Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:34
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 08:34:37
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1231.31 | 589.05 | 589.05 |
Net Site Energy | 1231.31 | 589.05 | 589.05 |
Total Source Energy | 3376.96 | 1615.52 | 1615.52 |
Net Source Energy | 3376.96 | 1615.52 | 1615.52 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 250.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 36.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 496.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 153.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 64.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 980.42 | 250.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 250.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 36.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 496.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 100.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 153.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 64.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 250.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 36.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 496.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 100.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 153.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 64.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 285.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 121.75 | 120.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 469.03 | 120.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 285.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 121.75 | 120.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 469.03 | 120.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 980.421 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 980.421 | 100.00 |
Total On-Site and Utility Electric Sources | 980.421 | 100.00 |
Total Electricity End Uses | 980.421 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1072.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:34 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 20.1123 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 23.1025 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 20.9200 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 20.9200 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 20.9200 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 13.4438 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 17.2687 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 17.2687 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 20.1123 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 23.1025 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 20.9200 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 20.9200 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 20.9200 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 13.4438 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 13.5625 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 13.5625 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 13.5625 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 13.5625 | 6.19 | 4.3000 | |
Total | 2090.32 | 17.2687 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 17.2687 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 17.2687 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-AUG-14:50 | 16-JAN-09:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 137988.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 30000.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 30804.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9680.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5444.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 83988.27 | 137988.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 137988.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 30000.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 30804.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 9680.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5444.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 271.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 116.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 319.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 486.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 203.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3104.99 | 271.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 130.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 55.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 752.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 152.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 232.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 97.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1485.42 | 130.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 130.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 55.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 752.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 152.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 232.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 97.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1485.42 | 130.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.07 |
SMSTORE1 DIRECT AIR | 1.10 |
SMSTORE2 DIRECT AIR | 1.10 |
SMSTORE3 DIRECT AIR | 1.09 |
SMSTORE4 DIRECT AIR | 1.09 |
LGSTORE2 DIRECT AIR | 1.95 |
SMSTORE5 DIRECT AIR | 1.01 |
SMSTORE6 DIRECT AIR | 1.00 |
SMSTORE7 DIRECT AIR | 0.995109 |
SMSTORE8 DIRECT AIR | 1.06 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.07 | 2.07 | 2.07 | 2.07 | 2.07 | 2.07 | 1.00 | 1.00 | 2.07 |
PSZ-AC_2:2 | 1.10 | 1.10 | 1.10 | 1.10 | 1.12 | 1.12 | 1.00 | 0.984476 | 1.12 |
PSZ-AC_3:3 | 1.10 | 1.10 | 1.10 | 1.10 | 1.12 | 1.12 | 1.00 | 0.983353 | 1.12 |
PSZ-AC_4:4 | 1.09 | 1.09 | 1.09 | 1.09 | 1.12 | 1.12 | 1.00 | 0.974053 | 1.12 |
PSZ-AC_5:5 | 1.09 | 1.09 | 1.09 | 1.09 | 1.11 | 1.11 | 1.00 | 0.981702 | 1.11 |
PSZ-AC_6:6 | 1.95 | 1.95 | 1.95 | 1.95 | 1.95 | 1.95 | 1.00 | 1.00 | 1.95 |
PSZ-AC_7:7 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.00 | 0.995160 | 1.01 |
PSZ-AC_8:8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.01 | 1.01 | 1.00 | 0.994742 | 1.01 |
PSZ-AC_9:9 | 0.995109 | 0.995109 | 0.995109 | 0.995109 | 1.00 | 1.00 | 1.00 | 0.993558 | 1.00 |
PSZ-AC_10:10 | 1.06 | 1.06 | 1.06 | 1.06 | 1.07 | 1.07 | 1.00 | 0.986665 | 1.07 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.07 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.12 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.12 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.12 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.11 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.95 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.01 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.01 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.00 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.07 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.07 | 2214.66 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.12 | 1237.59 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.12 | 1234.86 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.12 | 1238.06 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.11 | 1227.50 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.95 | 2089.32 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.01 | 1121.84 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.01 | 1115.73 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.00 | 1108.89 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.07 | 1184.29 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.07 | 2.07 | 2.07 | 1.37 | 35805.87 | 59060.51 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.12 | 1.12 | 1.12 | 0.737750 | 19175.16 | 31008.43 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.12 | 1.12 | 1.12 | 0.736122 | 19137.94 | 30925.49 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.12 | 1.12 | 1.12 | 0.738033 | 19182.42 | 30755.28 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.11 | 1.11 | 1.11 | 1.11 | 19036.14 | 30736.99 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.95 | 1.95 | 1.95 | 1.29 | 34012.09 | 56420.07 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.01 | 1.01 | 1.01 | 1.01 | 17579.68 | 28933.08 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.01 | 1.01 | 1.01 | 1.01 | 17496.06 | 28799.78 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.00 | 1.00 | 1.00 | 1.00 | 17396.56 | 28634.59 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.07 | 1.07 | 1.07 | 1.07 | 18280.99 | 29994.01 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.07 | 1.03 | 1.38 | 35805.87 | 17902.94 | 0.800790 | 0.800790 |
PSZ-AC_2:2 COOLING COIL | 1.12 | 0.558901 | 0.745200 | 19175.16 | 9587.58 | 0.800780 | 0.800780 |
PSZ-AC_3:3 COOLING COIL | 1.12 | 0.557668 | 0.743560 | 19137.94 | 9568.97 | 0.800680 | 0.800680 |
PSZ-AC_4:4 COOLING COIL | 1.12 | 0.559116 | 0.745487 | 19182.42 | 9591.21 | 0.800780 | 0.800780 |
PSZ-AC_5:5 COOLING COIL | 1.11 | 0.554346 | 0.739127 | 19036.14 | 9518.07 | 0.800460 | 0.800460 |
PSZ-AC_6:6 COOLING COIL | 1.95 | 0.976274 | 1.30 | 34012.09 | 17006.04 | 0.800380 | 0.800380 |
PSZ-AC_7:7 COOLING COIL | 1.01 | 0.506629 | 0.675507 | 17579.68 | 8789.84 | 0.800790 | 0.800790 |
PSZ-AC_8:8 COOLING COIL | 1.01 | 0.503869 | 0.671827 | 17496.06 | 8748.03 | 0.800540 | 0.800540 |
PSZ-AC_9:9 COOLING COIL | 1.00 | 0.500781 | 0.667707 | 17396.56 | 8698.28 | 0.800390 | 0.800390 |
PSZ-AC_10:10 COOLING COIL | 1.07 | 0.534832 | 0.713107 | 18280.99 | 9140.50 | 0.800110 | 0.800110 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 59060.51 |
PSZ-AC_2:2 HEATING COIL | 31008.43 |
PSZ-AC_3:3 HEATING COIL | 30925.49 |
PSZ-AC_4:4 HEATING COIL | 30755.28 |
PSZ-AC_5:5 HEATING COIL | 30736.99 |
PSZ-AC_6:6 HEATING COIL | 56420.07 |
PSZ-AC_7:7 HEATING COIL | 28933.08 |
PSZ-AC_8:8 HEATING COIL | 28799.78 |
PSZ-AC_9:9 HEATING COIL | 28634.59 |
PSZ-AC_10:10 HEATING COIL | 29994.01 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 20.112 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.412 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 23.103 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 27.403 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 20.920 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.220 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 20.920 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.220 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 20.920 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.220 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 4694.002 | 13.474 | 83.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4694.002 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 2312.850 | 6.639 | 41.117 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2312.850 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2367.672 | 13.592 | 84.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2367.672 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1656.630 | 9.510 | 58.904 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1656.630 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1281.630 | 7.358 | 45.570 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1281.630 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1281.630 | 7.358 | 45.570 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1281.630 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1281.630 | 7.358 | 45.570 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1281.630 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 4683.651 | 13.444 | 83.264 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4683.651 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6000 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1408 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2031 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.433 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.024 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.847 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.34128934E-12 | 0.10473450E-14 | -0.10397207E-12 | 0.10371484E-15 |
23 | 6 | 0.30755064E-07 | 0.17217129E-09 | 0.70279215E-08 | -0.14642558E-12 |
24 | 5 | -0.20062951E-03 | 0.14545406E-05 | -0.10304618E-03 | 0.69406843E-08 |
25 | 4 | 0.30437449 | 0.69977658E-03 | 0.10408506 | -0.35305012E-04 |
26 | 3 | -7.5082928 | 0.21456968E-01 | -2.4107259 | 0.30195353E-01 |
27 | 2 | 41.668927 | 0.75582488E-01 | 15.559173 | -0.34222686 |
28 | 1 | -81.156896 | 0.33830739E-01 | -29.405205 | 1.0916426 |
29 | 0 | 46.824335 | 0.67514285E-03 | 16.285023 | |
30 | 7 | -0.30155247E-08 | -0.19705740E-14 | 0.18469307E-14 | -0.46079768E-16 |
31 | 6 | 0.40551627E-05 | 0.26926011E-08 | 0.31944497E-02 | -0.26797721E-04 |
32 | 5 | -0.28496186E-03 | 0.15923452E-05 | -0.22398486 | 0.19584477E-02 |
33 | 4 | 0.65115693E-02 | 0.72427529E-04 | 4.8338806 | -0.45306652E-01 |
34 | 3 | -0.57046066E-01 | 0.57554694E-03 | -38.045903 | 0.39892442 |
35 | 2 | 0.20237164 | 0.95689144E-03 | 116.53161 | -1.4185768 |
36 | 1 | -0.29197338 | 0.29127682E-03 | -143.93536 | 2.0495010 |
37 | 0 | 0.14232195 | 0.70641069E-05 | 60.838472 | |
38 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
39 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
40 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
41 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
42 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
43 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
44 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
45 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
46 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
47 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
48 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
49 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
50 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
51 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
52 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
53 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
54 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521549E-14 | -0.37274185E-16 |
55 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
56 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
57 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
58 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
59 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
60 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
61 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
62 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521548E-14 | -0.37274183E-16 |
63 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
64 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
65 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
66 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
67 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
68 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
69 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
70 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
71 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
72 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
73 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
74 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
75 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
76 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
77 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
78 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274181E-16 |
79 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
80 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
81 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
82 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
83 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
84 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
85 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
86 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
87 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
88 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
89 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
90 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
91 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
92 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
93 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
94 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
95 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
96 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
97 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
98 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
99 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
100 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
101 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
102 | 7 | -0.20778300E-08 | -0.65167512E-15 | 0.79548166E-14 | -0.12010680E-15 |
103 | 6 | 0.57088823E-05 | 0.38884884E-08 | 0.31895855E-02 | -0.26756916E-04 |
104 | 5 | -0.40892418E-03 | 0.23023551E-05 | -0.22370841 | 0.19560076E-02 |
105 | 4 | 0.93961169E-02 | 0.10478953E-03 | 4.8292766 | -0.45262394E-01 |
106 | 3 | -0.82481111E-01 | 0.83319714E-03 | -38.019897 | 0.39863696 |
107 | 2 | 0.29283299 | 0.13859693E-02 | 116.48099 | -1.4178998 |
108 | 1 | -0.42263540 | 0.42218679E-03 | -143.90557 | 2.0490113 |
109 | 0 | 0.20604930 | 0.10232106E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.419_SHGC_0.4 | 35 | 1 | VerySmooth | 2.381 | 2.381 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.03930E-002 | 0.31435 | 0.47506 | 0.47506 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12237 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 23168.34920 | 27802.01904 | 1.72474 | 2.06969 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 19472.69960 | 23367.23952 | 0.85153 | 1.02184 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 12656.07278 | 15187.28734 | 0.91704 | 1.10045 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 9040.10594 | 10848.12712 | 0.39532 | 0.47439 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 12616.30865 | 15139.57038 | 0.91398 | 1.09677 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 9153.59586 | 10984.31503 | 0.40029 | 0.48034 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 12531.82549 | 15038.19059 | 0.90768 | 1.08922 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 9253.59597 | 11104.31517 | 0.40466 | 0.48559 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 12522.16714 | 15026.60056 | 0.90700 | 1.08841 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 9429.98767 | 11315.98521 | 0.41237 | 0.49485 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 21857.05043 | 26228.46052 | 1.62712 | 1.95255 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.82122E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 18313.18246 | 21975.81896 | 0.80084 | 0.96101 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11619.29767 | 13943.15720 | 0.84030 | 1.00835 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 9739.09163 | 11686.90996 | 0.42589 | 0.51107 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11552.74729 | 13863.29675 | 0.83537 | 1.00244 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 9739.17114 | 11687.00537 | 0.42589 | 0.51107 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 11470.08517 | 13764.10221 | 0.82926 | 0.99511 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 10014.63260 | 12017.55912 | 0.43794 | 0.52553 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 12146.17128 | 14575.40553 | 0.87950 | 1.05540 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 12315.57677 | 14778.69213 | 0.53854 | 0.64625 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 30077.39 | 2.06969 | 2.06969 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 35447.41 | 1.02184 | 1.02184 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 16135.93 | 1.11780 | 1.11780 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 16900.44 | 0.47439 | 0.47439 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 16099.33 | 1.11534 | 1.11534 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 17034.65 | 0.48034 | 0.48034 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 16136.85 | 1.11823 | 1.11823 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 17152.90 | 0.48559 | 0.48559 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 16010.90 | 1.10869 | 1.10869 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 17361.49 | 0.49485 | 0.49485 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 28513.01 | 1.95255 | 1.95255 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 34076.46 | 0.96101 | 0.96101 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 14680.98 | 1.01326 | 1.01326 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 17727.01 | 0.51107 | 0.51107 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 14598.65 | 1.00774 | 1.00774 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 17727.11 | 0.51107 | 0.51107 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 14546.39 | 1.00156 | 1.00156 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 18052.85 | 0.52553 | 0.52553 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 15268.59 | 1.06966 | 1.06966 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 20773.58 | 0.64625 | 0.64625 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.06969 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.10045 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.09677 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.08922 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.08841 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.95255 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00835 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00244 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99511 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05540 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.06969 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.06969 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.06969 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.06969 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.06969 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.06969 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.10045 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.10045 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.10045 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.10045 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.11780 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.11780 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.98448 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.09677 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.09677 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.09677 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.09677 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.11534 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.11534 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 0.98335 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.08922 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08922 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.08922 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.08922 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.11823 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.11823 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 0.97405 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.08841 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08841 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.08841 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.08841 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.10869 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.10869 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 0.98170 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.95255 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.95255 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.95255 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.95255 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.95255 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.95255 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00835 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00835 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00835 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00835 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.01326 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.01326 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.99516 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00244 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00244 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00244 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00244 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00774 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00774 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.99474 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99511 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99511 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99511 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99511 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00156 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00156 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.99356 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05540 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05540 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05540 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05540 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06966 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.06966 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 0.98667 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.06969 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.11780 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.11534 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.11823 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.10869 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.95255 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.01326 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.00774 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.00156 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.06966 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.06969 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.06969 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2214.66298 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.06969 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.06969 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.06969 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.36599 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.06969 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.03484 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.37979 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 35805.87000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17902.93500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80079 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80079 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 35805.87000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 59060.51445 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 59060.51445 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.11780 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.11780 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1237.58523 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.11780 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.11780 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.11780 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.73775 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.11780 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55890 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.74520 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 19175.16000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9587.58000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80078 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80078 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19175.16000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31008.42657 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 31008.42657 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.11534 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.11534 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1234.85501 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.11534 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.11534 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.11534 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.73612 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.11534 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55767 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.74356 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 19137.94000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9568.97000 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80068 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80068 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19137.94000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30925.49140 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 30925.49140 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.11823 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.11823 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1238.05962 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.11823 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.11823 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.11823 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.73803 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.11823 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55912 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.74549 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 19182.42000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9591.21000 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80078 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80078 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19182.42000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30755.27774 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 30755.27774 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.10869 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.10869 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1227.49791 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.10869 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.10869 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.10869 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.10869 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.10869 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55435 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.73913 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 19036.14000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9518.07000 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80046 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80046 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19036.14000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30736.99068 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 30736.99068 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.95255 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.95255 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2089.31965 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.95255 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.95255 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.95255 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.28868 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.95255 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.97627 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.30170 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 34012.09000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17006.04500 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80038 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80038 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34012.09000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 56420.06804 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 56420.06804 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.01326 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.01326 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1121.83802 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.01326 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.01326 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.01326 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.01326 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.01326 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50663 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67551 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17579.68000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8789.84000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80079 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80079 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17579.68000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28933.07730 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 28933.07730 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00774 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00774 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1115.72586 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00774 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00774 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00774 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.00774 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00774 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50387 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67183 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17496.06000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8748.03000 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80054 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80054 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17496.06000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28799.77955 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 28799.77955 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00156 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00156 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1108.88749 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00156 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00156 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00156 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.00156 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00156 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50078 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66771 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17396.56000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8698.28000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80039 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80039 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17396.56000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28634.58926 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 28634.58926 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06966 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06966 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1184.28850 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06966 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06966 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06966 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.06966 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06966 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53483 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71311 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18280.99000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9140.49500 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80011 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80011 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18280.99000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29994.00764 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 29994.00764 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 34182.9 | 11.21 | 11.21 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 18298.7 | 11.19 | 11.19 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 18263.4 | 11.19 | 11.19 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 18305.6 | 11.19 | 11.19 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 18166.8 | 11.93 | 11.93 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 32480.8 | 11.23 | 11.23 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 16785.1 | 11.96 | 11.96 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 16705.8 | 11.96 | 11.96 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 16611.1 | 11.96 | 11.96 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 17442.3 | 11.92 | 11.92 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.141 | 0.136 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.419_SHGC_0.4 | N/A | 2.381 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.203 | 0.194 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 2.6175275382E-002 | 0.1521158035 | Pass | Pass | 0.1792634050 | 0.8043611578 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 4.9409080599E-002 | 0.1215181713 | Pass | Pass | 0.4259740937 | 1.4964438036 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 2.6902104683E-002 | 0.1511141162 | Pass | Pass | 0.1531894211 | 0.7929079950 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.2451295298E-002 | 0.1796779840 | Pass | Pass | 0.1673200717 | 0.7597774575 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.7959838996E-002 | 0.2161242131 | Pass | Pass | 0.1543448705 | 0.6917380754 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.7727724283E-002 | 0.2602161841 | Pass | Pass | 3.2470300324E-002 | 9.5304602922E-002 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.7799254357E-002 | 0.2610912941 | Pass | Pass | 3.0793168966E-002 | 8.9091803929E-002 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.8971875924E-002 | 0.2685848818 | Pass | Pass | 3.0099337529E-002 | 8.7124243462E-002 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 5.4162975509E-002 | 0.2949034914 | Pass | Pass | 2.7506592835E-002 | 8.1518432822E-002 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 7.3189800816E-002 | 0.3856960948 | Pass | Pass | 2.2949579709E-002 | 7.3562918684E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3440.91 | 209.25 | 0.00 | 585.49 | 243.12 | 4478.79 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.197 | 0.203 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.381 | 0.401 | 0.442 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.381 | 0.401 | 0.442 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.381 | 0.401 | 0.442 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.381 | 0.401 | 0.442 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.381 | 0.401 | 0.442 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.381 | 0.401 | 0.442 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.381 | 0.401 | 0.442 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.381 | 0.401 | 0.442 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.381 | 0.401 | 0.442 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.381 | 0.401 | 0.442 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.381 | 0.401 | 0.442 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.381 | 0.401 | 0.442 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.419_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.381 | 0.401 | 0.442 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.381 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.381 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.992 | 2.839 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.992 | 2.839 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 13.4735 | 348.39 | 4694.00 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 83.90 | 0.0000 | Y | 73.93 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 6.6387 | 348.39 | 2312.85 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 42.32 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 13.5922 | 174.19 | 2367.67 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 85.39 | 0.0000 | Y | 37.95 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 9.5103 | 174.19 | 1656.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 30.31 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 30.25 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 7.3575 | 174.19 | 1281.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.76 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 30.25 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 7.3575 | 174.19 | 1281.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.76 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 30.25 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 7.3575 | 174.19 | 1281.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.76 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 13.4438 | 348.39 | 4683.65 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 54.16 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 8.6344 | 4180.64 | 36097.17 | 496.92 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 458.42 | AstronomicalClock | - | 42.59 | 42.59 | 3.67 | |
EXTERIOR_LIGHTS_B | 7264.83 | AstronomicalClock | - | 83.55 | 71.26 | 97.18 | |
Exterior Lighting Total | 7723.25 | 100.84 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 35805.87 | 28672.98 | 7132.89 | 0.80 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19175.16 | 15355.08 | 3820.08 | 0.80 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19137.94 | 15323.37 | 3814.57 | 0.80 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19182.42 | 15360.90 | 3821.52 | 0.80 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19036.14 | 15237.67 | 3798.47 | 0.80 | 4.12 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 34012.09 | 27222.60 | 6789.49 | 0.80 | 3.80 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17579.68 | 14077.63 | 3502.05 | 0.80 | 4.12 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17496.06 | 14006.30 | 3489.76 | 0.80 | 4.12 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17396.56 | 13924.03 | 3472.53 | 0.80 | 4.12 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18280.99 | 14626.80 | 3654.19 | 0.80 | 4.12 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 34182.9 | 11.21 | 11.21 | ||||
PSZ-AC_2:2 COOLING COIL | 18298.7 | 11.19 | 11.19 | ||||
PSZ-AC_3:3 COOLING COIL | 18263.4 | 11.19 | 11.19 | ||||
PSZ-AC_4:4 COOLING COIL | 18305.6 | 11.19 | 11.19 | ||||
PSZ-AC_5:5 COOLING COIL | 18166.8 | 11.93 | 11.93 | ||||
PSZ-AC_6:6 COOLING COIL | 32480.8 | 11.23 | 11.23 | ||||
PSZ-AC_7:7 COOLING COIL | 16785.1 | 11.96 | 11.96 | ||||
PSZ-AC_8:8 COOLING COIL | 16705.8 | 11.96 | 11.96 | ||||
PSZ-AC_9:9 COOLING COIL | 16611.1 | 11.96 | 11.96 | ||||
PSZ-AC_10:10 COOLING COIL | 17442.3 | 11.92 | 11.92 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 59060.51 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 31008.43 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 30925.49 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 30755.28 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 30736.99 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 56420.07 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 28933.08 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 28799.78 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 28634.59 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 29994.01 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.07 | 2214.66 | 1070.05 | 1.00 | 1.31 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.12 | 1237.59 | 1107.16 | 1.00 | 1.38 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.12 | 1234.86 | 1107.16 | 1.00 | 1.38 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.12 | 1238.06 | 1107.16 | 1.00 | 1.38 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.11 | 1227.50 | 1107.16 | 1.00 | 1.38 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.95 | 2089.32 | 1070.05 | 1.00 | 1.32 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.01 | 1121.84 | 1107.16 | 1.00 | 1.40 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.01 | 1115.73 | 1107.16 | 1.00 | 1.40 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1108.89 | 1107.16 | 1.00 | 1.40 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.07 | 1184.29 | 1107.16 | 1.00 | 1.39 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 23168.35 | 27802.02 | 79.80 | 1.725 | 2.070 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 23.89 | 23.89 | 0.00901 | 29.40 | 0.00882 | 0.411 | 0.00 |
SMSTORE1 | 12656.07 | 15187.29 | 87.19 | 0.917 | 1.100 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00910 | 25.45 | 0.00882 | 0.206 | 0.00 |
SMSTORE2 | 12616.31 | 15139.57 | 86.91 | 0.914 | 1.097 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00934 | 23.68 | 0.00881 | 0.206 | 0.00 |
SMSTORE3 | 12531.83 | 15038.19 | 86.33 | 0.908 | 1.089 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00933 | 23.68 | 0.00881 | 0.206 | 0.00 |
SMSTORE4 | 12522.17 | 15026.60 | 86.26 | 0.907 | 1.088 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00936 | 23.68 | 0.00881 | 0.206 | 0.00 |
LGSTORE2 | 21857.05 | 26228.46 | 75.29 | 1.627 | 1.953 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.89 | 0.00904 | 29.23 | 0.00882 | 0.411 | 0.00 |
SMSTORE5 | 11619.30 | 13943.16 | 80.04 | 0.840 | 1.008 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00927 | 25.45 | 0.00882 | 0.206 | 0.00 |
SMSTORE6 | 11552.75 | 13863.30 | 79.59 | 0.835 | 1.002 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00928 | 25.45 | 0.00882 | 0.206 | 0.00 |
SMSTORE7 | 11470.09 | 13764.10 | 79.02 | 0.829 | 0.995 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00931 | 25.45 | 0.00882 | 0.206 | 0.00 |
SMSTORE8 | 12146.17 | 14575.41 | 83.67 | 0.880 | 1.055 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00923 | 25.45 | 0.00882 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 19472.70 | 23367.24 | 67.07 | 0.852 | 1.022 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00671 | -4.20 | 0.00269 | 0.411 | 0.00 |
SMSTORE1 | 9040.11 | 10848.13 | 62.28 | 0.395 | 0.474 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00663 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE2 | 9153.60 | 10984.32 | 63.06 | 0.400 | 0.480 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00664 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE3 | 9253.60 | 11104.32 | 63.75 | 0.405 | 0.486 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00665 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE4 | 9429.99 | 11315.99 | 64.96 | 0.412 | 0.495 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00666 | -4.20 | 0.00269 | 0.206 | 0.00 |
LGSTORE2 | 18313.18 | 21975.82 | 63.08 | 0.801 | 0.961 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00675 | -4.20 | 0.00269 | 0.411 | 0.00 |
SMSTORE5 | 9739.09 | 11686.91 | 67.09 | 0.426 | 0.511 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00669 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE6 | 9739.17 | 11687.01 | 67.09 | 0.426 | 0.511 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00669 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE7 | 10014.63 | 12017.56 | 68.99 | 0.438 | 0.526 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00671 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE8 | 12315.58 | 14778.69 | 84.84 | 0.539 | 0.646 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00674 | -4.20 | 0.00269 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.07 | 2.07 | 1.02 | 1.02 | 2.0697 | 2.0697 | 2.0697 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.12 | 1.12 | 0.47 | 0.47 | 1.1178 | 1.1004 | 1.1178 | 0.9845 | 1.0000 |
PSZ-AC_3:3 | 1.12 | 1.12 | 0.48 | 0.48 | 1.1153 | 1.0968 | 1.1153 | 0.9834 | 1.0000 |
PSZ-AC_4:4 | 1.12 | 1.12 | 0.49 | 0.49 | 1.1182 | 1.0892 | 1.1182 | 0.9741 | 1.0000 |
PSZ-AC_5:5 | 1.11 | 1.11 | 0.49 | 0.49 | 1.1087 | 1.0884 | 1.1087 | 0.9817 | 1.0000 |
PSZ-AC_6:6 | 1.95 | 1.95 | 0.96 | 0.96 | 1.9525 | 1.9525 | 1.9525 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.01 | 1.01 | 0.51 | 0.51 | 1.0133 | 1.0084 | 1.0133 | 0.9952 | 1.0000 |
PSZ-AC_8:8 | 1.01 | 1.01 | 0.51 | 0.51 | 1.0077 | 1.0024 | 1.0077 | 0.9947 | 1.0000 |
PSZ-AC_9:9 | 1.00 | 1.00 | 0.53 | 0.53 | 1.0016 | 0.9951 | 1.0016 | 0.9936 | 1.0000 |
PSZ-AC_10:10 | 1.07 | 1.07 | 0.65 | 0.65 | 1.0697 | 1.0554 | 1.0697 | 0.9867 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 35805.870 | 28672.983 | 2.069690 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 17902.94 | 16555.49 | 1.379793 | 25.87 | 17.29 | 0.00897204 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 29.8218 | 23.89 | 0.00900940 | 48.0907 | 23168.35 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 59060.514 | 59060.514 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 59060.51 | 59060.51 | 2.069687 | 16.08 | 10.70 | 0.00590774 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 19.8812 | 21.11 | 0.00670613 | 42.5452 | 19472.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 19175.160 | 15355.085 | 1.117800 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 9587.58 | 8898.78 | 0.745200 | 25.82 | 17.25 | 0.00894737 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 27.6086 | 23.89 | 0.00897577 | 47.9135 | 12512.92 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 31008.427 | 31008.427 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 31008.43 | 31008.43 | 1.117803 | 16.45 | 10.85 | 0.00590308 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 18.4057 | 21.11 | 0.00662781 | 42.0531 | 9040.11 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 19137.940 | 15323.366 | 1.115340 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 9568.97 | 8880.51 | 0.743560 | 25.82 | 17.25 | 0.00894815 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 27.6695 | 23.89 | 0.00897681 | 47.9190 | 12481.93 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 30925.491 | 30925.491 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30925.49 | 30925.49 | 1.115337 | 16.44 | 10.86 | 0.00591069 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 18.4464 | 21.11 | 0.00663910 | 42.1240 | 9153.60 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 19182.420 | 15360.898 | 1.118230 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 9591.21 | 8902.16 | 0.745487 | 25.82 | 17.25 | 0.00894737 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 27.5980 | 23.89 | 0.00897576 | 47.9135 | 12513.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 30755.278 | 30755.278 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30755.28 | 30755.28 | 1.118231 | 16.45 | 10.87 | 0.00592005 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 18.3986 | 21.11 | 0.00664825 | 42.1815 | 9253.60 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 19036.140 | 15237.669 | 1.108690 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 9518.07 | 8830.90 | 0.739127 | 25.82 | 17.25 | 0.00895001 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 27.8355 | 23.89 | 0.00897931 | 47.9322 | 12407.08 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 30736.991 | 30736.991 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30736.99 | 30736.99 | 1.108692 | 16.41 | 10.86 | 0.00592722 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 18.5570 | 21.11 | 0.00666476 | 42.2851 | 9429.99 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 34012.090 | 27222.597 | 1.952550 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 17006.04 | 15680.96 | 1.301700 | 25.93 | 17.33 | 0.00899232 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 31.6109 | 23.89 | 0.00903797 | 48.2411 | 21844.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 56420.068 | 56420.068 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 56420.07 | 56420.07 | 1.952549 | 15.77 | 10.55 | 0.00589053 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 21.0739 | 21.11 | 0.00674501 | 42.7881 | 18313.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 17579.680 | 14077.632 | 1.013260 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 8789.84 | 8120.87 | 0.675507 | 25.93 | 17.31 | 0.00897973 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 30.4571 | 23.89 | 0.00902032 | 48.1480 | 11281.41 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 28933.077 | 28933.077 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28933.08 | 28933.08 | 1.013259 | 15.97 | 10.62 | 0.00587899 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.3047 | 21.11 | 0.00669140 | 42.4524 | 9739.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 17496.060 | 14006.296 | 1.007740 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 8748.03 | 8080.03 | 0.671827 | 25.93 | 17.32 | 0.00898168 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 30.6239 | 23.89 | 0.00902309 | 48.1625 | 11211.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 28799.780 | 28799.780 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28799.78 | 28799.78 | 1.007738 | 15.94 | 10.60 | 0.00587462 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.4160 | 21.11 | 0.00669150 | 42.4530 | 9739.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 17396.560 | 13924.033 | 1.001560 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 8698.28 | 8032.68 | 0.667707 | 25.94 | 17.32 | 0.00898293 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 30.8128 | 23.89 | 0.00902487 | 48.1719 | 11167.49 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 28634.589 | 28634.589 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28634.59 | 28634.59 | 1.001561 | 15.91 | 10.60 | 0.00588782 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.5419 | 21.11 | 0.00671445 | 42.5971 | 10014.63 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 18280.990 | 14626.803 | 1.069660 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 9140.50 | 8462.57 | 0.713107 | 25.77 | 17.24 | 0.00896150 | 12.80 | 11.97 | 0.00850000 | 28.88 | 0.00882066 | 18.17 | 28.8511 | 23.89 | 0.00899534 | 48.0165 | 11886.78 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 29994.008 | 29994.008 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 29994.01 | 29994.01 | 1.069665 | 16.24 | 10.82 | 0.00596112 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 19.2340 | 21.11 | 0.00674005 | 42.7598 | 12315.58 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 35805.870 | 28672.983 | 2.069690 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5186 | 1004.8586 | 1.1870 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.069687 | 2.45669946 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | Sensible | 17902.94 | 16555.49 | 1.0000 | 1.63780197 | 1.379793 | 25.87 | 17.29 | 0.00897204 | 48861.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17902.94 | 29.40 | 0.00882150 | 18.34 | 0.41147883 | 29.8218 | 23.89 | 0.00900940 | 23.89 | 0.00900940 | 48.0907 | 23168.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 59060.514 | 59060.514 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.069687 | 2.45669946 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 59060.51 | 59060.51 | 1.0000 | 2.45669946 | 2.069687 | 16.08 | 10.70 | 0.00590774 | 31104.9 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59060.51 | -4.20 | 0.00269032 | -4.20 | 0.41147883 | 19.8812 | 21.11 | 0.00670613 | 21.11 | 0.00670613 | 42.5452 | 19472.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19175.160 | 15355.085 | 1.117800 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4727 | 1004.8586 | 1.1870 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.117803 | 1.32682173 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 9587.58 | 8898.78 | 1.0000 | 0.88454553 | 0.745200 | 25.82 | 17.25 | 0.00894737 | 48746.9 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9587.58 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 27.6086 | 23.89 | 0.00897577 | 23.89 | 0.00897577 | 47.9135 | 12512.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31008.427 | 31008.427 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.117803 | 1.32682173 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 31008.43 | 31008.43 | 1.0000 | 1.32682173 | 1.117803 | 16.45 | 10.85 | 0.00590308 | 31472.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31008.43 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 18.4057 | 21.11 | 0.00662781 | 21.11 | 0.00662781 | 42.0531 | 9040.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19137.940 | 15323.366 | 1.115340 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4742 | 1004.8586 | 1.1870 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.115337 | 1.32389464 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 9568.97 | 8880.51 | 1.0000 | 0.88259887 | 0.743560 | 25.82 | 17.25 | 0.00894815 | 48751.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9568.97 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 27.6695 | 23.89 | 0.00897681 | 23.89 | 0.00897681 | 47.9190 | 12481.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30925.491 | 30925.491 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.115337 | 1.32389464 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30925.49 | 30925.49 | 1.0000 | 1.32389464 | 1.115337 | 16.44 | 10.86 | 0.00591069 | 31481.4 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30925.49 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 18.4464 | 21.11 | 0.00663910 | 21.11 | 0.00663910 | 42.1240 | 9153.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19182.420 | 15360.898 | 1.118230 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4727 | 1004.8586 | 1.1870 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.118231 | 1.32733031 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 9591.21 | 8902.16 | 1.0000 | 0.88488580 | 0.745487 | 25.82 | 17.25 | 0.00894737 | 48746.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9591.21 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 27.5980 | 23.89 | 0.00897576 | 23.89 | 0.00897576 | 47.9135 | 12513.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30755.278 | 30755.278 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.118231 | 1.32733031 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30755.28 | 30755.28 | 1.0000 | 1.32733031 | 1.118231 | 16.45 | 10.87 | 0.00592005 | 31517.4 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30755.28 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 18.3986 | 21.11 | 0.00664825 | 21.11 | 0.00664825 | 42.1815 | 9253.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19036.140 | 15237.669 | 1.108690 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4776 | 1004.8586 | 1.1870 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.108692 | 1.31600705 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 9518.07 | 8830.90 | 1.0000 | 0.87733654 | 0.739127 | 25.82 | 17.25 | 0.00895001 | 48762.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9518.07 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 27.8355 | 23.89 | 0.00897931 | 23.89 | 0.00897931 | 47.9322 | 12407.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30736.991 | 30736.991 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.108692 | 1.31600705 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30736.99 | 30736.99 | 1.0000 | 1.31600705 | 1.108692 | 16.41 | 10.86 | 0.00592722 | 31494.9 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30736.99 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 18.5570 | 21.11 | 0.00666476 | 21.11 | 0.00666476 | 42.2851 | 9429.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34012.090 | 27222.597 | 1.952550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5563 | 1004.8586 | 1.1870 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.952549 | 2.31765758 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 17006.04 | 15680.96 | 1.0000 | 1.54510590 | 1.301700 | 25.93 | 17.33 | 0.00899232 | 48981.0 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17006.04 | 29.40 | 0.00882150 | 18.34 | 0.41147883 | 31.6109 | 23.89 | 0.00903797 | 23.89 | 0.00903797 | 48.2411 | 21844.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 56420.068 | 56420.068 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.952549 | 2.31765758 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 56420.07 | 56420.07 | 1.0000 | 2.31765758 | 1.952549 | 15.77 | 10.55 | 0.00589053 | 30755.1 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 56420.07 | -4.20 | 0.00269032 | -4.20 | 0.41147883 | 21.0739 | 21.11 | 0.00674501 | 21.11 | 0.00674501 | 42.7881 | 18313.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17579.680 | 14077.632 | 1.013260 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5329 | 1004.8586 | 1.1870 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.013259 | 1.20272852 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 8789.84 | 8120.87 | 1.0000 | 0.80182019 | 0.675507 | 25.93 | 17.31 | 0.00897973 | 48942.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8789.84 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 30.4571 | 23.89 | 0.00902032 | 23.89 | 0.00902032 | 48.1480 | 11281.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28933.077 | 28933.077 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.013259 | 1.20272852 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28933.08 | 28933.08 | 1.0000 | 1.20272852 | 1.013259 | 15.97 | 10.62 | 0.00587899 | 30923.5 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28933.08 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 20.3047 | 21.11 | 0.00669140 | 21.11 | 0.00669140 | 42.4524 | 9739.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17496.060 | 14006.296 | 1.007740 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5365 | 1004.8586 | 1.1870 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.007738 | 1.19617564 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 8748.03 | 8080.03 | 1.0000 | 0.79745206 | 0.671827 | 25.93 | 17.32 | 0.00898168 | 48954.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8748.03 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 30.6239 | 23.89 | 0.00902309 | 23.89 | 0.00902309 | 48.1625 | 11211.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28799.780 | 28799.780 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.007738 | 1.19617564 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28799.78 | 28799.78 | 1.0000 | 1.19617564 | 1.007738 | 15.94 | 10.60 | 0.00587462 | 30883.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28799.78 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 20.4160 | 21.11 | 0.00669150 | 21.11 | 0.00669150 | 42.4530 | 9739.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17396.560 | 13924.033 | 1.001560 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5388 | 1004.8586 | 1.1870 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.001561 | 1.18884419 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 8698.28 | 8032.68 | 1.0000 | 0.79256166 | 0.667707 | 25.94 | 17.32 | 0.00898293 | 48962.3 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8698.28 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 30.8128 | 23.89 | 0.00902487 | 23.89 | 0.00902487 | 48.1719 | 11167.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28634.589 | 28634.589 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.001561 | 1.18884419 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28634.59 | 28634.59 | 1.0000 | 1.18884419 | 1.001561 | 15.91 | 10.60 | 0.00588782 | 30884.9 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28634.59 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 20.5419 | 21.11 | 0.00671445 | 21.11 | 0.00671445 | 42.5971 | 10014.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18280.990 | 14626.803 | 1.069660 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4990 | 1004.8586 | 1.1870 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.069665 | 1.26968201 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 9140.50 | 8462.57 | 1.0000 | 0.84645104 | 0.713107 | 25.77 | 17.24 | 0.00896150 | 48734.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9140.50 | 28.88 | 0.00882066 | 18.17 | 0.20573941 | 28.8511 | 23.89 | 0.00899534 | 23.89 | 0.00899534 | 48.0165 | 11886.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29994.008 | 29994.008 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.069665 | 1.26968201 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 29994.01 | 29994.01 | 1.0000 | 1.26968201 | 1.069665 | 16.24 | 10.82 | 0.00596112 | 31406.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29994.01 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 19.2340 | 21.11 | 0.00674005 | 21.11 | 0.00674005 | 42.7598 | 12315.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.07 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.12 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.12 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.12 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.11 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.95 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.01 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.01 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.00 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.07 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 1627.67 | 3660.00 | 283.00 |
SMSTORE1 | 1509.17 | 3215.83 | 15.50 |
SMSTORE2 | 1224.83 | 2591.83 | 72.50 |
SMSTORE3 | 1232.50 | 2626.00 | 102.50 |
SMSTORE4 | 1251.00 | 2567.67 | 141.00 |
LGSTORE2 | 1097.33 | 2643.00 | 278.50 |
SMSTORE5 | 1043.83 | 2557.00 | 286.17 |
SMSTORE6 | 1055.67 | 2580.17 | 318.17 |
SMSTORE7 | 1106.67 | 2671.50 | 420.17 |
SMSTORE8 | 1494.67 | 2851.67 | 893.67 |
Facility | 2669.33 | 4109.17 | 1072.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 2.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 6.67 | 0.00 | 0.00 | 0.00 |
Facility | 9.00 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 1.044 | 0.230 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.977 | 0.245 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 1.110 | 0.320 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 1.107 | 0.320 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 1.299 | 0.320 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 1.035 | 0.307 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 1.238 | 0.341 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 1.230 | 0.341 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 1.205 | 0.341 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 1.199 | 0.359 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 0.808 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.47 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.76 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.91 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 10831669.86 | 0.00 | 10831669.86 | 2751432.93 | 13583102.79 | 12976396.34 | 3173.10 | 3895.56 | 1691.35 | 30.03 |
SMSTORE1 | 5069061.86 | 0.00 | 5069061.86 | 1379627.48 | 6448689.34 | 6488198.17 | 4176.32 | 2680.12 | 1903.56 | 37.97 |
SMSTORE2 | 4377999.10 | 0.00 | 4377999.10 | 1417008.46 | 5795007.57 | 6488198.17 | 4349.03 | 3140.17 | 1270.80 | 119.50 |
SMSTORE3 | 4364932.71 | 0.00 | 4364932.71 | 1417008.46 | 5781941.18 | 6488198.17 | 4349.03 | 3161.17 | 1249.80 | 116.78 |
SMSTORE4 | 5131194.30 | 0.00 | 5131194.30 | 1417008.46 | 6548202.77 | 6488198.17 | 4336.88 | 3017.50 | 1405.62 | 140.42 |
LGSTORE2 | 7459885.48 | 0.00 | 7459885.48 | 2601582.32 | 10061467.80 | 12976396.34 | 4720.08 | 3024.25 | 1015.67 | 91.00 |
SMSTORE5 | 4481345.73 | 0.00 | 4481345.73 | 1426750.59 | 5908096.33 | 6488198.17 | 4711.57 | 2849.85 | 1198.58 | 119.97 |
SMSTORE6 | 4448015.03 | 0.00 | 4448015.03 | 1426750.59 | 5874765.62 | 6488198.17 | 4714.12 | 2867.92 | 1177.96 | 117.19 |
SMSTORE7 | 4350919.78 | 0.00 | 4350919.78 | 1426750.59 | 5777670.38 | 6488198.17 | 4718.18 | 2939.17 | 1102.65 | 100.00 |
SMSTORE8 | 4309915.35 | 0.00 | 4309915.35 | 1741532.12 | 6051447.47 | 6488198.17 | 4719.22 | 3043.50 | 997.28 | 46.06 |
Total Facility | 54824939.20 | 0.00 | 54824939.20 | 17005452.03 | 71830391.23 | 77858378.04 | 4722.82 | 4442.69 | 2184.89 | 269.59 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.5144 | 0.0000 | 0.5144 | 0.1134 | 0.6278 | 0.4115 | 254.65 | 3895.56 | 1689.79 |
SMSTORE1 | 0.2403 | 0.0000 | 0.2403 | 0.0605 | 0.3008 | 0.2057 | 1261.54 | 2680.04 | 1898.42 |
SMSTORE2 | 0.2734 | 0.0000 | 0.2734 | 0.0789 | 0.3523 | 0.2057 | 0.00 | 3139.83 | 1255.17 |
SMSTORE3 | 0.2727 | 0.0000 | 0.2727 | 0.0789 | 0.3516 | 0.2057 | 0.00 | 3160.42 | 1234.58 |
SMSTORE4 | 0.3195 | 0.0000 | 0.3195 | 0.0789 | 0.3984 | 0.2057 | 0.00 | 3016.17 | 1378.83 |
LGSTORE2 | 0.5098 | 0.0000 | 0.5098 | 0.1515 | 0.6613 | 0.4115 | 0.00 | 3024.08 | 1005.92 |
SMSTORE5 | 0.3047 | 0.0000 | 0.3047 | 0.0841 | 0.3888 | 0.2057 | 0.00 | 2849.17 | 1180.83 |
SMSTORE6 | 0.3026 | 0.0000 | 0.3026 | 0.0841 | 0.3868 | 0.2057 | 0.00 | 2867.17 | 1162.83 |
SMSTORE7 | 0.2967 | 0.0000 | 0.2967 | 0.0841 | 0.3809 | 0.2057 | 0.00 | 2938.83 | 1091.17 |
SMSTORE8 | 0.2952 | 0.0000 | 0.2952 | 0.0886 | 0.3838 | 0.2057 | 0.00 | 3043.50 | 986.50 |
Total Facility | 3.3295 | 0.0000 | 3.3295 | 0.9031 | 4.2326 | 2.4689 | 1372.21 | 4438.60 | 2160.49 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 15261612.33 | 0.00 | 15261612.33 | 12976396.34 | 3166.79 | 0.42 | 5592.79 | 30.03 |
PSZ-AC_2:2 | 7142131.88 | 0.00 | 7142131.88 | 6488198.17 | 4081.59 | 5.41 | 4673.00 | 37.81 |
PSZ-AC_3:3 | 6168479.50 | 0.00 | 6168479.50 | 6488198.17 | 4334.78 | 0.75 | 4424.47 | 119.33 |
PSZ-AC_4:4 | 6150068.65 | 0.00 | 6150068.65 | 6488198.17 | 4335.42 | 1.17 | 4423.42 | 116.62 |
PSZ-AC_5:5 | 7229581.43 | 0.00 | 7229581.43 | 6488198.17 | 4312.84 | 0.87 | 4446.28 | 140.09 |
PSZ-AC_6:6 | 10510846.97 | 0.00 | 10510846.97 | 12976396.34 | 4716.50 | 0.33 | 4043.17 | 91.00 |
PSZ-AC_7:7 | 6313979.16 | 0.00 | 6313979.16 | 6488198.17 | 4693.74 | 1.37 | 4064.89 | 119.89 |
PSZ-AC_8:8 | 6267017.96 | 0.00 | 6267017.96 | 6488198.17 | 4697.32 | 0.75 | 4061.93 | 116.89 |
PSZ-AC_9:9 | 6130215.90 | 0.00 | 6130215.90 | 6488198.17 | 4707.87 | 0.83 | 4051.29 | 100.00 |
PSZ-AC_10:10 | 6072442.82 | 0.00 | 6072442.82 | 6488198.17 | 4715.51 | 0.21 | 4044.28 | 46.06 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.7248 | 0.0000 | 0.7248 | 0.4115 | 249.35 | 0.25 | 5590.40 |
PSZ-AC_2:2 | 0.3386 | 0.0000 | 0.3386 | 0.2057 | 1171.98 | 4.75 | 4663.28 |
PSZ-AC_3:3 | 0.3853 | 0.0000 | 0.3853 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3843 | 0.0000 | 0.3843 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.4502 | 0.0000 | 0.4502 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.7183 | 0.0000 | 0.7183 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.4293 | 0.0000 | 0.4293 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.4264 | 0.0000 | 0.4264 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.4181 | 0.0000 | 0.4181 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.4160 | 0.0000 | 0.4160 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 4812.29 | 863.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 3746.56 | 1417.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 3847.73 | 666.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 3862.23 | 649.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 3568.26 | 966.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3661.22 | 459.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3372.61 | 777.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3383.69 | 763.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3430.47 | 699.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3490.22 | 585.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.7273 | 0.8804 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.3871 | 0.3823 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3704 | 0.4896 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3694 | 0.4920 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.4140 | 0.6068 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.7001 | 0.8990 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3998 | 0.5804 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3975 | 0.5777 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3899 | 0.5796 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3878 | 0.5989 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 759 |
Defaulted Fields | 823 |
Fields with Defaults | 2681 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 980.42 | 3274.06 | 16-JAN-08:00 | 83988.27 | 29-AUG-14:50 |
Electricity:Building | 625.08 | 2063.06 | 01-JAN-00:10 | 38863.50 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 142.50 | 391.26 | 01-JAN-00:10 | 7378.51 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 625.08 | 2063.06 | 01-JAN-00:10 | 38863.50 | 01-JAN-11:10 |
InteriorLights:Electricity | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 116.25 | 317.63 | 01-JAN-00:10 | 6035.26 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 116.25 | 317.63 | 01-JAN-00:10 | 6035.26 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 81.39 | 223.36 | 01-JAN-00:10 | 4215.80 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 68.27 | 186.54 | 01-JAN-00:10 | 3544.17 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 68.27 | 186.54 | 01-JAN-00:10 | 3544.17 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 59.43 | 204.26 | 01-JAN-00:10 | 3853.00 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 59.43 | 204.26 | 01-JAN-00:10 | 3853.00 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 59.43 | 204.26 | 01-JAN-00:10 | 3853.00 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 73.33 | 274.94 | 01-JAN-00:10 | 5168.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 54.16 | 201.30 | 01-JAN-00:10 | 3825.14 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 54.16 | 201.30 | 01-JAN-00:10 | 3825.14 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 980.42 | 3274.06 | 16-JAN-08:00 | 83988.27 | 29-AUG-14:50 |
ElectricityPurchased:Plant | 980.42 | 3274.06 | 16-JAN-08:00 | 83988.27 | 29-AUG-14:50 |
Cogeneration:ElectricityPurchased | 980.42 | 3274.06 | 16-JAN-08:00 | 83988.27 | 29-AUG-14:50 |
General:Cogeneration:ElectricityPurchased | 980.42 | 3274.06 | 16-JAN-08:00 | 83988.27 | 29-AUG-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 980.42 | 3274.06 | 16-JAN-08:00 | 83988.27 | 29-AUG-14:50 |
ElectricityNet:Plant | 980.42 | 3274.06 | 16-JAN-08:00 | 83988.27 | 29-AUG-14:50 |
Cogeneration:ElectricityNet | 980.42 | 3274.06 | 16-JAN-08:00 | 83988.27 | 29-AUG-14:50 |
General:Cogeneration:ElectricityNet | 980.42 | 3274.06 | 16-JAN-08:00 | 83988.27 | 29-AUG-14:50 |
Electricity:HVAC | 190.35 | 0.00 | 01-JAN-00:10 | 39802.48 | 29-AUG-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 36.79 | 0.00 | 01-JAN-00:10 | 30114.04 | 29-AUG-15:00 |
General:Cooling:Electricity | 36.79 | 0.00 | 01-JAN-00:10 | 30114.04 | 29-AUG-15:00 |
Fans:Electricity | 153.56 | 0.00 | 01-JAN-00:10 | 10225.13 | 19-FEB-09:10 |
General:Fans:Electricity | 153.56 | 0.00 | 01-JAN-00:10 | 10225.13 | 19-FEB-09:10 |
ExteriorLights:Electricity | 100.84 | 0.00 | 01-JAN-08:10 | 7723.25 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 100.84 | 0.00 | 01-JAN-08:10 | 7723.25 | 01-JAN-06:10 |
Electricity:Plant | 64.15 | 1211.00 | 01-JAN-08:10 | 11853.16 | 04-JAN-13:30 |
WaterSystems:Electricity | 64.15 | 1211.00 | 01-JAN-08:10 | 11853.16 | 04-JAN-13:30 |
Water Heater:WaterSystems:Electricity | 64.15 | 1211.00 | 01-JAN-08:10 | 11853.16 | 04-JAN-13:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 250.89 | 0.00 | 01-JAN-00:10 | 137988.08 | 16-JAN-09:10 |
NaturalGas:HVAC | 250.89 | 0.00 | 01-JAN-00:10 | 137988.08 | 16-JAN-09:10 |
Heating:NaturalGas | 250.89 | 0.00 | 01-JAN-00:10 | 137988.08 | 16-JAN-09:10 |
General:Heating:NaturalGas | 250.89 | 0.00 | 01-JAN-00:10 | 137988.08 | 16-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 779.99 | 0.00 | 01-JAN-00:10 | 212060.75 | 29-AUG-15:00 |
EnergyTransfer:Building | 423.13 | 0.00 | 01-JAN-00:10 | 93301.85 | 26-DEC-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 93.16 | 0.00 | 01-JAN-00:10 | 19556.85 | 19-FEB-08:10 |
Heating:EnergyTransfer | 53.43 | 0.00 | 01-JAN-00:10 | 93293.48 | 26-DEC-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 6.16 | 0.00 | 01-JAN-00:10 | 19556.85 | 19-FEB-08:10 |
General:Heating:EnergyTransfer | 53.43 | 0.00 | 01-JAN-00:10 | 93293.48 | 26-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 6.16 | 0.00 | 01-JAN-00:10 | 19556.85 | 19-FEB-08:10 |
Cooling:EnergyTransfer | 369.70 | 0.00 | 01-JAN-00:10 | 87837.36 | 10-AUG-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 87.00 | 0.00 | 01-JAN-00:10 | 15273.17 | 10-AUG-16:30 |
General:Cooling:EnergyTransfer | 369.70 | 0.00 | 01-JAN-00:10 | 87837.36 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 87.00 | 0.00 | 01-JAN-00:10 | 15273.17 | 10-AUG-16:30 |
EnergyTransfer:Zone:SMSTORE1 | 50.71 | 0.00 | 01-JAN-00:10 | 8489.03 | 18-JUN-17:20 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 1.06 | 0.00 | 01-JAN-00:10 | 5545.34 | 19-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 1.06 | 0.00 | 01-JAN-00:10 | 5545.34 | 19-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 49.65 | 0.00 | 01-JAN-00:10 | 8489.03 | 18-JUN-17:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 49.65 | 0.00 | 01-JAN-00:10 | 8489.03 | 18-JUN-17:20 |
EnergyTransfer:Zone:SMSTORE2 | 38.13 | 0.00 | 01-JAN-00:10 | 7804.82 | 10-AUG-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 2.02 | 0.00 | 01-JAN-00:10 | 7551.05 | 19-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 2.02 | 0.00 | 01-JAN-00:10 | 7551.05 | 19-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 36.11 | 0.00 | 01-JAN-00:10 | 7804.82 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 36.11 | 0.00 | 01-JAN-00:10 | 7804.82 | 10-AUG-16:10 |
EnergyTransfer:Zone:SMSTORE3 | 37.51 | 0.00 | 01-JAN-00:10 | 8182.86 | 19-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 2.52 | 0.00 | 01-JAN-00:10 | 8178.41 | 19-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 2.52 | 0.00 | 01-JAN-00:10 | 8178.41 | 19-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 34.99 | 0.00 | 01-JAN-00:10 | 7800.75 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 34.99 | 0.00 | 01-JAN-00:10 | 7800.75 | 10-AUG-16:10 |
EnergyTransfer:Zone:SMSTORE4 | 33.72 | 0.00 | 01-JAN-00:10 | 8974.17 | 16-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 3.54 | 0.00 | 01-JAN-00:10 | 8974.17 | 16-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 3.54 | 0.00 | 01-JAN-00:10 | 8974.17 | 16-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 30.18 | 0.00 | 01-JAN-00:10 | 7673.17 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 30.18 | 0.00 | 01-JAN-00:10 | 7673.17 | 10-AUG-16:10 |
EnergyTransfer:Zone:LGSTORE2 | 57.39 | 0.00 | 01-JAN-00:10 | 20737.22 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 7.92 | 0.00 | 01-JAN-00:10 | 20737.22 | 16-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 7.92 | 0.00 | 01-JAN-00:10 | 20737.22 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 49.47 | 0.00 | 01-JAN-00:10 | 13651.01 | 10-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 49.47 | 0.00 | 01-JAN-00:10 | 13651.01 | 10-AUG-14:50 |
EnergyTransfer:Zone:SMSTORE5 | 27.87 | 0.00 | 01-JAN-00:10 | 10931.74 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 5.01 | 0.00 | 01-JAN-00:10 | 10931.74 | 16-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 5.01 | 0.00 | 01-JAN-00:10 | 10931.74 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 22.86 | 0.00 | 01-JAN-00:10 | 7106.27 | 10-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 22.86 | 0.00 | 01-JAN-00:10 | 7106.27 | 10-AUG-14:50 |
EnergyTransfer:Zone:SMSTORE6 | 27.58 | 0.00 | 01-JAN-00:10 | 11183.26 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 5.30 | 0.00 | 01-JAN-00:10 | 11183.26 | 16-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 5.30 | 0.00 | 01-JAN-00:10 | 11183.26 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 22.28 | 0.00 | 01-JAN-00:10 | 7050.20 | 10-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 22.28 | 0.00 | 01-JAN-00:10 | 7050.20 | 10-AUG-14:50 |
EnergyTransfer:Zone:SMSTORE7 | 26.97 | 0.00 | 01-JAN-00:10 | 12231.06 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 6.65 | 0.00 | 01-JAN-00:10 | 12231.06 | 16-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 6.65 | 0.00 | 01-JAN-00:10 | 12231.06 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 20.31 | 0.00 | 01-JAN-00:10 | 6984.94 | 10-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 20.31 | 0.00 | 01-JAN-00:10 | 6984.94 | 10-AUG-14:50 |
EnergyTransfer:Zone:SMSTORE8 | 30.09 | 0.00 | 01-JAN-00:10 | 16745.22 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 13.24 | 0.00 | 01-JAN-00:10 | 16745.22 | 16-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 13.24 | 0.00 | 01-JAN-00:10 | 16745.22 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 16.86 | 0.00 | 01-JAN-00:10 | 7355.94 | 10-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 16.86 | 0.00 | 01-JAN-00:10 | 7355.94 | 10-AUG-14:50 |
EnergyTransfer:HVAC | 356.86 | 0.00 | 01-JAN-00:10 | 128554.81 | 29-AUG-14:50 |
HeatingCoils:EnergyTransfer | 200.71 | 0.00 | 01-JAN-00:10 | 110390.46 | 16-JAN-09:10 |
CoolingCoils:EnergyTransfer | 156.15 | 0.00 | 01-JAN-00:10 | 128554.81 | 29-AUG-14:50 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 6.164 | -86.999 | 0.000 | 0.000 | 25.225 | 116.248 | 26.249 | 20.791 | 0.000 | 0.453 | 0.001 | 0.000 | -10.363 | 0.000 | -31.901 | -65.867 |
SMSTORE1 | 0.000 | 0.000 | 1.064 | -49.646 | 0.000 | 0.000 | 12.328 | 68.266 | 13.125 | 10.277 | 0.000 | 0.246 | 0.001 | 0.000 | -5.518 | 0.000 | -16.023 | -34.119 |
SMSTORE2 | 0.000 | 0.000 | 2.022 | -36.106 | 0.000 | 0.000 | 7.547 | 49.007 | 10.421 | 10.276 | 0.000 | 0.240 | 0.000 | 0.000 | -5.419 | 0.000 | -16.398 | -21.590 |
SMSTORE3 | 0.000 | 0.000 | 2.520 | -34.990 | 0.000 | 0.000 | 7.559 | 49.007 | 10.421 | 10.291 | 0.000 | 0.240 | 0.000 | 0.000 | -5.356 | 0.000 | -16.323 | -23.368 |
SMSTORE4 | 0.000 | 0.000 | 3.544 | -30.176 | 0.000 | 0.000 | 7.524 | 49.007 | 10.421 | 10.297 | 0.000 | 0.240 | 0.002 | 0.000 | -5.309 | 0.000 | -16.413 | -29.134 |
LGSTORE2 | 0.000 | 0.000 | 7.918 | -49.472 | 0.000 | 0.000 | 26.171 | 54.161 | 19.173 | 20.782 | 0.000 | 0.433 | 0.002 | 0.000 | -10.158 | 0.000 | -29.453 | -39.555 |
SMSTORE5 | 0.000 | 0.000 | 5.007 | -22.858 | 0.000 | 0.000 | 13.000 | 27.807 | 9.586 | 10.356 | 0.000 | 0.241 | 0.003 | 0.000 | -5.101 | 0.000 | -16.257 | -21.779 |
SMSTORE6 | 0.000 | 0.000 | 5.300 | -22.284 | 0.000 | 0.000 | 13.009 | 27.807 | 9.586 | 10.366 | 0.000 | 0.241 | 0.003 | 0.000 | -5.077 | 0.000 | -16.225 | -22.722 |
SMSTORE7 | 0.000 | 0.000 | 6.654 | -20.315 | 0.000 | 0.000 | 13.052 | 27.807 | 9.586 | 10.402 | 0.000 | 0.241 | 0.001 | 0.000 | -4.979 | 0.000 | -16.082 | -26.367 |
SMSTORE8 | 0.000 | 0.000 | 13.237 | -16.855 | 0.000 | 0.000 | 13.130 | 27.807 | 9.586 | 10.501 | 0.000 | 0.250 | 0.004 | 0.000 | -4.625 | 0.000 | -19.709 | -33.321 |
Total Facility | 0.000 | 0.000 | 53.429 | -369.701 | 0.000 | 0.000 | 138.544 | 496.921 | 128.154 | 124.338 | 0.000 | 2.826 | 0.017 | 0.000 | -61.905 | 0.000 | -194.783 | -317.823 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 10-AUG-07:03 | 0.00 | 0.00 | 0.00 | -27950.96 | 0.00 | 0.00 | 182.11 | 317.63 | 74.62 | 146.13 | 0.00 | 0.00 | 27413.25 | 0.00 | -0.00 | 0.00 | -182.78 | 0.00 |
SMSTORE1 | 24-JUL-07:03 | 0.00 | 0.00 | 0.00 | -17592.60 | 0.00 | 0.00 | 88.83 | 186.54 | 37.31 | 110.52 | 0.00 | 0.00 | 17269.60 | 0.00 | -0.00 | 0.00 | -100.20 | 0.00 |
SMSTORE2 | 14-AUG-06:02 | 0.00 | 0.00 | 0.00 | -19294.36 | 0.00 | 0.00 | 0.00 | 167.44 | 36.82 | 0.00 | 0.00 | 0.00 | 19219.57 | 0.00 | -109.37 | 0.00 | -20.10 | 0.00 |
SMSTORE3 | 14-AUG-06:02 | 0.00 | 0.00 | 0.00 | -19396.00 | 0.00 | 0.00 | 0.00 | 167.44 | 36.82 | 0.00 | 0.00 | 0.00 | 19322.43 | 0.00 | -110.48 | 0.00 | -20.21 | 0.00 |
SMSTORE4 | 14-AUG-06:02 | 0.00 | 0.00 | 0.00 | -19127.74 | 0.00 | 0.00 | 0.00 | 167.44 | 36.82 | 0.00 | 0.00 | 0.00 | 19052.33 | 0.00 | -108.84 | 0.00 | -20.02 | 0.00 |
LGSTORE2 | 14-AUG-07:03 | 0.00 | 0.00 | 0.00 | -31445.89 | 0.00 | 0.00 | 0.00 | 201.30 | 73.64 | 142.84 | 0.00 | 0.00 | 31331.63 | 0.00 | -0.00 | 0.00 | -303.53 | 0.00 |
SMSTORE5 | 14-AUG-07:03 | 0.00 | 0.00 | 0.00 | -15250.07 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 72.12 | 0.00 | 0.00 | 15205.06 | 0.00 | -0.00 | 0.00 | -167.29 | 0.00 |
SMSTORE6 | 14-AUG-07:03 | 0.00 | 0.00 | 0.00 | -14663.61 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 73.12 | 0.00 | 0.00 | 14617.50 | 0.00 | -0.00 | 0.00 | -167.19 | 0.00 |
SMSTORE7 | 14-AUG-07:03 | 0.00 | 0.00 | 0.00 | -12669.55 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 75.99 | 0.00 | 0.00 | 12620.24 | 0.00 | -0.00 | 0.00 | -166.86 | 0.00 |
SMSTORE8 | 10-AUG-14:40 | 0.00 | 0.00 | 0.00 | -7355.62 | 0.00 | 0.00 | 1359.36 | 1963.83 | 671.63 | 1752.53 | 0.00 | 966.94 | 641.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-07:03 | 0.00 | 0.00 | 0.00 | -130968.68 | 0.00 | 0.00 | 566.66 | 6142.12 | 1452.23 | 1416.60 | 0.00 | 0.00 | 122542.62 | 0.00 | 0.00 | 0.00 | -1151.55 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-JAN-08:61 | 0.00 | 0.00 | 59171.37 | 0.00 | 0.00 | 0.00 | 0.00 | 317.63 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -438.94 | 0.00 | -916.87 | -58206.82 |
SMSTORE1 | 07-JAN-08:61 | 0.00 | 0.00 | 31049.29 | 0.00 | 0.00 | 0.00 | 0.00 | 186.54 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -390.48 | 0.00 | -622.52 | -30259.63 |
SMSTORE2 | 19-FEB-08:61 | 0.00 | 0.00 | 30954.41 | 0.00 | 0.00 | 0.00 | 0.00 | 167.44 | 37.31 | 421.70 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -673.78 | -30907.09 |
SMSTORE3 | 19-FEB-08:61 | 0.00 | 0.00 | 30791.45 | 0.00 | 0.00 | 0.00 | 0.00 | 167.44 | 37.31 | 427.54 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -665.94 | -30757.81 |
SMSTORE4 | 19-FEB-08:61 | 0.00 | 0.00 | 30774.43 | 0.00 | 0.00 | 0.00 | 0.00 | 167.44 | 37.31 | 432.93 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -658.21 | -30753.90 |
LGSTORE2 | 17-JAN-08:61 | 0.00 | 0.00 | 56615.12 | 0.00 | 0.00 | 0.00 | 0.00 | 201.30 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -538.73 | 0.00 | -756.66 | -55594.67 |
SMSTORE5 | 17-JAN-08:61 | 0.00 | 0.00 | 29049.28 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -269.81 | 0.00 | -418.06 | -28501.60 |
SMSTORE6 | 17-JAN-08:61 | 0.00 | 0.00 | 28918.89 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -267.50 | 0.00 | -415.37 | -28376.20 |
SMSTORE7 | 17-JAN-08:61 | 0.00 | 0.00 | 28762.82 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -258.09 | 0.00 | -403.63 | -28241.28 |
SMSTORE8 | 16-JAN-09:13 | 0.00 | 0.00 | 30104.20 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -141.79 | 0.00 | -675.56 | -29427.03 |
Total Facility | 26-DEC-08:61 | 0.00 | 0.00 | 271133.49 | 0.00 | 0.00 | 0.00 | 725.41 | 6142.12 | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4708.24 | 0.00 | -6320.31 | -268424.70 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0697 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0697 | 0.1988 | 1.0000 | Not calculated | 0.4115 | 0.1988 | ||
PSZ-AC_2:2 | 1.1004 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1178 | 0.1841 | 1.0000 | Not calculated | 0.2057 | 0.1841 | ||
PSZ-AC_3:3 | 1.0968 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1153 | 0.1845 | 1.0000 | Not calculated | 0.2057 | 0.1845 | ||
PSZ-AC_4:4 | 1.0892 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1182 | 0.1840 | 1.0000 | Not calculated | 0.2057 | 0.1840 | ||
PSZ-AC_5:5 | 1.0884 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1087 | 0.1856 | 1.0000 | Not calculated | 0.2057 | 0.1856 | ||
PSZ-AC_6:6 | 1.9525 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9525 | 0.2107 | 1.0000 | Not calculated | 0.4115 | 0.2107 | ||
PSZ-AC_7:7 | 1.0084 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0133 | 0.2030 | 1.0000 | Not calculated | 0.2057 | 0.2030 | ||
PSZ-AC_8:8 | 1.0024 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0077 | 0.2042 | 1.0000 | Not calculated | 0.2057 | 0.2042 | ||
PSZ-AC_9:9 | 0.9951 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0016 | 0.2054 | 1.0000 | Not calculated | 0.2057 | 0.2054 | ||
PSZ-AC_10:10 | 1.0554 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0697 | 0.1923 | 1.0000 | Not calculated | 0.2057 | 0.1923 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0697 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0697 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1988 | ||
PSZ-AC_2:2 | 1.1004 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1004 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1870 | ||
PSZ-AC_3:3 | 1.0968 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0968 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1876 | ||
PSZ-AC_4:4 | 1.0892 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0892 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1889 | ||
PSZ-AC_5:5 | 1.0884 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0884 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1890 | ||
PSZ-AC_6:6 | 1.9525 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9525 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2107 | ||
PSZ-AC_7:7 | 1.0084 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0084 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2040 | ||
PSZ-AC_8:8 | 1.0024 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0024 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2052 | ||
PSZ-AC_9:9 | 0.9951 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9951 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2068 | ||
PSZ-AC_10:10 | 1.0554 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0554 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1949 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0697 | 2.0697 | 2.0697 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1004 | 1.1004 | 1.1004 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0968 | 1.0968 | 1.0968 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0892 | 1.0892 | 1.0892 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0884 | 1.0884 | 1.0884 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9525 | 1.9525 | 1.9525 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0084 | 1.0084 | 1.0084 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0024 | 1.0024 | 1.0024 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9951 | 0.9951 | 0.9951 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0554 | 1.0554 | 1.0554 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0697 | 2.0697 | 2.0697 | 2.0697 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1004 | 1.1178 | 1.1004 | 1.1004 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0968 | 1.1153 | 1.0968 | 1.0968 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0892 | 1.1182 | 1.0892 | 1.0892 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0884 | 1.1087 | 1.0884 | 1.0884 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.9525 | 1.9525 | 1.9525 | 1.9525 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0084 | 1.0133 | 1.0084 | 1.0084 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0024 | 1.0077 | 1.0024 | 1.0024 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9951 | 1.0016 | 0.9951 | 0.9951 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0554 | 1.0697 | 1.0554 | 1.0554 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0697 | 2.0697 | 2.0697 | No | 0.4115 | 0.4027 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1004 | 1.1004 | 1.1004 | No | 0.2057 | 0.4337 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0968 | 1.0968 | 1.0968 | No | 0.2057 | 0.4283 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0892 | 1.0892 | 1.0892 | No | 0.2057 | 0.4237 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0884 | 1.0884 | 1.0884 | No | 0.2057 | 0.4158 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9525 | 1.9525 | 1.9525 | No | 0.4115 | 0.4282 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0084 | 1.0084 | 1.0084 | No | 0.2057 | 0.4026 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0024 | 1.0024 | 1.0024 | No | 0.2057 | 0.4026 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9951 | 0.9951 | 0.9951 | No | 0.2057 | 0.3915 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0554 | 1.0554 | 1.0554 | No | 0.2057 | 0.3184 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0697 | 2.0697 | 2.0697 | 2.0697 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1004 | 1.1004 | 1.1004 | 1.1004 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0968 | 1.0968 | 1.0968 | 1.0968 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0892 | 1.0892 | 1.0892 | 1.0892 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0884 | 1.0884 | 1.0884 | 1.0884 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.9525 | 1.9525 | 1.9525 | 1.9525 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0084 | 1.0084 | 1.0084 | 1.0084 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0024 | 1.0024 | 1.0024 | 1.0024 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9951 | 0.9951 | 0.9951 | 0.9951 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0554 | 1.0554 | 1.0554 | 1.0554 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 250.89 | 137988.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 36.79 | 30114.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 496.92 | 30804.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 100.84 | 7723.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 153.56 | 10225.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 64.15 | 11853.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 980.42 |
Natural Gas | 0.00 | 250.89 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1231.31 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 237.73 |
Space Heating | 0.00 |
Space Cooling | 17.60 |
Fans (All) | 73.46 |
Service Water Heating | 30.69 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 469.03 |
Subtotal | 469.03 |
Natural Gas [MJ/m2] | |
Space Heating | 120.02 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 120.02 |
Subtotal | 120.02 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 40.36 |
Space Heating | 20.38 |
Space Cooling | 2.99 |
Fans (All) | 12.47 |
Service Water Heating | 5.21 |
Receptacle Equipment | 10.41 |
Miscellaneous | 8.19 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8753.50 | 6.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8751.33 | 8.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8757.17 | 2.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8757.33 | 2.67 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
Min | 8751.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 8.67 | 0.00 | 0.00 | 0.00 |
Average | 8756.53 | 3.47 | 0.00 | 0.00 | 0.00 |
Sum | 87565.33 | 34.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25473.67 | 1.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25473.67 | 1.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25471.67 | 3.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93206.00 | 5.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45909.00 | 3.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45909.00 | 3.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45909.00 | 3.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45909.00 | 3.00 | 0.00 | 0.00 | 0.00 |
Min | 25471.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93206.00 | 5.00 | 0.00 | 0.00 | 0.00 |
Average | 48607.90 | 2.30 | 0.00 | 0.00 | 0.00 |
Sum | 486079.00 | 23.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8733.50 | 26.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8733.00 | 27.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8726.83 | 33.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8744.17 | 15.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8743.00 | 17.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8743.67 | 16.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8746.00 | 14.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8750.00 | 10.00 | 0.00 | 0.00 | 0.00 |
Min | 8726.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 33.17 | 0.00 | 0.00 | 0.00 |
Average | 8744.02 | 15.98 | 0.00 | 0.00 | 0.00 |
Sum | 87440.17 | 159.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25471.67 | 3.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25471.67 | 3.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25467.67 | 7.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93200.00 | 11.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45903.00 | 9.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45903.50 | 8.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45903.50 | 8.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45903.50 | 8.50 | 0.00 | 0.00 | 0.00 |
Min | 25467.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93200.00 | 11.00 | 0.00 | 0.00 | 0.00 |
Average | 48604.25 | 5.95 | 0.00 | 0.00 | 0.00 |
Sum | 486042.50 | 59.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:37
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200940E+10 | 9577.59 | 07-JAN-00:03 | -1.2 | -1.2 | 0.106609E+10 | 1275.40 | 08-JAN-18:40 | 3.30 | 0.19 |
February | 0.300466E+10 | 9330.49 | 18-FEB-00:03 | -0.8 | -1.8 | 0.978871E+09 | 1415.33 | 26-FEB-17:19 | 13.30 | 9.51 |
March | 0.537597E+10 | 7197.63 | 24-MAR-23:03 | 3.80 | -1.4 | 0.110334E+10 | 1587.02 | 18-MAR-12:00 | 3.80 | -1.4 |
April | 0.694413E+10 | 11115.09 | 27-APR-16:10 | 27.02 | 16.89 | 0.118471E+10 | 1685.92 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.877420E+10 | 10705.35 | 15-MAY-16:10 | 23.98 | 12.88 | 0.133623E+10 | 1685.97 | 07-MAY-12:00 | 23.98 | 12.88 |
June | 0.100075E+11 | 11907.89 | 28-JUN-17:00 | 26.70 | 16.74 | 0.134401E+10 | 1685.93 | 11-JUN-12:09 | 26.70 | 16.74 |
July | 0.128339E+11 | 27581.96 | 24-JUL-07:03 | 19.37 | 15.37 | 0.141148E+10 | 1685.98 | 15-JUL-12:00 | 19.37 | 15.37 |
August | 0.134024E+11 | 27954.86 | 10-AUG-07:03 | 19.83 | 15.97 | 0.139302E+10 | 1685.98 | 26-AUG-12:39 | 22.20 | 17.20 |
September | 0.101455E+11 | 12300.15 | 14-SEP-07:03 | 14.18 | 13.39 | 0.134584E+10 | 1685.98 | 23-SEP-12:30 | 21.10 | 16.82 |
October | 0.764712E+10 | 9824.66 | 04-OCT-16:10 | 21.02 | 11.40 | 0.124834E+10 | 1685.87 | 08-OCT-16:40 | 18.87 | 12.78 |
November | 0.414423E+10 | 6929.80 | 17-NOV-00:03 | 4.40 | 4.09 | 0.106848E+10 | 1685.91 | 04-NOV-12:00 | 4.40 | 4.09 |
December | 0.271025E+10 | 8810.38 | 22-DEC-00:03 | 0.40 | -0.8 | 0.107159E+10 | 1341.23 | 03-DEC-13:00 | 0.40 | -0.8 |
Annual Sum or Average | 0.869993E+11 | 0.145520E+11 | ||||||||
Minimum of Months | 0.200940E+10 | 6929.80 | -1.2 | -1.8 | 0.978871E+09 | 1275.40 | 0.40 | -1.4 | ||
Maximum of Months | 0.134024E+11 | 27954.86 | 27.02 | 16.89 | 0.141148E+10 | 1685.98 | 26.70 | 17.20 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117142E+10 | 3367.39 | 26-JAN-09:33 | 4.40 | 4.13 | 0.559684E+09 | 816.16 | 29-JAN-18:00 | 9.40 | 5.55 |
February | 0.171393E+10 | 3926.63 | 13-FEB-09:43 | 1.88 | 0.03 | 0.521363E+09 | 842.90 | 26-FEB-18:00 | 10.00 | 7.75 |
March | 0.289300E+10 | 3688.06 | 01-MAR-09:03 | 4.37 | 0.91 | 0.601260E+09 | 842.90 | 19-MAR-17:00 | 10.00 | 6.56 |
April | 0.372884E+10 | 14302.15 | 02-APR-18:10 | 17.52 | 11.20 | 0.634171E+09 | 842.94 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.504838E+10 | 14627.67 | 13-MAY-18:44 | 17.30 | 11.04 | 0.689332E+09 | 842.96 | 07-MAY-12:39 | 17.30 | 11.04 |
June | 0.603092E+10 | 14563.39 | 04-JUN-17:08 | 16.02 | 11.26 | 0.675061E+09 | 842.94 | 11-JUN-12:09 | 21.70 | 15.54 |
July | 0.742309E+10 | 17592.34 | 24-JUL-07:03 | 19.37 | 15.37 | 0.704651E+09 | 843.12 | 23-JUL-17:00 | 19.37 | 15.37 |
August | 0.774734E+10 | 16958.32 | 10-AUG-07:03 | 19.83 | 15.97 | 0.695366E+09 | 842.96 | 26-AUG-12:39 | 22.20 | 17.20 |
September | 0.595516E+10 | 13292.80 | 09-SEP-19:10 | 17.12 | 12.72 | 0.678613E+09 | 842.97 | 22-SEP-12:30 | 20.55 | 16.47 |
October | 0.412761E+10 | 14013.40 | 08-OCT-17:50 | 16.47 | 11.90 | 0.664188E+09 | 842.92 | 08-OCT-12:00 | 16.47 | 11.90 |
November | 0.232348E+10 | 4101.63 | 04-NOV-14:00 | 21.10 | 15.94 | 0.569386E+09 | 842.95 | 04-NOV-12:00 | 21.10 | 15.94 |
December | 0.148304E+10 | 3471.12 | 05-DEC-18:10 | 5.00 | 3.89 | 0.567299E+09 | 842.77 | 03-DEC-18:00 | 5.00 | 3.89 |
Annual Sum or Average | 0.496462E+11 | 0.756037E+10 | ||||||||
Minimum of Months | 0.117142E+10 | 3367.39 | 1.88 | 0.03 | 0.521363E+09 | 816.16 | 5.00 | 3.89 | ||
Maximum of Months | 0.774734E+10 | 17592.34 | 21.10 | 15.97 | 0.704651E+09 | 843.12 | 22.20 | 17.20 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.698011E+09 | 4655.60 | 21-JAN-09:13 | -0.9 | -1.0 | 0.317536E+09 | 637.68 | 07-JAN-13:20 | -0.9 | -1.0 |
February | 0.124338E+10 | 4920.48 | 19-FEB-10:02 | -2.1 | -3.8 | 0.295585E+09 | 732.58 | 25-FEB-13:50 | 14.50 | 11.67 |
March | 0.241491E+10 | 4262.53 | 02-MAR-08:61 | 2.15 | 1.10 | 0.347224E+09 | 835.78 | 18-MAR-12:00 | 17.20 | 10.94 |
April | 0.289913E+10 | 5902.25 | 27-APR-16:10 | 27.02 | 16.89 | 0.363901E+09 | 842.94 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.364745E+10 | 5544.05 | 15-MAY-14:00 | 23.30 | 13.50 | 0.412415E+09 | 842.95 | 06-MAY-12:09 | 23.30 | 13.50 |
June | 0.425073E+10 | 8628.06 | 12-JUN-06:03 | 14.60 | 13.50 | 0.414409E+09 | 842.93 | 10-JUN-12:09 | 14.60 | 13.50 |
July | 0.520891E+10 | 18152.60 | 24-JUL-06:03 | 17.48 | 14.11 | 0.419371E+09 | 842.97 | 15-JUL-12:00 | 17.48 | 14.11 |
August | 0.569229E+10 | 19299.80 | 14-AUG-06:02 | 15.47 | 13.75 | 0.431055E+09 | 842.96 | 26-AUG-12:30 | 22.20 | 17.29 |
September | 0.418893E+10 | 10399.03 | 14-SEP-06:03 | 12.07 | 11.66 | 0.405891E+09 | 842.97 | 23-SEP-12:20 | 20.73 | 16.69 |
October | 0.317175E+10 | 5347.15 | 04-OCT-14:00 | 21.10 | 11.41 | 0.378698E+09 | 842.91 | 07-OCT-12:00 | 17.20 | 12.22 |
November | 0.169442E+10 | 3618.87 | 04-NOV-14:00 | 21.10 | 15.94 | 0.318777E+09 | 842.94 | 04-NOV-12:00 | 21.10 | 15.94 |
December | 0.996250E+09 | 4168.11 | 22-DEC-09:23 | 1.15 | -0.6 | 0.317759E+09 | 697.78 | 02-DEC-13:00 | 1.15 | -0.6 |
Annual Sum or Average | 0.361061E+11 | 0.442262E+10 | ||||||||
Minimum of Months | 0.698011E+09 | 3618.87 | -2.1 | -3.8 | 0.295585E+09 | 637.68 | -0.9 | -1.0 | ||
Maximum of Months | 0.569229E+10 | 19299.80 | 27.02 | 16.89 | 0.431055E+09 | 842.97 | 23.30 | 17.29 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.582719E+09 | 3459.45 | 18-JAN-10:03 | 3.98 | 3.51 | 0.317452E+09 | 637.68 | 07-JAN-13:20 | 3.98 | 3.51 |
February | 0.110824E+10 | 4575.86 | 18-FEB-18:53 | -0.6 | -1.4 | 0.294794E+09 | 724.38 | 25-FEB-13:50 | 14.50 | 11.67 |
March | 0.225486E+10 | 4208.70 | 02-MAR-08:61 | 2.15 | 1.10 | 0.344903E+09 | 828.98 | 18-MAR-12:00 | 17.20 | 10.94 |
April | 0.278926E+10 | 5796.12 | 27-APR-16:10 | 27.02 | 16.89 | 0.361287E+09 | 842.94 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.357547E+10 | 5488.31 | 06-MAY-13:00 | 23.90 | 17.58 | 0.411410E+09 | 842.95 | 06-MAY-12:09 | 23.90 | 17.58 |
June | 0.419692E+10 | 8459.96 | 29-JUN-06:03 | 12.70 | 11.22 | 0.414260E+09 | 842.93 | 10-JUN-12:09 | 12.70 | 11.22 |
July | 0.517716E+10 | 18457.44 | 24-JUL-06:03 | 17.48 | 14.11 | 0.419344E+09 | 842.97 | 15-JUL-12:00 | 17.48 | 14.11 |
August | 0.567623E+10 | 19401.46 | 14-AUG-06:02 | 15.47 | 13.75 | 0.431040E+09 | 842.96 | 26-AUG-12:30 | 22.20 | 17.29 |
September | 0.413771E+10 | 10363.14 | 14-SEP-06:03 | 12.07 | 11.66 | 0.405563E+09 | 842.97 | 23-SEP-12:20 | 20.73 | 16.69 |
October | 0.307594E+10 | 5269.87 | 04-OCT-14:00 | 21.10 | 11.41 | 0.375962E+09 | 842.91 | 07-OCT-12:00 | 17.20 | 12.22 |
November | 0.154552E+10 | 3421.38 | 04-NOV-14:00 | 21.10 | 15.94 | 0.317511E+09 | 842.94 | 04-NOV-12:00 | 21.10 | 15.94 |
December | 0.869571E+09 | 4050.57 | 22-DEC-09:33 | 1.33 | -0.5 | 0.317513E+09 | 691.80 | 02-DEC-13:00 | 1.33 | -0.5 |
Annual Sum or Average | 0.349896E+11 | 0.441104E+10 | ||||||||
Minimum of Months | 0.582719E+09 | 3421.38 | -0.6 | -1.4 | 0.294794E+09 | 637.68 | 1.33 | -0.5 | ||
Maximum of Months | 0.567623E+10 | 19401.46 | 27.02 | 17.58 | 0.431040E+09 | 842.97 | 23.90 | 17.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.425457E+09 | 3675.27 | 21-JAN-10:13 | -0.6 | -0.8 | 0.317752E+09 | 637.68 | 07-JAN-13:20 | -0.6 | -0.8 |
February | 0.817336E+09 | 3286.49 | 13-FEB-10:23 | 1.15 | 0.00 | 0.296671E+09 | 749.60 | 25-FEB-13:50 | 14.50 | 11.67 |
March | 0.168653E+10 | 3483.28 | 02-MAR-08:61 | 2.15 | 1.10 | 0.351293E+09 | 842.31 | 18-MAR-12:00 | 17.20 | 10.94 |
April | 0.214350E+10 | 5597.63 | 27-APR-16:10 | 27.02 | 16.89 | 0.368637E+09 | 842.92 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.301040E+10 | 5319.94 | 06-MAY-13:00 | 23.90 | 17.58 | 0.415807E+09 | 842.93 | 06-MAY-12:09 | 23.90 | 17.58 |
June | 0.382803E+10 | 6853.41 | 29-JUN-06:03 | 12.70 | 11.22 | 0.415511E+09 | 842.91 | 10-JUN-12:09 | 12.70 | 11.22 |
July | 0.489450E+10 | 16989.88 | 24-JUL-06:03 | 17.48 | 14.11 | 0.419674E+09 | 842.95 | 15-JUL-12:00 | 17.48 | 14.11 |
August | 0.540863E+10 | 19133.21 | 14-AUG-06:02 | 15.47 | 13.75 | 0.431357E+09 | 842.95 | 26-AUG-12:09 | 22.20 | 17.48 |
September | 0.372856E+10 | 8839.50 | 14-SEP-06:03 | 12.07 | 11.66 | 0.407769E+09 | 842.95 | 23-SEP-12:39 | 21.47 | 16.94 |
October | 0.241294E+10 | 5109.29 | 04-OCT-14:00 | 21.10 | 11.41 | 0.382770E+09 | 842.89 | 07-OCT-12:09 | 16.28 | 11.84 |
November | 0.115472E+10 | 3257.01 | 11-NOV-09:33 | 1.33 | 1.09 | 0.320679E+09 | 842.92 | 04-NOV-12:00 | 1.33 | 1.09 |
December | 0.665155E+09 | 2592.62 | 05-DEC-18:10 | 5.00 | 3.89 | 0.318134E+09 | 712.00 | 02-DEC-13:00 | 5.00 | 3.89 |
Annual Sum or Average | 0.301758E+11 | 0.444605E+10 | ||||||||
Minimum of Months | 0.425457E+09 | 2592.62 | -0.6 | -0.8 | 0.296671E+09 | 637.68 | -0.6 | -0.8 | ||
Maximum of Months | 0.540863E+10 | 19133.21 | 27.02 | 17.58 | 0.431357E+09 | 842.95 | 23.90 | 17.58 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.320339E+09 | 6591.31 | 09-JAN-20:43 | 5.10 | 1.93 | 0.108442E+10 | 1700.53 | 07-JAN-15:39 | 5.10 | 1.93 |
February | 0.106052E+10 | 6388.76 | 11-FEB-10:23 | 5.55 | 2.73 | 0.999884E+09 | 1958.68 | 27-FEB-17:10 | 18.62 | 12.15 |
March | 0.280462E+10 | 5888.26 | 22-MAR-15:23 | 6.70 | 5.33 | 0.114871E+10 | 2247.71 | 18-MAR-14:00 | 6.70 | 5.33 |
April | 0.398092E+10 | 9644.07 | 27-APR-14:50 | 27.02 | 17.21 | 0.119002E+10 | 2247.89 | 29-APR-14:09 | 21.28 | 14.86 |
May | 0.535245E+10 | 9372.99 | 15-MAY-14:30 | 23.30 | 13.06 | 0.136543E+10 | 2247.90 | 06-MAY-14:00 | 23.30 | 13.06 |
June | 0.621216E+10 | 10509.95 | 28-JUN-15:00 | 26.10 | 15.54 | 0.140977E+10 | 2247.85 | 03-JUN-14:09 | 26.10 | 15.54 |
July | 0.796559E+10 | 31292.48 | 24-JUL-07:03 | 19.37 | 15.37 | 0.143456E+10 | 2247.96 | 15-JUL-14:09 | 19.37 | 15.37 |
August | 0.885266E+10 | 31454.63 | 14-AUG-07:03 | 16.98 | 14.61 | 0.147765E+10 | 2247.96 | 26-AUG-14:30 | 20.35 | 16.60 |
September | 0.625396E+10 | 12030.33 | 14-SEP-07:03 | 14.18 | 13.39 | 0.137036E+10 | 2247.91 | 02-SEP-14:09 | 14.18 | 13.39 |
October | 0.438419E+10 | 8959.97 | 04-OCT-14:40 | 21.50 | 11.47 | 0.123218E+10 | 2247.83 | 07-OCT-14:00 | 18.30 | 12.37 |
November | 0.164705E+10 | 5967.93 | 10-NOV-09:33 | 6.50 | 5.53 | 0.106409E+10 | 2247.91 | 04-NOV-14:39 | 6.50 | 5.53 |
December | 0.637638E+09 | 6657.24 | 31-DEC-11:53 | 5.00 | 4.22 | 0.108642E+10 | 1709.13 | 02-DEC-15:09 | 5.00 | 4.22 |
Annual Sum or Average | 0.494721E+11 | 0.148635E+11 | ||||||||
Minimum of Months | 0.320339E+09 | 5888.26 | 5.00 | 1.93 | 0.999884E+09 | 1700.53 | 5.00 | 1.93 | ||
Maximum of Months | 0.885266E+10 | 31454.63 | 27.02 | 17.21 | 0.147765E+10 | 2247.96 | 26.10 | 16.60 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144330E+09 | 3124.17 | 05-JAN-20:23 | 2.50 | 2.15 | 0.542458E+09 | 850.24 | 07-JAN-15:20 | 3.13 | 1.56 |
February | 0.430313E+09 | 1885.70 | 28-FEB-20:00 | 9.40 | 7.97 | 0.503038E+09 | 997.43 | 27-FEB-17:10 | 9.40 | 7.97 |
March | 0.114018E+10 | 2743.81 | 01-MAR-09:03 | 4.37 | 0.91 | 0.585303E+09 | 1123.85 | 18-MAR-14:09 | 20.00 | 10.47 |
April | 0.162493E+10 | 5072.90 | 27-APR-14:50 | 27.02 | 17.21 | 0.610753E+09 | 1123.89 | 29-APR-14:09 | 21.28 | 14.86 |
May | 0.230151E+10 | 4860.53 | 15-MAY-14:30 | 23.30 | 13.06 | 0.699634E+09 | 1123.90 | 06-MAY-14:00 | 23.30 | 13.06 |
June | 0.298245E+10 | 5430.77 | 28-JUN-15:00 | 26.10 | 15.54 | 0.710376E+09 | 1123.87 | 03-JUN-14:09 | 26.10 | 15.54 |
July | 0.399735E+10 | 14995.22 | 24-JUL-07:03 | 19.37 | 15.37 | 0.718274E+09 | 1123.93 | 15-JUL-14:09 | 19.37 | 15.37 |
August | 0.448473E+10 | 15254.07 | 14-AUG-07:03 | 16.98 | 14.61 | 0.739451E+09 | 1123.92 | 26-AUG-14:09 | 20.45 | 16.60 |
September | 0.295077E+10 | 5778.22 | 14-SEP-14:30 | 23.90 | 17.04 | 0.694429E+09 | 1123.91 | 23-SEP-14:09 | 23.30 | 17.84 |
October | 0.183557E+10 | 4703.57 | 04-OCT-15:00 | 21.70 | 11.49 | 0.632661E+09 | 1123.83 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.680789E+09 | 2768.41 | 22-NOV-10:05 | 3.58 | 3.32 | 0.536917E+09 | 1123.90 | 04-NOV-14:50 | 3.58 | 3.32 |
December | 0.285448E+09 | 2441.38 | 19-DEC-20:43 | 5.60 | 4.76 | 0.543878E+09 | 899.19 | 02-DEC-15:09 | 5.60 | 4.76 |
Annual Sum or Average | 0.228584E+11 | 0.751717E+10 | ||||||||
Minimum of Months | 0.144330E+09 | 1885.70 | 2.50 | 0.91 | 0.503038E+09 | 850.24 | 3.13 | 1.56 | ||
Maximum of Months | 0.448473E+10 | 15254.07 | 27.02 | 17.21 | 0.739451E+09 | 1123.93 | 26.10 | 17.84 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129909E+09 | 3304.03 | 20-JAN-20:53 | 1.70 | 0.78 | 0.542406E+09 | 850.24 | 07-JAN-15:20 | 1.70 | 0.78 |
February | 0.399551E+09 | 3293.69 | 17-FEB-19:33 | 1.70 | -0.7 | 0.502626E+09 | 997.43 | 27-FEB-17:10 | 18.62 | 12.15 |
March | 0.108999E+10 | 2451.00 | 03-MAR-09:03 | 5.68 | 5.12 | 0.583780E+09 | 1123.85 | 18-MAR-14:09 | 20.00 | 10.47 |
April | 0.157994E+10 | 4988.15 | 27-APR-15:00 | 27.20 | 17.29 | 0.608765E+09 | 1123.89 | 29-APR-14:09 | 21.28 | 14.86 |
May | 0.225079E+10 | 4776.89 | 15-MAY-14:30 | 23.30 | 13.06 | 0.697709E+09 | 1123.90 | 06-MAY-14:00 | 23.30 | 13.06 |
June | 0.291383E+10 | 5366.22 | 28-JUN-15:00 | 26.10 | 15.54 | 0.709970E+09 | 1123.87 | 03-JUN-14:09 | 26.10 | 15.54 |
July | 0.391865E+10 | 14361.14 | 24-JUL-07:03 | 19.37 | 15.37 | 0.718209E+09 | 1123.93 | 15-JUL-14:09 | 19.37 | 15.37 |
August | 0.441016E+10 | 14667.25 | 14-AUG-07:03 | 16.98 | 14.61 | 0.739410E+09 | 1123.92 | 26-AUG-14:09 | 20.45 | 16.60 |
September | 0.289670E+10 | 5717.95 | 14-SEP-14:30 | 23.90 | 17.04 | 0.693794E+09 | 1123.91 | 23-SEP-14:09 | 23.30 | 17.84 |
October | 0.179232E+10 | 4625.47 | 04-OCT-15:00 | 21.70 | 11.49 | 0.630947E+09 | 1123.83 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.644135E+09 | 2655.22 | 04-NOV-14:40 | 21.10 | 15.94 | 0.536311E+09 | 1123.90 | 04-NOV-14:50 | 21.10 | 15.94 |
December | 0.258062E+09 | 3041.96 | 11-DEC-20:43 | 2.88 | 0.98 | 0.543791E+09 | 894.76 | 02-DEC-15:09 | 2.88 | 0.98 |
Annual Sum or Average | 0.222840E+11 | 0.750772E+10 | ||||||||
Minimum of Months | 0.129909E+09 | 2451.00 | 1.70 | -0.7 | 0.502626E+09 | 850.24 | 1.70 | 0.78 | ||
Maximum of Months | 0.441016E+10 | 14667.25 | 27.20 | 17.29 | 0.739410E+09 | 1123.93 | 26.10 | 17.84 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73182222.29 | 3544.97 | 06-JAN-19:03 | 0.68 | 0.68 | 0.542276E+09 | 850.24 | 07-JAN-15:09 | 3.22 | 1.63 |
February | 0.296584E+09 | 3251.08 | 17-FEB-18:23 | 1.95 | -0.4 | 0.501174E+09 | 997.29 | 27-FEB-17:19 | 18.33 | 12.12 |
March | 0.893968E+09 | 2271.18 | 01-MAR-19:00 | 7.20 | 2.85 | 0.578247E+09 | 1123.85 | 18-MAR-14:00 | 20.00 | 10.34 |
April | 0.139432E+10 | 4727.72 | 27-APR-15:00 | 27.20 | 17.29 | 0.600857E+09 | 1123.89 | 29-APR-14:20 | 21.47 | 14.94 |
May | 0.204598E+10 | 4537.46 | 15-MAY-14:30 | 23.30 | 13.06 | 0.688009E+09 | 1123.90 | 06-MAY-14:00 | 23.30 | 13.06 |
June | 0.269122E+10 | 5234.13 | 28-JUN-15:00 | 26.10 | 15.54 | 0.707493E+09 | 1123.87 | 03-JUN-14:09 | 26.10 | 15.54 |
July | 0.370190E+10 | 12094.75 | 24-JUL-07:03 | 19.37 | 15.37 | 0.717894E+09 | 1123.93 | 15-JUL-14:09 | 19.37 | 15.37 |
August | 0.422042E+10 | 12672.06 | 14-AUG-07:03 | 16.98 | 14.61 | 0.739229E+09 | 1123.92 | 26-AUG-14:09 | 20.45 | 16.60 |
September | 0.270621E+10 | 5614.06 | 14-SEP-14:30 | 23.90 | 17.04 | 0.689642E+09 | 1123.91 | 23-SEP-14:09 | 23.30 | 17.84 |
October | 0.159766E+10 | 4380.40 | 04-OCT-15:00 | 21.70 | 11.49 | 0.622825E+09 | 1123.83 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.521294E+09 | 2865.96 | 13-NOV-20:33 | 3.73 | 2.71 | 0.533929E+09 | 1123.90 | 04-NOV-14:50 | 3.73 | 2.71 |
December | 0.171938E+09 | 3013.53 | 08-DEC-20:13 | 3.07 | 2.46 | 0.543439E+09 | 876.80 | 02-DEC-15:09 | 3.07 | 2.46 |
Annual Sum or Average | 0.203147E+11 | 0.746501E+10 | ||||||||
Minimum of Months | 73182222.29 | 2271.18 | 0.68 | -0.4 | 0.501174E+09 | 850.24 | 3.07 | 1.63 | ||
Maximum of Months | 0.422042E+10 | 12672.06 | 27.20 | 17.29 | 0.739229E+09 | 1123.93 | 26.10 | 17.84 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3957163.24 | 461.00 | 11-JAN-18:10 | 12.70 | 9.55 | 0.542193E+09 | 850.24 | 07-JAN-15:20 | 12.70 | 9.55 |
February | 88406194.60 | 1460.70 | 28-FEB-18:40 | 10.37 | 8.44 | 0.498780E+09 | 970.63 | 27-FEB-17:10 | 10.37 | 8.44 |
March | 0.427739E+09 | 1995.47 | 01-MAR-12:00 | 8.30 | 4.65 | 0.570214E+09 | 1123.86 | 18-MAR-14:00 | 20.00 | 10.34 |
April | 0.966243E+09 | 4630.39 | 27-APR-14:50 | 27.02 | 17.21 | 0.589153E+09 | 1123.89 | 29-APR-14:39 | 21.83 | 15.09 |
May | 0.163333E+10 | 4379.26 | 15-MAY-14:20 | 23.30 | 13.21 | 0.669334E+09 | 1123.91 | 06-MAY-14:00 | 23.30 | 13.21 |
June | 0.240284E+10 | 5232.55 | 28-JUN-15:00 | 26.10 | 15.54 | 0.700575E+09 | 1123.87 | 03-JUN-14:09 | 26.10 | 15.54 |
July | 0.347962E+10 | 7018.88 | 24-JUL-15:00 | 30.60 | 18.78 | 0.716387E+09 | 1123.93 | 15-JUL-14:30 | 30.60 | 18.78 |
August | 0.408106E+10 | 7355.94 | 10-AUG-14:50 | 30.07 | 18.95 | 0.738496E+09 | 1123.91 | 26-AUG-14:09 | 20.45 | 16.60 |
September | 0.241639E+10 | 5703.15 | 14-SEP-14:20 | 23.90 | 17.07 | 0.678793E+09 | 1123.92 | 23-SEP-14:09 | 23.30 | 17.84 |
October | 0.110173E+10 | 3933.38 | 04-OCT-15:00 | 21.70 | 11.49 | 0.609189E+09 | 1123.84 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.224991E+09 | 2526.95 | 13-NOV-11:55 | 4.40 | 3.16 | 0.530825E+09 | 1123.89 | 04-NOV-14:50 | 4.40 | 3.16 |
December | 29158992.56 | 1118.75 | 02-DEC-11:40 | 11.83 | 6.03 | 0.543113E+09 | 850.24 | 02-DEC-15:09 | 11.52 | 5.36 |
Annual Sum or Average | 0.168555E+11 | 0.738705E+10 | ||||||||
Minimum of Months | 3957163.24 | 461.00 | 4.40 | 3.16 | 0.498780E+09 | 850.24 | 4.40 | 3.16 | ||
Maximum of Months | 0.408106E+10 | 7355.94 | 30.60 | 18.95 | 0.738496E+09 | 1123.93 | 30.60 | 18.78 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203291E+10 | 59171.41 | 06-JAN-08:61 | -2.7 |
February | 0.118380E+10 | 59141.18 | 08-FEB-08:61 | -0.4 |
March | 0.386884E+09 | 59147.22 | 25-MAR-07:01 | 2.15 |
April | 0.158053E+09 | 59103.43 | 18-APR-07:01 | 3.98 |
May | 74353239.59 | 891.50 | 17-MAY-07:25 | 9.15 |
June | 38187371.59 | 1086.65 | 12-JUN-07:07 | 15.50 |
July | 16714181.34 | 1688.75 | 24-JUL-07:05 | 19.37 |
August | 25116766.93 | 1692.05 | 10-AUG-07:05 | 19.83 |
September | 43443023.87 | 1277.16 | 14-SEP-07:07 | 14.18 |
October | 93958793.73 | 27025.00 | 31-OCT-07:01 | 11.20 |
November | 0.565647E+09 | 59162.85 | 24-NOV-08:61 | 1.97 |
December | 0.154507E+10 | 59165.44 | 11-DEC-08:61 | 2.88 |
Annual Sum or Average | 0.616414E+10 | |||
Minimum of Months | 16714181.34 | 891.50 | -2.7 | |
Maximum of Months | 0.203291E+10 | 59171.41 | 19.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.336635E+09 | 31049.36 | 07-JAN-08:61 | -3.8 |
February | 0.211920E+09 | 31025.25 | 18-FEB-08:61 | -1.5 |
March | 56290848.58 | 15804.29 | 25-MAR-07:01 | 2.15 |
April | 43514917.56 | 2468.93 | 19-APR-07:01 | 4.18 |
May | 30513010.77 | 674.88 | 07-MAY-07:10 | 14.97 |
June | 9793075.62 | 827.31 | 12-JUN-07:07 | 15.50 |
July | 12580876.50 | 1068.30 | 24-JUL-07:05 | 19.37 |
August | 15112891.57 | 1047.84 | 10-AUG-07:05 | 19.83 |
September | 13466076.54 | 846.26 | 14-SEP-07:07 | 14.18 |
October | 36256452.12 | 578.68 | 09-OCT-07:10 | 10.78 |
November | 71824619.04 | 18057.61 | 30-NOV-08:61 | 5.10 |
December | 0.225800E+09 | 31046.11 | 22-DEC-08:61 | 0.10 |
Annual Sum or Average | 0.106371E+10 | |||
Minimum of Months | 9793075.62 | 578.68 | -3.8 | |
Maximum of Months | 0.336635E+09 | 31049.36 | 19.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.685693E+09 | 30718.35 | 15-JAN-08:61 | -3.7 |
February | 0.387573E+09 | 30954.43 | 19-FEB-08:61 | -4.7 |
March | 88343680.52 | 16030.96 | 06-MAR-07:02 | 6.70 |
April | 47801896.40 | 5011.62 | 19-APR-06:03 | 2.48 |
May | 29171672.20 | 665.40 | 07-MAY-07:10 | 14.97 |
June | 9847493.61 | 788.98 | 12-JUN-06:07 | 14.60 |
July | 19796023.54 | 1057.94 | 24-JUL-06:05 | 17.48 |
August | 21348282.47 | 1449.65 | 10-AUG-19:03 | 29.18 |
September | 13509871.99 | 859.68 | 14-SEP-06:07 | 12.07 |
October | 34021614.71 | 525.43 | 09-OCT-07:10 | 10.78 |
November | 0.179481E+09 | 18439.77 | 24-NOV-07:02 | 1.20 |
December | 0.505635E+09 | 30490.70 | 26-DEC-07:01 | -1.6 |
Annual Sum or Average | 0.202222E+10 | |||
Minimum of Months | 9847493.61 | 525.43 | -4.7 | |
Maximum of Months | 0.685693E+09 | 30954.43 | 29.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.860919E+09 | 30555.86 | 15-JAN-08:61 | -3.7 |
February | 0.466244E+09 | 30791.47 | 19-FEB-08:61 | -4.7 |
March | 0.113620E+09 | 21556.92 | 06-MAR-07:02 | 6.70 |
April | 53275984.97 | 7066.72 | 19-APR-06:03 | 2.48 |
May | 31873059.77 | 651.23 | 07-MAY-07:10 | 14.97 |
June | 10714660.67 | 780.04 | 12-JUN-06:07 | 14.60 |
July | 19568342.90 | 1068.96 | 24-JUL-06:05 | 17.48 |
August | 21229481.46 | 1450.84 | 10-AUG-19:03 | 29.18 |
September | 14937576.52 | 860.98 | 14-SEP-06:07 | 12.07 |
October | 36479348.38 | 860.99 | 22-OCT-08:08 | 7.88 |
November | 0.249392E+09 | 23498.76 | 24-NOV-07:02 | 1.20 |
December | 0.641363E+09 | 30330.23 | 26-DEC-07:01 | -1.6 |
Annual Sum or Average | 0.251962E+10 | |||
Minimum of Months | 10714660.67 | 651.23 | -4.7 | |
Maximum of Months | 0.860919E+09 | 30791.47 | 29.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112804E+10 | 30540.92 | 15-JAN-08:61 | -3.7 |
February | 0.611951E+09 | 30774.44 | 19-FEB-08:61 | -4.7 |
March | 0.194997E+09 | 25776.10 | 06-MAR-07:02 | 6.70 |
April | 0.113341E+09 | 8695.76 | 19-APR-06:03 | 2.48 |
May | 69862406.42 | 1131.70 | 28-MAY-08:00 | 8.30 |
June | 20181015.13 | 1461.49 | 12-JUN-06:07 | 14.60 |
July | 34452314.75 | 1924.59 | 24-JUL-06:05 | 17.48 |
August | 47633619.98 | 1964.46 | 10-AUG-19:03 | 29.18 |
September | 25468348.53 | 1589.98 | 14-SEP-06:07 | 12.07 |
October | 84133357.86 | 1164.54 | 15-OCT-08:00 | 8.30 |
November | 0.370047E+09 | 27734.05 | 24-NOV-07:02 | 1.20 |
December | 0.843654E+09 | 30317.60 | 26-DEC-07:01 | -1.6 |
Annual Sum or Average | 0.354376E+10 | |||
Minimum of Months | 20181015.13 | 1131.70 | -4.7 | |
Maximum of Months | 0.112804E+10 | 30774.44 | 29.18 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265175E+10 | 56615.11 | 17-JAN-08:61 | 1.70 |
February | 0.140585E+10 | 56592.94 | 06-FEB-08:61 | 3.90 |
March | 0.475040E+09 | 56595.63 | 25-MAR-07:01 | 2.15 |
April | 0.178272E+09 | 56558.38 | 18-APR-07:01 | 3.98 |
May | 72448808.48 | 1656.79 | 18-MAY-08:10 | 6.28 |
June | 38478378.04 | 1141.70 | 12-JUN-07:07 | 15.50 |
July | 27091819.81 | 2131.06 | 23-JUL-16:03 | 27.62 |
August | 29704013.00 | 2414.90 | 13-AUG-16:02 | 28.08 |
September | 47140566.38 | 1226.49 | 14-SEP-07:07 | 14.18 |
October | 0.124306E+09 | 36493.14 | 31-OCT-07:01 | 11.20 |
November | 0.874206E+09 | 56605.99 | 24-NOV-08:61 | 1.97 |
December | 0.199359E+10 | 56610.16 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.791787E+10 | |||
Minimum of Months | 27091819.81 | 1141.70 | -1.1 | |
Maximum of Months | 0.265175E+10 | 56615.11 | 28.08 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159057E+10 | 29049.28 | 17-JAN-08:61 | 1.70 |
February | 0.854618E+09 | 29037.79 | 06-FEB-08:61 | 3.90 |
March | 0.304447E+09 | 29040.07 | 25-MAR-07:01 | 2.15 |
April | 0.146794E+09 | 29019.74 | 18-APR-07:01 | 3.98 |
May | 89496471.66 | 1116.85 | 17-MAY-07:25 | 9.15 |
June | 36705075.43 | 1248.57 | 12-JUN-07:07 | 15.50 |
July | 23936686.07 | 1731.96 | 24-JUL-07:05 | 19.37 |
August | 27999251.24 | 1722.74 | 14-AUG-07:05 | 16.98 |
September | 44793602.11 | 1290.24 | 14-SEP-07:07 | 14.18 |
October | 0.116639E+09 | 18812.16 | 31-OCT-07:01 | 11.20 |
November | 0.565302E+09 | 29044.93 | 24-NOV-08:61 | 1.97 |
December | 0.120548E+10 | 29047.41 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.500679E+10 | |||
Minimum of Months | 23936686.07 | 1116.85 | -1.1 | |
Maximum of Months | 0.159057E+10 | 29049.28 | 19.37 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167248E+10 | 28918.89 | 17-JAN-08:61 | 1.70 |
February | 0.910639E+09 | 28908.15 | 06-FEB-08:61 | 3.90 |
March | 0.333194E+09 | 28910.69 | 25-MAR-07:01 | 2.15 |
April | 0.154919E+09 | 28890.36 | 18-APR-07:01 | 3.98 |
May | 91539585.10 | 1111.39 | 17-MAY-07:25 | 9.15 |
June | 40091420.47 | 1211.89 | 12-JUN-07:07 | 15.50 |
July | 24864387.52 | 1689.06 | 24-JUL-07:05 | 19.37 |
August | 29086035.44 | 1717.91 | 13-AUG-16:02 | 28.08 |
September | 47237180.27 | 1260.77 | 14-SEP-07:07 | 14.18 |
October | 0.121861E+09 | 20820.06 | 31-OCT-07:01 | 11.20 |
November | 0.601687E+09 | 28915.36 | 24-NOV-08:61 | 1.97 |
December | 0.127209E+10 | 28917.85 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.529969E+10 | |||
Minimum of Months | 24864387.52 | 1111.39 | -1.1 | |
Maximum of Months | 0.167248E+10 | 28918.89 | 28.08 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202578E+10 | 28762.82 | 17-JAN-08:61 | 1.70 |
February | 0.116231E+10 | 28751.08 | 06-FEB-08:61 | 3.90 |
March | 0.475017E+09 | 28752.13 | 25-MAR-07:01 | 2.15 |
April | 0.204752E+09 | 28733.36 | 18-APR-07:01 | 3.98 |
May | 0.101303E+09 | 6856.81 | 29-MAY-08:62 | 10.60 |
June | 58622176.38 | 1061.78 | 15-JUN-07:13 | 10.97 |
July | 33501106.40 | 1629.31 | 23-JUL-16:12 | 27.43 |
August | 34669176.95 | 1720.08 | 13-AUG-16:02 | 28.08 |
September | 60304194.97 | 1166.99 | 14-SEP-07:07 | 14.18 |
October | 0.151419E+09 | 28343.46 | 30-OCT-07:01 | 7.20 |
November | 0.778527E+09 | 28757.35 | 24-NOV-08:61 | 1.97 |
December | 0.156817E+10 | 28760.00 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.665438E+10 | |||
Minimum of Months | 33501106.40 | 1061.78 | -1.1 | |
Maximum of Months | 0.202578E+10 | 28762.82 | 28.08 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.373644E+10 | 30104.20 | 16-JAN-09:13 | -0.4 |
February | 0.235623E+10 | 30081.73 | 20-FEB-09:01 | 1.47 |
March | 0.122338E+10 | 30066.31 | 25-MAR-07:01 | 2.15 |
April | 0.505945E+09 | 30050.43 | 18-APR-07:01 | 3.98 |
May | 0.168176E+09 | 28659.89 | 29-MAY-08:62 | 10.60 |
June | 99419909.87 | 2536.00 | 15-JUN-07:05 | 10.78 |
July | 87197871.20 | 1682.26 | 23-JUL-16:12 | 27.43 |
August | 60097634.72 | 1751.22 | 13-AUG-16:02 | 28.08 |
September | 96068350.30 | 7773.87 | 28-SEP-07:03 | 9.08 |
October | 0.339715E+09 | 29619.78 | 30-OCT-07:01 | 7.20 |
November | 0.157825E+10 | 30081.45 | 13-NOV-08:61 | 0.78 |
December | 0.298552E+10 | 30084.84 | 11-DEC-08:61 | 2.88 |
Annual Sum or Average | 0.132364E+11 | |||
Minimum of Months | 60097634.72 | 1682.26 | -0.4 | |
Maximum of Months | 0.373644E+10 | 30104.20 | 28.08 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.986629E+10 | 6035.26 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.891946E+10 | 6035.26 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.987658E+10 | 6035.26 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.956097E+10 | 6035.26 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.986629E+10 | 6035.26 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.956097E+10 | 6035.26 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.987658E+10 | 6035.26 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.986629E+10 | 6035.26 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.957126E+10 | 6035.26 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.986629E+10 | 6035.26 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.953010E+10 | 6035.26 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.988687E+10 | 6035.26 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.116248E+12 | 0.262491E+11 | ||||
Minimum of Months | 0.891946E+10 | 6035.26 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.988687E+10 | 6035.26 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.579394E+10 | 3544.17 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.523792E+10 | 3544.17 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.579999E+10 | 3544.17 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.561464E+10 | 3544.17 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.579394E+10 | 3544.17 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.561464E+10 | 3544.17 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.579999E+10 | 3544.17 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.579394E+10 | 3544.17 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.562069E+10 | 3544.17 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.579394E+10 | 3544.17 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.559651E+10 | 3544.17 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.580603E+10 | 3544.17 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.682662E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.523792E+10 | 3544.17 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.580603E+10 | 3544.17 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.413753E+10 | 3181.37 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.374692E+10 | 3181.37 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.422433E+10 | 3181.37 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.401456E+10 | 3181.37 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.418093E+10 | 3181.37 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.407966E+10 | 3181.37 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.411583E+10 | 3181.37 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.422433E+10 | 3181.37 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.401456E+10 | 3181.37 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.413753E+10 | 3181.37 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.401456E+10 | 3181.37 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.411583E+10 | 3181.37 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.490066E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.374692E+10 | 3181.37 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.422433E+10 | 3181.37 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.413753E+10 | 3181.37 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.374692E+10 | 3181.37 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.422433E+10 | 3181.37 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.401456E+10 | 3181.37 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.418093E+10 | 3181.37 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.407966E+10 | 3181.37 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.411583E+10 | 3181.37 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.422433E+10 | 3181.37 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.401456E+10 | 3181.37 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.413753E+10 | 3181.37 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.401456E+10 | 3181.37 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.411583E+10 | 3181.37 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.490066E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.374692E+10 | 3181.37 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.422433E+10 | 3181.37 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.413753E+10 | 3181.37 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.374692E+10 | 3181.37 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.422433E+10 | 3181.37 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.401456E+10 | 3181.37 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.418093E+10 | 3181.37 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.407966E+10 | 3181.37 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.411583E+10 | 3181.37 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.422433E+10 | 3181.37 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.401456E+10 | 3181.37 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.413753E+10 | 3181.37 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.401456E+10 | 3181.37 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.411583E+10 | 3181.37 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.490066E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.374692E+10 | 3181.37 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.422433E+10 | 3181.37 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.457032E+10 | 3825.14 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.413982E+10 | 3825.14 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.467469E+10 | 3825.14 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.443552E+10 | 3825.14 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.462251E+10 | 3825.14 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.451379E+10 | 3825.14 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.454423E+10 | 3825.14 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.467469E+10 | 3825.14 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.443552E+10 | 3825.14 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.457032E+10 | 3825.14 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.443552E+10 | 3825.14 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.454423E+10 | 3825.14 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.541612E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.413982E+10 | 3825.14 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.467469E+10 | 3825.14 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.986629E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450670E+10 |
February | 0.305697E+10 | 0.891946E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360406E+10 |
March | 0.335708E+10 | 0.987658E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327255E+10 |
April | 0.327081E+10 | 0.956097E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24394694.95 | 0.259694E+10 |
May | 0.336680E+10 | 0.986629E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2651719.53 | 0.225036E+10 |
June | 0.325380E+10 | 0.956097E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13745753.84 | 0.167447E+10 |
July | 0.339353E+10 | 0.987658E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130177E+09 | 0.114712E+10 |
August | 0.334857E+10 | 0.986629E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278909E+09 | 0.949353E+09 |
September | 0.327932E+10 | 0.957126E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3240989.79 | 0.158024E+10 |
October | 0.338624E+10 | 0.986629E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267423E+10 |
November | 0.327446E+10 | 0.953010E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352886E+10 |
December | 0.340325E+10 | 0.988687E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411620E+10 |
Annual Sum or Average | 0.397770E+11 | 0.116248E+12 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453119E+09 | 0.319011E+11 |
Minimum of Months | 0.305697E+10 | 0.891946E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.949353E+09 |
Maximum of Months | 0.340325E+10 | 0.988687E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278909E+09 | 0.450670E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.579394E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226863E+10 |
February | 0.152844E+10 | 0.523792E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181574E+10 |
March | 0.167849E+10 | 0.579999E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166742E+10 |
April | 0.163536E+10 | 0.561464E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13249810.91 | 0.132000E+10 |
May | 0.168335E+10 | 0.579394E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1455613.55 | 0.112888E+10 |
June | 0.162685E+10 | 0.561464E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7466182.36 | 0.793762E+09 |
July | 0.169671E+10 | 0.579999E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70583559.42 | 0.523070E+09 |
August | 0.167424E+10 | 0.579394E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151656E+09 | 0.421979E+09 |
September | 0.163961E+10 | 0.562069E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1785449.54 | 0.815417E+09 |
October | 0.169307E+10 | 0.579394E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137606E+10 |
November | 0.163718E+10 | 0.559651E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179099E+10 |
December | 0.170157E+10 | 0.580603E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210080E+10 |
Annual Sum or Average | 0.198880E+11 | 0.682662E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246197E+09 | 0.160227E+11 |
Minimum of Months | 0.152844E+10 | 0.523792E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421979E+09 |
Maximum of Months | 0.170157E+10 | 0.580603E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151656E+09 | 0.226863E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232509E+10 |
February | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185594E+10 |
March | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168451E+10 |
April | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13094501.88 | 0.134137E+10 |
May | 0.102058E+10 | 0.418093E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455583.92 | 0.116231E+10 |
June | 0.998711E+09 | 0.407966E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466057.15 | 0.829124E+09 |
July | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67111960.49 | 0.561253E+09 |
August | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149534E+09 | 0.454170E+09 |
September | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785334.08 | 0.837698E+09 |
October | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138639E+10 |
November | 0.973196E+09 | 0.401456E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181226E+10 |
December | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214746E+10 |
Annual Sum or Average | 0.119700E+11 | 0.490066E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240448E+09 | 0.163976E+11 |
Minimum of Months | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454170E+09 |
Maximum of Months | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149534E+09 | 0.232509E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231932E+10 |
February | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184900E+10 |
March | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167235E+10 |
April | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13097902.29 | 0.132824E+10 |
May | 0.102058E+10 | 0.418093E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455566.22 | 0.115678E+10 |
June | 0.998711E+09 | 0.407966E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466052.48 | 0.827775E+09 |
July | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67117504.66 | 0.560803E+09 |
August | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149535E+09 | 0.453971E+09 |
September | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785308.07 | 0.835912E+09 |
October | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137307E+10 |
November | 0.973196E+09 | 0.401456E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180344E+10 |
December | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214240E+10 |
Annual Sum or Average | 0.119700E+11 | 0.490066E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240457E+09 | 0.163230E+11 |
Minimum of Months | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453971E+09 |
Maximum of Months | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149535E+09 | 0.231932E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231586E+10 |
February | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185188E+10 |
March | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169011E+10 |
April | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13083399.09 | 0.135082E+10 |
May | 0.102058E+10 | 0.418093E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1456077.93 | 0.117049E+10 |
June | 0.998711E+09 | 0.407966E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466420.47 | 0.830826E+09 |
July | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66987063.92 | 0.560799E+09 |
August | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149450E+09 | 0.453728E+09 |
September | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785772.79 | 0.842704E+09 |
October | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139477E+10 |
November | 0.973196E+09 | 0.401456E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181045E+10 |
December | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214100E+10 |
Annual Sum or Average | 0.119700E+11 | 0.490066E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240229E+09 | 0.164134E+11 |
Minimum of Months | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453728E+09 |
Maximum of Months | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149450E+09 | 0.231586E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.457032E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422882E+10 |
February | 0.313522E+10 | 0.413982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336135E+10 |
March | 0.355148E+10 | 0.467469E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300656E+10 |
April | 0.338259E+10 | 0.443552E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23640594.09 | 0.234824E+10 |
May | 0.349753E+10 | 0.462251E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2614504.11 | 0.204552E+10 |
June | 0.343071E+10 | 0.451379E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13429670.86 | 0.151259E+10 |
July | 0.344942E+10 | 0.454423E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121097E+09 | 0.103728E+10 |
August | 0.355148E+10 | 0.467469E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269214E+09 | 0.844532E+09 |
September | 0.338259E+10 | 0.443552E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3205564.73 | 0.148609E+10 |
October | 0.344359E+10 | 0.457032E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242621E+10 |
November | 0.331698E+10 | 0.443552E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325956E+10 |
December | 0.344942E+10 | 0.454423E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389658E+10 |
Annual Sum or Average | 0.410346E+11 | 0.541612E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433201E+09 | 0.294533E+11 |
Minimum of Months | 0.313522E+10 | 0.413982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.844532E+09 |
Maximum of Months | 0.355148E+10 | 0.467469E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269214E+09 | 0.422882E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231856E+10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184586E+10 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166370E+10 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13114519.77 | 0.130973E+10 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455980.65 | 0.114691E+10 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466489.12 | 0.830085E+09 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67151144.97 | 0.560998E+09 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149587E+09 | 0.454448E+09 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785689.53 | 0.833197E+09 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135696E+10 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179565E+10 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214060E+10 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240561E+09 | 0.162567E+11 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454448E+09 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149587E+09 | 0.231856E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231703E+10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184377E+10 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165927E+10 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13119362.83 | 0.130429E+10 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455972.41 | 0.114190E+10 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466487.52 | 0.828380E+09 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67165951.63 | 0.560047E+09 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149595E+09 | 0.453662E+09 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785678.64 | 0.831501E+09 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135240E+10 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179310E+10 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213926E+10 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240589E+09 | 0.162246E+11 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453662E+09 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149595E+09 | 0.231703E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231047E+10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183545E+10 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164208E+10 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13139704.20 | 0.128165E+10 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455944.68 | 0.111691E+10 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466485.17 | 0.819661E+09 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67202528.10 | 0.556431E+09 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149612E+09 | 0.450845E+09 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785648.33 | 0.821307E+09 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133082E+10 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178262E+10 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213342E+10 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240663E+09 | 0.160817E+11 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450845E+09 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149612E+09 | 0.231047E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276605E+10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221927E+10 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200913E+10 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13738546.64 | 0.161394E+10 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1492788.00 | 0.138281E+10 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7781981.61 | 0.107240E+10 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70050074.34 | 0.769398E+09 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155572E+09 | 0.646093E+09 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1820501.46 | 0.950917E+09 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162863E+10 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213531E+10 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251467E+10 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250456E+09 | 0.197086E+11 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646093E+09 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155572E+09 | 0.276605E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 6035.26 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 6851.57 | 07-JAN-12:10 |
February | 4050.04 | 03-FEB-13:09 | 6035.26 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 7078.81 | 18-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 6035.26 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5122.21 | 22-MAR-11:10 |
April | 4050.04 | 01-APR-12:09 | 6035.26 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 996.74 | 01-APR-16:00 | 4438.64 | 18-APR-17:00 |
May | 4050.04 | 05-MAY-12:09 | 6035.26 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 321.48 | 05-MAY-16:00 | 4263.30 | 23-MAY-17:00 |
June | 4050.04 | 02-JUN-12:09 | 6035.26 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 818.14 | 28-JUN-17:00 | 3704.89 | 13-JUN-14:00 |
July | 4050.04 | 01-JUL-12:09 | 6035.26 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1923.97 | 24-JUL-15:00 | 3054.47 | 09-JUL-13:00 |
August | 4050.04 | 04-AUG-12:09 | 6035.26 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2236.67 | 10-AUG-17:00 | 3154.06 | 01-AUG-11:10 |
September | 4050.04 | 01-SEP-12:09 | 6035.26 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 323.76 | 14-SEP-17:00 | 3453.42 | 16-SEP-11:10 |
October | 4050.04 | 01-OCT-12:09 | 6035.26 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3842.84 | 31-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 6035.26 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5652.45 | 12-NOV-17:00 |
December | 4050.04 | 01-DEC-13:09 | 6035.26 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6746.90 | 26-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3054.47 | |||||
Maximum of Months | 4050.04 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2236.67 | 7078.81 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3544.17 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2024.96 | 03-FEB-13:09 | 3544.17 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 3544.17 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 3544.17 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2024.96 | 05-MAY-12:09 | 3544.17 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.98 | 05-MAY-16:00 | 2444.73 | 23-MAY-17:00 |
June | 2024.96 | 02-JUN-12:09 | 3544.17 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.29 | 28-JUN-17:00 | 2096.49 | 13-JUN-14:00 |
July | 2024.96 | 01-JUL-12:09 | 3544.17 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.56 | 24-JUL-15:00 | 1677.39 | 09-JUL-13:00 |
August | 2024.96 | 04-AUG-12:09 | 3544.17 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.08 | 10-AUG-17:00 | 1737.42 | 01-AUG-11:10 |
September | 2024.96 | 01-SEP-12:09 | 3544.17 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 1993.92 | 16-SEP-11:10 |
October | 2024.96 | 01-OCT-12:09 | 3544.17 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2086.64 | 29-OCT-11:10 |
November | 2024.96 | 03-NOV-12:09 | 3544.17 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2024.96 | 01-DEC-13:09 | 3544.17 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3544.17 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.39 | |||||
Maximum of Months | 2024.96 | 3544.17 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.08 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3181.37 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 3181.37 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3181.37 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 3181.37 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 3181.37 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.98 | 05-MAY-16:00 | 2418.65 | 23-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 3181.37 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.29 | 28-JUN-17:00 | 2073.47 | 13-JUN-14:00 |
July | 2024.96 | 01-JUL-12:09 | 3181.37 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.60 | 24-JUL-15:00 | 1677.41 | 09-JUL-13:00 |
August | 2024.96 | 05-AUG-12:09 | 3181.37 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.10 | 10-AUG-17:00 | 1738.91 | 01-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 3181.37 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.79 | 14-SEP-17:00 | 2009.92 | 16-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 3181.37 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 3181.37 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 3181.37 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.41 | |||||
Maximum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.10 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3181.37 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 3181.37 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3181.37 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 3181.37 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 3181.37 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.98 | 05-MAY-16:00 | 2408.11 | 23-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 3181.37 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.29 | 28-JUN-17:00 | 2071.68 | 13-JUN-14:00 |
July | 2024.96 | 01-JUL-12:09 | 3181.37 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.60 | 24-JUL-15:00 | 1677.41 | 09-JUL-13:00 |
August | 2024.96 | 05-AUG-12:09 | 3181.37 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.10 | 10-AUG-17:00 | 1739.44 | 01-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 3181.37 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.79 | 14-SEP-17:00 | 2010.62 | 16-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 3181.37 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 3181.37 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 3181.37 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.41 | |||||
Maximum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.10 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3181.37 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 3181.37 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3181.37 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 3181.37 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 3181.37 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.00 | 05-MAY-16:00 | 2455.80 | 23-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 3181.37 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 2128.07 | 13-JUN-14:00 |
July | 2024.96 | 01-JUL-12:09 | 3181.37 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.67 | 24-JUL-15:00 | 1677.42 | 09-JUL-13:00 |
August | 2024.96 | 05-AUG-12:09 | 3181.37 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1742.22 | 01-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 3181.37 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 2029.54 | 16-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 3181.37 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2065.65 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 3181.37 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 3181.37 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.42 | |||||
Maximum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3825.14 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 6800.61 | 07-JAN-12:10 |
February | 5400.05 | 04-FEB-15:09 | 3825.14 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6907.61 | 18-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3825.14 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5000.04 | 22-MAR-11:10 |
April | 5400.05 | 01-APR-14:09 | 3825.14 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 966.74 | 01-APR-16:00 | 4340.23 | 18-APR-17:00 |
May | 5400.05 | 06-MAY-14:09 | 3825.14 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 317.80 | 05-MAY-16:00 | 4094.39 | 23-MAY-17:00 |
June | 5400.05 | 03-JUN-14:09 | 3825.14 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 807.08 | 28-JUN-17:00 | 3559.29 | 13-JUN-14:00 |
July | 5400.05 | 01-JUL-14:09 | 3825.14 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1897.88 | 24-JUL-15:00 | 3000.85 | 09-JUL-13:00 |
August | 5400.05 | 05-AUG-14:09 | 3825.14 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2210.90 | 10-AUG-17:00 | 3086.60 | 01-AUG-11:10 |
September | 5400.05 | 02-SEP-14:09 | 3825.14 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 319.37 | 14-SEP-17:00 | 3487.32 | 16-SEP-11:10 |
October | 5400.05 | 07-OCT-14:09 | 3825.14 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3682.21 | 31-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 3825.14 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5588.12 | 12-NOV-17:00 |
December | 5400.05 | 02-DEC-15:09 | 3825.14 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6644.20 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3000.85 | |||||
Maximum of Months | 5400.05 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2210.90 | 6907.61 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.00 | 05-MAY-16:00 | 2362.45 | 23-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 2048.00 | 13-JUN-14:00 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.66 | 24-JUL-15:00 | 1677.43 | 09-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1736.43 | 01-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 2007.49 | 16-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.43 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.99 | 05-MAY-16:00 | 2353.03 | 23-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 2041.34 | 13-JUN-14:00 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.66 | 24-JUL-15:00 | 1677.43 | 09-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1734.84 | 01-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 2006.31 | 16-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.43 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.99 | 05-MAY-16:00 | 2306.37 | 23-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 2008.55 | 13-JUN-14:00 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.66 | 24-JUL-15:00 | 1677.43 | 09-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1729.79 | 01-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 1983.36 | 16-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.43 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3839.94 | 07-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4010.60 | 18-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2901.44 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 566.87 | 01-APR-16:00 | 2511.52 | 18-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.65 | 05-MAY-16:00 | 2273.64 | 23-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 460.34 | 28-JUN-17:00 | 2015.35 | 13-JUN-14:00 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.64 | 24-JUL-15:00 | 1684.11 | 09-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1256.75 | 10-AUG-17:00 | 1790.21 | 01-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.17 | 14-SEP-17:00 | 1947.83 | 16-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2201.94 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3176.04 | 12-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3817.59 | 26-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1684.11 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1256.75 | 4010.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9577.59 | 07-JAN-00:03 | 1350.01 | 12705.77 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.72 |
February | 9330.49 | 18-FEB-00:03 | 1350.01 | 12705.77 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.74 |
March | 7197.63 | 24-MAR-23:03 | 1012.51 | 9529.33 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.69 |
April | 11115.09 | 27-APR-16:10 | 3375.03 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 911.83 | 0.00 |
May | 10705.35 | 15-MAY-16:10 | 3375.03 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 25.20 | 0.00 |
June | 11907.89 | 28-JUN-17:00 | 3375.03 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 818.14 | 0.00 |
July | 27581.96 | 24-JUL-07:03 | 1350.01 | 1270.50 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.85 |
August | 27954.86 | 10-AUG-07:03 | 1350.01 | 1270.50 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.78 |
September | 12300.15 | 14-SEP-07:03 | 1012.51 | 952.88 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.04 |
October | 9824.66 | 04-OCT-16:10 | 3375.03 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 864.62 |
November | 6929.80 | 17-NOV-00:03 | 1012.51 | 952.88 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.43 |
December | 8810.38 | 22-DEC-00:03 | 1350.01 | 1270.50 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6929.80 | 1012.51 | 952.88 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27954.86 | 3375.03 | 12705.77 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 911.83 | 864.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3367.39 | 26-JAN-09:33 | 506.24 | 5596.07 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.05 |
February | 3926.63 | 13-FEB-09:43 | 506.24 | 5596.07 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.34 |
March | 3688.06 | 01-MAR-09:03 | 506.24 | 5596.07 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.01 |
April | 14302.15 | 02-APR-18:10 | 4049.92 | 10632.52 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.32 |
May | 14627.67 | 13-MAY-18:44 | 8437.34 | 17720.87 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.68 |
June | 14563.39 | 04-JUN-17:08 | 10124.81 | 17720.87 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.79 |
July | 17592.34 | 24-JUL-07:03 | 674.99 | 746.14 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.20 |
August | 16958.32 | 10-AUG-07:03 | 674.99 | 746.14 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.03 |
September | 13292.80 | 09-SEP-19:10 | 4049.92 | 14176.70 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.40 |
October | 14013.40 | 08-OCT-17:50 | 10124.81 | 17720.87 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.79 |
November | 4101.63 | 04-NOV-14:00 | 1349.97 | 3544.17 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.11 |
December | 3471.12 | 05-DEC-18:10 | 1687.47 | 3544.17 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3367.39 | 506.24 | 746.14 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.40 | |
Maximum of Months | 17592.34 | 10124.81 | 17720.87 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4655.60 | 21-JAN-09:13 | 1349.97 | 12725.50 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.18 |
February | 4920.48 | 19-FEB-10:02 | 1349.97 | 12725.50 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 639.06 |
March | 4262.53 | 02-MAR-08:61 | 1349.97 | 13395.26 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.66 |
April | 5902.25 | 27-APR-16:10 | 1687.47 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 498.92 | 0.00 |
May | 5544.05 | 15-MAY-14:00 | 1012.48 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.98 |
June | 8628.06 | 12-JUN-06:03 | 0.00 | 502.32 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.69 |
July | 18152.60 | 24-JUL-06:03 | 0.00 | 669.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.36 |
August | 19299.80 | 14-AUG-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.10 |
September | 10399.03 | 14-SEP-06:03 | 0.00 | 502.32 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5347.15 | 04-OCT-14:00 | 1012.48 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.74 |
November | 3618.87 | 04-NOV-14:00 | 1349.97 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.10 |
December | 4168.11 | 22-DEC-09:23 | 1349.97 | 12725.50 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3618.87 | 0.00 | 502.32 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19299.80 | 1687.47 | 13395.26 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.92 | 639.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3459.45 | 18-JAN-10:03 | 1012.48 | 9544.12 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.91 |
February | 4575.86 | 18-FEB-18:53 | 674.99 | 6697.63 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.87 |
March | 4208.70 | 02-MAR-08:61 | 1349.97 | 13395.26 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.25 |
April | 5796.12 | 27-APR-16:10 | 1687.47 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 498.92 | 0.00 |
May | 5488.31 | 06-MAY-13:00 | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 | 0.00 |
June | 8459.96 | 29-JUN-06:03 | 0.00 | 502.32 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.27 |
July | 18457.44 | 24-JUL-06:03 | 0.00 | 669.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.37 |
August | 19401.46 | 14-AUG-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.21 |
September | 10363.14 | 14-SEP-06:03 | 0.00 | 502.32 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5269.87 | 04-OCT-14:00 | 1012.48 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.74 |
November | 3421.38 | 04-NOV-14:00 | 1349.97 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.10 |
December | 4050.57 | 22-DEC-09:33 | 1012.48 | 9544.12 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3421.38 | 0.00 | 502.32 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19401.46 | 2024.96 | 13395.26 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.92 | 583.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3675.27 | 21-JAN-10:13 | 1012.48 | 9544.12 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 540.29 |
February | 3286.49 | 13-FEB-10:23 | 1012.48 | 9544.12 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 555.33 |
March | 3483.28 | 02-MAR-08:61 | 1349.97 | 13395.26 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.74 |
April | 5597.63 | 27-APR-16:10 | 1687.47 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 498.94 | 0.00 |
May | 5319.94 | 06-MAY-13:00 | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 0.00 |
June | 6853.41 | 29-JUN-06:03 | 0.00 | 502.32 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.30 |
July | 16989.88 | 24-JUL-06:03 | 0.00 | 669.76 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.36 |
August | 19133.21 | 14-AUG-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.02 |
September | 8839.50 | 14-SEP-06:03 | 0.00 | 502.32 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5109.29 | 04-OCT-14:00 | 1012.48 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.74 |
November | 3257.01 | 11-NOV-09:33 | 506.24 | 5023.22 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.92 |
December | 2592.62 | 05-DEC-18:10 | 1687.47 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2592.62 | 0.00 | 502.32 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19133.21 | 2024.96 | 13395.26 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.94 | 555.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6591.31 | 09-JAN-20:43 | 2227.52 | 6039.66 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.11 |
February | 6388.76 | 11-FEB-10:23 | 2227.52 | 11475.41 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.03 |
March | 5888.26 | 22-MAR-15:23 | 10935.10 | 11475.41 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4329.81 |
April | 9644.07 | 27-APR-14:50 | 4657.54 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 897.01 | 0.00 |
May | 9372.99 | 15-MAY-14:30 | 4657.54 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.44 |
June | 10509.95 | 28-JUN-15:00 | 4657.54 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 641.04 | 0.00 |
July | 31292.48 | 24-JUL-07:03 | 0.00 | 805.21 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.95 |
August | 31454.63 | 14-AUG-07:03 | 0.00 | 805.21 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.53 |
September | 12030.33 | 14-SEP-07:03 | 0.00 | 603.91 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.96 |
October | 8959.97 | 04-OCT-14:40 | 4657.54 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 704.06 |
November | 5967.93 | 10-NOV-09:33 | 2227.52 | 6039.66 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.20 |
December | 6657.24 | 31-DEC-11:53 | 2227.52 | 11475.41 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 716.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5888.26 | 0.00 | 603.91 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31454.63 | 10935.10 | 11475.41 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 897.01 | 4329.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3124.17 | 05-JAN-20:23 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.32 |
February | 1885.70 | 28-FEB-20:00 | 877.48 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.38 |
March | 2743.81 | 01-MAR-09:03 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.66 |
April | 5072.90 | 27-APR-14:50 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 499.14 | 0.00 |
May | 4860.53 | 15-MAY-14:30 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.54 |
June | 5430.77 | 28-JUN-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 356.54 | 0.00 |
July | 14995.22 | 24-JUL-07:03 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.61 |
August | 15254.07 | 14-AUG-07:03 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.29 |
September | 5778.22 | 14-SEP-14:30 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 0.00 |
October | 4703.57 | 04-OCT-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.31 |
November | 2768.41 | 22-NOV-10:05 | 742.49 | 3927.65 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.06 |
December | 2441.38 | 19-DEC-20:43 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1885.70 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15254.07 | 2328.71 | 3927.65 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 499.14 | 430.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3304.03 | 20-JAN-20:53 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.93 |
February | 3293.69 | 17-FEB-19:33 | 2632.45 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.37 |
March | 2451.00 | 03-MAR-09:03 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.10 |
April | 4988.15 | 27-APR-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 528.76 | 0.00 |
May | 4776.89 | 15-MAY-14:30 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.54 |
June | 5366.22 | 28-JUN-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 356.54 | 0.00 |
July | 14361.14 | 24-JUL-07:03 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.50 |
August | 14667.25 | 14-AUG-07:03 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.19 |
September | 5717.95 | 14-SEP-14:30 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 0.00 |
October | 4625.47 | 04-OCT-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.31 |
November | 2655.22 | 04-NOV-14:40 | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.14 |
December | 3041.96 | 11-DEC-20:43 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2451.00 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14667.25 | 2699.95 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 528.76 | 489.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3544.97 | 06-JAN-19:03 | 2632.45 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.09 |
February | 3251.08 | 17-FEB-18:23 | 3442.43 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.55 |
March | 2271.18 | 01-MAR-19:00 | 1147.48 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.71 |
April | 4727.72 | 27-APR-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 528.76 | 0.00 |
May | 4537.46 | 15-MAY-14:30 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.54 |
June | 5234.13 | 28-JUN-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 356.54 | 0.00 |
July | 12094.75 | 24-JUL-07:03 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.14 |
August | 12672.06 | 14-AUG-07:03 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.86 |
September | 5614.06 | 14-SEP-14:30 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 0.00 |
October | 4380.40 | 04-OCT-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.31 |
November | 2865.96 | 13-NOV-20:33 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.38 |
December | 3013.53 | 08-DEC-20:13 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2271.18 | 0.00 | 413.44 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12672.06 | 3442.43 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 528.76 | 487.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 461.00 | 11-JAN-18:10 | 1147.48 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.18 |
February | 1460.70 | 28-FEB-18:40 | 1147.48 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.42 |
March | 1995.47 | 01-MAR-12:00 | 1451.22 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.81 |
April | 4630.39 | 27-APR-14:50 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 514.32 | 0.00 |
May | 4379.26 | 15-MAY-14:20 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.44 |
June | 5232.55 | 28-JUN-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 369.44 | 0.00 |
July | 7018.88 | 24-JUL-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.64 | 0.00 |
August | 7355.94 | 10-AUG-14:50 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 991.10 | 0.00 |
September | 5703.15 | 14-SEP-14:20 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 0.00 |
October | 3933.38 | 04-OCT-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.96 |
November | 2526.95 | 13-NOV-11:55 | 2902.44 | 3927.65 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.54 |
December | 1118.75 | 02-DEC-11:40 | 1957.46 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 461.00 | 1147.48 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7355.94 | 2902.44 | 3927.65 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.64 | 466.54 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.832773E+11 | 65896.41 | 05-JAN-16:40 | 0.750605E+11 | 137988.08 | 16-JAN-09:09 |
February | 0.741243E+11 | 65649.99 | 07-FEB-17:00 | 0.477836E+11 | 134799.83 | 19-FEB-09:09 |
March | 0.811935E+11 | 64377.19 | 02-MAR-18:49 | 0.208467E+11 | 80030.82 | 05-MAR-09:09 |
April | 0.773052E+11 | 71837.24 | 27-APR-13:00 | 0.595420E+10 | 56645.84 | 18-APR-08:09 |
May | 0.802470E+11 | 72839.10 | 06-MAY-12:50 | 0.382831E+09 | 23843.45 | 18-MAY-08:30 |
June | 0.795858E+11 | 74106.08 | 28-JUN-16:49 | 1540563.52 | 1117.89 | 15-JUN-07:10 |
July | 0.868337E+11 | 80776.93 | 31-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.924335E+11 | 83988.27 | 29-AUG-14:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.812719E+11 | 75216.75 | 14-SEP-16:00 | 12464087.69 | 3121.86 | 28-SEP-07:10 |
October | 0.810079E+11 | 64069.98 | 04-OCT-14:39 | 0.326065E+10 | 35652.94 | 29-OCT-08:09 |
November | 0.798918E+11 | 65223.78 | 06-NOV-18:49 | 0.352750E+11 | 85630.46 | 24-NOV-08:09 |
December | 0.832495E+11 | 63924.90 | 24-DEC-16:30 | 0.623094E+11 | 128940.92 | 26-DEC-08:09 |
Annual Sum or Average | 0.980421E+12 | 0.250887E+12 | ||||
Minimum of Months | 0.741243E+11 | 63924.90 | 0.00 | 0.00 | ||
Maximum of Months | 0.924335E+11 | 83988.27 | 0.750605E+11 | 137988.08 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.420288E+11 | 0.114034E+11 | 0.108325E+11 | 0.00 | 0.134442E+11 | 0.00 | 0.00 | 81062.90 | 0.00 | 0.00 | 0.00 | 0.556843E+10 | 0.00 |
February | 0.380395E+11 | 0.926196E+10 | 0.980803E+10 | 0.00 | 0.119699E+11 | 0.00 | 0.00 | 1520890.18 | 0.00 | 0.00 | 0.00 | 0.504334E+10 | 0.00 |
March | 0.426243E+11 | 0.883153E+10 | 0.110075E+11 | 0.00 | 0.131299E+11 | 0.00 | 0.00 | 6056071.29 | 0.00 | 0.00 | 0.00 | 0.559436E+10 | 0.00 |
April | 0.407637E+11 | 0.711834E+10 | 0.105079E+11 | 0.00 | 0.124167E+11 | 0.00 | 0.00 | 0.117492E+10 | 0.00 | 0.00 | 0.00 | 0.532377E+10 | 0.00 |
May | 0.423184E+11 | 0.620411E+10 | 0.109147E+11 | 0.00 | 0.129356E+11 | 0.00 | 0.00 | 0.244436E+10 | 0.00 | 0.00 | 0.00 | 0.542980E+10 | 0.00 |
June | 0.411980E+11 | 0.541694E+10 | 0.106386E+11 | 0.00 | 0.126258E+11 | 0.00 | 0.00 | 0.449976E+10 | 0.00 | 0.00 | 0.00 | 0.520673E+10 | 0.00 |
July | 0.419004E+11 | 0.583080E+10 | 0.107945E+11 | 0.00 | 0.127748E+11 | 0.00 | 0.00 | 0.102357E+11 | 0.00 | 0.00 | 0.00 | 0.529744E+10 | 0.00 |
August | 0.426079E+11 | 0.679440E+10 | 0.110006E+11 | 0.00 | 0.130725E+11 | 0.00 | 0.00 | 0.136286E+11 | 0.00 | 0.00 | 0.00 | 0.532943E+10 | 0.00 |
September | 0.407800E+11 | 0.792464E+10 | 0.105148E+11 | 0.00 | 0.124633E+11 | 0.00 | 0.00 | 0.443401E+10 | 0.00 | 0.00 | 0.00 | 0.515520E+10 | 0.00 |
October | 0.420288E+11 | 0.966564E+10 | 0.108325E+11 | 0.00 | 0.127965E+11 | 0.00 | 0.00 | 0.300015E+09 | 0.00 | 0.00 | 0.00 | 0.538451E+10 | 0.00 |
November | 0.407147E+11 | 0.106494E+11 | 0.104978E+11 | 0.00 | 0.126710E+11 | 0.00 | 0.00 | 67657117.41 | 0.00 | 0.00 | 0.00 | 0.529123E+10 | 0.00 |
December | 0.419167E+11 | 0.117416E+11 | 0.108050E+11 | 0.00 | 0.132601E+11 | 0.00 | 0.00 | 116845.26 | 0.00 | 0.00 | 0.00 | 0.552585E+10 | 0.00 |
Annual Sum or Average | 0.496921E+12 | 0.100843E+12 | 0.128154E+12 | 0.00 | 0.153560E+12 | 0.00 | 0.00 | 0.367929E+11 | 0.00 | 0.00 | 0.00 | 0.641501E+11 | 0.00 |
Minimum of Months | 0.380395E+11 | 0.541694E+10 | 0.980803E+10 | 0.00 | 0.119699E+11 | 0.00 | 0.00 | 81062.90 | 0.00 | 0.00 | 0.00 | 0.504334E+10 | 0.00 |
Maximum of Months | 0.426243E+11 | 0.117416E+11 | 0.110075E+11 | 0.00 | 0.134442E+11 | 0.00 | 0.00 | 0.136286E+11 | 0.00 | 0.00 | 0.00 | 0.559436E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.750605E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.477836E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.208467E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.595420E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.382831E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1540563.52 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 12464087.69 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.326065E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.352750E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.623094E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.250887E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.750605E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30804.00 | 01-JAN-11:09 | 7723.25 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 10214.20 | 16-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30804.00 | 01-FEB-10:09 | 7723.25 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 10225.13 | 19-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 30804.00 | 01-MAR-10:09 | 7723.25 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 9701.34 | 05-MAR-09:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 30804.00 | 01-APR-09:09 | 7723.25 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 9539.87 | 18-APR-08:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 30804.00 | 01-MAY-09:09 | 7723.25 | 01-MAY-19:19 | 8059.50 | 01-MAY-09:09 | 0.00 | 9186.40 | 18-MAY-08:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 30804.00 | 01-JUN-09:09 | 7723.25 | 01-JUN-19:00 | 8059.50 | 01-JUN-09:09 | 0.00 | 8964.03 | 01-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 30804.00 | 01-JUL-09:09 | 7723.25 | 01-JUL-20:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 9668.19 | 24-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 30804.00 | 01-AUG-09:09 | 7723.25 | 01-AUG-19:40 | 8059.50 | 01-AUG-09:09 | 0.00 | 9699.14 | 10-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 30804.00 | 01-SEP-09:09 | 7723.25 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 8974.08 | 28-SEP-08:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 30804.00 | 01-OCT-10:09 | 7723.25 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 9298.51 | 30-OCT-08:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30804.00 | 01-NOV-09:09 | 7723.25 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 9807.35 | 30-NOV-12:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30804.00 | 01-DEC-10:09 | 7723.25 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 10196.64 | 26-DEC-12:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30804.00 | 7723.25 | 8059.50 | 0.00 | 8964.03 | 0.00 | 0.00 | |||||
Maximum of Months | 30804.00 | 7723.25 | 8059.50 | 0.00 | 10225.13 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 92.69 | 11-JAN-21:49 | 0.00 | 0.00 | 0.00 | 11853.16 | 04-JAN-13:30 | 0.00 |
February | 324.26 | 27-FEB-23:10 | 0.00 | 0.00 | 0.00 | 10769.13 | 15-FEB-14:00 | 0.00 |
March | 868.12 | 18-MAR-15:00 | 0.00 | 0.00 | 0.00 | 9720.07 | 30-MAR-13:09 | 0.00 |
April | 20183.07 | 27-APR-14:00 | 0.00 | 0.00 | 0.00 | 11797.09 | 04-APR-17:19 | 0.00 |
May | 18233.50 | 06-MAY-12:00 | 0.00 | 0.00 | 0.00 | 10571.41 | 24-MAY-12:50 | 0.00 |
June | 20044.06 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 | 7577.22 | 30-JUN-13:39 | 0.00 |
July | 27485.60 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 9642.34 | 02-JUL-12:20 | 0.00 |
August | 30114.04 | 29-AUG-14:00 | 0.00 | 0.00 | 0.00 | 7577.89 | 15-AUG-12:30 | 0.00 |
September | 20669.23 | 14-SEP-13:00 | 0.00 | 0.00 | 0.00 | 7581.03 | 15-SEP-12:00 | 0.00 |
October | 11199.34 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 9713.24 | 27-OCT-12:00 | 0.00 |
November | 6360.32 | 04-NOV-14:39 | 0.00 | 0.00 | 0.00 | 9689.50 | 06-NOV-12:39 | 0.00 |
December | 69.08 | 03-DEC-18:49 | 0.00 | 0.00 | 0.00 | 9721.01 | 11-DEC-13:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 69.08 | 0.00 | 0.00 | 0.00 | 7577.22 | 0.00 | ||
Maximum of Months | 30114.04 | 0.00 | 0.00 | 0.00 | 11853.16 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 65896.41 | 05-JAN-16:40 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 9631.68 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 65649.99 | 07-FEB-17:00 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 9380.64 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 64377.19 | 02-MAR-18:49 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 8964.03 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 71837.24 | 27-APR-13:00 | 30804.00 | 8059.50 | 0.00 | 0.00 | 8964.03 | 0.00 | 0.00 | 18547.58 | 0.00 |
May | 72839.10 | 06-MAY-12:50 | 30804.00 | 8059.50 | 0.00 | 0.00 | 8964.03 | 0.00 | 0.00 | 17847.20 | 0.00 |
June | 74106.08 | 28-JUN-16:49 | 30804.00 | 8059.50 | 0.00 | 0.00 | 8964.03 | 0.00 | 0.00 | 19926.66 | 0.00 |
July | 80776.93 | 31-JUL-14:00 | 30804.00 | 8059.50 | 0.00 | 0.00 | 9130.78 | 0.00 | 0.00 | 26055.78 | 0.00 |
August | 83988.27 | 29-AUG-14:50 | 30804.00 | 8059.50 | 0.00 | 0.00 | 9680.00 | 0.00 | 0.00 | 30000.36 | 0.00 |
September | 75216.75 | 14-SEP-16:00 | 30804.00 | 8059.50 | 0.00 | 0.00 | 8964.03 | 0.00 | 0.00 | 19836.62 | 0.00 |
October | 64069.98 | 04-OCT-14:39 | 30804.00 | 8059.50 | 0.00 | 0.00 | 8964.03 | 0.00 | 0.00 | 10799.32 | 0.00 |
November | 65223.78 | 06-NOV-18:49 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 8964.03 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 63924.90 | 24-DEC-16:30 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 9796.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 63924.90 | 30804.00 | 8059.50 | 0.00 | 0.00 | 8964.03 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83988.27 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 9796.54 | 0.00 | 0.00 | 30000.36 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 137988.08 | 16-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 134799.83 | 19-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 80030.82 | 05-MAR-09:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 56645.84 | 18-APR-08:09 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 23843.45 | 18-MAY-08:30 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1117.89 | 15-JUN-07:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 3121.86 | 28-SEP-07:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 35652.94 | 29-OCT-08:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 85630.46 | 24-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 128940.92 | 26-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 137988.08 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
February | 0.50 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Annual Sum or Average | 2.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
February | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
February | 2.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
March | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Annual Sum or Average | 6.67 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.08 | 106.17 | 21.06 | 106.17 | 21.04 |
February | 446.50 | 21.20 | 70.50 | 21.17 | 70.50 | 21.14 |
March | 497.00 | 21.39 | 21.50 | 21.37 | 21.50 | 21.35 |
April | 406.67 | 21.92 | 28.00 | 22.02 | 3.67 | 22.02 |
May | 262.83 | 22.60 | 76.83 | 22.89 | 0.00 | 22.89 |
June | 88.83 | 23.13 | 187.33 | 23.65 | 0.00 | 23.65 |
July | 24.83 | 23.55 | 351.00 | 23.87 | 0.00 | 23.87 |
August | 17.67 | 23.38 | 406.17 | 23.87 | 0.00 | 23.87 |
September | 98.83 | 22.93 | 260.83 | 23.62 | 0.00 | 23.62 |
October | 365.83 | 21.96 | 28.83 | 22.10 | 0.00 | 22.10 |
November | 459.00 | 21.27 | 29.50 | 21.30 | 20.17 | 21.29 |
December | 496.00 | 21.08 | 61.00 | 21.06 | 61.00 | 21.04 |
Annual Sum or Average | 3660.00 | 21.58 | 1627.67 | 22.13 | 283.00 | 22.07 |
Minimum of Months | 17.67 | 21.08 | 21.50 | 21.06 | 0.00 | 21.04 |
Maximum of Months | 497.00 | 23.55 | 406.17 | 23.87 | 106.17 | 23.87 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.60 | 8.33 | 21.60 | 8.33 | 21.59 |
February | 437.33 | 21.82 | 6.33 | 21.81 | 6.33 | 21.80 |
March | 484.33 | 22.24 | 0.00 | 22.24 | 0.00 | 22.24 |
April | 347.00 | 22.70 | 40.00 | 22.82 | 0.00 | 22.82 |
May | 133.67 | 23.12 | 97.83 | 23.44 | 0.00 | 23.44 |
June | 33.17 | 23.48 | 213.67 | 23.83 | 0.00 | 23.83 |
July | 10.17 | 23.72 | 356.00 | 23.87 | 0.00 | 23.87 |
August | 2.33 | 23.37 | 414.33 | 23.87 | 0.00 | 23.87 |
September | 38.00 | 23.27 | 306.17 | 23.81 | 0.00 | 23.81 |
October | 295.00 | 22.75 | 43.50 | 22.89 | 0.00 | 22.89 |
November | 442.83 | 21.92 | 22.17 | 22.02 | 0.00 | 22.02 |
December | 496.00 | 21.68 | 0.83 | 21.68 | 0.83 | 21.68 |
Annual Sum or Average | 3215.83 | 22.12 | 1509.17 | 22.67 | 15.50 | 22.67 |
Minimum of Months | 2.33 | 21.60 | 0.00 | 21.60 | 0.00 | 21.59 |
Maximum of Months | 496.00 | 23.72 | 414.33 | 23.87 | 8.33 | 23.87 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.12 | 33.50 | 21.12 | 33.50 | 21.12 |
February | 330.83 | 21.26 | 19.33 | 21.25 | 19.33 | 21.24 |
March | 377.17 | 21.57 | 1.67 | 21.57 | 1.67 | 21.57 |
April | 290.67 | 22.14 | 26.67 | 22.29 | 0.00 | 22.29 |
May | 140.33 | 22.78 | 75.33 | 23.21 | 0.00 | 23.21 |
June | 39.83 | 23.21 | 169.50 | 23.87 | 0.00 | 23.87 |
July | 8.00 | 23.51 | 284.83 | 24.01 | 0.00 | 24.01 |
August | 8.00 | 23.53 | 339.50 | 24.00 | 0.33 | 24.00 |
September | 56.83 | 23.02 | 219.00 | 23.77 | 0.00 | 23.77 |
October | 253.67 | 22.14 | 28.67 | 22.33 | 0.00 | 22.33 |
November | 346.50 | 21.35 | 10.67 | 21.42 | 1.50 | 21.42 |
December | 369.00 | 21.13 | 16.17 | 21.13 | 16.17 | 21.13 |
Annual Sum or Average | 2591.83 | 21.63 | 1224.83 | 22.34 | 72.50 | 22.31 |
Minimum of Months | 8.00 | 21.12 | 1.67 | 21.12 | 0.00 | 21.12 |
Maximum of Months | 377.17 | 23.53 | 339.50 | 24.01 | 33.50 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.12 | 46.17 | 21.12 | 46.17 | 21.11 |
February | 334.67 | 21.27 | 25.67 | 21.26 | 25.67 | 21.25 |
March | 379.00 | 21.53 | 3.50 | 21.52 | 3.50 | 21.52 |
April | 294.67 | 22.07 | 24.83 | 22.22 | 0.00 | 22.22 |
May | 148.33 | 22.75 | 72.83 | 23.17 | 0.00 | 23.17 |
June | 41.17 | 23.19 | 164.67 | 23.86 | 0.00 | 23.86 |
July | 9.33 | 23.48 | 281.50 | 24.00 | 0.00 | 24.00 |
August | 8.17 | 23.51 | 338.50 | 24.00 | 0.33 | 24.00 |
September | 59.50 | 22.99 | 214.17 | 23.75 | 0.00 | 23.75 |
October | 263.33 | 22.09 | 25.83 | 22.25 | 0.00 | 22.25 |
November | 347.83 | 21.32 | 12.00 | 21.38 | 4.00 | 21.37 |
December | 369.00 | 21.12 | 22.83 | 21.12 | 22.83 | 21.12 |
Annual Sum or Average | 2626.00 | 21.61 | 1232.50 | 22.30 | 102.50 | 22.27 |
Minimum of Months | 8.17 | 21.12 | 3.50 | 21.12 | 0.00 | 21.11 |
Maximum of Months | 379.00 | 23.51 | 338.50 | 24.00 | 46.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.12 | 61.17 | 21.12 | 61.17 | 21.12 |
February | 336.00 | 21.33 | 32.50 | 21.31 | 32.50 | 21.30 |
March | 379.00 | 21.68 | 5.67 | 21.67 | 5.67 | 21.67 |
April | 293.33 | 22.31 | 27.67 | 22.45 | 0.00 | 22.45 |
May | 131.67 | 22.97 | 67.83 | 23.34 | 0.00 | 23.34 |
June | 30.83 | 23.40 | 157.00 | 23.96 | 0.00 | 23.96 |
July | 6.00 | 23.83 | 278.00 | 24.05 | 0.17 | 24.05 |
August | 4.33 | 24.03 | 335.50 | 24.04 | 0.50 | 24.04 |
September | 45.17 | 23.21 | 215.00 | 23.86 | 0.00 | 23.86 |
October | 254.50 | 22.31 | 21.83 | 22.44 | 0.00 | 22.44 |
November | 346.83 | 21.41 | 15.00 | 21.46 | 7.17 | 21.45 |
December | 369.00 | 21.14 | 33.83 | 21.13 | 33.83 | 21.13 |
Annual Sum or Average | 2567.67 | 21.70 | 1251.00 | 22.36 | 141.00 | 22.31 |
Minimum of Months | 4.33 | 21.12 | 5.67 | 21.12 | 0.00 | 21.12 |
Maximum of Months | 379.00 | 24.03 | 335.50 | 24.05 | 61.17 | 24.05 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 113.50 | 21.11 | 113.50 | 21.11 |
February | 308.00 | 21.20 | 69.50 | 21.18 | 69.50 | 21.17 |
March | 348.00 | 21.29 | 12.67 | 21.29 | 12.67 | 21.28 |
April | 295.17 | 21.79 | 16.50 | 21.90 | 0.67 | 21.89 |
May | 217.50 | 22.55 | 46.00 | 22.80 | 0.00 | 22.80 |
June | 75.67 | 23.03 | 97.50 | 23.55 | 0.00 | 23.55 |
July | 17.17 | 23.36 | 225.67 | 23.90 | 0.00 | 23.90 |
August | 13.67 | 23.26 | 280.17 | 23.89 | 0.17 | 23.89 |
September | 96.17 | 22.72 | 142.00 | 23.44 | 0.00 | 23.44 |
October | 269.50 | 21.76 | 9.00 | 21.83 | 0.00 | 21.83 |
November | 324.17 | 21.20 | 17.33 | 21.22 | 14.50 | 21.21 |
December | 338.00 | 21.11 | 67.50 | 21.11 | 67.50 | 21.11 |
Annual Sum or Average | 2643.00 | 21.56 | 1097.33 | 22.04 | 278.50 | 21.98 |
Minimum of Months | 13.67 | 21.11 | 9.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.36 | 280.17 | 23.90 | 113.50 | 23.90 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 113.67 | 21.11 | 113.67 | 21.11 |
February | 308.00 | 21.25 | 72.33 | 21.22 | 72.33 | 21.20 |
March | 348.00 | 21.45 | 14.17 | 21.44 | 14.17 | 21.42 |
April | 295.50 | 22.08 | 15.67 | 22.16 | 1.00 | 22.16 |
May | 195.00 | 22.92 | 39.00 | 23.10 | 0.00 | 23.10 |
June | 53.67 | 23.36 | 79.33 | 23.73 | 0.00 | 23.73 |
July | 12.83 | 23.67 | 212.83 | 23.94 | 0.00 | 23.94 |
August | 9.83 | 23.65 | 264.00 | 23.92 | 0.33 | 23.93 |
September | 73.67 | 23.07 | 139.33 | 23.64 | 0.00 | 23.64 |
October | 260.50 | 22.05 | 6.17 | 22.09 | 0.00 | 22.09 |
November | 322.00 | 21.27 | 18.50 | 21.28 | 15.83 | 21.27 |
December | 338.00 | 21.12 | 68.83 | 21.12 | 68.83 | 21.12 |
Annual Sum or Average | 2557.00 | 21.67 | 1043.83 | 22.10 | 286.17 | 22.03 |
Minimum of Months | 9.83 | 21.11 | 6.17 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.67 | 264.00 | 23.94 | 113.67 | 23.94 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 122.67 | 21.11 | 122.67 | 21.11 |
February | 308.00 | 21.24 | 83.17 | 21.21 | 83.17 | 21.19 |
March | 348.00 | 21.43 | 16.67 | 21.41 | 16.67 | 21.40 |
April | 296.17 | 22.05 | 16.00 | 22.13 | 1.83 | 22.12 |
May | 203.83 | 22.90 | 37.33 | 23.07 | 0.00 | 23.07 |
June | 58.83 | 23.35 | 75.33 | 23.71 | 0.00 | 23.71 |
July | 14.83 | 23.65 | 209.00 | 23.93 | 0.00 | 23.93 |
August | 10.83 | 23.56 | 260.00 | 23.92 | 0.17 | 23.92 |
September | 76.67 | 23.05 | 135.83 | 23.62 | 0.00 | 23.62 |
October | 262.50 | 22.02 | 5.33 | 22.06 | 0.00 | 22.06 |
November | 322.50 | 21.26 | 18.83 | 21.26 | 18.17 | 21.25 |
December | 338.00 | 21.12 | 75.50 | 21.12 | 75.50 | 21.11 |
Annual Sum or Average | 2580.17 | 21.66 | 1055.67 | 22.08 | 318.17 | 22.00 |
Minimum of Months | 10.83 | 21.11 | 5.33 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.65 | 260.00 | 23.93 | 122.67 | 23.93 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 152.67 | 21.11 | 152.67 | 21.11 |
February | 308.00 | 21.22 | 110.17 | 21.19 | 110.17 | 21.17 |
March | 348.00 | 21.35 | 27.00 | 21.33 | 27.00 | 21.32 |
April | 299.17 | 21.93 | 16.83 | 22.00 | 4.17 | 21.99 |
May | 231.83 | 22.77 | 33.67 | 22.93 | 0.00 | 22.93 |
June | 81.67 | 23.29 | 64.50 | 23.60 | 0.00 | 23.60 |
July | 20.33 | 23.58 | 199.50 | 23.92 | 0.00 | 23.92 |
August | 13.83 | 23.47 | 249.67 | 23.91 | 0.17 | 23.91 |
September | 93.83 | 22.94 | 123.17 | 23.51 | 0.00 | 23.51 |
October | 272.67 | 21.93 | 3.50 | 21.95 | 0.00 | 21.95 |
November | 324.17 | 21.23 | 25.67 | 21.22 | 25.67 | 21.22 |
December | 338.00 | 21.11 | 100.33 | 21.11 | 100.33 | 21.11 |
Annual Sum or Average | 2671.50 | 21.65 | 1106.67 | 22.01 | 420.17 | 21.92 |
Minimum of Months | 13.83 | 21.11 | 3.50 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.58 | 249.67 | 23.92 | 152.67 | 23.92 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 283.83 | 21.11 | 283.83 | 21.11 |
February | 308.00 | 21.18 | 164.17 | 21.16 | 164.17 | 21.14 |
March | 348.00 | 21.24 | 80.00 | 21.22 | 80.00 | 21.20 |
April | 303.67 | 21.75 | 27.17 | 21.77 | 19.00 | 21.73 |
May | 257.67 | 22.45 | 23.67 | 22.58 | 0.33 | 22.58 |
June | 134.67 | 23.15 | 56.00 | 23.40 | 0.00 | 23.40 |
July | 45.17 | 23.41 | 180.50 | 23.84 | 0.00 | 23.84 |
August | 26.00 | 23.33 | 227.50 | 23.87 | 0.33 | 23.88 |
September | 134.50 | 22.71 | 105.83 | 23.25 | 0.00 | 23.25 |
October | 290.83 | 21.78 | 4.33 | 21.77 | 4.33 | 21.76 |
November | 325.17 | 21.18 | 105.50 | 21.16 | 105.50 | 21.15 |
December | 338.00 | 21.11 | 236.17 | 21.11 | 236.17 | 21.11 |
Annual Sum or Average | 2851.67 | 21.63 | 1494.67 | 21.84 | 893.67 | 21.72 |
Minimum of Months | 26.00 | 21.11 | 4.33 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.41 | 283.83 | 23.87 | 283.83 | 23.88 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.08039 | 30.39612 | -0.4760 | 9.90925 |
February | 448.00000 | 21.20776 | 32.07824 | -0.4036 | 9.02325 |
March | 497.00000 | 21.38813 | 33.22340 | -0.3094 | 7.56389 |
April | 479.00000 | 22.20735 | 36.29487 | -0.0655 | 6.64047 |
May | 496.00000 | 23.19331 | 39.21923 | -0.7377 | 18.24570 |
June | 481.00000 | 23.72886 | 40.31075 | -0.5216 | 11.22987 |
July | 495.00000 | 23.86018 | 44.01104 | -0.4096 | 8.79371 |
August | 497.00000 | 23.86090 | 47.09084 | -0.3846 | 8.35819 |
September | 479.00000 | 23.65882 | 45.97262 | -0.5050 | 11.17193 |
October | 496.00000 | 22.45959 | 40.21800 | 0.02949 | 6.50088 |
November | 480.00000 | 21.38421 | 38.89208 | -0.2931 | 7.81282 |
December | 496.00000 | 21.08016 | 32.64126 | -0.4452 | 9.28234 |
Annual Sum or Average | 5840.00000 | 22.43219 | 38.39108 | -0.3770 | 9.55236 |
Minimum of Months | 448.00000 | 21.08016 | 30.39612 | -0.7377 | 6.50088 |
Maximum of Months | 497.00000 | 23.86090 | 47.09084 | 0.02949 | 18.24570 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.60328 | 32.46543 | -0.3102 | 7.54391 |
February | 448.00000 | 21.86894 | 33.32839 | -0.2213 | 7.12615 |
March | 497.00000 | 22.28541 | 33.27706 | -0.0938 | 6.13042 |
April | 479.00000 | 23.01713 | 35.51366 | 0.12350 | 6.39980 |
May | 496.00000 | 23.65475 | 38.18308 | -0.5801 | 12.75771 |
June | 481.00000 | 23.83722 | 39.78973 | -0.4704 | 9.81895 |
July | 495.00000 | 23.85967 | 43.51556 | -0.4036 | 8.58516 |
August | 497.00000 | 23.85175 | 46.44682 | -0.3814 | 8.21025 |
September | 479.00000 | 23.80089 | 45.15783 | -0.4484 | 9.54218 |
October | 496.00000 | 23.19975 | 39.09505 | 0.19907 | 6.63606 |
November | 480.00000 | 22.07367 | 39.66745 | -0.1158 | 6.65631 |
December | 496.00000 | 21.68220 | 34.50415 | -0.2706 | 7.16383 |
Annual Sum or Average | 5840.00000 | 22.89971 | 38.43525 | -0.2482 | 8.05445 |
Minimum of Months | 448.00000 | 21.60328 | 32.46543 | -0.5801 | 6.13042 |
Maximum of Months | 497.00000 | 23.85967 | 46.44682 | 0.19907 | 12.75771 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11832 | 30.30052 | -0.4303 | 8.97768 |
February | 336.00000 | 21.30049 | 31.57200 | -0.3492 | 8.19073 |
March | 379.00000 | 21.58432 | 32.18249 | -0.2392 | 6.84942 |
April | 360.00000 | 22.47689 | 35.08492 | 0.01021 | 6.44418 |
May | 375.00000 | 23.47168 | 38.20972 | -0.6320 | 14.64513 |
June | 366.00000 | 23.86555 | 39.18765 | -0.4693 | 9.99364 |
July | 369.00000 | 23.97674 | 43.48413 | -0.3724 | 8.22182 |
August | 379.00000 | 23.98110 | 46.63144 | -0.3439 | 7.79053 |
September | 360.00000 | 23.77278 | 44.98807 | -0.4599 | 10.09952 |
October | 371.00000 | 22.69177 | 38.73954 | 0.09296 | 6.41521 |
November | 360.00000 | 21.44388 | 38.24753 | -0.2563 | 7.31060 |
December | 369.00000 | 21.12757 | 32.11566 | -0.4030 | 8.49038 |
Annual Sum or Average | 4395.00000 | 22.57785 | 37.60081 | -0.3214 | 8.62693 |
Minimum of Months | 336.00000 | 21.11832 | 30.30052 | -0.6320 | 6.41521 |
Maximum of Months | 379.00000 | 23.98110 | 46.63144 | 0.09296 | 14.64513 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11620 | 30.30520 | -0.4434 | 9.22268 |
February | 336.00000 | 21.27657 | 31.63287 | -0.3646 | 8.37518 |
March | 379.00000 | 21.52816 | 32.28794 | -0.2594 | 7.02010 |
April | 360.00000 | 22.40223 | 35.23823 | -0.0116 | 6.49301 |
May | 375.00000 | 23.43698 | 38.30442 | -0.6472 | 15.13226 |
June | 366.00000 | 23.85804 | 39.21407 | -0.4742 | 10.10476 |
July | 369.00000 | 23.97421 | 43.50100 | -0.3746 | 8.26046 |
August | 379.00000 | 23.97950 | 46.64106 | -0.3451 | 7.80959 |
September | 360.00000 | 23.75914 | 45.04249 | -0.4667 | 10.27407 |
October | 371.00000 | 22.61319 | 38.92940 | 0.07115 | 6.43632 |
November | 360.00000 | 21.40679 | 38.34972 | -0.2737 | 7.45008 |
December | 369.00000 | 21.12245 | 32.12274 | -0.4152 | 8.69977 |
Annual Sum or Average | 4395.00000 | 22.54973 | 37.66949 | -0.3340 | 8.78122 |
Minimum of Months | 336.00000 | 21.11620 | 30.30520 | -0.6472 | 6.43632 |
Maximum of Months | 379.00000 | 23.97950 | 46.64106 | 0.07115 | 15.13226 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.12322 | 30.27027 | -0.4576 | 9.50799 |
February | 336.00000 | 21.33207 | 31.47152 | -0.3691 | 8.54088 |
March | 379.00000 | 21.68201 | 31.98376 | -0.2455 | 6.99050 |
April | 360.00000 | 22.61040 | 34.79799 | 0.01152 | 6.48409 |
May | 375.00000 | 23.58847 | 37.94668 | -0.6251 | 14.33792 |
June | 366.00000 | 23.92623 | 39.05361 | -0.4684 | 9.94131 |
July | 369.00000 | 24.00861 | 43.85781 | -0.3718 | 8.24841 |
August | 379.00000 | 24.01290 | 47.17830 | -0.3410 | 7.78087 |
September | 360.00000 | 23.85341 | 45.02567 | -0.4532 | 9.90435 |
October | 371.00000 | 22.81497 | 38.40512 | 0.09373 | 6.42385 |
November | 360.00000 | 21.49766 | 38.09583 | -0.2708 | 7.54846 |
December | 369.00000 | 21.13573 | 32.08720 | -0.4268 | 8.92035 |
Annual Sum or Average | 4395.00000 | 22.64257 | 37.55490 | -0.3273 | 8.72505 |
Minimum of Months | 336.00000 | 21.12322 | 30.27027 | -0.6251 | 6.42385 |
Maximum of Months | 379.00000 | 24.01290 | 47.17830 | 0.09373 | 14.33792 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10980 | 31.82772 | -0.5054 | 10.44558 |
February | 308.00000 | 21.19698 | 33.32408 | -0.4312 | 9.32431 |
March | 348.00000 | 21.29453 | 34.23075 | -0.3461 | 7.88175 |
April | 330.00000 | 22.01241 | 37.43612 | -0.1224 | 6.77646 |
May | 344.00000 | 23.04688 | 40.62770 | -0.7970 | 20.22976 |
June | 336.00000 | 23.69524 | 40.75218 | -0.5537 | 11.99794 |
July | 338.00000 | 23.88040 | 44.97929 | -0.4236 | 9.06181 |
August | 348.00000 | 23.88118 | 48.04266 | -0.3952 | 8.54533 |
September | 330.00000 | 23.52903 | 47.03154 | -0.5633 | 12.86989 |
October | 340.00000 | 22.19963 | 41.28624 | -0.0436 | 6.57240 |
November | 330.00000 | 21.24380 | 40.28069 | -0.3536 | 8.20961 |
December | 338.00000 | 21.11058 | 33.63245 | -0.4738 | 9.78327 |
Annual Sum or Average | 4030.00000 | 22.36001 | 39.49382 | -0.4179 | 10.15560 |
Minimum of Months | 308.00000 | 21.10980 | 31.82772 | -0.7970 | 6.57240 |
Maximum of Months | 348.00000 | 23.88118 | 48.04266 | -0.0436 | 20.22976 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11344 | 31.70288 | -0.5061 | 10.46193 |
February | 308.00000 | 21.24597 | 33.07553 | -0.4279 | 9.35274 |
March | 348.00000 | 21.44828 | 33.82435 | -0.3278 | 7.76376 |
April | 330.00000 | 22.27227 | 36.75389 | -0.0885 | 6.65514 |
May | 344.00000 | 23.34972 | 39.71438 | -0.7380 | 17.87696 |
June | 336.00000 | 23.81968 | 40.16765 | -0.5419 | 11.48808 |
July | 338.00000 | 23.92010 | 44.98255 | -0.4341 | 9.20102 |
August | 348.00000 | 23.91099 | 48.24041 | -0.4069 | 8.69644 |
September | 330.00000 | 23.71144 | 46.46506 | -0.5338 | 11.74423 |
October | 340.00000 | 22.47891 | 40.43888 | -0.0041 | 6.49750 |
November | 330.00000 | 21.33146 | 39.91051 | -0.3441 | 8.20975 |
December | 338.00000 | 21.11740 | 33.50799 | -0.4749 | 9.80876 |
Annual Sum or Average | 4030.00000 | 22.48699 | 39.10536 | -0.4027 | 9.82407 |
Minimum of Months | 308.00000 | 21.11344 | 31.70288 | -0.7380 | 6.49750 |
Maximum of Months | 348.00000 | 23.92010 | 48.24041 | -0.0041 | 17.87696 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11257 | 31.70514 | -0.5113 | 10.57232 |
February | 308.00000 | 21.23946 | 33.09265 | -0.4344 | 9.46055 |
March | 348.00000 | 21.42787 | 33.86243 | -0.3365 | 7.86984 |
April | 330.00000 | 22.24058 | 36.82183 | -0.0986 | 6.70232 |
May | 344.00000 | 23.31592 | 39.80514 | -0.7526 | 18.39660 |
June | 336.00000 | 23.81033 | 40.20637 | -0.5490 | 11.67041 |
July | 338.00000 | 23.91725 | 45.00855 | -0.4392 | 9.29955 |
August | 348.00000 | 23.90887 | 48.26458 | -0.4114 | 8.77739 |
September | 330.00000 | 23.69904 | 46.51700 | -0.5410 | 11.93631 |
October | 340.00000 | 22.45108 | 40.51099 | -0.0127 | 6.51500 |
November | 330.00000 | 21.32135 | 39.93983 | -0.3507 | 8.29260 |
December | 338.00000 | 21.11658 | 33.50878 | -0.4801 | 9.91124 |
Annual Sum or Average | 4030.00000 | 22.47372 | 39.14376 | -0.4102 | 9.96204 |
Minimum of Months | 308.00000 | 21.11257 | 31.70514 | -0.7526 | 6.51500 |
Maximum of Months | 348.00000 | 23.91725 | 48.26458 | -0.0127 | 18.39660 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11089 | 31.70966 | -0.5288 | 10.95687 |
February | 308.00000 | 21.21664 | 33.15221 | -0.4561 | 9.82797 |
March | 348.00000 | 21.35238 | 34.00669 | -0.3677 | 8.26641 |
April | 330.00000 | 22.11387 | 37.09052 | -0.1375 | 6.90705 |
May | 344.00000 | 23.14809 | 40.22921 | -0.8192 | 20.92581 |
June | 336.00000 | 23.75748 | 40.38385 | -0.5772 | 12.48170 |
July | 338.00000 | 23.90507 | 45.09253 | -0.4518 | 9.57311 |
August | 348.00000 | 23.90040 | 48.32970 | -0.4209 | 8.97560 |
September | 330.00000 | 23.62181 | 46.78732 | -0.5751 | 12.99542 |
October | 340.00000 | 22.31757 | 40.84425 | -0.0518 | 6.60977 |
November | 330.00000 | 21.27965 | 40.05919 | -0.3738 | 8.58025 |
December | 338.00000 | 21.11294 | 33.51349 | -0.4972 | 10.26167 |
Annual Sum or Average | 4030.00000 | 22.41314 | 39.30723 | -0.4385 | 10.54483 |
Minimum of Months | 308.00000 | 21.11089 | 31.70966 | -0.8192 | 6.60977 |
Maximum of Months | 348.00000 | 23.90507 | 48.32970 | -0.0518 | 20.92581 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 31.54075 | -0.5987 | 12.64009 |
February | 308.00000 | 21.18148 | 33.06848 | -0.5297 | 11.34233 |
March | 348.00000 | 21.24350 | 34.08739 | -0.4493 | 9.60869 |
April | 330.00000 | 21.92219 | 37.37184 | -0.2182 | 7.57356 |
May | 344.00000 | 22.82466 | 40.86587 | -0.9613 | 26.89539 |
June | 336.00000 | 23.61297 | 40.69448 | -0.6483 | 14.87438 |
July | 338.00000 | 23.85927 | 45.15646 | -0.4834 | 10.42109 |
August | 348.00000 | 23.87227 | 48.33373 | -0.4403 | 9.52335 |
September | 330.00000 | 23.41880 | 47.32366 | -0.6643 | 16.20267 |
October | 340.00000 | 22.08356 | 41.27643 | -0.1386 | 7.05173 |
November | 330.00000 | 21.22258 | 40.01176 | -0.4410 | 9.70134 |
December | 338.00000 | 21.10998 | 33.34804 | -0.5635 | 11.76200 |
Annual Sum or Average | 4030.00000 | 22.29807 | 39.46516 | -0.5118 | 12.31809 |
Minimum of Months | 308.00000 | 21.10998 | 31.54075 | -0.9613 | 7.05173 |
Maximum of Months | 348.00000 | 23.87227 | 48.33373 | -0.1386 | 26.89539 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 1495970.40 | 418429.67 | 1.17 | 1495970.40 | 0.00 | 0.00 | 0.07 | 18-MAR-16:10 | 0.00 | 01-MAR-00:10 | 835.95 | 18-MAR-16:10 | 835.95 | 18-MAR-16:10 | 0.00 | 18-MAR-16:00 | 232.45 | 18-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.895161E+09 | 0.230288E+09 | 42.33 | 0.855551E+09 | 39609501.79 | 0.00 | 0.84 | 27-APR-16:10 | 0.00 | 01-APR-00:05 | 14145.74 | 27-APR-16:10 | 13554.21 | 27-APR-16:10 | 1010.26 | 29-APR-17:20 | 3482.36 | 27-APR-16:10 | 0.00 | 01-APR-00:05 |
May | 0.204088E+10 | 0.511812E+09 | 98.90 | 0.180680E+10 | 0.234077E+09 | 0.00 | 0.77 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 | 13140.11 | 06-MAY-13:00 | 11750.33 | 15-MAY-17:00 | 2651.21 | 06-MAY-12:50 | 3116.00 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.368321E+10 | 0.929691E+09 | 204.08 | 0.344020E+10 | 0.243006E+09 | 0.00 | 0.87 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 14720.90 | 28-JUN-17:00 | 14189.32 | 28-JUN-17:00 | 1514.17 | 11-JUN-12:10 | 3575.17 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.869509E+10 | 0.213772E+10 | 336.42 | 0.747553E+10 | 0.121956E+10 | 0.00 | 1.00 | 24-JUL-07:03 | 0.00 | 01-JUL-00:05 | 29602.32 | 24-JUL-07:03 | 22862.23 | 24-JUL-07:03 | 7540.86 | 31-JUL-07:03 | 6303.68 | 24-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.112353E+11 | 0.275042E+10 | 369.20 | 0.967084E+10 | 0.156443E+10 | 0.00 | 1.00 | 08-AUG-07:03 | 0.00 | 01-AUG-00:10 | 32408.57 | 10-AUG-07:03 | 23799.55 | 10-AUG-07:03 | 9355.90 | 30-AUG-07:03 | 6891.64 | 10-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.371070E+10 | 0.908022E+09 | 170.53 | 0.302272E+10 | 0.687973E+09 | 0.00 | 0.89 | 14-SEP-16:10 | 0.00 | 01-SEP-00:10 | 15537.05 | 14-SEP-14:00 | 13450.97 | 14-SEP-16:30 | 4000.77 | 23-SEP-14:00 | 3566.35 | 14-SEP-16:20 | 0.00 | 01-SEP-00:10 |
October | 0.239675E+09 | 61927331.18 | 23.83 | 0.233810E+09 | 5865622.24 | 0.00 | 0.54 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 7977.75 | 04-OCT-15:00 | 7977.75 | 04-OCT-15:00 | 697.91 | 08-OCT-14:00 | 1968.50 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 48299650.70 | 12898751.91 | 4.83 | 35990564.26 | 12309086.43 | 0.00 | 0.30 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4439.51 | 04-NOV-14:00 | 3369.95 | 04-NOV-14:00 | 1069.56 | 04-NOV-14:00 | 1165.31 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.305498E+11 | 0.754320E+10 | 1251.29 | 0.265429E+11 | 0.400683E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.112353E+11 | 0.275042E+10 | 369.20 | 0.967084E+10 | 0.156443E+10 | 0.00 | 1.00 | 0.00 | 32408.57 | 23799.55 | 9355.90 | 6891.64 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 288007.43 | 81062.90 | 0.50 | 263357.69 | 24649.74 | 0.00 | 0.05 | 11-JAN-21:50 | 0.00 | 01-JAN-00:10 | 329.89 | 11-JAN-21:50 | 291.28 | 11-JAN-21:50 | 38.61 | 11-JAN-21:50 | 92.69 | 11-JAN-21:50 | 0.00 | 01-JAN-00:10 |
February | 5380831.87 | 1489585.50 | 4.39 | 5140192.64 | 240639.23 | 0.00 | 0.16 | 27-FEB-23:10 | 0.00 | 01-FEB-00:10 | 1188.68 | 27-FEB-23:10 | 1062.30 | 27-FEB-23:10 | 138.37 | 25-FEB-19:40 | 324.26 | 27-FEB-23:10 | 0.00 | 01-FEB-00:10 |
March | 13736560.45 | 3797850.53 | 9.75 | 13558811.30 | 177749.15 | 0.00 | 0.20 | 02-MAR-21:17 | 0.00 | 01-MAR-00:10 | 1444.34 | 02-MAR-21:17 | 1404.87 | 02-MAR-21:17 | 105.05 | 11-MAR-00:10 | 388.62 | 02-MAR-21:17 | 0.00 | 01-MAR-00:10 |
April | 0.663874E+09 | 0.164791E+09 | 50.20 | 0.632850E+09 | 31024155.56 | 0.00 | 1.00 | 01-APR-18:32 | 0.00 | 01-APR-00:05 | 18690.47 | 29-APR-18:02 | 18157.36 | 01-APR-18:40 | 3765.53 | 29-APR-18:02 | 4035.92 | 01-APR-18:40 | 0.00 | 01-APR-00:05 |
May | 0.144177E+10 | 0.351223E+09 | 108.54 | 0.127413E+10 | 0.167641E+09 | 0.00 | 1.00 | 03-MAY-20:02 | 0.00 | 01-MAY-00:10 | 19412.52 | 07-MAY-17:03 | 18222.63 | 14-MAY-17:48 | 6115.64 | 06-MAY-19:08 | 4155.12 | 07-MAY-17:03 | 0.00 | 01-MAY-00:10 |
June | 0.265351E+10 | 0.649077E+09 | 222.42 | 0.245307E+10 | 0.200447E+09 | 0.00 | 1.00 | 02-JUN-20:06 | 0.00 | 01-JUN-00:10 | 19148.00 | 11-JUN-18:03 | 18476.30 | 25-JUN-17:28 | 4698.29 | 28-JUN-20:42 | 4127.73 | 10-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 0.566777E+10 | 0.135959E+10 | 337.17 | 0.484515E+10 | 0.822616E+09 | 0.00 | 1.00 | 01-JUL-18:02 | 0.00 | 01-JUL-00:05 | 19870.18 | 15-JUL-18:03 | 18104.81 | 07-JUL-20:58 | 6735.19 | 15-JUL-21:20 | 4284.16 | 15-JUL-18:03 | 0.00 | 01-JUL-00:05 |
August | 0.715779E+10 | 0.171180E+10 | 364.78 | 0.611650E+10 | 0.104129E+10 | 0.00 | 1.00 | 05-AUG-18:02 | 0.00 | 01-AUG-00:10 | 19745.30 | 26-AUG-18:03 | 18533.22 | 08-AUG-22:00 | 7378.47 | 26-AUG-19:47 | 4319.62 | 24-AUG-20:53 | 0.00 | 01-AUG-00:10 |
September | 0.258057E+10 | 0.615486E+09 | 188.64 | 0.209129E+10 | 0.489281E+09 | 0.00 | 1.00 | 02-SEP-18:02 | 0.00 | 01-SEP-00:10 | 19585.54 | 23-SEP-18:03 | 18056.04 | 10-SEP-17:03 | 6719.49 | 15-SEP-20:27 | 4160.63 | 23-SEP-18:03 | 0.00 | 01-SEP-00:10 |
October | 0.219522E+09 | 55607017.90 | 44.17 | 0.207674E+09 | 11848117.03 | 0.00 | 1.00 | 01-OCT-17:03 | 0.00 | 01-OCT-00:10 | 18724.12 | 01-OCT-17:10 | 16193.81 | 08-OCT-17:02 | 5249.14 | 01-OCT-17:10 | 3985.67 | 01-OCT-17:10 | 0.00 | 01-OCT-00:10 |
November | 53314373.20 | 13858138.90 | 10.42 | 40389834.83 | 12924538.37 | 0.00 | 0.45 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3724.91 | 04-NOV-14:00 | 2845.85 | 04-NOV-14:00 | 879.06 | 04-NOV-14:00 | 937.58 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 416133.64 | 116845.26 | 1.08 | 394426.96 | 21706.68 | 0.00 | 0.07 | 03-DEC-18:50 | 0.00 | 01-DEC-00:03 | 497.74 | 03-DEC-18:50 | 497.74 | 03-DEC-18:50 | 12.33 | 10-DEC-22:10 | 138.15 | 03-DEC-18:50 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.204580E+11 | 0.492692E+10 | 1342.05 | 0.176804E+11 | 0.277754E+10 | 0.00 | ||||||||||||||
Minimum of Months | 288007.43 | 81062.90 | 0.50 | 263357.69 | 21706.68 | 0.00 | 0.05 | 0.00 | 329.89 | 291.28 | 12.33 | 92.69 | 0.00 | |||||||
Maximum of Months | 0.715779E+10 | 0.171180E+10 | 364.78 | 0.611650E+10 | 0.104129E+10 | 0.00 | 1.00 | 0.00 | 19870.18 | 18533.22 | 7378.47 | 4319.62 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 111375.24 | 31294.84 | 0.33 | 111375.24 | -0.0 | 0.00 | 0.03 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 184.41 | 27-FEB-15:00 | 184.41 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 51.82 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 3655260.91 | 1016716.39 | 2.67 | 3655260.91 | -0.0 | 0.00 | 0.10 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 695.52 | 18-MAR-16:00 | 695.52 | 18-MAR-16:00 | 0.00 | 18-MAR-16:00 | 191.66 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.436179E+09 | 0.111104E+09 | 35.50 | 0.417528E+09 | 18651234.49 | 0.00 | 0.84 | 27-APR-15:00 | 0.00 | 01-APR-00:05 | 7509.04 | 27-APR-15:00 | 7173.11 | 27-APR-16:10 | 671.88 | 29-APR-13:00 | 1856.67 | 27-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.969173E+09 | 0.242416E+09 | 86.17 | 0.861100E+09 | 0.108073E+09 | 0.00 | 0.81 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 | 7412.39 | 06-MAY-13:00 | 6029.04 | 15-MAY-16:10 | 1497.59 | 06-MAY-12:50 | 1739.28 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.173091E+10 | 0.436702E+09 | 184.83 | 0.162650E+10 | 0.104410E+09 | 0.00 | 0.84 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 7471.63 | 28-JUN-17:00 | 7204.23 | 28-JUN-17:00 | 1932.46 | 12-JUN-06:03 | 1834.90 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.379574E+10 | 0.932968E+09 | 271.51 | 0.328402E+10 | 0.511721E+09 | 0.00 | 1.00 | 24-JUL-06:03 | 0.00 | 01-JUL-00:05 | 19201.75 | 31-JUL-06:03 | 13883.44 | 24-JUL-06:03 | 5416.90 | 31-JUL-06:03 | 4087.34 | 31-JUL-06:03 | 0.00 | 01-JUL-00:05 |
August | 0.497933E+10 | 0.121710E+10 | 303.67 | 0.429678E+10 | 0.682556E+09 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 19363.39 | 25-AUG-06:03 | 13429.61 | 25-AUG-06:03 | 6632.75 | 30-AUG-06:03 | 4118.70 | 25-AUG-06:03 | 0.00 | 01-AUG-00:10 |
September | 0.176882E+10 | 0.430587E+09 | 152.39 | 0.144433E+10 | 0.324484E+09 | 0.00 | 0.89 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 | 8348.67 | 14-SEP-13:50 | 6936.56 | 14-SEP-16:10 | 2311.70 | 14-SEP-06:03 | 1909.30 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 |
October | 0.139403E+09 | 36006429.75 | 29.67 | 0.135918E+09 | 3484985.54 | 0.00 | 0.56 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4361.85 | 04-OCT-15:00 | 4361.85 | 04-OCT-15:00 | 395.51 | 08-OCT-14:00 | 1072.93 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 35353428.49 | 9245407.52 | 5.42 | 26394957.83 | 8958470.66 | 0.00 | 0.39 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3104.34 | 04-NOV-14:00 | 2366.16 | 04-NOV-14:00 | 738.18 | 04-NOV-14:00 | 796.30 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.138587E+11 | 0.341717E+10 | 1072.16 | 0.120963E+11 | 0.176234E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.497933E+10 | 0.121710E+10 | 303.67 | 0.429678E+10 | 0.682556E+09 | 0.00 | 1.00 | 0.00 | 19363.39 | 13883.44 | 6632.75 | 4118.70 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 2274965.54 | 635210.47 | 2.67 | 2274965.54 | 0.00 | 0.00 | 0.08 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 558.06 | 18-MAR-16:00 | 558.06 | 18-MAR-16:00 | 0.00 | 18-MAR-15:30 | 154.55 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.421402E+09 | 0.107686E+09 | 33.75 | 0.403237E+09 | 18164604.03 | 0.00 | 0.83 | 27-APR-15:00 | 0.00 | 01-APR-00:05 | 7394.59 | 27-APR-15:00 | 7068.29 | 27-APR-16:10 | 655.95 | 29-APR-13:00 | 1835.09 | 27-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.944321E+09 | 0.236697E+09 | 84.83 | 0.839195E+09 | 0.105125E+09 | 0.00 | 0.80 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 | 7372.11 | 06-MAY-13:00 | 5981.10 | 06-MAY-13:00 | 1489.65 | 06-MAY-12:50 | 1732.53 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.169872E+10 | 0.429043E+09 | 181.67 | 0.159642E+10 | 0.102304E+09 | 0.00 | 0.83 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 7441.34 | 28-JUN-17:00 | 7175.06 | 28-JUN-17:00 | 1768.70 | 12-JUN-06:03 | 1829.90 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.376753E+10 | 0.926719E+09 | 270.51 | 0.325934E+10 | 0.508190E+09 | 0.00 | 1.00 | 24-JUL-06:03 | 0.00 | 01-JUL-00:05 | 19247.50 | 31-JUL-06:03 | 14147.41 | 24-JUL-06:03 | 5423.56 | 31-JUL-06:03 | 4097.06 | 31-JUL-06:03 | 0.00 | 01-JUL-00:05 |
August | 0.496229E+10 | 0.121357E+10 | 302.87 | 0.428193E+10 | 0.680360E+09 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 19409.44 | 25-AUG-06:03 | 13466.41 | 25-AUG-06:03 | 6637.44 | 30-AUG-06:03 | 4128.47 | 25-AUG-06:03 | 0.00 | 01-AUG-00:10 |
September | 0.174389E+10 | 0.424814E+09 | 148.89 | 0.142372E+10 | 0.320177E+09 | 0.00 | 0.88 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 | 8330.13 | 14-SEP-13:50 | 6918.90 | 14-SEP-16:10 | 2278.94 | 14-SEP-06:03 | 1907.17 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 |
October | 0.130753E+09 | 33797213.45 | 27.83 | 0.127690E+09 | 3062853.18 | 0.00 | 0.55 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4282.89 | 04-OCT-15:00 | 4282.89 | 04-OCT-15:00 | 377.98 | 08-OCT-14:00 | 1056.50 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 31071508.67 | 8181156.42 | 5.00 | 23208887.53 | 7862621.14 | 0.00 | 0.36 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2843.67 | 04-NOV-14:00 | 2165.55 | 04-NOV-14:00 | 678.11 | 04-NOV-14:00 | 735.56 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.137023E+11 | 0.338115E+10 | 1058.02 | 0.119570E+11 | 0.174525E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.496229E+10 | 0.121357E+10 | 302.87 | 0.428193E+10 | 0.680360E+09 | 0.00 | 1.00 | 0.00 | 19409.44 | 14147.41 | 6637.44 | 4128.47 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 14.86 | 3.68 | 0.17 | 14.86 | 0.00 | 0.00 | 0.00 | 27-FEB-16:50 | 0.00 | 01-FEB-00:10 | 0.02 | 27-FEB-16:50 | 0.02 | 27-FEB-16:50 | 0.00 | 27-FEB-16:50 | 0.01 | 27-FEB-16:50 | 0.00 | 01-FEB-00:10 |
March | 65009.41 | 15966.73 | 0.67 | 65009.41 | 0.00 | 0.00 | 0.01 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 105.14 | 18-MAR-16:00 | 105.14 | 18-MAR-16:00 | 0.00 | 18-MAR-16:00 | 25.82 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.421953E+09 | 94353883.92 | 30.83 | 0.413342E+09 | 8611296.26 | 0.00 | 0.80 | 27-APR-16:10 | 0.00 | 01-APR-00:05 | 7715.12 | 27-APR-15:00 | 7602.80 | 27-APR-16:10 | 384.47 | 29-APR-13:40 | 1681.69 | 27-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.863327E+09 | 0.189786E+09 | 79.42 | 0.794228E+09 | 69098422.27 | 0.00 | 0.78 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 | 7733.87 | 06-MAY-13:00 | 6546.56 | 06-MAY-13:00 | 1265.62 | 06-MAY-12:50 | 1594.30 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.149478E+10 | 0.329889E+09 | 150.36 | 0.145340E+10 | 41384516.61 | 0.00 | 0.81 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 7769.96 | 28-JUN-17:00 | 7769.96 | 28-JUN-17:00 | 580.04 | 11-JUN-12:00 | 1678.65 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.348741E+10 | 0.752091E+09 | 238.15 | 0.315078E+10 | 0.336636E+09 | 0.00 | 1.00 | 24-JUL-06:03 | 0.00 | 01-JUL-00:05 | 17826.66 | 31-JUL-06:03 | 12789.97 | 31-JUL-06:03 | 5036.69 | 31-JUL-06:03 | 3485.13 | 31-JUL-06:03 | 0.00 | 01-JUL-00:05 |
August | 0.477400E+10 | 0.102237E+10 | 266.44 | 0.430151E+10 | 0.472484E+09 | 0.00 | 1.00 | 08-AUG-06:03 | 0.00 | 01-AUG-00:10 | 19109.75 | 10-AUG-06:02 | 13165.13 | 10-AUG-06:02 | 6307.24 | 14-AUG-06:02 | 3753.14 | 10-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.150479E+10 | 0.321427E+09 | 125.81 | 0.129126E+10 | 0.213529E+09 | 0.00 | 0.86 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 | 8737.52 | 14-SEP-14:00 | 7526.31 | 14-SEP-16:10 | 1989.68 | 23-SEP-14:00 | 1757.05 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 |
October | 83424167.87 | 18805470.26 | 18.67 | 82818341.46 | 605826.41 | 0.00 | 0.49 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4180.22 | 04-OCT-15:00 | 4180.22 | 04-OCT-15:00 | 184.12 | 08-OCT-14:00 | 912.44 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 20441779.66 | 4780560.83 | 3.75 | 16092143.40 | 4349636.26 | 0.00 | 0.27 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2287.90 | 04-NOV-14:00 | 1825.39 | 04-NOV-14:00 | 462.51 | 04-NOV-14:00 | 528.08 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.126502E+11 | 0.273351E+10 | 914.26 | 0.115035E+11 | 0.114670E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.477400E+10 | 0.102237E+10 | 266.44 | 0.430151E+10 | 0.472484E+09 | 0.00 | 1.00 | 0.00 | 19109.75 | 13165.13 | 6307.24 | 3753.14 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 611869.65 | 171741.89 | 0.67 | 611869.65 | 0.00 | 0.00 | 0.04 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 450.10 | 18-MAR-16:00 | 450.10 | 18-MAR-16:00 | 0.00 | 18-MAR-16:00 | 126.05 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.636792E+09 | 0.165069E+09 | 29.00 | 0.603745E+09 | 33046992.63 | 0.00 | 0.82 | 27-APR-15:00 | 0.00 | 01-APR-00:05 | 13048.99 | 27-APR-15:00 | 12118.60 | 27-APR-15:00 | 1082.01 | 29-APR-14:40 | 3236.72 | 27-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.136579E+10 | 0.346265E+09 | 70.67 | 0.120916E+10 | 0.156630E+09 | 0.00 | 0.76 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 12299.78 | 06-MAY-13:30 | 10029.84 | 04-MAY-15:00 | 2437.97 | 06-MAY-12:50 | 2924.90 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.259547E+10 | 0.660806E+09 | 153.44 | 0.243044E+10 | 0.165030E+09 | 0.00 | 0.81 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 12854.54 | 28-JUN-17:00 | 12436.18 | 28-JUN-15:00 | 1337.60 | 21-JUN-17:00 | 3175.74 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.618687E+10 | 0.153169E+10 | 251.19 | 0.530890E+10 | 0.877967E+09 | 0.00 | 1.00 | 24-JUL-07:03 | 0.00 | 01-JUL-00:05 | 33784.37 | 31-JUL-07:03 | 26576.85 | 24-JUL-07:03 | 8988.54 | 31-JUL-07:03 | 7184.18 | 31-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.834555E+10 | 0.205078E+10 | 278.28 | 0.715954E+10 | 0.118601E+10 | 0.00 | 1.00 | 08-AUG-07:03 | 0.00 | 01-AUG-00:10 | 33446.37 | 14-AUG-07:03 | 24474.03 | 10-AUG-07:03 | 10697.39 | 14-AUG-07:03 | 7120.84 | 14-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.273633E+10 | 0.669231E+09 | 125.44 | 0.221919E+10 | 0.517140E+09 | 0.00 | 0.88 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 14709.14 | 14-SEP-14:10 | 12149.50 | 12-SEP-14:30 | 3962.90 | 14-SEP-13:00 | 3372.46 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 0.169657E+09 | 43954250.75 | 17.00 | 0.166307E+09 | 3349571.52 | 0.00 | 0.53 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 7401.24 | 04-OCT-15:00 | 7401.24 | 04-OCT-15:00 | 512.90 | 08-OCT-14:10 | 1832.29 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 32852533.92 | 8810525.64 | 3.50 | 24385911.64 | 8466622.28 | 0.00 | 0.27 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 | 3734.67 | 04-NOV-14:40 | 2819.60 | 04-NOV-14:40 | 915.61 | 04-NOV-14:30 | 988.81 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.220699E+11 | 0.547678E+10 | 929.19 | 0.191223E+11 | 0.294764E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.834555E+10 | 0.205078E+10 | 278.28 | 0.715954E+10 | 0.118601E+10 | 0.00 | 1.00 | 0.00 | 33784.37 | 26576.85 | 10697.39 | 7184.18 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.355248E+09 | 80109939.22 | 27.67 | 0.346038E+09 | 9209969.10 | 0.00 | 0.81 | 27-APR-15:00 | 0.00 | 01-APR-00:05 | 7319.07 | 27-APR-15:00 | 7017.16 | 27-APR-15:00 | 352.71 | 29-APR-14:30 | 1584.58 | 27-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.696368E+09 | 0.153882E+09 | 66.50 | 0.639764E+09 | 56603936.59 | 0.00 | 0.75 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 6859.22 | 06-MAY-13:30 | 5916.85 | 04-MAY-15:00 | 1088.25 | 06-MAY-13:20 | 1424.73 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.126674E+10 | 0.281257E+09 | 127.31 | 0.123117E+10 | 35568843.79 | 0.00 | 0.80 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 | 7101.98 | 28-JUN-17:00 | 7099.17 | 28-JUN-15:00 | 476.28 | 21-JUN-17:00 | 1536.02 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.309530E+10 | 0.670342E+09 | 220.11 | 0.277922E+10 | 0.316079E+09 | 0.00 | 1.00 | 24-JUL-07:03 | 0.00 | 01-JUL-00:05 | 15925.29 | 31-JUL-07:03 | 12558.19 | 24-JUL-07:03 | 4182.90 | 31-JUL-07:03 | 3100.24 | 31-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.434130E+10 | 0.932580E+09 | 248.47 | 0.388607E+10 | 0.455230E+09 | 0.00 | 1.00 | 08-AUG-14:10 | 0.00 | 01-AUG-00:10 | 15706.21 | 14-AUG-07:03 | 11038.32 | 10-AUG-07:03 | 4983.39 | 14-AUG-07:03 | 3061.30 | 14-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.129403E+10 | 0.277002E+09 | 105.25 | 0.110656E+10 | 0.187467E+09 | 0.00 | 0.86 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 8087.34 | 14-SEP-14:10 | 6970.01 | 12-SEP-14:30 | 1846.18 | 23-SEP-14:00 | 1625.41 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 64357658.46 | 14487937.61 | 10.67 | 63965307.67 | 392350.79 | 0.00 | 0.50 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3954.88 | 04-OCT-15:00 | 3954.88 | 04-OCT-15:00 | 124.52 | 08-OCT-14:10 | 860.75 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 13728331.01 | 3236424.99 | 3.00 | 10797265.14 | 2931065.88 | 0.00 | 0.23 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 | 1803.81 | 04-NOV-14:40 | 1437.34 | 04-NOV-14:40 | 366.47 | 04-NOV-14:40 | 420.48 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.111271E+11 | 0.241290E+10 | 808.97 | 0.100636E+11 | 0.106348E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.434130E+10 | 0.932580E+09 | 248.47 | 0.388607E+10 | 0.455230E+09 | 0.00 | 1.00 | 0.00 | 15925.29 | 12558.19 | 4983.39 | 3100.24 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.347649E+09 | 78518669.49 | 26.67 | 0.338635E+09 | 9013475.57 | 0.00 | 0.81 | 27-APR-15:00 | 0.00 | 01-APR-00:05 | 7226.24 | 27-APR-15:00 | 6926.95 | 27-APR-15:00 | 346.30 | 29-APR-14:30 | 1567.00 | 27-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.677539E+09 | 0.149920E+09 | 65.42 | 0.622472E+09 | 55067766.31 | 0.00 | 0.75 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 6770.25 | 06-MAY-13:30 | 5824.00 | 04-MAY-15:00 | 1077.04 | 06-MAY-13:20 | 1408.41 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.123994E+10 | 0.275565E+09 | 125.56 | 0.120518E+10 | 34766534.69 | 0.00 | 0.80 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 | 7034.55 | 28-JUN-17:00 | 7028.51 | 28-JUN-15:00 | 471.51 | 21-JUN-17:00 | 1522.88 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.304669E+10 | 0.660320E+09 | 216.86 | 0.273549E+10 | 0.311203E+09 | 0.00 | 1.00 | 24-JUL-07:03 | 0.00 | 01-JUL-00:05 | 15019.10 | 24-JUL-07:03 | 11924.77 | 24-JUL-07:03 | 3930.47 | 31-JUL-07:03 | 2919.01 | 24-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.428538E+10 | 0.921137E+09 | 246.03 | 0.383608E+10 | 0.449292E+09 | 0.00 | 1.00 | 08-AUG-14:10 | 0.00 | 01-AUG-00:10 | 14861.20 | 14-AUG-07:03 | 10446.87 | 10-AUG-07:03 | 4709.33 | 14-AUG-07:03 | 2885.69 | 14-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.127147E+10 | 0.272381E+09 | 103.92 | 0.108717E+10 | 0.184304E+09 | 0.00 | 0.86 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 8009.92 | 14-SEP-14:10 | 6900.26 | 12-SEP-14:30 | 1826.57 | 23-SEP-14:00 | 1611.51 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 61830030.33 | 13930527.01 | 10.50 | 61475017.40 | 355012.93 | 0.00 | 0.50 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3880.87 | 04-OCT-15:00 | 3880.87 | 04-OCT-15:00 | 117.46 | 08-OCT-14:10 | 846.14 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 12898432.91 | 3045945.87 | 3.00 | 10146639.97 | 2751792.94 | 0.00 | 0.23 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 | 1734.30 | 04-NOV-14:40 | 1381.45 | 04-NOV-14:40 | 352.85 | 04-NOV-14:40 | 405.07 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.109434E+11 | 0.237482E+10 | 797.94 | 0.989664E+10 | 0.104675E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.428538E+10 | 0.921137E+09 | 246.03 | 0.383608E+10 | 0.449292E+09 | 0.00 | 1.00 | 0.00 | 15019.10 | 11924.77 | 4709.33 | 2919.01 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 24.88 | 6.16 | 0.17 | 24.88 | 0.00 | 0.00 | 0.00 | 27-FEB-14:50 | 0.00 | 01-FEB-00:10 | 0.04 | 27-FEB-14:50 | 0.04 | 27-FEB-14:50 | 0.00 | 27-FEB-14:50 | 0.01 | 27-FEB-14:50 | 0.00 | 01-FEB-00:10 |
March | 163.71 | 40.48 | 0.33 | 163.71 | -0.0 | 0.00 | 0.00 | 18-MAR-13:40 | 0.00 | 01-MAR-00:10 | 0.18 | 18-MAR-13:40 | 0.18 | 18-MAR-13:40 | 0.00 | 01-MAR-00:10 | 0.04 | 18-MAR-13:40 | 0.00 | 01-MAR-00:10 |
April | 0.323347E+09 | 73497774.71 | 25.33 | 0.315071E+09 | 8276359.27 | 0.00 | 0.79 | 27-APR-15:00 | 0.00 | 01-APR-00:05 | 6949.77 | 27-APR-15:00 | 6659.78 | 27-APR-15:00 | 322.73 | 29-APR-14:40 | 1517.03 | 27-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.618504E+09 | 0.137484E+09 | 60.67 | 0.568089E+09 | 50414898.08 | 0.00 | 0.73 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 6548.00 | 06-MAY-13:30 | 5551.26 | 04-MAY-15:00 | 1048.41 | 06-MAY-13:20 | 1369.11 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.116635E+10 | 0.259923E+09 | 114.97 | 0.113402E+10 | 32323511.30 | 0.00 | 0.79 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 | 6901.54 | 28-JUN-17:00 | 6889.63 | 28-JUN-15:00 | 459.17 | 21-JUN-17:00 | 1498.02 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.292986E+10 | 0.636329E+09 | 207.25 | 0.263178E+10 | 0.298071E+09 | 0.00 | 1.00 | 24-JUL-07:03 | 0.00 | 01-JUL-00:05 | 12046.35 | 24-JUL-07:03 | 9626.90 | 24-JUL-07:03 | 2996.31 | 31-JUL-07:03 | 2298.74 | 24-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.416501E+10 | 0.896551E+09 | 239.67 | 0.373005E+10 | 0.434965E+09 | 0.00 | 1.00 | 08-AUG-14:10 | 0.00 | 01-AUG-00:10 | 11876.90 | 14-AUG-07:03 | 9821.68 | 10-AUG-16:10 | 3724.25 | 14-AUG-07:03 | 2346.53 | 29-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 0.121262E+10 | 0.260241E+09 | 98.53 | 0.103684E+10 | 0.175777E+09 | 0.00 | 0.85 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 7887.60 | 14-SEP-14:10 | 6769.28 | 12-SEP-14:30 | 1775.59 | 14-SEP-13:00 | 1590.16 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 53540543.84 | 12101801.82 | 8.83 | 53345005.22 | 195538.62 | 0.00 | 0.47 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3640.48 | 04-OCT-15:00 | 3640.48 | 04-OCT-15:00 | 84.34 | 08-OCT-14:10 | 799.36 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 9735278.25 | 2316103.73 | 2.83 | 7670115.98 | 2065162.28 | 0.00 | 0.19 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 | 1444.02 | 04-NOV-14:40 | 1149.26 | 04-NOV-14:40 | 294.76 | 04-NOV-14:40 | 340.38 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.104790E+11 | 0.227844E+10 | 758.58 | 0.947687E+10 | 0.100209E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.416501E+10 | 0.896551E+09 | 239.67 | 0.373005E+10 | 0.434965E+09 | 0.00 | 1.00 | 0.00 | 12046.35 | 9821.68 | 3724.25 | 2346.53 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 466.04 | 115.12 | 0.50 | 466.04 | 0.00 | 0.00 | 0.00 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 0.74 | 18-MAR-14:00 | 0.74 | 18-MAR-14:00 | 0.00 | 18-MAR-14:00 | 0.18 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.302836E+09 | 69506066.97 | 24.92 | 0.295293E+09 | 7542550.36 | 0.00 | 0.75 | 27-APR-15:00 | 0.00 | 01-APR-00:05 | 6941.94 | 27-APR-15:00 | 6631.71 | 27-APR-15:00 | 329.45 | 27-APR-17:00 | 1530.41 | 27-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 0.556858E+09 | 0.124876E+09 | 56.08 | 0.511475E+09 | 45383000.90 | 0.00 | 0.70 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 6553.75 | 06-MAY-13:30 | 5507.70 | 06-MAY-13:40 | 1065.95 | 06-MAY-13:10 | 1382.34 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.110586E+10 | 0.247804E+09 | 105.50 | 0.107423E+10 | 31629037.39 | 0.00 | 0.76 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 | 6963.66 | 28-JUN-15:00 | 6963.66 | 28-JUN-15:00 | 464.60 | 21-JUN-17:00 | 1517.24 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.288241E+10 | 0.627977E+09 | 192.93 | 0.259013E+10 | 0.292278E+09 | 0.00 | 1.00 | 24-JUL-14:10 | 0.00 | 01-JUL-00:05 | 10349.59 | 24-JUL-15:00 | 9873.55 | 24-JUL-15:00 | 1482.67 | 31-JUL-10:10 | 2247.43 | 24-JUL-15:00 | 0.00 | 01-JUL-00:05 |
August | 0.423965E+10 | 0.912305E+09 | 221.74 | 0.379539E+10 | 0.444260E+09 | 0.00 | 1.00 | 08-AUG-12:50 | 0.00 | 01-AUG-00:10 | 11180.47 | 29-AUG-14:50 | 10187.19 | 10-AUG-16:10 | 1981.91 | 30-AUG-13:00 | 2431.30 | 29-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 0.118137E+10 | 0.254825E+09 | 90.67 | 0.100649E+10 | 0.174880E+09 | 0.00 | 0.84 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 8114.66 | 14-SEP-14:10 | 6889.41 | 12-SEP-14:20 | 1876.71 | 14-SEP-13:00 | 1643.33 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 40966238.11 | 9396957.78 | 6.67 | 40965147.18 | 1090.93 | 0.00 | 0.40 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3143.70 | 04-OCT-15:00 | 3143.70 | 04-OCT-15:00 | 1.82 | 05-OCT-17:40 | 705.13 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 5325863.53 | 1284101.60 | 2.33 | 4201776.34 | 1124087.19 | 0.00 | 0.12 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 | 970.57 | 04-NOV-14:40 | 770.13 | 04-NOV-14:40 | 200.44 | 04-NOV-14:40 | 232.77 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.103153E+11 | 0.224797E+10 | 701.33 | 0.931817E+10 | 0.997098E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.423965E+10 | 0.912305E+09 | 221.74 | 0.379539E+10 | 0.444260E+09 | 0.00 | 1.00 | 0.00 | 11180.47 | 10187.19 | 1981.91 | 2431.30 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 54.13 | 76.47 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 95.74 | 66.72 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 108.60 | 56.67 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 121.13 | 48.00 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.48 | 41.97 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 102.31 | 33.84 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.72 | 30.57 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.00 | 29.85 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.48 | 41.67 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.46 | 53.20 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 59.43 | 62.88 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 63.54 | 77.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 102.86 | 51.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 54.13 | 29.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.48 | 77.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 54.13 | 76.47 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 95.74 | 66.72 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 108.60 | 56.67 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 121.13 | 48.00 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.48 | 41.97 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 102.31 | 33.84 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.72 | 30.57 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.00 | 29.85 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.48 | 41.67 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.46 | 53.20 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 59.43 | 62.88 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 63.54 | 77.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 102.86 | 51.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 54.13 | 29.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.48 | 77.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 54.13 | 76.47 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 95.74 | 66.72 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 108.60 | 56.67 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 121.13 | 48.00 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.48 | 41.97 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 102.31 | 33.84 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.72 | 30.57 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.00 | 29.85 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.48 | 41.67 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.46 | 53.20 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 59.43 | 62.88 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 63.54 | 77.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 102.86 | 51.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 54.13 | 29.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.48 | 77.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 54.13 | 76.47 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 95.74 | 66.72 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 108.60 | 56.67 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 121.13 | 48.00 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.48 | 41.97 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 102.31 | 33.84 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.72 | 30.57 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.00 | 29.85 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.48 | 41.67 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.46 | 53.20 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 59.43 | 62.88 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 63.54 | 77.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 102.86 | 51.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 54.13 | 29.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.48 | 77.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.22 | 43.48 | 29.74 | 65.41 | 90.60 | 0.00 | 0.00 | 0.00 |
February | 112.60 | 69.70 | 42.90 | 115.50 | 79.15 | 0.00 | 0.00 | 0.00 |
March | 121.13 | 64.60 | 56.53 | 130.91 | 67.24 | 0.00 | 0.00 | 0.00 |
April | 127.89 | 55.53 | 72.36 | 146.01 | 56.95 | 0.00 | 0.00 | 0.00 |
May | 116.94 | 34.84 | 82.10 | 133.18 | 49.84 | 0.00 | 0.00 | 0.00 |
June | 106.99 | 28.72 | 78.26 | 123.30 | 40.21 | 0.00 | 0.00 | 0.00 |
July | 116.67 | 42.73 | 73.94 | 147.69 | 36.38 | 0.00 | 0.00 | 0.00 |
August | 125.35 | 58.45 | 66.90 | 163.56 | 35.57 | 0.00 | 0.00 | 0.00 |
September | 138.88 | 76.70 | 62.19 | 170.16 | 49.66 | 0.00 | 0.00 | 0.00 |
October | 125.80 | 77.67 | 48.13 | 142.73 | 63.21 | 0.00 | 0.00 | 0.00 |
November | 74.38 | 42.63 | 31.75 | 71.71 | 74.56 | 0.00 | 0.00 | 0.00 |
December | 77.82 | 50.36 | 27.46 | 76.64 | 92.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.76 | 53.68 | 56.07 | 123.93 | 61.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.22 | 28.72 | 27.46 | 65.41 | 35.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.88 | 77.67 | 82.10 | 170.16 | 92.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.22 | 43.48 | 29.74 | 65.41 | 90.60 | 0.00 | 0.00 | 0.00 |
February | 112.60 | 69.70 | 42.90 | 115.50 | 79.15 | 0.00 | 0.00 | 0.00 |
March | 121.13 | 64.60 | 56.53 | 130.91 | 67.24 | 0.00 | 0.00 | 0.00 |
April | 127.89 | 55.53 | 72.36 | 146.01 | 56.95 | 0.00 | 0.00 | 0.00 |
May | 116.94 | 34.84 | 82.10 | 133.18 | 49.84 | 0.00 | 0.00 | 0.00 |
June | 106.99 | 28.72 | 78.26 | 123.30 | 40.21 | 0.00 | 0.00 | 0.00 |
July | 116.67 | 42.73 | 73.94 | 147.69 | 36.38 | 0.00 | 0.00 | 0.00 |
August | 125.35 | 58.45 | 66.90 | 163.56 | 35.57 | 0.00 | 0.00 | 0.00 |
September | 138.88 | 76.70 | 62.19 | 170.16 | 49.66 | 0.00 | 0.00 | 0.00 |
October | 125.80 | 77.67 | 48.13 | 142.73 | 63.21 | 0.00 | 0.00 | 0.00 |
November | 74.38 | 42.63 | 31.75 | 71.71 | 74.56 | 0.00 | 0.00 | 0.00 |
December | 77.82 | 50.36 | 27.46 | 76.64 | 92.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.76 | 53.68 | 56.07 | 123.93 | 61.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.22 | 28.72 | 27.46 | 65.41 | 35.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.88 | 77.67 | 82.10 | 170.16 | 92.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 53.21 | 81.64 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 94.35 | 71.63 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 106.89 | 62.06 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 119.00 | 52.31 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 108.73 | 44.63 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 101.31 | 35.19 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.19 | 31.32 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.54 | 30.55 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 140.67 | 42.96 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 116.86 | 57.23 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 58.38 | 67.59 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 62.70 | 82.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 101.68 | 54.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 53.21 | 30.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 140.67 | 82.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 53.21 | 81.64 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 94.35 | 71.63 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 106.89 | 62.06 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 119.00 | 52.31 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 108.73 | 44.63 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 101.31 | 35.19 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.19 | 31.32 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.54 | 30.55 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 140.67 | 42.96 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 116.86 | 57.23 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 58.38 | 67.59 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 62.70 | 82.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 101.68 | 54.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 53.21 | 30.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 140.67 | 82.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.22 | 43.48 | 29.74 | 64.32 | 96.65 | 0.00 | 0.00 | 0.00 |
February | 112.60 | 69.70 | 42.90 | 113.86 | 84.90 | 0.00 | 0.00 | 0.00 |
March | 121.13 | 64.60 | 56.53 | 128.89 | 73.56 | 0.00 | 0.00 | 0.00 |
April | 127.89 | 55.53 | 72.36 | 143.51 | 62.00 | 0.00 | 0.00 | 0.00 |
May | 116.94 | 34.84 | 82.10 | 131.13 | 52.95 | 0.00 | 0.00 | 0.00 |
June | 106.99 | 28.72 | 78.26 | 122.13 | 41.78 | 0.00 | 0.00 | 0.00 |
July | 116.67 | 42.73 | 73.94 | 147.09 | 37.25 | 0.00 | 0.00 | 0.00 |
August | 125.35 | 58.45 | 66.90 | 163.03 | 36.39 | 0.00 | 0.00 | 0.00 |
September | 138.88 | 76.70 | 62.19 | 169.22 | 51.17 | 0.00 | 0.00 | 0.00 |
October | 125.80 | 77.67 | 48.13 | 140.86 | 67.94 | 0.00 | 0.00 | 0.00 |
November | 74.38 | 42.63 | 31.75 | 70.47 | 80.07 | 0.00 | 0.00 | 0.00 |
December | 77.82 | 50.36 | 27.46 | 75.63 | 98.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.76 | 53.68 | 56.07 | 122.54 | 65.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.22 | 28.72 | 27.46 | 64.32 | 36.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.88 | 77.67 | 82.10 | 169.22 | 98.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 53.42 | 78.84 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 94.74 | 69.17 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 107.35 | 59.81 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 119.51 | 51.02 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 108.92 | 44.70 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 101.25 | 36.05 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.00 | 32.62 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.36 | 31.95 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 140.69 | 43.72 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 117.27 | 56.05 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 58.74 | 65.24 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 62.95 | 80.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 101.87 | 54.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 53.42 | 31.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 140.69 | 80.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 53.42 | 78.84 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 94.74 | 69.17 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 107.35 | 59.81 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 119.51 | 51.02 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 108.92 | 44.70 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 101.25 | 36.05 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.00 | 32.62 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.36 | 31.95 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 140.69 | 43.72 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 117.27 | 56.05 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 58.74 | 65.24 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 62.95 | 80.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 101.87 | 54.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 53.42 | 31.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 140.69 | 80.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 64.23 | 92.84 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 113.70 | 81.56 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 128.74 | 70.52 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 143.33 | 60.15 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 130.64 | 52.74 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 121.40 | 42.56 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 146.05 | 38.56 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 161.94 | 37.81 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 168.32 | 51.78 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 140.58 | 66.18 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 70.52 | 76.89 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 75.52 | 94.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 122.11 | 63.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 64.23 | 37.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 168.32 | 94.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 53.56 | 77.70 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 94.95 | 68.18 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 107.59 | 58.86 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 119.79 | 50.24 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 109.09 | 44.30 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 101.32 | 35.88 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.02 | 32.55 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.37 | 31.92 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 140.75 | 43.51 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 117.50 | 55.25 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 58.92 | 64.25 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 63.07 | 79.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 102.02 | 53.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 53.56 | 31.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 140.75 | 79.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 53.56 | 77.70 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 94.95 | 68.18 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 107.59 | 58.86 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 119.79 | 50.24 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 109.09 | 44.30 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 101.32 | 35.88 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.02 | 32.55 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.37 | 31.92 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 140.75 | 43.51 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 117.50 | 55.25 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 58.92 | 64.25 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 63.07 | 79.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 102.02 | 53.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 53.56 | 31.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 140.75 | 79.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 64.39 | 91.50 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 113.96 | 80.39 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 129.02 | 69.39 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 143.67 | 59.22 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 130.84 | 52.26 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 121.48 | 42.35 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 146.09 | 38.47 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 161.96 | 37.78 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 168.40 | 51.52 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 140.85 | 65.24 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 70.74 | 75.72 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 75.68 | 93.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 122.28 | 63.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 64.39 | 37.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 168.40 | 93.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 53.72 | 76.77 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 95.10 | 67.49 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 107.60 | 58.42 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 119.74 | 49.85 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 109.08 | 43.96 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 101.39 | 35.59 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.12 | 32.29 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.46 | 31.67 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 140.78 | 43.24 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 117.45 | 54.91 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 58.99 | 63.66 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 63.19 | 78.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 102.07 | 52.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 53.72 | 31.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 140.78 | 78.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 53.72 | 76.77 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 95.10 | 67.49 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 107.60 | 58.42 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 119.74 | 49.85 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 109.08 | 43.96 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 101.39 | 35.59 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.12 | 32.29 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.46 | 31.67 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 140.78 | 43.24 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 117.45 | 54.91 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 58.99 | 63.66 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 63.19 | 78.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 102.07 | 52.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 53.72 | 31.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 140.78 | 78.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 64.59 | 90.40 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 114.15 | 79.58 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 129.05 | 68.88 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 143.61 | 58.77 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 130.84 | 51.85 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 121.57 | 42.00 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 146.20 | 38.17 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 162.06 | 37.48 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 168.43 | 51.20 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 140.80 | 64.82 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 70.82 | 75.01 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 75.82 | 92.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 122.35 | 62.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 64.59 | 37.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 168.43 | 92.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 54.35 | 73.87 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 96.08 | 64.97 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 108.80 | 55.61 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 121.45 | 47.00 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.70 | 41.62 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 102.25 | 34.01 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.57 | 31.03 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.83 | 30.41 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.58 | 41.55 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.84 | 51.87 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 59.81 | 60.92 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 63.76 | 75.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.02 | 50.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 54.35 | 30.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.58 | 75.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 54.35 | 73.87 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 96.08 | 64.97 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 108.80 | 55.61 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 121.45 | 47.00 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.70 | 41.62 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 102.25 | 34.01 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.57 | 31.03 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.83 | 30.41 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.58 | 41.55 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.84 | 51.87 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 59.81 | 60.92 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 63.76 | 75.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.02 | 50.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 54.35 | 30.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.58 | 75.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 54.35 | 73.87 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 96.08 | 64.97 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 108.80 | 55.61 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 121.45 | 47.00 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.70 | 41.62 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 102.25 | 34.01 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.57 | 31.03 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.83 | 30.41 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.58 | 41.55 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.84 | 51.87 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 59.81 | 60.92 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 63.76 | 75.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.02 | 50.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 54.35 | 30.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.58 | 75.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 54.35 | 73.87 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 96.08 | 64.97 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 108.80 | 55.61 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 121.45 | 47.00 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.70 | 41.62 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 102.25 | 34.01 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.57 | 31.03 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.83 | 30.41 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.58 | 41.55 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.84 | 51.87 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 59.81 | 60.92 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 63.76 | 75.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.02 | 50.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 54.35 | 30.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.58 | 75.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 65.34 | 87.03 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 115.29 | 76.65 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 130.44 | 65.61 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 145.60 | 55.45 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 132.71 | 49.13 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 122.56 | 40.17 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 146.71 | 36.70 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 162.48 | 36.00 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 169.36 | 49.22 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 142.40 | 61.28 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 71.78 | 71.83 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 76.49 | 89.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 123.45 | 59.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 65.34 | 36.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 169.36 | 89.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 65.34 | 87.03 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 115.29 | 76.65 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 130.44 | 65.61 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 145.60 | 55.45 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 132.71 | 49.13 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 122.56 | 40.17 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 146.71 | 36.70 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 162.48 | 36.00 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 169.36 | 49.22 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 142.40 | 61.28 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 71.78 | 71.83 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 76.49 | 89.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 123.45 | 59.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 65.34 | 36.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 169.36 | 89.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 54.13 | 74.24 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 95.77 | 65.22 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 108.38 | 55.95 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 120.83 | 47.38 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 109.99 | 42.04 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 101.87 | 34.08 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.39 | 30.90 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.69 | 30.22 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.19 | 41.69 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.26 | 52.40 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 59.56 | 61.25 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 63.58 | 75.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 102.66 | 50.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 54.13 | 30.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.19 | 75.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 54.13 | 74.24 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 95.77 | 65.22 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 108.38 | 55.95 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 120.83 | 47.38 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 109.99 | 42.04 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 101.87 | 34.08 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.39 | 30.90 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.69 | 30.22 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.19 | 41.69 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.26 | 52.40 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 59.56 | 61.25 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 63.58 | 75.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 102.66 | 50.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 54.13 | 30.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.19 | 75.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 65.10 | 87.41 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 114.96 | 76.89 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 129.99 | 65.96 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 144.93 | 55.86 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 131.93 | 49.60 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 122.16 | 40.24 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 146.54 | 36.53 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 162.35 | 35.77 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 168.94 | 49.37 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 141.76 | 61.87 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 71.51 | 72.17 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 76.29 | 89.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 123.06 | 60.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 65.10 | 35.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 168.94 | 89.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 54.19 | 73.93 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 95.87 | 64.91 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 108.50 | 55.64 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 120.98 | 47.11 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.16 | 41.80 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 101.98 | 33.92 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.48 | 30.75 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.76 | 30.09 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.27 | 41.53 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.36 | 52.15 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 59.64 | 60.96 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 63.64 | 75.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 102.76 | 50.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 54.19 | 30.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.27 | 75.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 54.19 | 73.93 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 95.87 | 64.91 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 108.50 | 55.64 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 120.98 | 47.11 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.16 | 41.80 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 101.98 | 33.92 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.48 | 30.75 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.76 | 30.09 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.27 | 41.53 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.36 | 52.15 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 59.64 | 60.96 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 63.64 | 75.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 102.76 | 50.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 54.19 | 30.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.27 | 75.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 65.17 | 87.04 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 115.07 | 76.53 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 130.13 | 65.59 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 145.10 | 55.54 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 132.13 | 49.31 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 122.29 | 40.04 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 146.65 | 36.35 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 162.43 | 35.61 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 169.03 | 49.17 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 141.89 | 61.57 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 71.61 | 71.83 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 76.36 | 89.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 123.18 | 59.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 65.17 | 35.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 169.03 | 89.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 54.39 | 72.67 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 96.20 | 63.71 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 108.91 | 54.37 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 121.54 | 45.94 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.88 | 40.66 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 102.39 | 33.25 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.70 | 30.28 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.93 | 29.69 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.61 | 40.79 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.82 | 50.94 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 59.90 | 59.83 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 63.83 | 74.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.11 | 49.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 54.39 | 29.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.61 | 74.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 54.39 | 72.67 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 96.20 | 63.71 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 108.91 | 54.37 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 121.54 | 45.94 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.88 | 40.66 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 102.39 | 33.25 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.70 | 30.28 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.93 | 29.69 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.61 | 40.79 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.82 | 50.94 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 59.90 | 59.83 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 63.83 | 74.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.11 | 49.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 54.39 | 29.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.61 | 74.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 65.41 | 85.56 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 115.48 | 75.12 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 130.62 | 64.10 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 145.77 | 54.17 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 133.00 | 47.97 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 122.77 | 39.26 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 146.92 | 35.81 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 162.64 | 35.14 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 169.44 | 48.31 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 142.44 | 60.16 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 71.93 | 70.50 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 76.60 | 87.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 123.61 | 58.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 65.41 | 35.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 169.44 | 87.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 55.18 | 67.72 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 97.36 | 59.09 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.10 | 49.88 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 122.86 | 42.04 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 112.58 | 37.08 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.48 | 30.76 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.33 | 28.40 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.32 | 28.05 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.53 | 38.25 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 119.96 | 47.24 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 60.70 | 55.89 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 64.54 | 69.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.10 | 46.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 55.18 | 28.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.53 | 69.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 55.18 | 67.72 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 97.36 | 59.09 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.10 | 49.88 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 122.86 | 42.04 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 112.58 | 37.08 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.48 | 30.76 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.33 | 28.40 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.32 | 28.05 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.53 | 38.25 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 119.96 | 47.24 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 60.70 | 55.89 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 64.54 | 69.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.10 | 46.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 55.18 | 28.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.53 | 69.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 66.38 | 79.72 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 116.89 | 69.66 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 132.06 | 58.81 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 147.36 | 49.58 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 135.02 | 43.78 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 124.08 | 36.34 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 147.67 | 33.59 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 163.11 | 33.23 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 170.54 | 45.31 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 143.79 | 55.80 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 72.89 | 65.85 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 77.46 | 82.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 124.79 | 54.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 66.38 | 33.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 170.54 | 82.19 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.144971E+09 | 0.204815E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.231610E+09 | 0.161408E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.290876E+09 | 0.151790E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.313969E+09 | 0.124415E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.295905E+09 | 0.112423E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.265193E+09 | 87707356.00 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.328704E+09 | 81870794.55 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364265E+09 | 79952405.93 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.366706E+09 | 0.108012E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.317287E+09 | 0.142491E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.154037E+09 | 0.162978E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.170190E+09 | 0.207875E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.324371E+10 | 0.162574E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.144971E+09 | 79952405.93 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.366706E+09 | 0.207875E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.144971E+09 | 0.204815E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.231610E+09 | 0.161408E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.290876E+09 | 0.151790E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.313969E+09 | 0.124415E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.295905E+09 | 0.112423E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.265193E+09 | 87707356.00 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.328704E+09 | 81870794.55 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364265E+09 | 79952405.93 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.366706E+09 | 0.108012E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.317287E+09 | 0.142491E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.154037E+09 | 0.162978E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.170190E+09 | 0.207875E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.324371E+10 | 0.162574E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.144971E+09 | 79952405.93 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.366706E+09 | 0.207875E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.144971E+09 | 0.204815E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.231610E+09 | 0.161408E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.290876E+09 | 0.151790E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.313969E+09 | 0.124415E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.295905E+09 | 0.112423E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.265193E+09 | 87707356.00 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.328704E+09 | 81870794.55 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364265E+09 | 79952405.93 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.366706E+09 | 0.108012E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.317287E+09 | 0.142491E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.154037E+09 | 0.162978E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.170190E+09 | 0.207875E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.324371E+10 | 0.162574E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.144971E+09 | 79952405.93 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.366706E+09 | 0.207875E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.144971E+09 | 0.204815E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.231610E+09 | 0.161408E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.290876E+09 | 0.151790E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.313969E+09 | 0.124415E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.295905E+09 | 0.112423E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.265193E+09 | 87707356.00 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.328704E+09 | 81870794.55 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364265E+09 | 79952405.93 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.366706E+09 | 0.108012E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.317287E+09 | 0.142491E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.154037E+09 | 0.162978E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.170190E+09 | 0.207875E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.324371E+10 | 0.162574E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.144971E+09 | 79952405.93 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.366706E+09 | 0.207875E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196113E+09 | 0.116453E+09 | 79660284.81 | 0.175205E+09 | 0.242658E+09 |
February | 0.272406E+09 | 0.168623E+09 | 0.103783E+09 | 0.279422E+09 | 0.191473E+09 |
March | 0.324426E+09 | 0.173013E+09 | 0.151413E+09 | 0.350632E+09 | 0.180089E+09 |
April | 0.331483E+09 | 0.143928E+09 | 0.187555E+09 | 0.378469E+09 | 0.147621E+09 |
May | 0.313202E+09 | 93305917.62 | 0.219896E+09 | 0.356699E+09 | 0.133500E+09 |
June | 0.277305E+09 | 74452992.86 | 0.202852E+09 | 0.319593E+09 | 0.104221E+09 |
July | 0.312494E+09 | 0.114452E+09 | 0.198042E+09 | 0.395577E+09 | 97433744.00 |
August | 0.335735E+09 | 0.156559E+09 | 0.179176E+09 | 0.438085E+09 | 95259017.52 |
September | 0.359982E+09 | 0.198794E+09 | 0.161188E+09 | 0.441044E+09 | 0.128727E+09 |
October | 0.336952E+09 | 0.208043E+09 | 0.128909E+09 | 0.382287E+09 | 0.169304E+09 |
November | 0.192791E+09 | 0.110485E+09 | 82305443.16 | 0.185881E+09 | 0.193254E+09 |
December | 0.208438E+09 | 0.134889E+09 | 73549600.79 | 0.205263E+09 | 0.246575E+09 |
Annual Sum or Average | 0.346133E+10 | 0.169300E+10 | 0.176833E+10 | 0.390816E+10 | 0.193012E+10 |
Minimum of Months | 0.192791E+09 | 74452992.86 | 73549600.79 | 0.175205E+09 | 95259017.52 |
Maximum of Months | 0.359982E+09 | 0.208043E+09 | 0.219896E+09 | 0.441044E+09 | 0.246575E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196113E+09 | 0.116453E+09 | 79660284.81 | 0.175205E+09 | 0.242658E+09 |
February | 0.272406E+09 | 0.168623E+09 | 0.103783E+09 | 0.279422E+09 | 0.191473E+09 |
March | 0.324426E+09 | 0.173013E+09 | 0.151413E+09 | 0.350632E+09 | 0.180089E+09 |
April | 0.331483E+09 | 0.143928E+09 | 0.187555E+09 | 0.378469E+09 | 0.147621E+09 |
May | 0.313202E+09 | 93305917.62 | 0.219896E+09 | 0.356699E+09 | 0.133500E+09 |
June | 0.277305E+09 | 74452992.86 | 0.202852E+09 | 0.319593E+09 | 0.104221E+09 |
July | 0.312494E+09 | 0.114452E+09 | 0.198042E+09 | 0.395577E+09 | 97433744.00 |
August | 0.335735E+09 | 0.156559E+09 | 0.179176E+09 | 0.438085E+09 | 95259017.52 |
September | 0.359982E+09 | 0.198794E+09 | 0.161188E+09 | 0.441044E+09 | 0.128727E+09 |
October | 0.336952E+09 | 0.208043E+09 | 0.128909E+09 | 0.382287E+09 | 0.169304E+09 |
November | 0.192791E+09 | 0.110485E+09 | 82305443.16 | 0.185881E+09 | 0.193254E+09 |
December | 0.208438E+09 | 0.134889E+09 | 73549600.79 | 0.205263E+09 | 0.246575E+09 |
Annual Sum or Average | 0.346133E+10 | 0.169300E+10 | 0.176833E+10 | 0.390816E+10 | 0.193012E+10 |
Minimum of Months | 0.192791E+09 | 74452992.86 | 73549600.79 | 0.175205E+09 | 95259017.52 |
Maximum of Months | 0.359982E+09 | 0.208043E+09 | 0.219896E+09 | 0.441044E+09 | 0.246575E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.142524E+09 | 0.218653E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.228244E+09 | 0.173296E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.286291E+09 | 0.166233E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.308457E+09 | 0.135592E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.291218E+09 | 0.119542E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.262584E+09 | 91202534.77 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.327279E+09 | 83886643.85 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.363019E+09 | 81832740.13 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.364614E+09 | 0.111340E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.313007E+09 | 0.153289E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.151323E+09 | 0.175185E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.167930E+09 | 0.221699E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.320649E+10 | 0.173175E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.142524E+09 | 81832740.13 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.364614E+09 | 0.221699E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.142524E+09 | 0.218653E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.228244E+09 | 0.173296E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.286291E+09 | 0.166233E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.308457E+09 | 0.135592E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.291218E+09 | 0.119542E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.262584E+09 | 91202534.77 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.327279E+09 | 83886643.85 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.363019E+09 | 81832740.13 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.364614E+09 | 0.111340E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.313007E+09 | 0.153289E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.151323E+09 | 0.175185E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.167930E+09 | 0.221699E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.320649E+10 | 0.173175E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.142524E+09 | 81832740.13 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.364614E+09 | 0.221699E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196113E+09 | 0.116453E+09 | 79660284.81 | 0.172282E+09 | 0.258857E+09 |
February | 0.272406E+09 | 0.168623E+09 | 0.103783E+09 | 0.275441E+09 | 0.205398E+09 |
March | 0.324426E+09 | 0.173013E+09 | 0.151413E+09 | 0.345225E+09 | 0.197012E+09 |
April | 0.331483E+09 | 0.143928E+09 | 0.187555E+09 | 0.371987E+09 | 0.160694E+09 |
May | 0.313202E+09 | 93305917.62 | 0.219896E+09 | 0.351212E+09 | 0.141826E+09 |
June | 0.277305E+09 | 74452992.86 | 0.202852E+09 | 0.316566E+09 | 0.108304E+09 |
July | 0.312494E+09 | 0.114452E+09 | 0.198042E+09 | 0.393956E+09 | 99769469.19 |
August | 0.335735E+09 | 0.156559E+09 | 0.179176E+09 | 0.436673E+09 | 97455463.08 |
September | 0.359982E+09 | 0.198794E+09 | 0.161188E+09 | 0.438615E+09 | 0.132640E+09 |
October | 0.336952E+09 | 0.208043E+09 | 0.128909E+09 | 0.377283E+09 | 0.181962E+09 |
November | 0.192791E+09 | 0.110485E+09 | 82305443.16 | 0.182670E+09 | 0.207538E+09 |
December | 0.208438E+09 | 0.134889E+09 | 73549600.79 | 0.202579E+09 | 0.262800E+09 |
Annual Sum or Average | 0.346133E+10 | 0.169300E+10 | 0.176833E+10 | 0.386449E+10 | 0.205426E+10 |
Minimum of Months | 0.192791E+09 | 74452992.86 | 73549600.79 | 0.172282E+09 | 97455463.08 |
Maximum of Months | 0.359982E+09 | 0.208043E+09 | 0.219896E+09 | 0.438615E+09 | 0.262800E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.143089E+09 | 0.211154E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.229184E+09 | 0.167335E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.287524E+09 | 0.160196E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.309763E+09 | 0.132256E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.291734E+09 | 0.119730E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.262447E+09 | 93453212.09 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.326753E+09 | 87368687.48 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.362555E+09 | 85583418.02 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.364671E+09 | 0.113332E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.314108E+09 | 0.150124E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.152257E+09 | 0.169104E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.168601E+09 | 0.214657E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.321268E+10 | 0.170429E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.143089E+09 | 85583418.02 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.364671E+09 | 0.214657E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.143089E+09 | 0.211154E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.229184E+09 | 0.167335E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.287524E+09 | 0.160196E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.309763E+09 | 0.132256E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.291734E+09 | 0.119730E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.262447E+09 | 93453212.09 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.326753E+09 | 87368687.48 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.362555E+09 | 85583418.02 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.364671E+09 | 0.113332E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.314108E+09 | 0.150124E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.152257E+09 | 0.169104E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.168601E+09 | 0.214657E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.321268E+10 | 0.170429E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.143089E+09 | 85583418.02 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.364671E+09 | 0.214657E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.172032E+09 | 0.248671E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.275067E+09 | 0.197304E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.344810E+09 | 0.188884E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.371500E+09 | 0.155909E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.349906E+09 | 0.141246E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.314675E+09 | 0.110309E+09 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.391190E+09 | 0.103268E+09 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.433743E+09 | 0.101281E+09 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.436285E+09 | 0.134205E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.376526E+09 | 0.177249E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.182790E+09 | 0.199289E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.202281E+09 | 0.253112E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.385081E+10 | 0.201073E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.172032E+09 | 0.101281E+09 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.436285E+09 | 0.253112E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.143450E+09 | 0.208099E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.229705E+09 | 0.164945E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.288165E+09 | 0.157639E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.310501E+09 | 0.130211E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.292187E+09 | 0.118659E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.262611E+09 | 93005296.33 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.326827E+09 | 87176202.29 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.362587E+09 | 85498654.46 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.364834E+09 | 0.112767E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.314707E+09 | 0.147992E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.152723E+09 | 0.166537E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.168938E+09 | 0.211877E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.321723E+10 | 0.168441E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.143450E+09 | 85498654.46 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.364834E+09 | 0.211877E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.143450E+09 | 0.208099E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.229705E+09 | 0.164945E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.288165E+09 | 0.157639E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.310501E+09 | 0.130211E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.292187E+09 | 0.118659E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.262611E+09 | 93005296.33 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.326827E+09 | 87176202.29 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.362587E+09 | 85498654.46 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.364834E+09 | 0.112767E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.314707E+09 | 0.147992E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.152723E+09 | 0.166537E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.168938E+09 | 0.211877E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.321723E+10 | 0.168441E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.143450E+09 | 85498654.46 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.364834E+09 | 0.211877E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.172474E+09 | 0.245061E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.275696E+09 | 0.194481E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.345577E+09 | 0.185867E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.372382E+09 | 0.153503E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.350447E+09 | 0.139984E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.314872E+09 | 0.109781E+09 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.391278E+09 | 0.103041E+09 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.433781E+09 | 0.101181E+09 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.436481E+09 | 0.133538E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.377240E+09 | 0.174737E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.183352E+09 | 0.196260E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.202691E+09 | 0.249823E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.385627E+10 | 0.198726E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.172474E+09 | 0.101181E+09 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.436481E+09 | 0.249823E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.143884E+09 | 0.205626E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.230069E+09 | 0.163278E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.288209E+09 | 0.156485E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.310362E+09 | 0.129219E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.292161E+09 | 0.117734E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.262794E+09 | 92237274.04 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.327080E+09 | 86486415.60 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.362815E+09 | 84835401.03 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.364903E+09 | 0.112067E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.314578E+09 | 0.147060E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.152897E+09 | 0.165001E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.169249E+09 | 0.209615E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.321900E+10 | 0.166964E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.143884E+09 | 84835401.03 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.364903E+09 | 0.209615E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.143884E+09 | 0.205626E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.230069E+09 | 0.163278E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.288209E+09 | 0.156485E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.310362E+09 | 0.129219E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.292161E+09 | 0.117734E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.262794E+09 | 92237274.04 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.327080E+09 | 86486415.60 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.362815E+09 | 84835401.03 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.364903E+09 | 0.112067E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.314578E+09 | 0.147060E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.152897E+09 | 0.165001E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.169249E+09 | 0.209615E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.321900E+10 | 0.166964E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.143884E+09 | 84835401.03 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.364903E+09 | 0.209615E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.173005E+09 | 0.242139E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.276147E+09 | 0.192511E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.345655E+09 | 0.184494E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.372247E+09 | 0.152323E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.350442E+09 | 0.138887E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.315104E+09 | 0.108874E+09 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.391587E+09 | 0.102226E+09 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.434059E+09 | 0.100396E+09 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.436576E+09 | 0.132703E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.377110E+09 | 0.173622E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.183576E+09 | 0.194439E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.203073E+09 | 0.247145E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.385858E+10 | 0.196976E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.173005E+09 | 0.100396E+09 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.436576E+09 | 0.247145E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.145582E+09 | 0.197847E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.232438E+09 | 0.157183E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.291415E+09 | 0.148955E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.314797E+09 | 0.121832E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.296487E+09 | 0.111473E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.265021E+09 | 88163159.67 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.328280E+09 | 83121427.23 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.363818E+09 | 81446494.64 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.366979E+09 | 0.107687E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.318288E+09 | 0.138936E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.155020E+09 | 0.157901E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.170777E+09 | 0.202410E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.324890E+10 | 0.159696E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.145582E+09 | 81446494.64 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.366979E+09 | 0.202410E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.145582E+09 | 0.197847E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.232438E+09 | 0.157183E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.291415E+09 | 0.148955E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.314797E+09 | 0.121832E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.296487E+09 | 0.111473E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.265021E+09 | 88163159.67 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.328280E+09 | 83121427.23 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.363818E+09 | 81446494.64 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.366979E+09 | 0.107687E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.318288E+09 | 0.138936E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.155020E+09 | 0.157901E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.170777E+09 | 0.202410E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.324890E+10 | 0.159696E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.145582E+09 | 81446494.64 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.366979E+09 | 0.202410E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.145582E+09 | 0.197847E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.232438E+09 | 0.157183E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.291415E+09 | 0.148955E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.314797E+09 | 0.121832E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.296487E+09 | 0.111473E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.265021E+09 | 88163159.67 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.328280E+09 | 83121427.23 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.363818E+09 | 81446494.64 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.366979E+09 | 0.107687E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.318288E+09 | 0.138936E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.155020E+09 | 0.157901E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.170777E+09 | 0.202410E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.324890E+10 | 0.159696E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.145582E+09 | 81446494.64 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.366979E+09 | 0.202410E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.145582E+09 | 0.197847E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.232438E+09 | 0.157183E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.291415E+09 | 0.148955E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.314797E+09 | 0.121832E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.296487E+09 | 0.111473E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.265021E+09 | 88163159.67 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.328280E+09 | 83121427.23 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.363818E+09 | 81446494.64 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.366979E+09 | 0.107687E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.318288E+09 | 0.138936E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.155020E+09 | 0.157901E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.170777E+09 | 0.202410E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.324890E+10 | 0.159696E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.145582E+09 | 81446494.64 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.366979E+09 | 0.202410E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.175004E+09 | 0.233093E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.278902E+09 | 0.185420E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.349376E+09 | 0.175721E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.377402E+09 | 0.143732E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.355460E+09 | 0.131595E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.317666E+09 | 0.104130E+09 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.392943E+09 | 98301984.93 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.435190E+09 | 96430558.96 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.438983E+09 | 0.127569E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.381405E+09 | 0.164136E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.186059E+09 | 0.186171E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.204858E+09 | 0.238728E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.389325E+10 | 0.188503E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.175004E+09 | 96430558.96 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.438983E+09 | 0.238728E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.175004E+09 | 0.233093E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.278902E+09 | 0.185420E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.349376E+09 | 0.175721E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.377402E+09 | 0.143732E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.355460E+09 | 0.131595E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.317666E+09 | 0.104130E+09 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.392943E+09 | 98301984.93 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.435190E+09 | 96430558.96 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.438983E+09 | 0.127569E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.381405E+09 | 0.164136E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.186059E+09 | 0.186171E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.204858E+09 | 0.238728E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.389325E+10 | 0.188503E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.175004E+09 | 96430558.96 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.438983E+09 | 0.238728E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.144977E+09 | 0.198847E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.231682E+09 | 0.157780E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.290293E+09 | 0.149851E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.313200E+09 | 0.122818E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.294594E+09 | 0.112603E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.264046E+09 | 88345589.92 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.327812E+09 | 82756754.52 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.363426E+09 | 80949194.48 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.365972E+09 | 0.108066E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.316741E+09 | 0.140356E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.154376E+09 | 0.158761E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.170288E+09 | 0.203238E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.323741E+10 | 0.160437E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.144977E+09 | 80949194.48 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.365972E+09 | 0.203238E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.144977E+09 | 0.198847E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.231682E+09 | 0.157780E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.290293E+09 | 0.149851E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.313200E+09 | 0.122818E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.294594E+09 | 0.112603E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.264046E+09 | 88345589.92 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.327812E+09 | 82756754.52 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.363426E+09 | 80949194.48 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.365972E+09 | 0.108066E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.316741E+09 | 0.140356E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.154376E+09 | 0.158761E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.170288E+09 | 0.203238E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.323741E+10 | 0.160437E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.144977E+09 | 80949194.48 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.365972E+09 | 0.203238E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.174352E+09 | 0.234130E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.278100E+09 | 0.186020E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.348164E+09 | 0.176674E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.375646E+09 | 0.144802E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.353359E+09 | 0.132843E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.316628E+09 | 0.104292E+09 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.392500E+09 | 97832364.20 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.434827E+09 | 95815124.33 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.437889E+09 | 0.127968E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.379698E+09 | 0.165723E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.185364E+09 | 0.187074E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.204341E+09 | 0.239584E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.388087E+10 | 0.189276E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.174352E+09 | 95815124.33 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.437889E+09 | 0.239584E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.145132E+09 | 0.198003E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.231921E+09 | 0.157031E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.290602E+09 | 0.149015E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.313587E+09 | 0.122105E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.295046E+09 | 0.111944E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.264330E+09 | 87915667.07 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.328041E+09 | 82359038.70 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.363620E+09 | 80582798.38 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.366181E+09 | 0.107636E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.317029E+09 | 0.139669E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.154575E+09 | 0.157998E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.170443E+09 | 0.202416E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.324051E+10 | 0.159667E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.145132E+09 | 80582798.38 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.366181E+09 | 0.202416E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.145132E+09 | 0.198003E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.231921E+09 | 0.157031E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.290602E+09 | 0.149015E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.313587E+09 | 0.122105E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.295046E+09 | 0.111944E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.264330E+09 | 87915667.07 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.328041E+09 | 82359038.70 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.363620E+09 | 80582798.38 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.366181E+09 | 0.107636E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.317029E+09 | 0.139669E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.154575E+09 | 0.157998E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.170443E+09 | 0.202416E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.324051E+10 | 0.159667E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.145132E+09 | 80582798.38 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.366181E+09 | 0.202416E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.174541E+09 | 0.233132E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.278389E+09 | 0.185134E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.348535E+09 | 0.175688E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.376108E+09 | 0.143963E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.353898E+09 | 0.132068E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.316970E+09 | 0.103787E+09 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.392777E+09 | 97365465.23 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.435061E+09 | 95382632.80 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.438138E+09 | 0.127459E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.380041E+09 | 0.164912E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.185603E+09 | 0.186172E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.204528E+09 | 0.238608E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.388459E+10 | 0.188367E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.174541E+09 | 95382632.80 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.438138E+09 | 0.238608E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.145676E+09 | 0.194637E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.232734E+09 | 0.154137E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.291696E+09 | 0.145629E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.315040E+09 | 0.119071E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.296993E+09 | 0.108892E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.265383E+09 | 86194686.08 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.328649E+09 | 81111502.06 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364071E+09 | 79518046.60 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.367061E+09 | 0.105734E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.318254E+09 | 0.136450E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.155264E+09 | 0.155089E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.170972E+09 | 0.199231E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.325179E+10 | 0.156570E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.145676E+09 | 79518046.60 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.367061E+09 | 0.199231E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.145676E+09 | 0.194637E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.232734E+09 | 0.154137E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.291696E+09 | 0.145629E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.315040E+09 | 0.119071E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.296993E+09 | 0.108892E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.265383E+09 | 86194686.08 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.328649E+09 | 81111502.06 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364071E+09 | 79518046.60 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.367061E+09 | 0.105734E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.318254E+09 | 0.136450E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.155264E+09 | 0.155089E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.170972E+09 | 0.199231E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.325179E+10 | 0.156570E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.145676E+09 | 79518046.60 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.367061E+09 | 0.199231E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.175206E+09 | 0.229159E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.279372E+09 | 0.181721E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.349851E+09 | 0.171698E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.377844E+09 | 0.140399E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.356220E+09 | 0.128486E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.318230E+09 | 0.101766E+09 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.393510E+09 | 95901897.77 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.435603E+09 | 94131368.60 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.439191E+09 | 0.125217E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.381501E+09 | 0.161123E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.186433E+09 | 0.182742E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.205166E+09 | 0.234838E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.389813E+10 | 0.184718E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.175206E+09 | 94131368.60 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.439191E+09 | 0.234838E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.147798E+09 | 0.181376E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.235541E+09 | 0.142947E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.294881E+09 | 0.133587E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.318461E+09 | 0.108957E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.301531E+09 | 99324966.87 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.268211E+09 | 79723357.30 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.330318E+09 | 76055353.71 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365125E+09 | 75138426.61 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.369431E+09 | 99150712.60 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.321294E+09 | 0.126528E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.157322E+09 | 0.144869E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.172871E+09 | 0.186790E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.328278E+10 | 0.145445E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.147798E+09 | 75138426.61 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.369431E+09 | 0.186790E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.147798E+09 | 0.181376E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.235541E+09 | 0.142947E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.294881E+09 | 0.133587E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.318461E+09 | 0.108957E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.301531E+09 | 99324966.87 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.268211E+09 | 79723357.30 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.330318E+09 | 76055353.71 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365125E+09 | 75138426.61 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.369431E+09 | 99150712.60 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.321294E+09 | 0.126528E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.157322E+09 | 0.144869E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.172871E+09 | 0.186790E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.328278E+10 | 0.145445E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.147798E+09 | 75138426.61 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.369431E+09 | 0.186790E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.177788E+09 | 0.213515E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.282769E+09 | 0.168532E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.353705E+09 | 0.157524E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.381947E+09 | 0.128521E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.361638E+09 | 0.117253E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.321607E+09 | 94180661.63 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.395507E+09 | 89968176.85 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.436869E+09 | 88991522.25 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.442027E+09 | 0.117453E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.385136E+09 | 0.149448E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.188920E+09 | 0.170694E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.207463E+09 | 0.220128E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.393538E+10 | 0.171621E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.177788E+09 | 88991522.25 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.442027E+09 | 0.220128E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 347.33 | 487.07 | 390.07 | 231.63 | 158.44 | 0.00 | 0.00 |
February | 613.95 | 425.17 | 599.87 | 371.33 | 228.54 | 0.00 | 0.00 |
March | 696.22 | 361.16 | 645.29 | 344.12 | 301.16 | 0.00 | 0.00 |
April | 776.55 | 305.90 | 681.30 | 295.82 | 385.48 | 0.00 | 0.00 |
May | 708.26 | 267.58 | 622.96 | 185.59 | 437.37 | 0.00 | 0.00 |
June | 655.85 | 215.77 | 569.95 | 153.02 | 416.92 | 0.00 | 0.00 |
July | 786.28 | 195.02 | 621.55 | 227.65 | 393.91 | 0.00 | 0.00 |
August | 871.13 | 190.53 | 667.78 | 311.40 | 356.38 | 0.00 | 0.00 |
September | 906.22 | 266.01 | 739.87 | 408.58 | 331.29 | 0.00 | 0.00 |
October | 759.30 | 339.22 | 670.20 | 413.80 | 256.40 | 0.00 | 0.00 |
November | 381.14 | 400.62 | 396.24 | 227.08 | 169.16 | 0.00 | 0.00 |
December | 407.44 | 494.57 | 414.59 | 268.29 | 146.29 | 0.00 | 0.00 |
Annual Sum or Average | 659.28 | 328.61 | 584.72 | 286.00 | 298.72 | 0.00 | 0.00 |
Minimum of Months | 347.33 | 190.53 | 390.07 | 153.02 | 146.29 | 0.00 | 0.00 |
Maximum of Months | 906.22 | 494.57 | 739.87 | 413.80 | 437.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 170.75 | 259.92 | 195.04 | 115.81 | 79.22 | 0.00 | 0.00 |
February | 302.55 | 228.17 | 299.93 | 185.66 | 114.27 | 0.00 | 0.00 |
March | 342.67 | 197.68 | 322.64 | 172.06 | 150.58 | 0.00 | 0.00 |
April | 381.52 | 166.62 | 340.65 | 147.91 | 192.74 | 0.00 | 0.00 |
May | 348.58 | 142.22 | 311.48 | 92.79 | 218.69 | 0.00 | 0.00 |
June | 324.74 | 112.16 | 284.97 | 76.51 | 208.46 | 0.00 | 0.00 |
July | 391.47 | 99.89 | 310.78 | 113.82 | 196.95 | 0.00 | 0.00 |
August | 434.11 | 97.49 | 333.89 | 155.70 | 178.19 | 0.00 | 0.00 |
September | 450.56 | 137.08 | 369.94 | 204.29 | 165.65 | 0.00 | 0.00 |
October | 374.59 | 182.40 | 335.10 | 206.90 | 128.20 | 0.00 | 0.00 |
November | 187.23 | 215.24 | 198.12 | 113.54 | 84.58 | 0.00 | 0.00 |
December | 201.03 | 263.66 | 207.29 | 134.15 | 73.15 | 0.00 | 0.00 |
Annual Sum or Average | 325.90 | 174.97 | 292.36 | 143.00 | 149.36 | 0.00 | 0.00 |
Minimum of Months | 170.75 | 97.49 | 195.04 | 76.51 | 73.15 | 0.00 | 0.00 |
Maximum of Months | 450.56 | 263.66 | 369.94 | 206.90 | 218.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 171.07 | 250.51 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 303.17 | 219.90 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 343.43 | 190.14 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 382.34 | 162.20 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 348.48 | 142.14 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 323.91 | 114.67 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 390.04 | 103.79 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 432.67 | 101.72 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 449.70 | 139.22 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 375.13 | 178.28 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 188.00 | 207.37 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 201.42 | 254.79 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 325.85 | 171.84 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 171.07 | 101.72 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 449.70 | 254.79 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 171.51 | 246.88 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 303.86 | 216.75 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 344.20 | 187.11 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 383.25 | 159.69 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 349.02 | 140.87 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 324.11 | 114.12 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 390.13 | 103.57 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 432.70 | 101.62 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 449.90 | 138.53 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 375.84 | 175.75 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 188.58 | 204.22 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 201.82 | 251.48 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 326.32 | 169.84 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 171.51 | 101.62 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 449.90 | 251.48 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 172.03 | 243.95 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 304.35 | 214.56 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 344.26 | 185.73 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 383.09 | 158.47 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 349.00 | 139.77 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 324.34 | 113.17 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 390.44 | 102.75 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 432.98 | 100.83 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 449.99 | 137.67 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 375.70 | 174.63 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 188.80 | 202.33 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 202.20 | 248.80 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 326.50 | 168.35 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 172.03 | 100.83 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 449.99 | 248.80 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 348.09 | 469.52 | 389.27 | 231.15 | 158.12 | 0.00 | 0.00 |
February | 614.89 | 413.18 | 598.64 | 370.57 | 228.07 | 0.00 | 0.00 |
March | 696.09 | 353.67 | 643.96 | 343.42 | 300.54 | 0.00 | 0.00 |
April | 777.00 | 298.92 | 679.90 | 295.21 | 384.69 | 0.00 | 0.00 |
May | 708.21 | 264.74 | 621.68 | 185.21 | 436.48 | 0.00 | 0.00 |
June | 654.09 | 216.40 | 568.78 | 152.71 | 416.07 | 0.00 | 0.00 |
July | 783.68 | 197.54 | 620.28 | 227.18 | 393.10 | 0.00 | 0.00 |
August | 868.30 | 193.64 | 666.41 | 310.76 | 355.65 | 0.00 | 0.00 |
September | 905.05 | 264.62 | 738.36 | 407.74 | 330.61 | 0.00 | 0.00 |
October | 760.14 | 330.05 | 668.83 | 412.95 | 255.88 | 0.00 | 0.00 |
November | 382.79 | 387.32 | 395.43 | 226.62 | 168.82 | 0.00 | 0.00 |
December | 408.01 | 480.55 | 413.73 | 267.74 | 145.99 | 0.00 | 0.00 |
Annual Sum or Average | 659.00 | 322.10 | 583.52 | 285.41 | 298.11 | 0.00 | 0.00 |
Minimum of Months | 348.09 | 193.64 | 389.27 | 152.71 | 145.99 | 0.00 | 0.00 |
Maximum of Months | 905.05 | 480.55 | 738.36 | 412.95 | 436.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 173.35 | 235.89 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 306.49 | 207.33 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 346.76 | 177.86 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 386.59 | 150.63 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 351.91 | 133.68 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 325.89 | 108.40 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 391.32 | 98.32 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 433.72 | 96.22 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 451.32 | 132.75 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 378.28 | 166.68 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 190.63 | 194.67 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 203.45 | 241.21 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 328.38 | 161.77 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 173.35 | 96.22 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 451.32 | 241.21 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 173.54 | 234.89 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 306.81 | 206.35 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 347.12 | 176.87 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 387.07 | 149.76 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 352.45 | 132.90 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 326.25 | 107.88 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 391.60 | 97.85 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 433.95 | 95.78 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 451.58 | 132.23 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 378.62 | 165.86 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 190.88 | 193.74 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 203.63 | 240.23 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 328.69 | 160.99 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 173.54 | 95.78 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 451.58 | 240.23 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 174.19 | 230.90 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 307.89 | 202.54 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 348.43 | 172.85 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 388.86 | 146.04 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 354.77 | 129.28 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 327.54 | 105.77 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 392.33 | 96.37 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 434.49 | 94.52 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 452.67 | 129.89 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 380.08 | 162.05 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 191.73 | 190.17 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 204.27 | 236.45 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 329.84 | 157.87 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 174.19 | 94.52 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 452.67 | 236.45 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 176.74 | 215.15 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 311.61 | 187.84 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 352.25 | 158.56 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 393.08 | 133.65 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 360.18 | 117.94 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 331.03 | 97.85 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 394.32 | 90.38 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 435.75 | 89.33 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 455.59 | 121.82 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 383.71 | 150.28 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 194.28 | 177.63 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 206.54 | 221.66 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 332.98 | 146.66 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 176.74 | 89.33 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 455.59 | 221.66 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.930287E+09 | 0.130457E+10 | 0.104477E+10 | 0.620386E+09 | 0.424379E+09 | 0.00 | 0.00 |
February | 0.148528E+10 | 0.102857E+10 | 0.145120E+10 | 0.898314E+09 | 0.552889E+09 | 0.00 | 0.00 |
March | 0.186476E+10 | 0.967333E+09 | 0.172833E+10 | 0.921701E+09 | 0.806632E+09 | 0.00 | 0.00 |
April | 0.201281E+10 | 0.792896E+09 | 0.176593E+10 | 0.766756E+09 | 0.999171E+09 | 0.00 | 0.00 |
May | 0.189701E+10 | 0.716690E+09 | 0.166854E+10 | 0.497074E+09 | 0.117146E+10 | 0.00 | 0.00 |
June | 0.169995E+10 | 0.559269E+09 | 0.147731E+10 | 0.396638E+09 | 0.108067E+10 | 0.00 | 0.00 |
July | 0.210597E+10 | 0.522348E+09 | 0.166477E+10 | 0.609727E+09 | 0.105504E+10 | 0.00 | 0.00 |
August | 0.233323E+10 | 0.510327E+09 | 0.178858E+10 | 0.834046E+09 | 0.954537E+09 | 0.00 | 0.00 |
September | 0.234891E+10 | 0.689502E+09 | 0.191775E+10 | 0.105905E+10 | 0.858706E+09 | 0.00 | 0.00 |
October | 0.203372E+10 | 0.908573E+09 | 0.179506E+10 | 0.110832E+10 | 0.686745E+09 | 0.00 | 0.00 |
November | 0.987904E+09 | 0.103842E+10 | 0.102707E+10 | 0.588595E+09 | 0.438471E+09 | 0.00 | 0.00 |
December | 0.109128E+10 | 0.132465E+10 | 0.111043E+10 | 0.718600E+09 | 0.391825E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.207911E+11 | 0.103631E+11 | 0.184397E+11 | 0.901920E+10 | 0.942053E+10 | 0.00 | 0.00 |
Minimum of Months | 0.930287E+09 | 0.510327E+09 | 0.102707E+10 | 0.396638E+09 | 0.391825E+09 | 0.00 | 0.00 |
Maximum of Months | 0.234891E+10 | 0.132465E+10 | 0.191775E+10 | 0.110832E+10 | 0.117146E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.457325E+09 | 0.696157E+09 | 0.522383E+09 | 0.310193E+09 | 0.212190E+09 | 0.00 | 0.00 |
February | 0.731926E+09 | 0.551987E+09 | 0.725601E+09 | 0.449157E+09 | 0.276444E+09 | 0.00 | 0.00 |
March | 0.917806E+09 | 0.529478E+09 | 0.864166E+09 | 0.460850E+09 | 0.403316E+09 | 0.00 | 0.00 |
April | 0.988902E+09 | 0.431878E+09 | 0.882964E+09 | 0.383378E+09 | 0.499586E+09 | 0.00 | 0.00 |
May | 0.933648E+09 | 0.380910E+09 | 0.834269E+09 | 0.248537E+09 | 0.585732E+09 | 0.00 | 0.00 |
June | 0.841733E+09 | 0.290707E+09 | 0.738653E+09 | 0.198319E+09 | 0.540334E+09 | 0.00 | 0.00 |
July | 0.104851E+10 | 0.267542E+09 | 0.832384E+09 | 0.304863E+09 | 0.527521E+09 | 0.00 | 0.00 |
August | 0.116271E+10 | 0.261120E+09 | 0.894292E+09 | 0.417023E+09 | 0.477269E+09 | 0.00 | 0.00 |
September | 0.116784E+10 | 0.355318E+09 | 0.958876E+09 | 0.529523E+09 | 0.429353E+09 | 0.00 | 0.00 |
October | 0.100329E+10 | 0.488538E+09 | 0.897532E+09 | 0.554160E+09 | 0.343372E+09 | 0.00 | 0.00 |
November | 0.485312E+09 | 0.557905E+09 | 0.513533E+09 | 0.294298E+09 | 0.219235E+09 | 0.00 | 0.00 |
December | 0.538437E+09 | 0.706197E+09 | 0.555213E+09 | 0.359300E+09 | 0.195913E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102774E+11 | 0.551774E+10 | 0.921987E+10 | 0.450960E+10 | 0.471026E+10 | 0.00 | 0.00 |
Minimum of Months | 0.457325E+09 | 0.261120E+09 | 0.513533E+09 | 0.198319E+09 | 0.195913E+09 | 0.00 | 0.00 |
Maximum of Months | 0.116784E+10 | 0.706197E+09 | 0.958876E+09 | 0.554160E+09 | 0.585732E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.458207E+09 | 0.670976E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.733432E+09 | 0.531972E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.919856E+09 | 0.509275E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.991024E+09 | 0.420419E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.933372E+09 | 0.380705E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.839567E+09 | 0.297214E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.104469E+10 | 0.278004E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.115885E+10 | 0.272448E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.116563E+10 | 0.360868E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.100474E+10 | 0.477495E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.487300E+09 | 0.537495E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.539480E+09 | 0.682423E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102762E+11 | 0.541929E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.458207E+09 | 0.272448E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.116563E+10 | 0.682423E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.459370E+09 | 0.661254E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.735104E+09 | 0.524368E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.921903E+09 | 0.501142E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.993381E+09 | 0.413923E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.934820E+09 | 0.377300E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.840092E+09 | 0.295790E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.104493E+10 | 0.277392E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.115895E+10 | 0.272179E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.116615E+10 | 0.359072E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.100665E+10 | 0.470719E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.488795E+09 | 0.529330E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.540565E+09 | 0.673575E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102907E+11 | 0.535604E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.459370E+09 | 0.272179E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.116615E+10 | 0.673575E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.460768E+09 | 0.653386E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.736282E+09 | 0.519064E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.922070E+09 | 0.497461E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.992968E+09 | 0.410759E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.934763E+09 | 0.374353E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.840691E+09 | 0.293347E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.104575E+10 | 0.275198E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.115969E+10 | 0.270067E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.116638E+10 | 0.356836E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.100626E+10 | 0.467742E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.489369E+09 | 0.524439E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.541569E+09 | 0.666374E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102966E+11 | 0.530903E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.460768E+09 | 0.270067E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.116638E+10 | 0.666374E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.932333E+09 | 0.125757E+10 | 0.104262E+10 | 0.619114E+09 | 0.423508E+09 | 0.00 | 0.00 |
February | 0.148755E+10 | 0.999568E+09 | 0.144823E+10 | 0.896471E+09 | 0.551754E+09 | 0.00 | 0.00 |
March | 0.186441E+10 | 0.947260E+09 | 0.172479E+10 | 0.919810E+09 | 0.804977E+09 | 0.00 | 0.00 |
April | 0.201399E+10 | 0.774791E+09 | 0.176230E+10 | 0.765183E+09 | 0.997122E+09 | 0.00 | 0.00 |
May | 0.189686E+10 | 0.709077E+09 | 0.166511E+10 | 0.496055E+09 | 0.116906E+10 | 0.00 | 0.00 |
June | 0.169541E+10 | 0.560909E+09 | 0.147428E+10 | 0.395824E+09 | 0.107845E+10 | 0.00 | 0.00 |
July | 0.209900E+10 | 0.529087E+09 | 0.166135E+10 | 0.608476E+09 | 0.105288E+10 | 0.00 | 0.00 |
August | 0.232565E+10 | 0.518647E+09 | 0.178491E+10 | 0.832335E+09 | 0.952579E+09 | 0.00 | 0.00 |
September | 0.234588E+10 | 0.685887E+09 | 0.191382E+10 | 0.105687E+10 | 0.856945E+09 | 0.00 | 0.00 |
October | 0.203596E+10 | 0.884014E+09 | 0.179138E+10 | 0.110605E+10 | 0.685336E+09 | 0.00 | 0.00 |
November | 0.992196E+09 | 0.100394E+10 | 0.102496E+10 | 0.587388E+09 | 0.437571E+09 | 0.00 | 0.00 |
December | 0.109282E+10 | 0.128710E+10 | 0.110815E+10 | 0.717126E+09 | 0.391021E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.207821E+11 | 0.101578E+11 | 0.184019E+11 | 0.900070E+10 | 0.940120E+10 | 0.00 | 0.00 |
Minimum of Months | 0.932333E+09 | 0.518647E+09 | 0.102496E+10 | 0.395824E+09 | 0.391021E+09 | 0.00 | 0.00 |
Maximum of Months | 0.234588E+10 | 0.128710E+10 | 0.191382E+10 | 0.110605E+10 | 0.116906E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.464302E+09 | 0.631819E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.741462E+09 | 0.501579E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.928749E+09 | 0.476374E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.100205E+10 | 0.390436E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.942547E+09 | 0.358049E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.844718E+09 | 0.280981E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.104812E+10 | 0.263344E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.116168E+10 | 0.257713E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.116983E+10 | 0.344099E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.101318E+10 | 0.446435E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.494114E+09 | 0.504593E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.544915E+09 | 0.646059E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.103557E+11 | 0.510148E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.464302E+09 | 0.257713E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.116983E+10 | 0.646059E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.464799E+09 | 0.629132E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.742228E+09 | 0.499193E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.929737E+09 | 0.473717E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.100328E+10 | 0.388171E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.943989E+09 | 0.355954E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.845629E+09 | 0.279616E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.104886E+10 | 0.262081E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.116230E+10 | 0.256548E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.117050E+10 | 0.342730E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.101410E+10 | 0.444249E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.494751E+09 | 0.502166E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.545414E+09 | 0.643439E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.103656E+11 | 0.507700E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.464799E+09 | 0.256548E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117050E+10 | 0.643439E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.466555E+09 | 0.618429E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.744837E+09 | 0.489992E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.933241E+09 | 0.462954E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.100792E+10 | 0.378542E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.950206E+09 | 0.346269E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.848995E+09 | 0.274155E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.105081E+10 | 0.258125E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.116374E+10 | 0.253167E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.117331E+10 | 0.336685E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.101801E+10 | 0.434022E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.496959E+09 | 0.492918E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.547109E+09 | 0.633299E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104017E+11 | 0.497856E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.466555E+09 | 0.253167E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117331E+10 | 0.633299E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.473382E+09 | 0.576265E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.753849E+09 | 0.454423E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.943464E+09 | 0.424695E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.101887E+10 | 0.346433E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.964699E+09 | 0.315903E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.858028E+09 | 0.253627E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.105614E+10 | 0.242078E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.116712E+10 | 0.239268E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.118089E+10 | 0.315754E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.102772E+10 | 0.402502E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.503561E+09 | 0.460429E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.553204E+09 | 0.593707E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105009E+11 | 0.462508E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.473382E+09 | 0.239268E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118089E+10 | 0.593707E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.357127E+09 | -233295344.5 | 0.00 | 0.00 | 744.00 | 0.00 | -123831688.5 | 58.99 | 0.00 | 0.00 |
February | 0.324633E+09 | -213318542.7 | 0.00 | 0.00 | 672.00 | 0.00 | -111314490.5 | 58.99 | 0.00 | 0.00 |
March | 0.359463E+09 | -237338115.2 | 0.00 | 0.00 | 744.00 | 0.00 | -122124647.5 | 58.99 | 0.00 | 0.00 |
April | 0.335997E+09 | -220452614.2 | 0.00 | 0.00 | 720.00 | 0.00 | -115544091.0 | 58.99 | 0.00 | 0.00 |
May | 0.335469E+09 | -219627147.6 | 0.00 | 0.00 | 744.00 | 0.00 | -115841546.6 | 58.99 | 0.00 | 0.00 |
June | 0.316645E+09 | -206546928.2 | 0.00 | 0.00 | 720.00 | 0.00 | -110098243.2 | 58.99 | 0.00 | 0.00 |
July | 0.316202E+09 | -203260803.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112940727.3 | 58.99 | 0.00 | 0.00 |
August | 0.318551E+09 | -205770100.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112780450.2 | 58.99 | 0.00 | 0.00 |
September | 0.309609E+09 | -199580326.9 | 0.00 | 0.00 | 720.00 | 0.00 | -110029152.3 | 58.99 | 0.00 | 0.00 |
October | 0.328802E+09 | -210814116.9 | 0.00 | 0.00 | 744.00 | 0.00 | -117987450.7 | 58.99 | 0.00 | 0.00 |
November | 0.329704E+09 | -211655893.4 | 0.00 | 0.00 | 720.00 | 0.00 | -118048526.4 | 58.99 | 0.00 | 0.00 |
December | 0.351358E+09 | -227817223.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123541151.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.398356E+10 | -0.258948E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139408E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.309609E+09 | -237338115.2 | 0.00 | 0.00 | 672.00 | 0.00 | -123831688.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.359463E+09 | -199580326.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110029152.3 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.354737E+09 | -233294736.6 | 0.00 | 0.00 | 744.00 | 0.00 | -121442420.2 | 58.99 | 0.00 | 0.00 |
February | 0.322169E+09 | -213320029.2 | 0.00 | 0.00 | 672.00 | 0.00 | -108849344.8 | 58.99 | 0.00 | 0.00 |
March | 0.356093E+09 | -237336603.5 | 0.00 | 0.00 | 744.00 | 0.00 | -118756413.0 | 58.99 | 0.00 | 0.00 |
April | 0.333048E+09 | -220465562.1 | 0.00 | 0.00 | 720.00 | 0.00 | -112582259.6 | 58.99 | 0.00 | 0.00 |
May | 0.333502E+09 | -219624408.3 | 0.00 | 0.00 | 744.00 | 0.00 | -113877485.9 | 58.99 | 0.00 | 0.00 |
June | 0.315832E+09 | -206543227.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109288809.1 | 58.99 | 0.00 | 0.00 |
July | 0.315795E+09 | -203266790.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112528645.3 | 58.99 | 0.00 | 0.00 |
August | 0.318211E+09 | -205768918.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112441781.2 | 58.99 | 0.00 | 0.00 |
September | 0.308816E+09 | -199577930.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109238418.8 | 58.99 | 0.00 | 0.00 |
October | 0.326121E+09 | -210819862.2 | 0.00 | 0.00 | 744.00 | 0.00 | -115301178.1 | 58.99 | 0.00 | 0.00 |
November | 0.327132E+09 | -211657240.0 | 0.00 | 0.00 | 720.00 | 0.00 | -115474641.4 | 58.99 | 0.00 | 0.00 |
December | 0.348850E+09 | -227815207.7 | 0.00 | 0.00 | 744.00 | 0.00 | -121034549.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.396031E+10 | -0.258949E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.137082E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.308816E+09 | -237336603.5 | 0.00 | 0.00 | 672.00 | 0.00 | -121442420.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.356093E+09 | -199577930.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108849344.8 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.328525E+09 | -205146447.5 | 0.00 | 0.00 | 744.00 | 0.00 | -123378297.0 | 59.00 | 0.00 | 0.00 |
February | 0.298324E+09 | -187742919.8 | 0.00 | 0.00 | 672.00 | 0.00 | -110580993.4 | 58.99 | 0.00 | 0.00 |
March | 0.332467E+09 | -211833088.5 | 0.00 | 0.00 | 744.00 | 0.00 | -120633994.2 | 58.99 | 0.00 | 0.00 |
April | 0.307640E+09 | -193894613.7 | 0.00 | 0.00 | 720.00 | 0.00 | -113745557.1 | 58.99 | 0.00 | 0.00 |
May | 0.308743E+09 | -194779411.8 | 0.00 | 0.00 | 744.00 | 0.00 | -113963760.0 | 58.99 | 0.00 | 0.00 |
June | 0.292598E+09 | -183961168.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108636938.4 | 58.99 | 0.00 | 0.00 |
July | 0.289118E+09 | -177699605.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111418872.8 | 58.99 | 0.00 | 0.00 |
August | 0.295060E+09 | -183789617.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111269956.7 | 58.99 | 0.00 | 0.00 |
September | 0.284145E+09 | -175384044.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108760938.1 | 59.00 | 0.00 | 0.00 |
October | 0.301766E+09 | -185402716.7 | 0.00 | 0.00 | 744.00 | 0.00 | -116363283.0 | 58.99 | 0.00 | 0.00 |
November | 0.304114E+09 | -186880991.7 | 0.00 | 0.00 | 720.00 | 0.00 | -117232541.6 | 58.99 | 0.00 | 0.00 |
December | 0.321805E+09 | -198866303.1 | 0.00 | 0.00 | 744.00 | 0.00 | -122938877.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.366430E+10 | -0.228538E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.137892E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284145E+09 | -211833088.5 | 0.00 | 0.00 | 672.00 | 0.00 | -123378297.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.332467E+09 | -175384044.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108636938.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.328965E+09 | -205142352.9 | 0.00 | 0.00 | 744.00 | 0.00 | -123822932.9 | 59.00 | 0.00 | 0.00 |
February | 0.298740E+09 | -187741787.8 | 0.00 | 0.00 | 672.00 | 0.00 | -110998056.0 | 58.99 | 0.00 | 0.00 |
March | 0.332942E+09 | -211853165.8 | 0.00 | 0.00 | 744.00 | 0.00 | -121088528.5 | 58.98 | 0.00 | 0.00 |
April | 0.308082E+09 | -193903540.2 | 0.00 | 0.00 | 720.00 | 0.00 | -114178876.8 | 58.99 | 0.00 | 0.00 |
May | 0.308994E+09 | -194783554.5 | 0.00 | 0.00 | 744.00 | 0.00 | -114210333.8 | 58.99 | 0.00 | 0.00 |
June | 0.292680E+09 | -183948820.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108731296.0 | 58.99 | 0.00 | 0.00 |
July | 0.289152E+09 | -177734945.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111417009.4 | 58.98 | 0.00 | 0.00 |
August | 0.295061E+09 | -183811347.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111249872.8 | 58.98 | 0.00 | 0.00 |
September | 0.284246E+09 | -175430971.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108814570.6 | 58.98 | 0.00 | 0.00 |
October | 0.302215E+09 | -185405113.9 | 0.00 | 0.00 | 744.00 | 0.00 | -116809816.3 | 58.99 | 0.00 | 0.00 |
November | 0.304544E+09 | -186875316.4 | 0.00 | 0.00 | 720.00 | 0.00 | -117668452.7 | 58.99 | 0.00 | 0.00 |
December | 0.322231E+09 | -198835487.2 | 0.00 | 0.00 | 744.00 | 0.00 | -123395818.1 | 59.01 | 0.00 | 0.00 |
Annual Sum or Average | 0.366785E+10 | -0.228547E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138239E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284246E+09 | -211853165.8 | 0.00 | 0.00 | 672.00 | 0.00 | -123822932.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.332942E+09 | -175430971.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108731296.0 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.319211E+09 | -193895772.0 | 0.00 | 0.00 | 744.00 | 0.00 | -125315726.9 | 58.99 | 0.00 | 0.00 |
February | 0.289892E+09 | -177531990.9 | 0.00 | 0.00 | 672.00 | 0.00 | -112359962.8 | 58.99 | 0.00 | 0.00 |
March | 0.323244E+09 | -200425301.6 | 0.00 | 0.00 | 744.00 | 0.00 | -122819091.1 | 58.99 | 0.00 | 0.00 |
April | 0.299659E+09 | -183484310.2 | 0.00 | 0.00 | 720.00 | 0.00 | -116174502.3 | 58.99 | 0.00 | 0.00 |
May | 0.300291E+09 | -184190667.5 | 0.00 | 0.00 | 744.00 | 0.00 | -116100494.1 | 59.00 | 0.00 | 0.00 |
June | 0.283883E+09 | -174046815.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109836019.1 | 59.00 | 0.00 | 0.00 |
July | 0.280349E+09 | -168063709.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112285194.3 | 58.99 | 0.00 | 0.00 |
August | 0.286024E+09 | -173902134.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112121470.3 | 58.99 | 0.00 | 0.00 |
September | 0.276021E+09 | -165990860.1 | 0.00 | 0.00 | 720.00 | 0.00 | -110029811.4 | 58.99 | 0.00 | 0.00 |
October | 0.294017E+09 | -175236702.9 | 0.00 | 0.00 | 744.00 | 0.00 | -118779801.4 | 58.99 | 0.00 | 0.00 |
November | 0.295646E+09 | -176492007.9 | 0.00 | 0.00 | 720.00 | 0.00 | -119154342.7 | 58.99 | 0.00 | 0.00 |
December | 0.312805E+09 | -188082651.3 | 0.00 | 0.00 | 744.00 | 0.00 | -124722011.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.356104E+10 | -0.216134E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139970E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.276021E+09 | -200425301.6 | 0.00 | 0.00 | 672.00 | 0.00 | -125315726.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.323244E+09 | -165990860.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109836019.1 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.319189E+09 | -193896471.6 | 0.00 | 0.00 | 744.00 | 0.00 | -125292913.9 | 58.99 | 0.00 | 0.00 |
February | 0.289822E+09 | -177532524.1 | 0.00 | 0.00 | 672.00 | 0.00 | -112289481.2 | 58.99 | 0.00 | 0.00 |
March | 0.322958E+09 | -200433251.7 | 0.00 | 0.00 | 744.00 | 0.00 | -122525233.9 | 58.99 | 0.00 | 0.00 |
April | 0.299188E+09 | -183473394.8 | 0.00 | 0.00 | 720.00 | 0.00 | -115714828.0 | 59.00 | 0.00 | 0.00 |
May | 0.299674E+09 | -184195528.4 | 0.00 | 0.00 | 744.00 | 0.00 | -115478311.5 | 58.99 | 0.00 | 0.00 |
June | 0.283679E+09 | -174027879.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109651405.9 | 59.00 | 0.00 | 0.00 |
July | 0.280354E+09 | -168101285.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112252783.5 | 58.98 | 0.00 | 0.00 |
August | 0.286042E+09 | -173908621.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112133511.9 | 58.99 | 0.00 | 0.00 |
September | 0.275717E+09 | -165980106.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109736430.6 | 59.00 | 0.00 | 0.00 |
October | 0.293459E+09 | -175229253.8 | 0.00 | 0.00 | 744.00 | 0.00 | -118229366.9 | 58.99 | 0.00 | 0.00 |
November | 0.295491E+09 | -176506663.8 | 0.00 | 0.00 | 720.00 | 0.00 | -118984528.7 | 58.99 | 0.00 | 0.00 |
December | 0.312791E+09 | -188074772.4 | 0.00 | 0.00 | 744.00 | 0.00 | -124716617.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.355837E+10 | -0.216136E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139701E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.275717E+09 | -200433251.7 | 0.00 | 0.00 | 672.00 | 0.00 | -125292913.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.322958E+09 | -165980106.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109651405.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.319308E+09 | -193892956.7 | 0.00 | 0.00 | 744.00 | 0.00 | -125415260.7 | 59.00 | 0.00 | 0.00 |
February | 0.289947E+09 | -177525071.7 | 0.00 | 0.00 | 672.00 | 0.00 | -112422328.5 | 59.00 | 0.00 | 0.00 |
March | 0.323113E+09 | -200424517.2 | 0.00 | 0.00 | 744.00 | 0.00 | -122688769.0 | 58.99 | 0.00 | 0.00 |
April | 0.299339E+09 | -183480502.5 | 0.00 | 0.00 | 720.00 | 0.00 | -115858513.5 | 58.99 | 0.00 | 0.00 |
May | 0.299843E+09 | -184213115.7 | 0.00 | 0.00 | 744.00 | 0.00 | -115630117.8 | 58.99 | 0.00 | 0.00 |
June | 0.283769E+09 | -174091685.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109677633.7 | 58.98 | 0.00 | 0.00 |
July | 0.280441E+09 | -168048651.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112392178.3 | 59.00 | 0.00 | 0.00 |
August | 0.286103E+09 | -173911555.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112191395.8 | 58.99 | 0.00 | 0.00 |
September | 0.275803E+09 | -165993772.7 | 0.00 | 0.00 | 720.00 | 0.00 | -109808754.2 | 58.99 | 0.00 | 0.00 |
October | 0.293603E+09 | -175245172.0 | 0.00 | 0.00 | 744.00 | 0.00 | -118358136.3 | 58.99 | 0.00 | 0.00 |
November | 0.295614E+09 | -176503292.4 | 0.00 | 0.00 | 720.00 | 0.00 | -119110683.2 | 58.99 | 0.00 | 0.00 |
December | 0.312905E+09 | -188068841.5 | 0.00 | 0.00 | 744.00 | 0.00 | -124836161.7 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.355979E+10 | -0.216140E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139839E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.275803E+09 | -200424517.2 | 0.00 | 0.00 | 672.00 | 0.00 | -125415260.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.323113E+09 | -165993772.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109677633.7 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116150E+11 | 59060.51 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.763827E+10 | 59060.51 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.336321E+10 | 59060.51 | 06-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.916961E+09 | 59060.51 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38952614.51 | 6166.97 | 18-MAY-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.389935E+09 | 26729.52 | 31-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.537482E+10 | 59060.51 | 13-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.973171E+10 | 59060.51 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.390689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116150E+11 | 59060.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.324826E+10 | 31008.43 | 05-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188589E+10 | 31008.43 | 14-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.442119E+09 | 15446.66 | 25-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 56357510.17 | 3800.37 | 19-APR-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1088271.08 | 1179.59 | 18-MAY-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6047054.66 | 1614.91 | 30-OCT-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121227E+10 | 17753.74 | 30-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.254392E+10 | 31008.43 | 22-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.939595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.324826E+10 | 31008.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.438452E+10 | 30925.49 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.269375E+10 | 30925.49 | 14-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.932103E+09 | 16187.54 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187454E+09 | 5578.01 | 19-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2220737.80 | 1276.22 | 18-MAY-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 50575629.97 | 3235.82 | 30-OCT-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191106E+10 | 18701.71 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.358897E+10 | 30925.49 | 25-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.438452E+10 | 30925.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.466616E+10 | 30755.28 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288905E+10 | 30755.28 | 12-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108939E+10 | 22031.93 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.246108E+09 | 8465.43 | 18-APR-07:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2834866.27 | 1566.34 | 18-MAY-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 85751075.86 | 3551.51 | 22-OCT-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210596E+10 | 24065.41 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.384234E+10 | 30755.28 | 18-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.466616E+10 | 30755.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.414661E+10 | 30736.99 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246744E+10 | 30736.99 | 12-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.766012E+09 | 26514.80 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147922E+09 | 8530.94 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 701047.17 | 724.98 | 18-MAY-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36223319.73 | 2552.58 | 30-OCT-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169422E+10 | 28580.01 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.329314E+10 | 30736.99 | 18-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.414661E+10 | 30736.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104394E+11 | 56420.07 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.679393E+10 | 56420.07 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.342153E+10 | 56420.07 | 05-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108728E+10 | 56420.07 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 53978055.18 | 7966.89 | 18-MAY-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 271335.33 | 452.23 | 28-SEP-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.738725E+09 | 36458.51 | 31-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.542376E+10 | 56420.07 | 11-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.888756E+10 | 56420.07 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.368464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104394E+11 | 56420.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.467676E+10 | 28933.08 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.289240E+10 | 28933.08 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117673E+10 | 28933.08 | 05-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.294601E+09 | 28933.08 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6516522.16 | 1973.22 | 18-MAY-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149829E+09 | 18664.82 | 31-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.217598E+10 | 28933.08 | 11-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.385072E+10 | 28933.08 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.467676E+10 | 28933.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.478143E+10 | 28799.78 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.298404E+10 | 28799.78 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125627E+10 | 28799.78 | 05-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.328797E+09 | 28799.78 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8480837.38 | 1951.18 | 18-MAY-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173212E+09 | 20776.43 | 31-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.225217E+10 | 28799.78 | 11-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.395288E+10 | 28799.78 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.478143E+10 | 28799.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.520194E+10 | 28634.59 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.333901E+10 | 28634.59 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157642E+10 | 28634.59 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.480599E+09 | 28634.59 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21756750.26 | 6226.81 | 29-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.282805E+09 | 28634.59 | 29-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.254355E+10 | 28634.59 | 10-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.434490E+10 | 28634.59 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.520194E+10 | 28634.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.688832E+10 | 29994.01 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.464307E+10 | 29994.01 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.265355E+10 | 29994.01 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101728E+10 | 29994.01 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169735E+09 | 29590.39 | 29-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1232450.82 | 1788.63 | 15-JUN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9699934.83 | 7492.46 | 28-SEP-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.695416E+09 | 29994.01 | 16-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.352624E+10 | 29994.01 | 01-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.581136E+10 | 29994.01 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.254159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.688832E+10 | 29994.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1495970.40 | 1495970.40 | 835.95 | 18-MAR-16:10 | 835.95 | 0.00 |
April | 0.00 | 0.00 | 0.895161E+09 | 0.855551E+09 | 14145.74 | 27-APR-16:10 | 13554.21 | 0.00 |
May | 0.00 | 0.00 | 0.204088E+10 | 0.180680E+10 | 13140.11 | 06-MAY-13:00 | 10615.15 | 0.00 |
June | 0.00 | 0.00 | 0.368321E+10 | 0.344020E+10 | 14720.90 | 28-JUN-17:00 | 14189.32 | 0.00 |
July | 0.00 | 0.00 | 0.869509E+10 | 0.747553E+10 | 29602.32 | 24-JUL-07:03 | 22862.23 | 0.00 |
August | 0.00 | 0.00 | 0.112353E+11 | 0.967084E+10 | 32408.57 | 10-AUG-07:03 | 23799.55 | 0.00 |
September | 0.00 | 0.00 | 0.371070E+10 | 0.302272E+10 | 15537.05 | 14-SEP-14:00 | 12674.32 | 0.00 |
October | 0.00 | 0.00 | 0.239675E+09 | 0.233810E+09 | 7977.75 | 04-OCT-15:00 | 7977.75 | 0.00 |
November | 0.00 | 0.00 | 48299650.70 | 35990564.26 | 4439.51 | 04-NOV-14:00 | 3369.95 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.305498E+11 | 0.265429E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.112353E+11 | 0.967084E+10 | 32408.57 | 23799.55 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 288007.43 | 263357.69 | 329.89 | 11-JAN-21:50 | 291.28 | 0.00 |
February | 0.00 | 0.00 | 5380831.87 | 5140192.64 | 1188.68 | 27-FEB-23:10 | 1062.30 | 0.00 |
March | 0.00 | 0.00 | 13736560.45 | 13558811.30 | 1444.34 | 02-MAR-21:17 | 1404.87 | 0.00 |
April | 0.00 | 0.00 | 0.663874E+09 | 0.632850E+09 | 18690.47 | 29-APR-18:02 | 14924.94 | 0.00 |
May | 0.00 | 0.00 | 0.144177E+10 | 0.127413E+10 | 19412.52 | 07-MAY-17:03 | 15251.26 | 0.00 |
June | 0.00 | 0.00 | 0.265351E+10 | 0.245307E+10 | 19148.00 | 11-JUN-18:03 | 15775.57 | 0.00 |
July | 0.00 | 0.00 | 0.566777E+10 | 0.484515E+10 | 19870.18 | 15-JUL-18:03 | 14271.28 | 0.00 |
August | 0.00 | 0.00 | 0.715779E+10 | 0.611650E+10 | 19745.30 | 26-AUG-18:03 | 12996.33 | 0.00 |
September | 0.00 | 0.00 | 0.258057E+10 | 0.209129E+10 | 19585.54 | 23-SEP-18:03 | 13616.37 | 0.00 |
October | 0.00 | 0.00 | 0.219522E+09 | 0.207674E+09 | 18724.12 | 01-OCT-17:10 | 13474.97 | 0.00 |
November | 0.00 | 0.00 | 53314373.20 | 40389834.83 | 3724.91 | 04-NOV-14:00 | 2845.85 | 0.00 |
December | 0.00 | 0.00 | 416133.64 | 394426.96 | 497.74 | 03-DEC-18:50 | 497.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.204580E+11 | 0.176804E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 288007.43 | 263357.69 | 329.89 | 291.28 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.715779E+10 | 0.611650E+10 | 19870.18 | 15775.57 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 111375.24 | 111375.24 | 184.41 | 27-FEB-15:00 | 184.41 | 0.00 |
March | 0.00 | 0.00 | 3655260.91 | 3655260.91 | 695.52 | 18-MAR-16:00 | 695.52 | 0.00 |
April | 0.00 | 0.00 | 0.436179E+09 | 0.417528E+09 | 7509.04 | 27-APR-15:00 | 7157.48 | 0.00 |
May | 0.00 | 0.00 | 0.969173E+09 | 0.861100E+09 | 7412.39 | 06-MAY-13:00 | 6014.86 | 0.00 |
June | 0.00 | 0.00 | 0.173091E+10 | 0.162650E+10 | 7471.63 | 28-JUN-17:00 | 7204.23 | 0.00 |
July | 0.00 | 0.00 | 0.379574E+10 | 0.328402E+10 | 19201.75 | 31-JUL-06:03 | 13784.86 | 0.00 |
August | 0.00 | 0.00 | 0.497933E+10 | 0.429678E+10 | 19363.39 | 25-AUG-06:03 | 13429.61 | 0.00 |
September | 0.00 | 0.00 | 0.176882E+10 | 0.144433E+10 | 8348.67 | 14-SEP-13:50 | 6689.73 | 0.00 |
October | 0.00 | 0.00 | 0.139403E+09 | 0.135918E+09 | 4361.85 | 04-OCT-15:00 | 4361.85 | 0.00 |
November | 0.00 | 0.00 | 35353428.49 | 26394957.83 | 3104.34 | 04-NOV-14:00 | 2366.16 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.138587E+11 | 0.120963E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.497933E+10 | 0.429678E+10 | 19363.39 | 13784.86 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 2274965.54 | 2274965.54 | 558.06 | 18-MAR-16:00 | 558.06 | 0.00 |
April | 0.00 | 0.00 | 0.421402E+09 | 0.403237E+09 | 7394.59 | 27-APR-15:00 | 7046.17 | 0.00 |
May | 0.00 | 0.00 | 0.944321E+09 | 0.839195E+09 | 7372.11 | 06-MAY-13:00 | 5981.10 | 0.00 |
June | 0.00 | 0.00 | 0.169872E+10 | 0.159642E+10 | 7441.34 | 28-JUN-17:00 | 7175.06 | 0.00 |
July | 0.00 | 0.00 | 0.376753E+10 | 0.325934E+10 | 19247.50 | 31-JUL-06:03 | 13823.94 | 0.00 |
August | 0.00 | 0.00 | 0.496229E+10 | 0.428193E+10 | 19409.44 | 25-AUG-06:03 | 13466.41 | 0.00 |
September | 0.00 | 0.00 | 0.174389E+10 | 0.142372E+10 | 8330.13 | 14-SEP-13:50 | 6674.74 | 0.00 |
October | 0.00 | 0.00 | 0.130753E+09 | 0.127690E+09 | 4282.89 | 04-OCT-15:00 | 4282.89 | 0.00 |
November | 0.00 | 0.00 | 31071508.67 | 23208887.53 | 2843.67 | 04-NOV-14:00 | 2165.55 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.137023E+11 | 0.119570E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.496229E+10 | 0.428193E+10 | 19409.44 | 13823.94 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 14.86 | 14.86 | 0.02 | 27-FEB-16:50 | 0.02 | 0.00 |
March | 0.00 | 0.00 | 65009.41 | 65009.41 | 105.14 | 18-MAR-16:00 | 105.14 | 0.00 |
April | 0.00 | 0.00 | 0.421953E+09 | 0.413342E+09 | 7715.12 | 27-APR-15:00 | 7573.01 | 0.00 |
May | 0.00 | 0.00 | 0.863327E+09 | 0.794228E+09 | 7733.87 | 06-MAY-13:00 | 6546.56 | 0.00 |
June | 0.00 | 0.00 | 0.149478E+10 | 0.145340E+10 | 7769.96 | 28-JUN-17:00 | 7769.96 | 0.00 |
July | 0.00 | 0.00 | 0.348741E+10 | 0.315078E+10 | 17826.66 | 31-JUL-06:03 | 12789.97 | 0.00 |
August | 0.00 | 0.00 | 0.477400E+10 | 0.430151E+10 | 19109.75 | 10-AUG-06:02 | 13165.13 | 0.00 |
September | 0.00 | 0.00 | 0.150479E+10 | 0.129126E+10 | 8737.52 | 14-SEP-14:00 | 7434.81 | 0.00 |
October | 0.00 | 0.00 | 83424167.87 | 82818341.46 | 4180.22 | 04-OCT-15:00 | 4180.22 | 0.00 |
November | 0.00 | 0.00 | 20441779.66 | 16092143.40 | 2287.90 | 04-NOV-14:00 | 1825.39 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.126502E+11 | 0.115035E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.477400E+10 | 0.430151E+10 | 19109.75 | 13165.13 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 611869.65 | 611869.65 | 450.10 | 18-MAR-16:00 | 450.10 | 0.00 |
April | 0.00 | 0.00 | 0.636792E+09 | 0.603745E+09 | 13048.99 | 27-APR-15:00 | 12118.60 | 0.00 |
May | 0.00 | 0.00 | 0.136579E+10 | 0.120916E+10 | 12299.78 | 06-MAY-13:30 | 9926.12 | 0.00 |
June | 0.00 | 0.00 | 0.259547E+10 | 0.243044E+10 | 12854.54 | 28-JUN-17:00 | 12215.58 | 0.00 |
July | 0.00 | 0.00 | 0.618687E+10 | 0.530890E+10 | 33784.37 | 31-JUL-07:03 | 24795.83 | 0.00 |
August | 0.00 | 0.00 | 0.834555E+10 | 0.715954E+10 | 33446.37 | 14-AUG-07:03 | 22748.98 | 0.00 |
September | 0.00 | 0.00 | 0.273633E+10 | 0.221919E+10 | 14709.14 | 14-SEP-14:10 | 11985.78 | 0.00 |
October | 0.00 | 0.00 | 0.169657E+09 | 0.166307E+09 | 7401.24 | 04-OCT-15:00 | 7401.24 | 0.00 |
November | 0.00 | 0.00 | 32852533.92 | 24385911.64 | 3734.67 | 04-NOV-14:40 | 2819.60 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.220699E+11 | 0.191223E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.834555E+10 | 0.715954E+10 | 33784.37 | 24795.83 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.355248E+09 | 0.346038E+09 | 7319.07 | 27-APR-15:00 | 7017.16 | 0.00 |
May | 0.00 | 0.00 | 0.696368E+09 | 0.639764E+09 | 6859.22 | 06-MAY-13:30 | 5785.64 | 0.00 |
June | 0.00 | 0.00 | 0.126674E+10 | 0.123117E+10 | 7101.98 | 28-JUN-17:00 | 6977.36 | 0.00 |
July | 0.00 | 0.00 | 0.309530E+10 | 0.277922E+10 | 15925.29 | 31-JUL-07:03 | 11742.40 | 0.00 |
August | 0.00 | 0.00 | 0.434130E+10 | 0.388607E+10 | 15706.21 | 14-AUG-07:03 | 10722.82 | 0.00 |
September | 0.00 | 0.00 | 0.129403E+10 | 0.110656E+10 | 8087.34 | 14-SEP-14:10 | 6878.93 | 0.00 |
October | 0.00 | 0.00 | 64357658.46 | 63965307.67 | 3954.88 | 04-OCT-15:00 | 3954.88 | 0.00 |
November | 0.00 | 0.00 | 13728331.01 | 10797265.14 | 1803.81 | 04-NOV-14:40 | 1437.34 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.111271E+11 | 0.100636E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.434130E+10 | 0.388607E+10 | 15925.29 | 11742.40 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.347649E+09 | 0.338635E+09 | 7226.24 | 27-APR-15:00 | 6926.95 | 0.00 |
May | 0.00 | 0.00 | 0.677539E+09 | 0.622472E+09 | 6770.25 | 06-MAY-13:30 | 5706.93 | 0.00 |
June | 0.00 | 0.00 | 0.123994E+10 | 0.120518E+10 | 7034.55 | 28-JUN-17:00 | 6910.57 | 0.00 |
July | 0.00 | 0.00 | 0.304669E+10 | 0.273549E+10 | 15019.10 | 24-JUL-07:03 | 11924.77 | 0.00 |
August | 0.00 | 0.00 | 0.428538E+10 | 0.383608E+10 | 14861.20 | 14-AUG-07:03 | 10151.86 | 0.00 |
September | 0.00 | 0.00 | 0.127147E+10 | 0.108717E+10 | 8009.92 | 14-SEP-14:10 | 6809.60 | 0.00 |
October | 0.00 | 0.00 | 61830030.33 | 61475017.40 | 3880.87 | 04-OCT-15:00 | 3880.87 | 0.00 |
November | 0.00 | 0.00 | 12898432.91 | 10146639.97 | 1734.30 | 04-NOV-14:40 | 1381.45 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.109434E+11 | 0.989664E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.428538E+10 | 0.383608E+10 | 15019.10 | 11924.77 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 24.88 | 24.88 | 0.04 | 27-FEB-14:50 | 0.04 | 0.00 |
March | 0.00 | 0.00 | 163.71 | 163.71 | 0.18 | 18-MAR-13:40 | 0.18 | 0.00 |
April | 0.00 | 0.00 | 0.323347E+09 | 0.315071E+09 | 6949.77 | 27-APR-15:00 | 6659.78 | 0.00 |
May | 0.00 | 0.00 | 0.618504E+09 | 0.568089E+09 | 6548.00 | 06-MAY-13:30 | 5511.94 | 0.00 |
June | 0.00 | 0.00 | 0.116635E+10 | 0.113402E+10 | 6901.54 | 28-JUN-17:00 | 6779.77 | 0.00 |
July | 0.00 | 0.00 | 0.292986E+10 | 0.263178E+10 | 12046.35 | 24-JUL-07:03 | 9626.90 | 0.00 |
August | 0.00 | 0.00 | 0.416501E+10 | 0.373005E+10 | 11876.90 | 14-AUG-07:03 | 8152.66 | 0.00 |
September | 0.00 | 0.00 | 0.121262E+10 | 0.103684E+10 | 7887.60 | 14-SEP-14:10 | 6700.86 | 0.00 |
October | 0.00 | 0.00 | 53540543.84 | 53345005.22 | 3640.48 | 04-OCT-15:00 | 3640.48 | 0.00 |
November | 0.00 | 0.00 | 9735278.25 | 7670115.98 | 1444.02 | 04-NOV-14:40 | 1149.26 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.104790E+11 | 0.947687E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.416501E+10 | 0.373005E+10 | 12046.35 | 9626.90 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 466.04 | 466.04 | 0.74 | 18-MAR-14:00 | 0.74 | 0.00 |
April | 0.00 | 0.00 | 0.302836E+09 | 0.295293E+09 | 6941.94 | 27-APR-15:00 | 6631.71 | 0.00 |
May | 0.00 | 0.00 | 0.556858E+09 | 0.511475E+09 | 6553.75 | 06-MAY-13:30 | 5503.03 | 0.00 |
June | 0.00 | 0.00 | 0.110586E+10 | 0.107423E+10 | 6963.66 | 28-JUN-15:00 | 6963.66 | 0.00 |
July | 0.00 | 0.00 | 0.288241E+10 | 0.259013E+10 | 10349.59 | 24-JUL-15:00 | 9873.55 | 0.00 |
August | 0.00 | 0.00 | 0.423965E+10 | 0.379539E+10 | 11180.47 | 29-AUG-14:50 | 9810.60 | 0.00 |
September | 0.00 | 0.00 | 0.118137E+10 | 0.100649E+10 | 8114.66 | 14-SEP-14:10 | 6883.78 | 0.00 |
October | 0.00 | 0.00 | 40966238.11 | 40965147.18 | 3143.70 | 04-OCT-15:00 | 3143.70 | 0.00 |
November | 0.00 | 0.00 | 5325863.53 | 4201776.34 | 970.57 | 04-NOV-14:40 | 770.13 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.103153E+11 | 0.931817E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.423965E+10 | 0.379539E+10 | 11180.47 | 9873.55 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.186907E+10 | 0.40 | 2214.66 | 01-JAN-08:61 | 0.89 |
February | 0.162639E+10 | 0.39 | 2214.66 | 01-FEB-08:61 | 0.89 |
March | 0.168936E+10 | 0.38 | 2214.66 | 06-MAR-08:61 | 0.89 |
April | 0.157692E+10 | 0.37 | 2214.66 | 01-APR-07:01 | 0.89 |
May | 0.160819E+10 | 0.36 | 1024.62 | 18-MAY-08:10 | 0.59 |
June | 0.156267E+10 | 0.37 | 885.87 | 10-JUN-21:40 | 0.54 |
July | 0.160867E+10 | 0.36 | 1751.52 | 24-JUL-07:03 | 0.79 |
August | 0.162102E+10 | 0.36 | 1926.54 | 10-AUG-07:03 | 0.83 |
September | 0.155948E+10 | 0.36 | 885.87 | 15-SEP-20:03 | 0.53 |
October | 0.161609E+10 | 0.37 | 1487.25 | 31-OCT-07:01 | 0.73 |
November | 0.167408E+10 | 0.38 | 2214.66 | 13-NOV-08:61 | 0.89 |
December | 0.183295E+10 | 0.40 | 2214.66 | 01-DEC-08:61 | 0.89 |
Annual Sum or Average | 0.198449E+11 | 0.38 | |||
Minimum of Months | 0.155948E+10 | 0.36 | 885.87 | 0.53 | |
Maximum of Months | 0.186907E+10 | 0.40 | 2214.66 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.749920E+09 | 0.31 | 1237.59 | 05-JAN-08:61 | 0.92 |
February | 0.661947E+09 | 0.32 | 1237.59 | 14-FEB-08:61 | 0.92 |
March | 0.722024E+09 | 0.35 | 864.93 | 25-MAR-07:01 | 0.78 |
April | 0.738010E+09 | 0.37 | 586.04 | 19-APR-08:10 | 0.62 |
May | 0.841498E+09 | 0.37 | 523.28 | 18-MAY-08:30 | 0.58 |
June | 0.832189E+09 | 0.37 | 495.03 | 19-JUN-17:20 | 0.56 |
July | 0.842748E+09 | 0.37 | 1219.51 | 24-JUL-07:03 | 0.91 |
August | 0.841058E+09 | 0.37 | 1237.59 | 10-AUG-07:03 | 0.91 |
September | 0.836662E+09 | 0.37 | 495.03 | 01-SEP-12:10 | 0.55 |
October | 0.785305E+09 | 0.37 | 533.71 | 30-OCT-08:30 | 0.58 |
November | 0.712611E+09 | 0.33 | 920.18 | 30-NOV-08:61 | 0.80 |
December | 0.730123E+09 | 0.31 | 1237.59 | 22-DEC-08:61 | 0.92 |
Annual Sum or Average | 0.929409E+10 | 0.35 | |||
Minimum of Months | 0.661947E+09 | 0.31 | 495.03 | 0.55 | |
Maximum of Months | 0.842748E+09 | 0.37 | 1237.59 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.819877E+09 | 0.33 | 1234.86 | 01-JAN-08:61 | 0.92 |
February | 0.711798E+09 | 0.32 | 1234.86 | 14-FEB-07:02 | 0.92 |
March | 0.751390E+09 | 0.31 | 881.76 | 06-MAR-07:02 | 0.78 |
April | 0.697986E+09 | 0.30 | 627.58 | 19-APR-07:02 | 0.65 |
May | 0.721999E+09 | 0.30 | 524.52 | 18-MAY-07:50 | 0.58 |
June | 0.704164E+09 | 0.31 | 493.94 | 02-JUN-11:40 | 0.56 |
July | 0.711829E+09 | 0.30 | 1234.86 | 31-JUL-06:03 | 0.91 |
August | 0.733572E+09 | 0.31 | 1234.86 | 10-AUG-06:02 | 0.91 |
September | 0.693495E+09 | 0.30 | 493.94 | 22-SEP-16:10 | 0.55 |
October | 0.716045E+09 | 0.30 | 571.47 | 30-OCT-07:09 | 0.61 |
November | 0.739280E+09 | 0.31 | 942.00 | 24-NOV-07:02 | 0.81 |
December | 0.797261E+09 | 0.32 | 1234.86 | 25-DEC-08:62 | 0.92 |
Annual Sum or Average | 0.879869E+10 | 0.31 | |||
Minimum of Months | 0.693495E+09 | 0.30 | 493.94 | 0.55 | |
Maximum of Months | 0.819877E+09 | 0.33 | 1234.86 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.829390E+09 | 0.33 | 1238.06 | 01-JAN-08:61 | 0.92 |
February | 0.718721E+09 | 0.32 | 1238.06 | 12-FEB-08:62 | 0.92 |
March | 0.757263E+09 | 0.31 | 1027.36 | 06-MAR-07:02 | 0.84 |
April | 0.701239E+09 | 0.30 | 699.69 | 18-APR-07:47 | 0.69 |
May | 0.723888E+09 | 0.30 | 533.06 | 18-MAY-07:35 | 0.58 |
June | 0.705991E+09 | 0.31 | 495.22 | 02-JUN-14:10 | 0.56 |
July | 0.713651E+09 | 0.30 | 1238.06 | 31-JUL-06:03 | 0.91 |
August | 0.735259E+09 | 0.31 | 1238.06 | 10-AUG-06:02 | 0.91 |
September | 0.695294E+09 | 0.30 | 495.22 | 26-SEP-06:50 | 0.55 |
October | 0.718759E+09 | 0.30 | 581.00 | 22-OCT-08:08 | 0.62 |
November | 0.746160E+09 | 0.32 | 1076.48 | 24-NOV-07:02 | 0.86 |
December | 0.805927E+09 | 0.32 | 1238.06 | 18-DEC-07:02 | 0.92 |
Annual Sum or Average | 0.885154E+10 | 0.31 | |||
Minimum of Months | 0.695294E+09 | 0.30 | 495.22 | 0.55 | |
Maximum of Months | 0.829390E+09 | 0.33 | 1238.06 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.177643E+10 | 0.50 | 1227.50 | 01-JAN-08:50 | 0.92 |
February | 0.160851E+10 | 0.50 | 1227.50 | 02-FEB-08:30 | 0.92 |
March | 0.181179E+10 | 0.51 | 1227.50 | 04-MAR-08:06 | 0.92 |
April | 0.172341E+10 | 0.50 | 1227.50 | 01-APR-08:00 | 0.92 |
May | 0.179411E+10 | 0.50 | 1227.50 | 01-MAY-06:10 | 0.92 |
June | 0.174992E+10 | 0.50 | 1227.50 | 19-JUN-06:40 | 0.92 |
July | 0.176760E+10 | 0.49 | 1227.50 | 02-JUL-12:30 | 0.92 |
August | 0.181179E+10 | 0.50 | 1227.50 | 08-AUG-06:50 | 0.91 |
September | 0.172341E+10 | 0.50 | 1227.50 | 20-SEP-11:10 | 0.91 |
October | 0.177643E+10 | 0.50 | 1227.50 | 01-OCT-07:20 | 0.91 |
November | 0.172341E+10 | 0.50 | 1227.50 | 04-NOV-13:50 | 0.91 |
December | 0.176760E+10 | 0.49 | 1227.50 | 01-DEC-08:08 | 0.92 |
Annual Sum or Average | 0.210344E+11 | 0.50 | |||
Minimum of Months | 0.160851E+10 | 0.49 | 1227.50 | 0.91 | |
Maximum of Months | 0.181179E+10 | 0.51 | 1227.50 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134815E+10 | 0.30 | 2089.32 | 01-JAN-09:01 | 0.89 |
February | 0.116185E+10 | 0.29 | 2089.32 | 01-FEB-08:61 | 0.89 |
March | 0.121629E+10 | 0.29 | 2089.32 | 05-MAR-09:01 | 0.89 |
April | 0.110726E+10 | 0.27 | 2089.32 | 01-APR-07:01 | 0.89 |
May | 0.112943E+10 | 0.27 | 1012.74 | 18-MAY-08:10 | 0.61 |
June | 0.110116E+10 | 0.27 | 835.73 | 25-JUN-11:30 | 0.54 |
July | 0.111171E+10 | 0.27 | 2062.24 | 24-JUL-07:03 | 0.88 |
August | 0.114806E+10 | 0.27 | 2046.39 | 14-AUG-07:03 | 0.87 |
September | 0.108311E+10 | 0.27 | 845.78 | 28-SEP-08:30 | 0.54 |
October | 0.113261E+10 | 0.27 | 1645.80 | 31-OCT-07:01 | 0.79 |
November | 0.120361E+10 | 0.29 | 2089.32 | 11-NOV-09:01 | 0.89 |
December | 0.130765E+10 | 0.30 | 2089.32 | 01-DEC-08:61 | 0.89 |
Annual Sum or Average | 0.140509E+11 | 0.28 | |||
Minimum of Months | 0.108311E+10 | 0.27 | 835.73 | 0.54 | |
Maximum of Months | 0.134815E+10 | 0.30 | 2089.32 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149833E+10 | 0.46 | 1121.84 | 02-JAN-10:20 | 0.92 |
February | 0.135698E+10 | 0.46 | 1121.84 | 01-FEB-12:50 | 0.92 |
March | 0.153064E+10 | 0.47 | 1121.84 | 13-MAR-13:40 | 0.92 |
April | 0.145390E+10 | 0.46 | 1121.84 | 06-APR-09:10 | 0.92 |
May | 0.151448E+10 | 0.46 | 1121.84 | 28-MAY-16:40 | 0.92 |
June | 0.147813E+10 | 0.47 | 1121.84 | 04-JUN-10:30 | 0.91 |
July | 0.149025E+10 | 0.45 | 1121.84 | 04-JUL-12:40 | 0.92 |
August | 0.153064E+10 | 0.47 | 1121.84 | 11-AUG-17:40 | 0.91 |
September | 0.145390E+10 | 0.46 | 1121.84 | 09-SEP-07:30 | 0.91 |
October | 0.149833E+10 | 0.46 | 1121.84 | 04-OCT-14:20 | 0.92 |
November | 0.145390E+10 | 0.46 | 1121.84 | 04-NOV-15:50 | 0.91 |
December | 0.149025E+10 | 0.46 | 1121.84 | 02-DEC-09:40 | 0.92 |
Annual Sum or Average | 0.177497E+11 | 0.46 | |||
Minimum of Months | 0.135698E+10 | 0.45 | 1121.84 | 0.91 | |
Maximum of Months | 0.153064E+10 | 0.47 | 1121.84 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149016E+10 | 0.46 | 1115.73 | 12-JAN-19:20 | 0.92 |
February | 0.134958E+10 | 0.46 | 1115.73 | 02-FEB-21:00 | 0.92 |
March | 0.152230E+10 | 0.47 | 1115.73 | 11-MAR-15:30 | 0.92 |
April | 0.144598E+10 | 0.46 | 1115.73 | 04-APR-08:40 | 0.92 |
May | 0.150623E+10 | 0.46 | 1115.73 | 01-MAY-07:05 | 0.92 |
June | 0.147008E+10 | 0.47 | 1115.73 | 10-JUN-09:30 | 0.91 |
July | 0.148213E+10 | 0.45 | 1115.73 | 22-JUL-07:50 | 0.92 |
August | 0.152230E+10 | 0.47 | 1115.73 | 01-AUG-07:03 | 0.91 |
September | 0.144598E+10 | 0.46 | 1115.73 | 01-SEP-07:03 | 0.91 |
October | 0.149016E+10 | 0.46 | 1115.73 | 17-OCT-10:00 | 0.92 |
November | 0.144598E+10 | 0.46 | 1115.73 | 09-NOV-18:30 | 0.92 |
December | 0.148213E+10 | 0.46 | 1115.73 | 01-DEC-14:10 | 0.92 |
Annual Sum or Average | 0.176530E+11 | 0.46 | |||
Minimum of Months | 0.134958E+10 | 0.45 | 1115.73 | 0.91 | |
Maximum of Months | 0.152230E+10 | 0.47 | 1115.73 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148103E+10 | 0.46 | 1108.89 | 03-JAN-08:07 | 0.92 |
February | 0.134131E+10 | 0.46 | 1108.89 | 01-FEB-09:30 | 0.92 |
March | 0.151297E+10 | 0.47 | 1108.89 | 01-MAR-08:15 | 0.92 |
April | 0.143712E+10 | 0.46 | 1108.89 | 01-APR-07:02 | 0.92 |
May | 0.149700E+10 | 0.46 | 1108.89 | 03-MAY-13:00 | 0.92 |
June | 0.146107E+10 | 0.47 | 1108.89 | 02-JUN-13:50 | 0.92 |
July | 0.147305E+10 | 0.45 | 1108.89 | 01-JUL-12:50 | 0.92 |
August | 0.151297E+10 | 0.47 | 1108.89 | 01-AUG-08:00 | 0.91 |
September | 0.143712E+10 | 0.46 | 1108.89 | 01-SEP-07:15 | 0.91 |
October | 0.148103E+10 | 0.46 | 1108.89 | 03-OCT-15:00 | 0.92 |
November | 0.143712E+10 | 0.46 | 1108.89 | 01-NOV-07:02 | 0.92 |
December | 0.147305E+10 | 0.46 | 1108.89 | 01-DEC-08:08 | 0.92 |
Annual Sum or Average | 0.175448E+11 | 0.46 | |||
Minimum of Months | 0.134131E+10 | 0.45 | 1108.89 | 0.91 | |
Maximum of Months | 0.151297E+10 | 0.47 | 1108.89 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158182E+10 | 0.46 | 1184.29 | 27-JAN-12:50 | 0.92 |
February | 0.143278E+10 | 0.46 | 1184.29 | 01-FEB-08:09 | 0.92 |
March | 0.161584E+10 | 0.47 | 1184.29 | 22-MAR-15:10 | 0.92 |
April | 0.153484E+10 | 0.46 | 1184.29 | 01-APR-07:10 | 0.92 |
May | 0.159879E+10 | 0.46 | 1184.29 | 01-MAY-08:15 | 0.92 |
June | 0.156042E+10 | 0.47 | 1184.29 | 02-JUN-19:15 | 0.92 |
July | 0.157321E+10 | 0.45 | 1184.29 | 01-JUL-14:30 | 0.91 |
August | 0.161584E+10 | 0.47 | 1184.29 | 01-AUG-15:10 | 0.91 |
September | 0.153484E+10 | 0.46 | 1184.29 | 02-SEP-12:20 | 0.91 |
October | 0.158174E+10 | 0.46 | 1184.29 | 02-OCT-08:30 | 0.92 |
November | 0.153484E+10 | 0.46 | 1184.29 | 01-NOV-07:10 | 0.92 |
December | 0.157321E+10 | 0.46 | 1184.29 | 22-DEC-19:00 | 0.92 |
Annual Sum or Average | 0.187382E+11 | 0.46 | |||
Minimum of Months | 0.143278E+10 | 0.45 | 1184.29 | 0.91 | |
Maximum of Months | 0.161584E+10 | 0.47 | 1184.29 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.186907E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.162639E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.168978E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.180721E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.212000E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.249236E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.374639E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.437144E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.246750E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.167801E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.168698E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.183295E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.273881E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.162639E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.437144E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.750001E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.663437E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.725822E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.902801E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.119272E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.148127E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.220233E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.255286E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.145215E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.840912E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.726469E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.730240E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.142210E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.663437E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.255286E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.819877E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.711830E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.752406E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.809090E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.964415E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.114087E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.164480E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.195067E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.112408E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.752051E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.748525E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.797261E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.122159E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.711830E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.195067E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.829390E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.718721E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.757898E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.808924E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.960585E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.113503E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.164037E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.194883E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.112011E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.752556E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.754341E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.805927E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.122327E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.718721E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.194883E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.177643E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.160851E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.181180E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.181776E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.198390E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.207981E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.251969E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.283415E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.204483E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.179524E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.172819E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.176760E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.237679E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.160851E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.283415E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.134815E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.116185E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.121646E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.127233E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.147570E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.176196E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.264340E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.319884E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.175234E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.117657E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.121242E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.130765E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.195277E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.116185E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.319884E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.149833E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.135698E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.153064E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.153401E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.166836E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.175939E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.216059E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.246322E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.173090E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.151281E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.145714E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.149025E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.201626E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.135698E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.246322E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.149016E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.134958E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.152230E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.152450E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.165615E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.174565E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.214245E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.244343E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.171836E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.150409E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.144903E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.148213E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.200278E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.134958E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.244343E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.148103E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.134131E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.151297E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.151062E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.163448E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.172099E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.210938E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.240952E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.169736E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.149313E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.143943E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.147305E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.198233E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.134131E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.240952E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.158182E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.143278E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.161584E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.160434E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.172367E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.180822E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.220119E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.252815E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.178966E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.159113E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.153612E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.157321E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.209861E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.143278E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.252815E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.186907E+10 | 0.00 | 0.116150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162639E+10 | 0.00 | 0.763827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168936E+10 | 1495970.40 | 0.336321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157692E+10 | 0.895161E+09 | 0.916961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160819E+10 | 0.204088E+10 | 38952614.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156267E+10 | 0.368321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160867E+10 | 0.869509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.162102E+10 | 0.112353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155948E+10 | 0.371070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161609E+10 | 0.239675E+09 | 0.389935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167408E+10 | 48299650.70 | 0.537482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183295E+10 | 0.00 | 0.973171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198449E+11 | 0.305498E+11 | 0.390689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.186907E+10 | 0.112353E+11 | 0.116150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.749920E+09 | 288007.43 | 0.324826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.661947E+09 | 5380831.87 | 0.188589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.722024E+09 | 13736560.45 | 0.442119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.738010E+09 | 0.640044E+09 | 56357510.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.841498E+09 | 0.139475E+10 | 1088271.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.832189E+09 | 0.254444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.842748E+09 | 0.541213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.841058E+09 | 0.680221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.836662E+09 | 0.247353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.785305E+09 | 0.215826E+09 | 6047054.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.712611E+09 | 53314373.20 | 0.121227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.730123E+09 | 416133.64 | 0.254392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.929409E+10 | 0.195561E+11 | 0.939595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.661947E+09 | 288007.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.842748E+09 | 0.680221E+10 | 0.324826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.819877E+09 | 0.00 | 0.438452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.711798E+09 | 111375.24 | 0.269375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.751390E+09 | 3655260.91 | 0.932103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.697986E+09 | 0.436179E+09 | 0.187454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.721999E+09 | 0.969173E+09 | 2220737.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.704164E+09 | 0.173091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.711829E+09 | 0.379574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.733572E+09 | 0.497933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.693495E+09 | 0.176882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.716045E+09 | 0.139403E+09 | 50575629.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.739280E+09 | 35353428.49 | 0.191106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.797261E+09 | 0.00 | 0.358897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.879869E+10 | 0.138587E+11 | 0.137506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.693495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.819877E+09 | 0.497933E+10 | 0.438452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.829390E+09 | 0.00 | 0.466616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.718721E+09 | 0.00 | 0.288905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.757263E+09 | 2274965.54 | 0.108939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.701239E+09 | 0.421402E+09 | 0.246108E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.723888E+09 | 0.944321E+09 | 2834866.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.705991E+09 | 0.169872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.713651E+09 | 0.376753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.735259E+09 | 0.496229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.695294E+09 | 0.174389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.718759E+09 | 0.130753E+09 | 85751075.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.746160E+09 | 31071508.67 | 0.210596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.805927E+09 | 0.00 | 0.384234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.885154E+10 | 0.137023E+11 | 0.149276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.695294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.829390E+09 | 0.496229E+10 | 0.466616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.177643E+10 | 0.00 | 0.414661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160851E+10 | 14.86 | 0.246744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181179E+10 | 65009.41 | 0.766012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172341E+10 | 0.421953E+09 | 0.147922E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179411E+10 | 0.863327E+09 | 701047.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174992E+10 | 0.149478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176760E+10 | 0.348741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181179E+10 | 0.477400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172341E+10 | 0.150479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177643E+10 | 83424167.87 | 36223319.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172341E+10 | 20441779.66 | 0.169422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176760E+10 | 0.00 | 0.329314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210344E+11 | 0.126502E+11 | 0.125523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181179E+10 | 0.477400E+10 | 0.414661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.134815E+10 | 0.00 | 0.104394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116185E+10 | 0.00 | 0.679393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121629E+10 | 611869.65 | 0.342153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110726E+10 | 0.636792E+09 | 0.108728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112943E+10 | 0.136579E+10 | 53978055.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110116E+10 | 0.259547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111171E+10 | 0.618687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.114806E+10 | 0.834555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108311E+10 | 0.273633E+10 | 271335.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113261E+10 | 0.169657E+09 | 0.738725E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120361E+10 | 32852533.92 | 0.542376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130765E+10 | 0.00 | 0.888756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140509E+11 | 0.220699E+11 | 0.368464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.108311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134815E+10 | 0.834555E+10 | 0.104394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149833E+10 | 0.00 | 0.467676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135698E+10 | 0.00 | 0.289240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153064E+10 | 0.00 | 0.117673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145390E+10 | 0.355248E+09 | 0.294601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151448E+10 | 0.696368E+09 | 6516522.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147813E+10 | 0.126674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149025E+10 | 0.309530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153064E+10 | 0.434130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145390E+10 | 0.129403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149833E+10 | 64357658.46 | 0.149829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145390E+10 | 13728331.01 | 0.217598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149025E+10 | 0.00 | 0.385072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177497E+11 | 0.111271E+11 | 0.152235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153064E+10 | 0.434130E+10 | 0.467676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149016E+10 | 0.00 | 0.478143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134958E+10 | 0.00 | 0.298404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152230E+10 | 0.00 | 0.125627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144598E+10 | 0.347649E+09 | 0.328797E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150623E+10 | 0.677539E+09 | 8480837.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147008E+10 | 0.123994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148213E+10 | 0.304669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152230E+10 | 0.428538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144598E+10 | 0.127147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149016E+10 | 61830030.33 | 0.173212E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144598E+10 | 12898432.91 | 0.225217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148213E+10 | 0.00 | 0.395288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176530E+11 | 0.109434E+11 | 0.157373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152230E+10 | 0.428538E+10 | 0.478143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148103E+10 | 0.00 | 0.520194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134131E+10 | 24.88 | 0.333901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151297E+10 | 163.71 | 0.157642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143712E+10 | 0.323347E+09 | 0.480599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149700E+10 | 0.618504E+09 | 21756750.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146107E+10 | 0.116635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147305E+10 | 0.292986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151297E+10 | 0.416501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143712E+10 | 0.121262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148103E+10 | 53540543.84 | 0.282805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143712E+10 | 9735278.25 | 0.254355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147305E+10 | 0.00 | 0.434490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175448E+11 | 0.104790E+11 | 0.177910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151297E+10 | 0.416501E+10 | 0.520194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158182E+10 | 0.00 | 0.688832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143278E+10 | 0.00 | 0.464307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161584E+10 | 466.04 | 0.265355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153484E+10 | 0.302836E+09 | 0.101728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159879E+10 | 0.556858E+09 | 0.169735E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156042E+10 | 0.110586E+10 | 1232450.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157321E+10 | 0.288241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161584E+10 | 0.423965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153484E+10 | 0.118137E+10 | 9699934.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158174E+10 | 40966238.11 | 0.695416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153484E+10 | 5325863.53 | 0.352624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157321E+10 | 0.00 | 0.581136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187382E+11 | 0.103153E+11 | 0.254159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161584E+10 | 0.423965E+10 | 0.688832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.186907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168936E+10 | 0.00 | 0.00 | 0.00 | 418429.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157692E+10 | 0.00 | 0.00 | 0.00 | 0.230288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160819E+10 | 0.00 | 0.00 | 0.00 | 0.511812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156267E+10 | 0.00 | 0.00 | 0.00 | 0.929691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160867E+10 | 0.00 | 0.00 | 0.00 | 0.213772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.162102E+10 | 0.00 | 0.00 | 0.00 | 0.275042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155948E+10 | 0.00 | 0.00 | 0.00 | 0.908022E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161609E+10 | 0.00 | 0.00 | 0.00 | 61927331.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167408E+10 | 0.00 | 0.00 | 0.00 | 12898751.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198449E+11 | 0.00 | 0.00 | 0.00 | 0.754320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.186907E+10 | 0.00 | 0.00 | 0.00 | 0.275042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.749920E+09 | 0.00 | 0.00 | 0.00 | 81062.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.661947E+09 | 0.00 | 0.00 | 0.00 | 1489585.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.722024E+09 | 0.00 | 0.00 | 0.00 | 3797850.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.738010E+09 | 0.00 | 0.00 | 0.00 | 0.164791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.841498E+09 | 0.00 | 0.00 | 0.00 | 0.351223E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.832189E+09 | 0.00 | 0.00 | 0.00 | 0.649077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.842748E+09 | 0.00 | 0.00 | 0.00 | 0.135959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.841058E+09 | 0.00 | 0.00 | 0.00 | 0.171180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.836662E+09 | 0.00 | 0.00 | 0.00 | 0.615486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.785305E+09 | 0.00 | 0.00 | 0.00 | 55607017.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.712611E+09 | 0.00 | 0.00 | 0.00 | 13858138.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.730123E+09 | 0.00 | 0.00 | 0.00 | 116845.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.929409E+10 | 0.00 | 0.00 | 0.00 | 0.492692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.661947E+09 | 0.00 | 0.00 | 0.00 | 81062.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.842748E+09 | 0.00 | 0.00 | 0.00 | 0.171180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.819877E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.711798E+09 | 0.00 | 0.00 | 0.00 | 31294.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.751390E+09 | 0.00 | 0.00 | 0.00 | 1016716.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.697986E+09 | 0.00 | 0.00 | 0.00 | 0.111104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.721999E+09 | 0.00 | 0.00 | 0.00 | 0.242416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.704164E+09 | 0.00 | 0.00 | 0.00 | 0.436702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.711829E+09 | 0.00 | 0.00 | 0.00 | 0.932968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.733572E+09 | 0.00 | 0.00 | 0.00 | 0.121710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.693495E+09 | 0.00 | 0.00 | 0.00 | 0.430587E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.716045E+09 | 0.00 | 0.00 | 0.00 | 36006429.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.739280E+09 | 0.00 | 0.00 | 0.00 | 9245407.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.797261E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.879869E+10 | 0.00 | 0.00 | 0.00 | 0.341717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.693495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.819877E+09 | 0.00 | 0.00 | 0.00 | 0.121710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.829390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.718721E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.757263E+09 | 0.00 | 0.00 | 0.00 | 635210.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.701239E+09 | 0.00 | 0.00 | 0.00 | 0.107686E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.723888E+09 | 0.00 | 0.00 | 0.00 | 0.236697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.705991E+09 | 0.00 | 0.00 | 0.00 | 0.429043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.713651E+09 | 0.00 | 0.00 | 0.00 | 0.926719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.735259E+09 | 0.00 | 0.00 | 0.00 | 0.121357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.695294E+09 | 0.00 | 0.00 | 0.00 | 0.424814E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.718759E+09 | 0.00 | 0.00 | 0.00 | 33797213.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.746160E+09 | 0.00 | 0.00 | 0.00 | 8181156.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.805927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.885154E+10 | 0.00 | 0.00 | 0.00 | 0.338115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.695294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.829390E+09 | 0.00 | 0.00 | 0.00 | 0.121357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.177643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160851E+10 | 0.00 | 0.00 | 0.00 | 3.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181179E+10 | 0.00 | 0.00 | 0.00 | 15966.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172341E+10 | 0.00 | 0.00 | 0.00 | 94353883.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179411E+10 | 0.00 | 0.00 | 0.00 | 0.189786E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174992E+10 | 0.00 | 0.00 | 0.00 | 0.329889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176760E+10 | 0.00 | 0.00 | 0.00 | 0.752091E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181179E+10 | 0.00 | 0.00 | 0.00 | 0.102237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172341E+10 | 0.00 | 0.00 | 0.00 | 0.321427E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177643E+10 | 0.00 | 0.00 | 0.00 | 18805470.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172341E+10 | 0.00 | 0.00 | 0.00 | 4780560.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210344E+11 | 0.00 | 0.00 | 0.00 | 0.273351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181179E+10 | 0.00 | 0.00 | 0.00 | 0.102237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.134815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121629E+10 | 0.00 | 0.00 | 0.00 | 171741.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110726E+10 | 0.00 | 0.00 | 0.00 | 0.165069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112943E+10 | 0.00 | 0.00 | 0.00 | 0.346265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110116E+10 | 0.00 | 0.00 | 0.00 | 0.660806E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111171E+10 | 0.00 | 0.00 | 0.00 | 0.153169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.114806E+10 | 0.00 | 0.00 | 0.00 | 0.205078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108311E+10 | 0.00 | 0.00 | 0.00 | 0.669231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113261E+10 | 0.00 | 0.00 | 0.00 | 43954250.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120361E+10 | 0.00 | 0.00 | 0.00 | 8810525.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140509E+11 | 0.00 | 0.00 | 0.00 | 0.547678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.108311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134815E+10 | 0.00 | 0.00 | 0.00 | 0.205078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145390E+10 | 0.00 | 0.00 | 0.00 | 80109939.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151448E+10 | 0.00 | 0.00 | 0.00 | 0.153882E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147813E+10 | 0.00 | 0.00 | 0.00 | 0.281257E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149025E+10 | 0.00 | 0.00 | 0.00 | 0.670342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153064E+10 | 0.00 | 0.00 | 0.00 | 0.932580E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145390E+10 | 0.00 | 0.00 | 0.00 | 0.277002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149833E+10 | 0.00 | 0.00 | 0.00 | 14487937.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145390E+10 | 0.00 | 0.00 | 0.00 | 3236424.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177497E+11 | 0.00 | 0.00 | 0.00 | 0.241290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153064E+10 | 0.00 | 0.00 | 0.00 | 0.932580E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144598E+10 | 0.00 | 0.00 | 0.00 | 78518669.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150623E+10 | 0.00 | 0.00 | 0.00 | 0.149920E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147008E+10 | 0.00 | 0.00 | 0.00 | 0.275565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148213E+10 | 0.00 | 0.00 | 0.00 | 0.660320E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152230E+10 | 0.00 | 0.00 | 0.00 | 0.921137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144598E+10 | 0.00 | 0.00 | 0.00 | 0.272381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149016E+10 | 0.00 | 0.00 | 0.00 | 13930527.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144598E+10 | 0.00 | 0.00 | 0.00 | 3045945.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176530E+11 | 0.00 | 0.00 | 0.00 | 0.237482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152230E+10 | 0.00 | 0.00 | 0.00 | 0.921137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.148103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134131E+10 | 0.00 | 0.00 | 0.00 | 6.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151297E+10 | 0.00 | 0.00 | 0.00 | 40.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143712E+10 | 0.00 | 0.00 | 0.00 | 73497774.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149700E+10 | 0.00 | 0.00 | 0.00 | 0.137484E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146107E+10 | 0.00 | 0.00 | 0.00 | 0.259923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147305E+10 | 0.00 | 0.00 | 0.00 | 0.636329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151297E+10 | 0.00 | 0.00 | 0.00 | 0.896551E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143712E+10 | 0.00 | 0.00 | 0.00 | 0.260241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148103E+10 | 0.00 | 0.00 | 0.00 | 12101801.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143712E+10 | 0.00 | 0.00 | 0.00 | 2316103.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175448E+11 | 0.00 | 0.00 | 0.00 | 0.227844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151297E+10 | 0.00 | 0.00 | 0.00 | 0.896551E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.158182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161584E+10 | 0.00 | 0.00 | 0.00 | 115.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153484E+10 | 0.00 | 0.00 | 0.00 | 69506066.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159879E+10 | 0.00 | 0.00 | 0.00 | 0.124876E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156042E+10 | 0.00 | 0.00 | 0.00 | 0.247804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157321E+10 | 0.00 | 0.00 | 0.00 | 0.627977E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161584E+10 | 0.00 | 0.00 | 0.00 | 0.912305E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153484E+10 | 0.00 | 0.00 | 0.00 | 0.254825E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158174E+10 | 0.00 | 0.00 | 0.00 | 9396957.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153484E+10 | 0.00 | 0.00 | 0.00 | 1284101.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187382E+11 | 0.00 | 0.00 | 0.00 | 0.224797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161584E+10 | 0.00 | 0.00 | 0.00 | 0.912305E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.780658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648750E+10 | 0.00 | 0.00 | 0.53 |
February | 0.844395E+10 | 0.00 | 0.00 | 109624.64 | 0.00 | 0.327740E+10 | 0.106091E+09 | 0.00 | 0.53 |
March | 0.981009E+10 | 0.00 | 0.00 | 205676.12 | 0.00 | 0.849193E+09 | 0.230847E+09 | 0.00 | 0.54 |
April | 0.753338E+10 | 27756818.00 | 0.00 | 3456276.64 | 0.00 | 0.119313E+09 | 0.166974E+10 | 0.00 | 0.59 |
May | 0.458433E+10 | 19227667.31 | 0.00 | 10000660.85 | 0.00 | 0.00 | 0.482934E+10 | 0.00 | 0.72 |
June | 0.134252E+10 | 24275983.17 | 0.00 | 18578435.48 | 0.00 | 0.00 | 0.763697E+10 | 0.00 | 0.91 |
July | 0.275179E+09 | 0.379075E+09 | 0.00 | 22926694.78 | 0.00 | 0.00 | 0.717601E+10 | 0.00 | 1.01 |
August | 0.252719E+09 | 0.835261E+09 | 0.00 | 20675688.35 | 0.00 | 0.00 | 0.576554E+10 | 0.00 | 0.97 |
September | 0.183338E+10 | 49819721.90 | 0.00 | 16313644.64 | 0.00 | 0.00 | 0.736748E+10 | 0.00 | 0.88 |
October | 0.681189E+10 | 0.00 | 0.00 | 4589056.31 | 0.00 | 10755300.14 | 0.348184E+10 | 0.00 | 0.62 |
November | 0.887537E+10 | 0.00 | 0.00 | 464878.72 | 0.00 | 0.211429E+10 | 0.423052E+09 | 0.00 | 0.54 |
December | 0.873945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481989E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.663088E+11 | 0.133542E+10 | 0.00 | 97320636.53 | 0.00 | 0.176784E+11 | 0.386869E+11 | 0.00 | 0.70 |
Minimum of Months | 0.252719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.981009E+10 | 0.835261E+09 | 0.00 | 22926694.78 | 0.00 | 0.648750E+10 | 0.763697E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.380410E+10 | 0.00 | 0.00 | 5376.46 | 0.00 | 0.142329E+10 | 4206128.49 | 0.00 | 0.39 |
February | 0.339883E+10 | 0.00 | 0.00 | 232412.17 | 0.00 | 0.829992E+09 | 0.182116E+09 | 0.00 | 0.40 |
March | 0.396282E+10 | 0.00 | 0.00 | 553755.48 | 0.00 | 3918716.09 | 0.442739E+09 | 0.00 | 0.43 |
April | 0.243285E+10 | 14440036.35 | 0.00 | 3022680.14 | 0.00 | 2546908.39 | 0.187911E+10 | 0.00 | 0.54 |
May | 0.968735E+09 | 11725423.17 | 0.00 | 7393907.11 | 0.00 | 0.00 | 0.406666E+10 | 0.00 | 0.76 |
June | 0.206103E+09 | 12818067.19 | 0.00 | 10899006.64 | 0.00 | 0.00 | 0.468391E+10 | 0.00 | 0.98 |
July | 25565787.75 | 0.199541E+09 | 0.00 | 11489104.03 | 0.00 | 0.00 | 0.371247E+10 | 0.00 | 1.02 |
August | 36183892.54 | 0.440257E+09 | 0.00 | 9739686.98 | 0.00 | 0.00 | 0.291941E+10 | 0.00 | 0.95 |
September | 0.419698E+09 | 31157938.71 | 0.00 | 9599120.14 | 0.00 | 0.00 | 0.453560E+10 | 0.00 | 0.94 |
October | 0.218202E+10 | 0.00 | 0.00 | 4097203.28 | 0.00 | 0.00 | 0.298642E+10 | 0.00 | 0.61 |
November | 0.390886E+10 | 0.00 | 0.00 | 606747.01 | 0.00 | 0.158962E+09 | 0.469145E+09 | 0.00 | 0.43 |
December | 0.384345E+10 | 0.00 | 0.00 | 24603.10 | 0.00 | 0.107410E+10 | 20171027.07 | 0.00 | 0.38 |
Annual Sum or Average | 0.251892E+11 | 0.709939E+09 | 0.00 | 57663602.55 | 0.00 | 0.349281E+10 | 0.259020E+11 | 0.00 | 0.65 |
Minimum of Months | 25565787.75 | 0.00 | 0.00 | 5376.46 | 0.00 | 0.00 | 4206128.49 | 0.00 | 0.38 |
Maximum of Months | 0.396282E+10 | 0.440257E+09 | 0.00 | 11489104.03 | 0.00 | 0.142329E+10 | 0.468391E+10 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.296132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246245E+10 | 0.00 | 0.00 | 0.41 |
February | 0.316739E+10 | 0.00 | 0.00 | 65673.69 | 0.00 | 0.122266E+10 | 57576091.64 | 0.00 | 0.42 |
March | 0.397016E+10 | 0.00 | 0.00 | 85168.44 | 0.00 | 0.190342E+09 | 85611450.64 | 0.00 | 0.43 |
April | 0.287691E+10 | 14894363.78 | 0.00 | 1011231.41 | 0.00 | 14047983.38 | 0.654411E+09 | 0.00 | 0.47 |
May | 0.159554E+10 | 11441886.40 | 0.00 | 3506470.73 | 0.00 | 0.00 | 0.209535E+10 | 0.00 | 0.60 |
June | 0.544467E+09 | 13697010.82 | 0.00 | 5939897.66 | 52384.72 | 0.00 | 0.301515E+10 | 0.00 | 0.77 |
July | 0.189645E+09 | 0.182664E+09 | 0.00 | 6272157.96 | 4252184.41 | 0.00 | 0.249960E+10 | 0.00 | 0.81 |
August | 0.198419E+09 | 0.412459E+09 | 0.00 | 5372072.08 | 7026046.23 | 0.00 | 0.210785E+10 | 0.00 | 0.78 |
September | 0.805384E+09 | 31120089.67 | 0.00 | 5030704.85 | 0.00 | 0.00 | 0.267724E+10 | 0.00 | 0.72 |
October | 0.266697E+10 | 0.00 | 0.00 | 1840421.81 | 0.00 | 286910.37 | 0.137140E+10 | 0.00 | 0.51 |
November | 0.348007E+10 | 0.00 | 0.00 | 141945.69 | 0.00 | 0.771379E+09 | 93931004.81 | 0.00 | 0.43 |
December | 0.305022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203355E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.255065E+11 | 0.666276E+09 | 0.00 | 29265744.31 | 11330615.35 | 0.669471E+10 | 0.146581E+11 | 0.00 | 0.56 |
Minimum of Months | 0.189645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.397016E+10 | 0.412459E+09 | 0.00 | 6272157.96 | 7026046.23 | 0.246245E+10 | 0.301515E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.263468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278829E+10 | 0.00 | 0.00 | 0.41 |
February | 0.305317E+10 | 0.00 | 0.00 | 52022.18 | 0.00 | 0.133028E+10 | 51191651.34 | 0.00 | 0.42 |
March | 0.387901E+10 | 0.00 | 0.00 | 73130.04 | 0.00 | 0.264618E+09 | 79556521.30 | 0.00 | 0.43 |
April | 0.288984E+10 | 14843021.14 | 0.00 | 930047.61 | 0.00 | 35067769.77 | 0.578748E+09 | 0.00 | 0.47 |
May | 0.165680E+10 | 11310279.00 | 0.00 | 3336047.46 | 0.00 | 0.00 | 0.198375E+10 | 0.00 | 0.59 |
June | 0.561298E+09 | 13675034.36 | 0.00 | 5825881.74 | 52234.19 | 0.00 | 0.297658E+10 | 0.00 | 0.77 |
July | 0.202266E+09 | 0.182500E+09 | 0.00 | 6217984.93 | 4250586.99 | 0.00 | 0.248471E+10 | 0.00 | 0.81 |
August | 0.206012E+09 | 0.412381E+09 | 0.00 | 5353058.94 | 7022173.77 | 0.00 | 0.210237E+10 | 0.00 | 0.78 |
September | 0.830623E+09 | 30673150.34 | 0.00 | 4920126.64 | 0.00 | 0.00 | 0.262409E+10 | 0.00 | 0.72 |
October | 0.269116E+10 | 0.00 | 0.00 | 1745569.48 | 0.00 | 5763132.95 | 0.128677E+10 | 0.00 | 0.50 |
November | 0.329503E+10 | 0.00 | 0.00 | 124894.84 | 0.00 | 0.957245E+09 | 78087593.34 | 0.00 | 0.42 |
December | 0.286139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222053E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.247613E+11 | 0.665383E+09 | 0.00 | 28578763.85 | 11324994.95 | 0.760180E+10 | 0.142459E+11 | 0.00 | 0.56 |
Minimum of Months | 0.202266E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.387901E+10 | 0.412381E+09 | 0.00 | 6217984.93 | 7022173.77 | 0.278829E+10 | 0.297658E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.219330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322954E+10 | 0.00 | 0.00 | 0.41 |
February | 0.283530E+10 | 0.00 | 0.00 | 48035.75 | 0.00 | 0.156258E+10 | 62952947.88 | 0.00 | 0.42 |
March | 0.389120E+10 | 0.00 | 0.00 | 74021.24 | 0.00 | 0.297190E+09 | 0.108080E+09 | 0.00 | 0.43 |
April | 0.281304E+10 | 13354677.21 | 0.00 | 950578.54 | 0.00 | 44020654.82 | 0.847167E+09 | 0.00 | 0.50 |
May | 0.151951E+10 | 7887407.43 | 0.00 | 3384754.25 | 0.00 | 0.00 | 0.264817E+10 | 0.00 | 0.72 |
June | 0.466659E+09 | 12451567.64 | 0.00 | 5757500.22 | 15617.04 | 0.00 | 0.393160E+10 | 0.00 | 1.00 |
July | 0.187933E+09 | 0.153119E+09 | 0.00 | 6270388.87 | 2784742.38 | 0.00 | 0.346569E+10 | 0.00 | 1.09 |
August | 0.180787E+09 | 0.357830E+09 | 0.00 | 5408927.59 | 4882610.94 | 0.00 | 0.299440E+10 | 0.00 | 1.03 |
September | 0.767919E+09 | 15771107.37 | 0.00 | 5155470.62 | 0.00 | 0.00 | 0.349685E+10 | 0.00 | 0.92 |
October | 0.267068E+10 | 0.00 | 0.00 | 1730986.75 | 0.00 | 1310314.52 | 0.164851E+10 | 0.00 | 0.55 |
November | 0.309226E+10 | 0.00 | 0.00 | 122050.34 | 0.00 | 0.117730E+10 | 0.117023E+09 | 0.00 | 0.43 |
December | 0.262054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246389E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.232391E+11 | 0.560413E+09 | 0.00 | 28902714.16 | 7682970.36 | 0.877584E+10 | 0.193205E+11 | 0.00 | 0.66 |
Minimum of Months | 0.180787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.389120E+10 | 0.357830E+09 | 0.00 | 6270388.87 | 4882610.94 | 0.322954E+10 | 0.393160E+10 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.257843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758072E+10 | 0.00 | 0.00 | 0.38 |
February | 0.445904E+10 | 0.00 | 0.00 | 21230.62 | 0.00 | 0.376470E+10 | 29313441.00 | 0.00 | 0.38 |
March | 0.661401E+10 | 0.00 | 0.00 | 59994.62 | 0.00 | 0.105404E+10 | 80327481.90 | 0.00 | 0.39 |
April | 0.540542E+10 | 17251739.54 | 0.00 | 1109680.43 | 0.00 | 0.128922E+09 | 0.631818E+09 | 0.00 | 0.41 |
May | 0.391814E+10 | 7267139.00 | 0.00 | 3733651.76 | 0.00 | 1541190.81 | 0.216636E+10 | 0.00 | 0.49 |
June | 0.140914E+10 | 13633103.45 | 0.00 | 8175652.78 | 16466.45 | 0.00 | 0.437635E+10 | 0.00 | 0.62 |
July | 0.371258E+09 | 0.278998E+09 | 0.00 | 9707939.51 | 3737578.11 | 0.00 | 0.402973E+10 | 0.00 | 0.67 |
August | 0.284934E+09 | 0.667040E+09 | 0.00 | 8163554.47 | 3330753.77 | 0.00 | 0.341063E+10 | 0.00 | 0.65 |
September | 0.204794E+10 | 16203503.99 | 0.00 | 7149980.00 | 0.00 | 0.00 | 0.362352E+10 | 0.00 | 0.58 |
October | 0.520913E+10 | 0.00 | 0.00 | 1933530.28 | 0.00 | 36944716.23 | 0.157979E+10 | 0.00 | 0.43 |
November | 0.503154E+10 | 0.00 | 0.00 | 127414.09 | 0.00 | 0.294584E+10 | 95601999.69 | 0.00 | 0.39 |
December | 0.374585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.580097E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.410748E+11 | 0.100039E+10 | 0.00 | 40182628.56 | 7084798.34 | 0.213137E+11 | 0.200235E+11 | 0.00 | 0.48 |
Minimum of Months | 0.284934E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.661401E+10 | 0.667040E+09 | 0.00 | 9707939.51 | 3737578.11 | 0.758072E+10 | 0.437635E+10 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385926E+10 | 0.00 | 0.00 | 0.38 |
February | 0.193717E+10 | 0.00 | 0.00 | 16678.44 | 0.00 | 0.216013E+10 | 38109726.28 | 0.00 | 0.38 |
March | 0.322366E+10 | 0.00 | 0.00 | 34848.95 | 0.00 | 0.634260E+09 | 69789091.77 | 0.00 | 0.39 |
April | 0.269758E+10 | 7929616.90 | 0.00 | 633603.49 | 0.00 | 79471170.85 | 0.485728E+09 | 0.00 | 0.44 |
May | 0.170211E+10 | 2677381.46 | 0.00 | 2227765.32 | 0.00 | 0.00 | 0.182530E+10 | 0.00 | 0.60 |
June | 0.493853E+09 | 5949115.14 | 0.00 | 4442582.62 | 0.00 | 0.00 | 0.322184E+10 | 0.00 | 0.85 |
July | 0.126326E+09 | 0.120307E+09 | 0.00 | 5167278.34 | 1400480.01 | 0.00 | 0.297311E+10 | 0.00 | 0.95 |
August | 0.118333E+09 | 0.300127E+09 | 0.00 | 4446025.78 | 1262516.71 | 0.00 | 0.251253E+10 | 0.00 | 0.89 |
September | 0.834019E+09 | 4373796.05 | 0.00 | 4078247.59 | 0.00 | 0.00 | 0.278035E+10 | 0.00 | 0.78 |
October | 0.250189E+10 | 0.00 | 0.00 | 1151567.36 | 0.00 | 24050019.24 | 0.120866E+10 | 0.00 | 0.47 |
November | 0.230600E+10 | 0.00 | 0.00 | 74499.79 | 0.00 | 0.168547E+10 | 81981033.08 | 0.00 | 0.39 |
December | 0.171708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304468E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.188655E+11 | 0.441363E+09 | 0.00 | 22273097.68 | 2662996.71 | 0.114873E+11 | 0.151974E+11 | 0.00 | 0.58 |
Minimum of Months | 0.118333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.322366E+10 | 0.300127E+09 | 0.00 | 5167278.34 | 1400480.01 | 0.385926E+10 | 0.322184E+10 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394022E+10 | 0.00 | 0.00 | 0.38 |
February | 0.186930E+10 | 0.00 | 0.00 | 13573.51 | 0.00 | 0.222953E+10 | 33322843.04 | 0.00 | 0.38 |
March | 0.313880E+10 | 0.00 | 0.00 | 31057.56 | 0.00 | 0.716158E+09 | 64128820.53 | 0.00 | 0.39 |
April | 0.267415E+10 | 7907323.93 | 0.00 | 607023.77 | 0.00 | 0.100721E+09 | 0.467200E+09 | 0.00 | 0.44 |
May | 0.175518E+10 | 2602504.67 | 0.00 | 2122447.22 | 0.00 | 0.00 | 0.172834E+10 | 0.00 | 0.60 |
June | 0.547731E+09 | 5921818.55 | 0.00 | 4299848.94 | 0.00 | 0.00 | 0.311227E+10 | 0.00 | 0.84 |
July | 0.142989E+09 | 0.119640E+09 | 0.00 | 5034734.67 | 1405592.92 | 0.00 | 0.291507E+10 | 0.00 | 0.94 |
August | 0.128267E+09 | 0.298889E+09 | 0.00 | 4342007.42 | 1266137.97 | 0.00 | 0.247160E+10 | 0.00 | 0.88 |
September | 0.855518E+09 | 4240469.33 | 0.00 | 3964290.47 | 0.00 | 0.00 | 0.271456E+10 | 0.00 | 0.77 |
October | 0.250865E+10 | 0.00 | 0.00 | 1099948.26 | 0.00 | 30261182.43 | 0.116296E+10 | 0.00 | 0.47 |
November | 0.224640E+10 | 0.00 | 0.00 | 70871.12 | 0.00 | 0.174339E+10 | 79225265.59 | 0.00 | 0.39 |
December | 0.163522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312627E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.186284E+11 | 0.439201E+09 | 0.00 | 21585802.94 | 2671730.89 | 0.118866E+11 | 0.147487E+11 | 0.00 | 0.57 |
Minimum of Months | 0.128267E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.313880E+10 | 0.298889E+09 | 0.00 | 5034734.67 | 1405592.92 | 0.394022E+10 | 0.311227E+10 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.797501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426845E+10 | 0.00 | 0.00 | 0.38 |
February | 0.147351E+10 | 0.00 | 0.00 | 6908.03 | 0.00 | 0.262792E+10 | 19913036.09 | 0.00 | 0.38 |
March | 0.283529E+10 | 0.00 | 0.00 | 22933.26 | 0.00 | 0.100534E+10 | 46761178.51 | 0.00 | 0.39 |
April | 0.257151E+10 | 7852740.40 | 0.00 | 506059.96 | 0.00 | 0.198535E+09 | 0.397658E+09 | 0.00 | 0.43 |
May | 0.194877E+10 | 2404777.27 | 0.00 | 1745369.20 | 0.00 | 781557.31 | 0.136731E+10 | 0.00 | 0.58 |
June | 0.700397E+09 | 5877241.30 | 0.00 | 3824468.98 | 0.00 | 0.00 | 0.277323E+10 | 0.00 | 0.81 |
July | 0.205352E+09 | 0.118172E+09 | 0.00 | 4644387.42 | 1417695.99 | 0.00 | 0.272802E+10 | 0.00 | 0.91 |
August | 0.147844E+09 | 0.296561E+09 | 0.00 | 4034626.04 | 1277248.86 | 0.00 | 0.236017E+10 | 0.00 | 0.86 |
September | 0.997391E+09 | 3924809.89 | 0.00 | 3568079.88 | 0.00 | 0.00 | 0.240835E+10 | 0.00 | 0.74 |
October | 0.252567E+10 | 0.00 | 0.00 | 902930.01 | 0.00 | 82977558.42 | 0.968665E+09 | 0.00 | 0.46 |
November | 0.194887E+10 | 0.00 | 0.00 | 58522.76 | 0.00 | 0.203531E+10 | 68013745.36 | 0.00 | 0.39 |
December | 0.128637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347388E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.174385E+11 | 0.434792E+09 | 0.00 | 19314285.54 | 2694944.85 | 0.136932E+11 | 0.131381E+11 | 0.00 | 0.56 |
Minimum of Months | 0.147844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.283529E+10 | 0.296561E+09 | 0.00 | 4644387.42 | 1417695.99 | 0.426845E+10 | 0.277323E+10 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 33836834.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500982E+10 | 0.00 | 0.00 | 0.38 |
February | 0.527489E+09 | 0.00 | 0.00 | 327.73 | 0.00 | 0.355384E+10 | 4748660.00 | 0.00 | 0.38 |
March | 0.176837E+10 | 0.00 | 0.00 | 8987.96 | 0.00 | 0.201994E+10 | 33308575.11 | 0.00 | 0.39 |
April | 0.211480E+10 | 8160541.95 | 0.00 | 386693.28 | 0.00 | 0.650759E+09 | 0.296565E+09 | 0.00 | 0.43 |
May | 0.198350E+10 | 2432119.88 | 0.00 | 1341351.70 | 0.00 | 75066652.17 | 0.103916E+10 | 0.00 | 0.57 |
June | 0.866457E+09 | 6347680.48 | 0.00 | 3289111.57 | 0.00 | 0.00 | 0.240463E+10 | 0.00 | 0.79 |
July | 0.332592E+09 | 0.122394E+09 | 0.00 | 4112264.11 | 1445756.09 | 0.00 | 0.244045E+10 | 0.00 | 0.91 |
August | 0.217323E+09 | 0.309486E+09 | 0.00 | 3474090.56 | 1293310.05 | 0.00 | 0.215660E+10 | 0.00 | 0.85 |
September | 0.115840E+10 | 4076868.26 | 0.00 | 3101989.30 | 0.00 | 619002.43 | 0.202092E+10 | 0.00 | 0.73 |
October | 0.215638E+10 | 0.00 | 0.00 | 616503.98 | 0.00 | 0.489930E+09 | 0.730539E+09 | 0.00 | 0.44 |
November | 0.101227E+10 | 0.00 | 0.00 | 47703.53 | 0.00 | 0.293110E+10 | 62428892.73 | 0.00 | 0.39 |
December | 0.207540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453013E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.123790E+11 | 0.452897E+09 | 0.00 | 16379023.73 | 2739066.14 | 0.192612E+11 | 0.111893E+11 | 0.00 | 0.56 |
Minimum of Months | 33836834.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.215638E+10 | 0.309486E+09 | 0.00 | 4112264.11 | 1445756.09 | 0.500982E+10 | 0.244045E+10 | 0.00 | 0.91 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:34:37
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.446451E+11 | 0.295165E+11 | 0.00 | 0.687323E+11 | 0.150125E+11 |
February | 0.120219E+12 | 0.238168E+11 | 0.00 | 0.561435E+11 | 0.956372E+10 |
March | 0.235789E+12 | 0.217719E+11 | 0.00 | 0.522252E+11 | 0.419723E+10 |
April | 0.390751E+12 | 0.175501E+11 | 0.00 | 0.434044E+11 | 0.717020E+10 |
May | 0.529105E+12 | 0.153579E+11 | 0.00 | 0.454586E+11 | 0.126955E+11 |
June | 0.539250E+12 | 0.112517E+11 | 0.00 | 0.452715E+11 | 0.231356E+11 |
July | 0.573855E+12 | 0.652976E+10 | 0.00 | 0.347408E+11 | 0.537904E+11 |
August | 0.443382E+12 | 0.387551E+10 | 0.00 | 0.263215E+11 | 0.721142E+11 |
September | 0.302862E+12 | 0.108363E+11 | 0.00 | 0.447012E+11 | 0.234411E+11 |
October | 0.174884E+12 | 0.181577E+11 | 0.00 | 0.491593E+11 | 0.215527E+10 |
November | 0.598810E+11 | 0.232868E+11 | 0.00 | 0.546977E+11 | 0.738568E+10 |
December | 0.262913E+11 | 0.273004E+11 | 0.00 | 0.646348E+11 | 0.124624E+11 |
Annual Sum or Average | 0.344091E+13 | 0.209251E+12 | 0.00 | 0.585491E+12 | 0.243124E+12 |
Minimum of Months | 0.262913E+11 | 0.387551E+10 | 0.00 | 0.263215E+11 | 0.215527E+10 |
Maximum of Months | 0.573855E+12 | 0.295165E+11 | 0.00 | 0.687323E+11 | 0.721142E+11 |