 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.159133E+11 | 0.389853E+10 | 342.75 | 0.107364E+11 | 0.517691E+10 | 0.00 | 1.00 | 02-JUL-08:63 | 0.00 | 01-JUL-00:05 | 46084.00 | 16-JUL-08:62 | 28520.61 | 20-JUL-07:02 | 25336.66 | 29-JUL-07:03 | 9997.61 | 21-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.128856E+11 | 0.322663E+10 | 328.59 | 0.976141E+10 | 0.312419E+10 | 0.00 | 1.00 | 05-AUG-07:03 | 0.00 | 01-AUG-00:10 | 46156.35 | 14-AUG-07:02 | 32427.65 | 06-AUG-08:62 | 21949.63 | 15-AUG-07:03 | 9744.12 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.498073E+10 | 0.125923E+10 | 210.06 | 0.351550E+10 | 0.146523E+10 | 0.00 | 1.00 | 14-SEP-07:03 | 0.00 | 01-SEP-00:10 | 44232.21 | 16-SEP-07:03 | 24310.56 | 17-SEP-08:62 | 21394.41 | 14-SEP-07:03 | 9482.64 | 16-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 0.143414E+09 | 39262583.63 | 13.50 | 0.125634E+09 | 17780230.57 | 0.00 | 0.36 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 6009.90 | 11-OCT-15:00 | 5261.57 | 11-OCT-15:00 | 748.33 | 11-OCT-15:00 | 1608.32 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.428575E+11 | 0.106964E+11 | 1219.35 | 0.308223E+11 | 0.120352E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.159133E+11 | 0.389853E+10 | 342.75 | 0.107364E+11 | 0.517691E+10 | 0.00 | 1.00 | 0.00 | 46156.35 | 32427.65 | 25336.66 | 9997.61 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.149854E+09 | 40816865.69 | 15.17 | 0.126281E+09 | 23572879.13 | 0.00 | 0.50 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 4556.42 | 15-MAR-14:10 | 4154.87 | 15-MAR-14:10 | 896.88 | 14-MAR-13:00 | 1223.87 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 1255470.38 | 353494.86 | 1.33 | 1104339.02 | 151131.35 | 0.00 | 0.04 | 08-APR-13:30 | 0.00 | 01-APR-00:05 | 319.22 | 08-APR-13:30 | 281.32 | 08-APR-13:30 | 37.90 | 08-APR-13:30 | 89.76 | 08-APR-13:30 | 0.00 | 01-APR-00:05 |
May | 0.460163E+09 | 0.122558E+09 | 61.67 | 0.409840E+09 | 50323109.76 | 0.00 | 0.60 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5764.96 | 14-MAY-15:00 | 4491.43 | 14-MAY-15:00 | 1362.29 | 14-MAY-14:20 | 1488.96 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.389553E+10 | 0.965069E+09 | 235.96 | 0.283608E+10 | 0.105944E+10 | 0.00 | 1.00 | 12-JUN-07:03 | 0.00 | 01-JUN-00:10 | 23782.47 | 18-JUN-08:62 | 14483.22 | 12-JUN-07:03 | 11146.77 | 27-JUN-07:03 | 5036.67 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.814365E+10 | 0.196560E+10 | 342.07 | 0.550703E+10 | 0.263662E+10 | 0.00 | 1.00 | 02-JUL-08:63 | 0.00 | 01-JUL-00:05 | 24057.44 | 16-JUL-08:62 | 14884.07 | 20-JUL-07:02 | 13222.24 | 29-JUL-07:03 | 5127.39 | 21-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.659328E+10 | 0.162616E+10 | 327.11 | 0.500582E+10 | 0.158746E+10 | 0.00 | 1.00 | 05-AUG-07:03 | 0.00 | 01-AUG-00:10 | 24099.57 | 14-AUG-07:02 | 16955.01 | 06-AUG-08:62 | 11452.45 | 14-AUG-07:03 | 4997.57 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.252069E+10 | 0.627089E+09 | 205.50 | 0.177996E+10 | 0.740732E+09 | 0.00 | 1.00 | 14-SEP-07:03 | 0.00 | 01-SEP-00:10 | 23086.34 | 17-SEP-08:62 | 12707.92 | 17-SEP-08:62 | 10378.42 | 17-SEP-08:62 | 4854.42 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 68378068.79 | 18433723.07 | 11.83 | 60083772.36 | 8294296.43 | 0.00 | 0.35 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3018.97 | 11-OCT-15:00 | 2647.60 | 11-OCT-15:00 | 371.37 | 11-OCT-15:00 | 796.47 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.218328E+11 | 0.536608E+10 | 1200.64 | 0.157262E+11 | 0.610659E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.814365E+10 | 0.196560E+10 | 342.07 | 0.550703E+10 | 0.263662E+10 | 0.00 | 1.00 | 0.00 | 24099.57 | 16955.01 | 13222.24 | 5127.39 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.144524E+09 | 39447650.42 | 15.00 | 0.121741E+09 | 22782818.67 | 0.00 | 0.49 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 4452.47 | 15-MAR-14:10 | 4057.16 | 15-MAR-14:10 | 870.86 | 14-MAR-13:00 | 1198.73 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 674958.23 | 190691.81 | 1.17 | 594832.76 | 80125.47 | 0.00 | 0.03 | 08-APR-13:20 | 0.00 | 01-APR-00:05 | 199.08 | 08-APR-13:20 | 176.65 | 08-APR-13:20 | 23.06 | 08-APR-13:30 | 56.19 | 08-APR-13:20 | 0.00 | 01-APR-00:05 |
May | 0.426781E+09 | 0.114051E+09 | 59.33 | 0.379530E+09 | 47251157.09 | 0.00 | 0.59 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5617.23 | 14-MAY-15:00 | 4367.86 | 14-MAY-15:00 | 1331.39 | 14-MAY-14:20 | 1455.29 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.381408E+10 | 0.945876E+09 | 232.87 | 0.277282E+10 | 0.104126E+10 | 0.00 | 1.00 | 12-JUN-07:03 | 0.00 | 01-JUN-00:10 | 23673.04 | 18-JUN-08:62 | 13506.87 | 12-JUN-07:03 | 11118.71 | 27-JUN-07:03 | 5014.83 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.804216E+10 | 0.194258E+10 | 341.79 | 0.543388E+10 | 0.260828E+10 | 0.00 | 1.00 | 02-JUL-08:63 | 0.00 | 01-JUL-00:05 | 23950.08 | 16-JUL-08:62 | 14763.58 | 20-JUL-07:02 | 13182.44 | 29-JUL-07:03 | 5105.38 | 21-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.650981E+10 | 0.160685E+10 | 325.49 | 0.494082E+10 | 0.156899E+10 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 23990.97 | 14-AUG-07:02 | 16862.18 | 06-AUG-08:62 | 11444.78 | 14-AUG-07:03 | 4976.04 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.246340E+10 | 0.613293E+09 | 204.59 | 0.173728E+10 | 0.726117E+09 | 0.00 | 1.00 | 14-SEP-07:03 | 0.00 | 01-SEP-00:10 | 22985.93 | 17-SEP-08:62 | 12637.94 | 17-SEP-08:62 | 10347.99 | 17-SEP-08:62 | 4833.46 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 63612207.63 | 17192575.31 | 10.83 | 55876542.35 | 7735665.28 | 0.00 | 0.34 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2892.48 | 11-OCT-15:00 | 2535.12 | 11-OCT-15:00 | 357.36 | 11-OCT-15:00 | 765.63 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.214650E+11 | 0.527948E+10 | 1191.07 | 0.154425E+11 | 0.602250E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.804216E+10 | 0.194258E+10 | 341.79 | 0.543388E+10 | 0.260828E+10 | 0.00 | 1.00 | 0.00 | 23990.97 | 16862.18 | 13182.44 | 5105.38 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.128882E+09 | 35399619.22 | 14.33 | 0.108672E+09 | 20209909.51 | 0.00 | 0.47 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 4178.15 | 15-MAR-14:10 | 3801.93 | 15-MAR-14:10 | 790.02 | 14-MAR-13:00 | 1132.69 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.355824E+09 | 95838660.57 | 52.25 | 0.315218E+09 | 40606304.20 | 0.00 | 0.56 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5260.96 | 14-MAY-15:00 | 4073.43 | 14-MAY-15:00 | 1254.98 | 14-MAY-14:20 | 1374.31 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.361602E+10 | 0.899237E+09 | 222.50 | 0.262157E+10 | 0.994454E+09 | 0.00 | 1.00 | 12-JUN-07:03 | 0.00 | 01-JUN-00:10 | 23511.59 | 18-JUN-08:62 | 12734.05 | 18-JUN-08:62 | 10777.54 | 18-JUN-08:62 | 4985.31 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.783200E+10 | 0.189515E+10 | 338.32 | 0.528762E+10 | 0.254437E+10 | 0.00 | 1.00 | 05-JUL-07:03 | 0.00 | 01-JUL-00:05 | 23796.08 | 16-JUL-08:62 | 14530.23 | 20-JUL-07:02 | 12276.43 | 22-JUL-07:02 | 5076.12 | 21-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.634000E+10 | 0.156753E+10 | 320.91 | 0.481375E+10 | 0.152624E+10 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 23834.91 | 14-AUG-07:02 | 16728.32 | 06-AUG-08:62 | 11498.27 | 14-AUG-07:03 | 4947.21 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.232692E+10 | 0.580319E+09 | 192.20 | 0.163672E+10 | 0.690200E+09 | 0.00 | 1.00 | 14-SEP-07:03 | 0.00 | 01-SEP-00:10 | 22850.27 | 17-SEP-08:62 | 12532.88 | 17-SEP-08:62 | 10317.39 | 17-SEP-08:62 | 4805.39 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 54895282.50 | 14916362.01 | 10.50 | 48212675.16 | 6682607.34 | 0.00 | 0.31 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2655.50 | 11-OCT-15:00 | 2325.89 | 11-OCT-15:00 | 329.61 | 11-OCT-15:00 | 707.47 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.206545E+11 | 0.508839E+10 | 1151.02 | 0.148318E+11 | 0.582277E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.783200E+10 | 0.189515E+10 | 338.32 | 0.528762E+10 | 0.254437E+10 | 0.00 | 1.00 | 0.00 | 23834.91 | 16728.32 | 12276.43 | 5076.12 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.106821E+09 | 29705148.84 | 12.83 | 90710097.98 | 16111096.78 | 0.00 | 0.42 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 3830.38 | 15-MAR-14:10 | 3499.73 | 15-MAR-14:10 | 668.24 | 14-MAR-13:00 | 1053.02 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.259586E+09 | 71009598.94 | 43.67 | 0.228900E+09 | 30685968.83 | 0.00 | 0.49 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4712.30 | 14-MAY-15:00 | 3639.15 | 14-MAY-15:00 | 1117.79 | 14-MAY-14:30 | 1254.64 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.340361E+10 | 0.851595E+09 | 206.12 | 0.247576E+10 | 0.927852E+09 | 0.00 | 1.00 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 | 17325.49 | 18-JUN-08:62 | 8831.58 | 27-JUN-13:00 | 8547.60 | 18-JUN-08:62 | 3672.44 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.777971E+10 | 0.189142E+10 | 333.31 | 0.530027E+10 | 0.247945E+10 | 0.00 | 1.00 | 15-JUL-07:02 | 0.00 | 01-JUL-00:05 | 25158.83 | 21-JUL-07:01 | 13333.23 | 20-JUL-07:02 | 13507.80 | 21-JUL-07:03 | 5277.74 | 21-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.633500E+10 | 0.157030E+10 | 305.79 | 0.486316E+10 | 0.147184E+10 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 24902.94 | 14-AUG-07:02 | 13450.29 | 06-AUG-08:62 | 12747.81 | 14-AUG-07:02 | 5147.56 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.216865E+10 | 0.542419E+09 | 170.11 | 0.153237E+10 | 0.636280E+09 | 0.00 | 1.00 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 | 23799.75 | 17-SEP-08:62 | 12847.05 | 17-SEP-08:62 | 10952.69 | 17-SEP-08:62 | 5001.51 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 49499372.18 | 13516407.59 | 10.00 | 43889664.62 | 5609707.56 | 0.00 | 0.29 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2506.57 | 11-OCT-15:00 | 2210.70 | 11-OCT-15:00 | 295.88 | 11-OCT-15:00 | 672.67 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.201029E+11 | 0.496997E+10 | 1081.83 | 0.145351E+11 | 0.556783E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.777971E+10 | 0.189142E+10 | 333.31 | 0.530027E+10 | 0.247945E+10 | 0.00 | 1.00 | 0.00 | 25158.83 | 13450.29 | 13507.80 | 5277.74 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 67.51 | 104.86 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 76.12 | 101.42 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 116.22 | 73.44 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 101.33 | 56.70 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 95.10 | 39.80 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 101.91 | 26.38 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.49 | 17.81 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.94 | 23.77 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.78 | 38.54 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 113.73 | 56.45 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 71.58 | 71.24 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 53.27 | 103.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 98.04 | 59.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 53.27 | 17.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.78 | 104.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 67.51 | 104.86 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 76.12 | 101.42 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 116.22 | 73.44 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 101.33 | 56.70 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 95.10 | 39.80 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 101.91 | 26.38 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.49 | 17.81 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.94 | 23.77 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.78 | 38.54 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 113.73 | 56.45 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 71.58 | 71.24 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 53.27 | 103.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 98.04 | 59.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 53.27 | 17.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.78 | 104.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 67.51 | 104.86 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 76.12 | 101.42 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 116.22 | 73.44 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 101.33 | 56.70 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 95.10 | 39.80 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 101.91 | 26.38 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.49 | 17.81 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.94 | 23.77 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.78 | 38.54 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 113.73 | 56.45 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 71.58 | 71.24 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 53.27 | 103.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 98.04 | 59.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 53.27 | 17.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.78 | 104.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 67.51 | 104.86 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 76.12 | 101.42 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 116.22 | 73.44 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 101.33 | 56.70 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 95.10 | 39.80 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 101.91 | 26.38 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.49 | 17.81 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.94 | 23.77 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.78 | 38.54 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 113.73 | 56.45 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 71.58 | 71.24 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 53.27 | 103.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 98.04 | 59.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 53.27 | 17.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.78 | 104.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.80 | 58.25 | 41.54 | 81.78 | 124.00 | 0.00 | 0.00 | 0.00 |
February | 113.94 | 54.94 | 59.00 | 92.46 | 119.79 | 0.00 | 0.00 | 0.00 |
March | 139.08 | 78.15 | 60.93 | 140.46 | 87.04 | 0.00 | 0.00 | 0.00 |
April | 115.18 | 46.02 | 69.15 | 122.34 | 67.21 | 0.00 | 0.00 | 0.00 |
May | 100.79 | 29.27 | 71.52 | 114.68 | 47.29 | 0.00 | 0.00 | 0.00 |
June | 97.94 | 20.75 | 77.18 | 122.70 | 31.44 | 0.00 | 0.00 | 0.00 |
July | 99.98 | 24.26 | 75.72 | 138.83 | 21.27 | 0.00 | 0.00 | 0.00 |
August | 112.24 | 36.39 | 75.85 | 152.62 | 28.36 | 0.00 | 0.00 | 0.00 |
September | 130.50 | 63.56 | 66.94 | 163.40 | 45.91 | 0.00 | 0.00 | 0.00 |
October | 124.87 | 71.33 | 53.54 | 137.17 | 67.05 | 0.00 | 0.00 | 0.00 |
November | 89.43 | 50.49 | 38.94 | 86.48 | 84.39 | 0.00 | 0.00 | 0.00 |
December | 83.45 | 43.19 | 40.26 | 64.63 | 121.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.90 | 48.03 | 60.87 | 118.28 | 70.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 83.45 | 20.75 | 38.94 | 64.63 | 21.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.08 | 78.15 | 77.18 | 163.40 | 124.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.80 | 58.25 | 41.54 | 81.78 | 124.00 | 0.00 | 0.00 | 0.00 |
February | 113.94 | 54.94 | 59.00 | 92.46 | 119.79 | 0.00 | 0.00 | 0.00 |
March | 139.08 | 78.15 | 60.93 | 140.46 | 87.04 | 0.00 | 0.00 | 0.00 |
April | 115.18 | 46.02 | 69.15 | 122.34 | 67.21 | 0.00 | 0.00 | 0.00 |
May | 100.79 | 29.27 | 71.52 | 114.68 | 47.29 | 0.00 | 0.00 | 0.00 |
June | 97.94 | 20.75 | 77.18 | 122.70 | 31.44 | 0.00 | 0.00 | 0.00 |
July | 99.98 | 24.26 | 75.72 | 138.83 | 21.27 | 0.00 | 0.00 | 0.00 |
August | 112.24 | 36.39 | 75.85 | 152.62 | 28.36 | 0.00 | 0.00 | 0.00 |
September | 130.50 | 63.56 | 66.94 | 163.40 | 45.91 | 0.00 | 0.00 | 0.00 |
October | 124.87 | 71.33 | 53.54 | 137.17 | 67.05 | 0.00 | 0.00 | 0.00 |
November | 89.43 | 50.49 | 38.94 | 86.48 | 84.39 | 0.00 | 0.00 | 0.00 |
December | 83.45 | 43.19 | 40.26 | 64.63 | 121.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.90 | 48.03 | 60.87 | 118.28 | 70.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 83.45 | 20.75 | 38.94 | 64.63 | 21.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.08 | 78.15 | 77.18 | 163.40 | 124.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 66.33 | 110.33 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 74.53 | 106.86 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 114.46 | 78.19 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 99.36 | 61.58 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 93.21 | 42.72 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 101.20 | 27.19 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.18 | 18.18 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.64 | 24.20 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.16 | 39.53 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 112.27 | 60.13 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 70.43 | 76.11 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 52.28 | 108.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 96.89 | 62.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 52.28 | 18.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.16 | 110.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 66.33 | 110.33 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 74.53 | 106.86 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 114.46 | 78.19 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 99.36 | 61.58 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 93.21 | 42.72 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 101.20 | 27.19 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.18 | 18.18 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.64 | 24.20 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.16 | 39.53 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 112.27 | 60.13 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 70.43 | 76.11 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 52.28 | 108.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 96.89 | 62.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 52.28 | 18.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.16 | 110.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.80 | 58.25 | 41.54 | 80.38 | 130.40 | 0.00 | 0.00 | 0.00 |
February | 113.94 | 54.94 | 59.00 | 90.58 | 126.13 | 0.00 | 0.00 | 0.00 |
March | 139.08 | 78.15 | 60.93 | 138.39 | 92.60 | 0.00 | 0.00 | 0.00 |
April | 115.18 | 46.02 | 69.15 | 120.02 | 72.92 | 0.00 | 0.00 | 0.00 |
May | 100.79 | 29.27 | 71.52 | 112.45 | 50.72 | 0.00 | 0.00 | 0.00 |
June | 97.94 | 20.75 | 77.18 | 121.88 | 32.39 | 0.00 | 0.00 | 0.00 |
July | 99.98 | 24.26 | 75.72 | 138.48 | 21.70 | 0.00 | 0.00 | 0.00 |
August | 112.24 | 36.39 | 75.85 | 152.30 | 28.86 | 0.00 | 0.00 | 0.00 |
September | 130.50 | 63.56 | 66.94 | 162.70 | 47.07 | 0.00 | 0.00 | 0.00 |
October | 124.87 | 71.33 | 53.54 | 135.46 | 71.34 | 0.00 | 0.00 | 0.00 |
November | 89.43 | 50.49 | 38.94 | 85.14 | 90.07 | 0.00 | 0.00 | 0.00 |
December | 83.45 | 43.19 | 40.26 | 63.45 | 128.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.90 | 48.03 | 60.87 | 116.92 | 74.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 83.45 | 20.75 | 38.94 | 63.45 | 21.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.08 | 78.15 | 77.18 | 162.70 | 130.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 66.53 | 107.43 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 74.76 | 104.03 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 114.71 | 76.02 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 99.79 | 59.57 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 93.48 | 42.47 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 100.99 | 28.44 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 114.69 | 19.89 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.36 | 25.86 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.13 | 40.57 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 112.71 | 58.67 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 70.80 | 73.59 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 52.47 | 105.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 97.00 | 61.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 52.47 | 19.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.13 | 107.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 66.53 | 107.43 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 74.76 | 104.03 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 114.71 | 76.02 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 99.79 | 59.57 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 93.48 | 42.47 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 100.99 | 28.44 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 114.69 | 19.89 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.36 | 25.86 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.13 | 40.57 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 112.71 | 58.67 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 70.80 | 73.59 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 52.47 | 105.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 97.00 | 61.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 52.47 | 19.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.13 | 107.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.25 | 57.94 | 41.32 | 80.19 | 126.28 | 0.00 | 0.00 | 0.00 |
February | 113.32 | 54.64 | 58.68 | 90.36 | 122.14 | 0.00 | 0.00 | 0.00 |
March | 138.32 | 77.72 | 60.60 | 137.94 | 89.55 | 0.00 | 0.00 | 0.00 |
April | 114.55 | 45.77 | 68.77 | 119.88 | 70.17 | 0.00 | 0.00 | 0.00 |
May | 100.24 | 29.11 | 71.13 | 112.16 | 50.15 | 0.00 | 0.00 | 0.00 |
June | 97.40 | 20.64 | 76.76 | 120.96 | 33.66 | 0.00 | 0.00 | 0.00 |
July | 99.43 | 24.12 | 75.30 | 137.16 | 23.58 | 0.00 | 0.00 | 0.00 |
August | 111.63 | 36.19 | 75.43 | 151.13 | 30.64 | 0.00 | 0.00 | 0.00 |
September | 129.79 | 63.22 | 66.57 | 161.77 | 48.02 | 0.00 | 0.00 | 0.00 |
October | 124.19 | 70.94 | 53.25 | 135.25 | 69.24 | 0.00 | 0.00 | 0.00 |
November | 88.94 | 50.21 | 38.73 | 85.11 | 86.63 | 0.00 | 0.00 | 0.00 |
December | 82.99 | 42.95 | 40.04 | 63.34 | 124.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.30 | 47.76 | 60.54 | 116.42 | 72.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.99 | 20.64 | 38.73 | 63.34 | 23.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.32 | 77.72 | 76.76 | 161.77 | 126.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 66.68 | 106.21 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 74.93 | 102.91 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 114.93 | 75.09 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 100.12 | 58.55 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 93.80 | 41.76 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 101.03 | 28.35 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 114.68 | 19.94 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.35 | 25.89 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.19 | 40.39 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 113.01 | 57.77 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 71.02 | 72.49 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 52.59 | 104.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 97.16 | 60.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 52.59 | 19.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.19 | 106.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 66.68 | 106.21 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 74.93 | 102.91 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 114.93 | 75.09 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 100.12 | 58.55 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 93.80 | 41.76 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 101.03 | 28.35 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 114.68 | 19.94 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.35 | 25.89 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.19 | 40.39 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 113.01 | 57.77 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 71.02 | 72.49 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 52.59 | 104.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 97.16 | 60.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 52.59 | 19.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.19 | 106.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.25 | 57.94 | 41.32 | 80.37 | 124.84 | 0.00 | 0.00 | 0.00 |
February | 113.32 | 54.64 | 58.68 | 90.58 | 120.82 | 0.00 | 0.00 | 0.00 |
March | 138.32 | 77.72 | 60.60 | 138.20 | 88.46 | 0.00 | 0.00 | 0.00 |
April | 114.55 | 45.77 | 68.77 | 120.27 | 68.98 | 0.00 | 0.00 | 0.00 |
May | 100.24 | 29.11 | 71.13 | 112.54 | 49.30 | 0.00 | 0.00 | 0.00 |
June | 97.40 | 20.64 | 76.76 | 121.01 | 33.55 | 0.00 | 0.00 | 0.00 |
July | 99.43 | 24.12 | 75.30 | 137.15 | 23.64 | 0.00 | 0.00 | 0.00 |
August | 111.63 | 36.19 | 75.43 | 151.13 | 30.67 | 0.00 | 0.00 | 0.00 |
September | 129.79 | 63.22 | 66.57 | 161.83 | 47.81 | 0.00 | 0.00 | 0.00 |
October | 124.19 | 70.94 | 53.25 | 135.60 | 68.18 | 0.00 | 0.00 | 0.00 |
November | 88.94 | 50.21 | 38.73 | 85.37 | 85.33 | 0.00 | 0.00 | 0.00 |
December | 82.99 | 42.95 | 40.04 | 63.49 | 122.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.30 | 47.76 | 60.54 | 116.61 | 71.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.99 | 20.64 | 38.73 | 63.49 | 23.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.32 | 77.72 | 76.76 | 161.83 | 124.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 66.87 | 105.17 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 75.17 | 101.94 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 115.22 | 74.26 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 100.54 | 57.58 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 94.37 | 40.77 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 101.23 | 27.97 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 114.83 | 19.63 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.48 | 25.57 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.35 | 39.94 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 113.40 | 56.84 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 71.26 | 71.57 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 52.76 | 103.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 97.42 | 60.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 52.76 | 19.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.35 | 105.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 66.87 | 105.17 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 75.17 | 101.94 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 115.22 | 74.26 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 100.54 | 57.58 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 94.37 | 40.77 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 101.23 | 27.97 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 114.83 | 19.63 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.48 | 25.57 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.35 | 39.94 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 113.40 | 56.84 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 71.26 | 71.57 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 52.76 | 103.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 97.42 | 60.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 52.76 | 19.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.35 | 105.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.25 | 57.94 | 41.32 | 80.60 | 123.61 | 0.00 | 0.00 | 0.00 |
February | 113.32 | 54.64 | 58.68 | 90.87 | 119.68 | 0.00 | 0.00 | 0.00 |
March | 138.32 | 77.72 | 60.60 | 138.56 | 87.47 | 0.00 | 0.00 | 0.00 |
April | 114.55 | 45.77 | 68.77 | 120.78 | 67.84 | 0.00 | 0.00 | 0.00 |
May | 100.24 | 29.11 | 71.13 | 113.21 | 48.14 | 0.00 | 0.00 | 0.00 |
June | 97.40 | 20.64 | 76.76 | 121.25 | 33.11 | 0.00 | 0.00 | 0.00 |
July | 99.43 | 24.12 | 75.30 | 137.32 | 23.28 | 0.00 | 0.00 | 0.00 |
August | 111.63 | 36.19 | 75.43 | 151.28 | 30.29 | 0.00 | 0.00 | 0.00 |
September | 129.79 | 63.22 | 66.57 | 162.04 | 47.28 | 0.00 | 0.00 | 0.00 |
October | 124.19 | 70.94 | 53.25 | 136.07 | 67.09 | 0.00 | 0.00 | 0.00 |
November | 88.94 | 50.21 | 38.73 | 85.67 | 84.25 | 0.00 | 0.00 | 0.00 |
December | 82.99 | 42.95 | 40.04 | 63.69 | 121.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.30 | 47.76 | 60.54 | 116.93 | 70.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.99 | 20.64 | 38.73 | 63.69 | 23.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.32 | 77.72 | 76.76 | 162.04 | 123.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 67.70 | 101.64 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 76.36 | 98.51 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 116.47 | 71.73 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 101.70 | 55.18 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 95.68 | 38.52 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 101.68 | 26.82 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.01 | 18.64 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.67 | 24.50 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.78 | 38.70 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 114.42 | 54.75 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 72.05 | 69.13 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 53.50 | 100.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 98.21 | 57.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 53.50 | 18.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.78 | 101.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 67.70 | 101.64 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 76.36 | 98.51 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 116.47 | 71.73 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 101.70 | 55.18 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 95.68 | 38.52 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 101.68 | 26.82 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.01 | 18.64 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.67 | 24.50 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.78 | 38.70 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 114.42 | 54.75 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 72.05 | 69.13 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 53.50 | 100.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 98.21 | 57.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 53.50 | 18.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.78 | 101.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 67.70 | 101.64 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 76.36 | 98.51 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 116.47 | 71.73 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 101.70 | 55.18 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 95.68 | 38.52 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 101.68 | 26.82 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.01 | 18.64 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.67 | 24.50 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.78 | 38.70 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 114.42 | 54.75 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 72.05 | 69.13 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 53.50 | 100.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 98.21 | 57.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 53.50 | 18.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.78 | 101.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 67.70 | 101.64 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 76.36 | 98.51 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 116.47 | 71.73 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 101.70 | 55.18 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 95.68 | 38.52 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 101.68 | 26.82 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.01 | 18.64 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.67 | 24.50 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.78 | 38.70 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 114.42 | 54.75 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 72.05 | 69.13 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 53.50 | 100.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 98.21 | 57.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 53.50 | 18.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.78 | 101.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.25 | 57.94 | 41.32 | 81.57 | 119.53 | 0.00 | 0.00 | 0.00 |
February | 113.32 | 54.64 | 58.68 | 92.24 | 115.72 | 0.00 | 0.00 | 0.00 |
March | 138.32 | 77.72 | 60.60 | 139.99 | 84.55 | 0.00 | 0.00 | 0.00 |
April | 114.55 | 45.77 | 68.77 | 122.13 | 65.05 | 0.00 | 0.00 | 0.00 |
May | 100.24 | 29.11 | 71.13 | 114.74 | 45.52 | 0.00 | 0.00 | 0.00 |
June | 97.40 | 20.64 | 76.76 | 121.76 | 31.76 | 0.00 | 0.00 | 0.00 |
July | 99.43 | 24.12 | 75.30 | 137.53 | 22.12 | 0.00 | 0.00 | 0.00 |
August | 111.63 | 36.19 | 75.43 | 151.48 | 29.04 | 0.00 | 0.00 | 0.00 |
September | 129.79 | 63.22 | 66.57 | 162.51 | 45.83 | 0.00 | 0.00 | 0.00 |
October | 124.19 | 70.94 | 53.25 | 137.24 | 64.65 | 0.00 | 0.00 | 0.00 |
November | 88.94 | 50.21 | 38.73 | 86.58 | 81.42 | 0.00 | 0.00 | 0.00 |
December | 82.99 | 42.95 | 40.04 | 64.55 | 117.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.30 | 47.76 | 60.54 | 117.84 | 68.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.99 | 20.64 | 38.73 | 64.55 | 22.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.32 | 77.72 | 76.76 | 162.51 | 119.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.25 | 57.94 | 41.32 | 81.57 | 119.53 | 0.00 | 0.00 | 0.00 |
February | 113.32 | 54.64 | 58.68 | 92.24 | 115.72 | 0.00 | 0.00 | 0.00 |
March | 138.32 | 77.72 | 60.60 | 139.99 | 84.55 | 0.00 | 0.00 | 0.00 |
April | 114.55 | 45.77 | 68.77 | 122.13 | 65.05 | 0.00 | 0.00 | 0.00 |
May | 100.24 | 29.11 | 71.13 | 114.74 | 45.52 | 0.00 | 0.00 | 0.00 |
June | 97.40 | 20.64 | 76.76 | 121.76 | 31.76 | 0.00 | 0.00 | 0.00 |
July | 99.43 | 24.12 | 75.30 | 137.53 | 22.12 | 0.00 | 0.00 | 0.00 |
August | 111.63 | 36.19 | 75.43 | 151.48 | 29.04 | 0.00 | 0.00 | 0.00 |
September | 129.79 | 63.22 | 66.57 | 162.51 | 45.83 | 0.00 | 0.00 | 0.00 |
October | 124.19 | 70.94 | 53.25 | 137.24 | 64.65 | 0.00 | 0.00 | 0.00 |
November | 88.94 | 50.21 | 38.73 | 86.58 | 81.42 | 0.00 | 0.00 | 0.00 |
December | 82.99 | 42.95 | 40.04 | 64.55 | 117.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.30 | 47.76 | 60.54 | 117.84 | 68.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.99 | 20.64 | 38.73 | 64.55 | 22.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.32 | 77.72 | 76.76 | 162.51 | 119.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 67.32 | 102.39 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 75.81 | 99.28 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 116.03 | 71.95 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 101.47 | 55.15 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 95.70 | 38.19 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 101.64 | 26.60 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.04 | 18.38 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.63 | 24.23 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.65 | 38.49 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 114.24 | 54.60 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 71.83 | 69.33 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 53.16 | 100.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 98.01 | 58.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 53.16 | 18.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.65 | 102.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 67.32 | 102.39 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 75.81 | 99.28 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 116.03 | 71.95 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 101.47 | 55.15 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 95.70 | 38.19 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 101.64 | 26.60 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.04 | 18.38 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.63 | 24.23 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.65 | 38.49 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 114.24 | 54.60 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 71.83 | 69.33 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 53.16 | 100.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 98.01 | 58.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 53.16 | 18.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.65 | 102.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.25 | 57.94 | 41.32 | 81.15 | 120.34 | 0.00 | 0.00 | 0.00 |
February | 113.32 | 54.64 | 58.68 | 91.65 | 116.55 | 0.00 | 0.00 | 0.00 |
March | 138.32 | 77.72 | 60.60 | 139.54 | 84.76 | 0.00 | 0.00 | 0.00 |
April | 114.55 | 45.77 | 68.77 | 121.90 | 64.98 | 0.00 | 0.00 | 0.00 |
May | 100.24 | 29.11 | 71.13 | 114.80 | 45.10 | 0.00 | 0.00 | 0.00 |
June | 97.40 | 20.64 | 76.76 | 121.75 | 31.50 | 0.00 | 0.00 | 0.00 |
July | 99.43 | 24.12 | 75.30 | 137.59 | 21.80 | 0.00 | 0.00 | 0.00 |
August | 111.63 | 36.19 | 75.43 | 151.47 | 28.72 | 0.00 | 0.00 | 0.00 |
September | 129.79 | 63.22 | 66.57 | 162.39 | 45.57 | 0.00 | 0.00 | 0.00 |
October | 124.19 | 70.94 | 53.25 | 137.07 | 64.45 | 0.00 | 0.00 | 0.00 |
November | 88.94 | 50.21 | 38.73 | 86.35 | 81.60 | 0.00 | 0.00 | 0.00 |
December | 82.99 | 42.95 | 40.04 | 64.18 | 118.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.30 | 47.76 | 60.54 | 117.64 | 68.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.99 | 20.64 | 38.73 | 64.18 | 21.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.32 | 77.72 | 76.76 | 162.39 | 120.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 67.37 | 102.13 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 75.87 | 99.05 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 116.15 | 71.63 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 101.65 | 54.76 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 96.04 | 37.66 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 101.79 | 26.41 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.13 | 18.26 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.71 | 24.10 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.75 | 38.29 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 114.41 | 54.23 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 71.92 | 69.00 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 53.20 | 100.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 98.13 | 57.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 53.20 | 18.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.75 | 102.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 67.37 | 102.13 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 75.87 | 99.05 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 116.15 | 71.63 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 101.65 | 54.76 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 96.04 | 37.66 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 101.79 | 26.41 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.13 | 18.26 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.71 | 24.10 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.75 | 38.29 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 114.41 | 54.23 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 71.92 | 69.00 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 53.20 | 100.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 98.13 | 57.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 53.20 | 18.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.75 | 102.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.25 | 57.94 | 41.32 | 81.21 | 120.03 | 0.00 | 0.00 | 0.00 |
February | 113.32 | 54.64 | 58.68 | 91.72 | 116.28 | 0.00 | 0.00 | 0.00 |
March | 138.32 | 77.72 | 60.60 | 139.68 | 84.38 | 0.00 | 0.00 | 0.00 |
April | 114.55 | 45.77 | 68.77 | 122.11 | 64.51 | 0.00 | 0.00 | 0.00 |
May | 100.24 | 29.11 | 71.13 | 115.22 | 44.48 | 0.00 | 0.00 | 0.00 |
June | 97.40 | 20.64 | 76.76 | 121.92 | 31.27 | 0.00 | 0.00 | 0.00 |
July | 99.43 | 24.12 | 75.30 | 137.70 | 21.66 | 0.00 | 0.00 | 0.00 |
August | 111.63 | 36.19 | 75.43 | 151.56 | 28.57 | 0.00 | 0.00 | 0.00 |
September | 129.79 | 63.22 | 66.57 | 162.52 | 45.33 | 0.00 | 0.00 | 0.00 |
October | 124.19 | 70.94 | 53.25 | 137.28 | 64.01 | 0.00 | 0.00 | 0.00 |
November | 88.94 | 50.21 | 38.73 | 86.46 | 81.22 | 0.00 | 0.00 | 0.00 |
December | 82.99 | 42.95 | 40.04 | 64.23 | 118.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.30 | 47.76 | 60.54 | 117.79 | 68.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.99 | 20.64 | 38.73 | 64.23 | 21.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.32 | 77.72 | 76.76 | 162.52 | 120.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 67.56 | 100.85 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 76.12 | 97.89 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 116.54 | 70.36 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 102.12 | 53.50 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 96.85 | 36.35 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 102.15 | 25.86 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.28 | 17.98 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.83 | 23.82 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.99 | 37.73 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 114.81 | 53.27 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 72.18 | 67.92 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 53.37 | 99.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 98.45 | 56.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 53.37 | 17.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.99 | 100.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 67.56 | 100.85 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 76.12 | 97.89 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 116.54 | 70.36 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 102.12 | 53.50 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 96.85 | 36.35 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 102.15 | 25.86 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.28 | 17.98 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 126.83 | 23.82 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 135.99 | 37.73 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 114.81 | 53.27 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 72.18 | 67.92 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 53.37 | 99.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 98.45 | 56.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 53.37 | 17.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 135.99 | 100.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.25 | 57.94 | 41.32 | 81.46 | 118.52 | 0.00 | 0.00 | 0.00 |
February | 113.32 | 54.64 | 58.68 | 92.02 | 114.90 | 0.00 | 0.00 | 0.00 |
March | 138.32 | 77.72 | 60.60 | 140.15 | 82.88 | 0.00 | 0.00 | 0.00 |
April | 114.55 | 45.77 | 68.77 | 122.68 | 63.03 | 0.00 | 0.00 | 0.00 |
May | 100.24 | 29.11 | 71.13 | 116.17 | 42.95 | 0.00 | 0.00 | 0.00 |
June | 97.40 | 20.64 | 76.76 | 122.36 | 30.63 | 0.00 | 0.00 | 0.00 |
July | 99.43 | 24.12 | 75.30 | 137.88 | 21.34 | 0.00 | 0.00 | 0.00 |
August | 111.63 | 36.19 | 75.43 | 151.71 | 28.24 | 0.00 | 0.00 | 0.00 |
September | 129.79 | 63.22 | 66.57 | 162.80 | 44.67 | 0.00 | 0.00 | 0.00 |
October | 124.19 | 70.94 | 53.25 | 137.75 | 62.88 | 0.00 | 0.00 | 0.00 |
November | 88.94 | 50.21 | 38.73 | 86.77 | 79.95 | 0.00 | 0.00 | 0.00 |
December | 82.99 | 42.95 | 40.04 | 64.44 | 116.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.30 | 47.76 | 60.54 | 118.17 | 66.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.99 | 20.64 | 38.73 | 64.44 | 21.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.32 | 77.72 | 76.76 | 162.80 | 118.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 68.43 | 95.32 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 77.17 | 92.67 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 117.93 | 65.17 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 103.48 | 48.79 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 98.66 | 32.51 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 103.14 | 23.84 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.57 | 16.92 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 127.04 | 22.70 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 136.57 | 35.73 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 115.71 | 50.20 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 72.99 | 63.88 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 54.08 | 93.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 99.36 | 53.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 54.08 | 16.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 136.57 | 95.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.02 | 48.46 | 34.56 | 68.43 | 95.32 | 0.00 | 0.00 | 0.00 |
February | 94.78 | 45.70 | 49.08 | 77.17 | 92.67 | 0.00 | 0.00 | 0.00 |
March | 115.69 | 65.00 | 50.68 | 117.93 | 65.17 | 0.00 | 0.00 | 0.00 |
April | 95.81 | 38.29 | 57.52 | 103.48 | 48.79 | 0.00 | 0.00 | 0.00 |
May | 83.84 | 24.35 | 59.49 | 98.66 | 32.51 | 0.00 | 0.00 | 0.00 |
June | 81.47 | 17.26 | 64.20 | 103.14 | 23.84 | 0.00 | 0.00 | 0.00 |
July | 83.16 | 20.18 | 62.99 | 115.57 | 16.92 | 0.00 | 0.00 | 0.00 |
August | 93.37 | 30.27 | 63.09 | 127.04 | 22.70 | 0.00 | 0.00 | 0.00 |
September | 108.56 | 52.87 | 55.68 | 136.57 | 35.73 | 0.00 | 0.00 | 0.00 |
October | 103.87 | 59.33 | 44.54 | 115.71 | 50.20 | 0.00 | 0.00 | 0.00 |
November | 74.39 | 42.00 | 32.39 | 72.99 | 63.88 | 0.00 | 0.00 | 0.00 |
December | 69.42 | 35.93 | 33.49 | 54.08 | 93.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.59 | 39.95 | 50.64 | 99.36 | 53.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.42 | 17.26 | 32.39 | 54.08 | 16.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.69 | 65.00 | 64.20 | 136.57 | 95.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.25 | 57.94 | 41.32 | 82.52 | 111.99 | 0.00 | 0.00 | 0.00 |
February | 113.32 | 54.64 | 58.68 | 93.30 | 108.75 | 0.00 | 0.00 | 0.00 |
March | 138.32 | 77.72 | 60.60 | 141.83 | 76.77 | 0.00 | 0.00 | 0.00 |
April | 114.55 | 45.77 | 68.77 | 124.31 | 57.50 | 0.00 | 0.00 | 0.00 |
May | 100.24 | 29.11 | 71.13 | 118.34 | 38.44 | 0.00 | 0.00 | 0.00 |
June | 97.40 | 20.64 | 76.76 | 123.54 | 28.25 | 0.00 | 0.00 | 0.00 |
July | 99.43 | 24.12 | 75.30 | 138.21 | 20.10 | 0.00 | 0.00 | 0.00 |
August | 111.63 | 36.19 | 75.43 | 151.97 | 26.93 | 0.00 | 0.00 | 0.00 |
September | 129.79 | 63.22 | 66.57 | 163.50 | 42.32 | 0.00 | 0.00 | 0.00 |
October | 124.19 | 70.94 | 53.25 | 138.84 | 59.28 | 0.00 | 0.00 | 0.00 |
November | 88.94 | 50.21 | 38.73 | 87.76 | 75.19 | 0.00 | 0.00 | 0.00 |
December | 82.99 | 42.95 | 40.04 | 65.32 | 110.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.30 | 47.76 | 60.54 | 119.27 | 62.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.99 | 20.64 | 38.73 | 65.32 | 20.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.32 | 77.72 | 76.76 | 163.50 | 111.99 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.180817E+09 | 0.280857E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.184161E+09 | 0.245364E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.311286E+09 | 0.196701E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.262640E+09 | 0.146960E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.254722E+09 | 0.106589E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.264159E+09 | 68375153.37 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.309332E+09 | 47706067.98 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339987E+09 | 63668050.77 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.351939E+09 | 99887429.08 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.304621E+09 | 0.151201E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.185530E+09 | 0.184665E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.142687E+09 | 0.276347E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.309188E+10 | 0.186832E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.142687E+09 | 47706067.98 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.351939E+09 | 0.280857E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.180817E+09 | 0.280857E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.184161E+09 | 0.245364E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.311286E+09 | 0.196701E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.262640E+09 | 0.146960E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.254722E+09 | 0.106589E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.264159E+09 | 68375153.37 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.309332E+09 | 47706067.98 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339987E+09 | 63668050.77 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.351939E+09 | 99887429.08 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.304621E+09 | 0.151201E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.185530E+09 | 0.184665E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.142687E+09 | 0.276347E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.309188E+10 | 0.186832E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.142687E+09 | 47706067.98 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.351939E+09 | 0.280857E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.180817E+09 | 0.280857E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.184161E+09 | 0.245364E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.311286E+09 | 0.196701E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.262640E+09 | 0.146960E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.254722E+09 | 0.106589E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.264159E+09 | 68375153.37 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.309332E+09 | 47706067.98 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339987E+09 | 63668050.77 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.351939E+09 | 99887429.08 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.304621E+09 | 0.151201E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.185530E+09 | 0.184665E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.142687E+09 | 0.276347E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.309188E+10 | 0.186832E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.142687E+09 | 47706067.98 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.351939E+09 | 0.280857E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.180817E+09 | 0.280857E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.184161E+09 | 0.245364E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.311286E+09 | 0.196701E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.262640E+09 | 0.146960E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.254722E+09 | 0.106589E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.264159E+09 | 68375153.37 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.309332E+09 | 47706067.98 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339987E+09 | 63668050.77 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.351939E+09 | 99887429.08 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.304621E+09 | 0.151201E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.185530E+09 | 0.184665E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.142687E+09 | 0.276347E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.309188E+10 | 0.186832E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.142687E+09 | 47706067.98 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.351939E+09 | 0.280857E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.267297E+09 | 0.156029E+09 | 0.111268E+09 | 0.219039E+09 | 0.332109E+09 |
February | 0.275652E+09 | 0.132917E+09 | 0.142735E+09 | 0.223683E+09 | 0.289791E+09 |
March | 0.372500E+09 | 0.209306E+09 | 0.163195E+09 | 0.376210E+09 | 0.233120E+09 |
April | 0.298538E+09 | 0.119297E+09 | 0.179241E+09 | 0.317103E+09 | 0.174214E+09 |
May | 0.269955E+09 | 78406390.86 | 0.191549E+09 | 0.307157E+09 | 0.126662E+09 |
June | 0.253848E+09 | 53791640.83 | 0.200056E+09 | 0.318032E+09 | 81485159.50 |
July | 0.267775E+09 | 64971097.01 | 0.202804E+09 | 0.371853E+09 | 56982165.19 |
August | 0.300622E+09 | 97469222.59 | 0.203153E+09 | 0.408784E+09 | 75969219.03 |
September | 0.338259E+09 | 0.164757E+09 | 0.173502E+09 | 0.423522E+09 | 0.119003E+09 |
October | 0.334452E+09 | 0.191046E+09 | 0.143407E+09 | 0.367386E+09 | 0.179581E+09 |
November | 0.231801E+09 | 0.130860E+09 | 0.100942E+09 | 0.224163E+09 | 0.218730E+09 |
December | 0.223514E+09 | 0.115678E+09 | 0.107835E+09 | 0.173100E+09 | 0.326410E+09 |
Annual Sum or Average | 0.343421E+10 | 0.151453E+10 | 0.191969E+10 | 0.373003E+10 | 0.221406E+10 |
Minimum of Months | 0.223514E+09 | 53791640.83 | 0.100942E+09 | 0.173100E+09 | 56982165.19 |
Maximum of Months | 0.372500E+09 | 0.209306E+09 | 0.203153E+09 | 0.423522E+09 | 0.332109E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.267297E+09 | 0.156029E+09 | 0.111268E+09 | 0.219039E+09 | 0.332109E+09 |
February | 0.275652E+09 | 0.132917E+09 | 0.142735E+09 | 0.223683E+09 | 0.289791E+09 |
March | 0.372500E+09 | 0.209306E+09 | 0.163195E+09 | 0.376210E+09 | 0.233120E+09 |
April | 0.298538E+09 | 0.119297E+09 | 0.179241E+09 | 0.317103E+09 | 0.174214E+09 |
May | 0.269955E+09 | 78406390.86 | 0.191549E+09 | 0.307157E+09 | 0.126662E+09 |
June | 0.253848E+09 | 53791640.83 | 0.200056E+09 | 0.318032E+09 | 81485159.50 |
July | 0.267775E+09 | 64971097.01 | 0.202804E+09 | 0.371853E+09 | 56982165.19 |
August | 0.300622E+09 | 97469222.59 | 0.203153E+09 | 0.408784E+09 | 75969219.03 |
September | 0.338259E+09 | 0.164757E+09 | 0.173502E+09 | 0.423522E+09 | 0.119003E+09 |
October | 0.334452E+09 | 0.191046E+09 | 0.143407E+09 | 0.367386E+09 | 0.179581E+09 |
November | 0.231801E+09 | 0.130860E+09 | 0.100942E+09 | 0.224163E+09 | 0.218730E+09 |
December | 0.223514E+09 | 0.115678E+09 | 0.107835E+09 | 0.173100E+09 | 0.326410E+09 |
Annual Sum or Average | 0.343421E+10 | 0.151453E+10 | 0.191969E+10 | 0.373003E+10 | 0.221406E+10 |
Minimum of Months | 0.223514E+09 | 53791640.83 | 0.100942E+09 | 0.173100E+09 | 56982165.19 |
Maximum of Months | 0.372500E+09 | 0.209306E+09 | 0.203153E+09 | 0.423522E+09 | 0.332109E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.177655E+09 | 0.295519E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.180301E+09 | 0.258507E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.306570E+09 | 0.209431E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.257536E+09 | 0.159611E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.249657E+09 | 0.114422E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.262317E+09 | 70476011.71 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308493E+09 | 48681948.89 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339199E+09 | 64805351.11 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.350346E+09 | 0.102449E+09 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.300708E+09 | 0.161046E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.182565E+09 | 0.197288E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.140019E+09 | 0.291221E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.305537E+10 | 0.197346E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.140019E+09 | 48681948.89 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.350346E+09 | 0.295519E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.177655E+09 | 0.295519E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.180301E+09 | 0.258507E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.306570E+09 | 0.209431E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.257536E+09 | 0.159611E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.249657E+09 | 0.114422E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.262317E+09 | 70476011.71 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308493E+09 | 48681948.89 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339199E+09 | 64805351.11 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.350346E+09 | 0.102449E+09 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.300708E+09 | 0.161046E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.182565E+09 | 0.197288E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.140019E+09 | 0.291221E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.305537E+10 | 0.197346E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.140019E+09 | 48681948.89 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.350346E+09 | 0.295519E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.267297E+09 | 0.156029E+09 | 0.111268E+09 | 0.215287E+09 | 0.349261E+09 |
February | 0.275652E+09 | 0.132917E+09 | 0.142735E+09 | 0.219122E+09 | 0.305131E+09 |
March | 0.372500E+09 | 0.209306E+09 | 0.163195E+09 | 0.370665E+09 | 0.248010E+09 |
April | 0.298538E+09 | 0.119297E+09 | 0.179241E+09 | 0.311090E+09 | 0.189015E+09 |
May | 0.269955E+09 | 78406390.86 | 0.191549E+09 | 0.301192E+09 | 0.135854E+09 |
June | 0.253848E+09 | 53791640.83 | 0.200056E+09 | 0.315901E+09 | 83947764.77 |
July | 0.267775E+09 | 64971097.01 | 0.202804E+09 | 0.370914E+09 | 58124558.10 |
August | 0.300622E+09 | 97469222.59 | 0.203153E+09 | 0.407912E+09 | 77293593.10 |
September | 0.338259E+09 | 0.164757E+09 | 0.173502E+09 | 0.421707E+09 | 0.122001E+09 |
October | 0.334452E+09 | 0.191046E+09 | 0.143407E+09 | 0.362822E+09 | 0.191084E+09 |
November | 0.231801E+09 | 0.130860E+09 | 0.100942E+09 | 0.220671E+09 | 0.233455E+09 |
December | 0.223514E+09 | 0.115678E+09 | 0.107835E+09 | 0.169946E+09 | 0.343780E+09 |
Annual Sum or Average | 0.343421E+10 | 0.151453E+10 | 0.191969E+10 | 0.368723E+10 | 0.233696E+10 |
Minimum of Months | 0.223514E+09 | 53791640.83 | 0.100942E+09 | 0.169946E+09 | 58124558.10 |
Maximum of Months | 0.372500E+09 | 0.209306E+09 | 0.203153E+09 | 0.421707E+09 | 0.349261E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.178207E+09 | 0.287742E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.180849E+09 | 0.251678E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.307245E+09 | 0.203614E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.258656E+09 | 0.154395E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.250373E+09 | 0.113758E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.261760E+09 | 73711206.06 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.307195E+09 | 53270895.99 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.338436E+09 | 69272213.50 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.350256E+09 | 0.105162E+09 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.301885E+09 | 0.157141E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.183506E+09 | 0.190741E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.140529E+09 | 0.283555E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.305890E+10 | 0.194404E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.140529E+09 | 53270895.99 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.350256E+09 | 0.287742E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.178207E+09 | 0.287742E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.180849E+09 | 0.251678E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.307245E+09 | 0.203614E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.258656E+09 | 0.154395E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.250373E+09 | 0.113758E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.261760E+09 | 73711206.06 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.307195E+09 | 53270895.99 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.338436E+09 | 69272213.50 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.350256E+09 | 0.105162E+09 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.301885E+09 | 0.157141E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.183506E+09 | 0.190741E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.140529E+09 | 0.283555E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.305890E+10 | 0.194404E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.140529E+09 | 53270895.99 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.350256E+09 | 0.287742E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265837E+09 | 0.155177E+09 | 0.110660E+09 | 0.214783E+09 | 0.338234E+09 |
February | 0.274146E+09 | 0.132191E+09 | 0.141955E+09 | 0.218598E+09 | 0.295486E+09 |
March | 0.370465E+09 | 0.208162E+09 | 0.162303E+09 | 0.369456E+09 | 0.239854E+09 |
April | 0.296906E+09 | 0.118645E+09 | 0.178262E+09 | 0.310727E+09 | 0.181890E+09 |
May | 0.268480E+09 | 77977940.64 | 0.190502E+09 | 0.300397E+09 | 0.134309E+09 |
June | 0.252461E+09 | 53497697.44 | 0.198963E+09 | 0.313518E+09 | 87241248.31 |
July | 0.266312E+09 | 64616063.69 | 0.201696E+09 | 0.367369E+09 | 63151374.84 |
August | 0.298979E+09 | 96936603.89 | 0.202043E+09 | 0.404789E+09 | 82070403.67 |
September | 0.336410E+09 | 0.163857E+09 | 0.172553E+09 | 0.419298E+09 | 0.124473E+09 |
October | 0.332625E+09 | 0.190002E+09 | 0.142623E+09 | 0.362242E+09 | 0.185462E+09 |
November | 0.230534E+09 | 0.130144E+09 | 0.100390E+09 | 0.220596E+09 | 0.224538E+09 |
December | 0.222292E+09 | 0.115046E+09 | 0.107246E+09 | 0.169640E+09 | 0.332933E+09 |
Annual Sum or Average | 0.341545E+10 | 0.150625E+10 | 0.190920E+10 | 0.367142E+10 | 0.228964E+10 |
Minimum of Months | 0.222292E+09 | 53497697.44 | 0.100390E+09 | 0.169640E+09 | 63151374.84 |
Maximum of Months | 0.370465E+09 | 0.208162E+09 | 0.202043E+09 | 0.419298E+09 | 0.338234E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.178593E+09 | 0.284480E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.181279E+09 | 0.248961E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.307820E+09 | 0.201134E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.259499E+09 | 0.151769E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.251243E+09 | 0.111847E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.261872E+09 | 73482790.00 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.307168E+09 | 53402357.74 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.338428E+09 | 69347441.30 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.350401E+09 | 0.104690E+09 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.302674E+09 | 0.154726E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.184074E+09 | 0.187900E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.140867E+09 | 0.280454E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.306392E+10 | 0.192219E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.140867E+09 | 53402357.74 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.350401E+09 | 0.284480E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.178593E+09 | 0.284480E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.181279E+09 | 0.248961E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.307820E+09 | 0.201134E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.259499E+09 | 0.151769E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.251243E+09 | 0.111847E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.261872E+09 | 73482790.00 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.307168E+09 | 53402357.74 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.338428E+09 | 69347441.30 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.350401E+09 | 0.104690E+09 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.302674E+09 | 0.154726E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.184074E+09 | 0.187900E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.140867E+09 | 0.280454E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.306392E+10 | 0.192219E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.140867E+09 | 53402357.74 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.350401E+09 | 0.284480E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265837E+09 | 0.155177E+09 | 0.110660E+09 | 0.215256E+09 | 0.334377E+09 |
February | 0.274146E+09 | 0.132191E+09 | 0.141955E+09 | 0.219126E+09 | 0.292286E+09 |
March | 0.370465E+09 | 0.208162E+09 | 0.162303E+09 | 0.370153E+09 | 0.236929E+09 |
April | 0.296906E+09 | 0.118645E+09 | 0.178262E+09 | 0.311736E+09 | 0.178795E+09 |
May | 0.268480E+09 | 77977940.64 | 0.190502E+09 | 0.301435E+09 | 0.132057E+09 |
June | 0.252461E+09 | 53497697.44 | 0.198963E+09 | 0.313653E+09 | 86972273.94 |
July | 0.266312E+09 | 64616063.69 | 0.201696E+09 | 0.367337E+09 | 63306145.75 |
August | 0.298979E+09 | 96936603.89 | 0.202043E+09 | 0.404780E+09 | 82159514.58 |
September | 0.336410E+09 | 0.163857E+09 | 0.172553E+09 | 0.419472E+09 | 0.123915E+09 |
October | 0.332625E+09 | 0.190002E+09 | 0.142623E+09 | 0.363183E+09 | 0.182613E+09 |
November | 0.230534E+09 | 0.130144E+09 | 0.100390E+09 | 0.221277E+09 | 0.221188E+09 |
December | 0.222292E+09 | 0.115046E+09 | 0.107246E+09 | 0.170053E+09 | 0.329268E+09 |
Annual Sum or Average | 0.341545E+10 | 0.150625E+10 | 0.190920E+10 | 0.367746E+10 | 0.226387E+10 |
Minimum of Months | 0.222292E+09 | 53497697.44 | 0.100390E+09 | 0.170053E+09 | 63306145.75 |
Maximum of Months | 0.370465E+09 | 0.208162E+09 | 0.202043E+09 | 0.419472E+09 | 0.334377E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.179095E+09 | 0.281682E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.181853E+09 | 0.246613E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.308617E+09 | 0.198885E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.260603E+09 | 0.149257E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.252747E+09 | 0.109186E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.262389E+09 | 72502886.08 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.307555E+09 | 52588302.32 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.338765E+09 | 68476088.50 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.350836E+09 | 0.103529E+09 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.303729E+09 | 0.152251E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.184717E+09 | 0.185507E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.141300E+09 | 0.277704E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.307221E+10 | 0.189818E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.141300E+09 | 52588302.32 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.350836E+09 | 0.281682E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.179095E+09 | 0.281682E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.181853E+09 | 0.246613E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.308617E+09 | 0.198885E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.260603E+09 | 0.149257E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.252747E+09 | 0.109186E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.262389E+09 | 72502886.08 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.307555E+09 | 52588302.32 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.338765E+09 | 68476088.50 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.350836E+09 | 0.103529E+09 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.303729E+09 | 0.152251E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.184717E+09 | 0.185507E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.141300E+09 | 0.277704E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.307221E+10 | 0.189818E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.141300E+09 | 52588302.32 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.350836E+09 | 0.281682E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265837E+09 | 0.155177E+09 | 0.110660E+09 | 0.215870E+09 | 0.331070E+09 |
February | 0.274146E+09 | 0.132191E+09 | 0.141955E+09 | 0.219827E+09 | 0.289518E+09 |
March | 0.370465E+09 | 0.208162E+09 | 0.162303E+09 | 0.371115E+09 | 0.234279E+09 |
April | 0.296906E+09 | 0.118645E+09 | 0.178262E+09 | 0.313057E+09 | 0.175839E+09 |
May | 0.268480E+09 | 77977940.64 | 0.190502E+09 | 0.303227E+09 | 0.128928E+09 |
June | 0.252461E+09 | 53497697.44 | 0.198963E+09 | 0.314272E+09 | 85822337.26 |
July | 0.266312E+09 | 64616063.69 | 0.201696E+09 | 0.367801E+09 | 62353433.85 |
August | 0.298979E+09 | 96936603.89 | 0.202043E+09 | 0.405185E+09 | 81137496.53 |
September | 0.336410E+09 | 0.163857E+09 | 0.172553E+09 | 0.419995E+09 | 0.122550E+09 |
October | 0.332625E+09 | 0.190002E+09 | 0.142623E+09 | 0.364440E+09 | 0.179701E+09 |
November | 0.230534E+09 | 0.130144E+09 | 0.100390E+09 | 0.222051E+09 | 0.218369E+09 |
December | 0.222292E+09 | 0.115046E+09 | 0.107246E+09 | 0.170580E+09 | 0.326019E+09 |
Annual Sum or Average | 0.341545E+10 | 0.150625E+10 | 0.190920E+10 | 0.368742E+10 | 0.223559E+10 |
Minimum of Months | 0.222292E+09 | 53497697.44 | 0.100390E+09 | 0.170580E+09 | 62353433.85 |
Maximum of Months | 0.370465E+09 | 0.208162E+09 | 0.202043E+09 | 0.419995E+09 | 0.331070E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.181325E+09 | 0.272228E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.184726E+09 | 0.238306E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.311942E+09 | 0.192130E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.263615E+09 | 0.143037E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.256264E+09 | 0.103174E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.263555E+09 | 69518231.27 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308054E+09 | 49935720.40 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339263E+09 | 65616840.46 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.351938E+09 | 0.100310E+09 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.306468E+09 | 0.146633E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.186758E+09 | 0.179182E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.143290E+09 | 0.268266E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.309720E+10 | 0.182834E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.143290E+09 | 49935720.40 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.351938E+09 | 0.272228E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.181325E+09 | 0.272228E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.184726E+09 | 0.238306E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.311942E+09 | 0.192130E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.263615E+09 | 0.143037E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.256264E+09 | 0.103174E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.263555E+09 | 69518231.27 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308054E+09 | 49935720.40 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339263E+09 | 65616840.46 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.351938E+09 | 0.100310E+09 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.306468E+09 | 0.146633E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.186758E+09 | 0.179182E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.143290E+09 | 0.268266E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.309720E+10 | 0.182834E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.143290E+09 | 49935720.40 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.351938E+09 | 0.272228E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.181325E+09 | 0.272228E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.184726E+09 | 0.238306E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.311942E+09 | 0.192130E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.263615E+09 | 0.143037E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.256264E+09 | 0.103174E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.263555E+09 | 69518231.27 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308054E+09 | 49935720.40 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339263E+09 | 65616840.46 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.351938E+09 | 0.100310E+09 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.306468E+09 | 0.146633E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.186758E+09 | 0.179182E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.143290E+09 | 0.268266E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.309720E+10 | 0.182834E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.143290E+09 | 49935720.40 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.351938E+09 | 0.272228E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.181325E+09 | 0.272228E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.184726E+09 | 0.238306E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.311942E+09 | 0.192130E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.263615E+09 | 0.143037E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.256264E+09 | 0.103174E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.263555E+09 | 69518231.27 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308054E+09 | 49935720.40 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339263E+09 | 65616840.46 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.351938E+09 | 0.100310E+09 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.306468E+09 | 0.146633E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.186758E+09 | 0.179182E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.143290E+09 | 0.268266E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.309720E+10 | 0.182834E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.143290E+09 | 49935720.40 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.351938E+09 | 0.272228E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265837E+09 | 0.155177E+09 | 0.110660E+09 | 0.218479E+09 | 0.320155E+09 |
February | 0.274146E+09 | 0.132191E+09 | 0.141955E+09 | 0.223148E+09 | 0.279944E+09 |
March | 0.370465E+09 | 0.208162E+09 | 0.162303E+09 | 0.374958E+09 | 0.226457E+09 |
April | 0.296906E+09 | 0.118645E+09 | 0.178262E+09 | 0.316550E+09 | 0.168619E+09 |
May | 0.268480E+09 | 77977940.64 | 0.190502E+09 | 0.307326E+09 | 0.121910E+09 |
June | 0.252461E+09 | 53497697.44 | 0.198963E+09 | 0.315604E+09 | 82333916.23 |
July | 0.266312E+09 | 64616063.69 | 0.201696E+09 | 0.368354E+09 | 59245193.46 |
August | 0.298979E+09 | 96936603.89 | 0.202043E+09 | 0.405729E+09 | 77789193.01 |
September | 0.336410E+09 | 0.163857E+09 | 0.172553E+09 | 0.421233E+09 | 0.118783E+09 |
October | 0.332625E+09 | 0.190002E+09 | 0.142623E+09 | 0.367595E+09 | 0.173171E+09 |
November | 0.230534E+09 | 0.130144E+09 | 0.100390E+09 | 0.224426E+09 | 0.211048E+09 |
December | 0.222292E+09 | 0.115046E+09 | 0.107246E+09 | 0.172899E+09 | 0.315126E+09 |
Annual Sum or Average | 0.341545E+10 | 0.150625E+10 | 0.190920E+10 | 0.371630E+10 | 0.215458E+10 |
Minimum of Months | 0.222292E+09 | 53497697.44 | 0.100390E+09 | 0.172899E+09 | 59245193.46 |
Maximum of Months | 0.370465E+09 | 0.208162E+09 | 0.202043E+09 | 0.421233E+09 | 0.320155E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265837E+09 | 0.155177E+09 | 0.110660E+09 | 0.218479E+09 | 0.320155E+09 |
February | 0.274146E+09 | 0.132191E+09 | 0.141955E+09 | 0.223148E+09 | 0.279944E+09 |
March | 0.370465E+09 | 0.208162E+09 | 0.162303E+09 | 0.374958E+09 | 0.226457E+09 |
April | 0.296906E+09 | 0.118645E+09 | 0.178262E+09 | 0.316550E+09 | 0.168619E+09 |
May | 0.268480E+09 | 77977940.64 | 0.190502E+09 | 0.307326E+09 | 0.121910E+09 |
June | 0.252461E+09 | 53497697.44 | 0.198963E+09 | 0.315604E+09 | 82333916.23 |
July | 0.266312E+09 | 64616063.69 | 0.201696E+09 | 0.368354E+09 | 59245193.46 |
August | 0.298979E+09 | 96936603.89 | 0.202043E+09 | 0.405729E+09 | 77789193.01 |
September | 0.336410E+09 | 0.163857E+09 | 0.172553E+09 | 0.421233E+09 | 0.118783E+09 |
October | 0.332625E+09 | 0.190002E+09 | 0.142623E+09 | 0.367595E+09 | 0.173171E+09 |
November | 0.230534E+09 | 0.130144E+09 | 0.100390E+09 | 0.224426E+09 | 0.211048E+09 |
December | 0.222292E+09 | 0.115046E+09 | 0.107246E+09 | 0.172899E+09 | 0.315126E+09 |
Annual Sum or Average | 0.341545E+10 | 0.150625E+10 | 0.190920E+10 | 0.371630E+10 | 0.215458E+10 |
Minimum of Months | 0.222292E+09 | 53497697.44 | 0.100390E+09 | 0.172899E+09 | 59245193.46 |
Maximum of Months | 0.370465E+09 | 0.208162E+09 | 0.202043E+09 | 0.421233E+09 | 0.320155E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.180307E+09 | 0.274248E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.183407E+09 | 0.240188E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.310777E+09 | 0.192724E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.263015E+09 | 0.142954E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.256311E+09 | 0.102275E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.263458E+09 | 68946276.62 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308136E+09 | 49217851.82 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339172E+09 | 64895235.35 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.351593E+09 | 99765137.47 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.305976E+09 | 0.146250E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.186184E+09 | 0.179690E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.142373E+09 | 0.270331E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.309071E+10 | 0.183149E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.142373E+09 | 49217851.82 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.351593E+09 | 0.274248E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.180307E+09 | 0.274248E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.183407E+09 | 0.240188E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.310777E+09 | 0.192724E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.263015E+09 | 0.142954E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.256311E+09 | 0.102275E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.263458E+09 | 68946276.62 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308136E+09 | 49217851.82 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339172E+09 | 64895235.35 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.351593E+09 | 99765137.47 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.305976E+09 | 0.146250E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.186184E+09 | 0.179690E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.142373E+09 | 0.270331E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.309071E+10 | 0.183149E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.142373E+09 | 49217851.82 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.351593E+09 | 0.274248E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265837E+09 | 0.155177E+09 | 0.110660E+09 | 0.217365E+09 | 0.322310E+09 |
February | 0.274146E+09 | 0.132191E+09 | 0.141955E+09 | 0.221716E+09 | 0.281957E+09 |
March | 0.370465E+09 | 0.208162E+09 | 0.162303E+09 | 0.373735E+09 | 0.227026E+09 |
April | 0.296906E+09 | 0.118645E+09 | 0.178262E+09 | 0.315964E+09 | 0.168422E+09 |
May | 0.268480E+09 | 77977940.64 | 0.190502E+09 | 0.307486E+09 | 0.120800E+09 |
June | 0.252461E+09 | 53497697.44 | 0.198963E+09 | 0.315578E+09 | 81638370.31 |
July | 0.266312E+09 | 64616063.69 | 0.201696E+09 | 0.368529E+09 | 58389608.83 |
August | 0.298979E+09 | 96936603.89 | 0.202043E+09 | 0.405709E+09 | 76919433.07 |
September | 0.336410E+09 | 0.163857E+09 | 0.172553E+09 | 0.420928E+09 | 0.118105E+09 |
October | 0.332625E+09 | 0.190002E+09 | 0.142623E+09 | 0.367134E+09 | 0.172633E+09 |
November | 0.230534E+09 | 0.130144E+09 | 0.100390E+09 | 0.223827E+09 | 0.211511E+09 |
December | 0.222292E+09 | 0.115046E+09 | 0.107246E+09 | 0.171898E+09 | 0.317320E+09 |
Annual Sum or Average | 0.341545E+10 | 0.150625E+10 | 0.190920E+10 | 0.370987E+10 | 0.215703E+10 |
Minimum of Months | 0.222292E+09 | 53497697.44 | 0.100390E+09 | 0.171898E+09 | 58389608.83 |
Maximum of Months | 0.370465E+09 | 0.208162E+09 | 0.202043E+09 | 0.420928E+09 | 0.322310E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.180432E+09 | 0.273550E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.183546E+09 | 0.239627E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.311094E+09 | 0.191851E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.263476E+09 | 0.141929E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.257242E+09 | 0.100866E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.263834E+09 | 68450650.02 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308371E+09 | 48902578.35 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339368E+09 | 64562681.35 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.351853E+09 | 99243000.86 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.306447E+09 | 0.145245E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.186416E+09 | 0.178854E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.142487E+09 | 0.269599E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.309457E+10 | 0.182268E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.142487E+09 | 48902578.35 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.351853E+09 | 0.273550E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.180432E+09 | 0.273550E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.183546E+09 | 0.239627E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.311094E+09 | 0.191851E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.263476E+09 | 0.141929E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.257242E+09 | 0.100866E+09 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.263834E+09 | 68450650.02 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308371E+09 | 48902578.35 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339368E+09 | 64562681.35 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.351853E+09 | 99243000.86 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.306447E+09 | 0.145245E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.186416E+09 | 0.178854E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.142487E+09 | 0.269599E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.309457E+10 | 0.182268E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.142487E+09 | 48902578.35 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.351853E+09 | 0.273550E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265837E+09 | 0.155177E+09 | 0.110660E+09 | 0.217518E+09 | 0.321483E+09 |
February | 0.274146E+09 | 0.132191E+09 | 0.141955E+09 | 0.221885E+09 | 0.281294E+09 |
March | 0.370465E+09 | 0.208162E+09 | 0.162303E+09 | 0.374118E+09 | 0.225994E+09 |
April | 0.296906E+09 | 0.118645E+09 | 0.178262E+09 | 0.316519E+09 | 0.167216E+09 |
May | 0.268480E+09 | 77977940.64 | 0.190502E+09 | 0.308594E+09 | 0.119142E+09 |
June | 0.252461E+09 | 53497697.44 | 0.198963E+09 | 0.316027E+09 | 81054696.58 |
July | 0.266312E+09 | 64616063.69 | 0.201696E+09 | 0.368811E+09 | 58018018.85 |
August | 0.298979E+09 | 96936603.89 | 0.202043E+09 | 0.405945E+09 | 76527009.52 |
September | 0.336410E+09 | 0.163857E+09 | 0.172553E+09 | 0.421239E+09 | 0.117489E+09 |
October | 0.332625E+09 | 0.190002E+09 | 0.142623E+09 | 0.367697E+09 | 0.171449E+09 |
November | 0.230534E+09 | 0.130144E+09 | 0.100390E+09 | 0.224109E+09 | 0.210525E+09 |
December | 0.222292E+09 | 0.115046E+09 | 0.107246E+09 | 0.172036E+09 | 0.316455E+09 |
Annual Sum or Average | 0.341545E+10 | 0.150625E+10 | 0.190920E+10 | 0.371450E+10 | 0.214665E+10 |
Minimum of Months | 0.222292E+09 | 53497697.44 | 0.100390E+09 | 0.172036E+09 | 58018018.85 |
Maximum of Months | 0.370465E+09 | 0.208162E+09 | 0.202043E+09 | 0.421239E+09 | 0.321483E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.180964E+09 | 0.270120E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.184140E+09 | 0.236805E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.312144E+09 | 0.188447E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.264704E+09 | 0.138669E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.259394E+09 | 97368951.30 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.264780E+09 | 67040953.65 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308773E+09 | 48166810.20 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339697E+09 | 63805392.34 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.352481E+09 | 97802382.77 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.307498E+09 | 0.142672E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.187087E+09 | 0.176060E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.142944E+09 | 0.266224E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.310461E+10 | 0.179318E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.142944E+09 | 48166810.20 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.352481E+09 | 0.270120E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.180964E+09 | 0.270120E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.184140E+09 | 0.236805E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.312144E+09 | 0.188447E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.264704E+09 | 0.138669E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.259394E+09 | 97368951.30 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.264780E+09 | 67040953.65 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.308773E+09 | 48166810.20 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.339697E+09 | 63805392.34 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.352481E+09 | 97802382.77 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.307498E+09 | 0.142672E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.187087E+09 | 0.176060E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.142944E+09 | 0.266224E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.310461E+10 | 0.179318E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.142944E+09 | 48166810.20 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.352481E+09 | 0.270120E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265837E+09 | 0.155177E+09 | 0.110660E+09 | 0.218170E+09 | 0.317439E+09 |
February | 0.274146E+09 | 0.132191E+09 | 0.141955E+09 | 0.222606E+09 | 0.277967E+09 |
March | 0.370465E+09 | 0.208162E+09 | 0.162303E+09 | 0.375384E+09 | 0.221981E+09 |
April | 0.296906E+09 | 0.118645E+09 | 0.178262E+09 | 0.317994E+09 | 0.163377E+09 |
May | 0.268480E+09 | 77977940.64 | 0.190502E+09 | 0.311158E+09 | 0.115035E+09 |
June | 0.252461E+09 | 53497697.44 | 0.198963E+09 | 0.317158E+09 | 79400405.80 |
July | 0.266312E+09 | 64616063.69 | 0.201696E+09 | 0.369290E+09 | 57157001.81 |
August | 0.298979E+09 | 96936603.89 | 0.202043E+09 | 0.406339E+09 | 75639616.14 |
September | 0.336410E+09 | 0.163857E+09 | 0.172553E+09 | 0.421989E+09 | 0.115793E+09 |
October | 0.332625E+09 | 0.190002E+09 | 0.142623E+09 | 0.368955E+09 | 0.168425E+09 |
November | 0.230534E+09 | 0.130144E+09 | 0.100390E+09 | 0.224921E+09 | 0.207234E+09 |
December | 0.222292E+09 | 0.115046E+09 | 0.107246E+09 | 0.172597E+09 | 0.312477E+09 |
Annual Sum or Average | 0.341545E+10 | 0.150625E+10 | 0.190920E+10 | 0.372656E+10 | 0.211192E+10 |
Minimum of Months | 0.222292E+09 | 53497697.44 | 0.100390E+09 | 0.172597E+09 | 57157001.81 |
Maximum of Months | 0.370465E+09 | 0.208162E+09 | 0.202043E+09 | 0.421989E+09 | 0.317439E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.183273E+09 | 0.255294E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.186690E+09 | 0.224182E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.315861E+09 | 0.174562E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.268209E+09 | 0.126474E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.264248E+09 | 87083234.03 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.267345E+09 | 61785665.08 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.309532E+09 | 45324975.35 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.340275E+09 | 60807947.89 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.353991E+09 | 92621016.27 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.309922E+09 | 0.134457E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.189187E+09 | 0.165571E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.144858E+09 | 0.251724E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.313339E+10 | 0.167989E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.144858E+09 | 45324975.35 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.353991E+09 | 0.255294E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222349E+09 | 0.129792E+09 | 92557189.18 | 0.183273E+09 | 0.255294E+09 |
February | 0.229299E+09 | 0.110566E+09 | 0.118733E+09 | 0.186690E+09 | 0.224182E+09 |
March | 0.309861E+09 | 0.174109E+09 | 0.135752E+09 | 0.315861E+09 | 0.174562E+09 |
April | 0.248336E+09 | 99235703.68 | 0.149100E+09 | 0.268209E+09 | 0.126474E+09 |
May | 0.224560E+09 | 65221588.97 | 0.159338E+09 | 0.264248E+09 | 87083234.03 |
June | 0.211161E+09 | 44746050.03 | 0.166415E+09 | 0.267345E+09 | 61785665.08 |
July | 0.222746E+09 | 54045571.25 | 0.168701E+09 | 0.309532E+09 | 45324975.35 |
August | 0.250070E+09 | 81078819.00 | 0.168991E+09 | 0.340275E+09 | 60807947.89 |
September | 0.281377E+09 | 0.137052E+09 | 0.144326E+09 | 0.353991E+09 | 92621016.27 |
October | 0.278211E+09 | 0.158919E+09 | 0.119291E+09 | 0.309922E+09 | 0.134457E+09 |
November | 0.192821E+09 | 0.108854E+09 | 83967293.25 | 0.189187E+09 | 0.165571E+09 |
December | 0.185928E+09 | 96225999.83 | 89701650.75 | 0.144858E+09 | 0.251724E+09 |
Annual Sum or Average | 0.285672E+10 | 0.125985E+10 | 0.159687E+10 | 0.313339E+10 | 0.167989E+10 |
Minimum of Months | 0.185928E+09 | 44746050.03 | 83967293.25 | 0.144858E+09 | 45324975.35 |
Maximum of Months | 0.309861E+09 | 0.174109E+09 | 0.168991E+09 | 0.353991E+09 | 0.255294E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265837E+09 | 0.155177E+09 | 0.110660E+09 | 0.221008E+09 | 0.299965E+09 |
February | 0.274146E+09 | 0.132191E+09 | 0.141955E+09 | 0.225720E+09 | 0.263090E+09 |
March | 0.370465E+09 | 0.208162E+09 | 0.162303E+09 | 0.379881E+09 | 0.205629E+09 |
April | 0.296906E+09 | 0.118645E+09 | 0.178262E+09 | 0.322218E+09 | 0.149044E+09 |
May | 0.268480E+09 | 77977940.64 | 0.190502E+09 | 0.316952E+09 | 0.102955E+09 |
June | 0.252461E+09 | 53497697.44 | 0.198963E+09 | 0.320212E+09 | 73226703.01 |
July | 0.266312E+09 | 64616063.69 | 0.201696E+09 | 0.370193E+09 | 53822627.20 |
August | 0.298979E+09 | 96936603.89 | 0.202043E+09 | 0.407029E+09 | 72121195.72 |
September | 0.336410E+09 | 0.163857E+09 | 0.172553E+09 | 0.423792E+09 | 0.109700E+09 |
October | 0.332625E+09 | 0.190002E+09 | 0.142623E+09 | 0.371864E+09 | 0.158772E+09 |
November | 0.230534E+09 | 0.130144E+09 | 0.100390E+09 | 0.227467E+09 | 0.194903E+09 |
December | 0.222292E+09 | 0.115046E+09 | 0.107246E+09 | 0.174953E+09 | 0.295406E+09 |
Annual Sum or Average | 0.341545E+10 | 0.150625E+10 | 0.190920E+10 | 0.376129E+10 | 0.197863E+10 |
Minimum of Months | 0.222292E+09 | 53497697.44 | 0.100390E+09 | 0.174953E+09 | 53822627.20 |
Maximum of Months | 0.370465E+09 | 0.208162E+09 | 0.202043E+09 | 0.423792E+09 | 0.299965E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 433.59 | 667.42 | 531.66 | 310.34 | 221.31 | 0.00 | 0.00 |
February | 489.42 | 645.27 | 607.02 | 292.70 | 314.32 | 0.00 | 0.00 |
March | 745.80 | 467.83 | 740.91 | 416.31 | 324.60 | 0.00 | 0.00 |
April | 649.98 | 361.21 | 613.59 | 245.19 | 368.40 | 0.00 | 0.00 |
May | 609.77 | 253.76 | 536.94 | 155.95 | 380.99 | 0.00 | 0.00 |
June | 653.05 | 168.39 | 521.74 | 110.56 | 411.18 | 0.00 | 0.00 |
July | 739.63 | 113.79 | 532.61 | 129.23 | 403.38 | 0.00 | 0.00 |
August | 812.99 | 151.81 | 597.94 | 193.87 | 404.07 | 0.00 | 0.00 |
September | 869.91 | 245.97 | 695.23 | 338.63 | 356.60 | 0.00 | 0.00 |
October | 729.26 | 359.90 | 665.23 | 379.99 | 285.24 | 0.00 | 0.00 |
November | 459.27 | 453.75 | 476.42 | 268.96 | 207.47 | 0.00 | 0.00 |
December | 342.34 | 656.44 | 444.57 | 230.09 | 214.49 | 0.00 | 0.00 |
Annual Sum or Average | 628.73 | 377.39 | 580.14 | 255.85 | 324.29 | 0.00 | 0.00 |
Minimum of Months | 342.34 | 113.79 | 444.57 | 110.56 | 207.47 | 0.00 | 0.00 |
Maximum of Months | 869.91 | 667.42 | 740.91 | 416.31 | 411.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 213.03 | 351.07 | 265.83 | 155.17 | 110.66 | 0.00 | 0.00 |
February | 239.63 | 339.84 | 303.51 | 146.35 | 157.16 | 0.00 | 0.00 |
March | 367.31 | 248.98 | 370.45 | 208.16 | 162.30 | 0.00 | 0.00 |
April | 318.73 | 196.08 | 306.79 | 122.60 | 184.20 | 0.00 | 0.00 |
May | 298.87 | 136.16 | 268.47 | 77.98 | 190.50 | 0.00 | 0.00 |
June | 324.28 | 86.77 | 260.87 | 55.28 | 205.59 | 0.00 | 0.00 |
July | 368.84 | 58.05 | 266.30 | 64.61 | 201.69 | 0.00 | 0.00 |
August | 405.58 | 77.25 | 298.97 | 96.93 | 202.04 | 0.00 | 0.00 |
September | 433.02 | 126.12 | 347.61 | 169.31 | 178.30 | 0.00 | 0.00 |
October | 360.00 | 191.60 | 332.61 | 190.00 | 142.62 | 0.00 | 0.00 |
November | 226.00 | 242.29 | 238.21 | 134.48 | 103.73 | 0.00 | 0.00 |
December | 168.00 | 345.81 | 222.29 | 115.04 | 107.24 | 0.00 | 0.00 |
Annual Sum or Average | 310.69 | 199.26 | 290.07 | 127.92 | 162.15 | 0.00 | 0.00 |
Minimum of Months | 168.00 | 58.05 | 222.29 | 55.28 | 103.73 | 0.00 | 0.00 |
Maximum of Months | 433.02 | 351.07 | 370.45 | 208.16 | 205.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 213.26 | 341.14 | 265.28 | 154.85 | 110.43 | 0.00 | 0.00 |
February | 239.87 | 330.21 | 302.89 | 146.05 | 156.84 | 0.00 | 0.00 |
March | 367.36 | 241.59 | 369.69 | 207.73 | 161.96 | 0.00 | 0.00 |
April | 319.46 | 189.30 | 306.16 | 122.34 | 183.82 | 0.00 | 0.00 |
May | 299.11 | 135.09 | 267.92 | 77.82 | 190.11 | 0.00 | 0.00 |
June | 322.93 | 90.53 | 260.33 | 55.17 | 205.17 | 0.00 | 0.00 |
July | 366.55 | 63.36 | 265.76 | 64.48 | 201.28 | 0.00 | 0.00 |
August | 403.85 | 82.37 | 298.36 | 96.73 | 201.62 | 0.00 | 0.00 |
September | 432.02 | 129.16 | 346.90 | 168.97 | 177.93 | 0.00 | 0.00 |
October | 360.67 | 186.58 | 331.93 | 189.61 | 142.33 | 0.00 | 0.00 |
November | 226.70 | 233.80 | 237.72 | 134.20 | 103.52 | 0.00 | 0.00 |
December | 168.27 | 336.04 | 221.83 | 114.81 | 107.02 | 0.00 | 0.00 |
Annual Sum or Average | 310.41 | 195.89 | 289.48 | 127.66 | 161.81 | 0.00 | 0.00 |
Minimum of Months | 168.27 | 63.36 | 221.83 | 55.17 | 103.52 | 0.00 | 0.00 |
Maximum of Months | 432.02 | 341.14 | 369.69 | 207.73 | 205.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 213.72 | 337.26 | 265.28 | 154.85 | 110.43 | 0.00 | 0.00 |
February | 240.44 | 326.64 | 302.89 | 146.05 | 156.84 | 0.00 | 0.00 |
March | 368.05 | 238.65 | 369.69 | 207.73 | 161.96 | 0.00 | 0.00 |
April | 320.50 | 186.08 | 306.16 | 122.34 | 183.82 | 0.00 | 0.00 |
May | 300.15 | 132.82 | 267.92 | 77.82 | 190.11 | 0.00 | 0.00 |
June | 323.07 | 90.25 | 260.33 | 55.17 | 205.17 | 0.00 | 0.00 |
July | 366.51 | 63.51 | 265.76 | 64.48 | 201.28 | 0.00 | 0.00 |
August | 403.84 | 82.46 | 298.36 | 96.73 | 201.62 | 0.00 | 0.00 |
September | 432.20 | 128.59 | 346.90 | 168.97 | 177.93 | 0.00 | 0.00 |
October | 361.61 | 183.72 | 331.93 | 189.61 | 142.33 | 0.00 | 0.00 |
November | 227.40 | 230.32 | 237.72 | 134.20 | 103.52 | 0.00 | 0.00 |
December | 168.68 | 332.35 | 221.83 | 114.81 | 107.02 | 0.00 | 0.00 |
Annual Sum or Average | 310.92 | 193.69 | 289.48 | 127.66 | 161.81 | 0.00 | 0.00 |
Minimum of Months | 168.68 | 63.51 | 221.83 | 55.17 | 103.52 | 0.00 | 0.00 |
Maximum of Months | 432.20 | 337.26 | 369.69 | 207.73 | 205.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 214.33 | 333.94 | 265.28 | 154.85 | 110.43 | 0.00 | 0.00 |
February | 241.20 | 323.55 | 302.89 | 146.05 | 156.84 | 0.00 | 0.00 |
March | 369.01 | 235.98 | 369.69 | 207.73 | 161.96 | 0.00 | 0.00 |
April | 321.86 | 183.00 | 306.16 | 122.34 | 183.82 | 0.00 | 0.00 |
May | 301.94 | 129.67 | 267.92 | 77.82 | 190.11 | 0.00 | 0.00 |
June | 323.71 | 89.05 | 260.33 | 55.17 | 205.17 | 0.00 | 0.00 |
July | 366.98 | 62.55 | 265.76 | 64.48 | 201.28 | 0.00 | 0.00 |
August | 404.24 | 81.43 | 298.36 | 96.73 | 201.62 | 0.00 | 0.00 |
September | 432.74 | 127.16 | 346.90 | 168.97 | 177.93 | 0.00 | 0.00 |
October | 362.86 | 180.78 | 331.93 | 189.61 | 142.33 | 0.00 | 0.00 |
November | 228.20 | 227.38 | 237.72 | 134.20 | 103.52 | 0.00 | 0.00 |
December | 169.20 | 329.09 | 221.83 | 114.81 | 107.02 | 0.00 | 0.00 |
Annual Sum or Average | 311.76 | 191.27 | 289.48 | 127.66 | 161.81 | 0.00 | 0.00 |
Minimum of Months | 169.20 | 62.55 | 221.83 | 55.17 | 103.52 | 0.00 | 0.00 |
Maximum of Months | 432.74 | 333.94 | 369.69 | 207.73 | 205.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 433.93 | 645.61 | 530.57 | 309.71 | 220.86 | 0.00 | 0.00 |
February | 489.91 | 625.45 | 605.77 | 292.10 | 313.67 | 0.00 | 0.00 |
March | 745.85 | 456.03 | 739.39 | 415.46 | 323.93 | 0.00 | 0.00 |
April | 651.06 | 350.84 | 612.33 | 244.69 | 367.64 | 0.00 | 0.00 |
May | 612.20 | 245.11 | 535.84 | 155.63 | 380.21 | 0.00 | 0.00 |
June | 650.24 | 170.81 | 520.67 | 110.33 | 410.33 | 0.00 | 0.00 |
July | 735.11 | 118.81 | 531.52 | 128.96 | 402.55 | 0.00 | 0.00 |
August | 809.63 | 156.08 | 596.71 | 193.47 | 403.24 | 0.00 | 0.00 |
September | 868.14 | 246.45 | 693.80 | 337.93 | 355.87 | 0.00 | 0.00 |
October | 732.18 | 348.29 | 663.86 | 379.21 | 284.65 | 0.00 | 0.00 |
November | 461.37 | 439.36 | 475.45 | 268.40 | 207.04 | 0.00 | 0.00 |
December | 343.09 | 635.94 | 443.66 | 229.61 | 214.05 | 0.00 | 0.00 |
Annual Sum or Average | 628.53 | 368.54 | 578.95 | 255.32 | 323.63 | 0.00 | 0.00 |
Minimum of Months | 343.09 | 118.81 | 443.66 | 110.33 | 207.04 | 0.00 | 0.00 |
Maximum of Months | 868.14 | 645.61 | 739.39 | 415.46 | 410.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 215.79 | 325.12 | 265.28 | 154.85 | 110.43 | 0.00 | 0.00 |
February | 243.27 | 315.12 | 302.89 | 146.05 | 156.84 | 0.00 | 0.00 |
March | 371.60 | 228.67 | 369.69 | 207.73 | 161.96 | 0.00 | 0.00 |
April | 324.84 | 175.28 | 306.16 | 122.34 | 183.82 | 0.00 | 0.00 |
May | 306.19 | 121.47 | 267.92 | 77.82 | 190.11 | 0.00 | 0.00 |
June | 325.04 | 84.70 | 260.33 | 55.17 | 205.17 | 0.00 | 0.00 |
July | 367.68 | 58.55 | 265.76 | 64.48 | 201.28 | 0.00 | 0.00 |
August | 404.74 | 77.18 | 298.36 | 96.73 | 201.62 | 0.00 | 0.00 |
September | 433.69 | 122.54 | 346.90 | 168.97 | 177.93 | 0.00 | 0.00 |
October | 365.55 | 173.66 | 331.93 | 189.61 | 142.33 | 0.00 | 0.00 |
November | 230.01 | 220.25 | 237.72 | 134.20 | 103.52 | 0.00 | 0.00 |
December | 170.49 | 320.33 | 221.83 | 114.81 | 107.02 | 0.00 | 0.00 |
Annual Sum or Average | 313.65 | 184.55 | 289.48 | 127.66 | 161.81 | 0.00 | 0.00 |
Minimum of Months | 170.49 | 58.55 | 221.83 | 55.17 | 103.52 | 0.00 | 0.00 |
Maximum of Months | 433.69 | 325.12 | 369.69 | 207.73 | 205.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 215.94 | 324.29 | 265.28 | 154.85 | 110.43 | 0.00 | 0.00 |
February | 243.46 | 314.38 | 302.89 | 146.05 | 156.84 | 0.00 | 0.00 |
March | 371.98 | 227.63 | 369.69 | 207.73 | 161.96 | 0.00 | 0.00 |
April | 325.41 | 174.02 | 306.16 | 122.34 | 183.82 | 0.00 | 0.00 |
May | 307.30 | 119.80 | 267.92 | 77.82 | 190.11 | 0.00 | 0.00 |
June | 325.50 | 84.09 | 260.33 | 55.17 | 205.17 | 0.00 | 0.00 |
July | 367.96 | 58.18 | 265.76 | 64.48 | 201.28 | 0.00 | 0.00 |
August | 404.97 | 76.78 | 298.36 | 96.73 | 201.62 | 0.00 | 0.00 |
September | 434.01 | 121.90 | 346.90 | 168.97 | 177.93 | 0.00 | 0.00 |
October | 366.11 | 172.47 | 331.93 | 189.61 | 142.33 | 0.00 | 0.00 |
November | 230.30 | 219.22 | 237.72 | 134.20 | 103.52 | 0.00 | 0.00 |
December | 170.62 | 319.46 | 221.83 | 114.81 | 107.02 | 0.00 | 0.00 |
Annual Sum or Average | 314.04 | 183.66 | 289.48 | 127.66 | 161.81 | 0.00 | 0.00 |
Minimum of Months | 170.62 | 58.18 | 221.83 | 55.17 | 103.52 | 0.00 | 0.00 |
Maximum of Months | 434.01 | 324.29 | 369.69 | 207.73 | 205.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 216.58 | 320.22 | 265.28 | 154.85 | 110.43 | 0.00 | 0.00 |
February | 244.25 | 310.67 | 302.89 | 146.05 | 156.84 | 0.00 | 0.00 |
March | 373.23 | 223.59 | 369.69 | 207.73 | 161.96 | 0.00 | 0.00 |
April | 326.93 | 170.03 | 306.16 | 122.34 | 183.82 | 0.00 | 0.00 |
May | 309.87 | 115.66 | 267.92 | 77.82 | 190.11 | 0.00 | 0.00 |
June | 326.67 | 82.36 | 260.33 | 55.17 | 205.17 | 0.00 | 0.00 |
July | 368.44 | 57.31 | 265.76 | 64.48 | 201.28 | 0.00 | 0.00 |
August | 405.37 | 75.88 | 298.36 | 96.73 | 201.62 | 0.00 | 0.00 |
September | 434.78 | 120.14 | 346.90 | 168.97 | 177.93 | 0.00 | 0.00 |
October | 367.36 | 169.42 | 331.93 | 189.61 | 142.33 | 0.00 | 0.00 |
November | 231.13 | 215.80 | 237.72 | 134.20 | 103.52 | 0.00 | 0.00 |
December | 171.17 | 315.45 | 221.83 | 114.81 | 107.02 | 0.00 | 0.00 |
Annual Sum or Average | 315.06 | 180.69 | 289.48 | 127.66 | 161.81 | 0.00 | 0.00 |
Minimum of Months | 171.17 | 57.31 | 221.83 | 55.17 | 103.52 | 0.00 | 0.00 |
Maximum of Months | 434.78 | 320.22 | 369.69 | 207.73 | 205.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 219.37 | 302.62 | 265.28 | 154.85 | 110.43 | 0.00 | 0.00 |
February | 247.64 | 294.08 | 302.89 | 146.05 | 156.84 | 0.00 | 0.00 |
March | 377.69 | 207.12 | 369.69 | 207.73 | 161.96 | 0.00 | 0.00 |
April | 331.26 | 155.09 | 306.16 | 122.34 | 183.82 | 0.00 | 0.00 |
May | 315.65 | 103.46 | 267.92 | 77.82 | 190.11 | 0.00 | 0.00 |
June | 329.82 | 75.93 | 260.33 | 55.17 | 205.17 | 0.00 | 0.00 |
July | 369.35 | 53.94 | 265.76 | 64.48 | 201.28 | 0.00 | 0.00 |
August | 406.06 | 72.33 | 298.36 | 96.73 | 201.62 | 0.00 | 0.00 |
September | 436.64 | 113.79 | 346.90 | 168.97 | 177.93 | 0.00 | 0.00 |
October | 370.26 | 159.68 | 331.93 | 189.61 | 142.33 | 0.00 | 0.00 |
November | 233.73 | 202.95 | 237.72 | 134.20 | 103.52 | 0.00 | 0.00 |
December | 173.48 | 298.25 | 221.83 | 114.81 | 107.02 | 0.00 | 0.00 |
Annual Sum or Average | 317.99 | 169.28 | 289.48 | 127.66 | 161.81 | 0.00 | 0.00 |
Minimum of Months | 173.48 | 53.94 | 221.83 | 55.17 | 103.52 | 0.00 | 0.00 |
Maximum of Months | 436.64 | 302.62 | 369.69 | 207.73 | 205.17 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.116132E+10 | 0.178762E+10 | 0.142399E+10 | 0.831225E+09 | 0.592765E+09 | 0.00 | 0.00 |
February | 0.118400E+10 | 0.156103E+10 | 0.146850E+10 | 0.708098E+09 | 0.760402E+09 | 0.00 | 0.00 |
March | 0.199756E+10 | 0.125304E+10 | 0.198444E+10 | 0.111505E+10 | 0.869398E+09 | 0.00 | 0.00 |
April | 0.168476E+10 | 0.936261E+09 | 0.159042E+10 | 0.635536E+09 | 0.954882E+09 | 0.00 | 0.00 |
May | 0.163320E+10 | 0.679678E+09 | 0.143815E+10 | 0.417699E+09 | 0.102045E+10 | 0.00 | 0.00 |
June | 0.169270E+10 | 0.436470E+09 | 0.135234E+10 | 0.286567E+09 | 0.106577E+10 | 0.00 | 0.00 |
July | 0.198104E+10 | 0.304788E+09 | 0.142654E+10 | 0.346124E+09 | 0.108041E+10 | 0.00 | 0.00 |
August | 0.217751E+10 | 0.406610E+09 | 0.160152E+10 | 0.519254E+09 | 0.108227E+10 | 0.00 | 0.00 |
September | 0.225480E+10 | 0.637555E+09 | 0.180203E+10 | 0.877721E+09 | 0.924306E+09 | 0.00 | 0.00 |
October | 0.195325E+10 | 0.963964E+09 | 0.178175E+10 | 0.101777E+10 | 0.763979E+09 | 0.00 | 0.00 |
November | 0.119044E+10 | 0.117611E+10 | 0.123489E+10 | 0.697136E+09 | 0.537752E+09 | 0.00 | 0.00 |
December | 0.916936E+09 | 0.175820E+10 | 0.119074E+10 | 0.616261E+09 | 0.574477E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.198275E+11 | 0.119013E+11 | 0.182953E+11 | 0.806844E+10 | 0.102269E+11 | 0.00 | 0.00 |
Minimum of Months | 0.916936E+09 | 0.304788E+09 | 0.119074E+10 | 0.286567E+09 | 0.537752E+09 | 0.00 | 0.00 |
Maximum of Months | 0.225480E+10 | 0.178762E+10 | 0.198444E+10 | 0.111505E+10 | 0.108227E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.570591E+09 | 0.940294E+09 | 0.711995E+09 | 0.415612E+09 | 0.296382E+09 | 0.00 | 0.00 |
February | 0.579719E+09 | 0.822139E+09 | 0.734250E+09 | 0.354049E+09 | 0.380201E+09 | 0.00 | 0.00 |
March | 0.983798E+09 | 0.666865E+09 | 0.992222E+09 | 0.557523E+09 | 0.434699E+09 | 0.00 | 0.00 |
April | 0.826157E+09 | 0.508233E+09 | 0.795209E+09 | 0.317768E+09 | 0.477441E+09 | 0.00 | 0.00 |
May | 0.800505E+09 | 0.364698E+09 | 0.719075E+09 | 0.208850E+09 | 0.510225E+09 | 0.00 | 0.00 |
June | 0.840536E+09 | 0.224899E+09 | 0.676170E+09 | 0.143284E+09 | 0.532886E+09 | 0.00 | 0.00 |
July | 0.987900E+09 | 0.155488E+09 | 0.713268E+09 | 0.173062E+09 | 0.540206E+09 | 0.00 | 0.00 |
August | 0.108631E+10 | 0.206904E+09 | 0.800761E+09 | 0.259627E+09 | 0.541134E+09 | 0.00 | 0.00 |
September | 0.112240E+10 | 0.326898E+09 | 0.901013E+09 | 0.438860E+09 | 0.462153E+09 | 0.00 | 0.00 |
October | 0.964236E+09 | 0.513175E+09 | 0.890874E+09 | 0.508884E+09 | 0.381990E+09 | 0.00 | 0.00 |
November | 0.585798E+09 | 0.628028E+09 | 0.617444E+09 | 0.348568E+09 | 0.268876E+09 | 0.00 | 0.00 |
December | 0.449978E+09 | 0.926216E+09 | 0.595369E+09 | 0.308130E+09 | 0.287238E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.979793E+10 | 0.628384E+10 | 0.914765E+10 | 0.403422E+10 | 0.511343E+10 | 0.00 | 0.00 |
Minimum of Months | 0.449978E+09 | 0.155488E+09 | 0.595369E+09 | 0.143284E+09 | 0.268876E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112240E+10 | 0.940294E+09 | 0.992222E+09 | 0.557523E+09 | 0.541134E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.571191E+09 | 0.913712E+09 | 0.710534E+09 | 0.414760E+09 | 0.295774E+09 | 0.00 | 0.00 |
February | 0.580290E+09 | 0.798835E+09 | 0.732744E+09 | 0.353323E+09 | 0.379421E+09 | 0.00 | 0.00 |
March | 0.983941E+09 | 0.647076E+09 | 0.990187E+09 | 0.556380E+09 | 0.433807E+09 | 0.00 | 0.00 |
April | 0.828037E+09 | 0.490678E+09 | 0.793578E+09 | 0.317116E+09 | 0.476462E+09 | 0.00 | 0.00 |
May | 0.801143E+09 | 0.361824E+09 | 0.717599E+09 | 0.208421E+09 | 0.509178E+09 | 0.00 | 0.00 |
June | 0.837036E+09 | 0.234663E+09 | 0.674783E+09 | 0.142990E+09 | 0.531793E+09 | 0.00 | 0.00 |
July | 0.981758E+09 | 0.169693E+09 | 0.711805E+09 | 0.172707E+09 | 0.539098E+09 | 0.00 | 0.00 |
August | 0.108166E+10 | 0.220615E+09 | 0.799118E+09 | 0.259094E+09 | 0.540024E+09 | 0.00 | 0.00 |
September | 0.111981E+10 | 0.334795E+09 | 0.899165E+09 | 0.437960E+09 | 0.461205E+09 | 0.00 | 0.00 |
October | 0.966012E+09 | 0.499743E+09 | 0.889046E+09 | 0.507840E+09 | 0.381206E+09 | 0.00 | 0.00 |
November | 0.587605E+09 | 0.606015E+09 | 0.616177E+09 | 0.347853E+09 | 0.268325E+09 | 0.00 | 0.00 |
December | 0.450693E+09 | 0.900038E+09 | 0.594148E+09 | 0.307498E+09 | 0.286649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.978918E+10 | 0.617769E+10 | 0.912888E+10 | 0.402594E+10 | 0.510294E+10 | 0.00 | 0.00 |
Minimum of Months | 0.450693E+09 | 0.169693E+09 | 0.594148E+09 | 0.142990E+09 | 0.268325E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111981E+10 | 0.913712E+09 | 0.990187E+09 | 0.556380E+09 | 0.540024E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.572435E+09 | 0.903330E+09 | 0.710534E+09 | 0.414760E+09 | 0.295774E+09 | 0.00 | 0.00 |
February | 0.581677E+09 | 0.790201E+09 | 0.732744E+09 | 0.353323E+09 | 0.379421E+09 | 0.00 | 0.00 |
March | 0.985787E+09 | 0.639191E+09 | 0.990187E+09 | 0.556380E+09 | 0.433807E+09 | 0.00 | 0.00 |
April | 0.830732E+09 | 0.482332E+09 | 0.793578E+09 | 0.317116E+09 | 0.476462E+09 | 0.00 | 0.00 |
May | 0.803921E+09 | 0.355750E+09 | 0.717599E+09 | 0.208421E+09 | 0.509178E+09 | 0.00 | 0.00 |
June | 0.837396E+09 | 0.233938E+09 | 0.674783E+09 | 0.142990E+09 | 0.531793E+09 | 0.00 | 0.00 |
July | 0.981673E+09 | 0.170111E+09 | 0.711805E+09 | 0.172707E+09 | 0.539098E+09 | 0.00 | 0.00 |
August | 0.108164E+10 | 0.220854E+09 | 0.799118E+09 | 0.259094E+09 | 0.540024E+09 | 0.00 | 0.00 |
September | 0.112027E+10 | 0.333294E+09 | 0.899165E+09 | 0.437960E+09 | 0.461205E+09 | 0.00 | 0.00 |
October | 0.968531E+09 | 0.492066E+09 | 0.889046E+09 | 0.507840E+09 | 0.381206E+09 | 0.00 | 0.00 |
November | 0.589420E+09 | 0.596984E+09 | 0.616177E+09 | 0.347853E+09 | 0.268325E+09 | 0.00 | 0.00 |
December | 0.451781E+09 | 0.890170E+09 | 0.594148E+09 | 0.307498E+09 | 0.286649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.980526E+10 | 0.610822E+10 | 0.912888E+10 | 0.402594E+10 | 0.510294E+10 | 0.00 | 0.00 |
Minimum of Months | 0.451781E+09 | 0.170111E+09 | 0.594148E+09 | 0.142990E+09 | 0.268325E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112027E+10 | 0.903330E+09 | 0.990187E+09 | 0.556380E+09 | 0.540024E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.574054E+09 | 0.894427E+09 | 0.710534E+09 | 0.414760E+09 | 0.295774E+09 | 0.00 | 0.00 |
February | 0.583523E+09 | 0.782733E+09 | 0.732744E+09 | 0.353323E+09 | 0.379421E+09 | 0.00 | 0.00 |
March | 0.988344E+09 | 0.632045E+09 | 0.990187E+09 | 0.556380E+09 | 0.433807E+09 | 0.00 | 0.00 |
April | 0.834260E+09 | 0.474348E+09 | 0.793578E+09 | 0.317116E+09 | 0.476462E+09 | 0.00 | 0.00 |
May | 0.808720E+09 | 0.347299E+09 | 0.717599E+09 | 0.208421E+09 | 0.509178E+09 | 0.00 | 0.00 |
June | 0.839050E+09 | 0.230828E+09 | 0.674783E+09 | 0.142990E+09 | 0.531793E+09 | 0.00 | 0.00 |
July | 0.982910E+09 | 0.167530E+09 | 0.711805E+09 | 0.172707E+09 | 0.539098E+09 | 0.00 | 0.00 |
August | 0.108271E+10 | 0.218090E+09 | 0.799118E+09 | 0.259094E+09 | 0.540024E+09 | 0.00 | 0.00 |
September | 0.112167E+10 | 0.329606E+09 | 0.899165E+09 | 0.437960E+09 | 0.461205E+09 | 0.00 | 0.00 |
October | 0.971897E+09 | 0.484202E+09 | 0.889046E+09 | 0.507840E+09 | 0.381206E+09 | 0.00 | 0.00 |
November | 0.591484E+09 | 0.589380E+09 | 0.616177E+09 | 0.347853E+09 | 0.268325E+09 | 0.00 | 0.00 |
December | 0.453175E+09 | 0.881424E+09 | 0.594148E+09 | 0.307498E+09 | 0.286649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.983180E+10 | 0.603191E+10 | 0.912888E+10 | 0.402594E+10 | 0.510294E+10 | 0.00 | 0.00 |
Minimum of Months | 0.453175E+09 | 0.167530E+09 | 0.594148E+09 | 0.142990E+09 | 0.268325E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112167E+10 | 0.894427E+09 | 0.990187E+09 | 0.556380E+09 | 0.540024E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.116224E+10 | 0.172920E+10 | 0.142107E+10 | 0.829520E+09 | 0.591549E+09 | 0.00 | 0.00 |
February | 0.118519E+10 | 0.151310E+10 | 0.146549E+10 | 0.706645E+09 | 0.758842E+09 | 0.00 | 0.00 |
March | 0.199768E+10 | 0.122143E+10 | 0.198037E+10 | 0.111276E+10 | 0.867614E+09 | 0.00 | 0.00 |
April | 0.168755E+10 | 0.909382E+09 | 0.158716E+10 | 0.634232E+09 | 0.952924E+09 | 0.00 | 0.00 |
May | 0.163970E+10 | 0.656514E+09 | 0.143520E+10 | 0.416842E+09 | 0.101836E+10 | 0.00 | 0.00 |
June | 0.168543E+10 | 0.442740E+09 | 0.134957E+10 | 0.285980E+09 | 0.106359E+10 | 0.00 | 0.00 |
July | 0.196892E+10 | 0.318232E+09 | 0.142361E+10 | 0.345414E+09 | 0.107820E+10 | 0.00 | 0.00 |
August | 0.216851E+10 | 0.418045E+09 | 0.159824E+10 | 0.518188E+09 | 0.108005E+10 | 0.00 | 0.00 |
September | 0.225022E+10 | 0.638807E+09 | 0.179833E+10 | 0.875920E+09 | 0.922409E+09 | 0.00 | 0.00 |
October | 0.196106E+10 | 0.932873E+09 | 0.177809E+10 | 0.101568E+10 | 0.762412E+09 | 0.00 | 0.00 |
November | 0.119587E+10 | 0.113881E+10 | 0.123235E+10 | 0.695706E+09 | 0.536649E+09 | 0.00 | 0.00 |
December | 0.918941E+09 | 0.170330E+10 | 0.118830E+10 | 0.614997E+09 | 0.573298E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.198213E+11 | 0.116224E+11 | 0.182578E+11 | 0.805188E+10 | 0.102059E+11 | 0.00 | 0.00 |
Minimum of Months | 0.918941E+09 | 0.318232E+09 | 0.118830E+10 | 0.285980E+09 | 0.536649E+09 | 0.00 | 0.00 |
Maximum of Months | 0.225022E+10 | 0.172920E+10 | 0.198037E+10 | 0.111276E+10 | 0.108005E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.577972E+09 | 0.870800E+09 | 0.710534E+09 | 0.414760E+09 | 0.295774E+09 | 0.00 | 0.00 |
February | 0.588527E+09 | 0.762331E+09 | 0.732744E+09 | 0.353323E+09 | 0.379421E+09 | 0.00 | 0.00 |
March | 0.995287E+09 | 0.612471E+09 | 0.990187E+09 | 0.556380E+09 | 0.433807E+09 | 0.00 | 0.00 |
April | 0.841991E+09 | 0.454327E+09 | 0.793578E+09 | 0.317116E+09 | 0.476462E+09 | 0.00 | 0.00 |
May | 0.820108E+09 | 0.325349E+09 | 0.717599E+09 | 0.208421E+09 | 0.509178E+09 | 0.00 | 0.00 |
June | 0.842493E+09 | 0.219530E+09 | 0.674783E+09 | 0.142990E+09 | 0.531793E+09 | 0.00 | 0.00 |
July | 0.984800E+09 | 0.156825E+09 | 0.711805E+09 | 0.172707E+09 | 0.539098E+09 | 0.00 | 0.00 |
August | 0.108405E+10 | 0.206710E+09 | 0.799118E+09 | 0.259094E+09 | 0.540024E+09 | 0.00 | 0.00 |
September | 0.112411E+10 | 0.317634E+09 | 0.899165E+09 | 0.437960E+09 | 0.461205E+09 | 0.00 | 0.00 |
October | 0.979085E+09 | 0.465132E+09 | 0.889046E+09 | 0.507840E+09 | 0.381206E+09 | 0.00 | 0.00 |
November | 0.596186E+09 | 0.570883E+09 | 0.616177E+09 | 0.347853E+09 | 0.268325E+09 | 0.00 | 0.00 |
December | 0.456637E+09 | 0.857974E+09 | 0.594148E+09 | 0.307498E+09 | 0.286649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.989125E+10 | 0.581997E+10 | 0.912888E+10 | 0.402594E+10 | 0.510294E+10 | 0.00 | 0.00 |
Minimum of Months | 0.456637E+09 | 0.156825E+09 | 0.594148E+09 | 0.142990E+09 | 0.268325E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112411E+10 | 0.870800E+09 | 0.990187E+09 | 0.556380E+09 | 0.540024E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.578374E+09 | 0.868575E+09 | 0.710534E+09 | 0.414760E+09 | 0.295774E+09 | 0.00 | 0.00 |
February | 0.588974E+09 | 0.760545E+09 | 0.732744E+09 | 0.353323E+09 | 0.379421E+09 | 0.00 | 0.00 |
March | 0.996305E+09 | 0.609693E+09 | 0.990187E+09 | 0.556380E+09 | 0.433807E+09 | 0.00 | 0.00 |
April | 0.843466E+09 | 0.451069E+09 | 0.793578E+09 | 0.317116E+09 | 0.476462E+09 | 0.00 | 0.00 |
May | 0.823076E+09 | 0.320871E+09 | 0.717599E+09 | 0.208421E+09 | 0.509178E+09 | 0.00 | 0.00 |
June | 0.843694E+09 | 0.217956E+09 | 0.674783E+09 | 0.142990E+09 | 0.531793E+09 | 0.00 | 0.00 |
July | 0.985553E+09 | 0.155823E+09 | 0.711805E+09 | 0.172707E+09 | 0.539098E+09 | 0.00 | 0.00 |
August | 0.108468E+10 | 0.205652E+09 | 0.799118E+09 | 0.259094E+09 | 0.540024E+09 | 0.00 | 0.00 |
September | 0.112494E+10 | 0.315974E+09 | 0.899165E+09 | 0.437960E+09 | 0.461205E+09 | 0.00 | 0.00 |
October | 0.980590E+09 | 0.461937E+09 | 0.889046E+09 | 0.507840E+09 | 0.381206E+09 | 0.00 | 0.00 |
November | 0.596933E+09 | 0.568225E+09 | 0.616177E+09 | 0.347853E+09 | 0.268325E+09 | 0.00 | 0.00 |
December | 0.457001E+09 | 0.855645E+09 | 0.594148E+09 | 0.307498E+09 | 0.286649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.990359E+10 | 0.579196E+10 | 0.912888E+10 | 0.402594E+10 | 0.510294E+10 | 0.00 | 0.00 |
Minimum of Months | 0.457001E+09 | 0.155823E+09 | 0.594148E+09 | 0.142990E+09 | 0.268325E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112494E+10 | 0.868575E+09 | 0.990187E+09 | 0.556380E+09 | 0.540024E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.580087E+09 | 0.857668E+09 | 0.710534E+09 | 0.414760E+09 | 0.295774E+09 | 0.00 | 0.00 |
February | 0.590878E+09 | 0.751570E+09 | 0.732744E+09 | 0.353323E+09 | 0.379421E+09 | 0.00 | 0.00 |
March | 0.999672E+09 | 0.598873E+09 | 0.990187E+09 | 0.556380E+09 | 0.433807E+09 | 0.00 | 0.00 |
April | 0.847401E+09 | 0.440712E+09 | 0.793578E+09 | 0.317116E+09 | 0.476462E+09 | 0.00 | 0.00 |
May | 0.829945E+09 | 0.309771E+09 | 0.717599E+09 | 0.208421E+09 | 0.509178E+09 | 0.00 | 0.00 |
June | 0.846718E+09 | 0.213482E+09 | 0.674783E+09 | 0.142990E+09 | 0.531793E+09 | 0.00 | 0.00 |
July | 0.986835E+09 | 0.153490E+09 | 0.711805E+09 | 0.172707E+09 | 0.539098E+09 | 0.00 | 0.00 |
August | 0.108573E+10 | 0.203250E+09 | 0.799118E+09 | 0.259094E+09 | 0.540024E+09 | 0.00 | 0.00 |
September | 0.112695E+10 | 0.311397E+09 | 0.899165E+09 | 0.437960E+09 | 0.461205E+09 | 0.00 | 0.00 |
October | 0.983949E+09 | 0.453768E+09 | 0.889046E+09 | 0.507840E+09 | 0.381206E+09 | 0.00 | 0.00 |
November | 0.599090E+09 | 0.559348E+09 | 0.616177E+09 | 0.347853E+09 | 0.268325E+09 | 0.00 | 0.00 |
December | 0.458472E+09 | 0.844913E+09 | 0.594148E+09 | 0.307498E+09 | 0.286649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.993573E+10 | 0.569824E+10 | 0.912888E+10 | 0.402594E+10 | 0.510294E+10 | 0.00 | 0.00 |
Minimum of Months | 0.458472E+09 | 0.153490E+09 | 0.594148E+09 | 0.142990E+09 | 0.268325E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112695E+10 | 0.857668E+09 | 0.990187E+09 | 0.556380E+09 | 0.540024E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.587551E+09 | 0.810550E+09 | 0.710534E+09 | 0.414760E+09 | 0.295774E+09 | 0.00 | 0.00 |
February | 0.599096E+09 | 0.711450E+09 | 0.732744E+09 | 0.353323E+09 | 0.379421E+09 | 0.00 | 0.00 |
March | 0.101160E+10 | 0.554751E+09 | 0.990187E+09 | 0.556380E+09 | 0.433807E+09 | 0.00 | 0.00 |
April | 0.858635E+09 | 0.401991E+09 | 0.793578E+09 | 0.317116E+09 | 0.476462E+09 | 0.00 | 0.00 |
May | 0.845446E+09 | 0.277121E+09 | 0.717599E+09 | 0.208421E+09 | 0.509178E+09 | 0.00 | 0.00 |
June | 0.854902E+09 | 0.196798E+09 | 0.674783E+09 | 0.142990E+09 | 0.531793E+09 | 0.00 | 0.00 |
July | 0.989256E+09 | 0.144472E+09 | 0.711805E+09 | 0.172707E+09 | 0.539098E+09 | 0.00 | 0.00 |
August | 0.108758E+10 | 0.193737E+09 | 0.799118E+09 | 0.259094E+09 | 0.540024E+09 | 0.00 | 0.00 |
September | 0.113177E+10 | 0.294941E+09 | 0.899165E+09 | 0.437960E+09 | 0.461205E+09 | 0.00 | 0.00 |
October | 0.991707E+09 | 0.427685E+09 | 0.889046E+09 | 0.507840E+09 | 0.381206E+09 | 0.00 | 0.00 |
November | 0.605836E+09 | 0.526040E+09 | 0.616177E+09 | 0.347853E+09 | 0.268325E+09 | 0.00 | 0.00 |
December | 0.464659E+09 | 0.798844E+09 | 0.594148E+09 | 0.307498E+09 | 0.286649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100280E+11 | 0.533838E+10 | 0.912888E+10 | 0.402594E+10 | 0.510294E+10 | 0.00 | 0.00 |
Minimum of Months | 0.464659E+09 | 0.144472E+09 | 0.594148E+09 | 0.142990E+09 | 0.268325E+09 | 0.00 | 0.00 |
Maximum of Months | 0.113177E+10 | 0.810550E+09 | 0.990187E+09 | 0.556380E+09 | 0.540024E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.379006E+09 | -253693370.1 | 0.00 | 0.00 | 744.00 | 0.00 | -125312938.0 | 58.99 | 0.00 | 0.00 |
February | 0.347237E+09 | -233690658.5 | 0.00 | 0.00 | 672.00 | 0.00 | -113546190.2 | 59.00 | 0.00 | 0.00 |
March | 0.382838E+09 | -259389071.6 | 0.00 | 0.00 | 744.00 | 0.00 | -123449405.3 | 58.99 | 0.00 | 0.00 |
April | 0.355886E+09 | -237979713.8 | 0.00 | 0.00 | 720.00 | 0.00 | -117906484.6 | 58.99 | 0.00 | 0.00 |
May | 0.348474E+09 | -232230213.3 | 0.00 | 0.00 | 744.00 | 0.00 | -116243972.1 | 58.99 | 0.00 | 0.00 |
June | 0.322528E+09 | -213013046.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109514533.4 | 58.99 | 0.00 | 0.00 |
July | 0.317427E+09 | -205145362.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112281304.4 | 58.99 | 0.00 | 0.00 |
August | 0.317815E+09 | -205439960.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112374787.0 | 58.99 | 0.00 | 0.00 |
September | 0.309696E+09 | -200159966.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109536130.8 | 58.99 | 0.00 | 0.00 |
October | 0.334050E+09 | -215136030.6 | 0.00 | 0.00 | 744.00 | 0.00 | -118914452.9 | 59.00 | 0.00 | 0.00 |
November | 0.339650E+09 | -221152375.9 | 0.00 | 0.00 | 720.00 | 0.00 | -118498104.5 | 58.99 | 0.00 | 0.00 |
December | 0.368528E+09 | -243519301.7 | 0.00 | 0.00 | 744.00 | 0.00 | -125008555.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.412314E+10 | -0.272055E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140259E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.309696E+09 | -259389071.6 | 0.00 | 0.00 | 672.00 | 0.00 | -125312938.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.382838E+09 | -200159966.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109514533.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.376957E+09 | -253676085.3 | 0.00 | 0.00 | 744.00 | 0.00 | -123280414.9 | 59.00 | 0.00 | 0.00 |
February | 0.345329E+09 | -233695984.7 | 0.00 | 0.00 | 672.00 | 0.00 | -111632958.2 | 58.99 | 0.00 | 0.00 |
March | 0.380411E+09 | -259387770.6 | 0.00 | 0.00 | 744.00 | 0.00 | -121023054.3 | 59.00 | 0.00 | 0.00 |
April | 0.352913E+09 | -237982213.1 | 0.00 | 0.00 | 720.00 | 0.00 | -114931022.0 | 58.99 | 0.00 | 0.00 |
May | 0.346391E+09 | -232231822.2 | 0.00 | 0.00 | 744.00 | 0.00 | -114159157.1 | 58.99 | 0.00 | 0.00 |
June | 0.322062E+09 | -213014293.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109048179.0 | 58.99 | 0.00 | 0.00 |
July | 0.317301E+09 | -205136955.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112163731.5 | 58.99 | 0.00 | 0.00 |
August | 0.317626E+09 | -205443443.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112182232.7 | 58.99 | 0.00 | 0.00 |
September | 0.309168E+09 | -200156538.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109011563.5 | 58.99 | 0.00 | 0.00 |
October | 0.331592E+09 | -215144912.2 | 0.00 | 0.00 | 744.00 | 0.00 | -116447279.0 | 58.99 | 0.00 | 0.00 |
November | 0.337051E+09 | -221149098.5 | 0.00 | 0.00 | 720.00 | 0.00 | -115901765.3 | 58.99 | 0.00 | 0.00 |
December | 0.366371E+09 | -243522742.2 | 0.00 | 0.00 | 744.00 | 0.00 | -122848588.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.410317E+10 | -0.272054E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138263E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.309168E+09 | -259387770.6 | 0.00 | 0.00 | 672.00 | 0.00 | -123280414.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.380411E+09 | -200156538.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109011563.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.348261E+09 | -223085748.4 | 0.00 | 0.00 | 744.00 | 0.00 | -125174952.3 | 58.99 | 0.00 | 0.00 |
February | 0.319007E+09 | -205667922.2 | 0.00 | 0.00 | 672.00 | 0.00 | -113338653.6 | 58.99 | 0.00 | 0.00 |
March | 0.354122E+09 | -231508051.3 | 0.00 | 0.00 | 744.00 | 0.00 | -122614054.4 | 58.99 | 0.00 | 0.00 |
April | 0.325856E+09 | -209298254.2 | 0.00 | 0.00 | 720.00 | 0.00 | -116558149.4 | 58.99 | 0.00 | 0.00 |
May | 0.320442E+09 | -205979697.0 | 0.00 | 0.00 | 744.00 | 0.00 | -114462076.9 | 58.99 | 0.00 | 0.00 |
June | 0.297676E+09 | -189708985.0 | 0.00 | 0.00 | 720.00 | 0.00 | -107966672.6 | 58.99 | 0.00 | 0.00 |
July | 0.289745E+09 | -179349536.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110395145.1 | 58.98 | 0.00 | 0.00 |
August | 0.294217E+09 | -183492587.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110724527.7 | 58.99 | 0.00 | 0.00 |
September | 0.284166E+09 | -175920933.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108245326.7 | 58.99 | 0.00 | 0.00 |
October | 0.306907E+09 | -189213410.7 | 0.00 | 0.00 | 744.00 | 0.00 | -117693919.6 | 58.99 | 0.00 | 0.00 |
November | 0.312999E+09 | -195263971.0 | 0.00 | 0.00 | 720.00 | 0.00 | -117735126.5 | 58.99 | 0.00 | 0.00 |
December | 0.337323E+09 | -212553108.8 | 0.00 | 0.00 | 744.00 | 0.00 | -124769832.9 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.379072E+10 | -0.240104E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138968E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284166E+09 | -231508051.3 | 0.00 | 0.00 | 672.00 | 0.00 | -125174952.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.354122E+09 | -175920933.6 | 0.00 | 0.00 | 744.00 | 0.00 | -107966672.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.348733E+09 | -223080983.9 | 0.00 | 0.00 | 744.00 | 0.00 | -125651850.1 | 59.00 | 0.00 | 0.00 |
February | 0.319406E+09 | -205666365.9 | 0.00 | 0.00 | 672.00 | 0.00 | -113739926.6 | 58.99 | 0.00 | 0.00 |
March | 0.354538E+09 | -231510624.0 | 0.00 | 0.00 | 744.00 | 0.00 | -123027520.0 | 58.99 | 0.00 | 0.00 |
April | 0.326379E+09 | -209308374.4 | 0.00 | 0.00 | 720.00 | 0.00 | -117070396.2 | 58.99 | 0.00 | 0.00 |
May | 0.320879E+09 | -205982756.2 | 0.00 | 0.00 | 744.00 | 0.00 | -114895762.2 | 58.99 | 0.00 | 0.00 |
June | 0.297716E+09 | -189702672.8 | 0.00 | 0.00 | 720.00 | 0.00 | -108013012.6 | 58.99 | 0.00 | 0.00 |
July | 0.289725E+09 | -179332470.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110392281.3 | 58.99 | 0.00 | 0.00 |
August | 0.294202E+09 | -183478781.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110722897.1 | 59.00 | 0.00 | 0.00 |
September | 0.284249E+09 | -175945352.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108303624.4 | 58.98 | 0.00 | 0.00 |
October | 0.307403E+09 | -189215998.8 | 0.00 | 0.00 | 744.00 | 0.00 | -118186731.0 | 58.99 | 0.00 | 0.00 |
November | 0.313471E+09 | -195263352.3 | 0.00 | 0.00 | 720.00 | 0.00 | -118207204.0 | 58.99 | 0.00 | 0.00 |
December | 0.337764E+09 | -212572668.3 | 0.00 | 0.00 | 744.00 | 0.00 | -125191608.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.379446E+10 | -0.240106E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139340E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284249E+09 | -231510624.0 | 0.00 | 0.00 | 672.00 | 0.00 | -125651850.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.354538E+09 | -175945352.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108013012.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.338323E+09 | -210840234.3 | 0.00 | 0.00 | 744.00 | 0.00 | -127483007.0 | 59.00 | 0.00 | 0.00 |
February | 0.309897E+09 | -194482890.5 | 0.00 | 0.00 | 672.00 | 0.00 | -115414600.7 | 59.00 | 0.00 | 0.00 |
March | 0.343710E+09 | -219069610.3 | 0.00 | 0.00 | 744.00 | 0.00 | -124640582.8 | 58.98 | 0.00 | 0.00 |
April | 0.316986E+09 | -198055304.0 | 0.00 | 0.00 | 720.00 | 0.00 | -118930885.3 | 59.00 | 0.00 | 0.00 |
May | 0.311915E+09 | -194801568.8 | 0.00 | 0.00 | 744.00 | 0.00 | -117113391.1 | 58.99 | 0.00 | 0.00 |
June | 0.288394E+09 | -179500398.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108893994.0 | 58.99 | 0.00 | 0.00 |
July | 0.280756E+09 | -169565169.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111191026.9 | 59.01 | 0.00 | 0.00 |
August | 0.285076E+09 | -173639548.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111436320.6 | 58.99 | 0.00 | 0.00 |
September | 0.275696E+09 | -166489468.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109206665.8 | 58.99 | 0.00 | 0.00 |
October | 0.298819E+09 | -178821287.4 | 0.00 | 0.00 | 744.00 | 0.00 | -119997970.8 | 59.00 | 0.00 | 0.00 |
November | 0.304087E+09 | -184416396.1 | 0.00 | 0.00 | 720.00 | 0.00 | -119670464.7 | 58.99 | 0.00 | 0.00 |
December | 0.327964E+09 | -201019986.5 | 0.00 | 0.00 | 744.00 | 0.00 | -126944096.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.368162E+10 | -0.227070E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141092E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.275696E+09 | -219069610.3 | 0.00 | 0.00 | 672.00 | 0.00 | -127483007.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.343710E+09 | -166489468.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108893994.0 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.338236E+09 | -210833772.2 | 0.00 | 0.00 | 744.00 | 0.00 | -127402006.5 | 59.00 | 0.00 | 0.00 |
February | 0.309806E+09 | -194489837.0 | 0.00 | 0.00 | 672.00 | 0.00 | -115316237.7 | 58.99 | 0.00 | 0.00 |
March | 0.343723E+09 | -219067044.9 | 0.00 | 0.00 | 744.00 | 0.00 | -124655571.6 | 58.99 | 0.00 | 0.00 |
April | 0.317092E+09 | -198065365.5 | 0.00 | 0.00 | 720.00 | 0.00 | -119026872.4 | 58.99 | 0.00 | 0.00 |
May | 0.312173E+09 | -194795085.9 | 0.00 | 0.00 | 744.00 | 0.00 | -117377618.0 | 58.99 | 0.00 | 0.00 |
June | 0.288506E+09 | -179477952.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109028378.3 | 59.00 | 0.00 | 0.00 |
July | 0.280869E+09 | -169609527.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111259065.8 | 58.99 | 0.00 | 0.00 |
August | 0.285205E+09 | -173618213.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111586628.6 | 59.00 | 0.00 | 0.00 |
September | 0.275796E+09 | -166474254.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109321289.7 | 58.99 | 0.00 | 0.00 |
October | 0.298946E+09 | -178868673.6 | 0.00 | 0.00 | 744.00 | 0.00 | -120077814.8 | 58.98 | 0.00 | 0.00 |
November | 0.304140E+09 | -184423733.6 | 0.00 | 0.00 | 720.00 | 0.00 | -119716759.3 | 58.99 | 0.00 | 0.00 |
December | 0.327887E+09 | -201017227.6 | 0.00 | 0.00 | 744.00 | 0.00 | -126869584.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.368238E+10 | -0.227074E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141164E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.275796E+09 | -219067044.9 | 0.00 | 0.00 | 672.00 | 0.00 | -127402006.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.343723E+09 | -166474254.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109028378.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.338330E+09 | -210840638.1 | 0.00 | 0.00 | 744.00 | 0.00 | -127489025.9 | 59.00 | 0.00 | 0.00 |
February | 0.309892E+09 | -194483034.4 | 0.00 | 0.00 | 672.00 | 0.00 | -115408970.5 | 59.00 | 0.00 | 0.00 |
March | 0.343863E+09 | -219067695.9 | 0.00 | 0.00 | 744.00 | 0.00 | -124795532.7 | 58.99 | 0.00 | 0.00 |
April | 0.317295E+09 | -198045454.0 | 0.00 | 0.00 | 720.00 | 0.00 | -119249103.1 | 59.00 | 0.00 | 0.00 |
May | 0.312529E+09 | -194798398.2 | 0.00 | 0.00 | 744.00 | 0.00 | -117730708.3 | 58.99 | 0.00 | 0.00 |
June | 0.288611E+09 | -179516112.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109095032.1 | 58.99 | 0.00 | 0.00 |
July | 0.280952E+09 | -169568978.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111382801.7 | 59.00 | 0.00 | 0.00 |
August | 0.285261E+09 | -173635980.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111625405.3 | 58.99 | 0.00 | 0.00 |
September | 0.275904E+09 | -166477694.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109426790.2 | 58.99 | 0.00 | 0.00 |
October | 0.299166E+09 | -178870728.3 | 0.00 | 0.00 | 744.00 | 0.00 | -120294983.2 | 58.98 | 0.00 | 0.00 |
November | 0.304268E+09 | -184424214.6 | 0.00 | 0.00 | 720.00 | 0.00 | -119843482.0 | 58.99 | 0.00 | 0.00 |
December | 0.327989E+09 | -201014173.1 | 0.00 | 0.00 | 744.00 | 0.00 | -126974640.9 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.368406E+10 | -0.227074E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141332E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.275904E+09 | -219067695.9 | 0.00 | 0.00 | 672.00 | 0.00 | -127489025.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.343863E+09 | -166477694.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109095032.1 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 255.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 262.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 339.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 371.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 332.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 430.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 289.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 314.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 258.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3928.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.240286E+11 | 63847.93 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227583E+11 | 63847.93 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133146E+11 | 63847.93 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.483267E+10 | 63847.93 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82999092.30 | 21667.03 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182813E+10 | 63847.93 | 17-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.724585E+10 | 63847.93 | 03-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221171E+11 | 63847.93 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.962083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.240286E+11 | 63847.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.819354E+10 | 33675.94 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.774008E+10 | 33675.94 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.394525E+10 | 33675.94 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100590E+10 | 33675.94 | 05-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 818991.94 | 950.93 | 01-MAY-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.218210E+09 | 12601.01 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.179913E+10 | 33675.94 | 24-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.743192E+10 | 33675.94 | 02-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.303348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.819354E+10 | 33675.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.945893E+10 | 35992.16 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.886263E+10 | 35992.16 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.489460E+10 | 35992.16 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152051E+10 | 35992.16 | 16-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12034425.65 | 3380.83 | 01-MAY-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.509758E+09 | 18077.08 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.256913E+10 | 35992.16 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.861806E+10 | 35992.16 | 03-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.364456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.945893E+10 | 35992.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.974837E+10 | 35817.68 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.910955E+10 | 35817.68 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511546E+10 | 35817.68 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168891E+10 | 35817.68 | 16-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22565803.56 | 5053.82 | 01-MAY-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.616364E+09 | 24110.33 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.280498E+10 | 35817.68 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.888699E+10 | 35817.68 | 03-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.379932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.974837E+10 | 35817.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.101786E+11 | 35815.28 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.949630E+10 | 35815.28 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.546164E+10 | 35815.28 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.193857E+10 | 35815.28 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 42263282.82 | 4644.09 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.765921E+09 | 28830.73 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.312210E+10 | 35815.28 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.929392E+10 | 35815.28 | 02-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.402993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.101786E+11 | 35815.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.200087E+11 | 60072.26 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185825E+11 | 60072.26 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110943E+11 | 60072.26 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.437340E+10 | 60072.26 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170995E+09 | 60072.26 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 112144.99 | 186.91 | 30-SEP-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.203704E+10 | 60072.26 | 09-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.697390E+10 | 60072.26 | 03-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183745E+11 | 60072.26 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.816156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.200087E+11 | 60072.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104134E+11 | 31635.26 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.967825E+10 | 31635.26 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.579416E+10 | 31635.26 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.230697E+10 | 31635.26 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101156E+09 | 31635.26 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 109888.72 | 183.15 | 30-SEP-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106784E+10 | 31635.26 | 09-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.362817E+10 | 31635.26 | 03-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.956587E+10 | 31635.26 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.425559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104134E+11 | 31635.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105082E+11 | 31505.27 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.975758E+10 | 31505.27 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.590046E+10 | 31505.27 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.240598E+10 | 31505.27 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124097E+09 | 31505.27 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 498837.04 | 660.21 | 30-SEP-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112941E+10 | 31505.27 | 09-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.372200E+10 | 31505.27 | 03-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.965890E+10 | 31505.27 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.432071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105082E+11 | 31505.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109775E+11 | 31336.48 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101766E+11 | 31336.48 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.632706E+10 | 31336.48 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.274470E+10 | 31336.48 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.203408E+09 | 31336.48 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2316337.66 | 1631.98 | 30-SEP-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131901E+10 | 31336.48 | 09-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.404776E+10 | 31336.48 | 03-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100986E+11 | 31336.48 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.458969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109775E+11 | 31336.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137565E+11 | 32375.69 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129464E+11 | 32375.69 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.826605E+10 | 32375.69 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.391679E+10 | 32375.69 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.536736E+09 | 32375.69 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1510517.49 | 1678.89 | 14-JUN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 22896972.42 | 16358.51 | 30-SEP-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.191825E+10 | 32375.69 | 08-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.520975E+10 | 32375.69 | 02-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125950E+11 | 32375.69 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.591698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137565E+11 | 32375.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.414220E+09 | 0.352793E+09 | 10321.59 | 15-MAR-14:00 | 9575.19 | 0.00 |
April | 0.00 | 0.00 | 9078712.51 | 8080589.72 | 2140.57 | 08-APR-13:00 | 1946.35 | 0.00 |
May | 0.00 | 0.00 | 0.137505E+10 | 0.122822E+10 | 13242.15 | 14-MAY-15:00 | 10580.98 | 0.00 |
June | 0.00 | 0.00 | 0.109417E+11 | 0.796279E+10 | 47651.47 | 18-JUN-07:02 | 24040.83 | 0.00 |
July | 0.00 | 0.00 | 0.226993E+11 | 0.152232E+11 | 48700.86 | 21-JUL-07:01 | 25177.55 | 0.00 |
August | 0.00 | 0.00 | 0.178479E+11 | 0.133464E+11 | 47637.15 | 14-AUG-07:02 | 28092.55 | 0.00 |
September | 0.00 | 0.00 | 0.720017E+10 | 0.505303E+10 | 46478.84 | 16-SEP-07:03 | 25408.19 | 0.00 |
October | 0.00 | 0.00 | 0.344458E+09 | 0.295888E+09 | 8024.18 | 11-OCT-16:10 | 6942.44 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.608319E+11 | 0.434704E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.226993E+11 | 0.152232E+11 | 48700.86 | 28092.55 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.297240E+09 | 0.254056E+09 | 22565.06 | 15-MAR-20:01 | 18941.27 | 0.00 |
April | 0.00 | 0.00 | 24808776.17 | 22597293.08 | 3491.47 | 30-APR-17:20 | 2839.66 | 0.00 |
May | 0.00 | 0.00 | 0.124765E+10 | 0.111980E+10 | 23191.84 | 14-MAY-17:45 | 14986.55 | 0.00 |
June | 0.00 | 0.00 | 0.720047E+10 | 0.534540E+10 | 25161.68 | 18-JUN-07:02 | 13524.76 | 0.00 |
July | 0.00 | 0.00 | 0.137676E+11 | 0.944818E+10 | 25067.56 | 17-JUL-07:02 | 13892.64 | 0.00 |
August | 0.00 | 0.00 | 0.109234E+11 | 0.825141E+10 | 24975.71 | 15-AUG-07:02 | 13860.33 | 0.00 |
September | 0.00 | 0.00 | 0.483762E+10 | 0.345091E+10 | 24926.93 | 15-SEP-20:03 | 12025.77 | 0.00 |
October | 0.00 | 0.00 | 0.333693E+09 | 0.283416E+09 | 22556.02 | 22-OCT-18:54 | 16688.36 | 0.00 |
November | 0.00 | 0.00 | 2805434.49 | 2588465.32 | 1482.46 | 27-NOV-21:20 | 1323.81 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.386353E+11 | 0.281784E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.137676E+11 | 0.944818E+10 | 25161.68 | 18941.27 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.220207E+09 | 0.197401E+09 | 5458.86 | 15-MAR-14:00 | 5328.38 | 0.00 |
April | 0.00 | 0.00 | 8763342.26 | 8216814.09 | 1596.68 | 08-APR-13:00 | 1536.32 | 0.00 |
May | 0.00 | 0.00 | 0.712931E+09 | 0.656959E+09 | 6606.91 | 10-MAY-14:00 | 5635.45 | 0.00 |
June | 0.00 | 0.00 | 0.453246E+10 | 0.347595E+10 | 24925.17 | 18-JUN-07:02 | 12978.16 | 0.00 |
July | 0.00 | 0.00 | 0.908168E+10 | 0.642305E+10 | 25424.25 | 21-JUL-06:01 | 14273.71 | 0.00 |
August | 0.00 | 0.00 | 0.733473E+10 | 0.581554E+10 | 25174.41 | 14-AUG-06:02 | 11693.78 | 0.00 |
September | 0.00 | 0.00 | 0.302990E+10 | 0.224608E+10 | 24348.01 | 16-SEP-06:03 | 13378.89 | 0.00 |
October | 0.00 | 0.00 | 0.144616E+09 | 0.133476E+09 | 3930.87 | 11-OCT-15:00 | 3679.47 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.250653E+11 | 0.189567E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.908168E+10 | 0.642305E+10 | 25424.25 | 14273.71 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.206283E+09 | 0.185107E+09 | 5250.87 | 15-MAR-14:00 | 5124.03 | 0.00 |
April | 0.00 | 0.00 | 7135148.42 | 6695886.47 | 1413.42 | 08-APR-13:00 | 1359.60 | 0.00 |
May | 0.00 | 0.00 | 0.676006E+09 | 0.623441E+09 | 6367.09 | 14-MAY-14:50 | 5298.21 | 0.00 |
June | 0.00 | 0.00 | 0.450726E+10 | 0.345395E+10 | 24769.90 | 18-JUN-07:02 | 12890.79 | 0.00 |
July | 0.00 | 0.00 | 0.909136E+10 | 0.642843E+10 | 25272.47 | 21-JUL-06:01 | 14223.63 | 0.00 |
August | 0.00 | 0.00 | 0.734118E+10 | 0.581955E+10 | 25019.60 | 14-AUG-06:02 | 11631.51 | 0.00 |
September | 0.00 | 0.00 | 0.299738E+10 | 0.222048E+10 | 24196.60 | 16-SEP-06:03 | 13293.60 | 0.00 |
October | 0.00 | 0.00 | 0.124045E+09 | 0.114868E+09 | 3659.36 | 11-OCT-15:00 | 3424.54 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.249507E+11 | 0.188525E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.909136E+10 | 0.642843E+10 | 25272.47 | 14223.63 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.186632E+09 | 0.167798E+09 | 4943.06 | 15-MAR-14:00 | 4825.11 | 0.00 |
April | 0.00 | 0.00 | 4248092.96 | 4000073.28 | 1051.69 | 08-APR-13:00 | 1012.20 | 0.00 |
May | 0.00 | 0.00 | 0.599018E+09 | 0.552670E+09 | 5974.69 | 14-MAY-15:00 | 5005.25 | 0.00 |
June | 0.00 | 0.00 | 0.430954E+10 | 0.329975E+10 | 24804.64 | 18-JUN-07:02 | 12862.25 | 0.00 |
July | 0.00 | 0.00 | 0.882016E+10 | 0.623484E+10 | 25297.00 | 21-JUL-06:01 | 14075.23 | 0.00 |
August | 0.00 | 0.00 | 0.711029E+10 | 0.564096E+10 | 25055.82 | 14-AUG-06:02 | 11611.04 | 0.00 |
September | 0.00 | 0.00 | 0.282418E+10 | 0.208935E+10 | 24233.84 | 16-SEP-06:03 | 13267.40 | 0.00 |
October | 0.00 | 0.00 | 97730093.82 | 91077043.23 | 3281.41 | 11-OCT-15:00 | 3072.95 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.239518E+11 | 0.180805E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.882016E+10 | 0.623484E+10 | 25297.00 | 14075.23 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.300908E+09 | 0.252811E+09 | 8923.35 | 15-MAR-14:10 | 8127.55 | 0.00 |
April | 0.00 | 0.00 | 5024661.94 | 4404656.42 | 1078.51 | 08-APR-13:30 | 948.88 | 0.00 |
May | 0.00 | 0.00 | 0.953625E+09 | 0.848593E+09 | 11330.95 | 14-MAY-15:00 | 8828.83 | 0.00 |
June | 0.00 | 0.00 | 0.767489E+10 | 0.557759E+10 | 45562.96 | 18-JUN-08:62 | 25250.45 | 0.00 |
July | 0.00 | 0.00 | 0.159133E+11 | 0.107364E+11 | 46084.00 | 16-JUL-08:62 | 24415.64 | 0.00 |
August | 0.00 | 0.00 | 0.128856E+11 | 0.976141E+10 | 46156.35 | 14-AUG-07:02 | 24512.29 | 0.00 |
September | 0.00 | 0.00 | 0.498073E+10 | 0.351550E+10 | 44232.21 | 16-SEP-07:03 | 24258.61 | 0.00 |
October | 0.00 | 0.00 | 0.143414E+09 | 0.125634E+09 | 6009.90 | 11-OCT-15:00 | 5261.57 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.428575E+11 | 0.308223E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.159133E+11 | 0.107364E+11 | 46156.35 | 25250.45 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.149854E+09 | 0.126281E+09 | 4556.42 | 15-MAR-14:10 | 4154.87 | 0.00 |
April | 0.00 | 0.00 | 1255470.38 | 1104339.02 | 319.22 | 08-APR-13:30 | 281.32 | 0.00 |
May | 0.00 | 0.00 | 0.460163E+09 | 0.409840E+09 | 5764.96 | 14-MAY-15:00 | 4491.43 | 0.00 |
June | 0.00 | 0.00 | 0.389553E+10 | 0.283608E+10 | 23782.47 | 18-JUN-08:62 | 13146.33 | 0.00 |
July | 0.00 | 0.00 | 0.814365E+10 | 0.550703E+10 | 24057.44 | 16-JUL-08:62 | 12706.97 | 0.00 |
August | 0.00 | 0.00 | 0.659328E+10 | 0.500582E+10 | 24099.57 | 14-AUG-07:02 | 12774.45 | 0.00 |
September | 0.00 | 0.00 | 0.252069E+10 | 0.177996E+10 | 23086.34 | 17-SEP-08:62 | 12707.92 | 0.00 |
October | 0.00 | 0.00 | 68378068.79 | 60083772.36 | 3018.97 | 11-OCT-15:00 | 2647.60 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.218328E+11 | 0.157262E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.814365E+10 | 0.550703E+10 | 24099.57 | 13146.33 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.144524E+09 | 0.121741E+09 | 4452.47 | 15-MAR-14:10 | 4057.16 | 0.00 |
April | 0.00 | 0.00 | 674958.23 | 594832.76 | 199.08 | 08-APR-13:20 | 176.65 | 0.00 |
May | 0.00 | 0.00 | 0.426781E+09 | 0.379530E+09 | 5617.23 | 14-MAY-15:00 | 4367.86 | 0.00 |
June | 0.00 | 0.00 | 0.381408E+10 | 0.277282E+10 | 23673.04 | 18-JUN-08:62 | 13020.04 | 0.00 |
July | 0.00 | 0.00 | 0.804216E+10 | 0.543388E+10 | 23950.08 | 16-JUL-08:62 | 12601.59 | 0.00 |
August | 0.00 | 0.00 | 0.650981E+10 | 0.494082E+10 | 23990.97 | 14-AUG-07:02 | 12668.90 | 0.00 |
September | 0.00 | 0.00 | 0.246340E+10 | 0.173728E+10 | 22985.93 | 17-SEP-08:62 | 12637.94 | 0.00 |
October | 0.00 | 0.00 | 63612207.63 | 55876542.35 | 2892.48 | 11-OCT-15:00 | 2535.12 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.214650E+11 | 0.154425E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.804216E+10 | 0.543388E+10 | 23990.97 | 13020.04 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.128882E+09 | 0.108672E+09 | 4178.15 | 15-MAR-14:10 | 3801.93 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.355824E+09 | 0.315218E+09 | 5260.96 | 14-MAY-15:00 | 4073.43 | 0.00 |
June | 0.00 | 0.00 | 0.361602E+10 | 0.262157E+10 | 23511.59 | 18-JUN-08:62 | 12734.05 | 0.00 |
July | 0.00 | 0.00 | 0.783200E+10 | 0.528762E+10 | 23796.08 | 16-JUL-08:62 | 12378.66 | 0.00 |
August | 0.00 | 0.00 | 0.634000E+10 | 0.481375E+10 | 23834.91 | 14-AUG-07:02 | 12445.66 | 0.00 |
September | 0.00 | 0.00 | 0.232692E+10 | 0.163672E+10 | 22850.27 | 17-SEP-08:62 | 12532.88 | 0.00 |
October | 0.00 | 0.00 | 54895282.50 | 48212675.16 | 2655.50 | 11-OCT-15:00 | 2325.89 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.206545E+11 | 0.148318E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.783200E+10 | 0.528762E+10 | 23834.91 | 12734.05 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.106821E+09 | 90710097.98 | 3830.38 | 15-MAR-14:10 | 3499.73 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.259586E+09 | 0.228900E+09 | 4712.30 | 14-MAY-15:00 | 3639.15 | 0.00 |
June | 0.00 | 0.00 | 0.340361E+10 | 0.247576E+10 | 17325.49 | 18-JUN-08:62 | 8777.89 | 0.00 |
July | 0.00 | 0.00 | 0.777971E+10 | 0.530027E+10 | 25158.83 | 21-JUL-07:01 | 11702.28 | 0.00 |
August | 0.00 | 0.00 | 0.633500E+10 | 0.486316E+10 | 24902.94 | 14-AUG-07:02 | 12155.13 | 0.00 |
September | 0.00 | 0.00 | 0.216865E+10 | 0.153237E+10 | 23799.75 | 17-SEP-08:62 | 12847.05 | 0.00 |
October | 0.00 | 0.00 | 49499372.18 | 43889664.62 | 2506.57 | 11-OCT-15:00 | 2210.70 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.201029E+11 | 0.145351E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.777971E+10 | 0.530027E+10 | 25158.83 | 12847.05 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.209072E+10 | 0.45 | 2193.57 | 01-JAN-08:61 | 0.90 |
February | 0.191330E+10 | 0.45 | 2193.57 | 01-FEB-08:61 | 0.90 |
March | 0.187449E+10 | 0.42 | 2193.57 | 01-MAR-08:61 | 0.90 |
April | 0.164140E+10 | 0.39 | 2193.57 | 01-APR-07:01 | 0.90 |
May | 0.159372E+10 | 0.37 | 1324.07 | 01-MAY-07:01 | 0.70 |
June | 0.155002E+10 | 0.37 | 2193.57 | 18-JUN-07:02 | 0.88 |
July | 0.160749E+10 | 0.37 | 2193.57 | 15-JUL-07:02 | 0.89 |
August | 0.160131E+10 | 0.37 | 2193.57 | 06-AUG-07:02 | 0.89 |
September | 0.154530E+10 | 0.37 | 2193.57 | 14-SEP-07:03 | 0.89 |
October | 0.162969E+10 | 0.37 | 2193.57 | 17-OCT-07:01 | 0.90 |
November | 0.168780E+10 | 0.39 | 2193.57 | 03-NOV-07:01 | 0.90 |
December | 0.205687E+10 | 0.44 | 2193.57 | 01-DEC-08:61 | 0.90 |
Annual Sum or Average | 0.207921E+11 | 0.40 | |||
Minimum of Months | 0.154530E+10 | 0.37 | 1324.07 | 0.70 | |
Maximum of Months | 0.209072E+10 | 0.45 | 2193.57 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.845465E+09 | 0.34 | 1226.41 | 01-JAN-08:61 | 0.93 |
February | 0.772346E+09 | 0.35 | 1226.41 | 01-FEB-08:61 | 0.93 |
March | 0.778748E+09 | 0.33 | 1226.41 | 01-MAR-08:61 | 0.93 |
April | 0.712894E+09 | 0.35 | 1226.41 | 05-APR-07:01 | 0.93 |
May | 0.823974E+09 | 0.38 | 511.34 | 01-MAY-08:30 | 0.58 |
June | 0.794340E+09 | 0.37 | 1226.41 | 12-JUN-07:03 | 0.92 |
July | 0.797927E+09 | 0.36 | 1226.41 | 02-JUL-07:03 | 0.92 |
August | 0.805326E+09 | 0.37 | 1226.41 | 06-AUG-07:02 | 0.92 |
September | 0.814987E+09 | 0.37 | 1226.41 | 14-SEP-07:03 | 0.92 |
October | 0.756903E+09 | 0.36 | 765.90 | 30-OCT-07:01 | 0.74 |
November | 0.706370E+09 | 0.33 | 1226.41 | 24-NOV-08:61 | 0.93 |
December | 0.825130E+09 | 0.33 | 1226.41 | 02-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.943441E+10 | 0.35 | |||
Minimum of Months | 0.706370E+09 | 0.33 | 511.34 | 0.58 | |
Maximum of Months | 0.845465E+09 | 0.38 | 1226.41 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.984734E+09 | 0.36 | 1336.93 | 01-JAN-08:61 | 0.93 |
February | 0.898287E+09 | 0.36 | 1336.93 | 01-FEB-07:01 | 0.93 |
March | 0.898410E+09 | 0.34 | 1336.93 | 01-MAR-07:01 | 0.93 |
April | 0.784708E+09 | 0.31 | 1336.93 | 16-APR-07:01 | 0.93 |
May | 0.781891E+09 | 0.31 | 610.12 | 01-MAY-07:20 | 0.61 |
June | 0.764029E+09 | 0.31 | 1336.93 | 12-JUN-06:03 | 0.92 |
July | 0.778640E+09 | 0.30 | 1336.93 | 02-JUL-07:03 | 0.92 |
August | 0.792409E+09 | 0.31 | 1336.93 | 06-AUG-07:02 | 0.92 |
September | 0.751343E+09 | 0.30 | 1336.93 | 14-SEP-06:02 | 0.92 |
October | 0.785283E+09 | 0.31 | 937.66 | 30-OCT-06:02 | 0.79 |
November | 0.808078E+09 | 0.32 | 1336.93 | 24-NOV-07:01 | 0.93 |
December | 0.962143E+09 | 0.35 | 1336.93 | 03-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.998996E+10 | 0.32 | |||
Minimum of Months | 0.751343E+09 | 0.30 | 610.12 | 0.61 | |
Maximum of Months | 0.984734E+09 | 0.36 | 1336.93 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.985810E+09 | 0.36 | 1328.26 | 01-JAN-08:61 | 0.93 |
February | 0.898914E+09 | 0.36 | 1328.26 | 01-FEB-07:01 | 0.93 |
March | 0.898028E+09 | 0.34 | 1328.26 | 01-MAR-07:01 | 0.93 |
April | 0.783531E+09 | 0.31 | 1328.26 | 16-APR-07:01 | 0.93 |
May | 0.777058E+09 | 0.31 | 643.75 | 01-MAY-07:03 | 0.63 |
June | 0.759119E+09 | 0.31 | 1328.26 | 12-JUN-06:03 | 0.92 |
July | 0.774073E+09 | 0.30 | 1328.26 | 02-JUL-07:03 | 0.92 |
August | 0.787460E+09 | 0.31 | 1328.26 | 06-AUG-07:02 | 0.92 |
September | 0.746475E+09 | 0.30 | 1328.26 | 14-SEP-06:02 | 0.92 |
October | 0.782619E+09 | 0.31 | 1067.77 | 30-OCT-06:02 | 0.84 |
November | 0.808364E+09 | 0.32 | 1328.26 | 24-NOV-07:01 | 0.93 |
December | 0.962819E+09 | 0.35 | 1328.26 | 03-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.996427E+10 | 0.32 | |||
Minimum of Months | 0.746475E+09 | 0.30 | 643.75 | 0.63 | |
Maximum of Months | 0.985810E+09 | 0.36 | 1328.26 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.995309E+09 | 0.36 | 1328.14 | 01-JAN-08:61 | 0.93 |
February | 0.907452E+09 | 0.36 | 1328.14 | 01-FEB-07:01 | 0.93 |
March | 0.905657E+09 | 0.34 | 1328.14 | 01-MAR-07:01 | 0.93 |
April | 0.789019E+09 | 0.32 | 1328.14 | 03-APR-06:02 | 0.93 |
May | 0.777427E+09 | 0.31 | 634.59 | 01-MAY-06:05 | 0.63 |
June | 0.758715E+09 | 0.31 | 1328.14 | 18-JUN-07:02 | 0.91 |
July | 0.772511E+09 | 0.30 | 1328.14 | 02-JUL-07:03 | 0.92 |
August | 0.786684E+09 | 0.31 | 1328.14 | 06-AUG-07:02 | 0.92 |
September | 0.746333E+09 | 0.30 | 1328.14 | 14-SEP-06:02 | 0.92 |
October | 0.785878E+09 | 0.31 | 1172.74 | 30-OCT-06:02 | 0.88 |
November | 0.815352E+09 | 0.32 | 1328.14 | 24-NOV-07:01 | 0.93 |
December | 0.971800E+09 | 0.35 | 1328.14 | 02-DEC-07:02 | 0.93 |
Annual Sum or Average | 0.100121E+11 | 0.32 | |||
Minimum of Months | 0.746333E+09 | 0.30 | 634.59 | 0.63 | |
Maximum of Months | 0.995309E+09 | 0.36 | 1328.14 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.151823E+10 | 0.33 | 2068.19 | 01-JAN-09:01 | 0.90 |
February | 0.138491E+10 | 0.34 | 2068.19 | 01-FEB-08:61 | 0.90 |
March | 0.135791E+10 | 0.31 | 2068.19 | 01-MAR-08:61 | 0.90 |
April | 0.116249E+10 | 0.29 | 2068.19 | 01-APR-07:01 | 0.90 |
May | 0.112035E+10 | 0.27 | 2068.19 | 01-MAY-07:01 | 0.89 |
June | 0.109243E+10 | 0.28 | 2068.19 | 18-JUN-08:62 | 0.88 |
July | 0.111453E+10 | 0.27 | 2068.19 | 15-JUL-07:02 | 0.89 |
August | 0.113359E+10 | 0.28 | 2068.19 | 06-AUG-08:62 | 0.89 |
September | 0.107276E+10 | 0.27 | 2068.19 | 14-SEP-07:03 | 0.89 |
October | 0.114699E+10 | 0.28 | 2068.19 | 09-OCT-08:61 | 0.90 |
November | 0.121621E+10 | 0.29 | 2068.19 | 03-NOV-07:01 | 0.90 |
December | 0.147852E+10 | 0.33 | 2068.19 | 01-DEC-08:61 | 0.90 |
Annual Sum or Average | 0.147989E+11 | 0.29 | |||
Minimum of Months | 0.107276E+10 | 0.27 | 2068.19 | 0.88 | |
Maximum of Months | 0.151823E+10 | 0.34 | 2068.19 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.819922E+09 | 0.34 | 1120.51 | 01-JAN-09:01 | 0.93 |
February | 0.747986E+09 | 0.35 | 1120.51 | 01-FEB-08:61 | 0.93 |
March | 0.734664E+09 | 0.32 | 1120.51 | 01-MAR-08:61 | 0.93 |
April | 0.629898E+09 | 0.30 | 1120.51 | 01-APR-07:01 | 0.93 |
May | 0.607223E+09 | 0.28 | 1120.51 | 01-MAY-07:01 | 0.93 |
June | 0.591626E+09 | 0.28 | 1120.51 | 18-JUN-08:62 | 0.91 |
July | 0.602833E+09 | 0.28 | 1120.51 | 15-JUL-07:02 | 0.92 |
August | 0.613707E+09 | 0.29 | 1120.51 | 06-AUG-08:62 | 0.92 |
September | 0.581153E+09 | 0.28 | 1120.51 | 17-SEP-08:62 | 0.92 |
October | 0.621313E+09 | 0.29 | 1120.51 | 09-OCT-08:61 | 0.93 |
November | 0.657975E+09 | 0.30 | 1120.51 | 03-NOV-07:01 | 0.93 |
December | 0.798684E+09 | 0.34 | 1120.51 | 01-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.800698E+10 | 0.30 | |||
Minimum of Months | 0.581153E+09 | 0.28 | 1120.51 | 0.91 | |
Maximum of Months | 0.819922E+09 | 0.35 | 1120.51 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.818116E+09 | 0.34 | 1114.05 | 01-JAN-09:01 | 0.93 |
February | 0.746205E+09 | 0.35 | 1114.05 | 01-FEB-08:61 | 0.93 |
March | 0.733190E+09 | 0.32 | 1114.05 | 01-MAR-08:61 | 0.93 |
April | 0.628570E+09 | 0.30 | 1114.05 | 01-APR-07:01 | 0.93 |
May | 0.604220E+09 | 0.28 | 1114.05 | 01-MAY-07:01 | 0.93 |
June | 0.588129E+09 | 0.28 | 1114.05 | 18-JUN-08:62 | 0.91 |
July | 0.599137E+09 | 0.28 | 1114.05 | 15-JUL-07:02 | 0.92 |
August | 0.610049E+09 | 0.29 | 1114.05 | 06-AUG-08:62 | 0.92 |
September | 0.577789E+09 | 0.28 | 1114.05 | 17-SEP-08:62 | 0.92 |
October | 0.619132E+09 | 0.29 | 1114.05 | 09-OCT-08:61 | 0.93 |
November | 0.656491E+09 | 0.31 | 1114.05 | 03-NOV-07:01 | 0.93 |
December | 0.796889E+09 | 0.34 | 1114.05 | 01-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.797792E+10 | 0.30 | |||
Minimum of Months | 0.577789E+09 | 0.28 | 1114.05 | 0.91 | |
Maximum of Months | 0.818116E+09 | 0.35 | 1114.05 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.823750E+09 | 0.35 | 1106.56 | 01-JAN-09:01 | 0.93 |
February | 0.751447E+09 | 0.35 | 1106.56 | 01-FEB-08:61 | 0.93 |
March | 0.737968E+09 | 0.33 | 1106.56 | 01-MAR-08:61 | 0.93 |
April | 0.631792E+09 | 0.30 | 1106.56 | 01-APR-07:01 | 0.93 |
May | 0.601851E+09 | 0.28 | 1106.56 | 01-MAY-07:01 | 0.93 |
June | 0.583942E+09 | 0.28 | 1106.56 | 18-JUN-08:62 | 0.91 |
July | 0.594600E+09 | 0.28 | 1106.56 | 15-JUL-07:02 | 0.92 |
August | 0.605640E+09 | 0.29 | 1106.56 | 06-AUG-08:62 | 0.92 |
September | 0.573868E+09 | 0.28 | 1106.56 | 17-SEP-08:62 | 0.92 |
October | 0.619114E+09 | 0.29 | 1106.56 | 09-OCT-08:61 | 0.93 |
November | 0.659400E+09 | 0.31 | 1106.56 | 03-NOV-07:01 | 0.93 |
December | 0.801973E+09 | 0.34 | 1106.56 | 01-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.798534E+10 | 0.31 | |||
Minimum of Months | 0.573868E+09 | 0.28 | 1106.56 | 0.91 | |
Maximum of Months | 0.823750E+09 | 0.35 | 1106.56 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.928900E+09 | 0.42 | 1168.43 | 01-JAN-09:01 | 0.93 |
February | 0.856466E+09 | 0.45 | 1168.43 | 01-FEB-08:61 | 0.93 |
March | 0.818790E+09 | 0.36 | 1168.43 | 01-MAR-08:61 | 0.94 |
April | 0.690619E+09 | 0.31 | 1168.43 | 01-APR-07:01 | 0.93 |
May | 0.642574E+09 | 0.29 | 1168.43 | 01-MAY-07:01 | 0.93 |
June | 0.616367E+09 | 0.28 | 759.50 | 18-JUN-08:62 | 0.74 |
July | 0.626911E+09 | 0.28 | 1168.43 | 16-JUL-08:62 | 0.91 |
August | 0.639069E+09 | 0.28 | 1168.43 | 07-AUG-07:02 | 0.92 |
September | 0.606294E+09 | 0.28 | 1168.43 | 17-SEP-08:62 | 0.92 |
October | 0.665759E+09 | 0.29 | 1168.43 | 08-OCT-08:62 | 0.93 |
November | 0.718525E+09 | 0.31 | 1168.43 | 02-NOV-07:01 | 0.93 |
December | 0.898681E+09 | 0.39 | 1168.43 | 01-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.870895E+10 | 0.33 | |||
Minimum of Months | 0.606294E+09 | 0.28 | 759.50 | 0.74 | |
Maximum of Months | 0.928900E+09 | 0.45 | 1168.43 | 0.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.209072E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.191330E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.198740E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.164396E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.196091E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.429103E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.715283E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.605084E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.335898E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.172237E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.168780E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.205687E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.359170E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.164396E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.715283E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.845465E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.772346E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.855974E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.719612E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.113442E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.251630E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.402986E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.341964E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.197744E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.841322E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.707152E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.825130E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.186447E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.707152E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.402986E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.984734E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.898287E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.957081E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.787113E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.967647E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.187881E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.295564E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.258804E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.149947E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.823605E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.808078E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.962143E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.161106E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.787113E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.295564E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.985810E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.898914E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.953248E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.785497E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.953694E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.186714E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.295120E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.258292E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.148640E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.815607E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.808364E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.962819E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.160516E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.785497E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.295120E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.995309E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.907452E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.956017E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.790199E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.935082E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.182202E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.289284E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.253268E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.144604E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.812007E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.815352E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.971800E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.158768E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.790199E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.289284E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.151823E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.138491E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.144108E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.116392E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.137792E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.302299E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.501306E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.436022E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.233199E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.118625E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.121621E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.147852E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.254953E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.116392E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.501306E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.819922E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.747986E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.775480E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.630251E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.729781E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.155669E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.256844E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.223986E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.120824E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.639747E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.657975E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.798684E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.133731E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.630251E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.256844E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.818116E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.746205E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.772638E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.628760E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.718270E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.153401E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.254171E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.221690E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.119108E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.636324E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.656491E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.796889E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.132574E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.628760E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.254171E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.823750E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.751447E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.773368E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.631792E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.697690E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.148318E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.248975E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.217317E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.115419E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.634030E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.659400E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.801973E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.130737E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.631792E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.248975E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.928900E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.856466E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.848495E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.690619E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.713584E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.146796E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.251833E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.220937E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.114871E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.679275E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.718525E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.898681E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.136789E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.679275E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.251833E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.209072E+10 | 0.00 | 0.240286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191330E+10 | 0.00 | 0.227583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187449E+10 | 0.414220E+09 | 0.133146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164140E+10 | 9078712.51 | 0.483267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159372E+10 | 0.137505E+10 | 82999092.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155002E+10 | 0.109417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160749E+10 | 0.226993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160131E+10 | 0.178479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154530E+10 | 0.720017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162969E+10 | 0.344458E+09 | 0.182813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168780E+10 | 0.00 | 0.724585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205687E+10 | 0.00 | 0.221171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207921E+11 | 0.608319E+11 | 0.962083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.209072E+10 | 0.226993E+11 | 0.240286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.845465E+09 | 0.00 | 0.819354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.772346E+09 | 0.00 | 0.774008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.778748E+09 | 0.292981E+09 | 0.394525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.712894E+09 | 24808776.17 | 0.100590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.823974E+09 | 0.117220E+10 | 818991.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.794340E+09 | 0.678280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.797927E+09 | 0.129824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.805326E+09 | 0.104013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.814987E+09 | 0.461264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.756903E+09 | 0.316368E+09 | 0.218210E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.706370E+09 | 2805434.49 | 0.179913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.825130E+09 | 0.00 | 0.743192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.943441E+10 | 0.365883E+11 | 0.303348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.706370E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.845465E+09 | 0.129824E+11 | 0.819354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.984734E+09 | 0.00 | 0.945893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.898287E+09 | 0.00 | 0.886263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.898410E+09 | 0.220207E+09 | 0.489460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.784708E+09 | 8763342.26 | 0.152051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.781891E+09 | 0.712931E+09 | 12034425.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.764029E+09 | 0.453246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.778640E+09 | 0.908168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.792409E+09 | 0.733473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.751343E+09 | 0.302990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.785283E+09 | 0.144616E+09 | 0.509758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.808078E+09 | 0.00 | 0.256913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.962143E+09 | 0.00 | 0.861806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.998996E+10 | 0.250653E+11 | 0.364456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.751343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.984734E+09 | 0.908168E+10 | 0.945893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.985810E+09 | 0.00 | 0.974837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.898914E+09 | 0.00 | 0.910955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.898028E+09 | 0.206283E+09 | 0.511546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.783531E+09 | 7135148.42 | 0.168891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.777058E+09 | 0.676006E+09 | 22565803.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.759119E+09 | 0.450726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.774073E+09 | 0.909136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.787460E+09 | 0.734118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.746475E+09 | 0.299738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.782619E+09 | 0.124045E+09 | 0.616364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.808364E+09 | 0.00 | 0.280498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.962819E+09 | 0.00 | 0.888699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.996427E+10 | 0.249507E+11 | 0.379932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.746475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.985810E+09 | 0.909136E+10 | 0.974837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.995309E+09 | 0.00 | 0.101786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.907452E+09 | 0.00 | 0.949630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.905657E+09 | 0.186632E+09 | 0.546164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.789019E+09 | 4248092.96 | 0.193857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.777427E+09 | 0.599018E+09 | 42263282.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.758715E+09 | 0.430954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.772511E+09 | 0.882016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.786684E+09 | 0.711029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.746333E+09 | 0.282418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.785878E+09 | 97730093.82 | 0.765921E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.815352E+09 | 0.00 | 0.312210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.971800E+09 | 0.00 | 0.929392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100121E+11 | 0.239518E+11 | 0.402993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.746333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.995309E+09 | 0.882016E+10 | 0.101786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.151823E+10 | 0.00 | 0.200087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138491E+10 | 0.00 | 0.185825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135791E+10 | 0.300908E+09 | 0.110943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116249E+10 | 5024661.94 | 0.437340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112035E+10 | 0.953625E+09 | 0.170995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.109243E+10 | 0.767489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111453E+10 | 0.159133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.113359E+10 | 0.128856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107276E+10 | 0.498073E+10 | 112144.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114699E+10 | 0.143414E+09 | 0.203704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121621E+10 | 0.00 | 0.697390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147852E+10 | 0.00 | 0.183745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147989E+11 | 0.428575E+11 | 0.816156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151823E+10 | 0.159133E+11 | 0.200087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.819922E+09 | 0.00 | 0.104134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.747986E+09 | 0.00 | 0.967825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.734664E+09 | 0.149854E+09 | 0.579416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.629898E+09 | 1255470.38 | 0.230697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.607223E+09 | 0.460163E+09 | 0.101156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.591626E+09 | 0.389553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.602833E+09 | 0.814365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.613707E+09 | 0.659328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.581153E+09 | 0.252069E+10 | 109888.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.621313E+09 | 68378068.79 | 0.106784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.657975E+09 | 0.00 | 0.362817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.798684E+09 | 0.00 | 0.956587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.800698E+10 | 0.218328E+11 | 0.425559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.581153E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.819922E+09 | 0.814365E+10 | 0.104134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.818116E+09 | 0.00 | 0.105082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.746205E+09 | 0.00 | 0.975758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.733190E+09 | 0.144524E+09 | 0.590046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.628570E+09 | 674958.23 | 0.240598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.604220E+09 | 0.426781E+09 | 0.124097E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.588129E+09 | 0.381408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.599137E+09 | 0.804216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.610049E+09 | 0.650981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.577789E+09 | 0.246340E+10 | 498837.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.619132E+09 | 63612207.63 | 0.112941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.656491E+09 | 0.00 | 0.372200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.796889E+09 | 0.00 | 0.965890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.797792E+10 | 0.214650E+11 | 0.432071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.577789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.818116E+09 | 0.804216E+10 | 0.105082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.823750E+09 | 0.00 | 0.109775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.751447E+09 | 0.00 | 0.101766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.737968E+09 | 0.128882E+09 | 0.632706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.631792E+09 | 0.00 | 0.274470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.601851E+09 | 0.355824E+09 | 0.203408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.583942E+09 | 0.361602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.594600E+09 | 0.783200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.605640E+09 | 0.634000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.573868E+09 | 0.232692E+10 | 2316337.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.619114E+09 | 54895282.50 | 0.131901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.659400E+09 | 0.00 | 0.404776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.801973E+09 | 0.00 | 0.100986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.798534E+10 | 0.206545E+11 | 0.458969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.573868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.823750E+09 | 0.783200E+10 | 0.109775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.928900E+09 | 0.00 | 0.137565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.856466E+09 | 0.00 | 0.129464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.818790E+09 | 0.106821E+09 | 0.826605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.690619E+09 | 0.00 | 0.391679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.642574E+09 | 0.259586E+09 | 0.536736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.616367E+09 | 0.340361E+10 | 1510517.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.626911E+09 | 0.777971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.639069E+09 | 0.633500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.606294E+09 | 0.216865E+10 | 22896972.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.665759E+09 | 49499372.18 | 0.191825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.718525E+09 | 0.00 | 0.520975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.898681E+09 | 0.00 | 0.125950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.870895E+10 | 0.201029E+11 | 0.591698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.606294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.928900E+09 | 0.777971E+10 | 0.137565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.209072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187449E+10 | 0.00 | 0.00 | 0.00 | 0.112914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164140E+10 | 0.00 | 0.00 | 0.00 | 2562683.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159372E+10 | 0.00 | 0.00 | 0.00 | 0.367192E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155002E+10 | 0.00 | 0.00 | 0.00 | 0.274101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160749E+10 | 0.00 | 0.00 | 0.00 | 0.554534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160131E+10 | 0.00 | 0.00 | 0.00 | 0.444952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154530E+10 | 0.00 | 0.00 | 0.00 | 0.181367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162969E+10 | 0.00 | 0.00 | 0.00 | 92679333.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207921E+11 | 0.00 | 0.00 | 0.00 | 0.151249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.209072E+10 | 0.00 | 0.00 | 0.00 | 0.554534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.845465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.772346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.778748E+09 | 0.00 | 0.00 | 0.00 | 77226684.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.712894E+09 | 0.00 | 0.00 | 0.00 | 6717661.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.823974E+09 | 0.00 | 0.00 | 0.00 | 0.310444E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.794340E+09 | 0.00 | 0.00 | 0.00 | 0.172196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.797927E+09 | 0.00 | 0.00 | 0.00 | 0.323193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.805326E+09 | 0.00 | 0.00 | 0.00 | 0.261432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.814987E+09 | 0.00 | 0.00 | 0.00 | 0.116246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.756903E+09 | 0.00 | 0.00 | 0.00 | 84418403.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.706370E+09 | 0.00 | 0.00 | 0.00 | 781592.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.825130E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.943441E+10 | 0.00 | 0.00 | 0.00 | 0.921025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.706370E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.845465E+09 | 0.00 | 0.00 | 0.00 | 0.323193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.984734E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.898287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.898410E+09 | 0.00 | 0.00 | 0.00 | 58671647.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.784708E+09 | 0.00 | 0.00 | 0.00 | 2404849.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.781891E+09 | 0.00 | 0.00 | 0.00 | 0.185756E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.764029E+09 | 0.00 | 0.00 | 0.00 | 0.111478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.778640E+09 | 0.00 | 0.00 | 0.00 | 0.217700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.792409E+09 | 0.00 | 0.00 | 0.00 | 0.179563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.751343E+09 | 0.00 | 0.00 | 0.00 | 0.748125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.785283E+09 | 0.00 | 0.00 | 0.00 | 38321664.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.808078E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.962143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.998996E+10 | 0.00 | 0.00 | 0.00 | 0.612069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.751343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.984734E+09 | 0.00 | 0.00 | 0.00 | 0.217700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.985810E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.898914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.898028E+09 | 0.00 | 0.00 | 0.00 | 55220060.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.783531E+09 | 0.00 | 0.00 | 0.00 | 1965869.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.777058E+09 | 0.00 | 0.00 | 0.00 | 0.176637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.759119E+09 | 0.00 | 0.00 | 0.00 | 0.110802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.774073E+09 | 0.00 | 0.00 | 0.00 | 0.217713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.787460E+09 | 0.00 | 0.00 | 0.00 | 0.179545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.746475E+09 | 0.00 | 0.00 | 0.00 | 0.739924E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.782619E+09 | 0.00 | 0.00 | 0.00 | 32987330.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.808364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.962819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.996427E+10 | 0.00 | 0.00 | 0.00 | 0.608734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.746475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.985810E+09 | 0.00 | 0.00 | 0.00 | 0.217713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.995309E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.907452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.905657E+09 | 0.00 | 0.00 | 0.00 | 50360014.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.789019E+09 | 0.00 | 0.00 | 0.00 | 1180234.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.777427E+09 | 0.00 | 0.00 | 0.00 | 0.157655E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.758715E+09 | 0.00 | 0.00 | 0.00 | 0.106331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.772511E+09 | 0.00 | 0.00 | 0.00 | 0.212033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.786684E+09 | 0.00 | 0.00 | 0.00 | 0.174600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.746333E+09 | 0.00 | 0.00 | 0.00 | 0.699712E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.785878E+09 | 0.00 | 0.00 | 0.00 | 26128699.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.815352E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.971800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100121E+11 | 0.00 | 0.00 | 0.00 | 0.586467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.746333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.995309E+09 | 0.00 | 0.00 | 0.00 | 0.212033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.151823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135791E+10 | 0.00 | 0.00 | 0.00 | 83172475.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116249E+10 | 0.00 | 0.00 | 0.00 | 1430753.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112035E+10 | 0.00 | 0.00 | 0.00 | 0.257563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.109243E+10 | 0.00 | 0.00 | 0.00 | 0.193056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111453E+10 | 0.00 | 0.00 | 0.00 | 0.389853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.113359E+10 | 0.00 | 0.00 | 0.00 | 0.322663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107276E+10 | 0.00 | 0.00 | 0.00 | 0.125923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114699E+10 | 0.00 | 0.00 | 0.00 | 39262583.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147989E+11 | 0.00 | 0.00 | 0.00 | 0.106964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151823E+10 | 0.00 | 0.00 | 0.00 | 0.389853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.819922E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.747986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.734664E+09 | 0.00 | 0.00 | 0.00 | 40816865.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.629898E+09 | 0.00 | 0.00 | 0.00 | 353494.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.607223E+09 | 0.00 | 0.00 | 0.00 | 0.122558E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.591626E+09 | 0.00 | 0.00 | 0.00 | 0.965069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.602833E+09 | 0.00 | 0.00 | 0.00 | 0.196560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.613707E+09 | 0.00 | 0.00 | 0.00 | 0.162616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.581153E+09 | 0.00 | 0.00 | 0.00 | 0.627089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.621313E+09 | 0.00 | 0.00 | 0.00 | 18433723.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.657975E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.798684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.800698E+10 | 0.00 | 0.00 | 0.00 | 0.536608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.581153E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.819922E+09 | 0.00 | 0.00 | 0.00 | 0.196560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.818116E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.746205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.733190E+09 | 0.00 | 0.00 | 0.00 | 39447650.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.628570E+09 | 0.00 | 0.00 | 0.00 | 190691.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.604220E+09 | 0.00 | 0.00 | 0.00 | 0.114051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.588129E+09 | 0.00 | 0.00 | 0.00 | 0.945876E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.599137E+09 | 0.00 | 0.00 | 0.00 | 0.194258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.610049E+09 | 0.00 | 0.00 | 0.00 | 0.160685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.577789E+09 | 0.00 | 0.00 | 0.00 | 0.613293E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.619132E+09 | 0.00 | 0.00 | 0.00 | 17192575.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.656491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.796889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.797792E+10 | 0.00 | 0.00 | 0.00 | 0.527948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.577789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.818116E+09 | 0.00 | 0.00 | 0.00 | 0.194258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.823750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.751447E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.737968E+09 | 0.00 | 0.00 | 0.00 | 35399619.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.631792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.601851E+09 | 0.00 | 0.00 | 0.00 | 95838660.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.583942E+09 | 0.00 | 0.00 | 0.00 | 0.899237E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.594600E+09 | 0.00 | 0.00 | 0.00 | 0.189515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.605640E+09 | 0.00 | 0.00 | 0.00 | 0.156753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.573868E+09 | 0.00 | 0.00 | 0.00 | 0.580319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.619114E+09 | 0.00 | 0.00 | 0.00 | 14916362.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.659400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.801973E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.798534E+10 | 0.00 | 0.00 | 0.00 | 0.508839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.573868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.823750E+09 | 0.00 | 0.00 | 0.00 | 0.189515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.928900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.856466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.818790E+09 | 0.00 | 0.00 | 0.00 | 29705148.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.690619E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.642574E+09 | 0.00 | 0.00 | 0.00 | 71009598.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.616367E+09 | 0.00 | 0.00 | 0.00 | 0.851595E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.626911E+09 | 0.00 | 0.00 | 0.00 | 0.189142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.639069E+09 | 0.00 | 0.00 | 0.00 | 0.157030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.606294E+09 | 0.00 | 0.00 | 0.00 | 0.542419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.665759E+09 | 0.00 | 0.00 | 0.00 | 13516407.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.718525E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.898681E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.870895E+10 | 0.00 | 0.00 | 0.00 | 0.496997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.606294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.928900E+09 | 0.00 | 0.00 | 0.00 | 0.189142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.451696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161672E+11 | 0.00 | 0.00 | 0.52 |
February | 0.416526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150472E+11 | 0.00 | 0.00 | 0.53 |
March | 0.795508E+10 | 16119383.71 | 0.00 | 513591.34 | 0.00 | 0.733003E+10 | 0.199952E+09 | 0.00 | 0.54 |
April | 0.892759E+10 | 0.00 | 0.00 | 449924.94 | 0.00 | 0.170488E+10 | 0.562445E+09 | 0.00 | 0.54 |
May | 0.424656E+10 | 43248853.13 | 0.00 | 8009726.22 | 0.00 | 4275462.41 | 0.458182E+10 | 0.00 | 0.71 |
June | 0.633185E+09 | 0.169547E+10 | 0.00 | 15914128.58 | 1380136.58 | 0.00 | 0.501158E+10 | 0.00 | 0.95 |
July | 1263742.89 | 0.477971E+10 | 0.00 | 9981366.24 | 370667.24 | 0.00 | 0.138454E+10 | 0.00 | 0.94 |
August | 53681697.68 | 0.274354E+10 | 0.00 | 16435852.33 | 0.00 | 0.00 | 0.319954E+10 | 0.00 | 0.94 |
September | 0.924262E+09 | 0.722316E+09 | 0.00 | 16698983.61 | 0.00 | 0.00 | 0.678332E+10 | 0.00 | 0.98 |
October | 0.843766E+10 | 0.00 | 0.00 | 3722358.38 | 0.00 | 0.165753E+09 | 0.249318E+10 | 0.00 | 0.61 |
November | 0.947278E+10 | 0.00 | 0.00 | 71362.87 | 0.00 | 0.314492E+10 | 85376787.90 | 0.00 | 0.53 |
December | 0.529448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146782E+11 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.546287E+11 | 0.100004E+11 | 0.00 | 71797294.51 | 1750803.81 | 0.582425E+11 | 0.243018E+11 | 0.00 | 0.69 |
Minimum of Months | 1263742.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.947278E+10 | 0.477971E+10 | 0.00 | 16698983.61 | 1380136.58 | 0.161672E+11 | 0.678332E+10 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.258084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501413E+10 | 0.00 | 0.00 | 0.38 |
February | 0.207560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491572E+10 | 0.00 | 0.00 | 0.38 |
March | 0.347746E+10 | 10469971.46 | 0.00 | 450411.59 | 0.00 | 0.204844E+10 | 0.261768E+09 | 0.00 | 0.42 |
April | 0.322702E+10 | 0.00 | 0.00 | 1147734.99 | 0.00 | 0.304250E+09 | 0.100961E+10 | 0.00 | 0.45 |
May | 0.921704E+09 | 25451796.63 | 0.00 | 6338113.52 | 0.00 | 0.00 | 0.384236E+10 | 0.00 | 0.76 |
June | 0.143407E+09 | 0.933754E+09 | 0.00 | 7244143.31 | 6333433.08 | 0.00 | 0.266195E+10 | 0.00 | 0.92 |
July | 0.00 | 0.256299E+10 | 0.00 | 2973423.09 | 2212185.61 | 0.00 | 0.453144E+09 | 0.00 | 0.81 |
August | 7646860.03 | 0.142538E+10 | 0.00 | 6405197.55 | 145479.76 | 0.00 | 0.129713E+10 | 0.00 | 0.85 |
September | 0.163481E+09 | 0.430474E+09 | 0.00 | 8613711.44 | 0.00 | 0.00 | 0.381463E+10 | 0.00 | 1.01 |
October | 0.277568E+10 | 0.00 | 0.00 | 3293621.66 | 0.00 | 4415466.03 | 0.220491E+10 | 0.00 | 0.58 |
November | 0.387781E+10 | 0.00 | 0.00 | 365981.22 | 0.00 | 0.641821E+09 | 0.342807E+09 | 0.00 | 0.41 |
December | 0.249907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472669E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.217497E+11 | 0.538852E+10 | 0.00 | 36832338.35 | 8691098.45 | 0.176555E+11 | 0.158883E+11 | 0.00 | 0.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.387781E+10 | 0.256299E+10 | 0.00 | 8613711.44 | 6333433.08 | 0.501413E+10 | 0.384236E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.155042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645832E+10 | 0.00 | 0.00 | 0.41 |
February | 0.147828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592006E+10 | 0.00 | 0.00 | 0.41 |
March | 0.310089E+10 | 6453415.05 | 0.00 | 179206.16 | 0.00 | 0.278239E+10 | 0.102122E+09 | 0.00 | 0.43 |
April | 0.328964E+10 | 0.00 | 0.00 | 294334.50 | 0.00 | 0.636274E+09 | 0.309602E+09 | 0.00 | 0.43 |
May | 0.155276E+10 | 20149033.54 | 0.00 | 3075486.82 | 433336.89 | 1945482.43 | 0.200336E+10 | 0.00 | 0.63 |
June | 0.321057E+09 | 0.650905E+09 | 0.00 | 4468006.13 | 24677820.65 | 0.00 | 0.210616E+10 | 0.00 | 0.82 |
July | 25742210.06 | 0.173794E+10 | 0.00 | 2591415.01 | 75410317.82 | 0.00 | 0.594966E+09 | 0.00 | 0.76 |
August | 82580145.57 | 0.101016E+10 | 0.00 | 4584936.03 | 33568022.37 | 0.00 | 0.129443E+10 | 0.00 | 0.79 |
September | 0.470003E+09 | 0.279126E+09 | 0.00 | 5143485.64 | 4255890.49 | 0.00 | 0.261210E+10 | 0.00 | 0.87 |
October | 0.309617E+10 | 0.00 | 0.00 | 1385475.64 | 0.00 | 68668721.08 | 0.107188E+10 | 0.00 | 0.50 |
November | 0.360648E+10 | 0.00 | 0.00 | 47045.12 | 0.00 | 0.114361E+10 | 53166286.26 | 0.00 | 0.42 |
December | 0.174496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585675E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.203190E+11 | 0.370474E+10 | 0.00 | 21769391.06 | 0.138345E+09 | 0.228680E+11 | 0.101478E+11 | 0.00 | 0.57 |
Minimum of Months | 25742210.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.360648E+10 | 0.173794E+10 | 0.00 | 5143485.64 | 75410317.82 | 0.645832E+10 | 0.261210E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674992E+10 | 0.00 | 0.00 | 0.41 |
February | 0.118390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621428E+10 | 0.00 | 0.00 | 0.41 |
March | 0.287403E+10 | 6112488.85 | 0.00 | 151911.81 | 0.00 | 0.302020E+10 | 83200086.35 | 0.00 | 0.43 |
April | 0.325486E+10 | 0.00 | 0.00 | 215006.23 | 0.00 | 0.714872E+09 | 0.229314E+09 | 0.00 | 0.43 |
May | 0.162878E+10 | 19435175.19 | 0.00 | 2824817.83 | 426529.18 | 2754438.69 | 0.182547E+10 | 0.00 | 0.61 |
June | 0.326227E+09 | 0.649780E+09 | 0.00 | 4407899.99 | 24719762.52 | 0.00 | 0.207908E+10 | 0.00 | 0.81 |
July | 25575977.54 | 0.174187E+10 | 0.00 | 2592000.90 | 75158481.62 | 0.00 | 0.590326E+09 | 0.00 | 0.75 |
August | 83515944.68 | 0.101120E+10 | 0.00 | 4586147.72 | 33715615.96 | 0.00 | 0.128377E+10 | 0.00 | 0.79 |
September | 0.483363E+09 | 0.277234E+09 | 0.00 | 5044533.91 | 4261600.16 | 0.00 | 0.256773E+10 | 0.00 | 0.86 |
October | 0.311493E+10 | 0.00 | 0.00 | 1194957.05 | 0.00 | 0.100628E+09 | 0.953574E+09 | 0.00 | 0.49 |
November | 0.336522E+10 | 0.00 | 0.00 | 33526.87 | 0.00 | 0.137890E+10 | 40581972.99 | 0.00 | 0.42 |
December | 0.148006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612140E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.190793E+11 | 0.370564E+10 | 0.00 | 21050802.31 | 0.138282E+09 | 0.243030E+11 | 0.965305E+10 | 0.00 | 0.57 |
Minimum of Months | 25575977.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.336522E+10 | 0.174187E+10 | 0.00 | 5044533.91 | 75158481.62 | 0.674992E+10 | 0.256773E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.852098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715664E+10 | 0.00 | 0.00 | 0.41 |
February | 0.863126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653490E+10 | 0.00 | 0.00 | 0.41 |
March | 0.254771E+10 | 5630100.94 | 0.00 | 128161.15 | 8210.63 | 0.335880E+10 | 57610242.20 | 0.00 | 0.43 |
April | 0.317784E+10 | 0.00 | 0.00 | 107314.79 | 0.00 | 0.835602E+09 | 0.140723E+09 | 0.00 | 0.42 |
May | 0.171429E+10 | 18077740.75 | 0.00 | 2329033.98 | 440324.06 | 14318465.56 | 0.154972E+10 | 0.00 | 0.59 |
June | 0.364923E+09 | 0.632439E+09 | 0.00 | 4103537.46 | 25114499.26 | 0.00 | 0.198159E+10 | 0.00 | 0.80 |
July | 25601728.20 | 0.169756E+10 | 0.00 | 2468854.50 | 74397320.35 | 0.00 | 0.593082E+09 | 0.00 | 0.75 |
August | 83363059.50 | 0.989656E+09 | 0.00 | 4333516.15 | 32999940.24 | 0.00 | 0.126816E+10 | 0.00 | 0.78 |
September | 0.525345E+09 | 0.260941E+09 | 0.00 | 4695895.26 | 4122159.20 | 0.00 | 0.245819E+10 | 0.00 | 0.85 |
October | 0.319903E+10 | 0.00 | 0.00 | 920298.50 | 0.00 | 0.142405E+09 | 0.727837E+09 | 0.00 | 0.48 |
November | 0.305025E+10 | 0.00 | 0.00 | 14973.66 | 0.00 | 0.169236E+10 | 22472889.37 | 0.00 | 0.42 |
December | 0.111819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648307E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.175218E+11 | 0.360431E+10 | 0.00 | 19101585.45 | 0.137082E+09 | 0.262181E+11 | 0.879938E+10 | 0.00 | 0.56 |
Minimum of Months | 25601728.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.319903E+10 | 0.169756E+10 | 0.00 | 4695895.26 | 74397320.35 | 0.715664E+10 | 0.245819E+10 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.284275E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146280E+11 | 0.00 | 0.00 | 0.38 |
February | 0.306691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134621E+11 | 0.00 | 0.00 | 0.38 |
March | 0.332675E+10 | 4517442.04 | 0.00 | 251211.45 | 401082.82 | 0.765584E+10 | 85492997.42 | 0.00 | 0.39 |
April | 0.557269E+10 | 0.00 | 0.00 | 85177.80 | 0.00 | 0.195873E+10 | 0.107851E+09 | 0.00 | 0.39 |
May | 0.362823E+10 | 26256176.82 | 0.00 | 2783026.97 | 3789989.73 | 14242638.99 | 0.193733E+10 | 0.00 | 0.48 |
June | 0.608979E+09 | 0.122205E+10 | 0.00 | 6217815.50 | 23598704.11 | 0.00 | 0.314369E+10 | 0.00 | 0.63 |
July | 10116059.11 | 0.328232E+10 | 0.00 | 3284237.15 | 45471649.92 | 0.00 | 0.775174E+09 | 0.00 | 0.60 |
August | 74298591.97 | 0.189721E+10 | 0.00 | 6642712.87 | 30536416.44 | 0.00 | 0.184716E+10 | 0.00 | 0.63 |
September | 0.896568E+09 | 0.426608E+09 | 0.00 | 7369477.48 | 5757458.18 | 0.00 | 0.389190E+10 | 0.00 | 0.67 |
October | 0.601114E+10 | 0.00 | 0.00 | 1041956.59 | 0.00 | 0.384203E+09 | 0.874795E+09 | 0.00 | 0.41 |
November | 0.503073E+10 | 0.00 | 0.00 | 162.27 | 0.00 | 0.391717E+10 | 3339036.18 | 0.00 | 0.38 |
December | 0.862211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133404E+11 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.266127E+11 | 0.685897E+10 | 0.00 | 27675778.09 | 0.109555E+09 | 0.553608E+11 | 0.126667E+11 | 0.00 | 0.48 |
Minimum of Months | 10116059.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.601114E+10 | 0.328232E+10 | 0.00 | 7369477.48 | 45471649.92 | 0.146280E+11 | 0.389190E+10 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 98092400.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.734663E+10 | 0.00 | 0.00 | 0.38 |
February | 0.119867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675414E+10 | 0.00 | 0.00 | 0.38 |
March | 0.146374E+10 | 2353741.66 | 0.00 | 118478.67 | 240047.80 | 0.401693E+10 | 40767341.12 | 0.00 | 0.39 |
April | 0.262936E+10 | 0.00 | 0.00 | 31903.49 | 0.00 | 0.113321E+10 | 37876488.70 | 0.00 | 0.39 |
May | 0.183833E+10 | 12776851.21 | 0.00 | 1283549.77 | 2230172.05 | 12635000.75 | 0.904212E+09 | 0.00 | 0.48 |
June | 0.318853E+09 | 0.609552E+09 | 0.00 | 3094949.94 | 11621250.21 | 0.00 | 0.158325E+10 | 0.00 | 0.65 |
July | 5107119.16 | 0.164324E+10 | 0.00 | 1664080.35 | 22956400.66 | 0.00 | 0.407164E+09 | 0.00 | 0.62 |
August | 40135063.41 | 0.953372E+09 | 0.00 | 3333335.60 | 15035558.39 | 0.00 | 0.951997E+09 | 0.00 | 0.65 |
September | 0.456698E+09 | 0.212524E+09 | 0.00 | 3695712.90 | 3080462.40 | 0.00 | 0.198270E+10 | 0.00 | 0.69 |
October | 0.292962E+10 | 0.00 | 0.00 | 481616.59 | 0.00 | 0.272486E+09 | 0.408597E+09 | 0.00 | 0.41 |
November | 0.232796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213394E+10 | 0.00 | 0.00 | 0.38 |
December | 0.311611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677813E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.125394E+11 | 0.343382E+10 | 0.00 | 13703627.31 | 55163891.52 | 0.284481E+11 | 0.631657E+10 | 0.00 | 0.48 |
Minimum of Months | 5107119.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.292962E+10 | 0.164324E+10 | 0.00 | 3695712.90 | 22956400.66 | 0.734663E+10 | 0.198270E+10 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 68601691.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737619E+10 | 0.00 | 0.00 | 0.38 |
February | 0.105796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676826E+10 | 0.00 | 0.00 | 0.38 |
March | 0.139196E+10 | 2250569.99 | 0.00 | 115313.66 | 265526.80 | 0.408889E+10 | 38038769.22 | 0.00 | 0.39 |
April | 0.253012E+10 | 0.00 | 0.00 | 27791.20 | 0.00 | 0.122727E+10 | 33079608.10 | 0.00 | 0.38 |
May | 0.187861E+10 | 12197465.67 | 0.00 | 1135018.34 | 2595497.80 | 19771499.29 | 0.802418E+09 | 0.00 | 0.47 |
June | 0.334775E+09 | 0.601478E+09 | 0.00 | 2979784.85 | 11552695.89 | 0.00 | 0.153607E+10 | 0.00 | 0.64 |
July | 5124432.61 | 0.162671E+10 | 0.00 | 1635359.17 | 22761238.88 | 0.00 | 0.405851E+09 | 0.00 | 0.61 |
August | 42923410.58 | 0.945059E+09 | 0.00 | 3266356.22 | 15007198.58 | 0.00 | 0.941524E+09 | 0.00 | 0.64 |
September | 0.488311E+09 | 0.207181E+09 | 0.00 | 3589995.05 | 3084802.31 | 0.00 | 0.192247E+10 | 0.00 | 0.68 |
October | 0.289139E+10 | 0.00 | 0.00 | 432175.72 | 0.00 | 0.319460E+09 | 0.373142E+09 | 0.00 | 0.41 |
November | 0.224828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221112E+10 | 0.00 | 0.00 | 0.38 |
December | 0.271860E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681795E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.122577E+11 | 0.339488E+10 | 0.00 | 13181794.21 | 55266960.27 | 0.288289E+11 | 0.605259E+10 | 0.00 | 0.48 |
Minimum of Months | 5124432.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.289139E+10 | 0.162671E+10 | 0.00 | 3589995.05 | 22761238.88 | 0.737619E+10 | 0.192247E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 23304666.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742152E+10 | 0.00 | 0.00 | 0.38 |
February | 41498143.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683258E+10 | 0.00 | 0.00 | 0.38 |
March | 0.105373E+10 | 2056078.47 | 0.00 | 98414.27 | 380989.54 | 0.442620E+10 | 32479650.17 | 0.00 | 0.39 |
April | 0.218759E+10 | 0.00 | 0.00 | 19278.15 | 0.00 | 0.155406E+10 | 25786107.46 | 0.00 | 0.38 |
May | 0.193068E+10 | 10772734.30 | 0.00 | 853947.96 | 3734231.93 | 46885919.79 | 0.612654E+09 | 0.00 | 0.46 |
June | 0.392503E+09 | 0.580500E+09 | 0.00 | 2699844.16 | 12116113.93 | 0.00 | 0.139824E+10 | 0.00 | 0.62 |
July | 5812461.06 | 0.158902E+10 | 0.00 | 1537012.84 | 22866214.98 | 0.00 | 0.403447E+09 | 0.00 | 0.61 |
August | 51917816.15 | 0.926850E+09 | 0.00 | 3081044.26 | 14981806.57 | 0.00 | 0.914838E+09 | 0.00 | 0.64 |
September | 0.553385E+09 | 0.194684E+09 | 0.00 | 3337773.72 | 3061461.65 | 0.00 | 0.178517E+10 | 0.00 | 0.67 |
October | 0.279078E+10 | 0.00 | 0.00 | 345720.24 | 0.00 | 0.436055E+09 | 0.304260E+09 | 0.00 | 0.41 |
November | 0.188017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257274E+10 | 0.00 | 0.00 | 0.38 |
December | 0.124305E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696547E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.110357E+11 | 0.330388E+10 | 0.00 | 11973035.59 | 57140818.61 | 0.302555E+11 | 0.547688E+10 | 0.00 | 0.47 |
Minimum of Months | 5812461.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.279078E+10 | 0.158902E+10 | 0.00 | 3337773.72 | 22866214.98 | 0.742152E+10 | 0.178517E+10 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741917E+10 | 0.00 | 0.00 | 0.38 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685508E+10 | 0.00 | 0.00 | 0.38 |
March | 0.337094E+09 | 1795831.47 | 0.00 | 71351.35 | 720417.16 | 0.511678E+10 | 22224386.93 | 0.00 | 0.39 |
April | 0.122699E+10 | 0.00 | 0.00 | 7101.90 | 0.00 | 0.246519E+10 | 12490796.32 | 0.00 | 0.38 |
May | 0.186500E+10 | 8855530.37 | 237077.60 | 521692.48 | 2649623.67 | 0.198156E+09 | 0.375516E+09 | 672.11 | 0.45 |
June | 0.456604E+09 | 0.542502E+09 | 0.00 | 2265286.15 | 13090619.28 | 0.00 | 0.122319E+10 | 0.00 | 0.60 |
July | 11999248.72 | 0.150060E+10 | 0.00 | 1549526.33 | 21410184.76 | 0.00 | 0.424356E+09 | 0.00 | 0.62 |
August | 0.113612E+09 | 0.892465E+09 | 0.00 | 2806839.06 | 14468872.91 | 0.00 | 0.841673E+09 | 0.00 | 0.64 |
September | 0.584005E+09 | 0.177117E+09 | 0.00 | 3045544.97 | 3052730.24 | 4466851.63 | 0.167316E+10 | 0.00 | 0.66 |
October | 0.215401E+10 | 0.00 | 0.00 | 261079.17 | 0.00 | 0.105895E+10 | 0.232635E+09 | 0.00 | 0.40 |
November | 0.834147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358737E+10 | 0.00 | 0.00 | 0.38 |
December | 11819787.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705742E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.759528E+10 | 0.312333E+10 | 237077.60 | 10528421.40 | 55392448.02 | 0.337626E+11 | 0.480524E+10 | 672.11 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.215401E+10 | 0.150060E+10 | 237077.60 | 3045544.97 | 21410184.76 | 0.741917E+10 | 0.167316E+10 | 672.11 | 0.66 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:34:27
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.111359E+12 | 0.483808E+11 | 0.00 | 0.100158E+12 | 0.318181E+11 |
February | 0.202848E+12 | 0.464144E+11 | 0.00 | 0.925110E+11 | 0.297771E+11 |
March | 0.335464E+12 | 0.337514E+11 | 0.00 | 0.745591E+11 | 0.202669E+11 |
April | 0.422157E+12 | 0.232362E+11 | 0.00 | 0.521622E+11 | 0.676139E+10 |
May | 0.540328E+12 | 0.138086E+11 | 0.00 | 0.398161E+11 | 0.924961E+10 |
June | 0.597031E+12 | 0.340210E+10 | 0.00 | 0.183960E+11 | 0.672373E+11 |
July | 0.558341E+12 | -0.671577E+10 | 0.00 | -0.164677E+11 | 0.138016E+12 |
August | 0.469294E+12 | -0.182663E+10 | 0.00 | 0.152221E+10 | 0.111220E+12 |
September | 0.344877E+12 | 0.753713E+10 | 0.00 | 0.318955E+11 | 0.441424E+11 |
October | 0.215537E+12 | 0.210166E+11 | 0.00 | 0.504574E+11 | 0.465468E+10 |
November | 0.970720E+11 | 0.276974E+11 | 0.00 | 0.603321E+11 | 0.102843E+11 |
December | 0.965463E+11 | 0.474786E+11 | 0.00 | 0.957767E+11 | 0.291602E+11 |
Annual Sum or Average | 0.399085E+13 | 0.264181E+12 | 0.00 | 0.601119E+12 | 0.502587E+12 |
Minimum of Months | 0.965463E+11 | -0.671577E+10 | 0.00 | -0.164677E+11 | 0.465468E+10 |