Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:34
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 08:34:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1144.93 | 547.73 | 547.73 |
Net Site Energy | 1144.93 | 547.73 | 547.73 |
Total Source Energy | 3540.39 | 1693.71 | 1693.71 |
Net Source Energy | 3540.39 | 1693.71 | 1693.71 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 41.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 197.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 496.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 119.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 61.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1103.84 | 41.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 41.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 197.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 496.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 100.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 119.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 61.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 41.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 197.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 496.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 100.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 119.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 61.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 285.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 180.89 | 19.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 528.07 | 19.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 285.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 180.89 | 19.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 528.07 | 19.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1103.835 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1103.835 | 100.00 |
Total On-Site and Utility Electric Sources | 1103.835 | 100.00 |
Total Electricity End Uses | 1103.835 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 599.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:34 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 20.1123 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 23.1025 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 20.9200 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 20.9200 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 20.9200 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 13.4438 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 17.2687 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 17.2687 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 20.1123 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 23.1025 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 20.9200 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 20.9200 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 20.9200 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 13.4438 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 13.5625 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 13.5625 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 13.5625 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 13.5625 | 6.19 | 4.3000 | |
Total | 2090.32 | 17.2687 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 17.2687 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 17.2687 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-JUL-13:50 | 27-DEC-08:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 106453.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 43973.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 30804.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8146.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7352.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 98336.31 | 106453.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 106453.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 43973.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 30804.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8146.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 7352.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 44.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 625.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 318.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 377.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 194.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3495.85 | 44.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 21.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 299.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 752.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 152.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 180.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 93.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1672.40 | 21.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 21.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 299.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 752.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 152.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 180.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 93.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1672.40 | 21.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.59 |
SMSTORE1 DIRECT AIR | 1.35 |
SMSTORE2 DIRECT AIR | 1.39 |
SMSTORE3 DIRECT AIR | 1.38 |
SMSTORE4 DIRECT AIR | 1.38 |
LGSTORE2 DIRECT AIR | 2.37 |
SMSTORE5 DIRECT AIR | 1.23 |
SMSTORE6 DIRECT AIR | 1.22 |
SMSTORE7 DIRECT AIR | 1.23 |
SMSTORE8 DIRECT AIR | 1.38 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.59 | 2.59 | 2.59 | 2.59 | 2.59 | 2.59 | 1.00 | 1.00 | 2.59 |
PSZ-AC_2:2 | 1.35 | 1.35 | 1.35 | 1.35 | 1.35 | 1.35 | 1.00 | 1.00 | 1.35 |
PSZ-AC_3:3 | 1.39 | 1.39 | 1.39 | 1.39 | 1.39 | 1.39 | 1.00 | 1.00 | 1.39 |
PSZ-AC_4:4 | 1.38 | 1.38 | 1.38 | 1.38 | 1.38 | 1.38 | 1.00 | 1.00 | 1.38 |
PSZ-AC_5:5 | 1.38 | 1.38 | 1.38 | 1.38 | 1.38 | 1.38 | 1.00 | 1.00 | 1.38 |
PSZ-AC_6:6 | 2.37 | 2.37 | 2.37 | 2.37 | 2.37 | 2.37 | 1.00 | 1.00 | 2.37 |
PSZ-AC_7:7 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.00 | 1.000000 | 1.23 |
PSZ-AC_8:8 | 1.22 | 1.22 | 1.22 | 1.22 | 1.22 | 1.22 | 1.00 | 1.00 | 1.22 |
PSZ-AC_9:9 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.00 | 1.00 | 1.23 |
PSZ-AC_10:10 | 1.38 | 1.38 | 1.38 | 1.38 | 1.38 | 1.38 | 1.00 | 1.00 | 1.38 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.59 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.35 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.39 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.38 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.38 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.37 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.23 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.22 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.23 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.38 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.59 | 2771.10 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.35 | 1497.10 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.39 | 1541.31 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.38 | 1531.31 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.38 | 1532.32 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.37 | 2532.87 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.23 | 1362.20 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.22 | 1355.58 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.23 | 1356.98 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.38 | 1527.49 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.59 | 2.59 | 2.59 | 1.71 | 48417.37 | 62702.73 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.35 | 1.35 | 1.35 | 0.892453 | 25119.52 | 32488.34 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.39 | 1.39 | 1.39 | 0.918804 | 25875.17 | 33279.92 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.38 | 1.38 | 1.38 | 0.912848 | 25699.03 | 33101.00 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.38 | 1.38 | 1.38 | 0.913449 | 25744.33 | 33119.07 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.37 | 2.37 | 2.37 | 1.56 | 44877.47 | 58288.34 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.23 | 1.23 | 1.23 | 0.812038 | 23174.31 | 30072.75 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.22 | 1.22 | 1.22 | 0.808088 | 23078.45 | 29954.09 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.23 | 1.23 | 1.23 | 0.808922 | 23099.31 | 29979.14 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.38 | 1.38 | 1.38 | 0.910566 | 25189.74 | 33032.97 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.59 | 1.29 | 1.73 | 48417.37 | 24208.69 | 0.800520 | 0.800520 |
PSZ-AC_2:2 COOLING COIL | 1.35 | 0.676101 | 0.901467 | 25119.52 | 12559.76 | 0.800610 | 0.800610 |
PSZ-AC_3:3 COOLING COIL | 1.39 | 0.696064 | 0.928087 | 25875.17 | 12937.58 | 0.800440 | 0.800440 |
PSZ-AC_4:4 COOLING COIL | 1.38 | 0.691551 | 0.922067 | 25699.03 | 12849.51 | 0.800540 | 0.800540 |
PSZ-AC_5:5 COOLING COIL | 1.38 | 0.692007 | 0.922673 | 25744.33 | 12872.17 | 0.800180 | 0.800180 |
PSZ-AC_6:6 COOLING COIL | 2.37 | 1.18 | 1.58 | 44877.47 | 22438.74 | 0.798010 | 0.798010 |
PSZ-AC_7:7 COOLING COIL | 1.23 | 0.615180 | 0.820240 | 23174.31 | 11587.16 | 0.800120 | 0.800120 |
PSZ-AC_8:8 COOLING COIL | 1.22 | 0.612188 | 0.816253 | 23078.45 | 11539.23 | 0.800880 | 0.800880 |
PSZ-AC_9:9 COOLING COIL | 1.23 | 0.612819 | 0.817093 | 23099.31 | 11549.66 | 0.800920 | 0.800920 |
PSZ-AC_10:10 COOLING COIL | 1.38 | 0.689823 | 0.919767 | 25189.74 | 12594.87 | 0.800330 | 0.800330 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 62702.73 |
PSZ-AC_2:2 HEATING COIL | 32488.34 |
PSZ-AC_3:3 HEATING COIL | 33279.92 |
PSZ-AC_4:4 HEATING COIL | 33101.00 |
PSZ-AC_5:5 HEATING COIL | 33119.07 |
PSZ-AC_6:6 HEATING COIL | 58288.34 |
PSZ-AC_7:7 HEATING COIL | 30072.75 |
PSZ-AC_8:8 HEATING COIL | 29954.09 |
PSZ-AC_9:9 HEATING COIL | 29979.14 |
PSZ-AC_10:10 HEATING COIL | 33032.97 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 20.112 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.412 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 23.103 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 27.403 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 20.920 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.220 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 20.920 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.220 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 20.920 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.220 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 4694.002 | 13.474 | 83.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4694.002 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 2312.850 | 6.639 | 41.117 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2312.850 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2367.672 | 13.592 | 84.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2367.672 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1656.630 | 9.510 | 58.904 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1656.630 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1281.630 | 7.358 | 45.570 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1281.630 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1281.630 | 7.358 | 45.570 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1281.630 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1281.630 | 7.358 | 45.570 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1281.630 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 4683.651 | 13.444 | 83.264 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4683.651 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6887 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.218 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
19 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
20 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
21 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
22 | 7 | -0.33074266E-12 | 0.10604805E-14 | -0.10376772E-12 | 0.10050050E-15 |
23 | 6 | 0.29711555E-07 | 0.19576406E-09 | 0.67975929E-08 | -0.14079383E-12 |
24 | 5 | -0.19537397E-03 | 0.16642354E-05 | -0.10041974E-03 | 0.67165186E-08 |
25 | 4 | 0.29828781 | 0.80514357E-03 | 0.10189302 | -0.34439683E-04 |
26 | 3 | -7.3878975 | 0.24810408E-01 | -2.3749899 | 0.29604922E-01 |
27 | 2 | 41.272027 | 0.87780140E-01 | 15.412956 | -0.33780550 |
28 | 1 | -80.852930 | 0.39442104E-01 | -29.274215 | 1.0851646 |
29 | 0 | 46.824337 | 0.79011109E-03 | 16.288086 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 35 | 1 | VerySmooth | 2.826 | 2.826 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.02458E-002 | 0.16139 | 0.61152 | 0.61152 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.11029 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 25435.67364 | 30522.80836 | 2.15808 | 2.58970 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 18864.93652 | 22637.92382 | 0.93767 | 1.12521 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 13281.24577 | 15937.49492 | 1.12683 | 1.35220 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 8887.20650 | 10664.64780 | 0.44174 | 0.53008 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 13987.53491 | 16785.04189 | 1.16011 | 1.39213 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 30.95000 | 6.86012E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 9017.30278 | 10820.76333 | 0.44820 | 0.53784 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 13898.69107 | 16678.42929 | 1.15259 | 1.38310 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 30.95000 | 6.86012E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 9122.36345 | 10946.83614 | 0.45342 | 0.54411 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 13906.82742 | 16688.19290 | 1.15335 | 1.38401 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 30.95000 | 6.86012E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 9302.16730 | 11162.60077 | 0.46236 | 0.55483 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 23248.87579 | 27898.65094 | 1.97255 | 2.36706 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 18133.07897 | 21759.69476 | 0.90131 | 1.08157 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 12084.46472 | 14501.35767 | 1.02530 | 1.23036 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 37.77500 | 6.87096E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 9627.66832 | 11553.20199 | 0.47854 | 0.57425 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 12025.67992 | 14430.81590 | 1.02031 | 1.22438 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 37.77500 | 6.87096E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 9621.41169 | 11545.69403 | 0.47823 | 0.57388 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 12038.09127 | 14445.70953 | 1.02137 | 1.22564 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 37.77500 | 6.87096E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 9870.15520 | 11844.18624 | 0.49059 | 0.58871 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 13550.60338 | 16260.72405 | 1.14970 | 1.37965 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 37.45000 | 6.87043E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 11827.48547 | 14192.98256 | 0.58787 | 0.70544 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 36270.02 | 2.58970 | 2.58970 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 33668.01 | 1.12521 | 1.12521 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 18798.05 | 1.35220 | 1.35220 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 16189.24 | 0.53008 | 0.53008 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 18738.38 | 1.39213 | 1.39213 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 16343.08 | 0.53784 | 0.53784 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 18774.81 | 1.38310 | 1.38310 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 16467.31 | 0.54411 | 0.54411 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 18652.72 | 1.38401 | 1.38401 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 16679.94 | 0.55483 | 0.55483 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 33655.38 | 2.36706 | 2.36706 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 32802.67 | 1.08157 | 1.08157 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 17368.05 | 1.23036 | 1.23036 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 17064.85 | 0.57425 | 0.57425 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 17298.25 | 1.22438 | 1.22438 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 17057.45 | 0.57388 | 0.57388 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 17310.50 | 1.22564 | 1.22564 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 17351.59 | 0.58871 | 0.58871 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 18981.25 | 1.37965 | 1.37965 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 19666.09 | 0.70544 | 0.70544 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.58970 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.35220 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.39213 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.38310 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.38401 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.36706 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.23036 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.22438 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.22564 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.37965 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.58970 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.58970 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.58970 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.58970 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.58970 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.58970 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.35220 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.35220 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.35220 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.35220 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.35220 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.35220 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.39213 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39213 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.39213 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.39213 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.39213 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.39213 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.38310 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.38310 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.38310 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.38310 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.38310 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.38310 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.38401 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.38401 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.38401 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.38401 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.38401 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.38401 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.36706 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.36706 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.36706 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.36706 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.36706 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.36706 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.23036 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.23036 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.23036 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.23036 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.23036 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.23036 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.22438 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.22438 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.22438 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.22438 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.22438 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.22438 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.22564 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.22564 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.22564 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.22564 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.22564 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.22564 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.37965 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.37965 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.37965 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.37965 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.37965 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.37965 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.58970 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.35220 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.39213 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.38310 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.38401 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.36706 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.23036 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.22438 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.22564 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.37965 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.58970 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.58970 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2771.09918 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.58970 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.58970 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.58970 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.70920 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.58970 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.29485 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.72647 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 48417.37000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 24208.68500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80052 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80052 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 48417.37000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 62702.73277 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 62702.73277 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.35220 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.35220 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1497.10123 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.35220 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.35220 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.35220 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.89245 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.35220 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67610 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.90147 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25119.52000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12559.76000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80061 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80061 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25119.52000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32488.34230 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 32488.34230 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.39213 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.39213 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1541.30622 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.39213 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.39213 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.39213 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.91880 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.39213 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.69606 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.92809 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25875.17000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12937.58500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80044 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80044 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25875.17000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33279.91920 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 33279.91920 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.38310 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.38310 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1531.31456 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.38310 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.38310 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.38310 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.91285 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.38310 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.69155 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.92207 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25699.03000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12849.51500 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80054 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80054 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25699.03000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33101.00126 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 33101.00126 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.38401 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.38401 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1532.32359 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.38401 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.38401 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.38401 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.91345 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.38401 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.69201 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.92267 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25744.33000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12872.16500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80018 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80018 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25744.33000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33119.06815 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 33119.06815 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.36706 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.36706 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2532.86839 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.36706 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.36706 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.36706 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.56226 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.36706 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.18353 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.57804 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 44877.47000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 22438.73500 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79801 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79801 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 44877.47000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 58288.34013 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 58288.34013 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.23036 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.23036 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1362.20400 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.23036 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.23036 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.23036 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.81204 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.23036 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61518 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.82024 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23174.31000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11587.15500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80012 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80012 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23174.31000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30072.74938 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 30072.74938 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.22438 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.22438 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1355.57769 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.22438 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.22438 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.22438 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.80809 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.22438 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61219 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.81625 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23078.45000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11539.22500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80088 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80088 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23078.45000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29954.09215 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 29954.09215 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.22564 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.22564 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1356.97657 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.22564 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.22564 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.22564 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.80892 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.22564 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61282 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.81709 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23099.31000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11549.65500 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80092 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80092 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23099.31000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29979.14467 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 29979.14467 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.37965 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.37965 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1527.48697 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.37965 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.37965 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.37965 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.91057 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.37965 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68982 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.91977 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25189.74000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12594.87000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80033 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80033 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25189.74000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33032.96579 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 33032.96579 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 46384.3 | 11.22 | 11.22 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 24058.1 | 11.37 | 11.37 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 24782.4 | 11.37 | 11.37 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 24613.3 | 11.37 | 11.37 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 24657.9 | 11.37 | 11.37 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 43018.8 | 11.25 | 11.25 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 22208.3 | 11.40 | 11.40 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 22117.1 | 11.40 | 11.40 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 22137.0 | 11.40 | 11.40 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 24107.0 | 11.33 | 11.33 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.497_SHGC_0.25 | N/A | 2.826 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 6.3984918799E-002 | 8.8851928018E-002 | Pass | Pass | 3.2757280015E-002 | 0.1142954172 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 3.1374138426E-002 | 7.0751792628E-002 | Pass | Pass | 4.6265941418E-002 | 0.1312666869 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 5.5306738847E-002 | 8.5439229948E-002 | Pass | Pass | 2.6006553848E-002 | 0.1104059385 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 5.8602776622E-002 | 8.2397898351E-002 | Pass | Pass | 2.4547331805E-002 | 0.1101124389 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 5.9036211613E-002 | 7.4349209786E-002 | Pass | Pass | 2.5428457803E-002 | 0.1106304997 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 6.1759774081E-002 | 8.8281906739E-002 | Pass | Pass | 4.0527834414E-002 | 0.1824193970 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 6.0924020652E-002 | 9.7181764083E-002 | Pass | Pass | 3.0928661685E-002 | 0.1212085880 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 6.0864319474E-002 | 0.1129610441 | Pass | Pass | 9.2728618013E-002 | 0.4799414463 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 5.9376018501E-002 | 0.1533886829 | Pass | Pass | 8.3551643162E-002 | 0.3948477331 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 5.7928041372E-002 | 0.1980152079 | Pass | Pass | 0.1875341200 | 0.6960734018 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3203.21 | 42.02 | 0.00 | 159.79 | 939.95 | 4345.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.826 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.826 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.826 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.826 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.497_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.826 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.826 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.826 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 13.4735 | 348.39 | 4694.00 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 83.90 | 0.0000 | Y | 73.93 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 6.6387 | 348.39 | 2312.85 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 42.32 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 13.5922 | 174.19 | 2367.67 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 85.39 | 0.0000 | Y | 37.95 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 9.5103 | 174.19 | 1656.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 30.31 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 30.25 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 7.3575 | 174.19 | 1281.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.76 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 30.25 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 7.3575 | 174.19 | 1281.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.76 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 30.25 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 7.3575 | 174.19 | 1281.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.76 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 13.4438 | 348.39 | 4683.65 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 54.16 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 8.6344 | 4180.64 | 36097.17 | 496.92 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 458.42 | AstronomicalClock | - | 41.77 | 41.77 | 3.59 | |
EXTERIOR_LIGHTS_B | 7264.83 | AstronomicalClock | - | 83.77 | 71.17 | 97.05 | |
Exterior Lighting Total | 7723.25 | 100.64 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 48417.37 | 38759.07 | 9658.30 | 0.80 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25119.52 | 20110.94 | 5008.58 | 0.80 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25875.17 | 20711.52 | 5163.65 | 0.80 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25699.03 | 20573.10 | 5125.93 | 0.80 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25744.33 | 20600.10 | 5144.23 | 0.80 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 44877.47 | 35812.67 | 9064.80 | 0.80 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23174.31 | 18542.23 | 4632.08 | 0.80 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23078.45 | 18483.07 | 4595.38 | 0.80 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23099.31 | 18500.70 | 4598.61 | 0.80 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25189.74 | 20160.10 | 5029.64 | 0.80 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 46384.3 | 11.22 | 11.22 | ||||
PSZ-AC_2:2 COOLING COIL | 24058.1 | 11.37 | 11.37 | ||||
PSZ-AC_3:3 COOLING COIL | 24782.4 | 11.37 | 11.37 | ||||
PSZ-AC_4:4 COOLING COIL | 24613.3 | 11.37 | 11.37 | ||||
PSZ-AC_5:5 COOLING COIL | 24657.9 | 11.37 | 11.37 | ||||
PSZ-AC_6:6 COOLING COIL | 43018.8 | 11.25 | 11.25 | ||||
PSZ-AC_7:7 COOLING COIL | 22208.3 | 11.40 | 11.40 | ||||
PSZ-AC_8:8 COOLING COIL | 22117.1 | 11.40 | 11.40 | ||||
PSZ-AC_9:9 COOLING COIL | 22137.0 | 11.40 | 11.40 | ||||
PSZ-AC_10:10 COOLING COIL | 24107.0 | 11.33 | 11.33 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 62702.73 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 32488.34 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 33279.92 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 33101.00 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 33119.07 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 58288.34 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 30072.75 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 29954.09 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 29979.14 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 33032.97 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.59 | 2771.10 | 1070.05 | 1.00 | 1.28 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.35 | 1497.10 | 1107.16 | 1.00 | 1.34 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.39 | 1541.31 | 1107.16 | 1.00 | 1.33 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.38 | 1531.31 | 1107.16 | 1.00 | 1.33 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.38 | 1532.32 | 1107.16 | 1.00 | 1.33 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.37 | 2532.87 | 1070.05 | 1.00 | 1.29 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.23 | 1362.20 | 1107.16 | 1.00 | 1.35 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.22 | 1355.58 | 1107.16 | 1.00 | 1.36 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.23 | 1356.98 | 1107.16 | 1.00 | 1.36 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.38 | 1527.49 | 1107.16 | 1.00 | 1.33 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 25435.67 | 30522.81 | 87.61 | 2.158 | 2.590 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 23.89 | 23.89 | 0.00742 | 38.10 | 0.00687 | 0.411 | 0.00 |
SMSTORE1 | 13281.25 | 15937.49 | 91.49 | 1.127 | 1.352 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00740 | 37.99 | 0.00687 | 0.206 | 0.00 |
SMSTORE2 | 13987.53 | 16785.04 | 96.36 | 1.160 | 1.392 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00756 | 30.95 | 0.00686 | 0.206 | 0.00 |
SMSTORE3 | 13898.69 | 16678.43 | 95.75 | 1.153 | 1.383 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00756 | 30.95 | 0.00686 | 0.206 | 0.00 |
SMSTORE4 | 13906.83 | 16688.19 | 95.80 | 1.153 | 1.384 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00756 | 30.95 | 0.00686 | 0.206 | 0.00 |
LGSTORE2 | 23248.88 | 27898.65 | 80.08 | 1.973 | 2.367 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00746 | 37.88 | 0.00687 | 0.411 | 0.00 |
SMSTORE5 | 12084.46 | 14501.36 | 83.25 | 1.025 | 1.230 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.89 | 0.00744 | 37.77 | 0.00687 | 0.206 | 0.00 |
SMSTORE6 | 12025.68 | 14430.82 | 82.84 | 1.020 | 1.224 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.89 | 0.00744 | 37.77 | 0.00687 | 0.206 | 0.00 |
SMSTORE7 | 12038.09 | 14445.71 | 82.93 | 1.021 | 1.226 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.89 | 0.00744 | 37.77 | 0.00687 | 0.206 | 0.00 |
SMSTORE8 | 13550.60 | 16260.72 | 93.35 | 1.150 | 1.380 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 23.89 | 23.89 | 0.00739 | 37.45 | 0.00687 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 18864.94 | 22637.92 | 64.98 | 0.938 | 1.125 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00690 | -5.20 | 0.00281 | 0.411 | 0.00 |
SMSTORE1 | 8887.21 | 10664.65 | 61.22 | 0.442 | 0.530 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00680 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE2 | 9017.30 | 10820.76 | 62.12 | 0.448 | 0.538 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00681 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE3 | 9122.36 | 10946.84 | 62.84 | 0.453 | 0.544 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00682 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE4 | 9302.17 | 11162.60 | 64.08 | 0.462 | 0.555 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00683 | -5.20 | 0.00281 | 0.206 | 0.00 |
LGSTORE2 | 18133.08 | 21759.69 | 62.46 | 0.901 | 1.082 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00691 | -5.20 | 0.00281 | 0.411 | 0.00 |
SMSTORE5 | 9627.67 | 11553.20 | 66.32 | 0.479 | 0.574 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00686 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE6 | 9621.41 | 11545.69 | 66.28 | 0.478 | 0.574 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00686 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE7 | 9870.16 | 11844.19 | 67.99 | 0.491 | 0.589 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00687 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE8 | 11827.49 | 14192.98 | 81.48 | 0.588 | 0.705 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00693 | -5.20 | 0.00281 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.59 | 2.59 | 1.13 | 1.13 | 2.5897 | 2.5897 | 2.5897 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.35 | 1.35 | 0.53 | 0.53 | 1.3522 | 1.3522 | 1.3522 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.39 | 1.39 | 0.54 | 0.54 | 1.3921 | 1.3921 | 1.3921 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.38 | 1.38 | 0.54 | 0.54 | 1.3831 | 1.3831 | 1.3831 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.38 | 1.38 | 0.55 | 0.55 | 1.3840 | 1.3840 | 1.3840 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.37 | 2.37 | 1.08 | 1.08 | 2.3671 | 2.3671 | 2.3671 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.23 | 1.23 | 0.57 | 0.57 | 1.2304 | 1.2304 | 1.2304 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.22 | 1.22 | 0.57 | 0.57 | 1.2244 | 1.2244 | 1.2244 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.23 | 1.23 | 0.59 | 0.59 | 1.2256 | 1.2256 | 1.2256 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.38 | 1.38 | 0.71 | 0.71 | 1.3796 | 1.3796 | 1.3796 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 48417.370 | 38759.073 | 2.589700 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24208.69 | 23255.62 | 1.726467 | 27.15 | 15.04 | 0.00733526 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 23.8336 | 23.89 | 0.00742288 | 34.9480 | 25435.67 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 62702.733 | 62702.733 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 62702.73 | 62702.73 | 2.589698 | 16.93 | 10.27 | 0.00624716 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 15.8891 | 21.11 | 0.00689676 | 38.4831 | 18864.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 25119.520 | 20110.939 | 1.352200 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 12559.76 | 12080.60 | 0.901467 | 27.09 | 15.01 | 0.00732354 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 22.8227 | 23.89 | 0.00740469 | 34.8632 | 13277.53 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 32488.342 | 32488.342 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 32488.34 | 32488.34 | 1.352201 | 17.10 | 10.29 | 0.00619151 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 15.2151 | 21.11 | 0.00679863 | 37.9414 | 8887.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 25875.170 | 20711.521 | 1.392130 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 12937.58 | 12442.90 | 0.928087 | 27.10 | 15.01 | 0.00732442 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 22.1681 | 23.89 | 0.00740610 | 34.8697 | 13227.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 33279.919 | 33279.919 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 33279.92 | 33279.92 | 1.392128 | 17.22 | 10.36 | 0.00621790 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 14.7788 | 21.11 | 0.00680917 | 37.9996 | 9017.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 25699.030 | 20573.101 | 1.383100 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 12849.51 | 12358.84 | 0.922067 | 27.10 | 15.01 | 0.00732390 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 22.3129 | 23.89 | 0.00740526 | 34.8658 | 13257.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 33101.001 | 33101.001 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 33101.00 | 33101.00 | 1.383103 | 17.19 | 10.35 | 0.00622117 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 14.8752 | 21.11 | 0.00681754 | 38.0459 | 9122.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 25744.330 | 20600.098 | 1.384010 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 12872.17 | 12378.45 | 0.922673 | 27.11 | 15.02 | 0.00732566 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 22.2982 | 23.89 | 0.00740809 | 34.8790 | 13154.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 33119.068 | 33119.068 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 33119.07 | 33119.07 | 1.384014 | 17.20 | 10.37 | 0.00623378 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 14.8654 | 21.11 | 0.00683189 | 38.1251 | 9302.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 44877.470 | 35812.670 | 2.367060 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 22438.74 | 21502.92 | 1.578040 | 27.37 | 15.13 | 0.00735969 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 26.0753 | 23.89 | 0.00746253 | 35.1325 | 23228.63 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 58288.340 | 58288.340 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 58288.34 | 58288.34 | 2.367062 | 16.53 | 10.07 | 0.00619890 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 17.3835 | 21.11 | 0.00691231 | 38.5684 | 18133.08 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 23174.310 | 18542.229 | 1.230360 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 11587.16 | 11121.33 | 0.820240 | 27.31 | 15.10 | 0.00734522 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 25.0828 | 23.89 | 0.00744048 | 35.0297 | 12070.45 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 30072.749 | 30072.749 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30072.75 | 30072.75 | 1.230360 | 16.71 | 10.12 | 0.00617976 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 16.7219 | 21.11 | 0.00685671 | 38.2622 | 9627.67 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 23078.450 | 18483.069 | 1.224380 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 11539.23 | 11074.13 | 0.816253 | 27.32 | 15.11 | 0.00734634 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 25.2053 | 23.89 | 0.00744239 | 35.0386 | 12011.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 29954.092 | 29954.092 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 29954.09 | 29954.09 | 1.224375 | 16.69 | 10.11 | 0.00617609 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 16.8036 | 21.11 | 0.00685629 | 38.2598 | 9621.41 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 23099.310 | 18500.699 | 1.225640 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 11549.66 | 11084.35 | 0.817093 | 27.32 | 15.10 | 0.00734615 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 25.1794 | 23.89 | 0.00744206 | 35.0370 | 12021.88 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 29979.145 | 29979.145 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 29979.14 | 29979.14 | 1.225639 | 16.69 | 10.12 | 0.00619179 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 16.7863 | 21.11 | 0.00687430 | 38.3593 | 9870.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 25189.740 | 20160.105 | 1.379650 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 12594.87 | 12125.72 | 0.919767 | 26.95 | 14.95 | 0.00731347 | 12.80 | 9.33 | 0.00700000 | 37.45 | 0.00687043 | 17.97 | 22.3687 | 23.89 | 0.00739111 | 34.7999 | 13550.60 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 33032.966 | 33032.966 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 33032.97 | 33032.97 | 1.379646 | 17.18 | 10.45 | 0.00631730 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 14.9125 | 21.11 | 0.00693227 | 38.6803 | 11827.49 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 48417.370 | 38759.073 | 2.589700 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4759 | 1004.8586 | 1.0443 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.589698 | 2.70450370 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 24208.69 | 23255.62 | 1.0000 | 1.80300392 | 1.726467 | 27.15 | 15.04 | 0.00733526 | 45998.9 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24208.69 | 38.10 | 0.00687148 | 18.17 | 0.41147883 | 23.8336 | 23.89 | 0.00742288 | 23.89 | 0.00742288 | 34.9480 | 25435.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 62702.733 | 62702.733 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.589698 | 2.70450370 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 62702.73 | 62702.73 | 1.0000 | 2.70450370 | 2.589698 | 16.93 | 10.27 | 0.00624716 | 32829.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 62702.73 | -5.20 | 0.00280840 | -5.20 | 0.41147883 | 15.8891 | 21.11 | 0.00689676 | 21.11 | 0.00689676 | 38.4831 | 18864.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25119.520 | 20110.939 | 1.352200 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4541 | 1004.8586 | 1.0443 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.352201 | 1.41214648 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 12559.76 | 12080.60 | 1.0000 | 0.94143025 | 0.901467 | 27.09 | 15.01 | 0.00732354 | 45907.7 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12559.76 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 22.8227 | 23.89 | 0.00740469 | 23.89 | 0.00740469 | 34.8632 | 13277.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32488.342 | 32488.342 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.352201 | 1.41214648 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 32488.34 | 32488.34 | 1.0000 | 1.41214648 | 1.352201 | 17.10 | 10.29 | 0.00619151 | 32869.1 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32488.34 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 15.2151 | 21.11 | 0.00679863 | 21.11 | 0.00679863 | 37.9414 | 8887.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25875.170 | 20711.521 | 1.392130 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4557 | 1004.8586 | 1.0443 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.392128 | 1.45384301 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 12937.58 | 12442.90 | 1.0000 | 0.96923036 | 0.928087 | 27.10 | 15.01 | 0.00732442 | 45918.3 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12937.58 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 22.1681 | 23.89 | 0.00740610 | 23.89 | 0.00740610 | 34.8697 | 13227.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33279.919 | 33279.919 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.392128 | 1.45384301 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 33279.92 | 33279.92 | 1.0000 | 1.45384301 | 1.392128 | 17.22 | 10.36 | 0.00621790 | 33052.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33279.92 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 14.7788 | 21.11 | 0.00680917 | 21.11 | 0.00680917 | 37.9996 | 9017.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25699.030 | 20573.101 | 1.383100 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4548 | 1004.8586 | 1.0443 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.383103 | 1.44441834 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 12849.51 | 12358.84 | 1.0000 | 0.96294348 | 0.922067 | 27.10 | 15.01 | 0.00732390 | 45911.9 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12849.51 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 22.3129 | 23.89 | 0.00740526 | 23.89 | 0.00740526 | 34.8658 | 13257.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33101.001 | 33101.001 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.383103 | 1.44441834 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 33101.00 | 33101.00 | 1.0000 | 1.44441834 | 1.383103 | 17.19 | 10.35 | 0.00622117 | 33035.2 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33101.00 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 14.8752 | 21.11 | 0.00681754 | 21.11 | 0.00681754 | 38.0459 | 9122.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25744.330 | 20600.098 | 1.384010 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4580 | 1004.8586 | 1.0443 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.384014 | 1.44537012 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 12872.17 | 12378.45 | 1.0000 | 0.96357704 | 0.922673 | 27.11 | 15.02 | 0.00732566 | 45933.6 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12872.17 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 22.2982 | 23.89 | 0.00740809 | 23.89 | 0.00740809 | 34.8790 | 13154.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33119.068 | 33119.068 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.384014 | 1.44537012 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 33119.07 | 33119.07 | 1.0000 | 1.44537012 | 1.384014 | 17.20 | 10.37 | 0.00623378 | 33069.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33119.07 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 14.8654 | 21.11 | 0.00683189 | 21.11 | 0.00683189 | 38.1251 | 9302.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 44877.470 | 35812.670 | 2.367060 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5213 | 1004.8586 | 1.0443 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.367062 | 2.47199811 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 22438.74 | 21502.92 | 1.0000 | 1.64799725 | 1.578040 | 27.37 | 15.13 | 0.00735969 | 46279.7 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22438.74 | 38.10 | 0.00687148 | 18.17 | 0.41147883 | 26.0753 | 23.89 | 0.00746253 | 23.89 | 0.00746253 | 35.1325 | 23228.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 58288.340 | 58288.340 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.367062 | 2.47199811 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 58288.34 | 58288.34 | 1.0000 | 2.47199811 | 2.367062 | 16.53 | 10.07 | 0.00619890 | 32308.2 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58288.34 | -5.20 | 0.00280840 | -5.20 | 0.41147883 | 17.3835 | 21.11 | 0.00691231 | 21.11 | 0.00691231 | 38.5684 | 18133.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23174.310 | 18542.229 | 1.230360 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4944 | 1004.8586 | 1.0443 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.230360 | 1.28490416 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 11587.16 | 11121.33 | 1.0000 | 0.85660266 | 0.820240 | 27.31 | 15.10 | 0.00734522 | 46183.3 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11587.16 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 25.0828 | 23.89 | 0.00744048 | 23.89 | 0.00744048 | 35.0297 | 12070.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30072.749 | 30072.749 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.230360 | 1.28490416 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30072.75 | 30072.75 | 1.0000 | 1.28490416 | 1.230360 | 16.71 | 10.12 | 0.00617976 | 32436.5 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30072.75 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 16.7219 | 21.11 | 0.00685671 | 21.11 | 0.00685671 | 38.2622 | 9627.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23078.450 | 18483.069 | 1.224380 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4965 | 1004.8586 | 1.0443 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.224375 | 1.27865387 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 11539.23 | 11074.13 | 1.0000 | 0.85243926 | 0.816253 | 27.32 | 15.11 | 0.00734634 | 46198.0 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11539.23 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 25.2053 | 23.89 | 0.00744239 | 23.89 | 0.00744239 | 35.0386 | 12011.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29954.092 | 29954.092 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.224375 | 1.27865387 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 29954.09 | 29954.09 | 1.0000 | 1.27865387 | 1.224375 | 16.69 | 10.11 | 0.00617609 | 32405.4 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29954.09 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 16.8036 | 21.11 | 0.00685629 | 21.11 | 0.00685629 | 38.2598 | 9621.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23099.310 | 18500.699 | 1.225640 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4961 | 1004.8586 | 1.0443 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.225639 | 1.27997336 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 11549.66 | 11084.35 | 1.0000 | 0.85331650 | 0.817093 | 27.32 | 15.10 | 0.00734615 | 46195.4 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11549.66 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 25.1794 | 23.89 | 0.00744206 | 23.89 | 0.00744206 | 35.0370 | 12021.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29979.145 | 29979.145 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.225639 | 1.27997336 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 29979.14 | 29979.14 | 1.0000 | 1.27997336 | 1.225639 | 16.69 | 10.12 | 0.00619179 | 32449.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29979.14 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 16.7863 | 21.11 | 0.00687430 | 21.11 | 0.00687430 | 38.3593 | 9870.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25189.740 | 20160.105 | 1.379650 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4354 | 1004.8586 | 1.0443 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.379646 | 1.44080795 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 12594.87 | 12125.72 | 1.0000 | 0.96054152 | 0.919767 | 26.95 | 14.95 | 0.00731347 | 45738.7 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12594.87 | 37.45 | 0.00687043 | 17.97 | 0.20573941 | 22.3687 | 23.89 | 0.00739111 | 23.89 | 0.00739111 | 34.7999 | 13550.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33032.966 | 33032.966 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.379646 | 1.44080795 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 33032.97 | 33032.97 | 1.0000 | 1.44080795 | 1.379646 | 17.18 | 10.45 | 0.00631730 | 33268.3 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33032.97 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 14.9125 | 21.11 | 0.00693227 | 21.11 | 0.00693227 | 38.6803 | 11827.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.59 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.35 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.39 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.38 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.38 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.37 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.23 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.22 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.23 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.38 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 2436.50 | 2621.33 | 226.67 |
SMSTORE1 | 2289.33 | 2348.33 | 74.50 |
SMSTORE2 | 1849.83 | 1844.17 | 143.17 |
SMSTORE3 | 1857.33 | 1887.67 | 151.83 |
SMSTORE4 | 1843.17 | 1962.17 | 169.83 |
LGSTORE2 | 1635.50 | 1914.50 | 184.33 |
SMSTORE5 | 1583.00 | 1961.83 | 199.00 |
SMSTORE6 | 1589.50 | 1984.67 | 216.67 |
SMSTORE7 | 1628.17 | 2024.00 | 266.50 |
SMSTORE8 | 1858.17 | 2033.33 | 421.50 |
Facility | 2870.00 | 3126.50 | 599.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 0.33 | 0.00 | 0.00 | 0.00 |
Facility | 0.50 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 1.131 | 0.224 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 1.023 | 0.239 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 1.184 | 0.312 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 1.174 | 0.312 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 1.156 | 0.312 | 0.000 | 0.000 |
LGSTORE2 | 24.75 | 56.25 | 1805.20 | 1.062 | 0.299 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 1.071 | 0.333 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 1.064 | 0.333 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 1.051 | 0.332 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 1.072 | 0.351 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.812 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.811 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.811 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.75 | 56.25 | 1805.20 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.47 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.75 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.88 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 11809779.65 | 0.00 | 11809779.65 | 2654284.96 | 14464064.61 | 12976396.34 | 3112.71 | 4081.08 | 1566.21 | 33.21 |
SMSTORE1 | 5349687.54 | 0.00 | 5349687.54 | 1335851.20 | 6685538.74 | 6488198.17 | 4237.17 | 2869.17 | 1653.66 | 39.63 |
SMSTORE2 | 4827699.24 | 0.00 | 4827699.24 | 1373042.31 | 6200741.55 | 6488198.17 | 4271.56 | 3250.25 | 1238.19 | 155.81 |
SMSTORE3 | 4784598.64 | 0.00 | 4784598.64 | 1373042.31 | 6157640.95 | 6488198.17 | 4271.41 | 3286.20 | 1202.39 | 153.88 |
SMSTORE4 | 4708496.31 | 0.00 | 4708496.31 | 1373042.31 | 6081538.61 | 6488198.17 | 4273.52 | 3352.17 | 1134.31 | 149.75 |
LGSTORE2 | 7849294.13 | 0.00 | 7849294.13 | 2517504.51 | 10366798.64 | 12976396.34 | 4666.71 | 3188.28 | 905.01 | 108.78 |
SMSTORE5 | 3963433.86 | 0.00 | 3963433.86 | 1381311.82 | 5344745.68 | 6488198.17 | 4665.08 | 3204.92 | 890.00 | 110.03 |
SMSTORE6 | 3935421.07 | 0.00 | 3935421.07 | 1381311.82 | 5316732.89 | 6488198.17 | 4665.76 | 3221.42 | 872.82 | 106.00 |
SMSTORE7 | 3884096.45 | 0.00 | 3884096.45 | 1381311.82 | 5265408.27 | 6488198.17 | 4668.42 | 3275.42 | 816.16 | 95.33 |
SMSTORE8 | 3972205.36 | 0.00 | 3972205.36 | 1677204.46 | 5649409.82 | 6488198.17 | 4667.67 | 3333.01 | 759.32 | 84.62 |
Total Facility | 55084712.25 | 0.00 | 55084712.25 | 16447907.52 | 71532619.77 | 77858378.04 | 4674.96 | 4650.74 | 1997.15 | 289.86 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.5579 | 0.0000 | 0.5579 | 0.1106 | 0.6685 | 0.4115 | 211.42 | 4081.08 | 1547.50 |
SMSTORE1 | 0.2521 | 0.0000 | 0.2521 | 0.0589 | 0.3111 | 0.2057 | 1338.24 | 2868.92 | 1632.84 |
SMSTORE2 | 0.2919 | 0.0000 | 0.2919 | 0.0768 | 0.3688 | 0.2057 | 0.00 | 3250.25 | 1144.75 |
SMSTORE3 | 0.2893 | 0.0000 | 0.2893 | 0.0768 | 0.3661 | 0.2057 | 0.00 | 3286.00 | 1109.00 |
SMSTORE4 | 0.2849 | 0.0000 | 0.2849 | 0.0768 | 0.3618 | 0.2057 | 0.00 | 3352.00 | 1043.00 |
LGSTORE2 | 0.5235 | 0.0000 | 0.5235 | 0.1476 | 0.6712 | 0.4115 | 0.00 | 3188.25 | 841.75 |
SMSTORE5 | 0.2640 | 0.0000 | 0.2640 | 0.0820 | 0.3460 | 0.2057 | 0.00 | 3204.42 | 825.58 |
SMSTORE6 | 0.2623 | 0.0000 | 0.2623 | 0.0820 | 0.3443 | 0.2057 | 0.00 | 3221.25 | 808.75 |
SMSTORE7 | 0.2591 | 0.0000 | 0.2591 | 0.0820 | 0.3411 | 0.2057 | 0.00 | 3275.08 | 754.92 |
SMSTORE8 | 0.2645 | 0.0000 | 0.2645 | 0.0865 | 0.3510 | 0.2057 | 0.00 | 3332.58 | 697.42 |
Total Facility | 3.2495 | 0.0000 | 3.2495 | 0.8802 | 4.1297 | 2.4689 | 1431.41 | 4648.92 | 1916.57 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 12880112.43 | 0.00 | 12880112.43 | 12976396.34 | 3111.37 | 0.20 | 5648.43 | 33.07 |
PSZ-AC_2:2 | 5834525.58 | 0.00 | 5834525.58 | 6488198.17 | 4203.39 | 8.34 | 4548.27 | 39.63 |
PSZ-AC_3:3 | 5265235.21 | 0.00 | 5265235.21 | 6488198.17 | 4269.66 | 0.20 | 4490.14 | 155.60 |
PSZ-AC_4:4 | 5218229.32 | 0.00 | 5218229.32 | 6488198.17 | 4269.85 | 0.33 | 4489.81 | 153.72 |
PSZ-AC_5:5 | 5135229.62 | 0.00 | 5135229.62 | 6488198.17 | 4272.02 | 0.17 | 4487.81 | 149.25 |
PSZ-AC_6:6 | 8560687.00 | 0.00 | 8560687.00 | 12976396.34 | 4665.71 | 0.00 | 4094.29 | 108.78 |
PSZ-AC_7:7 | 4322642.73 | 0.00 | 4322642.73 | 6488198.17 | 4664.02 | 0.17 | 4095.81 | 109.69 |
PSZ-AC_8:8 | 4292087.26 | 0.00 | 4292087.26 | 6488198.17 | 4664.62 | 0.83 | 4094.54 | 106.00 |
PSZ-AC_9:9 | 4236095.94 | 0.00 | 4236095.94 | 6488198.17 | 4667.12 | 0.08 | 4092.80 | 95.33 |
PSZ-AC_10:10 | 4332164.00 | 0.00 | 4332164.00 | 6488198.17 | 4665.97 | 0.40 | 4093.63 | 84.29 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6084 | 0.0000 | 0.6084 | 0.4115 | 210.16 | 0.20 | 5629.64 |
PSZ-AC_2:2 | 0.2750 | 0.0000 | 0.2750 | 0.2057 | 1305.16 | 8.31 | 4526.54 |
PSZ-AC_3:3 | 0.3184 | 0.0000 | 0.3184 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3155 | 0.0000 | 0.3155 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3107 | 0.0000 | 0.3107 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.5710 | 0.0000 | 0.5710 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2879 | 0.0000 | 0.2879 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2860 | 0.0000 | 0.2860 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2826 | 0.0000 | 0.2826 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2885 | 0.0000 | 0.2885 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5018.03 | 681.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4302.07 | 1181.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 3957.47 | 593.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 3984.64 | 564.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4014.29 | 529.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3747.54 | 391.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3751.40 | 388.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3757.93 | 378.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3786.70 | 338.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3803.63 | 310.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.6076 | 0.7745 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2903 | 0.3127 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3043 | 0.4303 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3018 | 0.4312 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.2972 | 0.4344 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.5529 | 0.7787 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.2782 | 0.4001 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.2766 | 0.3977 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2738 | 0.3987 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.2783 | 0.4323 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 759 |
Defaulted Fields | 823 |
Fields with Defaults | 2681 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1103.84 | 3274.06 | 01-JAN-07:20 | 98336.31 | 03-JUL-13:50 |
Electricity:Building | 625.08 | 2063.06 | 01-JAN-00:10 | 38863.50 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 142.50 | 391.26 | 01-JAN-00:10 | 7378.51 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 625.08 | 2063.06 | 01-JAN-00:10 | 38863.50 | 01-JAN-11:10 |
InteriorLights:Electricity | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 116.25 | 317.63 | 01-JAN-00:10 | 6035.26 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 116.25 | 317.63 | 01-JAN-00:10 | 6035.26 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 81.39 | 223.36 | 01-JAN-00:10 | 4215.80 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 68.27 | 186.54 | 01-JAN-00:10 | 3544.17 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 68.27 | 186.54 | 01-JAN-00:10 | 3544.17 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 59.43 | 204.26 | 01-JAN-00:10 | 3853.00 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 59.43 | 204.26 | 01-JAN-00:10 | 3853.00 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 59.43 | 204.26 | 01-JAN-00:10 | 3853.00 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 73.33 | 274.94 | 01-JAN-00:10 | 5168.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 54.16 | 201.30 | 01-JAN-00:10 | 3825.14 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 54.16 | 201.30 | 01-JAN-00:10 | 3825.14 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1103.84 | 3274.06 | 01-JAN-07:20 | 98336.31 | 03-JUL-13:50 |
ElectricityPurchased:Plant | 1103.84 | 3274.06 | 01-JAN-07:20 | 98336.31 | 03-JUL-13:50 |
Cogeneration:ElectricityPurchased | 1103.84 | 3274.06 | 01-JAN-07:20 | 98336.31 | 03-JUL-13:50 |
General:Cogeneration:ElectricityPurchased | 1103.84 | 3274.06 | 01-JAN-07:20 | 98336.31 | 03-JUL-13:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1103.84 | 3274.06 | 01-JAN-07:20 | 98336.31 | 03-JUL-13:50 |
ElectricityNet:Plant | 1103.84 | 3274.06 | 01-JAN-07:20 | 98336.31 | 03-JUL-13:50 |
Cogeneration:ElectricityNet | 1103.84 | 3274.06 | 01-JAN-07:20 | 98336.31 | 03-JUL-13:50 |
General:Cogeneration:ElectricityNet | 1103.84 | 3274.06 | 01-JAN-07:20 | 98336.31 | 03-JUL-13:50 |
Electricity:HVAC | 316.73 | 0.00 | 01-JAN-00:10 | 53583.52 | 15-JUN-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 197.47 | 0.00 | 01-JAN-00:10 | 45140.29 | 02-JUN-16:20 |
General:Cooling:Electricity | 197.47 | 0.00 | 01-JAN-00:10 | 45140.29 | 02-JUN-16:20 |
Fans:Electricity | 119.26 | 0.00 | 01-JAN-00:10 | 9113.67 | 27-DEC-08:10 |
General:Fans:Electricity | 119.26 | 0.00 | 01-JAN-00:10 | 9113.67 | 27-DEC-08:10 |
ExteriorLights:Electricity | 100.64 | 0.00 | 01-JAN-07:20 | 7723.25 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 100.64 | 0.00 | 01-JAN-07:20 | 7723.25 | 01-JAN-06:10 |
Electricity:Plant | 61.39 | 1211.00 | 01-JAN-09:10 | 11809.26 | 10-NOV-15:00 |
WaterSystems:Electricity | 61.39 | 1211.00 | 01-JAN-09:10 | 11809.26 | 10-NOV-15:00 |
Water Heater:WaterSystems:Electricity | 61.39 | 1211.00 | 01-JAN-09:10 | 11809.26 | 10-NOV-15:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 41.09 | 0.00 | 01-JAN-00:10 | 106453.85 | 27-DEC-08:10 |
NaturalGas:HVAC | 41.09 | 0.00 | 01-JAN-00:10 | 106453.85 | 27-DEC-08:10 |
Heating:NaturalGas | 41.09 | 0.00 | 01-JAN-00:10 | 106453.85 | 27-DEC-08:10 |
General:Heating:NaturalGas | 41.09 | 0.00 | 01-JAN-00:10 | 106453.85 | 27-DEC-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1456.49 | 0.00 | 01-JAN-00:10 | 255196.95 | 03-JUL-14:10 |
EnergyTransfer:Building | 689.35 | 0.00 | 01-JAN-00:10 | 106255.61 | 03-JUL-13:00 |
EnergyTransfer:Zone:LGSTORE1 | 148.33 | 0.00 | 01-JAN-00:10 | 18145.92 | 07-AUG-16:10 |
Heating:EnergyTransfer | 14.60 | 0.00 | 01-JAN-00:10 | 75150.57 | 27-DEC-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 1.40 | 0.00 | 01-JAN-00:10 | 14445.83 | 28-JAN-08:10 |
General:Heating:EnergyTransfer | 14.60 | 0.00 | 01-JAN-00:10 | 75150.57 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 1.40 | 0.00 | 01-JAN-00:10 | 14445.83 | 28-JAN-08:10 |
Cooling:EnergyTransfer | 674.75 | 0.00 | 01-JAN-00:10 | 106255.61 | 03-JUL-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 146.92 | 0.00 | 01-JAN-00:10 | 18145.92 | 07-AUG-16:10 |
General:Cooling:EnergyTransfer | 674.75 | 0.00 | 01-JAN-00:10 | 106255.61 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 146.92 | 0.00 | 01-JAN-00:10 | 18145.92 | 07-AUG-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 80.68 | 0.00 | 01-JAN-00:10 | 9949.76 | 20-OCT-20:20 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.40 | 0.00 | 01-JAN-00:10 | 3747.86 | 28-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.40 | 0.00 | 01-JAN-00:10 | 3747.86 | 28-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 80.28 | 0.00 | 01-JAN-00:10 | 9949.76 | 20-OCT-20:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 80.28 | 0.00 | 01-JAN-00:10 | 9949.76 | 20-OCT-20:20 |
EnergyTransfer:Zone:SMSTORE2 | 60.20 | 0.00 | 01-JAN-00:10 | 9082.83 | 03-JUL-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.03 | 0.00 | 01-JAN-00:10 | 4844.60 | 28-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 1.03 | 0.00 | 01-JAN-00:10 | 4844.60 | 28-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 59.17 | 0.00 | 01-JAN-00:10 | 9082.83 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 59.17 | 0.00 | 01-JAN-00:10 | 9082.83 | 03-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 59.66 | 0.00 | 01-JAN-00:10 | 9165.82 | 03-JUL-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.10 | 0.00 | 01-JAN-00:10 | 5598.85 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 1.10 | 0.00 | 01-JAN-00:10 | 5598.85 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 58.56 | 0.00 | 01-JAN-00:10 | 9165.82 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 58.56 | 0.00 | 01-JAN-00:10 | 9165.82 | 03-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 57.15 | 0.00 | 01-JAN-00:10 | 9065.20 | 03-JUL-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.24 | 0.00 | 01-JAN-00:10 | 6031.38 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 1.24 | 0.00 | 01-JAN-00:10 | 6031.38 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 55.91 | 0.00 | 01-JAN-00:10 | 9065.20 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 55.91 | 0.00 | 01-JAN-00:10 | 9065.20 | 03-JUL-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 93.09 | 0.00 | 01-JAN-00:10 | 16666.62 | 03-JUL-14:20 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 2.12 | 0.00 | 01-JAN-00:10 | 14957.28 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 2.12 | 0.00 | 01-JAN-00:10 | 14957.28 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 90.97 | 0.00 | 01-JAN-00:10 | 16666.62 | 03-JUL-14:20 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 90.97 | 0.00 | 01-JAN-00:10 | 16666.62 | 03-JUL-14:20 |
EnergyTransfer:Zone:SMSTORE5 | 47.48 | 0.00 | 01-JAN-00:10 | 8745.85 | 03-JUL-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 1.21 | 0.00 | 01-JAN-00:10 | 7860.28 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 1.21 | 0.00 | 01-JAN-00:10 | 7860.28 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 46.27 | 0.00 | 01-JAN-00:10 | 8745.85 | 03-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 46.27 | 0.00 | 01-JAN-00:10 | 8745.85 | 03-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE6 | 46.79 | 0.00 | 01-JAN-00:10 | 8707.60 | 03-JUL-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 1.29 | 0.00 | 01-JAN-00:10 | 8051.37 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 1.29 | 0.00 | 01-JAN-00:10 | 8051.37 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 45.50 | 0.00 | 01-JAN-00:10 | 8707.60 | 03-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 45.50 | 0.00 | 01-JAN-00:10 | 8707.60 | 03-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE7 | 45.69 | 0.00 | 01-JAN-00:10 | 9024.17 | 27-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 1.62 | 0.00 | 01-JAN-00:10 | 9024.17 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 1.62 | 0.00 | 01-JAN-00:10 | 9024.17 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 44.07 | 0.00 | 01-JAN-00:10 | 8766.87 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 44.07 | 0.00 | 01-JAN-00:10 | 8766.87 | 03-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE8 | 50.28 | 0.00 | 01-JAN-00:10 | 13543.41 | 27-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 3.17 | 0.00 | 01-JAN-00:10 | 13543.41 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 3.17 | 0.00 | 01-JAN-00:10 | 13543.41 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 47.11 | 0.00 | 01-JAN-00:10 | 10290.69 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 47.11 | 0.00 | 01-JAN-00:10 | 10290.69 | 03-JUL-13:00 |
EnergyTransfer:HVAC | 767.14 | 0.00 | 01-JAN-00:10 | 152202.70 | 26-JUL-14:10 |
HeatingCoils:EnergyTransfer | 32.87 | 0.00 | 01-JAN-00:10 | 85163.08 | 27-DEC-08:10 |
CoolingCoils:EnergyTransfer | 734.26 | 0.00 | 01-JAN-00:10 | 152202.70 | 26-JUL-14:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 1.404 | -146.922 | 0.000 | 0.000 | 23.907 | 116.248 | 26.249 | 21.412 | 0.000 | 7.111 | 0.003 | 0.000 | -8.646 | 0.000 | -13.317 | -27.446 |
SMSTORE1 | 0.000 | 0.000 | 0.405 | -80.275 | 0.000 | 0.000 | 11.803 | 68.266 | 13.125 | 10.620 | 0.000 | 3.827 | 0.001 | 0.000 | -4.517 | 0.000 | -6.504 | -16.749 |
SMSTORE2 | 0.000 | 0.000 | 1.034 | -59.166 | 0.000 | 0.000 | 7.149 | 49.007 | 10.421 | 10.570 | 0.000 | 3.760 | 0.001 | 0.000 | -4.546 | 0.000 | -6.658 | -11.571 |
SMSTORE3 | 0.000 | 0.000 | 1.100 | -58.561 | 0.000 | 0.000 | 7.165 | 49.007 | 10.421 | 10.584 | 0.000 | 3.759 | 0.000 | 0.000 | -4.505 | 0.000 | -6.595 | -12.374 |
SMSTORE4 | 0.000 | 0.000 | 1.240 | -55.910 | 0.000 | 0.000 | 7.188 | 49.007 | 10.421 | 10.617 | 0.000 | 3.762 | 0.000 | 0.000 | -4.432 | 0.000 | -6.497 | -15.396 |
LGSTORE2 | 0.000 | 0.000 | 2.118 | -90.968 | 0.000 | 0.000 | 24.793 | 54.161 | 19.173 | 21.386 | 0.000 | 6.807 | 0.000 | 0.000 | -8.500 | 0.000 | -11.783 | -17.186 |
SMSTORE5 | 0.000 | 0.000 | 1.214 | -46.267 | 0.000 | 0.000 | 12.407 | 27.807 | 9.586 | 10.695 | 0.000 | 3.782 | 0.001 | 0.000 | -4.225 | 0.000 | -6.366 | -8.631 |
SMSTORE6 | 0.000 | 0.000 | 1.294 | -45.499 | 0.000 | 0.000 | 12.419 | 27.807 | 9.586 | 10.708 | 0.000 | 3.783 | 0.001 | 0.000 | -4.200 | 0.000 | -6.334 | -9.563 |
SMSTORE7 | 0.000 | 0.000 | 1.620 | -44.067 | 0.000 | 0.000 | 12.449 | 27.807 | 9.586 | 10.734 | 0.000 | 3.784 | 0.001 | 0.000 | -4.138 | 0.000 | -6.252 | -11.524 |
SMSTORE8 | 0.000 | 0.000 | 3.174 | -47.108 | 0.000 | 0.000 | 12.490 | 27.807 | 9.586 | 10.755 | 0.000 | 4.019 | 0.002 | 0.000 | -3.928 | 0.000 | -8.149 | -8.644 |
Total Facility | 0.000 | 0.000 | 14.602 | -674.743 | 0.000 | 0.000 | 131.770 | 496.921 | 128.154 | 128.082 | 0.000 | 44.392 | 0.011 | 0.000 | -51.638 | 0.000 | -78.455 | -139.085 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 23-AUG-07:02 | 0.00 | 0.00 | 0.00 | -43657.84 | 0.00 | 0.00 | 175.60 | 317.63 | 74.62 | 68.26 | 0.00 | 0.00 | 43104.71 | 0.00 | -0.00 | 0.00 | -82.98 | 0.00 |
SMSTORE1 | 23-AUG-07:02 | 0.00 | 0.00 | 0.00 | -23832.77 | 0.00 | 0.00 | 86.36 | 186.54 | 37.31 | 30.98 | 0.00 | 0.00 | 23534.17 | 0.00 | -0.00 | 0.00 | -42.58 | 0.00 |
SMSTORE2 | 23-AUG-06:02 | 0.00 | 0.00 | 0.00 | -26410.59 | 0.00 | 0.00 | 0.00 | 167.44 | 36.82 | 0.00 | 0.00 | 0.00 | 26334.66 | 0.00 | -118.46 | 0.00 | -9.87 | 0.00 |
SMSTORE3 | 23-AUG-06:02 | 0.00 | 0.00 | 0.00 | -26288.33 | 0.00 | 0.00 | 0.00 | 167.44 | 36.82 | 0.00 | 0.00 | 0.00 | 26213.51 | 0.00 | -119.45 | 0.00 | -9.99 | 0.00 |
SMSTORE4 | 23-AUG-06:02 | 0.00 | 0.00 | 0.00 | -26187.95 | 0.00 | 0.00 | 0.00 | 167.44 | 36.82 | 0.00 | 0.00 | 0.00 | 26110.02 | 0.00 | -116.67 | 0.00 | -9.67 | 0.00 |
LGSTORE2 | 23-AUG-07:02 | 0.00 | 0.00 | 0.00 | -42194.72 | 0.00 | 0.00 | 0.00 | 201.30 | 73.64 | 70.33 | 0.00 | 0.00 | 41924.24 | 0.00 | -0.00 | 0.00 | -74.79 | 0.00 |
SMSTORE5 | 02-OCT-07:02 | 0.00 | 0.00 | 0.00 | -21112.23 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 0.00 | 0.00 | 0.00 | 21088.00 | 0.00 | -58.65 | 0.00 | -57.30 | 0.00 |
SMSTORE6 | 02-OCT-07:02 | 0.00 | 0.00 | 0.00 | -21023.13 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 0.00 | 0.00 | 0.00 | 20997.74 | 0.00 | -57.98 | 0.00 | -56.80 | 0.00 |
SMSTORE7 | 02-OCT-07:02 | 0.00 | 0.00 | 0.00 | -20980.81 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 0.00 | 0.00 | 0.00 | 20953.71 | 0.00 | -57.42 | 0.00 | -55.66 | 0.00 |
SMSTORE8 | 02-OCT-07:02 | 0.00 | 0.00 | 0.00 | -22554.46 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 0.00 | 0.00 | 0.00 | 22535.43 | 0.00 | -58.49 | 0.00 | -62.66 | 0.00 |
Total Facility | 02-OCT-07:02 | 0.00 | 0.00 | 0.00 | -202973.28 | 0.00 | 0.00 | 546.97 | 6142.12 | 1452.23 | 0.00 | 0.00 | 0.00 | 196095.29 | 0.00 | -639.46 | 0.00 | -623.87 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 19-DEC-08:61 | 0.00 | 0.00 | 62699.40 | 0.00 | 0.00 | 0.00 | 245.10 | 317.63 | 74.62 | 101.46 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -843.59 | -62594.62 |
SMSTORE1 | 28-JAN-08:61 | 0.00 | 0.00 | 32228.26 | 0.00 | 0.00 | 0.00 | 0.00 | 186.54 | 36.82 | 330.54 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -506.87 | -32275.29 |
SMSTORE2 | 28-JAN-07:02 | 0.00 | 0.00 | 26160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 167.44 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -563.53 | 0.00 | -80.89 | -25720.17 |
SMSTORE3 | 27-DEC-07:02 | 0.00 | 0.00 | 30603.84 | 0.00 | 0.00 | 0.00 | 0.00 | 167.44 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -567.85 | 0.00 | -46.08 | -30194.17 |
SMSTORE4 | 27-DEC-07:02 | 0.00 | 0.00 | 32141.17 | 0.00 | 0.00 | 0.00 | 0.00 | 167.44 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -560.85 | 0.00 | -45.67 | -31738.91 |
LGSTORE2 | 19-DEC-08:61 | 0.00 | 0.00 | 58460.11 | 0.00 | 0.00 | 0.00 | 0.00 | 201.30 | 73.64 | 121.88 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -823.79 | -58033.14 |
SMSTORE5 | 19-DEC-08:61 | 0.00 | 0.00 | 30172.79 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 63.25 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -458.38 | -29917.84 |
SMSTORE6 | 19-DEC-08:61 | 0.00 | 0.00 | 30057.63 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 65.88 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -456.08 | -29807.61 |
SMSTORE7 | 19-DEC-08:61 | 0.00 | 0.00 | 30086.52 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 74.12 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -448.61 | -29852.20 |
SMSTORE8 | 19-DEC-08:61 | 0.00 | 0.00 | 33028.18 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 106.07 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -421.98 | -32852.45 |
Total Facility | 28-JAN-08:61 | 0.00 | 0.00 | 280743.19 | 0.00 | 0.00 | 0.00 | 346.82 | 6142.12 | 1450.75 | 4281.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5789.68 | -287174.64 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.5897 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.5897 | 0.1589 | 1.0000 | Not calculated | 0.4115 | 0.1589 | ||
PSZ-AC_2:2 | 1.3522 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3522 | 0.1522 | 1.0000 | Not calculated | 0.2057 | 0.1522 | ||
PSZ-AC_3:3 | 1.3921 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3921 | 0.1478 | 1.0000 | Not calculated | 0.2057 | 0.1478 | ||
PSZ-AC_4:4 | 1.3831 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3831 | 0.1488 | 1.0000 | Not calculated | 0.2057 | 0.1488 | ||
PSZ-AC_5:5 | 1.3840 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3840 | 0.1487 | 1.0000 | Not calculated | 0.2057 | 0.1487 | ||
PSZ-AC_6:6 | 2.3671 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.3671 | 0.1738 | 1.0000 | Not calculated | 0.4115 | 0.1738 | ||
PSZ-AC_7:7 | 1.2304 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2304 | 0.1672 | 1.0000 | Not calculated | 0.2057 | 0.1672 | ||
PSZ-AC_8:8 | 1.2244 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2244 | 0.1680 | 1.0000 | Not calculated | 0.2057 | 0.1680 | ||
PSZ-AC_9:9 | 1.2256 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2256 | 0.1679 | 1.0000 | Not calculated | 0.2057 | 0.1679 | ||
PSZ-AC_10:10 | 1.3796 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3796 | 0.1491 | 1.0000 | Not calculated | 0.2057 | 0.1491 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.5897 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.5897 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1589 | ||
PSZ-AC_2:2 | 1.3522 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3522 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1522 | ||
PSZ-AC_3:3 | 1.3921 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3921 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1478 | ||
PSZ-AC_4:4 | 1.3831 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3831 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1488 | ||
PSZ-AC_5:5 | 1.3840 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3840 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1487 | ||
PSZ-AC_6:6 | 2.3671 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.3671 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1738 | ||
PSZ-AC_7:7 | 1.2304 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2304 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1672 | ||
PSZ-AC_8:8 | 1.2244 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2244 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1680 | ||
PSZ-AC_9:9 | 1.2256 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2256 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1679 | ||
PSZ-AC_10:10 | 1.3796 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3796 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1491 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.5897 | 2.5897 | 2.5897 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3522 | 1.3522 | 1.3522 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3921 | 1.3921 | 1.3921 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3831 | 1.3831 | 1.3831 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3840 | 1.3840 | 1.3840 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.3671 | 2.3671 | 2.3671 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2304 | 1.2304 | 1.2304 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2244 | 1.2244 | 1.2244 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2256 | 1.2256 | 1.2256 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3796 | 1.3796 | 1.3796 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.5897 | 2.5897 | 2.5897 | 2.5897 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.3522 | 1.3522 | 1.3522 | 1.3522 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.3921 | 1.3921 | 1.3921 | 1.3921 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.3831 | 1.3831 | 1.3831 | 1.3831 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.3840 | 1.3840 | 1.3840 | 1.3840 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.3671 | 2.3671 | 2.3671 | 2.3671 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.2304 | 1.2304 | 1.2304 | 1.2304 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.2244 | 1.2244 | 1.2244 | 1.2244 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.2256 | 1.2256 | 1.2256 | 1.2256 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.3796 | 1.3796 | 1.3796 | 1.3796 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.5897 | 2.5897 | 2.5897 | No | 0.4115 | 0.3657 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3522 | 1.3522 | 1.3522 | No | 0.2057 | 0.3881 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3921 | 1.3921 | 1.3921 | No | 0.2057 | 0.3825 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3831 | 1.3831 | 1.3831 | No | 0.2057 | 0.3781 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3840 | 1.3840 | 1.3840 | No | 0.2057 | 0.3708 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.3671 | 2.3671 | 2.3671 | No | 0.4115 | 0.3804 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2304 | 1.2304 | 1.2304 | No | 0.2057 | 0.3583 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2244 | 1.2244 | 1.2244 | No | 0.2057 | 0.3585 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2256 | 1.2256 | 1.2256 | No | 0.2057 | 0.3495 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3796 | 1.3796 | 1.3796 | No | 0.2057 | 0.2916 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.5897 | 2.5897 | 2.5897 | 2.5897 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.3522 | 1.3522 | 1.3522 | 1.3522 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.3921 | 1.3921 | 1.3921 | 1.3921 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.3831 | 1.3831 | 1.3831 | 1.3831 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.3840 | 1.3840 | 1.3840 | 1.3840 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.3671 | 2.3671 | 2.3671 | 2.3671 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.2304 | 1.2304 | 1.2304 | 1.2304 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.2244 | 1.2244 | 1.2244 | 1.2244 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.2256 | 1.2256 | 1.2256 | 1.2256 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.3796 | 1.3796 | 1.3796 | 1.3796 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 41.09 | 106453.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 197.47 | 45140.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 496.92 | 30804.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 100.64 | 7723.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 119.26 | 9113.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 61.39 | 11809.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 1103.84 |
Natural Gas | 0.00 | 41.09 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1144.93 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 237.73 |
Space Heating | 0.00 |
Space Cooling | 94.47 |
Fans (All) | 57.05 |
Service Water Heating | 29.37 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 528.07 |
Subtotal | 528.07 |
Natural Gas [MJ/m2] | |
Space Heating | 19.66 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 19.66 |
Subtotal | 19.66 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 43.40 |
Space Heating | 3.59 |
Space Cooling | 17.25 |
Fans (All) | 10.42 |
Service Water Heating | 5.36 |
Receptacle Equipment | 11.19 |
Miscellaneous | 8.79 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8588.17 | 171.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8557.67 | 202.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8601.33 | 158.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8676.67 | 83.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8692.33 | 67.67 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8695.33 | 64.67 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8695.83 | 64.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8647.83 | 112.17 | 0.00 | 0.00 | 0.00 |
Min | 8557.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 202.33 | 0.00 | 0.00 | 0.00 |
Average | 8667.52 | 92.48 | 0.00 | 0.00 | 0.00 |
Sum | 86675.17 | 924.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25429.67 | 45.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25429.50 | 45.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25432.17 | 42.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93090.00 | 121.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45856.00 | 56.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45856.00 | 56.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45857.00 | 55.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45846.00 | 66.00 | 0.00 | 0.00 | 0.00 |
Min | 25429.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93090.00 | 121.00 | 0.00 | 0.00 | 0.00 |
Average | 48561.43 | 48.77 | 0.00 | 0.00 | 0.00 |
Sum | 485614.33 | 487.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8538.17 | 221.83 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8735.17 | 24.83 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8330.33 | 429.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8307.67 | 452.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8350.00 | 410.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8470.83 | 289.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8480.17 | 279.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8484.17 | 275.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8489.67 | 270.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8431.33 | 328.67 | 0.00 | 0.00 | 0.00 |
Min | 8307.67 | 24.83 | 0.00 | 0.00 | 0.00 |
Max | 8735.17 | 452.33 | 0.00 | 0.00 | 0.00 |
Average | 8461.75 | 298.25 | 0.00 | 0.00 | 0.00 |
Sum | 84617.50 | 2982.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 88978.67 | 62.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43766.50 | 10.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25420.00 | 55.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25420.67 | 54.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25417.83 | 57.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93002.33 | 208.67 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45810.17 | 101.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45809.67 | 102.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45807.17 | 104.83 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45785.83 | 126.17 | 0.00 | 0.00 | 0.00 |
Min | 25417.83 | 10.50 | 0.00 | 0.00 | 0.00 |
Max | 93002.33 | 208.67 | 0.00 | 0.00 | 0.00 |
Average | 48521.88 | 88.32 | 0.00 | 0.00 | 0.00 |
Sum | 485218.83 | 883.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:43
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.586738E+10 | 7575.53 | 28-JAN-00:25 | -0.6 | -4.4 | 0.120114E+10 | 1685.80 | 01-JAN-18:00 | -0.6 | -4.4 |
February | 0.544257E+10 | 7486.43 | 03-FEB-00:12 | 0.00 | -4.2 | 0.115008E+10 | 1685.85 | 12-FEB-18:19 | 19.43 | 7.64 |
March | 0.655387E+10 | 7999.54 | 16-MAR-16:10 | 22.02 | 8.30 | 0.133852E+10 | 1685.85 | 12-MAR-17:40 | 22.02 | 8.30 |
April | 0.106804E+11 | 13230.16 | 30-APR-16:04 | 30.50 | 12.87 | 0.135729E+10 | 1685.86 | 29-APR-12:00 | 30.50 | 12.87 |
May | 0.150473E+11 | 39810.68 | 31-MAY-07:02 | 25.37 | 12.75 | 0.140145E+10 | 1685.95 | 21-MAY-17:00 | 25.37 | 12.75 |
June | 0.184703E+11 | 42202.39 | 17-JUN-07:02 | 24.78 | 15.73 | 0.135464E+10 | 1685.95 | 18-JUN-17:10 | 37.12 | 16.85 |
July | 0.197540E+11 | 42187.53 | 03-JUL-07:01 | 27.98 | 16.41 | 0.141295E+10 | 1686.01 | 21-JUL-12:09 | 27.30 | 21.88 |
August | 0.193886E+11 | 43652.45 | 23-AUG-07:02 | 22.07 | 13.03 | 0.139419E+10 | 1686.01 | 18-AUG-12:09 | 22.07 | 13.03 |
September | 0.178936E+11 | 39518.22 | 20-SEP-07:02 | 22.48 | 15.94 | 0.136523E+10 | 1686.01 | 08-SEP-12:09 | 22.48 | 15.94 |
October | 0.138235E+11 | 43640.89 | 02-OCT-07:02 | 22.02 | 15.21 | 0.140887E+10 | 1686.01 | 08-OCT-17:00 | 23.90 | 16.81 |
November | 0.824325E+10 | 10610.23 | 09-NOV-15:00 | 23.30 | 12.64 | 0.130015E+10 | 1685.94 | 03-NOV-12:39 | 23.30 | 12.64 |
December | 0.575841E+10 | 7466.80 | 30-DEC-00:03 | 0.00 | -2.4 | 0.118594E+10 | 1685.84 | 10-DEC-13:20 | 0.00 | -2.4 |
Annual Sum or Average | 0.146923E+12 | 0.158704E+11 | ||||||||
Minimum of Months | 0.544257E+10 | 7466.80 | -0.6 | -4.4 | 0.115008E+10 | 1685.80 | -0.6 | -4.4 | ||
Maximum of Months | 0.197540E+11 | 43652.45 | 30.50 | 16.41 | 0.141295E+10 | 1686.01 | 37.12 | 21.88 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.291953E+10 | 3478.78 | 03-JAN-14:50 | 20.50 | 8.55 | 0.651018E+09 | 842.90 | 16-JAN-18:00 | 12.20 | 7.35 |
February | 0.306449E+10 | 18187.28 | 12-FEB-18:59 | 18.30 | 7.48 | 0.606786E+09 | 842.90 | 20-FEB-17:10 | 22.02 | 8.16 |
March | 0.404458E+10 | 19181.20 | 19-MAR-17:34 | 16.67 | 7.44 | 0.684531E+09 | 842.90 | 19-MAR-16:19 | 16.67 | 7.44 |
April | 0.644832E+10 | 18372.14 | 22-APR-18:07 | 18.03 | 6.57 | 0.675829E+09 | 842.91 | 09-APR-17:00 | 18.03 | 6.57 |
May | 0.847575E+10 | 20884.90 | 31-MAY-07:02 | 25.37 | 12.75 | 0.698491E+09 | 842.94 | 28-MAY-12:09 | 25.37 | 12.75 |
June | 0.991961E+10 | 23301.03 | 14-JUN-07:02 | 22.12 | 9.77 | 0.676796E+09 | 842.95 | 23-JUN-12:09 | 27.57 | 16.83 |
July | 0.104522E+11 | 21898.95 | 03-JUL-07:01 | 27.98 | 16.41 | 0.706348E+09 | 842.99 | 07-JUL-12:39 | 25.60 | 19.09 |
August | 0.102626E+11 | 23830.75 | 23-AUG-07:02 | 22.07 | 13.03 | 0.696493E+09 | 842.98 | 18-AUG-12:09 | 22.07 | 13.03 |
September | 0.948984E+10 | 20923.74 | 18-SEP-07:02 | 21.05 | 15.73 | 0.680250E+09 | 842.97 | 08-SEP-12:09 | 21.05 | 15.73 |
October | 0.774365E+10 | 22528.13 | 02-OCT-07:02 | 22.02 | 15.21 | 0.700842E+09 | 842.98 | 08-OCT-12:00 | 23.30 | 16.64 |
November | 0.467562E+10 | 19224.95 | 05-NOV-17:06 | 16.83 | 7.70 | 0.664310E+09 | 842.95 | 03-NOV-12:30 | 16.83 | 7.70 |
December | 0.277957E+10 | 3436.90 | 12-DEC-09:03 | 2.38 | -1.5 | 0.643372E+09 | 842.90 | 25-DEC-18:00 | 8.30 | 4.75 |
Annual Sum or Average | 0.802758E+11 | 0.808507E+10 | ||||||||
Minimum of Months | 0.277957E+10 | 3436.90 | 2.38 | -1.5 | 0.606786E+09 | 842.90 | 8.30 | 4.75 | ||
Maximum of Months | 0.104522E+11 | 23830.75 | 27.98 | 16.41 | 0.706348E+09 | 842.99 | 27.57 | 19.09 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233033E+10 | 4093.18 | 06-JAN-08:61 | -0.6 | -4.4 | 0.366513E+09 | 758.83 | 07-JAN-13:00 | 13.90 | 6.19 |
February | 0.227207E+10 | 4275.28 | 10-FEB-08:61 | -2.0 | -4.5 | 0.351000E+09 | 842.89 | 11-FEB-13:20 | 18.50 | 6.88 |
March | 0.285963E+10 | 4273.07 | 16-MAR-14:00 | 22.80 | 9.34 | 0.415795E+09 | 842.90 | 25-MAR-12:00 | 19.40 | 8.67 |
April | 0.436788E+10 | 8513.69 | 20-APR-06:03 | 20.60 | 8.90 | 0.409482E+09 | 842.91 | 29-APR-12:09 | 27.30 | 15.21 |
May | 0.611595E+10 | 22972.24 | 31-MAY-06:02 | 23.58 | 11.53 | 0.426472E+09 | 842.90 | 27-MAY-12:09 | 23.58 | 11.53 |
June | 0.754431E+10 | 24719.60 | 06-JUN-06:02 | 22.57 | 13.18 | 0.417818E+09 | 842.92 | 03-JUN-12:09 | 22.57 | 13.18 |
July | 0.779101E+10 | 22929.93 | 03-JUL-06:01 | 26.88 | 16.13 | 0.420918E+09 | 842.96 | 08-JUL-12:09 | 28.68 | 20.13 |
August | 0.779001E+10 | 26408.13 | 23-AUG-06:02 | 20.28 | 12.08 | 0.432345E+09 | 842.95 | 12-AUG-12:09 | 20.28 | 12.08 |
September | 0.703716E+10 | 24094.26 | 18-SEP-06:02 | 18.68 | 14.33 | 0.411192E+09 | 842.94 | 09-SEP-12:09 | 18.68 | 14.33 |
October | 0.548415E+10 | 24287.01 | 02-OCT-06:01 | 22.70 | 15.09 | 0.419898E+09 | 842.94 | 28-OCT-12:20 | 21.13 | 13.40 |
November | 0.335745E+10 | 5535.65 | 09-NOV-14:00 | 23.30 | 12.45 | 0.389506E+09 | 842.90 | 18-NOV-13:00 | 19.40 | 6.83 |
December | 0.221695E+10 | 4102.57 | 22-DEC-08:61 | -1.3 | -3.8 | 0.359662E+09 | 842.89 | 09-DEC-13:09 | -1.3 | -3.8 |
Annual Sum or Average | 0.591669E+11 | 0.482060E+10 | ||||||||
Minimum of Months | 0.221695E+10 | 4093.18 | -2.0 | -4.5 | 0.351000E+09 | 758.83 | -1.3 | -3.8 | ||
Maximum of Months | 0.779101E+10 | 26408.13 | 26.88 | 16.13 | 0.432345E+09 | 842.96 | 28.68 | 20.13 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.216895E+10 | 4047.02 | 06-JAN-08:61 | -0.6 | -4.4 | 0.361368E+09 | 747.97 | 07-JAN-13:00 | 13.90 | 6.19 |
February | 0.214126E+10 | 4056.64 | 01-FEB-08:61 | -0.7 | -3.3 | 0.347611E+09 | 842.89 | 11-FEB-13:30 | 18.60 | 6.82 |
March | 0.271241E+10 | 4175.35 | 16-MAR-14:00 | 22.80 | 9.34 | 0.414329E+09 | 842.90 | 25-MAR-12:00 | 19.40 | 8.67 |
April | 0.431867E+10 | 8365.57 | 20-APR-06:03 | 20.60 | 8.90 | 0.409396E+09 | 842.91 | 29-APR-12:09 | 27.30 | 15.21 |
May | 0.613281E+10 | 22863.76 | 31-MAY-06:02 | 23.58 | 11.53 | 0.426468E+09 | 842.90 | 27-MAY-12:09 | 23.58 | 11.53 |
June | 0.759130E+10 | 24625.46 | 06-JUN-06:02 | 22.57 | 13.18 | 0.417820E+09 | 842.92 | 03-JUN-12:09 | 22.57 | 13.18 |
July | 0.783837E+10 | 22924.17 | 03-JUL-06:01 | 26.88 | 16.13 | 0.420919E+09 | 842.96 | 08-JUL-12:09 | 28.68 | 20.13 |
August | 0.783680E+10 | 26285.88 | 23-AUG-06:02 | 20.28 | 12.08 | 0.432346E+09 | 842.95 | 12-AUG-12:09 | 20.28 | 12.08 |
September | 0.706662E+10 | 24496.21 | 11-SEP-06:02 | 16.05 | 10.85 | 0.411190E+09 | 842.94 | 09-SEP-12:09 | 16.05 | 10.85 |
October | 0.545870E+10 | 24200.19 | 02-OCT-06:01 | 22.70 | 15.09 | 0.419870E+09 | 842.94 | 28-OCT-12:20 | 21.13 | 13.40 |
November | 0.323150E+10 | 5463.02 | 09-NOV-14:00 | 23.30 | 12.45 | 0.388520E+09 | 842.90 | 18-NOV-13:00 | 19.40 | 6.83 |
December | 0.206439E+10 | 3858.97 | 07-DEC-08:61 | 0.15 | -2.4 | 0.355002E+09 | 842.89 | 09-DEC-13:09 | 17.70 | 7.41 |
Annual Sum or Average | 0.585618E+11 | 0.480484E+10 | ||||||||
Minimum of Months | 0.206439E+10 | 3858.97 | -0.7 | -4.4 | 0.347611E+09 | 747.97 | 13.90 | 6.19 | ||
Maximum of Months | 0.783837E+10 | 26285.88 | 26.88 | 16.13 | 0.432346E+09 | 842.96 | 28.68 | 20.13 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194177E+10 | 3847.10 | 05-JAN-08:61 | 0.28 | -4.7 | 0.354859E+09 | 731.30 | 07-JAN-13:00 | 13.90 | 6.19 |
February | 0.192885E+10 | 3569.20 | 09-FEB-08:61 | 1.78 | -1.8 | 0.342484E+09 | 842.89 | 11-FEB-13:00 | 18.90 | 6.65 |
March | 0.243688E+10 | 3919.58 | 16-MAR-16:10 | 22.02 | 8.30 | 0.411414E+09 | 842.89 | 25-MAR-12:20 | 19.07 | 8.79 |
April | 0.406954E+10 | 6873.53 | 20-APR-06:03 | 20.60 | 8.90 | 0.409080E+09 | 842.91 | 29-APR-12:09 | 27.30 | 15.21 |
May | 0.590478E+10 | 22765.96 | 31-MAY-06:02 | 23.58 | 11.53 | 0.426414E+09 | 842.90 | 27-MAY-12:09 | 23.58 | 11.53 |
June | 0.739112E+10 | 24527.56 | 06-JUN-06:02 | 22.57 | 13.18 | 0.417780E+09 | 842.92 | 03-JUN-12:09 | 22.57 | 13.18 |
July | 0.765068E+10 | 22844.71 | 03-JUL-06:01 | 26.88 | 16.13 | 0.420881E+09 | 842.97 | 08-JUL-12:09 | 28.68 | 20.13 |
August | 0.764087E+10 | 26185.51 | 23-AUG-06:02 | 20.28 | 12.08 | 0.432308E+09 | 842.95 | 12-AUG-12:09 | 20.28 | 12.08 |
September | 0.686879E+10 | 23962.43 | 18-SEP-06:02 | 18.68 | 14.33 | 0.411151E+09 | 842.95 | 09-SEP-12:09 | 18.68 | 14.33 |
October | 0.523265E+10 | 24067.17 | 02-OCT-06:01 | 22.70 | 15.09 | 0.419734E+09 | 842.94 | 28-OCT-12:30 | 21.40 | 13.50 |
November | 0.299763E+10 | 5259.03 | 09-NOV-14:00 | 23.30 | 12.45 | 0.386606E+09 | 842.90 | 18-NOV-13:00 | 19.40 | 6.83 |
December | 0.184681E+10 | 3614.70 | 12-DEC-08:61 | 1.28 | -2.3 | 0.348812E+09 | 842.89 | 09-DEC-13:20 | 1.28 | -2.3 |
Annual Sum or Average | 0.559104E+11 | 0.478152E+10 | ||||||||
Minimum of Months | 0.184681E+10 | 3569.20 | 0.28 | -4.7 | 0.342484E+09 | 731.30 | 1.28 | -2.3 | ||
Maximum of Months | 0.765068E+10 | 26185.51 | 26.88 | 16.13 | 0.432308E+09 | 842.97 | 28.68 | 20.13 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.289632E+10 | 5123.40 | 04-JAN-20:30 | 6.65 | 0.29 | 0.117720E+10 | 2027.85 | 07-JAN-15:00 | 15.60 | 7.02 |
February | 0.286795E+10 | 6146.47 | 08-FEB-19:30 | 4.45 | 0.04 | 0.114681E+10 | 2247.76 | 04-FEB-15:00 | 4.45 | 0.04 |
March | 0.355827E+10 | 6739.69 | 16-MAR-14:50 | 22.80 | 8.82 | 0.139150E+10 | 2247.80 | 25-MAR-14:00 | 21.10 | 8.87 |
April | 0.637851E+10 | 11559.65 | 21-APR-14:30 | 32.20 | 15.35 | 0.140349E+10 | 2247.80 | 29-APR-14:09 | 30.10 | 15.60 |
May | 0.971588E+10 | 37398.68 | 30-MAY-07:02 | 25.78 | 12.49 | 0.145838E+10 | 2247.80 | 27-MAY-14:09 | 25.78 | 12.49 |
June | 0.124659E+11 | 39903.89 | 17-JUN-07:02 | 24.78 | 15.73 | 0.143077E+10 | 2247.94 | 03-JUN-14:30 | 24.78 | 15.73 |
July | 0.129071E+11 | 39455.29 | 03-JUL-07:01 | 27.98 | 16.41 | 0.143945E+10 | 2248.09 | 01-JUL-14:20 | 27.98 | 16.41 |
August | 0.129159E+11 | 42189.78 | 23-AUG-07:02 | 22.07 | 13.03 | 0.148122E+10 | 2247.84 | 12-AUG-14:09 | 22.07 | 13.03 |
September | 0.115586E+11 | 38377.75 | 18-SEP-07:02 | 21.05 | 15.73 | 0.141044E+10 | 2247.90 | 23-SEP-14:00 | 28.30 | 18.50 |
October | 0.845764E+10 | 40972.85 | 02-OCT-07:02 | 22.02 | 15.21 | 0.143308E+10 | 2247.93 | 14-OCT-14:00 | 19.40 | 15.20 |
November | 0.454127E+10 | 9058.65 | 09-NOV-14:00 | 23.30 | 12.45 | 0.130374E+10 | 2247.80 | 18-NOV-15:00 | 19.40 | 6.83 |
December | 0.270569E+10 | 5594.53 | 22-DEC-09:43 | 4.77 | 0.23 | 0.116526E+10 | 2247.76 | 09-DEC-15:00 | 4.77 | 0.23 |
Annual Sum or Average | 0.909691E+11 | 0.162414E+11 | ||||||||
Minimum of Months | 0.270569E+10 | 5123.40 | 4.45 | 0.04 | 0.114681E+10 | 2027.85 | 4.45 | 0.04 | ||
Maximum of Months | 0.129159E+11 | 42189.78 | 32.20 | 16.41 | 0.148122E+10 | 2248.09 | 30.10 | 18.50 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136368E+10 | 2530.89 | 04-JAN-20:30 | 6.65 | 0.29 | 0.586051E+09 | 1005.17 | 07-JAN-15:00 | 15.60 | 7.02 |
February | 0.135987E+10 | 3074.64 | 08-FEB-19:40 | 4.27 | -0.4 | 0.571152E+09 | 1123.85 | 18-FEB-15:30 | 19.70 | 8.67 |
March | 0.169872E+10 | 3407.18 | 16-MAR-15:00 | 22.80 | 8.72 | 0.693541E+09 | 1123.87 | 25-MAR-14:00 | 21.10 | 8.87 |
April | 0.322861E+10 | 6008.96 | 21-APR-14:40 | 32.20 | 15.40 | 0.701526E+09 | 1123.87 | 29-APR-14:09 | 30.10 | 15.60 |
May | 0.500204E+10 | 19214.64 | 30-MAY-07:02 | 25.78 | 12.49 | 0.729136E+09 | 1123.87 | 27-MAY-14:09 | 25.78 | 12.49 |
June | 0.645132E+10 | 20510.10 | 17-JUN-07:02 | 24.78 | 15.73 | 0.715333E+09 | 1123.94 | 03-JUN-14:30 | 24.78 | 15.73 |
July | 0.668617E+10 | 20292.51 | 03-JUL-07:01 | 27.98 | 16.41 | 0.719666E+09 | 1124.02 | 01-JUL-14:20 | 27.98 | 16.41 |
August | 0.667795E+10 | 20988.29 | 28-AUG-07:02 | 22.38 | 15.17 | 0.740551E+09 | 1123.89 | 12-AUG-14:09 | 22.38 | 15.17 |
September | 0.596703E+10 | 19772.46 | 18-SEP-07:02 | 21.05 | 15.73 | 0.705183E+09 | 1123.92 | 23-SEP-14:00 | 28.30 | 18.50 |
October | 0.432032E+10 | 21108.52 | 02-OCT-07:02 | 22.02 | 15.21 | 0.716502E+09 | 1123.93 | 14-OCT-14:00 | 19.40 | 15.20 |
November | 0.223350E+10 | 4645.67 | 09-NOV-14:00 | 23.30 | 12.45 | 0.651069E+09 | 1123.87 | 18-NOV-15:00 | 19.40 | 6.83 |
December | 0.127841E+10 | 3343.15 | 26-DEC-20:13 | 1.83 | -0.3 | 0.580296E+09 | 1122.91 | 09-DEC-15:30 | 1.83 | -0.3 |
Annual Sum or Average | 0.462676E+11 | 0.811001E+10 | ||||||||
Minimum of Months | 0.127841E+10 | 2530.89 | 1.83 | -0.4 | 0.571152E+09 | 1005.17 | 1.83 | -0.3 | ||
Maximum of Months | 0.668617E+10 | 21108.52 | 32.20 | 16.41 | 0.740551E+09 | 1124.02 | 30.10 | 18.50 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129777E+10 | 3297.01 | 27-JAN-10:13 | 2.03 | -3.7 | 0.583109E+09 | 998.08 | 07-JAN-15:00 | 2.03 | -3.7 |
February | 0.129391E+10 | 2992.67 | 08-FEB-19:20 | 4.63 | 0.20 | 0.568697E+09 | 1123.85 | 11-FEB-15:09 | 19.50 | 6.65 |
March | 0.161621E+10 | 3304.35 | 16-MAR-15:00 | 22.80 | 8.72 | 0.691045E+09 | 1123.87 | 25-MAR-14:00 | 21.10 | 8.87 |
April | 0.314972E+10 | 5950.13 | 21-APR-14:40 | 32.20 | 15.40 | 0.701189E+09 | 1123.87 | 29-APR-14:09 | 30.10 | 15.60 |
May | 0.493665E+10 | 19136.58 | 30-MAY-07:02 | 25.78 | 12.49 | 0.729118E+09 | 1123.87 | 27-MAY-14:09 | 25.78 | 12.49 |
June | 0.639379E+10 | 20424.51 | 17-JUN-07:02 | 24.78 | 15.73 | 0.715326E+09 | 1123.94 | 03-JUN-14:30 | 24.78 | 15.73 |
July | 0.663161E+10 | 20214.06 | 03-JUL-07:01 | 27.98 | 16.41 | 0.719657E+09 | 1124.02 | 01-JUL-14:20 | 27.98 | 16.41 |
August | 0.662463E+10 | 20910.68 | 28-AUG-07:02 | 22.38 | 15.17 | 0.740545E+09 | 1123.89 | 12-AUG-14:09 | 22.38 | 15.17 |
September | 0.591435E+10 | 19692.42 | 18-SEP-07:02 | 21.05 | 15.73 | 0.705176E+09 | 1123.92 | 23-SEP-14:00 | 28.30 | 18.50 |
October | 0.425479E+10 | 21019.44 | 02-OCT-07:02 | 22.02 | 15.21 | 0.716375E+09 | 1123.92 | 14-OCT-14:00 | 19.40 | 15.20 |
November | 0.216122E+10 | 4568.37 | 09-NOV-14:00 | 23.30 | 12.45 | 0.649478E+09 | 1123.87 | 18-NOV-15:00 | 19.40 | 6.83 |
December | 0.122499E+10 | 3348.04 | 26-DEC-20:20 | 1.83 | -0.3 | 0.577723E+09 | 1114.58 | 09-DEC-15:30 | 1.83 | -0.3 |
Annual Sum or Average | 0.454997E+11 | 0.809744E+10 | ||||||||
Minimum of Months | 0.122499E+10 | 2992.67 | 1.83 | -3.7 | 0.568697E+09 | 998.08 | 1.83 | -3.7 | ||
Maximum of Months | 0.663161E+10 | 21019.44 | 32.20 | 16.41 | 0.740545E+09 | 1124.02 | 30.10 | 18.50 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111689E+10 | 2442.35 | 04-JAN-20:00 | 7.20 | 0.59 | 0.576896E+09 | 997.42 | 03-JAN-17:10 | 7.20 | 0.59 |
February | 0.111983E+10 | 2897.82 | 08-FEB-19:00 | 5.00 | 0.53 | 0.562676E+09 | 1123.85 | 11-FEB-15:30 | 19.70 | 6.77 |
March | 0.140559E+10 | 3069.68 | 16-MAR-15:00 | 22.80 | 8.72 | 0.684554E+09 | 1123.87 | 25-MAR-14:00 | 21.10 | 8.87 |
April | 0.296054E+10 | 5839.14 | 21-APR-14:40 | 32.20 | 15.40 | 0.700018E+09 | 1123.87 | 29-APR-14:09 | 30.10 | 15.60 |
May | 0.481345E+10 | 18865.53 | 30-MAY-07:02 | 25.78 | 12.49 | 0.729062E+09 | 1123.87 | 27-MAY-14:09 | 25.78 | 12.49 |
June | 0.634942E+10 | 20349.05 | 17-JUN-07:02 | 24.78 | 15.73 | 0.715321E+09 | 1123.93 | 03-JUN-14:20 | 24.78 | 15.73 |
July | 0.661203E+10 | 20220.09 | 03-JUL-07:01 | 27.98 | 16.41 | 0.719653E+09 | 1124.01 | 01-JUL-14:20 | 27.98 | 16.41 |
August | 0.661302E+10 | 20888.55 | 28-AUG-07:02 | 22.38 | 15.17 | 0.740545E+09 | 1123.89 | 12-AUG-14:09 | 22.38 | 15.17 |
September | 0.588578E+10 | 19660.62 | 18-SEP-07:02 | 21.05 | 15.73 | 0.705170E+09 | 1123.92 | 23-SEP-14:00 | 28.30 | 18.50 |
October | 0.412695E+10 | 20977.13 | 02-OCT-07:02 | 22.02 | 15.21 | 0.715908E+09 | 1123.91 | 14-OCT-14:00 | 19.40 | 15.20 |
November | 0.199495E+10 | 4425.20 | 09-NOV-14:00 | 23.30 | 12.45 | 0.645257E+09 | 1123.87 | 18-NOV-15:00 | 19.40 | 6.83 |
December | 0.106884E+10 | 3342.16 | 26-DEC-19:13 | 1.87 | -0.3 | 0.572453E+09 | 1098.46 | 09-DEC-15:30 | 1.87 | -0.3 |
Annual Sum or Average | 0.440673E+11 | 0.806751E+10 | ||||||||
Minimum of Months | 0.106884E+10 | 2442.35 | 1.87 | -0.3 | 0.562676E+09 | 997.42 | 1.87 | -0.3 | ||
Maximum of Months | 0.661302E+10 | 20977.13 | 32.20 | 16.41 | 0.740545E+09 | 1124.01 | 30.10 | 18.50 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.741769E+09 | 2100.77 | 21-JAN-10:05 | 7.30 | 4.09 | 0.568999E+09 | 997.43 | 03-JAN-17:10 | 7.30 | 4.09 |
February | 0.755078E+09 | 2668.24 | 01-FEB-19:23 | 4.75 | -1.2 | 0.553735E+09 | 1123.31 | 18-FEB-15:00 | 20.00 | 8.60 |
March | 0.107154E+10 | 2819.31 | 16-MAR-14:20 | 22.80 | 9.14 | 0.675173E+09 | 1123.85 | 25-MAR-14:09 | 20.18 | 8.75 |
April | 0.297393E+10 | 6236.18 | 21-APR-14:20 | 32.20 | 15.31 | 0.698511E+09 | 1123.87 | 29-APR-14:09 | 30.10 | 15.60 |
May | 0.525080E+10 | 15271.98 | 30-MAY-07:02 | 25.78 | 12.49 | 0.729025E+09 | 1123.87 | 27-MAY-14:09 | 25.78 | 12.49 |
June | 0.725551E+10 | 21697.21 | 18-JUN-08:61 | 26.47 | 16.53 | 0.715403E+09 | 1123.95 | 03-JUN-14:20 | 26.47 | 16.53 |
July | 0.765879E+10 | 21966.18 | 03-JUL-07:01 | 27.98 | 16.41 | 0.719782E+09 | 1124.05 | 01-JUL-14:20 | 27.98 | 16.41 |
August | 0.769349E+10 | 22322.39 | 28-AUG-07:02 | 22.38 | 15.17 | 0.740668E+09 | 1123.94 | 05-AUG-14:20 | 22.38 | 15.17 |
September | 0.683757E+10 | 20179.19 | 18-SEP-07:02 | 21.05 | 15.73 | 0.705286E+09 | 1123.91 | 23-SEP-14:00 | 28.30 | 18.50 |
October | 0.435206E+10 | 22551.45 | 02-OCT-07:02 | 22.02 | 15.21 | 0.714306E+09 | 1123.90 | 28-OCT-14:09 | 22.98 | 13.61 |
November | 0.178023E+10 | 4614.56 | 09-NOV-14:00 | 23.30 | 12.45 | 0.639278E+09 | 1123.84 | 18-NOV-15:09 | 19.40 | 6.83 |
December | 0.738250E+09 | 2651.54 | 19-DEC-19:13 | 4.80 | -2.3 | 0.566983E+09 | 1084.95 | 09-DEC-15:30 | 4.80 | -2.3 |
Annual Sum or Average | 0.471090E+11 | 0.802715E+10 | ||||||||
Minimum of Months | 0.738250E+09 | 2100.77 | 4.75 | -2.3 | 0.553735E+09 | 997.43 | 4.80 | -2.3 | ||
Maximum of Months | 0.769349E+10 | 22551.45 | 32.20 | 16.53 | 0.740668E+09 | 1124.05 | 30.10 | 18.50 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.284488E+09 | 62674.77 | 06-JAN-08:61 | -0.6 |
February | 0.222935E+09 | 62693.89 | 03-FEB-08:61 | -2.0 |
March | 0.162677E+09 | 62685.28 | 02-MAR-08:61 | -0.9 |
April | 68382785.43 | 1342.02 | 20-APR-07:07 | 20.60 |
May | 31332183.30 | 2365.25 | 31-MAY-07:04 | 25.37 |
June | 37157804.44 | 2405.06 | 03-JUN-07:04 | 25.18 |
July | 26235821.15 | 2230.87 | 01-JUL-07:03 | 27.38 |
August | 33154353.01 | 2394.64 | 23-AUG-07:04 | 22.07 |
September | 32240191.80 | 2268.46 | 20-SEP-07:04 | 22.48 |
October | 26412128.78 | 2218.43 | 05-OCT-07:04 | 20.97 |
November | 0.104910E+09 | 62652.33 | 28-NOV-08:61 | 2.48 |
December | 0.374148E+09 | 62699.33 | 19-DEC-08:61 | -2.3 |
Annual Sum or Average | 0.140407E+10 | |||
Minimum of Months | 26235821.15 | 1342.02 | -2.3 | |
Maximum of Months | 0.374148E+09 | 62699.33 | 27.38 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 69310668.12 | 32228.29 | 28-JAN-08:61 | -0.6 |
February | 57897169.20 | 27210.67 | 03-FEB-08:61 | -2.0 |
March | 60004697.54 | 20154.25 | 02-MAR-08:61 | -0.9 |
April | 18555368.56 | 898.77 | 20-APR-07:07 | 20.60 |
May | 14612111.87 | 1273.61 | 31-MAY-07:04 | 25.37 |
June | 17687031.91 | 1369.31 | 14-JUN-07:04 | 22.12 |
July | 10931419.68 | 1221.38 | 22-JUL-07:04 | 23.07 |
August | 14255902.18 | 1349.53 | 23-AUG-07:04 | 22.07 |
September | 17004151.11 | 1246.12 | 18-SEP-07:04 | 21.05 |
October | 10879904.41 | 1217.61 | 05-OCT-07:04 | 20.97 |
November | 36290134.66 | 8617.58 | 28-NOV-08:61 | 2.48 |
December | 77116608.29 | 30794.03 | 27-DEC-08:61 | -3.4 |
Annual Sum or Average | 0.404545E+09 | |||
Minimum of Months | 10879904.41 | 898.77 | -3.4 | |
Maximum of Months | 77116608.29 | 32228.29 | 25.37 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 86395291.41 | 26160.32 | 28-JAN-07:02 | -2.9 |
February | 67212504.02 | 18819.12 | 03-FEB-07:02 | -5.1 |
March | 63039982.29 | 15025.16 | 02-MAR-07:02 | -1.6 |
April | 53340926.70 | 1635.41 | 30-APR-16:02 | 30.50 |
May | 0.100930E+09 | 2305.28 | 21-MAY-16:02 | 33.57 |
June | 0.165665E+09 | 3060.74 | 18-JUN-16:01 | 37.20 |
July | 0.139298E+09 | 3269.77 | 02-JUL-16:01 | 38.22 |
August | 0.117926E+09 | 2831.39 | 06-AUG-16:01 | 36.10 |
September | 59306635.18 | 2076.77 | 17-SEP-16:02 | 32.62 |
October | 22274440.36 | 1826.10 | 01-OCT-16:12 | 31.50 |
November | 41684576.96 | 10488.55 | 28-NOV-07:03 | 0.87 |
December | 0.117169E+09 | 25651.99 | 27-DEC-07:02 | -4.3 |
Annual Sum or Average | 0.103424E+10 | |||
Minimum of Months | 22274440.36 | 1635.41 | -5.1 | |
Maximum of Months | 0.165665E+09 | 26160.32 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104794E+09 | 29833.49 | 28-JAN-07:02 | -2.9 |
February | 75105954.94 | 22332.83 | 03-FEB-07:02 | -5.1 |
March | 66179664.16 | 19031.75 | 02-MAR-07:02 | -1.6 |
April | 55064607.34 | 1634.96 | 30-APR-16:02 | 30.50 |
May | 0.100683E+09 | 2304.20 | 21-MAY-16:02 | 33.57 |
June | 0.164666E+09 | 3058.75 | 18-JUN-16:01 | 37.20 |
July | 0.138362E+09 | 3268.35 | 02-JUL-16:01 | 38.22 |
August | 0.117379E+09 | 2829.26 | 06-AUG-16:01 | 36.10 |
September | 58433758.63 | 2075.28 | 17-SEP-16:02 | 32.62 |
October | 22389270.79 | 1823.09 | 01-OCT-16:12 | 31.50 |
November | 47338140.07 | 13206.53 | 28-NOV-07:03 | 0.87 |
December | 0.149370E+09 | 30603.82 | 27-DEC-07:02 | -4.3 |
Annual Sum or Average | 0.109976E+10 | |||
Minimum of Months | 22389270.79 | 1634.96 | -5.1 | |
Maximum of Months | 0.164666E+09 | 30603.82 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142091E+09 | 32131.11 | 28-JAN-07:02 | -2.9 |
February | 93522198.26 | 26430.90 | 03-FEB-07:02 | -5.1 |
March | 72868637.87 | 23705.56 | 02-MAR-07:02 | -1.6 |
April | 62092189.95 | 1643.34 | 30-APR-16:02 | 30.50 |
May | 0.102434E+09 | 2310.94 | 21-MAY-16:02 | 33.57 |
June | 0.167242E+09 | 3063.81 | 18-JUN-16:01 | 37.20 |
July | 0.139878E+09 | 3273.53 | 02-JUL-16:01 | 38.22 |
August | 0.119021E+09 | 2834.03 | 06-AUG-16:01 | 36.10 |
September | 60266024.69 | 2081.45 | 17-SEP-16:02 | 32.62 |
October | 22676273.84 | 1829.16 | 01-OCT-16:12 | 31.50 |
November | 55808274.34 | 15847.89 | 28-NOV-07:03 | 0.87 |
December | 0.201662E+09 | 32141.15 | 27-DEC-07:02 | -4.3 |
Annual Sum or Average | 0.123956E+10 | |||
Minimum of Months | 22676273.84 | 1643.34 | -5.1 | |
Maximum of Months | 0.201662E+09 | 32141.15 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.376421E+09 | 58436.21 | 06-JAN-08:61 | -0.6 |
February | 0.233456E+09 | 58450.81 | 02-FEB-08:61 | -1.7 |
March | 0.156837E+09 | 58452.60 | 02-MAR-08:61 | -0.9 |
April | 0.112444E+09 | 3280.71 | 30-APR-16:02 | 30.50 |
May | 0.114684E+09 | 4611.61 | 21-MAY-16:02 | 33.57 |
June | 0.122007E+09 | 6115.74 | 18-JUN-16:01 | 37.20 |
July | 0.132930E+09 | 6543.75 | 02-JUL-16:01 | 38.22 |
August | 0.122826E+09 | 5655.13 | 06-AUG-16:01 | 36.10 |
September | 76260722.49 | 4154.13 | 17-SEP-16:02 | 32.62 |
October | 50317460.32 | 3668.44 | 01-OCT-16:02 | 31.60 |
November | 0.119402E+09 | 58426.02 | 28-NOV-08:61 | 2.48 |
December | 0.500165E+09 | 58460.11 | 19-DEC-08:61 | -2.3 |
Annual Sum or Average | 0.211775E+10 | |||
Minimum of Months | 50317460.32 | 3280.71 | -2.3 | |
Maximum of Months | 0.500165E+09 | 58460.11 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.228670E+09 | 30160.80 | 06-JAN-08:61 | -0.6 |
February | 0.138323E+09 | 30168.32 | 02-FEB-08:61 | -1.7 |
March | 92035035.69 | 30169.20 | 02-MAR-08:61 | -0.9 |
April | 62279991.00 | 1657.10 | 30-APR-16:02 | 30.50 |
May | 60260153.58 | 2320.94 | 21-MAY-16:02 | 33.57 |
June | 62841602.67 | 3070.98 | 18-JUN-16:01 | 37.20 |
July | 67527329.91 | 3283.62 | 02-JUL-16:01 | 38.22 |
August | 61708535.23 | 2840.90 | 06-AUG-16:01 | 36.10 |
September | 39453633.90 | 2091.43 | 17-SEP-16:02 | 32.62 |
October | 28527187.71 | 1846.99 | 01-OCT-16:02 | 31.60 |
November | 71211987.83 | 30154.81 | 28-NOV-08:61 | 2.48 |
December | 0.301265E+09 | 30172.79 | 19-DEC-08:61 | -2.3 |
Annual Sum or Average | 0.121410E+10 | |||
Minimum of Months | 28527187.71 | 1657.10 | -2.3 | |
Maximum of Months | 0.301265E+09 | 30172.79 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.254335E+09 | 30046.46 | 06-JAN-08:61 | -0.6 |
February | 0.152022E+09 | 30053.75 | 02-FEB-08:61 | -1.7 |
March | 0.100494E+09 | 30054.63 | 02-MAR-08:61 | -0.9 |
April | 64284413.98 | 1658.61 | 30-APR-16:02 | 30.50 |
May | 60886646.08 | 2321.98 | 21-MAY-16:02 | 33.57 |
June | 62979287.87 | 3071.80 | 18-JUN-16:01 | 37.20 |
July | 67896019.52 | 3284.44 | 02-JUL-16:01 | 38.22 |
August | 61857529.47 | 2841.53 | 06-AUG-16:01 | 36.10 |
September | 39466511.37 | 2092.19 | 17-SEP-16:02 | 32.62 |
October | 30104405.71 | 1848.41 | 01-OCT-16:02 | 31.60 |
November | 72586676.18 | 30040.44 | 28-NOV-08:61 | 2.48 |
December | 0.327124E+09 | 30057.63 | 19-DEC-08:61 | -2.3 |
Annual Sum or Average | 0.129404E+10 | |||
Minimum of Months | 30104405.71 | 1658.61 | -2.3 | |
Maximum of Months | 0.327124E+09 | 30057.63 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345771E+09 | 30073.87 | 06-JAN-08:61 | -0.6 |
February | 0.216494E+09 | 30081.69 | 02-FEB-08:61 | -1.7 |
March | 0.143651E+09 | 30083.06 | 02-MAR-08:61 | -0.9 |
April | 69142609.48 | 1663.67 | 30-APR-16:02 | 30.50 |
May | 62607165.87 | 2324.45 | 21-MAY-16:02 | 33.57 |
June | 63145478.08 | 3072.17 | 18-JUN-16:01 | 37.20 |
July | 67060038.86 | 3284.35 | 02-JUL-16:01 | 38.22 |
August | 61097905.01 | 2840.45 | 06-AUG-16:01 | 36.10 |
September | 39127414.11 | 2092.08 | 17-SEP-16:02 | 32.62 |
October | 35697238.65 | 1850.62 | 01-OCT-16:02 | 31.60 |
November | 87840608.90 | 30067.28 | 28-NOV-08:61 | 2.48 |
December | 0.428571E+09 | 30086.52 | 19-DEC-08:61 | -2.3 |
Annual Sum or Average | 0.162021E+10 | |||
Minimum of Months | 35697238.65 | 1663.67 | -2.3 | |
Maximum of Months | 0.428571E+09 | 30086.52 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.793589E+09 | 33006.74 | 06-JAN-08:61 | -0.6 |
February | 0.511672E+09 | 33019.75 | 03-FEB-08:61 | -2.0 |
March | 0.409330E+09 | 33017.68 | 02-MAR-08:61 | -0.9 |
April | 90040875.81 | 15072.95 | 12-APR-07:03 | 7.35 |
May | 65009119.63 | 2324.81 | 21-MAY-16:02 | 33.57 |
June | 60734125.13 | 3061.71 | 18-JUN-16:01 | 37.20 |
July | 62043161.47 | 3261.94 | 02-JUL-16:01 | 38.22 |
August | 56487906.78 | 2817.62 | 06-AUG-16:01 | 36.10 |
September | 39669543.23 | 2073.18 | 17-SEP-16:02 | 32.62 |
October | 48458833.38 | 1834.81 | 01-OCT-16:02 | 31.60 |
November | 0.183152E+09 | 32992.70 | 28-NOV-08:61 | 2.48 |
December | 0.853775E+09 | 33028.18 | 19-DEC-08:61 | -2.3 |
Annual Sum or Average | 0.317396E+10 | |||
Minimum of Months | 39669543.23 | 1834.81 | -2.3 | |
Maximum of Months | 0.853775E+09 | 33028.18 | 38.22 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.986629E+10 | 6035.26 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.891946E+10 | 6035.26 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.987658E+10 | 6035.26 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.956097E+10 | 6035.26 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.986629E+10 | 6035.26 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.956097E+10 | 6035.26 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.987658E+10 | 6035.26 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.986629E+10 | 6035.26 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.957126E+10 | 6035.26 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.986629E+10 | 6035.26 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.953010E+10 | 6035.26 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.988687E+10 | 6035.26 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.116248E+12 | 0.262491E+11 | ||||
Minimum of Months | 0.891946E+10 | 6035.26 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.988687E+10 | 6035.26 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.579394E+10 | 3544.17 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.523792E+10 | 3544.17 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.579999E+10 | 3544.17 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.561464E+10 | 3544.17 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.579394E+10 | 3544.17 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.561464E+10 | 3544.17 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.579999E+10 | 3544.17 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.579394E+10 | 3544.17 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.562069E+10 | 3544.17 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.579394E+10 | 3544.17 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.559651E+10 | 3544.17 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.580603E+10 | 3544.17 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.682662E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.523792E+10 | 3544.17 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.580603E+10 | 3544.17 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.413753E+10 | 3181.37 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.374692E+10 | 3181.37 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.422433E+10 | 3181.37 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.401456E+10 | 3181.37 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.418093E+10 | 3181.37 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.407966E+10 | 3181.37 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.411583E+10 | 3181.37 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.422433E+10 | 3181.37 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.401456E+10 | 3181.37 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.413753E+10 | 3181.37 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.401456E+10 | 3181.37 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.411583E+10 | 3181.37 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.490066E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.374692E+10 | 3181.37 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.422433E+10 | 3181.37 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.413753E+10 | 3181.37 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.374692E+10 | 3181.37 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.422433E+10 | 3181.37 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.401456E+10 | 3181.37 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.418093E+10 | 3181.37 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.407966E+10 | 3181.37 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.411583E+10 | 3181.37 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.422433E+10 | 3181.37 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.401456E+10 | 3181.37 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.413753E+10 | 3181.37 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.401456E+10 | 3181.37 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.411583E+10 | 3181.37 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.490066E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.374692E+10 | 3181.37 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.422433E+10 | 3181.37 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.413753E+10 | 3181.37 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.374692E+10 | 3181.37 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.422433E+10 | 3181.37 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.401456E+10 | 3181.37 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.418093E+10 | 3181.37 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.407966E+10 | 3181.37 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.411583E+10 | 3181.37 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.422433E+10 | 3181.37 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.401456E+10 | 3181.37 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.413753E+10 | 3181.37 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.401456E+10 | 3181.37 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.411583E+10 | 3181.37 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.490066E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.374692E+10 | 3181.37 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.422433E+10 | 3181.37 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.457032E+10 | 3825.14 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.413982E+10 | 3825.14 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.467469E+10 | 3825.14 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.443552E+10 | 3825.14 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.462251E+10 | 3825.14 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.451379E+10 | 3825.14 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.454423E+10 | 3825.14 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.467469E+10 | 3825.14 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.443552E+10 | 3825.14 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.457032E+10 | 3825.14 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.443552E+10 | 3825.14 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.454423E+10 | 3825.14 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.541612E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.413982E+10 | 3825.14 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.467469E+10 | 3825.14 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.986629E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265904E+10 |
February | 0.305697E+10 | 0.891946E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195046E+10 |
March | 0.335708E+10 | 0.987658E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4486640.23 | 0.172714E+10 |
April | 0.327081E+10 | 0.956097E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420058E+09 | 0.723743E+09 |
May | 0.336680E+10 | 0.986629E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100214E+10 | 0.263003E+09 |
June | 0.325380E+10 | 0.956097E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168757E+10 | 86802745.17 |
July | 0.339353E+10 | 0.987658E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153714E+10 | 60575246.27 |
August | 0.334857E+10 | 0.986629E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129931E+10 | 0.119211E+09 |
September | 0.327932E+10 | 0.957126E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934379E+09 | 0.137347E+09 |
October | 0.338624E+10 | 0.986629E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225717E+09 | 0.793963E+09 |
November | 0.327446E+10 | 0.953010E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 925.13 | 0.203452E+10 |
December | 0.340325E+10 | 0.988687E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276156E+10 |
Annual Sum or Average | 0.397770E+11 | 0.116248E+12 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711081E+10 | 0.133174E+11 |
Minimum of Months | 0.305697E+10 | 0.891946E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60575246.27 |
Maximum of Months | 0.340325E+10 | 0.988687E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168757E+10 | 0.276156E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.579394E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136726E+10 |
February | 0.152844E+10 | 0.523792E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.974546E+09 |
March | 0.167849E+10 | 0.579999E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2423143.20 | 0.829609E+09 |
April | 0.163536E+10 | 0.561464E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225057E+09 | 0.311377E+09 |
May | 0.168335E+10 | 0.579394E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534460E+09 | 93232706.38 |
June | 0.162685E+10 | 0.561464E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901337E+09 | 28107037.47 |
July | 0.169671E+10 | 0.579999E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826537E+09 | 19474232.55 |
August | 0.167424E+10 | 0.579394E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701085E+09 | 42721437.55 |
September | 0.163961E+10 | 0.562069E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512543E+09 | 48987263.63 |
October | 0.169307E+10 | 0.579394E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123195E+09 | 0.354125E+09 |
November | 0.163718E+10 | 0.559651E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 503.07 | 0.998533E+09 |
December | 0.170157E+10 | 0.580603E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143571E+10 |
Annual Sum or Average | 0.198880E+11 | 0.682662E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382664E+10 | 0.650368E+10 |
Minimum of Months | 0.152844E+10 | 0.523792E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19474232.55 |
Maximum of Months | 0.170157E+10 | 0.580603E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901337E+09 | 0.143571E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136350E+10 |
February | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.991216E+09 |
March | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423143.20 | 0.861943E+09 |
April | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217519E+09 | 0.333527E+09 |
May | 0.102058E+10 | 0.418093E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522238E+09 | 0.105456E+09 |
June | 0.998711E+09 | 0.407966E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892363E+09 | 32910206.84 |
July | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812695E+09 | 26506192.81 |
August | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690452E+09 | 47688250.29 |
September | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503276E+09 | 60096935.16 |
October | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119179E+09 | 0.379036E+09 |
November | 0.973196E+09 | 0.401456E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 503.07 | 0.102482E+10 |
December | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143089E+10 |
Annual Sum or Average | 0.119700E+11 | 0.490066E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376015E+10 | 0.665759E+10 |
Minimum of Months | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26506192.81 |
Maximum of Months | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892363E+09 | 0.143089E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134305E+10 |
February | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.977902E+09 |
March | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423143.20 | 0.854617E+09 |
April | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217544E+09 | 0.332708E+09 |
May | 0.102058E+10 | 0.418093E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522073E+09 | 0.105732E+09 |
June | 0.998711E+09 | 0.407966E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.891902E+09 | 33464466.42 |
July | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812192E+09 | 27079460.94 |
August | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690091E+09 | 48205263.72 |
September | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503222E+09 | 60393846.58 |
October | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119143E+09 | 0.378823E+09 |
November | 0.973196E+09 | 0.401456E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 503.07 | 0.102029E+10 |
December | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141262E+10 |
Annual Sum or Average | 0.119700E+11 | 0.490066E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375859E+10 | 0.659488E+10 |
Minimum of Months | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27079460.94 |
Maximum of Months | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.891902E+09 | 0.141262E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131872E+10 |
February | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.958967E+09 |
March | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423143.20 | 0.842057E+09 |
April | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217781E+09 | 0.329523E+09 |
May | 0.102058E+10 | 0.418093E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522689E+09 | 0.103663E+09 |
June | 0.998711E+09 | 0.407966E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892791E+09 | 32178118.93 |
July | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812996E+09 | 25878835.23 |
August | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690664E+09 | 47052754.23 |
September | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503368E+09 | 59413600.03 |
October | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119244E+09 | 0.376902E+09 |
November | 0.973196E+09 | 0.401456E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 503.07 | 0.101257E+10 |
December | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138961E+10 |
Annual Sum or Average | 0.119700E+11 | 0.490066E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376196E+10 | 0.649654E+10 |
Minimum of Months | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25878835.23 |
Maximum of Months | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892791E+09 | 0.138961E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.457032E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236429E+10 |
February | 0.313522E+10 | 0.413982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172021E+10 |
March | 0.355148E+10 | 0.467469E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4361872.63 | 0.152557E+10 |
April | 0.338259E+10 | 0.443552E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394504E+09 | 0.615108E+09 |
May | 0.349753E+10 | 0.462251E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.948356E+09 | 0.200341E+09 |
June | 0.343071E+10 | 0.451379E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161885E+10 | 61285674.93 |
July | 0.344942E+10 | 0.454423E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147179E+10 | 49859146.39 |
August | 0.355148E+10 | 0.467469E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124887E+10 | 90897612.89 |
September | 0.338259E+10 | 0.443552E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905661E+09 | 0.115680E+09 |
October | 0.344359E+10 | 0.457032E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214998E+09 | 0.705914E+09 |
November | 0.331698E+10 | 0.443552E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 898.92 | 0.184726E+10 |
December | 0.344942E+10 | 0.454423E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248684E+10 |
Annual Sum or Average | 0.410346E+11 | 0.541612E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680739E+10 | 0.117833E+11 |
Minimum of Months | 0.313522E+10 | 0.413982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49859146.39 |
Maximum of Months | 0.355148E+10 | 0.467469E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161885E+10 | 0.248684E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128510E+10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929659E+09 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423143.20 | 0.820408E+09 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219088E+09 | 0.327307E+09 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526387E+09 | 0.102778E+09 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898252E+09 | 30412725.32 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817501E+09 | 24558930.46 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693991E+09 | 46483339.90 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504296E+09 | 59482123.04 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119646E+09 | 0.379123E+09 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 501.58 | 0.100408E+10 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135702E+10 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378158E+10 | 0.636641E+10 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24558930.46 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898252E+09 | 0.135702E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127820E+10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.923806E+09 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423143.20 | 0.814492E+09 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219211E+09 | 0.325873E+09 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526570E+09 | 0.102244E+09 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898465E+09 | 30147311.41 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817700E+09 | 24313924.53 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694125E+09 | 46265225.33 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504344E+09 | 59267456.31 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119675E+09 | 0.378387E+09 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 501.96 | 0.100031E+10 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135102E+10 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378251E+10 | 0.633432E+10 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24313924.53 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898465E+09 | 0.135102E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126234E+10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.908526E+09 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423143.20 | 0.798452E+09 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219529E+09 | 0.320874E+09 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526950E+09 | 0.100410E+09 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898729E+09 | 29473068.99 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817833E+09 | 23789860.17 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694164E+09 | 45865209.66 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504361E+09 | 58891449.06 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119717E+09 | 0.376034E+09 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 501.98 | 0.989714E+09 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133763E+10 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378371E+10 | 0.625199E+10 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23789860.17 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898729E+09 | 0.133763E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155595E+10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116186E+10 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2547911.84 | 0.105552E+10 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235024E+09 | 0.474329E+09 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.568500E+09 | 0.186665E+09 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969207E+09 | 63061165.25 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.869652E+09 | 53144930.30 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733287E+09 | 88986422.40 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516505E+09 | 0.114034E+09 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123781E+09 | 0.536119E+09 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 522.68 | 0.125157E+10 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160815E+10 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401850E+10 | 0.814940E+10 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53144930.30 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969207E+09 | 0.160815E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 6035.26 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4759.78 | 26-JAN-12:10 |
February | 4050.04 | 03-FEB-13:09 | 6035.26 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4614.49 | 08-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 6035.26 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 295.61 | 22-MAR-13:00 | 4306.07 | 01-MAR-18:00 |
April | 4050.04 | 01-APR-12:09 | 6035.26 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2329.01 | 21-APR-15:00 | 2993.45 | 06-APR-12:00 |
May | 4050.04 | 05-MAY-12:09 | 6035.26 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2978.24 | 19-MAY-14:00 | 1256.31 | 01-MAY-12:00 |
June | 4050.04 | 02-JUN-12:09 | 6035.26 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3756.83 | 02-JUN-16:00 | 790.47 | 28-JUN-02:00 |
July | 4050.04 | 01-JUL-12:09 | 6035.26 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3667.71 | 03-JUL-17:00 | 605.29 | 08-JUL-15:00 |
August | 4050.04 | 04-AUG-12:09 | 6035.26 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3392.39 | 07-AUG-16:00 | 810.91 | 14-AUG-11:10 |
September | 4050.04 | 01-SEP-12:09 | 6035.26 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.35 | 19-SEP-14:00 | 1642.06 | 23-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 6035.26 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2302.69 | 01-OCT-15:00 | 2862.13 | 24-OCT-11:10 |
November | 4050.04 | 03-NOV-12:09 | 6035.26 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 03-NOV-16:00 | 4314.21 | 26-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 6035.26 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5586.01 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.29 | |||||
Maximum of Months | 4050.04 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3756.83 | 5586.01 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3544.17 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2024.96 | 03-FEB-13:09 | 3544.17 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2467.75 | 08-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 3544.17 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2359.28 | 01-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 3544.17 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1667.40 | 11-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 3544.17 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2024.96 | 02-JUN-12:09 | 3544.17 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.25 | 02-JUN-16:00 | 236.13 | 28-JUN-02:00 |
July | 2024.96 | 01-JUL-12:09 | 3544.17 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.07 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2024.96 | 04-AUG-12:09 | 3544.17 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1839.99 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2024.96 | 01-SEP-12:09 | 3544.17 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.71 | 23-SEP-17:00 |
October | 2024.96 | 01-OCT-12:09 | 3544.17 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1604.50 | 24-OCT-11:10 |
November | 2024.96 | 03-NOV-12:09 | 3544.17 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 03-NOV-16:00 | 2358.84 | 26-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 3544.17 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3544.17 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.13 | |||||
Maximum of Months | 2024.96 | 3544.17 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.25 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3181.37 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 3181.37 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2440.54 | 08-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3181.37 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2331.03 | 01-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 3181.37 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1659.69 | 11-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 3181.37 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2024.96 | 03-JUN-12:09 | 3181.37 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.27 | 02-JUN-16:00 | 242.98 | 28-JUN-02:00 |
July | 2024.96 | 01-JUL-12:09 | 3181.37 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.09 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 3181.37 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.01 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 3181.37 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.81 | 23-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 3181.37 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1603.16 | 24-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 3181.37 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 03-NOV-16:00 | 2329.09 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 3181.37 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.98 | |||||
Maximum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.27 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3181.37 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 3181.37 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2421.32 | 08-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3181.37 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.10 | 01-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 3181.37 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1651.22 | 11-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 3181.37 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2024.96 | 03-JUN-12:09 | 3181.37 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.27 | 02-JUN-16:00 | 244.46 | 28-JUN-02:00 |
July | 2024.96 | 01-JUL-12:09 | 3181.37 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.08 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 3181.37 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.00 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 3181.37 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.80 | 23-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 3181.37 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1602.19 | 24-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 3181.37 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 03-NOV-16:00 | 2329.09 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 3181.37 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.46 | |||||
Maximum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.27 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3181.37 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 3181.37 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2386.06 | 08-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3181.37 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 3181.37 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1625.44 | 11-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 3181.37 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2024.96 | 03-JUN-12:09 | 3181.37 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.28 | 02-JUN-16:00 | 240.54 | 28-JUN-02:00 |
July | 2024.96 | 01-JUL-12:09 | 3181.37 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.09 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 3181.37 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.01 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 3181.37 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.80 | 23-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 3181.37 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1595.99 | 24-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 3181.37 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 03-NOV-16:00 | 2329.09 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 3181.37 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.54 | |||||
Maximum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.28 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3825.14 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4695.52 | 26-JAN-12:10 |
February | 5400.05 | 04-FEB-15:09 | 3825.14 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4141.68 | 08-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3825.14 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 285.58 | 22-MAR-13:00 | 4193.35 | 01-MAR-18:00 |
April | 5400.05 | 01-APR-14:09 | 3825.14 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2194.06 | 21-APR-15:00 | 2825.64 | 11-APR-11:10 |
May | 5400.05 | 06-MAY-14:09 | 3825.14 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2853.75 | 19-MAY-14:00 | 1206.11 | 01-MAY-12:00 |
June | 5400.05 | 03-JUN-14:09 | 3825.14 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3682.73 | 02-JUN-16:00 | 457.70 | 28-JUN-02:00 |
July | 5400.05 | 01-JUL-14:09 | 3825.14 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3564.48 | 03-JUL-17:00 | 585.90 | 08-JUL-15:00 |
August | 5400.05 | 05-AUG-14:09 | 3825.14 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3310.42 | 07-AUG-16:00 | 804.87 | 14-AUG-11:10 |
September | 5400.05 | 02-SEP-14:09 | 3825.14 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2472.51 | 19-SEP-14:00 | 1605.78 | 23-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 3825.14 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2247.00 | 01-OCT-15:00 | 2826.33 | 24-OCT-11:10 |
November | 5400.05 | 04-NOV-14:09 | 3825.14 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 | 08-NOV-15:00 | 4192.77 | 26-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 3825.14 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5518.47 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.70 | |||||
Maximum of Months | 5400.05 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3682.73 | 5518.47 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2283.43 | 08-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1562.28 | 11-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.26 | 02-JUN-16:00 | 226.92 | 28-JUN-02:00 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.06 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.00 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.77 | 23-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1569.28 | 24-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 08-NOV-15:00 | 2329.09 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.92 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.26 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2267.75 | 08-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1552.04 | 11-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.26 | 02-JUN-16:00 | 225.98 | 28-JUN-02:00 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.06 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1839.96 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.77 | 23-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1562.41 | 24-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 03-NOV-16:00 | 2329.09 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.98 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.26 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2234.21 | 08-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1522.34 | 11-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.26 | 02-JUN-16:00 | 224.17 | 28-JUN-02:00 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.06 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1839.99 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.77 | 23-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1540.17 | 24-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 03-NOV-16:00 | 2329.09 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.17 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.26 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2678.15 | 26-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2519.17 | 08-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 168.54 | 22-MAR-13:00 | 2442.80 | 01-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.25 | 21-APR-15:00 | 1685.25 | 06-APR-12:00 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.53 | 19-MAY-14:00 | 719.02 | 01-MAY-12:00 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2122.39 | 02-JUN-16:00 | 525.72 | 28-JUN-02:00 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2083.28 | 03-JUL-17:00 | 344.67 | 08-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1922.00 | 07-AUG-16:00 | 481.26 | 14-AUG-01:00 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1410.22 | 19-SEP-14:00 | 929.20 | 23-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1304.62 | 01-OCT-15:00 | 1502.50 | 24-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 03-NOV-16:00 | 2450.53 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3140.15 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.67 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2122.39 | 3140.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7575.53 | 28-JAN-00:25 | 675.01 | 6352.88 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.86 |
February | 7486.43 | 03-FEB-00:12 | 1350.01 | 1270.50 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.79 |
March | 7999.54 | 16-MAR-16:10 | 3375.03 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.65 |
April | 13230.16 | 30-APR-16:04 | 20250.19 | 30176.29 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1709.19 | 0.00 |
May | 39810.68 | 31-MAY-07:02 | 1687.52 | 1588.13 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 47.65 | 0.00 |
June | 42202.39 | 17-JUN-07:02 | 0.00 | 1905.75 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 4.90 | 0.00 |
July | 42187.53 | 03-JUL-07:01 | 3037.53 | 2858.63 | 671.62 | 0.00 | 0.00 | 0.00 | 0.00 | 99.95 | 0.00 |
August | 43652.45 | 23-AUG-07:02 | 1687.52 | 1588.13 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.98 |
September | 39518.22 | 20-SEP-07:02 | 1687.52 | 1588.13 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.91 |
October | 43640.89 | 02-OCT-07:02 | 2025.02 | 1905.75 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.19 |
November | 10610.23 | 09-NOV-15:00 | 2700.03 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.88 |
December | 7466.80 | 30-DEC-00:03 | 1012.51 | 9529.33 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7466.80 | 0.00 | 1270.50 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43652.45 | 20250.19 | 30176.29 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1709.19 | 510.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3478.78 | 03-JAN-14:50 | 1349.97 | 3544.17 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.22 |
February | 18187.28 | 12-FEB-18:59 | 16199.69 | 28353.40 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.66 |
March | 19181.20 | 19-MAR-17:34 | 14174.73 | 24809.22 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.52 |
April | 18372.14 | 22-APR-18:07 | 11812.27 | 24809.22 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.87 |
May | 20884.90 | 31-MAY-07:02 | 843.73 | 932.68 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 20.85 | 0.00 |
June | 23301.03 | 14-JUN-07:02 | 843.73 | 932.68 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.04 |
July | 21898.95 | 03-JUL-07:01 | 1518.72 | 1678.82 | 335.81 | 0.00 | 0.00 | 0.00 | 0.00 | 46.94 | 0.00 |
August | 23830.75 | 23-AUG-07:02 | 843.73 | 932.68 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.58 |
September | 20923.74 | 18-SEP-07:02 | 843.73 | 932.68 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.44 |
October | 22528.13 | 02-OCT-07:02 | 1012.48 | 1119.21 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.56 |
November | 19224.95 | 05-NOV-17:06 | 16199.69 | 28353.40 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.87 |
December | 3436.90 | 12-DEC-09:03 | 506.24 | 5596.07 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3436.90 | 506.24 | 932.68 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23830.75 | 16199.69 | 28353.40 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.94 | 503.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4093.18 | 06-JAN-08:61 | 1687.47 | 16744.07 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.40 |
February | 4275.28 | 10-FEB-08:61 | 1687.47 | 16744.07 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.11 |
March | 4273.07 | 16-MAR-14:00 | 1012.48 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.05 |
April | 8513.69 | 20-APR-06:03 | 0.00 | 502.32 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.97 |
May | 22972.24 | 31-MAY-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 |
June | 24719.60 | 06-JUN-06:02 | 0.00 | 1004.64 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.14 |
July | 22929.93 | 03-JUL-06:01 | 0.00 | 1506.97 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 | 0.00 |
August | 26408.13 | 23-AUG-06:02 | 0.00 | 1004.64 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.87 |
September | 24094.26 | 18-SEP-06:02 | 0.00 | 1004.64 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.43 |
October | 24287.01 | 02-OCT-06:01 | 0.00 | 1172.09 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.31 |
November | 5535.65 | 09-NOV-14:00 | 1349.97 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 |
December | 4102.57 | 22-DEC-08:61 | 1687.47 | 16744.07 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4093.18 | 0.00 | 502.32 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26408.13 | 1687.47 | 16744.07 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 | 520.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4047.02 | 06-JAN-08:61 | 1687.47 | 16744.07 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.01 |
February | 4056.64 | 01-FEB-08:61 | 1687.47 | 16744.07 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.62 |
March | 4175.35 | 16-MAR-14:00 | 1012.48 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.05 |
April | 8365.57 | 20-APR-06:03 | 0.00 | 502.32 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.96 |
May | 22863.76 | 31-MAY-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
June | 24625.46 | 06-JUN-06:02 | 0.00 | 1004.64 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.37 |
July | 22924.17 | 03-JUL-06:01 | 0.00 | 1506.97 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 0.00 |
August | 26285.88 | 23-AUG-06:02 | 0.00 | 1004.64 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 |
September | 24496.21 | 11-SEP-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.11 |
October | 24200.19 | 02-OCT-06:01 | 0.00 | 1172.09 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 |
November | 5463.02 | 09-NOV-14:00 | 1349.97 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 |
December | 3858.97 | 07-DEC-08:61 | 1349.97 | 13395.26 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3858.97 | 0.00 | 502.32 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26285.88 | 1687.47 | 16744.07 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 548.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3847.10 | 05-JAN-08:61 | 1518.72 | 15069.67 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.22 |
February | 3569.20 | 09-FEB-08:61 | 1349.97 | 13395.26 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.18 |
March | 3919.58 | 16-MAR-16:10 | 1687.47 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.01 |
April | 6873.53 | 20-APR-06:03 | 0.00 | 502.32 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.89 |
May | 22765.96 | 31-MAY-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
June | 24527.56 | 06-JUN-06:02 | 0.00 | 1004.64 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.92 |
July | 22844.71 | 03-JUL-06:01 | 0.00 | 1506.97 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 0.00 |
August | 26185.51 | 23-AUG-06:02 | 0.00 | 1004.64 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 |
September | 23962.43 | 18-SEP-06:02 | 0.00 | 1004.64 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.43 |
October | 24067.17 | 02-OCT-06:01 | 0.00 | 1172.09 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.11 |
November | 5259.03 | 09-NOV-14:00 | 1349.97 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 |
December | 3614.70 | 12-DEC-08:61 | 1349.97 | 13395.26 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3569.20 | 0.00 | 502.32 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26185.51 | 1687.47 | 15069.67 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 488.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5123.40 | 04-JAN-20:30 | 742.51 | 2013.22 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.16 |
February | 6146.47 | 08-FEB-19:30 | 1755.02 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 899.19 |
March | 6739.69 | 16-MAR-14:50 | 4657.54 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.23 |
April | 11559.65 | 21-APR-14:30 | 4657.54 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2189.18 | 0.00 |
May | 37398.68 | 30-MAY-07:02 | 0.00 | 1006.52 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 64.16 | 0.00 |
June | 39903.89 | 17-JUN-07:02 | 0.00 | 1207.82 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 | 0.00 |
July | 39455.29 | 03-JUL-07:01 | 0.00 | 1811.73 | 662.75 | 0.00 | 0.00 | 0.00 | 0.00 | 70.28 | 0.00 |
August | 42189.78 | 23-AUG-07:02 | 0.00 | 1006.52 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.79 |
September | 38377.75 | 18-SEP-07:02 | 0.00 | 1006.52 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.67 |
October | 40972.85 | 02-OCT-07:02 | 0.00 | 1207.82 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.63 |
November | 9058.65 | 09-NOV-14:00 | 4792.55 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.17 |
December | 5594.53 | 22-DEC-09:43 | 2227.52 | 6039.66 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 565.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5123.40 | 0.00 | 1006.52 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42189.78 | 4792.55 | 6039.66 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 2189.18 | 899.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2530.89 | 04-JAN-20:30 | 371.24 | 1033.59 | 373.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.13 |
February | 3074.64 | 08-FEB-19:40 | 877.48 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.89 |
March | 3407.18 | 16-MAR-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.71 |
April | 6008.96 | 21-APR-14:40 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.72 | 0.00 |
May | 19214.64 | 30-MAY-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.12 | 0.00 |
June | 20510.10 | 17-JUN-07:02 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 3.49 | 0.00 |
July | 20292.51 | 03-JUL-07:01 | 0.00 | 930.23 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 39.42 | 0.00 |
August | 20988.29 | 28-AUG-07:02 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.10 |
September | 19772.46 | 18-SEP-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.13 |
October | 21108.52 | 02-OCT-07:02 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.30 |
November | 4645.67 | 09-NOV-14:00 | 2396.20 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 |
December | 3343.15 | 26-DEC-20:13 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2530.89 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21108.52 | 2396.20 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.72 | 485.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3297.01 | 27-JAN-10:13 | 1113.73 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.02 |
February | 2992.67 | 08-FEB-19:20 | 877.48 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.41 |
March | 3304.35 | 16-MAR-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.71 |
April | 5950.13 | 21-APR-14:40 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.72 | 0.00 |
May | 19136.58 | 30-MAY-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.00 | 0.00 |
June | 20424.51 | 17-JUN-07:02 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 4.11 | 0.00 |
July | 20214.06 | 03-JUL-07:01 | 0.00 | 930.23 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 39.70 | 0.00 |
August | 20910.68 | 28-AUG-07:02 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.78 |
September | 19692.42 | 18-SEP-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.76 |
October | 21019.44 | 02-OCT-07:02 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.80 |
November | 4568.37 | 09-NOV-14:00 | 2396.20 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 |
December | 3348.04 | 26-DEC-20:20 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2992.67 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21019.44 | 2396.20 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.72 | 480.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2442.35 | 04-JAN-20:00 | 877.48 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.11 |
February | 2897.82 | 08-FEB-19:00 | 1147.48 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.14 |
March | 3069.68 | 16-MAR-15:00 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.71 |
April | 5839.14 | 21-APR-14:40 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.72 | 0.00 |
May | 18865.53 | 30-MAY-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.22 | 0.00 |
June | 20349.05 | 17-JUN-07:02 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 | 0.00 |
July | 20220.09 | 03-JUL-07:01 | 0.00 | 930.23 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 40.31 | 0.00 |
August | 20888.55 | 28-AUG-07:02 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.01 |
September | 19660.62 | 18-SEP-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.85 |
October | 20977.13 | 02-OCT-07:02 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.66 |
November | 4425.20 | 09-NOV-14:00 | 2396.20 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 |
December | 3342.16 | 26-DEC-19:13 | 2632.45 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2442.35 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20977.13 | 2632.45 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.72 | 472.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2100.77 | 21-JAN-10:05 | 742.49 | 3927.65 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.97 |
February | 2668.24 | 01-FEB-19:23 | 2632.45 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.52 |
March | 2819.31 | 16-MAR-14:20 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.23 |
April | 6236.18 | 21-APR-14:20 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1339.13 | 0.00 |
May | 15271.98 | 30-MAY-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.74 | 0.00 |
June | 21697.21 | 18-JUN-08:61 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 33.60 | 0.00 |
July | 21966.18 | 03-JUL-07:01 | 0.00 | 930.23 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 46.56 | 0.00 |
August | 22322.39 | 28-AUG-07:02 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.82 |
September | 20179.19 | 18-SEP-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.26 |
October | 22551.45 | 02-OCT-07:02 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 |
November | 4614.56 | 09-NOV-14:00 | 2396.20 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.57 |
December | 2651.54 | 19-DEC-19:13 | 2632.45 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2100.77 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22551.45 | 2632.45 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1339.13 | 485.52 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.786358E+11 | 63331.72 | 05-JAN-17:30 | 0.118979E+11 | 98915.53 | 28-JAN-08:09 |
February | 0.712023E+11 | 61485.30 | 20-FEB-15:30 | 0.611038E+10 | 98804.35 | 03-FEB-08:09 |
March | 0.799519E+11 | 64434.27 | 22-MAR-13:20 | 0.318825E+10 | 92365.77 | 02-MAR-08:09 |
April | 0.864078E+11 | 79893.90 | 21-APR-13:50 | 45252981.88 | 11857.58 | 11-APR-08:30 |
May | 0.100540E+12 | 87452.44 | 19-MAY-16:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.109365E+12 | 97603.64 | 05-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.114549E+12 | 98336.31 | 03-JUL-13:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.111908E+12 | 95043.40 | 07-AUG-16:40 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.103898E+12 | 89260.59 | 15-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.914931E+11 | 87564.28 | 03-OCT-12:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.772081E+11 | 70337.93 | 09-NOV-14:09 | 0.295913E+10 | 62160.36 | 28-NOV-08:09 |
December | 0.786743E+11 | 63064.00 | 01-DEC-17:10 | 0.168890E+11 | 106453.85 | 27-DEC-08:09 |
Annual Sum or Average | 0.110384E+13 | 0.410900E+11 | ||||
Minimum of Months | 0.712023E+11 | 61485.30 | 0.00 | 0.00 | ||
Maximum of Months | 0.114549E+12 | 98336.31 | 0.168890E+11 | 106453.85 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.420288E+11 | 0.101615E+11 | 0.108325E+11 | 0.00 | 0.101640E+11 | 0.00 | 0.00 | 19704919.20 | 0.00 | 0.00 | 0.00 | 0.542931E+10 | 0.00 |
February | 0.380395E+11 | 0.860857E+10 | 0.980803E+10 | 0.00 | 0.916684E+10 | 0.00 | 0.00 | 0.676392E+09 | 0.00 | 0.00 | 0.00 | 0.490292E+10 | 0.00 |
March | 0.426243E+11 | 0.872031E+10 | 0.110075E+11 | 0.00 | 0.102657E+11 | 0.00 | 0.00 | 0.193340E+10 | 0.00 | 0.00 | 0.00 | 0.540080E+10 | 0.00 |
April | 0.407637E+11 | 0.762344E+10 | 0.105079E+11 | 0.00 | 0.967816E+10 | 0.00 | 0.00 | 0.127489E+11 | 0.00 | 0.00 | 0.00 | 0.508577E+10 | 0.00 |
May | 0.423184E+11 | 0.717721E+10 | 0.109147E+11 | 0.00 | 0.100475E+11 | 0.00 | 0.00 | 0.249301E+11 | 0.00 | 0.00 | 0.00 | 0.515242E+10 | 0.00 |
June | 0.411980E+11 | 0.659470E+10 | 0.106386E+11 | 0.00 | 0.992609E+10 | 0.00 | 0.00 | 0.361021E+11 | 0.00 | 0.00 | 0.00 | 0.490581E+10 | 0.00 |
July | 0.419004E+11 | 0.696868E+10 | 0.107945E+11 | 0.00 | 0.100661E+11 | 0.00 | 0.00 | 0.398378E+11 | 0.00 | 0.00 | 0.00 | 0.498197E+10 | 0.00 |
August | 0.426079E+11 | 0.756646E+10 | 0.110006E+11 | 0.00 | 0.102076E+11 | 0.00 | 0.00 | 0.355067E+11 | 0.00 | 0.00 | 0.00 | 0.501891E+10 | 0.00 |
September | 0.407800E+11 | 0.807756E+10 | 0.105148E+11 | 0.00 | 0.970275E+10 | 0.00 | 0.00 | 0.299325E+11 | 0.00 | 0.00 | 0.00 | 0.489079E+10 | 0.00 |
October | 0.420288E+11 | 0.919761E+10 | 0.108325E+11 | 0.00 | 0.100179E+11 | 0.00 | 0.00 | 0.142771E+11 | 0.00 | 0.00 | 0.00 | 0.513926E+10 | 0.00 |
November | 0.407147E+11 | 0.961140E+10 | 0.104978E+11 | 0.00 | 0.978500E+10 | 0.00 | 0.00 | 0.150216E+10 | 0.00 | 0.00 | 0.00 | 0.509709E+10 | 0.00 |
December | 0.419167E+11 | 0.103376E+11 | 0.108050E+11 | 0.00 | 0.102278E+11 | 0.00 | 0.00 | 2991976.27 | 0.00 | 0.00 | 0.00 | 0.538419E+10 | 0.00 |
Annual Sum or Average | 0.496921E+12 | 0.100645E+12 | 0.128154E+12 | 0.00 | 0.119256E+12 | 0.00 | 0.00 | 0.197470E+12 | 0.00 | 0.00 | 0.00 | 0.613892E+11 | 0.00 |
Minimum of Months | 0.380395E+11 | 0.659470E+10 | 0.980803E+10 | 0.00 | 0.916684E+10 | 0.00 | 0.00 | 2991976.27 | 0.00 | 0.00 | 0.00 | 0.489079E+10 | 0.00 |
Maximum of Months | 0.426243E+11 | 0.103376E+11 | 0.110075E+11 | 0.00 | 0.102657E+11 | 0.00 | 0.00 | 0.398378E+11 | 0.00 | 0.00 | 0.00 | 0.542931E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.118979E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.611038E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.318825E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 45252981.88 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.295913E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.168890E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.410900E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.168890E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30804.00 | 01-JAN-11:09 | 7723.25 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 8948.89 | 28-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30804.00 | 01-FEB-10:09 | 7723.25 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 8947.43 | 03-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 30804.00 | 01-MAR-10:09 | 7723.25 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 8808.31 | 02-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 30804.00 | 01-APR-09:09 | 7723.25 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 7058.37 | 11-APR-08:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 30804.00 | 01-MAY-09:09 | 7723.25 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 8178.19 | 31-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 30804.00 | 01-JUN-09:09 | 7723.25 | 01-JUN-19:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 8471.34 | 15-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 30804.00 | 01-JUL-09:09 | 7723.25 | 01-JUL-19:19 | 8059.50 | 01-JUL-09:09 | 0.00 | 8709.22 | 03-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 30804.00 | 01-AUG-09:09 | 7723.25 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 8867.22 | 05-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 30804.00 | 01-SEP-09:09 | 7723.25 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 8291.70 | 22-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 30804.00 | 01-OCT-10:09 | 7723.25 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 8227.31 | 05-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30804.00 | 01-NOV-09:09 | 7723.25 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 8153.94 | 28-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30804.00 | 01-DEC-10:09 | 7723.25 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 9113.67 | 27-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30804.00 | 7723.25 | 8059.50 | 0.00 | 7058.37 | 0.00 | 0.00 | |||||
Maximum of Months | 30804.00 | 7723.25 | 8059.50 | 0.00 | 9113.67 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 1829.11 | 03-JAN-14:00 | 0.00 | 0.00 | 0.00 | 9920.75 | 05-JAN-17:30 | 0.00 |
February | 10391.70 | 20-FEB-15:30 | 0.00 | 0.00 | 0.00 | 9713.36 | 04-FEB-13:39 | 0.00 |
March | 13868.83 | 22-MAR-12:00 | 0.00 | 0.00 | 0.00 | 7585.51 | 01-MAR-13:20 | 0.00 |
April | 29140.39 | 21-APR-14:30 | 0.00 | 0.00 | 0.00 | 9693.47 | 17-APR-12:20 | 0.00 |
May | 34593.25 | 19-MAY-16:10 | 0.00 | 0.00 | 0.00 | 9646.35 | 17-MAY-15:39 | 0.00 |
June | 45140.29 | 02-JUN-16:19 | 0.00 | 0.00 | 0.00 | 7553.84 | 20-JUN-13:39 | 0.00 |
July | 44771.95 | 03-JUL-16:10 | 0.00 | 0.00 | 0.00 | 7925.13 | 11-JUL-11:09 | 0.00 |
August | 43602.82 | 07-AUG-16:10 | 0.00 | 0.00 | 0.00 | 9665.15 | 03-AUG-12:30 | 0.00 |
September | 36010.38 | 15-SEP-12:00 | 0.00 | 0.00 | 0.00 | 9672.92 | 08-SEP-12:09 | 0.00 |
October | 36239.44 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 9653.92 | 26-OCT-16:40 | 0.00 |
November | 15887.62 | 09-NOV-13:00 | 0.00 | 0.00 | 0.00 | 11809.26 | 10-NOV-14:00 | 0.00 |
December | 453.62 | 09-DEC-22:49 | 0.00 | 0.00 | 0.00 | 10195.20 | 01-DEC-13:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 453.62 | 0.00 | 0.00 | 0.00 | 7553.84 | 0.00 | ||
Maximum of Months | 45140.29 | 0.00 | 0.00 | 0.00 | 11809.26 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 63331.72 | 05-JAN-17:30 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 6824.23 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 61485.30 | 20-FEB-15:30 | 30804.00 | 8059.50 | 0.00 | 0.00 | 6803.30 | 0.00 | 0.00 | 10391.70 | 0.00 |
March | 64434.27 | 22-MAR-13:20 | 30804.00 | 8059.50 | 0.00 | 0.00 | 6803.30 | 0.00 | 0.00 | 13312.51 | 0.00 |
April | 79893.90 | 21-APR-13:50 | 30804.00 | 8059.50 | 0.00 | 0.00 | 6803.30 | 0.00 | 0.00 | 28776.65 | 0.00 |
May | 87452.44 | 19-MAY-16:30 | 30804.00 | 8059.50 | 0.00 | 0.00 | 6803.30 | 0.00 | 0.00 | 34244.82 | 0.00 |
June | 97603.64 | 05-JUN-16:10 | 30804.00 | 8059.50 | 0.00 | 0.00 | 7956.38 | 0.00 | 0.00 | 43246.36 | 0.00 |
July | 98336.31 | 03-JUL-13:50 | 30804.00 | 8059.50 | 0.00 | 0.00 | 8146.84 | 0.00 | 0.00 | 43973.27 | 0.00 |
August | 95043.40 | 07-AUG-16:40 | 30804.00 | 8059.50 | 0.00 | 0.00 | 7964.85 | 0.00 | 0.00 | 42787.69 | 0.00 |
September | 89260.59 | 15-SEP-12:00 | 30804.00 | 8059.50 | 0.00 | 0.00 | 6827.06 | 0.00 | 0.00 | 36010.38 | 0.00 |
October | 87564.28 | 03-OCT-12:50 | 30804.00 | 8059.50 | 0.00 | 0.00 | 6803.30 | 0.00 | 0.00 | 33037.07 | 0.00 |
November | 70337.93 | 09-NOV-14:09 | 30804.00 | 8059.50 | 0.00 | 0.00 | 6803.30 | 0.00 | 0.00 | 15432.22 | 0.00 |
December | 63064.00 | 01-DEC-17:10 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 6811.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 61485.30 | 30804.00 | 8059.50 | 0.00 | 0.00 | 6803.30 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 98336.31 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 8146.84 | 0.00 | 0.00 | 43973.27 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 98915.53 | 28-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 98804.35 | 03-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 92365.77 | 02-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 11857.58 | 11-APR-08:30 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 62160.36 | 28-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 106453.85 | 27-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 106453.85 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Annual Sum or Average | 0.33 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 481.50 | 21.93 | 27.67 | 21.87 | 27.67 | 21.82 |
February | 441.00 | 22.50 | 20.50 | 22.42 | 20.50 | 22.35 |
March | 472.67 | 23.05 | 10.83 | 23.00 | 10.83 | 22.96 |
April | 195.33 | 23.63 | 33.83 | 23.67 | 0.00 | 23.67 |
May | 52.83 | 23.85 | 217.67 | 23.88 | 0.00 | 23.88 |
June | 7.17 | 23.84 | 377.33 | 23.89 | 0.00 | 23.89 |
July | 57.33 | 23.89 | 495.00 | 23.89 | 57.33 | 23.89 |
August | 29.00 | 23.89 | 490.17 | 23.89 | 29.00 | 23.89 |
September | 36.83 | 23.89 | 421.33 | 23.89 | 33.50 | 23.89 |
October | 44.50 | 23.68 | 275.00 | 23.86 | 11.33 | 23.86 |
November | 307.17 | 22.84 | 34.50 | 22.92 | 3.83 | 22.90 |
December | 496.00 | 21.84 | 32.67 | 21.79 | 32.67 | 21.74 |
Annual Sum or Average | 2621.33 | 22.61 | 2436.50 | 23.17 | 226.67 | 23.15 |
Minimum of Months | 7.17 | 21.84 | 10.83 | 21.79 | 0.00 | 21.74 |
Maximum of Months | 496.00 | 23.89 | 495.00 | 23.89 | 57.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 458.33 | 22.82 | 1.33 | 22.81 | 1.33 | 22.81 |
February | 407.00 | 23.17 | 1.17 | 23.16 | 1.17 | 23.16 |
March | 401.50 | 23.44 | 1.33 | 23.43 | 1.33 | 23.42 |
April | 180.17 | 23.63 | 35.00 | 23.67 | 0.00 | 23.67 |
May | 50.50 | 23.60 | 205.33 | 23.82 | 0.00 | 23.82 |
June | 2.67 | 23.52 | 357.67 | 23.88 | 0.00 | 23.88 |
July | 32.83 | 23.89 | 495.00 | 23.89 | 32.83 | 23.89 |
August | 15.67 | 23.81 | 484.83 | 23.88 | 15.00 | 23.88 |
September | 20.00 | 23.62 | 408.00 | 23.86 | 15.00 | 23.86 |
October | 35.17 | 23.59 | 261.00 | 23.83 | 5.50 | 23.83 |
November | 253.00 | 23.27 | 36.33 | 23.34 | 0.00 | 23.34 |
December | 491.50 | 22.74 | 2.33 | 22.73 | 2.33 | 22.72 |
Annual Sum or Average | 2348.33 | 23.14 | 2289.33 | 23.50 | 74.50 | 23.50 |
Minimum of Months | 2.67 | 22.74 | 1.17 | 22.73 | 0.00 | 22.72 |
Maximum of Months | 491.50 | 23.89 | 495.00 | 23.89 | 32.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 352.67 | 22.19 | 7.67 | 22.16 | 7.67 | 22.14 |
February | 321.83 | 22.76 | 4.67 | 22.73 | 4.67 | 22.71 |
March | 330.17 | 23.20 | 2.83 | 23.19 | 2.83 | 23.17 |
April | 108.50 | 23.62 | 46.17 | 23.94 | 0.00 | 23.94 |
May | 24.50 | 24.14 | 174.50 | 24.29 | 1.67 | 24.33 |
June | 5.67 | 27.06 | 281.33 | 24.27 | 4.00 | 24.33 |
July | 59.17 | 24.93 | 368.50 | 24.26 | 59.17 | 24.34 |
August | 24.83 | 25.26 | 375.83 | 24.19 | 24.83 | 24.25 |
September | 23.50 | 24.39 | 333.83 | 24.12 | 22.00 | 24.14 |
October | 25.17 | 23.59 | 211.33 | 24.03 | 6.67 | 24.03 |
November | 199.17 | 22.90 | 33.50 | 23.05 | 0.00 | 23.05 |
December | 369.00 | 22.12 | 9.67 | 22.09 | 9.67 | 22.07 |
Annual Sum or Average | 1844.17 | 22.83 | 1849.83 | 23.48 | 143.17 | 23.51 |
Minimum of Months | 5.67 | 22.12 | 2.83 | 22.09 | 0.00 | 22.07 |
Maximum of Months | 369.00 | 27.06 | 375.83 | 24.29 | 59.17 | 24.34 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 360.17 | 22.08 | 11.00 | 22.05 | 11.00 | 22.03 |
February | 328.00 | 22.67 | 5.67 | 22.65 | 5.67 | 22.62 |
March | 338.67 | 23.16 | 3.17 | 23.15 | 3.17 | 23.13 |
April | 112.50 | 23.62 | 45.17 | 23.92 | 0.00 | 23.92 |
May | 24.33 | 24.15 | 174.67 | 24.29 | 1.67 | 24.33 |
June | 5.83 | 27.33 | 282.33 | 24.28 | 4.50 | 24.34 |
July | 58.83 | 24.96 | 368.50 | 24.26 | 58.83 | 24.34 |
August | 24.33 | 25.29 | 376.00 | 24.19 | 24.33 | 24.26 |
September | 23.33 | 24.39 | 333.83 | 24.12 | 22.00 | 24.14 |
October | 26.33 | 23.57 | 210.33 | 24.02 | 6.83 | 24.02 |
November | 216.33 | 22.92 | 33.17 | 23.05 | 0.33 | 23.05 |
December | 369.00 | 21.99 | 13.50 | 21.96 | 13.50 | 21.93 |
Annual Sum or Average | 1887.67 | 22.77 | 1857.33 | 23.43 | 151.83 | 23.46 |
Minimum of Months | 5.83 | 21.99 | 3.17 | 21.96 | 0.00 | 21.93 |
Maximum of Months | 369.00 | 27.33 | 376.00 | 24.29 | 58.83 | 24.34 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 368.17 | 21.95 | 15.33 | 21.92 | 15.33 | 21.89 |
February | 332.67 | 22.53 | 9.50 | 22.49 | 9.50 | 22.46 |
March | 357.67 | 23.10 | 3.83 | 23.08 | 3.83 | 23.06 |
April | 125.00 | 23.59 | 37.67 | 23.86 | 0.00 | 23.86 |
May | 28.50 | 24.09 | 170.33 | 24.28 | 1.67 | 24.31 |
June | 5.00 | 26.94 | 277.50 | 24.26 | 3.33 | 24.31 |
July | 59.83 | 24.85 | 368.50 | 24.24 | 59.83 | 24.32 |
August | 24.33 | 25.09 | 375.50 | 24.18 | 24.33 | 24.23 |
September | 24.17 | 24.36 | 331.50 | 24.11 | 22.50 | 24.13 |
October | 30.17 | 23.54 | 204.83 | 24.00 | 7.00 | 24.00 |
November | 237.67 | 22.91 | 28.00 | 23.00 | 1.83 | 22.98 |
December | 369.00 | 21.84 | 20.67 | 21.80 | 20.67 | 21.76 |
Annual Sum or Average | 1962.17 | 22.68 | 1843.17 | 23.36 | 169.83 | 23.37 |
Minimum of Months | 5.00 | 21.84 | 3.83 | 21.80 | 0.00 | 21.76 |
Maximum of Months | 369.00 | 26.94 | 375.50 | 24.28 | 59.83 | 24.32 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.71 | 22.83 | 21.67 | 22.83 | 21.64 |
February | 308.00 | 22.32 | 13.67 | 22.27 | 13.67 | 22.22 |
March | 348.00 | 23.01 | 7.50 | 22.97 | 7.50 | 22.93 |
April | 155.67 | 23.65 | 18.50 | 23.75 | 0.00 | 23.75 |
May | 35.50 | 24.00 | 135.33 | 24.07 | 1.17 | 24.09 |
June | 3.00 | 27.26 | 239.83 | 24.04 | 2.17 | 24.08 |
July | 62.50 | 24.30 | 337.50 | 24.04 | 62.50 | 24.08 |
August | 19.83 | 24.71 | 342.33 | 24.01 | 19.83 | 24.05 |
September | 14.83 | 24.42 | 295.33 | 23.99 | 13.67 | 24.01 |
October | 39.33 | 23.62 | 174.83 | 23.91 | 8.17 | 23.91 |
November | 249.83 | 22.87 | 18.00 | 22.90 | 3.00 | 22.88 |
December | 338.00 | 21.59 | 29.83 | 21.55 | 29.83 | 21.52 |
Annual Sum or Average | 1914.50 | 22.56 | 1635.50 | 23.16 | 184.33 | 23.16 |
Minimum of Months | 3.00 | 21.59 | 7.50 | 21.55 | 0.00 | 21.52 |
Maximum of Months | 348.00 | 27.26 | 342.33 | 24.07 | 62.50 | 24.09 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.68 | 27.33 | 21.64 | 27.33 | 21.60 |
February | 308.00 | 22.29 | 17.17 | 22.23 | 17.17 | 22.18 |
March | 348.00 | 22.98 | 9.17 | 22.94 | 9.17 | 22.89 |
April | 177.33 | 23.68 | 11.83 | 23.75 | 0.00 | 23.75 |
May | 44.17 | 23.94 | 117.83 | 24.06 | 0.83 | 24.08 |
June | 4.33 | 25.83 | 222.17 | 24.04 | 1.83 | 24.08 |
July | 62.00 | 24.25 | 336.33 | 24.03 | 62.00 | 24.06 |
August | 19.67 | 24.57 | 339.33 | 24.00 | 19.67 | 24.03 |
September | 15.33 | 24.27 | 286.00 | 23.99 | 13.17 | 24.00 |
October | 45.33 | 23.64 | 166.00 | 23.91 | 8.17 | 23.91 |
November | 259.67 | 22.90 | 13.67 | 22.91 | 3.50 | 22.89 |
December | 338.00 | 21.56 | 36.17 | 21.52 | 36.17 | 21.48 |
Annual Sum or Average | 1961.83 | 22.57 | 1583.00 | 23.13 | 199.00 | 23.12 |
Minimum of Months | 4.33 | 21.56 | 9.17 | 21.52 | 0.00 | 21.48 |
Maximum of Months | 348.00 | 25.83 | 339.33 | 24.06 | 62.00 | 24.08 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.64 | 31.00 | 21.59 | 31.00 | 21.56 |
February | 308.00 | 22.25 | 20.67 | 22.18 | 20.67 | 22.12 |
March | 348.00 | 22.94 | 11.00 | 22.89 | 11.00 | 22.83 |
April | 185.50 | 23.67 | 11.33 | 23.74 | 0.00 | 23.74 |
May | 46.67 | 23.94 | 115.50 | 24.06 | 0.83 | 24.08 |
June | 4.50 | 25.75 | 220.50 | 24.04 | 1.83 | 24.08 |
July | 63.33 | 24.24 | 336.33 | 24.03 | 63.33 | 24.06 |
August | 19.83 | 24.56 | 339.17 | 24.00 | 19.83 | 24.03 |
September | 15.50 | 24.22 | 284.50 | 23.99 | 13.17 | 24.00 |
October | 47.33 | 23.63 | 164.00 | 23.90 | 8.33 | 23.90 |
November | 268.00 | 22.88 | 12.67 | 22.89 | 3.83 | 22.87 |
December | 338.00 | 21.53 | 42.83 | 21.48 | 42.83 | 21.44 |
Annual Sum or Average | 1984.67 | 22.54 | 1589.50 | 23.10 | 216.67 | 23.08 |
Minimum of Months | 4.50 | 21.53 | 11.00 | 21.48 | 0.00 | 21.44 |
Maximum of Months | 348.00 | 25.75 | 339.17 | 24.06 | 63.33 | 24.08 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.55 | 41.67 | 21.50 | 41.67 | 21.47 |
February | 308.00 | 22.15 | 30.33 | 22.06 | 30.33 | 21.98 |
March | 348.00 | 22.83 | 17.67 | 22.75 | 17.67 | 22.67 |
April | 199.00 | 23.63 | 10.33 | 23.69 | 0.00 | 23.69 |
May | 50.33 | 23.92 | 114.50 | 24.05 | 0.83 | 24.07 |
June | 5.00 | 25.56 | 221.33 | 24.04 | 1.83 | 24.08 |
July | 65.33 | 24.23 | 336.33 | 24.03 | 65.33 | 24.06 |
August | 20.67 | 24.54 | 339.33 | 24.00 | 20.67 | 24.03 |
September | 16.33 | 24.25 | 285.00 | 23.99 | 13.83 | 24.00 |
October | 52.67 | 23.57 | 161.17 | 23.88 | 8.83 | 23.88 |
November | 280.67 | 22.82 | 10.50 | 22.81 | 5.50 | 22.78 |
December | 338.00 | 21.46 | 60.00 | 21.40 | 60.00 | 21.37 |
Annual Sum or Average | 2024.00 | 22.49 | 1628.17 | 23.04 | 266.50 | 23.00 |
Minimum of Months | 5.00 | 21.46 | 10.33 | 21.40 | 0.00 | 21.37 |
Maximum of Months | 348.00 | 25.56 | 339.33 | 24.05 | 65.33 | 24.08 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.44 | 87.33 | 21.38 | 87.33 | 21.33 |
February | 308.00 | 22.00 | 66.33 | 21.84 | 66.33 | 21.73 |
March | 348.00 | 22.67 | 43.50 | 22.50 | 43.50 | 22.36 |
April | 209.17 | 23.56 | 13.67 | 23.60 | 1.67 | 23.59 |
May | 46.17 | 23.92 | 129.50 | 24.05 | 1.17 | 24.07 |
June | 3.67 | 26.90 | 252.00 | 24.04 | 2.67 | 24.08 |
July | 55.83 | 24.39 | 337.67 | 24.05 | 55.83 | 24.10 |
August | 22.83 | 24.77 | 345.00 | 24.02 | 22.83 | 24.07 |
September | 17.00 | 24.57 | 298.17 | 24.01 | 14.50 | 24.04 |
October | 60.83 | 23.42 | 163.50 | 23.83 | 9.17 | 23.83 |
November | 283.83 | 22.69 | 17.00 | 22.65 | 12.00 | 22.59 |
December | 338.00 | 21.38 | 104.50 | 21.32 | 104.50 | 21.28 |
Annual Sum or Average | 2033.33 | 22.39 | 1858.17 | 22.92 | 421.50 | 22.83 |
Minimum of Months | 3.67 | 21.38 | 13.67 | 21.32 | 1.17 | 21.28 |
Maximum of Months | 348.00 | 26.90 | 345.00 | 24.05 | 104.50 | 24.10 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.98526 | 22.48618 | -0.2314 | 7.24415 |
February | 448.00000 | 22.52001 | 18.42832 | -0.1364 | 6.80380 |
March | 497.00000 | 23.09108 | 17.15057 | -0.0039 | 6.26425 |
April | 479.00000 | 23.78304 | 19.89342 | 0.23807 | 6.60973 |
May | 496.00000 | 23.88574 | 29.44939 | -0.4875 | 10.31347 |
June | 481.00000 | 23.88774 | 33.99070 | -0.3893 | 8.33055 |
July | 495.00000 | 23.89067 | 49.03275 | -0.2674 | 6.56709 |
August | 497.00000 | 23.88950 | 44.71571 | -0.3017 | 7.01184 |
September | 479.00000 | 23.88885 | 42.68210 | -0.3288 | 7.48531 |
October | 496.00000 | 23.86564 | 36.22336 | 0.41578 | 8.86943 |
November | 480.00000 | 23.21262 | 22.62915 | 0.10120 | 6.54752 |
December | 496.00000 | 21.84347 | 19.52302 | -0.2856 | 7.65843 |
Annual Sum or Average | 5840.00000 | 23.31418 | 29.77227 | -0.1403 | 7.48369 |
Minimum of Months | 448.00000 | 21.84347 | 17.15057 | -0.4875 | 6.26425 |
Maximum of Months | 497.00000 | 23.89067 | 49.03275 | 0.41578 | 10.31347 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 22.90109 | 22.75162 | -0.0196 | 5.99033 |
February | 448.00000 | 23.23584 | 18.22327 | 0.03778 | 5.82396 |
March | 497.00000 | 23.52496 | 16.88368 | 0.11258 | 5.91405 |
April | 479.00000 | 23.78226 | 20.44379 | 0.25587 | 6.61427 |
May | 496.00000 | 23.83676 | 30.10984 | -0.4968 | 10.45242 |
June | 481.00000 | 23.87347 | 34.17532 | -0.4073 | 8.59438 |
July | 495.00000 | 23.88593 | 47.68446 | -0.2991 | 6.93401 |
August | 497.00000 | 23.86802 | 44.14014 | -0.3328 | 7.42030 |
September | 479.00000 | 23.83782 | 41.85497 | -0.3686 | 8.09188 |
October | 496.00000 | 23.82844 | 35.95626 | 0.40560 | 8.64746 |
November | 480.00000 | 23.55690 | 22.51842 | 0.18531 | 6.46729 |
December | 496.00000 | 22.74879 | 20.27898 | -0.0749 | 6.10810 |
Annual Sum or Average | 5840.00000 | 23.57402 | 29.67413 | -0.0845 | 7.26463 |
Minimum of Months | 448.00000 | 22.74879 | 16.88368 | -0.4968 | 5.82396 |
Maximum of Months | 497.00000 | 23.88593 | 47.68446 | 0.40560 | 10.45242 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.26962 | 20.86998 | -0.1564 | 6.63527 |
February | 336.00000 | 22.81058 | 17.39090 | -0.0543 | 6.21416 |
March | 379.00000 | 23.31151 | 16.18028 | 0.06094 | 6.11463 |
April | 360.00000 | 23.93665 | 19.91675 | 0.27686 | 7.04581 |
May | 375.00000 | 24.08930 | 28.74836 | -0.4420 | 9.77822 |
June | 366.00000 | 24.14052 | 33.00026 | -0.3449 | 8.22778 |
July | 369.00000 | 24.14710 | 48.30942 | -0.2253 | 6.75417 |
August | 379.00000 | 24.11937 | 44.37192 | -0.2642 | 7.03769 |
September | 360.00000 | 24.08464 | 42.12307 | -0.2973 | 7.33433 |
October | 371.00000 | 23.98335 | 35.18349 | 0.43101 | 9.20715 |
November | 360.00000 | 23.35179 | 22.01677 | 0.14228 | 6.63676 |
December | 369.00000 | 22.11513 | 18.30515 | -0.2108 | 6.94663 |
Annual Sum or Average | 4395.00000 | 23.53459 | 28.96208 | -0.0916 | 7.33791 |
Minimum of Months | 336.00000 | 22.11513 | 16.18028 | -0.4420 | 6.11463 |
Maximum of Months | 379.00000 | 24.14710 | 48.30942 | 0.43101 | 9.77822 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.13543 | 21.03164 | -0.1950 | 6.87992 |
February | 336.00000 | 22.70498 | 17.52930 | -0.0854 | 6.35231 |
March | 379.00000 | 23.25698 | 16.25680 | 0.04205 | 6.14531 |
April | 360.00000 | 23.93037 | 19.92670 | 0.27353 | 7.02124 |
May | 375.00000 | 24.08894 | 28.74673 | -0.4413 | 9.76663 |
June | 366.00000 | 24.14080 | 32.99260 | -0.3429 | 8.19946 |
July | 369.00000 | 24.14743 | 48.28432 | -0.2234 | 6.73921 |
August | 379.00000 | 24.11956 | 44.35049 | -0.2625 | 7.02038 |
September | 360.00000 | 24.08448 | 42.10486 | -0.2962 | 7.32085 |
October | 371.00000 | 23.98063 | 35.19428 | 0.42958 | 9.18310 |
November | 360.00000 | 23.31454 | 22.08330 | 0.12875 | 6.62905 |
December | 369.00000 | 21.99459 | 18.43131 | -0.2463 | 7.21901 |
Annual Sum or Average | 4395.00000 | 23.49659 | 29.00445 | -0.1027 | 7.38276 |
Minimum of Months | 336.00000 | 21.99459 | 16.25680 | -0.4413 | 6.14531 |
Maximum of Months | 379.00000 | 24.14743 | 48.28432 | 0.42958 | 9.76663 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.96817 | 21.22725 | -0.2425 | 7.22879 |
February | 336.00000 | 22.54977 | 17.72899 | -0.1300 | 6.60537 |
March | 379.00000 | 23.15346 | 16.39929 | 0.00856 | 6.21080 |
April | 360.00000 | 23.90678 | 19.96128 | 0.26078 | 6.91565 |
May | 375.00000 | 24.08287 | 28.77641 | -0.4509 | 9.93605 |
June | 366.00000 | 24.13624 | 33.02474 | -0.3505 | 8.28595 |
July | 369.00000 | 24.14298 | 48.41410 | -0.2297 | 6.77166 |
August | 379.00000 | 24.11515 | 44.44064 | -0.2691 | 7.07271 |
September | 360.00000 | 24.07960 | 42.18779 | -0.3036 | 7.40017 |
October | 371.00000 | 23.96809 | 35.26623 | 0.42164 | 9.05009 |
November | 360.00000 | 23.24485 | 22.20984 | 0.10563 | 6.58853 |
December | 369.00000 | 21.83712 | 18.59469 | -0.2916 | 7.61253 |
Annual Sum or Average | 4395.00000 | 23.43771 | 29.11218 | -0.1236 | 7.48244 |
Minimum of Months | 336.00000 | 21.83712 | 16.39929 | -0.4509 | 6.21080 |
Maximum of Months | 379.00000 | 24.14298 | 48.41410 | 0.42164 | 9.93605 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.71089 | 22.88460 | -0.3220 | 7.95637 |
February | 308.00000 | 22.32381 | 19.22963 | -0.2048 | 7.09524 |
March | 348.00000 | 23.01138 | 17.77125 | -0.0484 | 6.22126 |
April | 330.00000 | 23.83203 | 21.45466 | 0.23169 | 6.56451 |
May | 344.00000 | 23.96337 | 30.51781 | -0.4942 | 10.59866 |
June | 336.00000 | 23.96890 | 34.52091 | -0.3996 | 8.70882 |
July | 338.00000 | 23.99430 | 49.76638 | -0.2739 | 6.93575 |
August | 348.00000 | 23.97060 | 45.68800 | -0.3131 | 7.37351 |
September | 330.00000 | 23.96366 | 43.23932 | -0.3417 | 7.77341 |
October | 340.00000 | 23.89738 | 36.38971 | 0.39819 | 8.60283 |
November | 330.00000 | 23.10720 | 23.75616 | 0.05847 | 6.46171 |
December | 338.00000 | 21.59003 | 20.31884 | -0.3700 | 8.46466 |
Annual Sum or Average | 4030.00000 | 23.28404 | 30.55442 | -0.1742 | 7.73890 |
Minimum of Months | 308.00000 | 21.59003 | 17.77125 | -0.4942 | 6.22126 |
Maximum of Months | 348.00000 | 23.99430 | 49.76638 | 0.39819 | 10.59866 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.68077 | 22.82124 | -0.3385 | 8.14308 |
February | 308.00000 | 22.29487 | 19.17800 | -0.2213 | 7.23391 |
March | 348.00000 | 22.98454 | 17.73101 | -0.0655 | 6.27040 |
April | 330.00000 | 23.82800 | 21.36379 | 0.21731 | 6.42647 |
May | 344.00000 | 23.96140 | 30.43566 | -0.5169 | 11.06074 |
June | 336.00000 | 23.96726 | 34.44445 | -0.4267 | 9.16497 |
July | 338.00000 | 23.99222 | 49.75148 | -0.3012 | 7.24603 |
August | 348.00000 | 23.96882 | 45.65699 | -0.3400 | 7.71996 |
September | 330.00000 | 23.96251 | 43.20164 | -0.3676 | 8.14204 |
October | 340.00000 | 23.89780 | 36.32846 | 0.38365 | 8.35375 |
November | 330.00000 | 23.10072 | 23.68563 | 0.04570 | 6.41774 |
December | 338.00000 | 21.56316 | 20.24164 | -0.3846 | 8.65262 |
Annual Sum or Average | 4030.00000 | 23.27316 | 30.49639 | -0.1939 | 7.91294 |
Minimum of Months | 308.00000 | 21.56316 | 17.73101 | -0.5169 | 6.27040 |
Maximum of Months | 348.00000 | 23.99222 | 49.75148 | 0.38365 | 11.06074 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.63912 | 22.86942 | -0.3528 | 8.30922 |
February | 308.00000 | 22.25293 | 19.23608 | -0.2358 | 7.36483 |
March | 348.00000 | 22.94174 | 17.80191 | -0.0804 | 6.33448 |
April | 330.00000 | 23.81788 | 21.38645 | 0.21111 | 6.39143 |
May | 344.00000 | 23.96041 | 30.45290 | -0.5206 | 11.14521 |
June | 336.00000 | 23.96691 | 34.46638 | -0.4296 | 9.21447 |
July | 338.00000 | 23.99176 | 49.82780 | -0.3035 | 7.27220 |
August | 348.00000 | 23.96851 | 45.71012 | -0.3423 | 7.75096 |
September | 330.00000 | 23.96207 | 43.24822 | -0.3701 | 8.18019 |
October | 340.00000 | 23.89362 | 36.36584 | 0.38032 | 8.30552 |
November | 330.00000 | 23.06836 | 23.75167 | 0.03455 | 6.42034 |
December | 338.00000 | 21.52778 | 20.27323 | -0.3969 | 8.81871 |
Annual Sum or Average | 4030.00000 | 23.25574 | 30.54219 | -0.2014 | 7.96903 |
Minimum of Months | 308.00000 | 21.52778 | 17.80191 | -0.5206 | 6.33448 |
Maximum of Months | 348.00000 | 23.99176 | 49.82780 | 0.38032 | 11.14521 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.55278 | 22.96785 | -0.3833 | 8.71287 |
February | 308.00000 | 22.14904 | 19.37428 | -0.2701 | 7.71947 |
March | 348.00000 | 22.83114 | 17.97729 | -0.1163 | 6.53783 |
April | 330.00000 | 23.78323 | 21.44772 | 0.19600 | 6.34046 |
May | 344.00000 | 23.95737 | 30.47509 | -0.5250 | 11.25797 |
June | 336.00000 | 23.96665 | 34.48094 | -0.4286 | 9.19719 |
July | 338.00000 | 23.99155 | 49.86750 | -0.3012 | 7.24277 |
August | 348.00000 | 23.96850 | 45.72878 | -0.3397 | 7.71765 |
September | 330.00000 | 23.96174 | 43.25904 | -0.3685 | 8.16107 |
October | 340.00000 | 23.87907 | 36.43180 | 0.37425 | 8.23511 |
November | 330.00000 | 22.98060 | 23.91524 | 0.00764 | 6.47310 |
December | 338.00000 | 21.45688 | 20.33588 | -0.4227 | 9.20482 |
Annual Sum or Average | 4030.00000 | 23.21344 | 30.61437 | -0.2155 | 8.07561 |
Minimum of Months | 308.00000 | 21.45688 | 17.97729 | -0.5250 | 6.34046 |
Maximum of Months | 348.00000 | 23.99155 | 49.86750 | 0.37425 | 11.25797 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.44369 | 22.91957 | -0.4448 | 9.75051 |
February | 308.00000 | 22.00034 | 19.49984 | -0.3377 | 8.64351 |
March | 348.00000 | 22.67094 | 18.07278 | -0.1821 | 7.09585 |
April | 330.00000 | 23.73248 | 21.41841 | 0.17668 | 6.36098 |
May | 344.00000 | 23.95633 | 30.23174 | -0.5078 | 10.97681 |
June | 336.00000 | 23.97093 | 34.30780 | -0.3856 | 8.48246 |
July | 338.00000 | 23.99840 | 49.28595 | -0.2541 | 6.74438 |
August | 348.00000 | 23.97465 | 45.30123 | -0.2907 | 7.14184 |
September | 330.00000 | 23.96848 | 42.76922 | -0.3212 | 7.54985 |
October | 340.00000 | 23.84064 | 36.38344 | 0.37254 | 8.34342 |
November | 330.00000 | 22.85798 | 23.97013 | -0.0369 | 6.71684 |
December | 338.00000 | 21.38412 | 20.23614 | -0.4721 | 10.13855 |
Annual Sum or Average | 4030.00000 | 23.15742 | 30.45677 | -0.2240 | 8.16589 |
Minimum of Months | 308.00000 | 21.38412 | 18.07278 | -0.5078 | 6.36098 |
Maximum of Months | 348.00000 | 23.99840 | 49.28595 | 0.37254 | 10.97681 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 13775720.74 | 3897165.66 | 4.17 | 13775720.74 | 0.00 | 0.00 | 0.11 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 1947.97 | 03-JAN-15:00 | 1947.97 | 03-JAN-15:00 | 0.00 | 03-JAN-15:10 | 544.89 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 0.540355E+09 | 0.148136E+09 | 46.17 | 0.540355E+09 | 0.00 | 0.00 | 0.42 | 20-FEB-16:00 | 0.00 | 01-FEB-00:10 | 7830.49 | 20-FEB-16:00 | 7830.49 | 20-FEB-16:00 | 0.00 | 20-FEB-16:00 | 2101.63 | 20-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.141585E+10 | 0.388652E+09 | 108.17 | 0.141585E+10 | 87.97 | 0.00 | 0.48 | 14-MAR-16:30 | 0.00 | 01-MAR-00:10 | 9142.32 | 14-MAR-16:30 | 9142.32 | 14-MAR-16:30 | 0.05 | 10-MAR-19:10 | 2462.66 | 14-MAR-16:30 | 0.00 | 01-MAR-00:10 |
April | 0.979200E+10 | 0.269772E+10 | 331.31 | 0.976159E+10 | 30414652.90 | 0.00 | 0.84 | 30-APR-16:02 | 0.00 | 01-APR-00:10 | 17227.03 | 21-APR-14:00 | 17227.03 | 21-APR-14:00 | 774.58 | 18-APR-18:10 | 4957.05 | 21-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.186769E+11 | 0.517748E+10 | 465.65 | 0.181438E+11 | 0.533067E+09 | 0.00 | 1.00 | 09-MAY-07:03 | 0.00 | 01-MAY-00:10 | 46087.10 | 31-MAY-07:02 | 46087.10 | 31-MAY-07:02 | 6042.30 | 28-MAY-07:03 | 10773.74 | 31-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.260393E+11 | 0.744907E+10 | 482.26 | 0.251279E+11 | 0.911360E+09 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 48918.52 | 19-JUN-07:01 | 47333.68 | 05-JUN-07:02 | 10682.87 | 04-JUN-07:02 | 11191.41 | 08-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.312966E+11 | 0.836308E+10 | 499.30 | 0.260346E+11 | 0.526198E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 52819.47 | 19-JUL-07:02 | 47174.50 | 03-JUL-07:01 | 31321.87 | 19-JUL-07:02 | 11496.05 | 03-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.273988E+11 | 0.738381E+10 | 493.25 | 0.242965E+11 | 0.310233E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 52276.26 | 02-AUG-07:02 | 46620.13 | 07-AUG-07:01 | 22515.05 | 02-AUG-07:02 | 11375.70 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.232022E+11 | 0.609518E+10 | 470.31 | 0.202089E+11 | 0.299334E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:03 | 51484.41 | 23-SEP-07:02 | 40159.02 | 20-SEP-07:02 | 24605.14 | 04-SEP-07:02 | 11103.42 | 23-SEP-07:02 | 0.00 | 01-SEP-00:03 |
October | 0.111587E+11 | 0.291285E+10 | 351.63 | 0.100121E+11 | 0.114655E+10 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 49576.44 | 05-OCT-07:02 | 42190.72 | 02-OCT-07:02 | 15036.41 | 05-OCT-07:02 | 10715.16 | 05-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.112503E+10 | 0.301750E+09 | 87.69 | 0.111248E+10 | 12548901.61 | 0.00 | 0.55 | 09-NOV-15:00 | 0.00 | 01-NOV-00:10 | 10967.15 | 09-NOV-15:00 | 10967.15 | 09-NOV-15:00 | 814.67 | 03-NOV-12:40 | 2840.82 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.150659E+12 | 0.409216E+11 | 3339.89 | 0.136668E+12 | 0.139916E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.312966E+11 | 0.836308E+10 | 499.30 | 0.260346E+11 | 0.526198E+10 | 0.00 | 1.00 | 0.00 | 52819.47 | 47333.68 | 31321.87 | 11496.05 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 37317847.07 | 10210443.93 | 13.92 | 37181873.15 | 135973.93 | 0.00 | 0.32 | 29-JAN-18:10 | 0.00 | 01-JAN-00:05 | 3103.06 | 29-JAN-18:10 | 3103.06 | 29-JAN-18:10 | 106.06 | 15-JAN-19:00 | 806.42 | 29-JAN-18:10 | 0.00 | 01-JAN-00:05 |
February | 0.496156E+09 | 0.127899E+09 | 62.45 | 0.496012E+09 | 144512.17 | 0.00 | 1.00 | 12-FEB-18:01 | 0.00 | 01-FEB-00:10 | 23639.05 | 19-FEB-18:01 | 23639.05 | 12-FEB-18:07 | 244.27 | 27-FEB-21:10 | 5004.80 | 12-FEB-18:01 | 0.00 | 01-FEB-00:10 |
March | 0.115562E+10 | 0.300389E+09 | 131.89 | 0.115552E+10 | 102015.97 | 0.00 | 1.00 | 12-MAR-17:01 | 0.00 | 01-MAR-00:10 | 23639.05 | 12-MAR-17:20 | 23639.05 | 12-MAR-17:01 | 169.55 | 11-MAR-00:10 | 5101.01 | 26-MAR-17:01 | 0.00 | 01-MAR-00:10 |
April | 0.636538E+10 | 0.164683E+10 | 324.04 | 0.633787E+10 | 27503230.27 | 0.00 | 1.00 | 01-APR-21:01 | 0.00 | 01-APR-00:10 | 24434.77 | 18-APR-20:36 | 23908.56 | 29-APR-20:40 | 2670.78 | 18-APR-20:45 | 5306.43 | 29-APR-20:17 | 0.00 | 01-APR-00:10 |
May | 0.106532E+11 | 0.283714E+10 | 451.06 | 0.103055E+11 | 0.347712E+09 | 0.00 | 1.00 | 02-MAY-20:01 | 0.00 | 01-MAY-00:10 | 25526.68 | 27-MAY-21:00 | 24183.53 | 30-MAY-07:02 | 8231.05 | 24-MAY-22:40 | 5617.67 | 27-MAY-20:38 | 0.00 | 01-MAY-00:10 |
June | 0.135636E+11 | 0.379796E+10 | 476.75 | 0.130614E+11 | 0.502207E+09 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 25524.48 | 23-JUN-20:02 | 24590.39 | 05-JUN-07:02 | 6753.38 | 28-JUN-07:03 | 5729.31 | 08-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.160419E+11 | 0.421695E+10 | 497.17 | 0.134296E+11 | 0.261233E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 27060.66 | 19-JUL-07:02 | 24592.13 | 03-JUL-07:01 | 14815.15 | 18-JUL-20:53 | 5870.78 | 03-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.144004E+11 | 0.379094E+10 | 484.50 | 0.127034E+11 | 0.169700E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 26860.53 | 02-AUG-07:02 | 24149.82 | 27-AUG-07:02 | 12424.70 | 16-AUG-20:20 | 5813.26 | 07-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.128905E+11 | 0.326942E+10 | 439.99 | 0.112325E+11 | 0.165798E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:03 | 26445.55 | 23-SEP-07:02 | 23841.92 | 28-SEP-21:25 | 13516.60 | 23-SEP-18:02 | 5695.97 | 09-SEP-20:00 | 0.00 | 01-SEP-00:03 |
October | 0.698597E+10 | 0.173040E+10 | 332.74 | 0.624194E+10 | 0.744034E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 26439.85 | 03-OCT-20:03 | 23639.05 | 09-OCT-18:05 | 11668.95 | 08-OCT-21:50 | 5687.52 | 03-OCT-20:03 | 0.00 | 01-OCT-00:10 |
November | 0.828811E+09 | 0.213555E+09 | 108.86 | 0.817739E+09 | 11071828.91 | 0.00 | 1.00 | 05-NOV-17:01 | 0.00 | 01-NOV-00:10 | 23639.05 | 09-NOV-21:34 | 23639.05 | 05-NOV-17:06 | 1939.23 | 09-NOV-22:55 | 5004.80 | 05-NOV-17:06 | 0.00 | 01-NOV-00:10 |
December | 10885271.33 | 2991976.27 | 6.33 | 10860629.89 | 24641.44 | 0.00 | 0.25 | 08-DEC-21:10 | 0.00 | 01-DEC-00:10 | 2402.50 | 08-DEC-21:10 | 2402.50 | 08-DEC-21:10 | 16.73 | 14-DEC-21:30 | 635.94 | 08-DEC-21:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.834298E+11 | 0.219447E+11 | 3329.71 | 0.758296E+11 | 0.760026E+10 | 0.00 | ||||||||||||||
Minimum of Months | 10885271.33 | 2991976.27 | 6.33 | 10860629.89 | 24641.44 | 0.00 | 0.25 | 0.00 | 2402.50 | 2402.50 | 16.73 | 635.94 | 0.00 | |||||||
Maximum of Months | 0.160419E+11 | 0.421695E+10 | 497.17 | 0.134296E+11 | 0.261233E+10 | 0.00 | 1.00 | 0.00 | 27060.66 | 24592.13 | 14815.15 | 5870.78 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 10900179.90 | 3016538.35 | 5.67 | 10900179.90 | 0.00 | 0.00 | 0.13 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 1239.88 | 03-JAN-15:00 | 1239.88 | 03-JAN-15:00 | 0.00 | 03-JAN-15:00 | 338.95 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 0.282194E+09 | 76034933.38 | 44.50 | 0.282194E+09 | 0.00 | 0.00 | 0.39 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 3928.63 | 20-FEB-15:00 | 3928.63 | 20-FEB-15:00 | 0.00 | 06-FEB-14:00 | 1042.56 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.783015E+09 | 0.210423E+09 | 104.08 | 0.783015E+09 | 192.72 | 0.00 | 0.50 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 5093.87 | 22-MAR-13:00 | 5093.87 | 22-MAR-13:00 | 0.06 | 10-MAR-19:00 | 1357.04 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.396567E+10 | 0.107456E+10 | 249.25 | 0.395311E+10 | 12558284.14 | 0.00 | 0.82 | 21-APR-14:00 | 0.00 | 01-APR-00:10 | 9097.17 | 21-APR-14:00 | 9097.17 | 21-APR-14:00 | 575.80 | 29-APR-06:03 | 2579.63 | 21-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.748493E+10 | 0.204489E+10 | 345.31 | 0.728768E+10 | 0.197252E+09 | 0.00 | 1.00 | 09-MAY-06:03 | 0.00 | 01-MAY-00:10 | 24567.03 | 30-MAY-06:02 | 24567.03 | 30-MAY-06:02 | 5135.79 | 28-MAY-07:03 | 5612.65 | 30-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.104192E+11 | 0.293764E+10 | 359.41 | 0.100488E+11 | 0.370429E+09 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 26516.87 | 04-JUN-07:02 | 25113.37 | 03-JUN-06:02 | 9091.77 | 28-JUN-06:02 | 5773.77 | 08-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.123281E+11 | 0.324579E+10 | 364.66 | 0.102203E+11 | 0.210781E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 28000.26 | 19-JUL-06:02 | 25598.01 | 03-JUL-06:01 | 15113.38 | 17-JUL-06:02 | 5990.37 | 16-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.108870E+11 | 0.288313E+10 | 371.76 | 0.956320E+10 | 0.132376E+10 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 27897.30 | 03-AUG-06:02 | 24810.47 | 27-AUG-07:02 | 12589.16 | 03-AUG-06:02 | 5926.99 | 06-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.937332E+10 | 0.244056E+10 | 345.60 | 0.821694E+10 | 0.115638E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:03 | 27357.25 | 23-SEP-06:02 | 20308.82 | 18-SEP-06:02 | 12639.82 | 14-SEP-06:02 | 5764.91 | 23-SEP-06:02 | 0.00 | 01-SEP-00:03 |
October | 0.464551E+10 | 0.119571E+10 | 272.83 | 0.420922E+10 | 0.436293E+09 | 0.00 | 1.00 | 02-OCT-06:01 | 0.00 | 01-OCT-00:10 | 26536.74 | 04-OCT-06:02 | 23816.38 | 02-OCT-06:01 | 11204.08 | 04-OCT-06:02 | 5633.36 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.586063E+09 | 0.154626E+09 | 89.58 | 0.579412E+09 | 6651198.98 | 0.00 | 0.55 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 5748.64 | 09-NOV-14:00 | 5748.64 | 09-NOV-14:00 | 434.65 | 03-NOV-12:40 | 1461.14 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.607659E+11 | 0.162664E+11 | 2552.64 | 0.551548E+11 | 0.561113E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.123281E+11 | 0.324579E+10 | 371.76 | 0.102203E+11 | 0.210781E+10 | 0.00 | 1.00 | 0.00 | 28000.26 | 25598.01 | 15113.38 | 5990.37 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 6813743.79 | 1894971.13 | 4.67 | 6813743.79 | -0.0 | 0.00 | 0.11 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 976.99 | 03-JAN-15:00 | 976.99 | 03-JAN-15:00 | 0.00 | 03-JAN-15:20 | 268.91 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 0.250628E+09 | 67804457.35 | 41.58 | 0.250628E+09 | 0.00 | 0.00 | 0.37 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 3665.71 | 20-FEB-15:00 | 3665.71 | 20-FEB-15:00 | 0.00 | 20-FEB-15:00 | 978.61 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.729583E+09 | 0.196547E+09 | 100.75 | 0.729582E+09 | 170.84 | 0.00 | 0.49 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4941.29 | 22-MAR-13:00 | 4941.29 | 22-MAR-13:00 | 0.05 | 10-MAR-19:00 | 1320.23 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.392721E+10 | 0.106436E+10 | 247.75 | 0.391475E+10 | 12466389.73 | 0.00 | 0.83 | 21-APR-14:00 | 0.00 | 01-APR-00:10 | 9078.33 | 21-APR-14:00 | 9078.33 | 21-APR-14:00 | 591.82 | 29-APR-06:03 | 2571.76 | 21-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.749788E+10 | 0.204577E+10 | 345.47 | 0.729978E+10 | 0.198101E+09 | 0.00 | 1.00 | 09-MAY-06:03 | 0.00 | 01-MAY-00:10 | 24406.16 | 30-MAY-06:02 | 24406.16 | 30-MAY-06:02 | 5256.72 | 28-MAY-07:03 | 5575.88 | 30-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.104640E+11 | 0.294483E+10 | 359.25 | 0.100918E+11 | 0.372198E+09 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 26338.35 | 04-JUN-07:02 | 24945.96 | 03-JUN-06:02 | 9019.80 | 28-JUN-06:02 | 5735.27 | 08-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.123763E+11 | 0.325198E+10 | 364.77 | 0.102634E+11 | 0.211293E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 27814.48 | 19-JUL-06:02 | 25434.32 | 03-JUL-06:01 | 14988.48 | 17-JUL-06:02 | 5950.00 | 16-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.109355E+11 | 0.289030E+10 | 371.80 | 0.960603E+10 | 0.132951E+10 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 27708.83 | 03-AUG-06:02 | 24646.24 | 27-AUG-07:02 | 12495.60 | 03-AUG-06:02 | 5887.22 | 06-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.940205E+10 | 0.244389E+10 | 345.77 | 0.824141E+10 | 0.116064E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:03 | 27173.07 | 23-SEP-06:02 | 20196.81 | 18-SEP-06:02 | 12550.26 | 14-SEP-06:02 | 5725.94 | 23-SEP-06:02 | 0.00 | 01-SEP-00:03 |
October | 0.462798E+10 | 0.119052E+10 | 273.17 | 0.419385E+10 | 0.434127E+09 | 0.00 | 1.00 | 02-OCT-06:01 | 0.00 | 01-OCT-00:10 | 26357.33 | 04-OCT-06:02 | 23673.35 | 02-OCT-06:01 | 11121.08 | 04-OCT-06:02 | 5595.22 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.556805E+09 | 0.146982E+09 | 84.75 | 0.550493E+09 | 6311960.26 | 0.00 | 0.54 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 5674.63 | 09-NOV-14:00 | 5674.63 | 09-NOV-14:00 | 424.01 | 03-NOV-12:40 | 1443.53 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.607748E+11 | 0.162449E+11 | 2539.73 | 0.551485E+11 | 0.562628E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.123763E+11 | 0.325198E+10 | 371.80 | 0.102634E+11 | 0.211293E+10 | 0.00 | 1.00 | 0.00 | 27814.48 | 25434.32 | 14988.48 | 5950.00 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 2036344.81 | 569707.02 | 2.83 | 2036344.81 | -0.0 | 0.00 | 0.06 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 583.39 | 03-JAN-15:00 | 583.39 | 03-JAN-15:00 | 0.00 | 03-JAN-14:10 | 162.29 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 0.204832E+09 | 55809840.29 | 37.25 | 0.204832E+09 | -0.0 | 0.00 | 0.34 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 3313.04 | 20-FEB-15:00 | 3313.04 | 20-FEB-15:00 | 0.00 | 20-FEB-15:50 | 892.56 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.631084E+09 | 0.171035E+09 | 92.67 | 0.631084E+09 | 97.95 | 0.00 | 0.46 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4641.05 | 22-MAR-13:00 | 4641.05 | 22-MAR-13:00 | 0.03 | 10-MAR-19:00 | 1249.55 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.374849E+10 | 0.102134E+10 | 240.17 | 0.373686E+10 | 11629580.36 | 0.00 | 0.81 | 21-APR-14:00 | 0.00 | 01-APR-00:10 | 8902.14 | 21-APR-14:00 | 8902.14 | 21-APR-14:00 | 377.70 | 18-APR-18:00 | 2532.90 | 21-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.728760E+10 | 0.199706E+10 | 344.92 | 0.709502E+10 | 0.192574E+09 | 0.00 | 1.00 | 09-MAY-06:03 | 0.00 | 01-MAY-00:10 | 24437.37 | 30-MAY-06:02 | 24437.37 | 30-MAY-06:02 | 4740.39 | 28-MAY-07:03 | 5583.03 | 30-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.102571E+11 | 0.289704E+10 | 359.43 | 0.989386E+10 | 0.363221E+09 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 26379.00 | 04-JUN-07:02 | 24978.69 | 03-JUN-06:02 | 8619.24 | 28-JUN-06:02 | 5742.44 | 08-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.121610E+11 | 0.320688E+10 | 365.16 | 0.100759E+11 | 0.208512E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 27848.95 | 19-JUL-06:02 | 25469.51 | 03-JUL-06:01 | 15047.31 | 17-JUL-06:02 | 5959.57 | 16-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.107183E+11 | 0.284339E+10 | 371.61 | 0.941563E+10 | 0.130264E+10 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 27753.20 | 03-AUG-06:02 | 24678.33 | 27-AUG-07:02 | 12567.92 | 03-AUG-06:02 | 5896.74 | 06-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.919564E+10 | 0.239943E+10 | 345.11 | 0.805943E+10 | 0.113621E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:03 | 27215.51 | 23-SEP-06:02 | 20197.05 | 18-SEP-06:02 | 12619.34 | 14-SEP-06:02 | 5735.31 | 23-SEP-06:02 | 0.00 | 01-SEP-00:03 |
October | 0.445907E+10 | 0.115150E+10 | 267.33 | 0.404124E+10 | 0.417827E+09 | 0.00 | 1.00 | 02-OCT-06:01 | 0.00 | 01-OCT-00:10 | 26399.22 | 04-OCT-06:02 | 23664.32 | 02-OCT-06:01 | 11181.34 | 04-OCT-06:02 | 5604.29 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.491675E+09 | 0.130187E+09 | 74.08 | 0.486365E+09 | 5309730.36 | 0.00 | 0.52 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 5470.82 | 09-NOV-14:00 | 5470.82 | 09-NOV-14:00 | 393.29 | 03-NOV-12:40 | 1398.81 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.591568E+11 | 0.158743E+11 | 2500.55 | 0.536423E+11 | 0.551454E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.121610E+11 | 0.320688E+10 | 371.61 | 0.100759E+11 | 0.208512E+10 | 0.00 | 1.00 | 0.00 | 27848.95 | 25469.51 | 15047.31 | 5959.57 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 396769.37 | 113613.11 | 0.67 | 396769.37 | 0.00 | 0.00 | 0.02 | 03-JAN-15:10 | 0.00 | 01-JAN-00:05 | 388.72 | 03-JAN-15:10 | 388.72 | 03-JAN-15:10 | 0.00 | 03-JAN-15:10 | 111.16 | 03-JAN-15:10 | 0.00 | 01-JAN-00:05 |
February | 0.285794E+09 | 79715156.86 | 31.50 | 0.285794E+09 | -0.0 | 0.00 | 0.32 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 | 5530.38 | 20-FEB-15:30 | 5530.38 | 20-FEB-15:30 | 0.00 | 19-FEB-15:50 | 1521.96 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 |
March | 0.914477E+09 | 0.253898E+09 | 80.67 | 0.914477E+09 | 0.00 | 0.00 | 0.45 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 7790.62 | 22-MAR-13:00 | 7790.62 | 22-MAR-13:00 | 0.00 | 19-MAR-14:10 | 2144.13 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.633798E+10 | 0.176675E+10 | 230.89 | 0.631638E+10 | 21602577.18 | 0.00 | 0.84 | 21-APR-14:20 | 0.00 | 01-APR-00:10 | 16196.47 | 21-APR-14:30 | 16196.47 | 21-APR-14:30 | 739.36 | 18-APR-17:00 | 4638.14 | 21-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.127712E+11 | 0.356803E+10 | 338.23 | 0.124162E+11 | 0.355018E+09 | 0.00 | 1.00 | 09-MAY-07:03 | 0.00 | 01-MAY-00:10 | 43128.92 | 30-MAY-07:02 | 43128.92 | 30-MAY-07:02 | 6082.06 | 28-MAY-08:63 | 10145.40 | 30-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.182190E+11 | 0.524615E+10 | 350.12 | 0.175844E+11 | 0.634582E+09 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 46047.97 | 04-JUN-08:62 | 43828.81 | 03-JUN-07:02 | 11058.39 | 28-JUN-07:03 | 10385.60 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.213266E+11 | 0.570837E+10 | 352.10 | 0.176623E+11 | 0.366425E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 48578.03 | 19-JUL-07:02 | 43893.53 | 03-JUL-07:01 | 27341.46 | 19-JUL-07:02 | 10783.66 | 02-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.189566E+11 | 0.510629E+10 | 361.40 | 0.166370E+11 | 0.231960E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 48277.79 | 03-AUG-07:02 | 44015.58 | 06-AUG-08:61 | 20286.38 | 14-AUG-07:02 | 10569.14 | 07-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.163150E+11 | 0.431901E+10 | 337.86 | 0.142670E+11 | 0.204798E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:03 | 47368.70 | 23-SEP-07:02 | 37266.43 | 20-SEP-07:02 | 21556.75 | 14-SEP-07:02 | 10377.73 | 10-SEP-08:62 | 0.00 | 01-SEP-00:03 |
October | 0.769144E+10 | 0.201986E+10 | 255.32 | 0.690651E+10 | 0.784927E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 45912.27 | 05-OCT-07:02 | 39437.86 | 02-OCT-07:02 | 14423.06 | 04-OCT-07:03 | 9924.68 | 05-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.742812E+09 | 0.200586E+09 | 62.47 | 0.734049E+09 | 8762563.06 | 0.00 | 0.52 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 9382.74 | 09-NOV-14:00 | 9382.74 | 09-NOV-14:00 | 702.86 | 03-NOV-12:50 | 2447.40 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.103561E+12 | 0.282688E+11 | 2401.23 | 0.937246E+11 | 0.983672E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.213266E+11 | 0.570837E+10 | 361.40 | 0.176623E+11 | 0.366425E+10 | 0.00 | 1.00 | 0.00 | 48578.03 | 44015.58 | 27341.46 | 10783.66 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 8734.92 | 2468.00 | 0.17 | 8734.92 | 0.00 | 0.00 | 0.00 | 03-JAN-15:10 | 0.00 | 01-JAN-00:05 | 14.56 | 03-JAN-15:10 | 14.56 | 03-JAN-15:10 | 0.00 | 01-JAN-00:05 | 4.11 | 03-JAN-15:10 | 0.00 | 01-JAN-00:05 |
February | 0.135969E+09 | 37325339.74 | 30.17 | 0.135969E+09 | -0.0 | 0.00 | 0.32 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 | 2786.23 | 20-FEB-15:30 | 2786.23 | 20-FEB-15:30 | 0.00 | 21-FEB-14:50 | 754.82 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 |
March | 0.444649E+09 | 0.121480E+09 | 76.33 | 0.444649E+09 | -0.0 | 0.00 | 0.44 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 3933.30 | 22-MAR-13:00 | 3933.30 | 22-MAR-13:00 | 0.00 | 22-MAR-15:30 | 1066.20 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.324656E+10 | 0.889617E+09 | 228.22 | 0.323620E+10 | 10352663.58 | 0.00 | 0.84 | 21-APR-14:20 | 0.00 | 01-APR-00:10 | 8365.83 | 21-APR-14:40 | 8365.83 | 21-APR-14:40 | 365.80 | 18-APR-17:00 | 2353.89 | 21-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.657262E+10 | 0.180485E+10 | 338.40 | 0.639399E+10 | 0.178622E+09 | 0.00 | 1.00 | 14-MAY-08:62 | 0.00 | 01-MAY-00:10 | 22274.45 | 30-MAY-07:02 | 22274.45 | 30-MAY-07:02 | 2833.60 | 28-MAY-08:63 | 5148.15 | 30-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.937739E+10 | 0.265490E+10 | 350.90 | 0.905799E+10 | 0.319398E+09 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 23780.31 | 04-JUN-08:62 | 22674.31 | 03-JUN-07:02 | 5124.54 | 28-JUN-07:03 | 5269.19 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.109852E+11 | 0.289144E+10 | 353.91 | 0.911410E+10 | 0.187107E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 25085.08 | 19-JUL-07:02 | 22668.48 | 03-JUL-07:01 | 14093.16 | 19-JUL-07:02 | 5470.49 | 02-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.975869E+10 | 0.258452E+10 | 362.31 | 0.858013E+10 | 0.117855E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24930.23 | 03-AUG-07:02 | 22777.70 | 06-AUG-08:61 | 10440.50 | 14-AUG-07:02 | 5362.47 | 07-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.840050E+10 | 0.218602E+10 | 338.15 | 0.736109E+10 | 0.103941E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:03 | 24461.33 | 23-SEP-07:02 | 18787.41 | 18-SEP-07:02 | 11110.10 | 14-SEP-07:02 | 5265.41 | 10-SEP-08:62 | 0.00 | 01-SEP-00:03 |
October | 0.395431E+10 | 0.102043E+10 | 252.49 | 0.355827E+10 | 0.396031E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 23709.22 | 05-OCT-07:02 | 20437.91 | 02-OCT-07:02 | 7169.14 | 05-OCT-07:02 | 5035.27 | 05-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.371978E+09 | 98691990.27 | 60.67 | 0.367958E+09 | 4019674.59 | 0.00 | 0.52 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4832.53 | 09-NOV-14:00 | 4832.53 | 09-NOV-14:00 | 341.00 | 03-NOV-12:50 | 1238.92 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.532478E+11 | 0.142893E+11 | 2391.71 | 0.482504E+11 | 0.499745E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.109852E+11 | 0.289144E+10 | 362.31 | 0.911410E+10 | 0.187107E+10 | 0.00 | 1.00 | 0.00 | 25085.08 | 22777.70 | 14093.16 | 5470.49 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.125394E+09 | 34499691.78 | 28.50 | 0.125394E+09 | 0.00 | 0.00 | 0.31 | 20-FEB-15:40 | 0.00 | 01-FEB-00:10 | 2678.94 | 20-FEB-15:40 | 2678.94 | 20-FEB-15:40 | 0.00 | 23-FEB-14:30 | 727.75 | 20-FEB-15:40 | 0.00 | 01-FEB-00:10 |
March | 0.416470E+09 | 0.114037E+09 | 74.17 | 0.416470E+09 | -0.0 | 0.00 | 0.43 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 3820.75 | 22-MAR-13:00 | 3820.75 | 22-MAR-13:00 | 0.00 | 14-MAR-16:40 | 1038.49 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.318530E+10 | 0.874161E+09 | 226.81 | 0.317544E+10 | 9866061.47 | 0.00 | 0.83 | 21-APR-14:20 | 0.00 | 01-APR-00:10 | 8304.35 | 21-APR-14:40 | 8304.35 | 21-APR-14:40 | 355.89 | 18-APR-17:00 | 2338.19 | 21-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.650583E+10 | 0.178791E+10 | 338.07 | 0.633057E+10 | 0.175260E+09 | 0.00 | 1.00 | 14-MAY-08:62 | 0.00 | 01-MAY-00:10 | 22175.18 | 30-MAY-07:02 | 22175.18 | 30-MAY-07:02 | 2698.96 | 28-MAY-08:63 | 5125.45 | 30-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.931174E+10 | 0.263756E+10 | 350.86 | 0.899760E+10 | 0.314145E+09 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 23680.93 | 04-JUN-08:62 | 22578.80 | 03-JUN-07:02 | 4942.99 | 04-JUN-08:62 | 5246.84 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.109088E+11 | 0.287242E+10 | 353.91 | 0.905603E+10 | 0.185282E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 24981.36 | 19-JUL-07:02 | 22574.39 | 03-JUL-07:01 | 14043.20 | 19-JUL-07:02 | 5447.34 | 02-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.968977E+10 | 0.256726E+10 | 361.98 | 0.852531E+10 | 0.116446E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24827.37 | 03-AUG-07:02 | 22691.97 | 06-AUG-08:61 | 10393.82 | 14-AUG-07:02 | 5340.21 | 07-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.833580E+10 | 0.217017E+10 | 337.32 | 0.730839E+10 | 0.102741E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:03 | 24360.13 | 23-SEP-07:02 | 18726.63 | 18-SEP-07:02 | 11063.96 | 14-SEP-07:02 | 5243.53 | 10-SEP-08:62 | 0.00 | 01-SEP-00:03 |
October | 0.390085E+10 | 0.100745E+10 | 251.49 | 0.351191E+10 | 0.388936E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 23611.12 | 05-OCT-07:02 | 20372.54 | 02-OCT-07:02 | 7136.02 | 05-OCT-07:02 | 5014.44 | 05-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.353885E+09 | 94002216.98 | 59.00 | 0.350136E+09 | 3748881.53 | 0.00 | 0.51 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4754.34 | 09-NOV-14:00 | 4754.34 | 09-NOV-14:00 | 326.58 | 03-NOV-12:50 | 1220.80 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.527339E+11 | 0.141595E+11 | 2382.10 | 0.477972E+11 | 0.493665E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.109088E+11 | 0.287242E+10 | 361.98 | 0.905603E+10 | 0.185282E+10 | 0.00 | 1.00 | 0.00 | 24981.36 | 22691.97 | 14043.20 | 5447.34 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.102029E+09 | 28241427.06 | 25.33 | 0.102029E+09 | 0.00 | 0.00 | 0.28 | 20-FEB-15:40 | 0.00 | 01-FEB-00:10 | 2439.36 | 20-FEB-15:40 | 2439.36 | 20-FEB-15:40 | 0.00 | 20-FEB-15:50 | 667.30 | 20-FEB-15:40 | 0.00 | 01-FEB-00:10 |
March | 0.351563E+09 | 96845352.42 | 67.42 | 0.351563E+09 | 0.00 | 0.00 | 0.40 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 3546.03 | 22-MAR-13:00 | 3546.03 | 22-MAR-13:00 | 0.00 | 14-MAR-15:00 | 971.39 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.304747E+10 | 0.840163E+09 | 221.86 | 0.303838E+10 | 9091645.72 | 0.00 | 0.82 | 21-APR-14:20 | 0.00 | 01-APR-00:10 | 8193.94 | 21-APR-14:40 | 8193.94 | 21-APR-14:40 | 339.83 | 18-APR-17:00 | 2313.80 | 21-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.639264E+10 | 0.176094E+10 | 335.12 | 0.622124E+10 | 0.171398E+09 | 0.00 | 1.00 | 14-MAY-08:62 | 0.00 | 01-MAY-00:10 | 21841.40 | 30-MAY-07:02 | 21841.40 | 30-MAY-07:02 | 2356.02 | 23-MAY-07:03 | 5049.32 | 30-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.926538E+10 | 0.262689E+10 | 351.00 | 0.895507E+10 | 0.310306E+09 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 23697.15 | 04-JUN-08:62 | 22594.30 | 03-JUN-07:02 | 4972.33 | 04-JUN-08:62 | 5247.41 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.108849E+11 | 0.286773E+10 | 353.76 | 0.903788E+10 | 0.184702E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 25000.58 | 19-JUL-07:02 | 22589.73 | 03-JUL-07:01 | 14085.55 | 19-JUL-07:02 | 5450.82 | 02-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.967620E+10 | 0.256443E+10 | 362.23 | 0.851802E+10 | 0.115818E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24847.26 | 03-AUG-07:02 | 22674.71 | 06-AUG-08:61 | 10416.04 | 14-AUG-07:02 | 5344.86 | 07-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.830915E+10 | 0.216411E+10 | 335.84 | 0.728624E+10 | 0.102291E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:03 | 24379.76 | 23-SEP-07:02 | 18732.29 | 18-SEP-07:02 | 11092.76 | 14-SEP-07:02 | 5247.91 | 10-SEP-08:62 | 0.00 | 01-SEP-00:03 |
October | 0.381062E+10 | 0.985978E+09 | 243.85 | 0.343179E+10 | 0.378834E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 23629.85 | 05-OCT-07:02 | 20375.80 | 02-OCT-07:02 | 7162.84 | 05-OCT-07:02 | 5018.51 | 05-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.315343E+09 | 84006992.30 | 54.56 | 0.312007E+09 | 3335545.50 | 0.00 | 0.50 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4611.42 | 09-NOV-14:00 | 4611.42 | 09-NOV-14:00 | 298.92 | 03-NOV-12:50 | 1188.79 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.521553E+11 | 0.140193E+11 | 2350.98 | 0.472542E+11 | 0.490108E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.108849E+11 | 0.286773E+10 | 362.23 | 0.903788E+10 | 0.184702E+10 | 0.00 | 1.00 | 0.00 | 25000.58 | 22674.71 | 14085.55 | 5450.82 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 42.48 | 12.01 | 0.33 | 42.48 | 0.00 | 0.00 | 0.00 | 03-JAN-17:00 | 0.00 | 01-JAN-00:05 | 0.05 | 03-JAN-17:00 | 0.05 | 03-JAN-17:00 | 0.00 | 03-JAN-17:00 | 0.01 | 03-JAN-17:00 | 0.00 | 01-JAN-00:05 |
February | 74857797.47 | 20926508.08 | 22.33 | 74857797.47 | 0.00 | 0.00 | 0.24 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 | 2235.75 | 20-FEB-15:30 | 2235.75 | 20-FEB-15:30 | 0.00 | 20-FEB-15:40 | 618.55 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 |
March | 0.287873E+09 | 80095911.89 | 57.17 | 0.287873E+09 | -0.0 | 0.00 | 0.36 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 3483.23 | 22-MAR-13:00 | 3483.23 | 22-MAR-13:00 | 0.00 | 14-MAR-15:30 | 963.75 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.315177E+10 | 0.873415E+09 | 213.67 | 0.314271E+10 | 9055570.34 | 0.00 | 0.81 | 21-APR-14:10 | 0.00 | 01-APR-00:10 | 8659.16 | 21-APR-14:20 | 8659.16 | 21-APR-14:20 | 329.61 | 18-APR-17:00 | 2462.30 | 21-APR-14:20 | 0.00 | 01-APR-00:10 |
May | 0.691031E+10 | 0.190605E+10 | 331.89 | 0.672305E+10 | 0.187256E+09 | 0.00 | 1.00 | 30-MAY-07:02 | 0.00 | 01-MAY-00:10 | 17537.31 | 30-MAY-07:02 | 17537.31 | 30-MAY-07:02 | 2042.21 | 24-MAY-13:00 | 4063.57 | 30-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.102950E+11 | 0.291004E+10 | 350.01 | 0.994876E+10 | 0.346249E+09 | 0.00 | 1.00 | 01-JUN-14:10 | 0.00 | 01-JUN-00:10 | 25805.55 | 04-JUN-08:62 | 24757.34 | 18-JUN-08:61 | 5317.83 | 04-JUN-08:62 | 5743.25 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.122292E+11 | 0.321313E+10 | 354.97 | 0.101795E+11 | 0.204975E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 27236.09 | 17-JUL-07:02 | 24725.47 | 03-JUL-07:01 | 11950.20 | 18-JUL-07:02 | 5976.43 | 02-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.109787E+11 | 0.289267E+10 | 361.02 | 0.968181E+10 | 0.129685E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 27169.87 | 03-AUG-07:02 | 24242.51 | 27-AUG-08:62 | 11905.06 | 14-AUG-07:02 | 5879.90 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.945354E+10 | 0.244470E+10 | 334.54 | 0.830015E+10 | 0.115339E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:03 | 26669.54 | 23-SEP-07:02 | 19251.80 | 18-SEP-07:02 | 11019.38 | 14-SEP-07:02 | 5728.96 | 10-SEP-08:62 | 0.00 | 01-SEP-00:03 |
October | 0.410707E+10 | 0.106235E+10 | 234.71 | 0.370448E+10 | 0.402591E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 24895.98 | 02-OCT-07:02 | 21956.91 | 02-OCT-07:02 | 6655.24 | 05-OCT-07:02 | 5373.15 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.291244E+09 | 77774768.04 | 46.17 | 0.287941E+09 | 3302611.41 | 0.00 | 0.48 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4824.58 | 09-NOV-14:00 | 4824.58 | 09-NOV-14:00 | 295.29 | 03-NOV-12:50 | 1249.98 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.577795E+11 | 0.154812E+11 | 2306.80 | 0.523311E+11 | 0.544845E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.122292E+11 | 0.321313E+10 | 361.02 | 0.101795E+11 | 0.204975E+10 | 0.00 | 1.00 | 0.00 | 27236.09 | 24757.34 | 11950.20 | 5976.43 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 135.57 | 75.01 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.12 | 67.51 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.07 | 60.57 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.84 | 38.39 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.62 | 22.83 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 69.51 | 11.59 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 70.45 | 9.55 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 83.53 | 13.86 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.71 | 26.52 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.57 | 42.56 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 144.46 | 67.55 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 135.78 | 81.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.04 | 42.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.62 | 9.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 144.46 | 81.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 135.57 | 75.01 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.12 | 67.51 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.07 | 60.57 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.84 | 38.39 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.62 | 22.83 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 69.51 | 11.59 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 70.45 | 9.55 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 83.53 | 13.86 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.71 | 26.52 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.57 | 42.56 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 144.46 | 67.55 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 135.78 | 81.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.04 | 42.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.62 | 9.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 144.46 | 81.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 135.57 | 75.01 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.12 | 67.51 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.07 | 60.57 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.84 | 38.39 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.62 | 22.83 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 69.51 | 11.59 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 70.45 | 9.55 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 83.53 | 13.86 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.71 | 26.52 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.57 | 42.56 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 144.46 | 67.55 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 135.78 | 81.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.04 | 42.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.62 | 9.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 144.46 | 81.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 135.57 | 75.01 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.12 | 67.51 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.07 | 60.57 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.84 | 38.39 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.62 | 22.83 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 69.51 | 11.59 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 70.45 | 9.55 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 83.53 | 13.86 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.71 | 26.52 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.57 | 42.56 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 144.46 | 67.55 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 135.78 | 81.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.04 | 42.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.62 | 9.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 144.46 | 81.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.27 | 89.61 | 28.67 | 163.38 | 89.12 | 0.00 | 0.00 | 0.00 |
February | 109.71 | 77.35 | 32.37 | 154.39 | 80.22 | 0.00 | 0.00 | 0.00 |
March | 89.16 | 51.41 | 37.75 | 129.13 | 72.05 | 0.00 | 0.00 | 0.00 |
April | 60.45 | 22.56 | 37.90 | 98.44 | 45.82 | 0.00 | 0.00 | 0.00 |
May | 42.72 | 5.98 | 36.74 | 77.37 | 27.40 | 0.00 | 0.00 | 0.00 |
June | 36.86 | 2.34 | 34.52 | 82.80 | 13.95 | 0.00 | 0.00 | 0.00 |
July | 37.57 | 3.48 | 34.09 | 84.09 | 11.48 | 0.00 | 0.00 | 0.00 |
August | 47.89 | 12.68 | 35.22 | 99.93 | 16.62 | 0.00 | 0.00 | 0.00 |
September | 74.76 | 38.84 | 35.92 | 141.22 | 31.72 | 0.00 | 0.00 | 0.00 |
October | 101.57 | 68.67 | 32.90 | 163.00 | 50.73 | 0.00 | 0.00 | 0.00 |
November | 122.24 | 93.19 | 29.05 | 173.92 | 80.36 | 0.00 | 0.00 | 0.00 |
December | 121.14 | 90.93 | 30.21 | 163.54 | 96.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.03 | 46.24 | 33.78 | 127.42 | 51.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.86 | 2.34 | 28.67 | 77.37 | 11.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.24 | 93.19 | 37.90 | 173.92 | 96.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.27 | 89.61 | 28.67 | 163.38 | 89.12 | 0.00 | 0.00 | 0.00 |
February | 109.71 | 77.35 | 32.37 | 154.39 | 80.22 | 0.00 | 0.00 | 0.00 |
March | 89.16 | 51.41 | 37.75 | 129.13 | 72.05 | 0.00 | 0.00 | 0.00 |
April | 60.45 | 22.56 | 37.90 | 98.44 | 45.82 | 0.00 | 0.00 | 0.00 |
May | 42.72 | 5.98 | 36.74 | 77.37 | 27.40 | 0.00 | 0.00 | 0.00 |
June | 36.86 | 2.34 | 34.52 | 82.80 | 13.95 | 0.00 | 0.00 | 0.00 |
July | 37.57 | 3.48 | 34.09 | 84.09 | 11.48 | 0.00 | 0.00 | 0.00 |
August | 47.89 | 12.68 | 35.22 | 99.93 | 16.62 | 0.00 | 0.00 | 0.00 |
September | 74.76 | 38.84 | 35.92 | 141.22 | 31.72 | 0.00 | 0.00 | 0.00 |
October | 101.57 | 68.67 | 32.90 | 163.00 | 50.73 | 0.00 | 0.00 | 0.00 |
November | 122.24 | 93.19 | 29.05 | 173.92 | 80.36 | 0.00 | 0.00 | 0.00 |
December | 121.14 | 90.93 | 30.21 | 163.54 | 96.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.03 | 46.24 | 33.78 | 127.42 | 51.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.86 | 2.34 | 28.67 | 77.37 | 11.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.24 | 93.19 | 37.90 | 173.92 | 96.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 133.21 | 80.50 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 125.70 | 72.26 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 104.90 | 64.01 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.08 | 39.46 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.57 | 23.14 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 69.92 | 11.77 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 70.92 | 9.65 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 83.95 | 13.89 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.84 | 26.37 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.18 | 42.92 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 143.01 | 70.07 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 133.48 | 86.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 105.17 | 44.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.57 | 9.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 143.01 | 86.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 133.21 | 80.50 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 125.70 | 72.26 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 104.90 | 64.01 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.08 | 39.46 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.57 | 23.14 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 69.92 | 11.77 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 70.92 | 9.65 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 83.95 | 13.89 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.84 | 26.37 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.18 | 42.92 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 143.01 | 70.07 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 133.48 | 86.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 105.17 | 44.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.57 | 9.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 143.01 | 86.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.27 | 89.61 | 28.67 | 160.63 | 95.55 | 0.00 | 0.00 | 0.00 |
February | 109.71 | 77.35 | 32.37 | 151.58 | 85.80 | 0.00 | 0.00 | 0.00 |
March | 89.16 | 51.41 | 37.75 | 126.61 | 76.08 | 0.00 | 0.00 | 0.00 |
April | 60.45 | 22.56 | 37.90 | 97.55 | 47.08 | 0.00 | 0.00 | 0.00 |
May | 42.72 | 5.98 | 36.74 | 77.29 | 27.78 | 0.00 | 0.00 | 0.00 |
June | 36.86 | 2.34 | 34.52 | 83.27 | 14.17 | 0.00 | 0.00 | 0.00 |
July | 37.57 | 3.48 | 34.09 | 84.64 | 11.59 | 0.00 | 0.00 | 0.00 |
August | 47.89 | 12.68 | 35.22 | 100.42 | 16.65 | 0.00 | 0.00 | 0.00 |
September | 74.76 | 38.84 | 35.92 | 141.41 | 31.54 | 0.00 | 0.00 | 0.00 |
October | 101.57 | 68.67 | 32.90 | 162.59 | 51.13 | 0.00 | 0.00 | 0.00 |
November | 122.24 | 93.19 | 29.05 | 172.25 | 83.32 | 0.00 | 0.00 | 0.00 |
December | 121.14 | 90.93 | 30.21 | 160.85 | 102.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.03 | 46.24 | 33.78 | 126.42 | 53.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.86 | 2.34 | 28.67 | 77.29 | 11.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.24 | 93.19 | 37.90 | 172.25 | 102.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 133.97 | 77.94 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 126.24 | 70.66 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 105.21 | 63.32 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 80.81 | 40.70 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 63.88 | 25.06 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.27 | 13.38 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.25 | 11.35 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.67 | 15.73 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.46 | 28.79 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 134.97 | 44.48 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 143.37 | 69.59 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 134.21 | 83.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 104.88 | 45.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 63.88 | 11.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 143.37 | 83.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 133.97 | 77.94 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 126.24 | 70.66 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 105.21 | 63.32 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 80.81 | 40.70 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 63.88 | 25.06 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.27 | 13.38 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.25 | 11.35 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.67 | 15.73 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.46 | 28.79 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 134.97 | 44.48 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 143.37 | 69.59 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 134.21 | 83.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 104.88 | 45.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 63.88 | 11.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 143.37 | 83.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 160.65 | 92.03 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 151.38 | 83.45 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 126.28 | 74.85 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 96.71 | 48.26 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.09 | 29.87 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 80.92 | 16.01 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 82.27 | 13.54 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 98.42 | 18.73 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 140.19 | 34.19 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 161.45 | 52.67 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 171.74 | 82.27 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 160.84 | 99.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 125.40 | 53.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.09 | 13.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 171.74 | 99.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 134.47 | 76.47 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 126.67 | 69.47 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 105.54 | 62.52 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 80.87 | 40.53 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 63.86 | 25.15 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.18 | 13.57 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.16 | 11.54 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.61 | 15.92 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.43 | 28.94 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 134.98 | 44.42 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 143.61 | 68.95 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 134.69 | 82.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 105.03 | 44.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 63.86 | 11.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 143.61 | 82.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 134.47 | 76.47 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 126.67 | 69.47 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 105.54 | 62.52 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 80.87 | 40.53 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 63.86 | 25.15 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.18 | 13.57 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.16 | 11.54 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.61 | 15.92 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.43 | 28.94 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 134.98 | 44.42 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 143.61 | 68.95 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 134.69 | 82.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 105.03 | 44.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 63.86 | 11.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 143.61 | 82.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 161.25 | 90.29 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 151.90 | 82.04 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 126.67 | 73.91 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 96.79 | 48.06 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.06 | 29.97 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 80.83 | 16.23 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 82.17 | 13.76 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 98.34 | 18.95 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 140.16 | 34.36 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 161.47 | 52.59 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 172.02 | 81.53 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 161.41 | 97.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 125.58 | 53.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.06 | 13.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 172.02 | 97.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 135.08 | 75.02 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 127.28 | 68.12 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 106.09 | 61.48 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.12 | 39.94 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.03 | 24.74 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.38 | 13.25 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.33 | 11.23 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.75 | 15.59 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.55 | 28.57 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.14 | 43.98 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 143.98 | 68.18 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 135.29 | 81.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 105.35 | 44.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.03 | 11.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 143.98 | 81.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 135.08 | 75.02 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 127.28 | 68.12 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 106.09 | 61.48 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.12 | 39.94 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.03 | 24.74 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.38 | 13.25 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.33 | 11.23 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.75 | 15.59 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.55 | 28.57 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.14 | 43.98 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 143.98 | 68.18 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 135.29 | 81.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 105.35 | 44.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.03 | 11.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 143.98 | 81.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 161.97 | 88.58 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 152.62 | 80.46 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 127.33 | 72.68 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 97.08 | 47.37 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.27 | 29.50 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 81.06 | 15.85 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 82.37 | 13.41 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 98.51 | 18.57 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 140.30 | 33.93 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 161.66 | 52.08 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 172.46 | 80.61 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 162.12 | 95.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 125.97 | 52.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.27 | 13.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 172.46 | 95.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 136.56 | 71.98 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.80 | 65.20 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.60 | 58.95 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.85 | 38.27 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.30 | 23.43 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.67 | 12.29 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.46 | 10.31 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.87 | 14.54 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.68 | 27.34 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.63 | 42.66 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.03 | 66.18 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 136.76 | 78.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.11 | 42.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.30 | 10.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.03 | 78.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 136.56 | 71.98 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.80 | 65.20 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.60 | 58.95 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.85 | 38.27 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.30 | 23.43 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.67 | 12.29 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.46 | 10.31 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.87 | 14.54 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.68 | 27.34 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.63 | 42.66 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.03 | 66.18 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 136.76 | 78.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.11 | 42.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.30 | 10.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.03 | 78.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 136.56 | 71.98 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.80 | 65.20 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.60 | 58.95 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.85 | 38.27 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.30 | 23.43 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.67 | 12.29 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.46 | 10.31 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.87 | 14.54 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.68 | 27.34 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.63 | 42.66 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.03 | 66.18 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 136.76 | 78.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.11 | 42.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.30 | 10.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.03 | 78.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 136.56 | 71.98 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.80 | 65.20 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.60 | 58.95 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.85 | 38.27 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.30 | 23.43 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.67 | 12.29 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.46 | 10.31 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.87 | 14.54 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.68 | 27.34 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.63 | 42.66 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.03 | 66.18 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 136.76 | 78.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.11 | 42.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.30 | 10.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.03 | 78.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 163.67 | 85.03 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 154.37 | 77.05 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 129.06 | 69.73 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 97.93 | 45.40 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.59 | 27.93 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 81.41 | 14.70 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 82.53 | 12.31 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 98.66 | 17.32 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 140.44 | 32.48 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.20 | 50.53 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 173.66 | 78.28 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 163.82 | 92.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 126.84 | 50.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.59 | 12.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 173.66 | 92.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 163.67 | 85.03 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 154.37 | 77.05 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 129.06 | 69.73 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 97.93 | 45.40 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.59 | 27.93 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 81.41 | 14.70 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 82.53 | 12.31 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 98.66 | 17.32 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 140.44 | 32.48 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.20 | 50.53 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 173.66 | 78.28 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 163.82 | 92.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 126.84 | 50.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.59 | 12.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 173.66 | 92.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 136.31 | 71.83 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.57 | 65.06 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.39 | 58.78 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.79 | 38.02 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.50 | 23.09 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 69.18 | 11.95 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.87 | 9.98 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 83.15 | 14.17 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.71 | 26.96 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.46 | 42.43 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 144.79 | 66.08 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 136.54 | 78.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.12 | 42.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.50 | 9.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 144.79 | 78.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 136.31 | 71.83 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.57 | 65.06 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.39 | 58.78 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.79 | 38.02 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.50 | 23.09 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 69.18 | 11.95 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.87 | 9.98 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 83.15 | 14.17 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.71 | 26.96 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.46 | 42.43 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 144.79 | 66.08 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 136.54 | 78.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.12 | 42.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.50 | 9.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 144.79 | 78.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 163.43 | 84.81 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 154.17 | 76.86 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 128.88 | 69.50 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 97.89 | 45.10 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.82 | 27.54 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 81.99 | 14.30 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 83.00 | 11.92 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 98.99 | 16.89 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 140.51 | 32.03 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.05 | 50.25 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 173.44 | 78.14 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 163.62 | 92.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 126.88 | 49.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.82 | 11.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 173.44 | 92.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 136.51 | 71.34 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.80 | 64.59 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.65 | 58.31 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.93 | 37.78 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.58 | 22.97 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 69.26 | 11.87 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.94 | 9.90 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 83.21 | 14.09 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.76 | 26.87 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.53 | 42.28 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 144.99 | 65.74 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 136.73 | 77.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.26 | 41.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.58 | 9.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 144.99 | 77.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 136.51 | 71.34 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.80 | 64.59 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.65 | 58.31 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.93 | 37.78 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.58 | 22.97 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 69.26 | 11.87 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.94 | 9.90 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 83.21 | 14.09 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.76 | 26.87 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.53 | 42.28 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 144.99 | 65.74 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 136.73 | 77.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.26 | 41.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.58 | 9.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 144.99 | 77.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 163.68 | 84.24 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 154.44 | 76.31 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 129.19 | 68.95 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 98.05 | 44.82 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.92 | 27.40 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 82.09 | 14.21 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 83.09 | 11.83 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 99.06 | 16.79 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 140.57 | 31.92 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.14 | 50.07 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 173.68 | 77.74 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 163.84 | 91.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 127.05 | 49.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.92 | 11.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 173.68 | 91.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 136.99 | 70.07 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 129.38 | 63.28 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 108.28 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.26 | 37.06 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.69 | 22.67 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 69.27 | 11.77 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.91 | 9.86 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 83.17 | 14.07 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.75 | 26.80 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.68 | 41.91 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.50 | 64.79 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 137.17 | 76.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.52 | 41.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.69 | 9.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.50 | 76.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 136.99 | 70.07 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 129.38 | 63.28 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 108.28 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.26 | 37.06 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.69 | 22.67 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 69.27 | 11.77 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.91 | 9.86 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 83.17 | 14.07 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.75 | 26.80 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.68 | 41.91 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.50 | 64.79 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 137.17 | 76.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.52 | 41.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.69 | 9.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.50 | 76.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 164.25 | 82.74 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 155.12 | 74.76 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 129.94 | 67.40 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 98.44 | 43.98 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 77.05 | 27.05 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 82.10 | 14.10 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 83.06 | 11.77 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 99.01 | 16.76 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 140.56 | 31.84 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.31 | 49.64 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 174.28 | 76.62 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 164.37 | 90.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 127.36 | 48.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 77.05 | 11.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 174.28 | 90.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 138.10 | 65.83 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 130.66 | 58.85 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 109.50 | 52.57 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.70 | 34.41 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.52 | 21.48 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.52 | 11.46 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.94 | 9.87 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.20 | 14.18 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.02 | 26.79 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.76 | 40.62 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.45 | 61.69 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.21 | 72.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.72 | 39.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.52 | 9.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.45 | 72.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 138.10 | 65.83 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 130.66 | 58.85 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 109.50 | 52.57 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.70 | 34.41 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.52 | 21.48 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.52 | 11.46 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.94 | 9.87 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.20 | 14.18 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.02 | 26.79 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.76 | 40.62 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.45 | 61.69 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.21 | 72.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.72 | 39.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.52 | 9.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.45 | 72.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 165.58 | 77.74 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 156.66 | 69.54 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 131.39 | 62.19 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 98.97 | 40.86 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.85 | 25.66 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 81.20 | 13.73 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 81.89 | 11.80 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.86 | 16.90 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.68 | 31.84 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.41 | 48.12 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 175.42 | 72.96 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 165.63 | 86.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 127.60 | 46.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.85 | 11.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 175.42 | 86.08 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.363119E+09 | 0.200918E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.309936E+09 | 0.163314E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.286765E+09 | 0.162237E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212124E+09 | 99500778.21 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.173088E+09 | 61150858.74 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.180174E+09 | 30032612.23 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.188680E+09 | 25582371.42 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.223737E+09 | 37133438.78 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.305102E+09 | 68740005.44 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363100E+09 | 0.113996E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.374433E+09 | 0.175092E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.363663E+09 | 0.216971E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334392E+10 | 0.135467E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.173088E+09 | 25582371.42 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.374433E+09 | 0.216971E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.363119E+09 | 0.200918E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.309936E+09 | 0.163314E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.286765E+09 | 0.162237E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212124E+09 | 99500778.21 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.173088E+09 | 61150858.74 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.180174E+09 | 30032612.23 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.188680E+09 | 25582371.42 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.223737E+09 | 37133438.78 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.305102E+09 | 68740005.44 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363100E+09 | 0.113996E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.374433E+09 | 0.175092E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.363663E+09 | 0.216971E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334392E+10 | 0.135467E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.173088E+09 | 25582371.42 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.374433E+09 | 0.216971E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.363119E+09 | 0.200918E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.309936E+09 | 0.163314E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.286765E+09 | 0.162237E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212124E+09 | 99500778.21 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.173088E+09 | 61150858.74 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.180174E+09 | 30032612.23 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.188680E+09 | 25582371.42 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.223737E+09 | 37133438.78 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.305102E+09 | 68740005.44 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363100E+09 | 0.113996E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.374433E+09 | 0.175092E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.363663E+09 | 0.216971E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334392E+10 | 0.135467E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.173088E+09 | 25582371.42 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.374433E+09 | 0.216971E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.363119E+09 | 0.200918E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.309936E+09 | 0.163314E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.286765E+09 | 0.162237E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212124E+09 | 99500778.21 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.173088E+09 | 61150858.74 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.180174E+09 | 30032612.23 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.188680E+09 | 25582371.42 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.223737E+09 | 37133438.78 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.305102E+09 | 68740005.44 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363100E+09 | 0.113996E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.374433E+09 | 0.175092E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.363663E+09 | 0.216971E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334392E+10 | 0.135467E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.173088E+09 | 25582371.42 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.374433E+09 | 0.216971E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316787E+09 | 0.239999E+09 | 76787787.94 | 0.437605E+09 | 0.238688E+09 |
February | 0.265418E+09 | 0.187115E+09 | 78302345.55 | 0.373511E+09 | 0.194057E+09 |
March | 0.238818E+09 | 0.137702E+09 | 0.101116E+09 | 0.345868E+09 | 0.192969E+09 |
April | 0.156695E+09 | 58466780.93 | 98228034.59 | 0.255145E+09 | 0.118756E+09 |
May | 0.114426E+09 | 16015840.86 | 98409804.77 | 0.207223E+09 | 73394354.44 |
June | 95535986.37 | 6061786.34 | 89474200.03 | 0.214619E+09 | 36154442.58 |
July | 0.100635E+09 | 9329009.15 | 91305690.16 | 0.225227E+09 | 30746444.65 |
August | 0.128281E+09 | 33956884.46 | 94324609.58 | 0.267652E+09 | 44519046.83 |
September | 0.193774E+09 | 0.100672E+09 | 93101553.68 | 0.366051E+09 | 82217825.86 |
October | 0.272058E+09 | 0.183929E+09 | 88128496.15 | 0.436580E+09 | 0.135863E+09 |
November | 0.316835E+09 | 0.241548E+09 | 75287263.97 | 0.450794E+09 | 0.208305E+09 |
December | 0.324462E+09 | 0.243556E+09 | 80906164.45 | 0.438025E+09 | 0.257994E+09 |
Annual Sum or Average | 0.252372E+10 | 0.145835E+10 | 0.106537E+10 | 0.401830E+10 | 0.161366E+10 |
Minimum of Months | 95535986.37 | 6061786.34 | 75287263.97 | 0.207223E+09 | 30746444.65 |
Maximum of Months | 0.324462E+09 | 0.243556E+09 | 0.101116E+09 | 0.450794E+09 | 0.257994E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316787E+09 | 0.239999E+09 | 76787787.94 | 0.437605E+09 | 0.238688E+09 |
February | 0.265418E+09 | 0.187115E+09 | 78302345.55 | 0.373511E+09 | 0.194057E+09 |
March | 0.238818E+09 | 0.137702E+09 | 0.101116E+09 | 0.345868E+09 | 0.192969E+09 |
April | 0.156695E+09 | 58466780.93 | 98228034.59 | 0.255145E+09 | 0.118756E+09 |
May | 0.114426E+09 | 16015840.86 | 98409804.77 | 0.207223E+09 | 73394354.44 |
June | 95535986.37 | 6061786.34 | 89474200.03 | 0.214619E+09 | 36154442.58 |
July | 0.100635E+09 | 9329009.15 | 91305690.16 | 0.225227E+09 | 30746444.65 |
August | 0.128281E+09 | 33956884.46 | 94324609.58 | 0.267652E+09 | 44519046.83 |
September | 0.193774E+09 | 0.100672E+09 | 93101553.68 | 0.366051E+09 | 82217825.86 |
October | 0.272058E+09 | 0.183929E+09 | 88128496.15 | 0.436580E+09 | 0.135863E+09 |
November | 0.316835E+09 | 0.241548E+09 | 75287263.97 | 0.450794E+09 | 0.208305E+09 |
December | 0.324462E+09 | 0.243556E+09 | 80906164.45 | 0.438025E+09 | 0.257994E+09 |
Annual Sum or Average | 0.252372E+10 | 0.145835E+10 | 0.106537E+10 | 0.401830E+10 | 0.161366E+10 |
Minimum of Months | 95535986.37 | 6061786.34 | 75287263.97 | 0.207223E+09 | 30746444.65 |
Maximum of Months | 0.324462E+09 | 0.243556E+09 | 0.101116E+09 | 0.450794E+09 | 0.257994E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.356789E+09 | 0.215614E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.304105E+09 | 0.174823E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.280966E+09 | 0.171440E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.210156E+09 | 0.102281E+09 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172935E+09 | 61989947.97 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.181242E+09 | 30514350.29 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.189945E+09 | 25840403.11 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.224841E+09 | 37199689.93 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.305442E+09 | 68363046.39 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.362067E+09 | 0.114949E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.370685E+09 | 0.181632E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.357513E+09 | 0.231241E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.331669E+10 | 0.141589E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172935E+09 | 25840403.11 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.370685E+09 | 0.231241E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.356789E+09 | 0.215614E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.304105E+09 | 0.174823E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.280966E+09 | 0.171440E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.210156E+09 | 0.102281E+09 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172935E+09 | 61989947.97 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.181242E+09 | 30514350.29 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.189945E+09 | 25840403.11 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.224841E+09 | 37199689.93 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.305442E+09 | 68363046.39 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.362067E+09 | 0.114949E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.370685E+09 | 0.181632E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.357513E+09 | 0.231241E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.331669E+10 | 0.141589E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172935E+09 | 25840403.11 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.370685E+09 | 0.231241E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316787E+09 | 0.239999E+09 | 76787787.94 | 0.430229E+09 | 0.255918E+09 |
February | 0.265418E+09 | 0.187115E+09 | 78302345.55 | 0.366692E+09 | 0.207563E+09 |
March | 0.238818E+09 | 0.137702E+09 | 0.101116E+09 | 0.339103E+09 | 0.203780E+09 |
April | 0.156695E+09 | 58466780.93 | 98228034.59 | 0.252850E+09 | 0.122032E+09 |
May | 0.114426E+09 | 16015840.86 | 98409804.77 | 0.207023E+09 | 74395904.07 |
June | 95535986.37 | 6061786.34 | 89474200.03 | 0.215828E+09 | 36739784.69 |
July | 0.100635E+09 | 9329009.15 | 91305690.16 | 0.226708E+09 | 31055921.68 |
August | 0.128281E+09 | 33956884.46 | 94324609.58 | 0.268977E+09 | 44598701.58 |
September | 0.193774E+09 | 0.100672E+09 | 93101553.68 | 0.366531E+09 | 81756380.88 |
October | 0.272058E+09 | 0.183929E+09 | 88128496.15 | 0.435473E+09 | 0.136954E+09 |
November | 0.316835E+09 | 0.241548E+09 | 75287263.97 | 0.446468E+09 | 0.215957E+09 |
December | 0.324462E+09 | 0.243556E+09 | 80906164.45 | 0.430831E+09 | 0.274744E+09 |
Annual Sum or Average | 0.252372E+10 | 0.145835E+10 | 0.106537E+10 | 0.398671E+10 | 0.168549E+10 |
Minimum of Months | 95535986.37 | 6061786.34 | 75287263.97 | 0.207023E+09 | 31055921.68 |
Maximum of Months | 0.324462E+09 | 0.243556E+09 | 0.101116E+09 | 0.446468E+09 | 0.274744E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.358818E+09 | 0.208767E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.305396E+09 | 0.170943E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.281793E+09 | 0.169588E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.209467E+09 | 0.105489E+09 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171103E+09 | 67116259.49 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.176946E+09 | 34682584.39 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.185476E+09 | 30389668.64 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.221435E+09 | 42120494.06 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.304457E+09 | 74626403.76 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.361492E+09 | 0.119146E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.371625E+09 | 0.180369E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.359467E+09 | 0.224546E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.330748E+10 | 0.142778E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171103E+09 | 30389668.64 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.371625E+09 | 0.224546E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.358818E+09 | 0.208767E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.305396E+09 | 0.170943E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.281793E+09 | 0.169588E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.209467E+09 | 0.105489E+09 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171103E+09 | 67116259.49 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.176946E+09 | 34682584.39 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.185476E+09 | 30389668.64 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.221435E+09 | 42120494.06 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.304457E+09 | 74626403.76 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.361492E+09 | 0.119146E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.371625E+09 | 0.180369E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.359467E+09 | 0.224546E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.330748E+10 | 0.142778E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171103E+09 | 30389668.64 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.371625E+09 | 0.224546E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.430277E+09 | 0.246486E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.366219E+09 | 0.201874E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.338233E+09 | 0.200477E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.250684E+09 | 0.125096E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.203804E+09 | 79994440.92 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.209749E+09 | 41488241.07 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.220355E+09 | 36260616.87 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.263617E+09 | 50160190.22 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.363383E+09 | 88616498.32 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.432426E+09 | 0.141072E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.445145E+09 | 0.213256E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.430790E+09 | 0.265379E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.395468E+10 | 0.169016E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.203804E+09 | 36260616.87 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.445145E+09 | 0.265379E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.360169E+09 | 0.204810E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.306445E+09 | 0.168062E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.282670E+09 | 0.167463E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.209623E+09 | 0.105048E+09 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171039E+09 | 67351946.90 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.176733E+09 | 35166680.15 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.185238E+09 | 30898904.61 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.221254E+09 | 42633854.59 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.304386E+09 | 75005756.41 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.361542E+09 | 0.118974E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.372226E+09 | 0.178728E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.360752E+09 | 0.220834E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.331208E+10 | 0.141498E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171039E+09 | 30898904.61 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.372226E+09 | 0.220834E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.360169E+09 | 0.204810E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.306445E+09 | 0.168062E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.282670E+09 | 0.167463E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.209623E+09 | 0.105048E+09 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171039E+09 | 67351946.90 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.176733E+09 | 35166680.15 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.185238E+09 | 30898904.61 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.221254E+09 | 42633854.59 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.304386E+09 | 75005756.41 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.361542E+09 | 0.118974E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.372226E+09 | 0.178728E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.360752E+09 | 0.220834E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.331208E+10 | 0.141498E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171039E+09 | 30898904.61 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.372226E+09 | 0.220834E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.431885E+09 | 0.241820E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.367467E+09 | 0.198482E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.339276E+09 | 0.197971E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.250870E+09 | 0.124577E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.203727E+09 | 80273278.92 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.209499E+09 | 42062285.94 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.220075E+09 | 36864011.13 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.263402E+09 | 50768370.31 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.363298E+09 | 89063952.34 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.432487E+09 | 0.140870E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.445864E+09 | 0.211321E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.432321E+09 | 0.260995E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.396017E+10 | 0.167507E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.203727E+09 | 36864011.13 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.445864E+09 | 0.260995E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.361801E+09 | 0.200932E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.307913E+09 | 0.164806E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.284163E+09 | 0.164656E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.210255E+09 | 0.103531E+09 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171495E+09 | 66270042.60 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.177244E+09 | 34345238.54 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.185690E+09 | 30091426.39 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.221639E+09 | 41761265.27 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.304691E+09 | 74053315.02 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.361955E+09 | 0.117806E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.373196E+09 | 0.176711E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.362360E+09 | 0.217146E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.332240E+10 | 0.139211E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171495E+09 | 30091426.39 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.373196E+09 | 0.217146E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.361801E+09 | 0.200932E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.307913E+09 | 0.164806E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.284163E+09 | 0.164656E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.210255E+09 | 0.103531E+09 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171495E+09 | 66270042.60 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.177244E+09 | 34345238.54 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.185690E+09 | 30091426.39 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.221639E+09 | 41761265.27 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.304691E+09 | 74053315.02 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.361955E+09 | 0.117806E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.373196E+09 | 0.176711E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.362360E+09 | 0.217146E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.332240E+10 | 0.139211E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171495E+09 | 30091426.39 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.373196E+09 | 0.217146E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.433822E+09 | 0.237248E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.369212E+09 | 0.194651E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.341052E+09 | 0.194669E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.251624E+09 | 0.122792E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.204271E+09 | 79001152.83 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.210105E+09 | 41093211.46 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.220610E+09 | 35912510.35 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.263861E+09 | 49740670.55 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.363665E+09 | 87944833.00 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.432983E+09 | 0.139497E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.447021E+09 | 0.208945E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.434234E+09 | 0.256648E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.397246E+10 | 0.164814E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.204271E+09 | 35912510.35 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.447021E+09 | 0.256648E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.365761E+09 | 0.192779E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.311591E+09 | 0.157739E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.288186E+09 | 0.157887E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212159E+09 | 99187338.65 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172228E+09 | 62742104.09 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.177985E+09 | 31850650.56 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.186033E+09 | 27624450.69 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.221963E+09 | 38941441.20 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.305025E+09 | 70865387.62 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363258E+09 | 0.114252E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.375915E+09 | 0.171530E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.366296E+09 | 0.209312E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334640E+10 | 0.133471E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172228E+09 | 27624450.69 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.375915E+09 | 0.209312E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.365761E+09 | 0.192779E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.311591E+09 | 0.157739E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.288186E+09 | 0.157887E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212159E+09 | 99187338.65 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172228E+09 | 62742104.09 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.177985E+09 | 31850650.56 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.186033E+09 | 27624450.69 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.221963E+09 | 38941441.20 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.305025E+09 | 70865387.62 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363258E+09 | 0.114252E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.375915E+09 | 0.171530E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.366296E+09 | 0.209312E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334640E+10 | 0.133471E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172228E+09 | 27624450.69 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.375915E+09 | 0.209312E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.365761E+09 | 0.192779E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.311591E+09 | 0.157739E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.288186E+09 | 0.157887E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212159E+09 | 99187338.65 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172228E+09 | 62742104.09 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.177985E+09 | 31850650.56 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.186033E+09 | 27624450.69 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.221963E+09 | 38941441.20 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.305025E+09 | 70865387.62 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363258E+09 | 0.114252E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.375915E+09 | 0.171530E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.366296E+09 | 0.209312E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334640E+10 | 0.133471E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172228E+09 | 27624450.69 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.375915E+09 | 0.209312E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.365761E+09 | 0.192779E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.311591E+09 | 0.157739E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.288186E+09 | 0.157887E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212159E+09 | 99187338.65 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172228E+09 | 62742104.09 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.177985E+09 | 31850650.56 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.186033E+09 | 27624450.69 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.221963E+09 | 38941441.20 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.305025E+09 | 70865387.62 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363258E+09 | 0.114252E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.375915E+09 | 0.171530E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.366296E+09 | 0.209312E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334640E+10 | 0.133471E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172228E+09 | 27624450.69 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.375915E+09 | 0.209312E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.438369E+09 | 0.227736E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.373454E+09 | 0.186402E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.345682E+09 | 0.186752E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.253827E+09 | 0.117681E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.205145E+09 | 74819732.34 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.211022E+09 | 38099774.45 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.221037E+09 | 32969162.30 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.264238E+09 | 46380865.92 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.364018E+09 | 84183200.30 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.434432E+09 | 0.135336E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.450117E+09 | 0.202899E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.438782E+09 | 0.247490E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.400012E+10 | 0.158075E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.205145E+09 | 32969162.30 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.450117E+09 | 0.247490E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.438369E+09 | 0.227736E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.373454E+09 | 0.186402E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.345682E+09 | 0.186752E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.253827E+09 | 0.117681E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.205145E+09 | 74819732.34 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.211022E+09 | 38099774.45 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.221037E+09 | 32969162.30 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.264238E+09 | 46380865.92 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.364018E+09 | 84183200.30 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.434432E+09 | 0.135336E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.450117E+09 | 0.202899E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.438782E+09 | 0.247490E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.400012E+10 | 0.158075E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.205145E+09 | 32969162.30 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.450117E+09 | 0.247490E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.365080E+09 | 0.192377E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.311045E+09 | 0.157404E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.287633E+09 | 0.157426E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212007E+09 | 98545193.99 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172747E+09 | 61842248.12 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.179306E+09 | 30969723.31 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.187129E+09 | 26728823.17 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.222706E+09 | 37962137.54 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.305112E+09 | 69887407.62 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.362805E+09 | 0.113648E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.375307E+09 | 0.171288E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.365711E+09 | 0.209005E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334659E+10 | 0.132708E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172747E+09 | 26728823.17 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.375307E+09 | 0.209005E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.365080E+09 | 0.192377E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.311045E+09 | 0.157404E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.287633E+09 | 0.157426E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212007E+09 | 98545193.99 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172747E+09 | 61842248.12 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.179306E+09 | 30969723.31 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.187129E+09 | 26728823.17 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.222706E+09 | 37962137.54 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.305112E+09 | 69887407.62 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.362805E+09 | 0.113648E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.375307E+09 | 0.171288E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.365711E+09 | 0.209005E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334659E+10 | 0.132708E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172747E+09 | 26728823.17 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.375307E+09 | 0.209005E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.437741E+09 | 0.227161E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.372957E+09 | 0.185936E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.345188E+09 | 0.186148E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.253721E+09 | 0.116911E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.205758E+09 | 73771942.16 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.212522E+09 | 37073750.49 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.222311E+09 | 31918112.03 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.265130E+09 | 45231890.91 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.364202E+09 | 83026229.71 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.434034E+09 | 0.134590E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.449559E+09 | 0.202538E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.438244E+09 | 0.247040E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.400137E+10 | 0.157135E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.205758E+09 | 31918112.03 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.449559E+09 | 0.247040E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.365637E+09 | 0.191085E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.311599E+09 | 0.156268E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.288334E+09 | 0.156175E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212359E+09 | 97916301.91 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172963E+09 | 61511611.91 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.179519E+09 | 30760369.09 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.187329E+09 | 26526025.92 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.222868E+09 | 37751726.49 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.305242E+09 | 69636174.61 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363012E+09 | 0.113237E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.375822E+09 | 0.170399E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.366212E+09 | 0.207925E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.335090E+10 | 0.131919E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172963E+09 | 26526025.92 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.375822E+09 | 0.207925E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.365637E+09 | 0.191085E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.311599E+09 | 0.156268E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.288334E+09 | 0.156175E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212359E+09 | 97916301.91 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172963E+09 | 61511611.91 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.179519E+09 | 30760369.09 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.187329E+09 | 26526025.92 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.222868E+09 | 37751726.49 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.305242E+09 | 69636174.61 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363012E+09 | 0.113237E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.375822E+09 | 0.170399E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.366212E+09 | 0.207925E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.335090E+10 | 0.131919E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172963E+09 | 26526025.92 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.375822E+09 | 0.207925E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.438405E+09 | 0.225635E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.373619E+09 | 0.184599E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.346023E+09 | 0.184674E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.254143E+09 | 0.116170E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.206015E+09 | 73381436.70 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.212775E+09 | 36825194.63 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.222549E+09 | 31678137.11 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.265324E+09 | 44982174.96 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.364358E+09 | 82729242.45 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.434282E+09 | 0.134103E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.450174E+09 | 0.201490E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.438841E+09 | 0.245765E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.400651E+10 | 0.156203E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.206015E+09 | 31678137.11 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.450174E+09 | 0.245765E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.366921E+09 | 0.187676E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.312992E+09 | 0.153095E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.290023E+09 | 0.152651E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.213212E+09 | 96061068.04 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.173271E+09 | 60721287.22 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.179552E+09 | 30513819.42 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.187255E+09 | 26400944.21 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.222751E+09 | 37673987.88 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.305211E+09 | 69459481.69 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363398E+09 | 0.112262E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.377126E+09 | 0.167946E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.367392E+09 | 0.205025E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.335911E+10 | 0.129948E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.173271E+09 | 26400944.21 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.377126E+09 | 0.205025E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.366921E+09 | 0.187676E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.312992E+09 | 0.153095E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.290023E+09 | 0.152651E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.213212E+09 | 96061068.04 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.173271E+09 | 60721287.22 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.179552E+09 | 30513819.42 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.187255E+09 | 26400944.21 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.222751E+09 | 37673987.88 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.305211E+09 | 69459481.69 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363398E+09 | 0.112262E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.377126E+09 | 0.167946E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.367392E+09 | 0.205025E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.335911E+10 | 0.129948E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.173271E+09 | 26400944.21 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.377126E+09 | 0.205025E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.439937E+09 | 0.221618E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.375277E+09 | 0.180861E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.348033E+09 | 0.180527E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.255160E+09 | 0.113991E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.206383E+09 | 72454838.30 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.212814E+09 | 36539935.29 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.222458E+09 | 31536801.08 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.265183E+09 | 44897419.23 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.364321E+09 | 82526917.42 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.434743E+09 | 0.132958E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.451728E+09 | 0.198605E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.440251E+09 | 0.242346E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.401629E+10 | 0.153886E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.206383E+09 | 31536801.08 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.451728E+09 | 0.242346E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.369888E+09 | 0.176308E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.316097E+09 | 0.142358E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.293281E+09 | 0.140792E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.214369E+09 | 89191282.68 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172809E+09 | 57538633.12 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.177602E+09 | 29706348.72 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.184651E+09 | 26442475.78 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.220173E+09 | 37976852.65 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303317E+09 | 69446614.83 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363619E+09 | 0.108792E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.379609E+09 | 0.159888E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.370194E+09 | 0.195027E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.336561E+10 | 0.123347E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172809E+09 | 26442475.78 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.379609E+09 | 0.195027E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.369888E+09 | 0.176308E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.316097E+09 | 0.142358E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.293281E+09 | 0.140792E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.214369E+09 | 89191282.68 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172809E+09 | 57538633.12 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.177602E+09 | 29706348.72 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.184651E+09 | 26442475.78 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.220173E+09 | 37976852.65 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303317E+09 | 69446614.83 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363619E+09 | 0.108792E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.379609E+09 | 0.159888E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.370194E+09 | 0.195027E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.336561E+10 | 0.123347E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172809E+09 | 26442475.78 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.379609E+09 | 0.195027E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.443495E+09 | 0.208225E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.378986E+09 | 0.168229E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.351926E+09 | 0.166578E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.256537E+09 | 0.105916E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.205830E+09 | 68720795.77 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.210481E+09 | 35596455.57 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.219347E+09 | 31600377.22 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.262097E+09 | 45270505.58 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.362041E+09 | 82524186.70 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.434999E+09 | 0.128885E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.454682E+09 | 0.189115E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.443613E+09 | 0.230554E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.402403E+10 | 0.146121E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.205830E+09 | 31600377.22 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.454682E+09 | 0.230554E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 869.06 | 478.29 | 630.09 | 477.36 | 152.73 | 0.00 | 0.00 |
February | 821.25 | 430.46 | 584.48 | 412.05 | 172.43 | 0.00 | 0.00 |
March | 686.53 | 386.38 | 475.01 | 273.89 | 201.12 | 0.00 | 0.00 |
April | 524.22 | 245.18 | 322.06 | 120.17 | 201.89 | 0.00 | 0.00 |
May | 413.23 | 146.13 | 227.59 | 31.86 | 195.74 | 0.00 | 0.00 |
June | 443.65 | 74.24 | 196.36 | 12.46 | 183.90 | 0.00 | 0.00 |
July | 449.96 | 61.16 | 200.16 | 18.56 | 181.61 | 0.00 | 0.00 |
August | 533.99 | 88.70 | 255.15 | 67.54 | 187.61 | 0.00 | 0.00 |
September | 753.28 | 169.52 | 398.26 | 206.91 | 191.35 | 0.00 | 0.00 |
October | 868.26 | 271.70 | 541.12 | 365.84 | 175.29 | 0.00 | 0.00 |
November | 925.66 | 430.93 | 651.19 | 496.46 | 154.74 | 0.00 | 0.00 |
December | 870.18 | 516.68 | 645.36 | 484.44 | 160.92 | 0.00 | 0.00 |
Annual Sum or Average | 678.98 | 274.16 | 426.33 | 246.36 | 179.97 | 0.00 | 0.00 |
Minimum of Months | 413.23 | 61.16 | 196.36 | 12.46 | 152.73 | 0.00 | 0.00 |
Maximum of Months | 925.66 | 516.68 | 651.19 | 496.46 | 201.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 427.05 | 256.55 | 315.05 | 238.68 | 76.37 | 0.00 | 0.00 |
February | 402.98 | 230.33 | 292.24 | 206.02 | 86.22 | 0.00 | 0.00 |
March | 336.41 | 204.10 | 237.51 | 136.95 | 100.56 | 0.00 | 0.00 |
April | 259.71 | 126.00 | 161.03 | 60.08 | 100.94 | 0.00 | 0.00 |
May | 206.43 | 74.06 | 113.80 | 15.93 | 97.87 | 0.00 | 0.00 |
June | 223.11 | 37.72 | 98.18 | 6.23 | 91.95 | 0.00 | 0.00 |
July | 226.48 | 30.89 | 100.08 | 9.28 | 90.80 | 0.00 | 0.00 |
August | 268.32 | 44.43 | 127.58 | 33.77 | 93.81 | 0.00 | 0.00 |
September | 377.09 | 84.29 | 199.13 | 103.46 | 95.68 | 0.00 | 0.00 |
October | 432.95 | 136.97 | 270.56 | 182.92 | 87.64 | 0.00 | 0.00 |
November | 458.27 | 223.46 | 325.60 | 248.23 | 77.37 | 0.00 | 0.00 |
December | 427.81 | 275.25 | 322.68 | 242.22 | 80.46 | 0.00 | 0.00 |
Annual Sum or Average | 336.76 | 143.24 | 213.17 | 123.18 | 89.99 | 0.00 | 0.00 |
Minimum of Months | 206.43 | 30.89 | 98.18 | 6.23 | 76.37 | 0.00 | 0.00 |
Maximum of Months | 458.27 | 275.25 | 325.60 | 248.23 | 100.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 428.58 | 247.92 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 403.86 | 224.77 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 336.70 | 201.48 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 258.34 | 129.66 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 203.86 | 79.98 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 217.45 | 42.77 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 220.77 | 36.23 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 263.77 | 50.18 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 375.11 | 91.77 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 431.38 | 141.64 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 458.49 | 221.45 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 429.26 | 266.75 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 335.16 | 144.14 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 203.86 | 36.23 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 458.49 | 266.75 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 430.19 | 243.22 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 405.24 | 220.98 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 337.74 | 198.96 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 258.53 | 129.12 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 203.78 | 80.26 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 217.19 | 43.36 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 220.49 | 36.84 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 263.56 | 50.79 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 375.03 | 92.24 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 431.44 | 141.43 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 459.23 | 219.44 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 430.79 | 262.34 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 335.63 | 142.85 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 203.78 | 36.84 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 459.23 | 262.34 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 432.13 | 238.62 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 407.17 | 216.71 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 339.52 | 195.63 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 259.31 | 127.26 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 204.32 | 78.98 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 217.82 | 42.35 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 221.02 | 35.88 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 264.01 | 49.75 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 375.40 | 91.07 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 431.93 | 140.05 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 460.42 | 216.96 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 432.70 | 257.97 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 336.67 | 140.55 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 204.32 | 35.88 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 460.42 | 257.97 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 873.57 | 457.96 | 628.80 | 476.38 | 152.42 | 0.00 | 0.00 |
February | 823.94 | 414.91 | 583.28 | 411.20 | 172.08 | 0.00 | 0.00 |
March | 688.51 | 375.24 | 474.04 | 273.33 | 200.71 | 0.00 | 0.00 |
April | 523.26 | 243.87 | 321.40 | 119.92 | 201.47 | 0.00 | 0.00 |
May | 410.39 | 149.57 | 227.13 | 31.79 | 195.34 | 0.00 | 0.00 |
June | 437.49 | 78.55 | 195.95 | 12.43 | 183.52 | 0.00 | 0.00 |
July | 442.88 | 65.87 | 199.75 | 18.52 | 181.24 | 0.00 | 0.00 |
August | 528.80 | 92.79 | 254.63 | 67.40 | 187.23 | 0.00 | 0.00 |
September | 751.60 | 174.32 | 397.45 | 206.49 | 190.96 | 0.00 | 0.00 |
October | 866.90 | 271.68 | 540.01 | 365.09 | 174.93 | 0.00 | 0.00 |
November | 927.43 | 421.26 | 649.86 | 495.44 | 154.42 | 0.00 | 0.00 |
December | 874.68 | 497.40 | 644.03 | 483.44 | 160.59 | 0.00 | 0.00 |
Annual Sum or Average | 678.14 | 269.54 | 425.46 | 245.85 | 179.60 | 0.00 | 0.00 |
Minimum of Months | 410.39 | 65.87 | 195.95 | 12.43 | 152.42 | 0.00 | 0.00 |
Maximum of Months | 927.43 | 497.40 | 649.86 | 495.44 | 201.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 436.04 | 228.46 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 411.31 | 206.99 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 343.66 | 187.05 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 261.47 | 121.14 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 205.81 | 73.72 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 220.34 | 38.20 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 222.73 | 31.88 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 265.29 | 45.23 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 375.94 | 85.96 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 432.96 | 135.11 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 463.03 | 210.31 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 436.70 | 248.30 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 339.12 | 133.99 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 205.81 | 31.88 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 463.03 | 248.30 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 436.71 | 226.93 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 412.04 | 205.49 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 344.49 | 185.57 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 261.91 | 120.37 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 206.07 | 73.33 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 220.61 | 37.94 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 222.97 | 31.63 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 265.48 | 44.98 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 376.10 | 85.65 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 433.21 | 134.62 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 463.66 | 209.22 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 437.30 | 247.02 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 339.56 | 133.19 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 206.07 | 31.63 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 463.66 | 247.02 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 438.24 | 222.88 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 413.88 | 201.33 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 346.50 | 181.39 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 262.96 | 118.10 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 206.44 | 72.39 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 220.65 | 37.64 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 222.88 | 31.49 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 265.34 | 44.89 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 376.06 | 85.43 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 433.67 | 133.47 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 465.27 | 206.21 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 438.71 | 243.58 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 340.39 | 131.21 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 206.44 | 31.49 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 465.27 | 243.58 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 441.78 | 209.39 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 417.98 | 187.23 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 350.39 | 167.32 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 264.38 | 109.68 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 205.89 | 68.62 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 218.24 | 36.65 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 219.78 | 31.54 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 262.26 | 45.26 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 373.72 | 85.42 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 433.93 | 129.36 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 468.33 | 196.33 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 442.06 | 231.71 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 341.05 | 124.56 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 205.89 | 31.54 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 468.33 | 231.71 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.232768E+10 | 0.128105E+10 | 0.168764E+10 | 0.127856E+10 | 0.409076E+09 | 0.00 | 0.00 |
February | 0.198676E+10 | 0.104137E+10 | 0.141398E+10 | 0.996831E+09 | 0.417145E+09 | 0.00 | 0.00 |
March | 0.183880E+10 | 0.103489E+10 | 0.127227E+10 | 0.733588E+09 | 0.538684E+09 | 0.00 | 0.00 |
April | 0.135878E+10 | 0.635514E+09 | 0.834770E+09 | 0.311474E+09 | 0.523296E+09 | 0.00 | 0.00 |
May | 0.110679E+10 | 0.391385E+09 | 0.609587E+09 | 85322163.70 | 0.524265E+09 | 0.00 | 0.00 |
June | 0.114993E+10 | 0.192436E+09 | 0.508955E+09 | 32293323.27 | 0.476661E+09 | 0.00 | 0.00 |
July | 0.120517E+10 | 0.163818E+09 | 0.536117E+09 | 49698998.17 | 0.486418E+09 | 0.00 | 0.00 |
August | 0.143025E+10 | 0.237567E+09 | 0.683402E+09 | 0.180901E+09 | 0.502501E+09 | 0.00 | 0.00 |
September | 0.195251E+10 | 0.439395E+09 | 0.103230E+10 | 0.536317E+09 | 0.495986E+09 | 0.00 | 0.00 |
October | 0.232556E+10 | 0.727709E+09 | 0.144935E+10 | 0.979857E+09 | 0.469492E+09 | 0.00 | 0.00 |
November | 0.239932E+10 | 0.111698E+10 | 0.168790E+10 | 0.128681E+10 | 0.401082E+09 | 0.00 | 0.00 |
December | 0.233070E+10 | 0.138387E+10 | 0.172853E+10 | 0.129751E+10 | 0.431016E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.214123E+11 | 0.864597E+10 | 0.134448E+11 | 0.776917E+10 | 0.567562E+10 | 0.00 | 0.00 |
Minimum of Months | 0.110679E+10 | 0.163818E+09 | 0.508955E+09 | 32293323.27 | 0.401082E+09 | 0.00 | 0.00 |
Maximum of Months | 0.239932E+10 | 0.138387E+10 | 0.172853E+10 | 0.129751E+10 | 0.538684E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114381E+10 | 0.687145E+09 | 0.843820E+09 | 0.639281E+09 | 0.204538E+09 | 0.00 | 0.00 |
February | 0.974901E+09 | 0.557207E+09 | 0.706988E+09 | 0.498416E+09 | 0.208572E+09 | 0.00 | 0.00 |
March | 0.901033E+09 | 0.546659E+09 | 0.636136E+09 | 0.366794E+09 | 0.269342E+09 | 0.00 | 0.00 |
April | 0.673159E+09 | 0.326593E+09 | 0.417385E+09 | 0.155737E+09 | 0.261648E+09 | 0.00 | 0.00 |
May | 0.552889E+09 | 0.198373E+09 | 0.304793E+09 | 42661081.85 | 0.262132E+09 | 0.00 | 0.00 |
June | 0.578310E+09 | 97765111.21 | 0.254477E+09 | 16146661.64 | 0.238331E+09 | 0.00 | 0.00 |
July | 0.606596E+09 | 82734749.55 | 0.268059E+09 | 24849499.09 | 0.243209E+09 | 0.00 | 0.00 |
August | 0.718656E+09 | 0.118996E+09 | 0.341701E+09 | 90450288.55 | 0.251251E+09 | 0.00 | 0.00 |
September | 0.977412E+09 | 0.218480E+09 | 0.516151E+09 | 0.268159E+09 | 0.247993E+09 | 0.00 | 0.00 |
October | 0.115961E+10 | 0.366852E+09 | 0.724674E+09 | 0.489928E+09 | 0.234746E+09 | 0.00 | 0.00 |
November | 0.118784E+10 | 0.579220E+09 | 0.843948E+09 | 0.643407E+09 | 0.200541E+09 | 0.00 | 0.00 |
December | 0.114586E+10 | 0.737225E+09 | 0.864264E+09 | 0.648756E+09 | 0.215508E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106201E+11 | 0.451725E+10 | 0.672240E+10 | 0.388458E+10 | 0.283781E+10 | 0.00 | 0.00 |
Minimum of Months | 0.552889E+09 | 82734749.55 | 0.254477E+09 | 16146661.64 | 0.200541E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118784E+10 | 0.737225E+09 | 0.864264E+09 | 0.648756E+09 | 0.269342E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114791E+10 | 0.664019E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.977011E+09 | 0.543759E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.901819E+09 | 0.539652E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.669617E+09 | 0.336074E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.546010E+09 | 0.214226E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.563638E+09 | 0.110851E+09 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.591305E+09 | 97038838.75 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.706486E+09 | 0.134400E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.972297E+09 | 0.237869E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.115541E+10 | 0.379364E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.118840E+10 | 0.573993E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.114972E+10 | 0.714471E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105696E+11 | 0.454572E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.546010E+09 | 97038838.75 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118840E+10 | 0.714471E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115222E+10 | 0.651439E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.980356E+09 | 0.534605E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.904616E+09 | 0.532896E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.670115E+09 | 0.334673E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.545803E+09 | 0.214976E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.562962E+09 | 0.112394E+09 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.590551E+09 | 98661116.85 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.705910E+09 | 0.136035E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.972070E+09 | 0.239075E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.115557E+10 | 0.378818E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.119031E+10 | 0.568777E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.115382E+10 | 0.702662E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105843E+11 | 0.450501E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.545803E+09 | 98661116.85 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.119031E+10 | 0.702662E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115742E+10 | 0.639111E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.985037E+09 | 0.524263E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.909376E+09 | 0.523981E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.672132E+09 | 0.329852E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.547259E+09 | 0.211540E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.564590E+09 | 0.109782E+09 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.591989E+09 | 96094656.61 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.707138E+09 | 0.133262E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.973046E+09 | 0.236051E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.115689E+10 | 0.375109E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.119341E+10 | 0.562368E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.115895E+10 | 0.690940E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106172E+11 | 0.443235E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.547259E+09 | 96094656.61 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.119341E+10 | 0.690940E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.233978E+10 | 0.122659E+10 | 0.168418E+10 | 0.127594E+10 | 0.408237E+09 | 0.00 | 0.00 |
February | 0.199327E+10 | 0.100376E+10 | 0.141108E+10 | 0.994786E+09 | 0.416289E+09 | 0.00 | 0.00 |
March | 0.184411E+10 | 0.100505E+10 | 0.126966E+10 | 0.732083E+09 | 0.537578E+09 | 0.00 | 0.00 |
April | 0.135629E+10 | 0.632108E+09 | 0.833057E+09 | 0.310835E+09 | 0.522223E+09 | 0.00 | 0.00 |
May | 0.109919E+10 | 0.400602E+09 | 0.608336E+09 | 85147127.19 | 0.523189E+09 | 0.00 | 0.00 |
June | 0.113398E+10 | 0.203600E+09 | 0.507911E+09 | 32227074.24 | 0.475683E+09 | 0.00 | 0.00 |
July | 0.118621E+10 | 0.176434E+09 | 0.535018E+09 | 49597041.79 | 0.485420E+09 | 0.00 | 0.00 |
August | 0.141633E+10 | 0.248526E+09 | 0.682000E+09 | 0.180529E+09 | 0.501470E+09 | 0.00 | 0.00 |
September | 0.194813E+10 | 0.451827E+09 | 0.103018E+10 | 0.535217E+09 | 0.494968E+09 | 0.00 | 0.00 |
October | 0.232190E+10 | 0.727678E+09 | 0.144638E+10 | 0.977846E+09 | 0.468529E+09 | 0.00 | 0.00 |
November | 0.240389E+10 | 0.109191E+10 | 0.168443E+10 | 0.128417E+10 | 0.400260E+09 | 0.00 | 0.00 |
December | 0.234275E+10 | 0.133223E+10 | 0.172498E+10 | 0.129485E+10 | 0.430132E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.213858E+11 | 0.850031E+10 | 0.134172E+11 | 0.775323E+10 | 0.566398E+10 | 0.00 | 0.00 |
Minimum of Months | 0.109919E+10 | 0.176434E+09 | 0.507911E+09 | 32227074.24 | 0.400260E+09 | 0.00 | 0.00 |
Maximum of Months | 0.240389E+10 | 0.133223E+10 | 0.172498E+10 | 0.129485E+10 | 0.537578E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.116790E+10 | 0.611914E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.995045E+09 | 0.500743E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.920454E+09 | 0.501000E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.677733E+09 | 0.314000E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.551249E+09 | 0.197454E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.571132E+09 | 99011197.03 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.596568E+09 | 85374672.80 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.710541E+09 | 0.121155E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.974425E+09 | 0.222800E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.115964E+10 | 0.361886E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.120017E+10 | 0.545112E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.116967E+10 | 0.665050E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106945E+11 | 0.422550E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.551249E+09 | 85374672.80 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120017E+10 | 0.665050E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.116968E+10 | 0.607804E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.996816E+09 | 0.497133E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.922690E+09 | 0.497024E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.678860E+09 | 0.312001E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.551938E+09 | 0.196402E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.571810E+09 | 98344272.17 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.597207E+09 | 84729024.96 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.711057E+09 | 0.120484E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.974840E+09 | 0.222001E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.116031E+10 | 0.360576E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.120182E+10 | 0.542286E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.117126E+10 | 0.661614E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107083E+11 | 0.420040E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.551938E+09 | 84729024.96 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120182E+10 | 0.661614E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117378E+10 | 0.596968E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.100126E+10 | 0.487050E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.928079E+09 | 0.485829E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.681584E+09 | 0.306113E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.552923E+09 | 0.193895E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.571917E+09 | 97565967.80 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.596967E+09 | 84337513.56 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.710683E+09 | 0.120244E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.974742E+09 | 0.221445E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.116154E+10 | 0.357480E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.120598E+10 | 0.534496E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.117503E+10 | 0.652395E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107345E+11 | 0.413782E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.552923E+09 | 84337513.56 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120598E+10 | 0.652395E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118327E+10 | 0.560840E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.101118E+10 | 0.452944E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.938488E+09 | 0.448161E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.685275E+09 | 0.284298E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.551446E+09 | 0.183796E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.565684E+09 | 95006885.59 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.588648E+09 | 84484218.10 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.702442E+09 | 0.121223E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.968674E+09 | 0.221417E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.116224E+10 | 0.346470E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.121390E+10 | 0.508891E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.118400E+10 | 0.620607E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107552E+11 | 0.392814E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.551446E+09 | 84484218.10 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121390E+10 | 0.620607E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.335708E+09 | -215194447.9 | 0.00 | 0.00 | 744.00 | 0.00 | -120513352.5 | 58.99 | 0.00 | 0.00 |
February | 0.302685E+09 | -195222793.5 | 0.00 | 0.00 | 672.00 | 0.00 | -107462409.4 | 58.99 | 0.00 | 0.00 |
March | 0.328720E+09 | -211647645.4 | 0.00 | 0.00 | 744.00 | 0.00 | -117072691.8 | 58.99 | 0.00 | 0.00 |
April | 0.298861E+09 | -188704321.1 | 0.00 | 0.00 | 720.00 | 0.00 | -110157012.8 | 58.99 | 0.00 | 0.00 |
May | 0.291808E+09 | -179189077.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112618882.9 | 58.99 | 0.00 | 0.00 |
June | 0.269616E+09 | -161374664.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108241627.7 | 58.99 | 0.00 | 0.00 |
July | 0.266844E+09 | -155331872.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111511782.3 | 58.99 | 0.00 | 0.00 |
August | 0.270302E+09 | -158719244.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111583137.9 | 58.99 | 0.00 | 0.00 |
September | 0.268199E+09 | -159853136.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108345639.9 | 58.99 | 0.00 | 0.00 |
October | 0.290316E+09 | -177583145.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112732851.5 | 58.99 | 0.00 | 0.00 |
November | 0.299046E+09 | -186789093.7 | 0.00 | 0.00 | 720.00 | 0.00 | -112257197.1 | 58.99 | 0.00 | 0.00 |
December | 0.328612E+09 | -207563825.5 | 0.00 | 0.00 | 744.00 | 0.00 | -121047969.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.355072E+10 | -0.219717E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.135354E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.266844E+09 | -215194447.9 | 0.00 | 0.00 | 672.00 | 0.00 | -121047969.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.335708E+09 | -155331872.4 | 0.00 | 0.00 | 744.00 | 0.00 | -107462409.4 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.332403E+09 | -215183411.2 | 0.00 | 0.00 | 744.00 | 0.00 | -117219686.8 | 58.99 | 0.00 | 0.00 |
February | 0.300144E+09 | -195221364.5 | 0.00 | 0.00 | 672.00 | 0.00 | -104922572.6 | 58.99 | 0.00 | 0.00 |
March | 0.326685E+09 | -211647317.1 | 0.00 | 0.00 | 744.00 | 0.00 | -115037740.6 | 58.99 | 0.00 | 0.00 |
April | 0.298325E+09 | -188705891.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109619431.1 | 58.99 | 0.00 | 0.00 |
May | 0.291643E+09 | -179185568.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112457440.2 | 58.99 | 0.00 | 0.00 |
June | 0.269456E+09 | -161378930.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108077045.6 | 58.99 | 0.00 | 0.00 |
July | 0.266734E+09 | -155330931.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111402850.3 | 58.99 | 0.00 | 0.00 |
August | 0.270251E+09 | -158719271.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111531639.4 | 58.99 | 0.00 | 0.00 |
September | 0.268229E+09 | -159854359.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108375083.4 | 58.99 | 0.00 | 0.00 |
October | 0.290133E+09 | -177582044.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112550662.3 | 58.99 | 0.00 | 0.00 |
November | 0.297559E+09 | -186779708.2 | 0.00 | 0.00 | 720.00 | 0.00 | -110779317.3 | 58.99 | 0.00 | 0.00 |
December | 0.325356E+09 | -207563369.3 | 0.00 | 0.00 | 744.00 | 0.00 | -117792637.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.353692E+10 | -0.219715E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133977E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.266734E+09 | -215183411.2 | 0.00 | 0.00 | 672.00 | 0.00 | -117792637.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.332403E+09 | -155330931.9 | 0.00 | 0.00 | 744.00 | 0.00 | -104922572.6 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.308314E+09 | -189223209.9 | 0.00 | 0.00 | 744.00 | 0.00 | -119090768.0 | 59.00 | 0.00 | 0.00 |
February | 0.277809E+09 | -171810967.8 | 0.00 | 0.00 | 672.00 | 0.00 | -105998387.6 | 58.99 | 0.00 | 0.00 |
March | 0.304430E+09 | -188891543.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115538453.1 | 58.99 | 0.00 | 0.00 |
April | 0.274516E+09 | -165945961.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108570322.5 | 59.00 | 0.00 | 0.00 |
May | 0.269583E+09 | -158973059.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110609973.8 | 58.99 | 0.00 | 0.00 |
June | 0.249635E+09 | -143737597.9 | 0.00 | 0.00 | 720.00 | 0.00 | -105897520.0 | 58.98 | 0.00 | 0.00 |
July | 0.244871E+09 | -135792138.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109079283.5 | 58.99 | 0.00 | 0.00 |
August | 0.251158E+09 | -141766155.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109391363.0 | 58.99 | 0.00 | 0.00 |
September | 0.246975E+09 | -140563261.3 | 0.00 | 0.00 | 720.00 | 0.00 | -106411954.1 | 58.98 | 0.00 | 0.00 |
October | 0.267517E+09 | -156206470.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111310097.8 | 58.99 | 0.00 | 0.00 |
November | 0.276098E+09 | -164905928.2 | 0.00 | 0.00 | 720.00 | 0.00 | -111191963.3 | 59.00 | 0.00 | 0.00 |
December | 0.300812E+09 | -181171363.7 | 0.00 | 0.00 | 744.00 | 0.00 | -119640398.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.327172E+10 | -0.193899E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133273E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.244871E+09 | -189223209.9 | 0.00 | 0.00 | 672.00 | 0.00 | -119640398.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.308314E+09 | -135792138.0 | 0.00 | 0.00 | 744.00 | 0.00 | -105897520.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.309056E+09 | -189228951.7 | 0.00 | 0.00 | 744.00 | 0.00 | -119827058.2 | 58.99 | 0.00 | 0.00 |
February | 0.278354E+09 | -171815247.3 | 0.00 | 0.00 | 672.00 | 0.00 | -106538711.6 | 58.99 | 0.00 | 0.00 |
March | 0.304833E+09 | -188882767.2 | 0.00 | 0.00 | 744.00 | 0.00 | -115950680.8 | 58.99 | 0.00 | 0.00 |
April | 0.274576E+09 | -165972728.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108603615.7 | 58.99 | 0.00 | 0.00 |
May | 0.269552E+09 | -158952040.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110599693.5 | 59.00 | 0.00 | 0.00 |
June | 0.249539E+09 | -143698820.8 | 0.00 | 0.00 | 720.00 | 0.00 | -105840322.2 | 58.99 | 0.00 | 0.00 |
July | 0.244761E+09 | -135790992.7 | 0.00 | 0.00 | 744.00 | 0.00 | -108969548.8 | 58.99 | 0.00 | 0.00 |
August | 0.251059E+09 | -141763761.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109295640.3 | 58.99 | 0.00 | 0.00 |
September | 0.246913E+09 | -140543971.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106369308.2 | 58.98 | 0.00 | 0.00 |
October | 0.267540E+09 | -156209993.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111330051.0 | 58.99 | 0.00 | 0.00 |
November | 0.276394E+09 | -164930815.1 | 0.00 | 0.00 | 720.00 | 0.00 | -111462996.2 | 58.99 | 0.00 | 0.00 |
December | 0.301504E+09 | -181176066.4 | 0.00 | 0.00 | 744.00 | 0.00 | -120327446.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.327408E+10 | -0.193897E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133512E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.244761E+09 | -189228951.7 | 0.00 | 0.00 | 672.00 | 0.00 | -120327446.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.309056E+09 | -135790992.7 | 0.00 | 0.00 | 744.00 | 0.00 | -105840322.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.301016E+09 | -178859752.0 | 0.00 | 0.00 | 744.00 | 0.00 | -122156620.3 | 58.99 | 0.00 | 0.00 |
February | 0.271095E+09 | -162483250.1 | 0.00 | 0.00 | 672.00 | 0.00 | -108611918.4 | 58.99 | 0.00 | 0.00 |
March | 0.296651E+09 | -178724239.6 | 0.00 | 0.00 | 744.00 | 0.00 | -117927174.6 | 58.99 | 0.00 | 0.00 |
April | 0.266844E+09 | -157063276.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109780961.8 | 58.99 | 0.00 | 0.00 |
May | 0.261881E+09 | -150347829.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111532971.0 | 58.98 | 0.00 | 0.00 |
June | 0.242751E+09 | -135985779.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106765695.9 | 58.99 | 0.00 | 0.00 |
July | 0.238194E+09 | -128416440.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109777143.8 | 58.99 | 0.00 | 0.00 |
August | 0.244253E+09 | -134142744.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110110729.0 | 58.99 | 0.00 | 0.00 |
September | 0.240150E+09 | -132975598.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107174291.5 | 58.99 | 0.00 | 0.00 |
October | 0.259818E+09 | -147618844.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112199466.1 | 59.00 | 0.00 | 0.00 |
November | 0.268664E+09 | -155760078.4 | 0.00 | 0.00 | 720.00 | 0.00 | -112903811.4 | 58.99 | 0.00 | 0.00 |
December | 0.293981E+09 | -171304890.1 | 0.00 | 0.00 | 744.00 | 0.00 | -122676245.5 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318530E+10 | -0.183368E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.135162E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.238194E+09 | -178859752.0 | 0.00 | 0.00 | 672.00 | 0.00 | -122676245.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.301016E+09 | -128416440.0 | 0.00 | 0.00 | 744.00 | 0.00 | -106765695.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.301177E+09 | -178855932.1 | 0.00 | 0.00 | 744.00 | 0.00 | -122321067.1 | 58.99 | 0.00 | 0.00 |
February | 0.271215E+09 | -162480985.4 | 0.00 | 0.00 | 672.00 | 0.00 | -108734224.1 | 58.99 | 0.00 | 0.00 |
March | 0.296790E+09 | -178701912.5 | 0.00 | 0.00 | 744.00 | 0.00 | -118087863.6 | 59.00 | 0.00 | 0.00 |
April | 0.266917E+09 | -157052582.7 | 0.00 | 0.00 | 720.00 | 0.00 | -109864856.0 | 58.99 | 0.00 | 0.00 |
May | 0.261989E+09 | -150308601.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111680745.0 | 59.00 | 0.00 | 0.00 |
June | 0.242872E+09 | -135983081.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106888573.8 | 58.99 | 0.00 | 0.00 |
July | 0.238347E+09 | -128428786.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109918690.2 | 58.99 | 0.00 | 0.00 |
August | 0.244393E+09 | -134131343.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110261990.1 | 58.99 | 0.00 | 0.00 |
September | 0.240281E+09 | -132973752.4 | 0.00 | 0.00 | 720.00 | 0.00 | -107307188.3 | 58.99 | 0.00 | 0.00 |
October | 0.259905E+09 | -147628624.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112276088.8 | 58.99 | 0.00 | 0.00 |
November | 0.268750E+09 | -155763588.7 | 0.00 | 0.00 | 720.00 | 0.00 | -112986279.8 | 58.99 | 0.00 | 0.00 |
December | 0.294115E+09 | -171309478.8 | 0.00 | 0.00 | 744.00 | 0.00 | -122805169.6 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318675E+10 | -0.183362E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.135313E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.238347E+09 | -178855932.1 | 0.00 | 0.00 | 672.00 | 0.00 | -122805169.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.301177E+09 | -128428786.7 | 0.00 | 0.00 | 744.00 | 0.00 | -106888573.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.301416E+09 | -178843583.5 | 0.00 | 0.00 | 744.00 | 0.00 | -122572392.2 | 59.00 | 0.00 | 0.00 |
February | 0.271421E+09 | -162481261.1 | 0.00 | 0.00 | 672.00 | 0.00 | -108939254.7 | 58.99 | 0.00 | 0.00 |
March | 0.297030E+09 | -178733294.5 | 0.00 | 0.00 | 744.00 | 0.00 | -118296424.8 | 58.99 | 0.00 | 0.00 |
April | 0.267043E+09 | -157059755.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109983038.1 | 58.99 | 0.00 | 0.00 |
May | 0.262037E+09 | -150334747.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111701804.2 | 58.99 | 0.00 | 0.00 |
June | 0.242926E+09 | -135996948.5 | 0.00 | 0.00 | 720.00 | 0.00 | -106928610.5 | 58.99 | 0.00 | 0.00 |
July | 0.238381E+09 | -128427410.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109953378.6 | 58.99 | 0.00 | 0.00 |
August | 0.244436E+09 | -134143129.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110292833.8 | 58.99 | 0.00 | 0.00 |
September | 0.240324E+09 | -132962027.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107362076.1 | 59.00 | 0.00 | 0.00 |
October | 0.259973E+09 | -147635898.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112336742.7 | 58.99 | 0.00 | 0.00 |
November | 0.268931E+09 | -155758567.7 | 0.00 | 0.00 | 720.00 | 0.00 | -113172581.1 | 58.99 | 0.00 | 0.00 |
December | 0.294317E+09 | -171312898.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123003674.5 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318823E+10 | -0.183369E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.135454E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.238381E+09 | -178843583.5 | 0.00 | 0.00 | 672.00 | 0.00 | -123003674.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.301416E+09 | -128427410.2 | 0.00 | 0.00 | 744.00 | 0.00 | -106928610.5 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 373.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 400.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 377.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 365.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 295.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4125.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125001E+10 | 62702.73 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.704863E+09 | 62702.73 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.345642E+09 | 62702.73 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3596158.99 | 2504.85 | 11-APR-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.328531E+09 | 62702.73 | 28-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207393E+10 | 62702.73 | 04-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.470658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.207393E+10 | 62702.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.112424E+09 | 32248.77 | 28-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53922439.30 | 27055.66 | 03-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26853804.68 | 19818.26 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24630744.03 | 8095.67 | 28-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.281804E+09 | 30760.00 | 27-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.499635E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.281804E+09 | 32248.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.357451E+09 | 26731.93 | 28-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162461E+09 | 19174.09 | 03-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 75237072.25 | 15126.91 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 95415381.40 | 10521.87 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.636247E+09 | 26180.95 | 27-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.636247E+09 | 26731.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.465214E+09 | 30652.77 | 28-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.203805E+09 | 22937.79 | 03-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 96902481.63 | 19389.07 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122834E+09 | 13440.09 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.768337E+09 | 31468.61 | 27-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.768337E+09 | 31468.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.633963E+09 | 33119.07 | 28-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285649E+09 | 27362.03 | 03-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141204E+09 | 24402.65 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158400E+09 | 16293.97 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.965565E+09 | 33119.07 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.965565E+09 | 33119.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.169495E+10 | 58288.34 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.800561E+09 | 58288.34 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.387037E+09 | 58288.34 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1806334.42 | 1976.48 | 11-APR-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.433570E+09 | 58288.34 | 28-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.240549E+10 | 58288.34 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.572341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.240549E+10 | 58288.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.905980E+09 | 30072.75 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.430669E+09 | 30072.75 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.210213E+09 | 30072.75 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 548310.74 | 790.40 | 11-APR-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227282E+09 | 30072.75 | 28-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126682E+10 | 30072.75 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.304151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.126682E+10 | 30072.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.982918E+09 | 29954.09 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.479123E+09 | 29954.09 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.237096E+09 | 29954.09 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1053363.84 | 1037.70 | 11-APR-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.240974E+09 | 29954.09 | 28-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133851E+10 | 29954.09 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.133851E+10 | 29954.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.121713E+10 | 29979.14 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.637654E+09 | 29979.14 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.336301E+09 | 29979.14 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3153737.35 | 1880.12 | 11-APR-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.288302E+09 | 29979.14 | 27-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157079E+10 | 29979.14 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.405333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.157079E+10 | 29979.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.189831E+10 | 33032.97 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112960E+10 | 33032.97 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.694114E+09 | 33032.97 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 26044480.17 | 15434.87 | 12-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.447364E+09 | 33032.97 | 27-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220371E+10 | 33032.97 | 02-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.639914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.220371E+10 | 33032.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 13775720.74 | 13775720.74 | 1947.97 | 03-JAN-15:00 | 1947.97 | 0.00 |
February | 0.00 | 0.00 | 0.540355E+09 | 0.540355E+09 | 7830.49 | 20-FEB-16:00 | 7830.49 | 0.00 |
March | 0.00 | 0.00 | 0.141585E+10 | 0.141585E+10 | 9142.32 | 14-MAR-16:30 | 9142.32 | 0.00 |
April | 0.00 | 0.00 | 0.979200E+10 | 0.976159E+10 | 17227.03 | 21-APR-14:00 | 17227.03 | 0.00 |
May | 0.00 | 0.00 | 0.186769E+11 | 0.181438E+11 | 46087.10 | 31-MAY-07:02 | 46087.10 | 0.00 |
June | 0.00 | 0.00 | 0.260393E+11 | 0.251279E+11 | 48918.52 | 19-JUN-07:01 | 42015.65 | 0.00 |
July | 0.00 | 0.00 | 0.312966E+11 | 0.260346E+11 | 52819.47 | 19-JUL-07:02 | 21497.60 | 0.00 |
August | 0.00 | 0.00 | 0.273988E+11 | 0.242965E+11 | 52276.26 | 02-AUG-07:02 | 29761.21 | 0.00 |
September | 0.00 | 0.00 | 0.232022E+11 | 0.202089E+11 | 51484.41 | 23-SEP-07:02 | 29960.41 | 0.00 |
October | 0.00 | 0.00 | 0.111587E+11 | 0.100121E+11 | 49576.44 | 05-OCT-07:02 | 34540.03 | 0.00 |
November | 0.00 | 0.00 | 0.112503E+10 | 0.111248E+10 | 10967.15 | 09-NOV-15:00 | 10967.15 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150659E+12 | 0.136668E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.312966E+11 | 0.260346E+11 | 52819.47 | 46087.10 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 37317847.07 | 37181873.15 | 3103.06 | 29-JAN-18:10 | 3103.06 | 0.00 |
February | 0.00 | 0.00 | 0.496156E+09 | 0.496012E+09 | 23639.05 | 19-FEB-18:01 | 23639.05 | 0.00 |
March | 0.00 | 0.00 | 0.115562E+10 | 0.115552E+10 | 23639.05 | 12-MAR-17:20 | 23639.05 | 0.00 |
April | 0.00 | 0.00 | 0.636538E+10 | 0.633787E+10 | 24434.77 | 18-APR-20:36 | 21875.27 | 0.00 |
May | 0.00 | 0.00 | 0.106532E+11 | 0.103055E+11 | 25526.68 | 27-MAY-21:00 | 19169.49 | 0.00 |
June | 0.00 | 0.00 | 0.135636E+11 | 0.130614E+11 | 25524.48 | 23-JUN-20:02 | 18886.77 | 0.00 |
July | 0.00 | 0.00 | 0.160419E+11 | 0.134296E+11 | 27060.66 | 19-JUL-07:02 | 12501.53 | 0.00 |
August | 0.00 | 0.00 | 0.144004E+11 | 0.127034E+11 | 26860.53 | 02-AUG-07:02 | 16404.69 | 0.00 |
September | 0.00 | 0.00 | 0.128905E+11 | 0.112325E+11 | 26445.55 | 23-SEP-07:02 | 16517.25 | 0.00 |
October | 0.00 | 0.00 | 0.698597E+10 | 0.624194E+10 | 26439.85 | 03-OCT-20:03 | 15929.68 | 0.00 |
November | 0.00 | 0.00 | 0.828811E+09 | 0.817739E+09 | 23639.05 | 09-NOV-21:34 | 23255.08 | 0.00 |
December | 0.00 | 0.00 | 10885271.33 | 10860629.89 | 2402.50 | 08-DEC-21:10 | 2402.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.834298E+11 | 0.758296E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 10885271.33 | 10860629.89 | 2402.50 | 2402.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.160419E+11 | 0.134296E+11 | 27060.66 | 23639.05 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 10900179.90 | 10900179.90 | 1239.88 | 03-JAN-15:00 | 1239.88 | 0.00 |
February | 0.00 | 0.00 | 0.282194E+09 | 0.282194E+09 | 3928.63 | 20-FEB-15:00 | 3928.63 | 0.00 |
March | 0.00 | 0.00 | 0.783015E+09 | 0.783015E+09 | 5093.87 | 22-MAR-13:00 | 5093.87 | 0.00 |
April | 0.00 | 0.00 | 0.396567E+10 | 0.395311E+10 | 9097.17 | 21-APR-14:00 | 9097.17 | 0.00 |
May | 0.00 | 0.00 | 0.748493E+10 | 0.728768E+10 | 24567.03 | 30-MAY-06:02 | 24567.03 | 0.00 |
June | 0.00 | 0.00 | 0.104192E+11 | 0.100488E+11 | 26516.87 | 04-JUN-07:02 | 19479.81 | 0.00 |
July | 0.00 | 0.00 | 0.123281E+11 | 0.102203E+11 | 28000.26 | 19-JUL-06:02 | 18297.65 | 0.00 |
August | 0.00 | 0.00 | 0.108870E+11 | 0.956320E+10 | 27897.30 | 03-AUG-06:02 | 15308.15 | 0.00 |
September | 0.00 | 0.00 | 0.937332E+10 | 0.821694E+10 | 27357.25 | 23-SEP-06:02 | 16019.84 | 0.00 |
October | 0.00 | 0.00 | 0.464551E+10 | 0.420922E+10 | 26536.74 | 04-OCT-06:02 | 15332.66 | 0.00 |
November | 0.00 | 0.00 | 0.586063E+09 | 0.579412E+09 | 5748.64 | 09-NOV-14:00 | 5748.64 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.607659E+11 | 0.551548E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.123281E+11 | 0.102203E+11 | 28000.26 | 24567.03 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6813743.79 | 6813743.79 | 976.99 | 03-JAN-15:00 | 976.99 | 0.00 |
February | 0.00 | 0.00 | 0.250628E+09 | 0.250628E+09 | 3665.71 | 20-FEB-15:00 | 3665.71 | 0.00 |
March | 0.00 | 0.00 | 0.729583E+09 | 0.729582E+09 | 4941.29 | 22-MAR-13:00 | 4941.29 | 0.00 |
April | 0.00 | 0.00 | 0.392721E+10 | 0.391475E+10 | 9078.33 | 21-APR-14:00 | 9078.33 | 0.00 |
May | 0.00 | 0.00 | 0.749788E+10 | 0.729978E+10 | 24406.16 | 30-MAY-06:02 | 24406.16 | 0.00 |
June | 0.00 | 0.00 | 0.104640E+11 | 0.100918E+11 | 26338.35 | 04-JUN-07:02 | 19360.13 | 0.00 |
July | 0.00 | 0.00 | 0.123763E+11 | 0.102634E+11 | 27814.48 | 19-JUL-06:02 | 18203.85 | 0.00 |
August | 0.00 | 0.00 | 0.109355E+11 | 0.960603E+10 | 27708.83 | 03-AUG-06:02 | 15213.23 | 0.00 |
September | 0.00 | 0.00 | 0.940205E+10 | 0.824141E+10 | 27173.07 | 23-SEP-06:02 | 15923.65 | 0.00 |
October | 0.00 | 0.00 | 0.462798E+10 | 0.419385E+10 | 26357.33 | 04-OCT-06:02 | 15236.25 | 0.00 |
November | 0.00 | 0.00 | 0.556805E+09 | 0.550493E+09 | 5674.63 | 09-NOV-14:00 | 5674.63 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.607748E+11 | 0.551485E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.123763E+11 | 0.102634E+11 | 27814.48 | 24406.16 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2036344.81 | 2036344.81 | 583.39 | 03-JAN-15:00 | 583.39 | 0.00 |
February | 0.00 | 0.00 | 0.204832E+09 | 0.204832E+09 | 3313.04 | 20-FEB-15:00 | 3313.04 | 0.00 |
March | 0.00 | 0.00 | 0.631084E+09 | 0.631084E+09 | 4641.05 | 22-MAR-13:00 | 4641.05 | 0.00 |
April | 0.00 | 0.00 | 0.374849E+10 | 0.373686E+10 | 8902.14 | 21-APR-14:00 | 8902.14 | 0.00 |
May | 0.00 | 0.00 | 0.728760E+10 | 0.709502E+10 | 24437.37 | 30-MAY-06:02 | 24437.37 | 0.00 |
June | 0.00 | 0.00 | 0.102571E+11 | 0.989386E+10 | 26379.00 | 04-JUN-07:02 | 19345.17 | 0.00 |
July | 0.00 | 0.00 | 0.121610E+11 | 0.100759E+11 | 27848.95 | 19-JUL-06:02 | 18074.28 | 0.00 |
August | 0.00 | 0.00 | 0.107183E+11 | 0.941563E+10 | 27753.20 | 03-AUG-06:02 | 15185.28 | 0.00 |
September | 0.00 | 0.00 | 0.919564E+10 | 0.805943E+10 | 27215.51 | 23-SEP-06:02 | 15901.27 | 0.00 |
October | 0.00 | 0.00 | 0.445907E+10 | 0.404124E+10 | 26399.22 | 04-OCT-06:02 | 15217.88 | 0.00 |
November | 0.00 | 0.00 | 0.491675E+09 | 0.486365E+09 | 5470.82 | 09-NOV-14:00 | 5470.82 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.591568E+11 | 0.536423E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.121610E+11 | 0.100759E+11 | 27848.95 | 24437.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 396769.37 | 396769.37 | 388.72 | 03-JAN-15:10 | 388.72 | 0.00 |
February | 0.00 | 0.00 | 0.285794E+09 | 0.285794E+09 | 5530.38 | 20-FEB-15:30 | 5530.38 | 0.00 |
March | 0.00 | 0.00 | 0.914477E+09 | 0.914477E+09 | 7790.62 | 22-MAR-13:00 | 7790.62 | 0.00 |
April | 0.00 | 0.00 | 0.633798E+10 | 0.631638E+10 | 16196.47 | 21-APR-14:30 | 16196.47 | 0.00 |
May | 0.00 | 0.00 | 0.127712E+11 | 0.124162E+11 | 43128.92 | 30-MAY-07:02 | 43128.92 | 0.00 |
June | 0.00 | 0.00 | 0.182190E+11 | 0.175844E+11 | 46047.97 | 04-JUN-08:62 | 36307.86 | 0.00 |
July | 0.00 | 0.00 | 0.213266E+11 | 0.176623E+11 | 48578.03 | 19-JUL-07:02 | 21236.57 | 0.00 |
August | 0.00 | 0.00 | 0.189566E+11 | 0.166370E+11 | 48277.79 | 03-AUG-07:02 | 28651.34 | 0.00 |
September | 0.00 | 0.00 | 0.163150E+11 | 0.142670E+11 | 47368.70 | 23-SEP-07:02 | 28810.76 | 0.00 |
October | 0.00 | 0.00 | 0.769144E+10 | 0.690651E+10 | 45912.27 | 05-OCT-07:02 | 31943.96 | 0.00 |
November | 0.00 | 0.00 | 0.742812E+09 | 0.734049E+09 | 9382.74 | 09-NOV-14:00 | 9382.74 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.103561E+12 | 0.937246E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.213266E+11 | 0.176623E+11 | 48578.03 | 43128.92 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8734.92 | 8734.92 | 14.56 | 03-JAN-15:10 | 14.56 | 0.00 |
February | 0.00 | 0.00 | 0.135969E+09 | 0.135969E+09 | 2786.23 | 20-FEB-15:30 | 2786.23 | 0.00 |
March | 0.00 | 0.00 | 0.444649E+09 | 0.444649E+09 | 3933.30 | 22-MAR-13:00 | 3933.30 | 0.00 |
April | 0.00 | 0.00 | 0.324656E+10 | 0.323620E+10 | 8365.83 | 21-APR-14:40 | 8365.83 | 0.00 |
May | 0.00 | 0.00 | 0.657262E+10 | 0.639399E+10 | 22274.45 | 30-MAY-07:02 | 22274.45 | 0.00 |
June | 0.00 | 0.00 | 0.937739E+10 | 0.905799E+10 | 23780.31 | 04-JUN-08:62 | 18803.00 | 0.00 |
July | 0.00 | 0.00 | 0.109852E+11 | 0.911410E+10 | 25085.08 | 19-JUL-07:02 | 10991.92 | 0.00 |
August | 0.00 | 0.00 | 0.975869E+10 | 0.858013E+10 | 24930.23 | 03-AUG-07:02 | 14836.06 | 0.00 |
September | 0.00 | 0.00 | 0.840050E+10 | 0.736109E+10 | 24461.33 | 23-SEP-07:02 | 14914.69 | 0.00 |
October | 0.00 | 0.00 | 0.395431E+10 | 0.355827E+10 | 23709.22 | 05-OCT-07:02 | 16540.08 | 0.00 |
November | 0.00 | 0.00 | 0.371978E+09 | 0.367958E+09 | 4832.53 | 09-NOV-14:00 | 4832.53 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.532478E+11 | 0.482504E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109852E+11 | 0.911410E+10 | 25085.08 | 22274.45 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.125394E+09 | 0.125394E+09 | 2678.94 | 20-FEB-15:40 | 2678.94 | 0.00 |
March | 0.00 | 0.00 | 0.416470E+09 | 0.416470E+09 | 3820.75 | 22-MAR-13:00 | 3820.75 | 0.00 |
April | 0.00 | 0.00 | 0.318530E+10 | 0.317544E+10 | 8304.35 | 21-APR-14:40 | 8304.35 | 0.00 |
May | 0.00 | 0.00 | 0.650583E+10 | 0.633057E+10 | 22175.18 | 30-MAY-07:02 | 22175.18 | 0.00 |
June | 0.00 | 0.00 | 0.931174E+10 | 0.899760E+10 | 23680.93 | 04-JUN-08:62 | 18737.94 | 0.00 |
July | 0.00 | 0.00 | 0.109088E+11 | 0.905603E+10 | 24981.36 | 19-JUL-07:02 | 10938.16 | 0.00 |
August | 0.00 | 0.00 | 0.968977E+10 | 0.852531E+10 | 24827.37 | 03-AUG-07:02 | 14776.22 | 0.00 |
September | 0.00 | 0.00 | 0.833580E+10 | 0.730839E+10 | 24360.13 | 23-SEP-07:02 | 14855.96 | 0.00 |
October | 0.00 | 0.00 | 0.390085E+10 | 0.351191E+10 | 23611.12 | 05-OCT-07:02 | 16475.10 | 0.00 |
November | 0.00 | 0.00 | 0.353885E+09 | 0.350136E+09 | 4754.34 | 09-NOV-14:00 | 4754.34 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.527339E+11 | 0.477972E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109088E+11 | 0.905603E+10 | 24981.36 | 22175.18 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.102029E+09 | 0.102029E+09 | 2439.36 | 20-FEB-15:40 | 2439.36 | 0.00 |
March | 0.00 | 0.00 | 0.351563E+09 | 0.351563E+09 | 3546.03 | 22-MAR-13:00 | 3546.03 | 0.00 |
April | 0.00 | 0.00 | 0.304747E+10 | 0.303838E+10 | 8193.94 | 21-APR-14:40 | 8193.94 | 0.00 |
May | 0.00 | 0.00 | 0.639264E+10 | 0.622124E+10 | 21841.40 | 30-MAY-07:02 | 21841.40 | 0.00 |
June | 0.00 | 0.00 | 0.926538E+10 | 0.895507E+10 | 23697.15 | 04-JUN-08:62 | 18724.82 | 0.00 |
July | 0.00 | 0.00 | 0.108849E+11 | 0.903788E+10 | 25000.58 | 19-JUL-07:02 | 10915.02 | 0.00 |
August | 0.00 | 0.00 | 0.967620E+10 | 0.851802E+10 | 24847.26 | 03-AUG-07:02 | 14770.80 | 0.00 |
September | 0.00 | 0.00 | 0.830915E+10 | 0.728624E+10 | 24379.76 | 23-SEP-07:02 | 14852.36 | 0.00 |
October | 0.00 | 0.00 | 0.381062E+10 | 0.343179E+10 | 23629.85 | 05-OCT-07:02 | 16467.01 | 0.00 |
November | 0.00 | 0.00 | 0.315343E+09 | 0.312007E+09 | 4611.42 | 09-NOV-14:00 | 4611.42 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.521553E+11 | 0.472542E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.108849E+11 | 0.903788E+10 | 25000.58 | 21841.40 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 42.48 | 42.48 | 0.05 | 03-JAN-17:00 | 0.05 | 0.00 |
February | 0.00 | 0.00 | 74857797.47 | 74857797.47 | 2235.75 | 20-FEB-15:30 | 2235.75 | 0.00 |
March | 0.00 | 0.00 | 0.287873E+09 | 0.287873E+09 | 3483.23 | 22-MAR-13:00 | 3483.23 | 0.00 |
April | 0.00 | 0.00 | 0.315177E+10 | 0.314271E+10 | 8659.16 | 21-APR-14:20 | 8659.16 | 0.00 |
May | 0.00 | 0.00 | 0.691031E+10 | 0.672305E+10 | 17537.31 | 30-MAY-07:02 | 17537.31 | 0.00 |
June | 0.00 | 0.00 | 0.102950E+11 | 0.994876E+10 | 25805.55 | 04-JUN-08:62 | 20487.72 | 0.00 |
July | 0.00 | 0.00 | 0.122292E+11 | 0.101795E+11 | 27236.09 | 17-JUL-07:02 | 17754.43 | 0.00 |
August | 0.00 | 0.00 | 0.109787E+11 | 0.968181E+10 | 27169.87 | 03-AUG-07:02 | 15829.81 | 0.00 |
September | 0.00 | 0.00 | 0.945354E+10 | 0.830015E+10 | 26669.54 | 23-SEP-07:02 | 15842.74 | 0.00 |
October | 0.00 | 0.00 | 0.410707E+10 | 0.370448E+10 | 24895.98 | 02-OCT-07:02 | 21956.91 | 0.00 |
November | 0.00 | 0.00 | 0.291244E+09 | 0.287941E+09 | 4824.58 | 09-NOV-14:00 | 4824.58 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.577795E+11 | 0.523311E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.122292E+11 | 0.101795E+11 | 27236.09 | 21956.91 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.204436E+10 | 0.42 | 2771.10 | 06-JAN-08:61 | 1.02 |
February | 0.183831E+10 | 0.42 | 2771.10 | 01-FEB-08:61 | 1.01 |
March | 0.202834E+10 | 0.42 | 2771.10 | 02-MAR-08:61 | 1.02 |
April | 0.194740E+10 | 0.42 | 1174.86 | 11-APR-08:30 | 0.64 |
May | 0.201160E+10 | 0.41 | 2771.10 | 31-MAY-07:02 | 1.01 |
June | 0.197846E+10 | 0.42 | 2771.10 | 03-JUN-07:02 | 1.00 |
July | 0.202863E+10 | 0.41 | 2771.10 | 01-JUL-07:02 | 1.00 |
August | 0.202554E+10 | 0.41 | 2771.10 | 01-AUG-07:02 | 1.00 |
September | 0.195462E+10 | 0.41 | 2771.10 | 02-SEP-07:02 | 1.00 |
October | 0.201174E+10 | 0.41 | 2771.10 | 02-OCT-07:02 | 1.00 |
November | 0.195203E+10 | 0.42 | 2771.10 | 28-NOV-08:61 | 1.01 |
December | 0.207420E+10 | 0.42 | 2771.10 | 04-DEC-08:61 | 1.01 |
Annual Sum or Average | 0.238952E+11 | 0.42 | |||
Minimum of Months | 0.183831E+10 | 0.41 | 1174.86 | 0.64 | |
Maximum of Months | 0.207420E+10 | 0.42 | 2771.10 | 1.02 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.886161E+09 | 0.41 | 1490.48 | 28-JAN-08:61 | 1.05 |
February | 0.866372E+09 | 0.41 | 1346.89 | 03-FEB-08:61 | 1.00 |
March | 0.101944E+10 | 0.43 | 1146.79 | 02-MAR-08:61 | 0.93 |
April | 0.926478E+09 | 0.41 | 598.84 | 08-APR-10:40 | 0.64 |
May | 0.947416E+09 | 0.42 | 1497.10 | 30-MAY-07:02 | 1.04 |
June | 0.950990E+09 | 0.44 | 1497.10 | 03-JUN-07:02 | 1.04 |
July | 0.986749E+09 | 0.44 | 1497.10 | 01-JUL-07:02 | 1.04 |
August | 0.979795E+09 | 0.43 | 1497.10 | 01-AUG-07:02 | 1.03 |
September | 0.928767E+09 | 0.42 | 1497.10 | 02-SEP-07:02 | 1.03 |
October | 0.991582E+09 | 0.41 | 1497.10 | 02-OCT-07:02 | 1.04 |
November | 0.974867E+09 | 0.42 | 822.68 | 28-NOV-08:61 | 0.77 |
December | 0.875366E+09 | 0.40 | 1449.31 | 27-DEC-08:61 | 1.03 |
Annual Sum or Average | 0.113340E+11 | 0.42 | |||
Minimum of Months | 0.866372E+09 | 0.40 | 598.84 | 0.64 | |
Maximum of Months | 0.101944E+10 | 0.44 | 1497.10 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.902164E+09 | 0.35 | 1359.35 | 28-JAN-07:02 | 0.99 |
February | 0.812406E+09 | 0.35 | 1149.33 | 03-FEB-07:02 | 0.92 |
March | 0.912078E+09 | 0.35 | 1036.87 | 02-MAR-07:02 | 0.87 |
April | 0.865598E+09 | 0.34 | 616.52 | 21-APR-09:10 | 0.64 |
May | 0.901726E+09 | 0.35 | 1541.31 | 30-MAY-06:02 | 1.05 |
June | 0.886081E+09 | 0.35 | 1541.31 | 03-JUN-06:02 | 1.04 |
July | 0.893403E+09 | 0.34 | 1541.31 | 01-JUL-06:02 | 1.04 |
August | 0.913516E+09 | 0.35 | 1541.31 | 01-AUG-06:01 | 1.03 |
September | 0.867812E+09 | 0.34 | 1541.31 | 01-SEP-06:02 | 1.03 |
October | 0.892655E+09 | 0.34 | 1541.31 | 02-OCT-06:01 | 1.04 |
November | 0.868249E+09 | 0.34 | 908.90 | 28-NOV-07:03 | 0.80 |
December | 0.905472E+09 | 0.35 | 1344.04 | 27-DEC-07:02 | 0.99 |
Annual Sum or Average | 0.106212E+11 | 0.34 | |||
Minimum of Months | 0.812406E+09 | 0.34 | 616.52 | 0.64 | |
Maximum of Months | 0.913516E+09 | 0.35 | 1541.31 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.899360E+09 | 0.35 | 1463.36 | 28-JAN-07:02 | 1.03 |
February | 0.808311E+09 | 0.35 | 1249.21 | 03-FEB-07:02 | 0.96 |
March | 0.906778E+09 | 0.35 | 1150.71 | 02-MAR-07:02 | 0.92 |
April | 0.859986E+09 | 0.34 | 612.53 | 08-APR-10:30 | 0.64 |
May | 0.895936E+09 | 0.35 | 1531.31 | 30-MAY-06:02 | 1.05 |
June | 0.881309E+09 | 0.35 | 1531.31 | 03-JUN-06:02 | 1.04 |
July | 0.888249E+09 | 0.34 | 1531.31 | 01-JUL-06:02 | 1.04 |
August | 0.907792E+09 | 0.35 | 1531.31 | 01-AUG-06:01 | 1.03 |
September | 0.862233E+09 | 0.34 | 1531.31 | 01-SEP-06:02 | 1.03 |
October | 0.886884E+09 | 0.34 | 1531.31 | 02-OCT-06:01 | 1.04 |
November | 0.863396E+09 | 0.34 | 985.58 | 28-NOV-07:03 | 0.84 |
December | 0.903364E+09 | 0.35 | 1486.00 | 27-DEC-07:02 | 1.03 |
Annual Sum or Average | 0.105636E+11 | 0.34 | |||
Minimum of Months | 0.808311E+09 | 0.34 | 612.53 | 0.64 | |
Maximum of Months | 0.907792E+09 | 0.35 | 1531.31 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.904630E+09 | 0.35 | 1532.32 | 28-JAN-07:02 | 1.05 |
February | 0.811112E+09 | 0.35 | 1372.51 | 03-FEB-07:02 | 1.00 |
March | 0.908604E+09 | 0.35 | 1290.35 | 02-MAR-07:02 | 0.97 |
April | 0.860553E+09 | 0.34 | 612.93 | 01-APR-11:40 | 0.64 |
May | 0.896352E+09 | 0.35 | 1532.32 | 30-MAY-06:02 | 1.05 |
June | 0.880158E+09 | 0.35 | 1532.32 | 03-JUN-06:02 | 1.04 |
July | 0.887944E+09 | 0.34 | 1532.32 | 01-JUL-06:02 | 1.04 |
August | 0.908102E+09 | 0.35 | 1532.32 | 01-AUG-06:01 | 1.03 |
September | 0.862689E+09 | 0.34 | 1532.32 | 01-SEP-06:02 | 1.03 |
October | 0.887425E+09 | 0.34 | 1532.32 | 02-OCT-06:01 | 1.04 |
November | 0.864950E+09 | 0.34 | 1065.25 | 28-NOV-07:03 | 0.88 |
December | 0.909423E+09 | 0.35 | 1532.32 | 04-DEC-07:02 | 1.05 |
Annual Sum or Average | 0.105819E+11 | 0.35 | |||
Minimum of Months | 0.811112E+09 | 0.34 | 612.93 | 0.64 | |
Maximum of Months | 0.909423E+09 | 0.35 | 1532.32 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139735E+10 | 0.31 | 2532.87 | 06-JAN-08:61 | 1.02 |
February | 0.124638E+10 | 0.31 | 2532.87 | 01-FEB-08:61 | 1.01 |
March | 0.139243E+10 | 0.31 | 2532.87 | 01-MAR-08:61 | 1.01 |
April | 0.131309E+10 | 0.31 | 1064.68 | 11-APR-08:30 | 0.63 |
May | 0.136841E+10 | 0.31 | 2532.87 | 30-MAY-07:02 | 1.01 |
June | 0.135391E+10 | 0.31 | 2532.87 | 03-JUN-07:02 | 1.00 |
July | 0.136275E+10 | 0.30 | 2532.87 | 01-JUL-07:02 | 1.01 |
August | 0.139168E+10 | 0.31 | 2532.87 | 01-AUG-07:02 | 1.00 |
September | 0.131632E+10 | 0.30 | 2532.87 | 02-SEP-07:02 | 1.00 |
October | 0.135374E+10 | 0.30 | 2532.87 | 02-OCT-07:02 | 1.00 |
November | 0.132434E+10 | 0.31 | 2532.87 | 28-NOV-08:61 | 1.01 |
December | 0.140858E+10 | 0.31 | 2532.87 | 03-DEC-09:01 | 1.01 |
Annual Sum or Average | 0.162290E+11 | 0.31 | |||
Minimum of Months | 0.124638E+10 | 0.30 | 1064.68 | 0.63 | |
Maximum of Months | 0.140858E+10 | 0.31 | 2532.87 | 1.02 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.752367E+09 | 0.32 | 1362.20 | 06-JAN-08:61 | 1.05 |
February | 0.670794E+09 | 0.32 | 1362.20 | 01-FEB-08:61 | 1.05 |
March | 0.749150E+09 | 0.33 | 1362.20 | 01-MAR-08:61 | 1.05 |
April | 0.706181E+09 | 0.32 | 566.36 | 11-APR-08:30 | 0.65 |
May | 0.735886E+09 | 0.32 | 1362.20 | 30-MAY-07:02 | 1.04 |
June | 0.728432E+09 | 0.32 | 1362.20 | 03-JUN-07:02 | 1.04 |
July | 0.733091E+09 | 0.31 | 1362.20 | 01-JUL-07:02 | 1.04 |
August | 0.748400E+09 | 0.32 | 1362.20 | 01-AUG-07:02 | 1.03 |
September | 0.707773E+09 | 0.31 | 1362.20 | 02-SEP-07:02 | 1.03 |
October | 0.728026E+09 | 0.31 | 1362.20 | 02-OCT-07:02 | 1.04 |
November | 0.712344E+09 | 0.32 | 1362.20 | 28-NOV-08:61 | 1.05 |
December | 0.758251E+09 | 0.32 | 1362.20 | 03-DEC-09:01 | 1.05 |
Annual Sum or Average | 0.873070E+10 | 0.32 | |||
Minimum of Months | 0.670794E+09 | 0.31 | 566.36 | 0.65 | |
Maximum of Months | 0.758251E+09 | 0.33 | 1362.20 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.750893E+09 | 0.32 | 1355.58 | 06-JAN-08:61 | 1.05 |
February | 0.668892E+09 | 0.32 | 1355.58 | 01-FEB-08:61 | 1.05 |
March | 0.746258E+09 | 0.33 | 1355.58 | 01-MAR-08:61 | 1.05 |
April | 0.702760E+09 | 0.32 | 570.41 | 11-APR-08:30 | 0.66 |
May | 0.732284E+09 | 0.32 | 1355.58 | 30-MAY-07:02 | 1.04 |
June | 0.724744E+09 | 0.32 | 1355.58 | 03-JUN-07:02 | 1.04 |
July | 0.729364E+09 | 0.31 | 1355.58 | 01-JUL-07:02 | 1.04 |
August | 0.744652E+09 | 0.32 | 1355.58 | 01-AUG-07:02 | 1.03 |
September | 0.704293E+09 | 0.31 | 1355.58 | 02-SEP-07:02 | 1.03 |
October | 0.724475E+09 | 0.31 | 1355.58 | 02-OCT-07:02 | 1.04 |
November | 0.709275E+09 | 0.32 | 1355.58 | 28-NOV-08:61 | 1.05 |
December | 0.756645E+09 | 0.32 | 1355.58 | 03-DEC-09:01 | 1.05 |
Annual Sum or Average | 0.869453E+10 | 0.32 | |||
Minimum of Months | 0.668892E+09 | 0.31 | 570.41 | 0.66 | |
Maximum of Months | 0.756645E+09 | 0.33 | 1355.58 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.758006E+09 | 0.33 | 1356.98 | 02-JAN-08:61 | 1.04 |
February | 0.673877E+09 | 0.32 | 1356.98 | 01-FEB-08:61 | 1.05 |
March | 0.749717E+09 | 0.33 | 1356.98 | 01-MAR-08:61 | 1.05 |
April | 0.703542E+09 | 0.32 | 593.85 | 11-APR-08:13 | 0.67 |
May | 0.732969E+09 | 0.32 | 1334.08 | 30-MAY-07:02 | 1.03 |
June | 0.725129E+09 | 0.32 | 1356.98 | 03-JUN-07:02 | 1.04 |
July | 0.730087E+09 | 0.31 | 1356.98 | 01-JUL-07:02 | 1.04 |
August | 0.745453E+09 | 0.32 | 1356.98 | 01-AUG-07:02 | 1.03 |
September | 0.704917E+09 | 0.31 | 1356.98 | 03-SEP-08:62 | 1.03 |
October | 0.725195E+09 | 0.31 | 1356.98 | 02-OCT-07:02 | 1.04 |
November | 0.711286E+09 | 0.32 | 1356.98 | 27-NOV-08:61 | 1.05 |
December | 0.763703E+09 | 0.33 | 1356.98 | 03-DEC-09:01 | 1.05 |
Annual Sum or Average | 0.872388E+10 | 0.32 | |||
Minimum of Months | 0.673877E+09 | 0.31 | 593.85 | 0.67 | |
Maximum of Months | 0.763703E+09 | 0.33 | 1356.98 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.868713E+09 | 0.33 | 1527.49 | 01-JAN-09:01 | 1.05 |
February | 0.770400E+09 | 0.33 | 1527.49 | 01-FEB-08:61 | 1.05 |
March | 0.852899E+09 | 0.33 | 1527.49 | 01-MAR-08:61 | 1.05 |
April | 0.792572E+09 | 0.32 | 1039.23 | 12-APR-07:03 | 0.87 |
May | 0.824944E+09 | 0.32 | 1043.54 | 30-MAY-07:02 | 0.87 |
June | 0.816887E+09 | 0.32 | 1527.49 | 04-JUN-08:62 | 1.03 |
July | 0.825873E+09 | 0.31 | 1527.49 | 02-JUL-08:61 | 1.03 |
August | 0.842691E+09 | 0.32 | 1527.49 | 01-AUG-07:02 | 1.03 |
September | 0.793324E+09 | 0.31 | 1527.49 | 03-SEP-08:62 | 1.03 |
October | 0.816211E+09 | 0.31 | 1527.49 | 02-OCT-07:02 | 1.04 |
November | 0.804261E+09 | 0.32 | 1527.49 | 27-NOV-08:61 | 1.05 |
December | 0.872787E+09 | 0.33 | 1527.49 | 02-DEC-08:62 | 1.05 |
Annual Sum or Average | 0.988156E+10 | 0.32 | |||
Minimum of Months | 0.770400E+09 | 0.31 | 1039.23 | 0.87 | |
Maximum of Months | 0.872787E+09 | 0.33 | 1527.49 | 1.05 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.204826E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.198644E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.241699E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.464513E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.718908E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.942753E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.103917E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.940935E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.804980E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.492460E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.225378E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.207420E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.648169E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.198644E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.103917E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.896371E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.994271E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.131983E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.257331E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.378455E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.474895E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.520369E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.477073E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.419818E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.272198E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.118842E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.878358E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.332786E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.878358E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.520369E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.905181E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.888440E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.112250E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.194016E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.294662E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.382372E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.413919E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.379665E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.330837E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.208837E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.102288E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.905472E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.268875E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.888440E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.413919E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.901255E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.876115E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.110332E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.192435E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.294171E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.382614E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.414023E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.379809E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.330612E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.207741E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.101038E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.903364E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.268085E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.876115E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.414023E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.905200E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.866922E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.107964E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.188189E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.289341E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.377720E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.409483E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.375150E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.326212E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.203892E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.995137E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.909423E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.264562E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.866922E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.409483E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.139746E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.132609E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.164633E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.307983E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.493644E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.660006E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.707112E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.649797E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.563534E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.337359E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.152493E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.140858E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.444978E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.132609E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.707112E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.752369E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.708119E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.870629E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.159580E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.254073E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.338334E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.362453E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.333292E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.289379E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.174846E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.811036E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.758251E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.230200E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.708119E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.362453E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.750893E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.703392E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.860295E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.157692E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.252019E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.336231E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.360178E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.331191E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.287446E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.173192E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.803277E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.756645E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.228540E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.703392E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.360178E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.758006E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.702119E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.846562E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.154371E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.249391E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.335202E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.359782E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.330989E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.286903E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.171117E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.795293E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.763703E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.227432E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.702119E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.359782E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.868713E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.791326E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.932995E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.166599E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.273100E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.372693E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.403900E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.373537E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.323802E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.187856E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.882036E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.872787E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.253627E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.791326E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.403900E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.204436E+10 | 13775720.74 | 0.125001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.183831E+10 | 0.540355E+09 | 0.704863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202834E+10 | 0.141585E+10 | 0.345642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194740E+10 | 0.979200E+10 | 3596158.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201160E+10 | 0.186769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.197846E+10 | 0.260393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.202863E+10 | 0.312966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202554E+10 | 0.273988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.195462E+10 | 0.232022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201174E+10 | 0.111587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.195203E+10 | 0.112503E+10 | 0.328531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207420E+10 | 0.00 | 0.207393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238952E+11 | 0.150659E+12 | 0.470658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.183831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.207420E+10 | 0.312966E+11 | 0.207393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.886161E+09 | 37317847.07 | 0.112424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.866372E+09 | 0.474779E+09 | 53922439.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101944E+10 | 0.111364E+10 | 26853804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.926478E+09 | 0.597262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.947416E+09 | 0.103014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.950990E+09 | 0.134409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.986749E+09 | 0.159440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.979795E+09 | 0.141527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.928767E+09 | 0.123960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.991582E+09 | 0.658909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.974867E+09 | 0.810327E+09 | 24630744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.875366E+09 | 10885271.33 | 0.281804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113340E+11 | 0.812435E+11 | 0.499635E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.866372E+09 | 10885271.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101944E+10 | 0.159440E+11 | 0.281804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.902164E+09 | 10900179.90 | 0.357451E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.812406E+09 | 0.282194E+09 | 0.162461E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.912078E+09 | 0.783015E+09 | 75237072.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.865598E+09 | 0.396567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.901726E+09 | 0.748493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.886081E+09 | 0.104192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.893403E+09 | 0.123281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.913516E+09 | 0.108870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.867812E+09 | 0.937332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.892655E+09 | 0.464551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.868249E+09 | 0.586063E+09 | 95415381.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.905472E+09 | 0.00 | 0.636247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106212E+11 | 0.607659E+11 | 0.132681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.812406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.913516E+09 | 0.123281E+11 | 0.636247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.899360E+09 | 6813743.79 | 0.465214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.808311E+09 | 0.250628E+09 | 0.203805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.906778E+09 | 0.729583E+09 | 96902481.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.859986E+09 | 0.392721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.895936E+09 | 0.749788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.881309E+09 | 0.104640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.888249E+09 | 0.123763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.907792E+09 | 0.109355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.862233E+09 | 0.940205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.886884E+09 | 0.462798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.863396E+09 | 0.556805E+09 | 0.122834E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.903364E+09 | 0.00 | 0.768337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105636E+11 | 0.607748E+11 | 0.165709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.808311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.907792E+09 | 0.123763E+11 | 0.768337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.904630E+09 | 2036344.81 | 0.633963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.811112E+09 | 0.204832E+09 | 0.285649E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.908604E+09 | 0.631084E+09 | 0.141204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.860553E+09 | 0.374849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.896352E+09 | 0.728760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.880158E+09 | 0.102571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.887944E+09 | 0.121610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.908102E+09 | 0.107183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.862689E+09 | 0.919564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.887425E+09 | 0.445907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.864950E+09 | 0.491675E+09 | 0.158400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.909423E+09 | 0.00 | 0.965565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105819E+11 | 0.591568E+11 | 0.218478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.811112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.909423E+09 | 0.121610E+11 | 0.965565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.139735E+10 | 396769.37 | 0.169495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124638E+10 | 0.285794E+09 | 0.800561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139243E+10 | 0.914477E+09 | 0.387037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131309E+10 | 0.633798E+10 | 1806334.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136841E+10 | 0.127712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135391E+10 | 0.182190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136275E+10 | 0.213266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139168E+10 | 0.189566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131632E+10 | 0.163150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135374E+10 | 0.769144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132434E+10 | 0.742812E+09 | 0.433570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140858E+10 | 0.00 | 0.240549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162290E+11 | 0.103561E+12 | 0.572341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140858E+10 | 0.213266E+11 | 0.240549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.752367E+09 | 8734.92 | 0.905980E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.670794E+09 | 0.135969E+09 | 0.430669E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.749150E+09 | 0.444649E+09 | 0.210213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.706181E+09 | 0.324656E+10 | 548310.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.735886E+09 | 0.657262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.728432E+09 | 0.937739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.733091E+09 | 0.109852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.748400E+09 | 0.975869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.707773E+09 | 0.840050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.728026E+09 | 0.395431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.712344E+09 | 0.371978E+09 | 0.227282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.758251E+09 | 0.00 | 0.126682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.873070E+10 | 0.532478E+11 | 0.304151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.670794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.758251E+09 | 0.109852E+11 | 0.126682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.750893E+09 | 0.00 | 0.982918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.668892E+09 | 0.125394E+09 | 0.479123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.746258E+09 | 0.416470E+09 | 0.237096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.702760E+09 | 0.318530E+10 | 1053363.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.732284E+09 | 0.650583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.724744E+09 | 0.931174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.729364E+09 | 0.109088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.744652E+09 | 0.968977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.704293E+09 | 0.833580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.724475E+09 | 0.390085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.709275E+09 | 0.353885E+09 | 0.240974E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.756645E+09 | 0.00 | 0.133851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.869453E+10 | 0.527339E+11 | 0.327968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.668892E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.756645E+09 | 0.109088E+11 | 0.133851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.758006E+09 | 0.00 | 0.121713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.673877E+09 | 0.102029E+09 | 0.637654E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.749717E+09 | 0.351563E+09 | 0.336301E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.703542E+09 | 0.304747E+10 | 3153737.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.732969E+09 | 0.639264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.725129E+09 | 0.926538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.730087E+09 | 0.108849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.745453E+09 | 0.967620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.704917E+09 | 0.830915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.725195E+09 | 0.381062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.711286E+09 | 0.315343E+09 | 0.288302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.763703E+09 | 0.00 | 0.157079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.872388E+10 | 0.521553E+11 | 0.405333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.673877E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.763703E+09 | 0.108849E+11 | 0.157079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.868713E+09 | 42.48 | 0.189831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.770400E+09 | 74857797.47 | 0.112960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.852899E+09 | 0.287873E+09 | 0.694114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.792572E+09 | 0.315177E+10 | 26044480.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.824944E+09 | 0.691031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.816887E+09 | 0.102950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.825873E+09 | 0.122292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.842691E+09 | 0.109787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.793324E+09 | 0.945354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.816211E+09 | 0.410707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.804261E+09 | 0.291244E+09 | 0.447364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.872787E+09 | 0.00 | 0.220371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.988156E+10 | 0.577795E+11 | 0.639914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.770400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.872787E+09 | 0.122292E+11 | 0.220371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.204436E+10 | 0.00 | 0.00 | 0.00 | 3897165.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.183831E+10 | 0.00 | 0.00 | 0.00 | 0.148136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202834E+10 | 0.00 | 0.00 | 0.00 | 0.388652E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194740E+10 | 0.00 | 0.00 | 0.00 | 0.269772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201160E+10 | 0.00 | 0.00 | 0.00 | 0.517748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.197846E+10 | 0.00 | 0.00 | 0.00 | 0.744907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.202863E+10 | 0.00 | 0.00 | 0.00 | 0.836308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202554E+10 | 0.00 | 0.00 | 0.00 | 0.738381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.195462E+10 | 0.00 | 0.00 | 0.00 | 0.609518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201174E+10 | 0.00 | 0.00 | 0.00 | 0.291285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.195203E+10 | 0.00 | 0.00 | 0.00 | 0.301750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238952E+11 | 0.00 | 0.00 | 0.00 | 0.409216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.183831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.207420E+10 | 0.00 | 0.00 | 0.00 | 0.836308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.886161E+09 | 0.00 | 0.00 | 0.00 | 10210443.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.866372E+09 | 0.00 | 0.00 | 0.00 | 0.127899E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101944E+10 | 0.00 | 0.00 | 0.00 | 0.300389E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.926478E+09 | 0.00 | 0.00 | 0.00 | 0.164683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.947416E+09 | 0.00 | 0.00 | 0.00 | 0.283714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.950990E+09 | 0.00 | 0.00 | 0.00 | 0.379796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.986749E+09 | 0.00 | 0.00 | 0.00 | 0.421695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.979795E+09 | 0.00 | 0.00 | 0.00 | 0.379094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.928767E+09 | 0.00 | 0.00 | 0.00 | 0.326942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.991582E+09 | 0.00 | 0.00 | 0.00 | 0.173040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.974867E+09 | 0.00 | 0.00 | 0.00 | 0.213555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.875366E+09 | 0.00 | 0.00 | 0.00 | 2991976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113340E+11 | 0.00 | 0.00 | 0.00 | 0.219447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.866372E+09 | 0.00 | 0.00 | 0.00 | 2991976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101944E+10 | 0.00 | 0.00 | 0.00 | 0.421695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.902164E+09 | 0.00 | 0.00 | 0.00 | 3016538.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.812406E+09 | 0.00 | 0.00 | 0.00 | 76034933.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.912078E+09 | 0.00 | 0.00 | 0.00 | 0.210423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.865598E+09 | 0.00 | 0.00 | 0.00 | 0.107456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.901726E+09 | 0.00 | 0.00 | 0.00 | 0.204489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.886081E+09 | 0.00 | 0.00 | 0.00 | 0.293764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.893403E+09 | 0.00 | 0.00 | 0.00 | 0.324579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.913516E+09 | 0.00 | 0.00 | 0.00 | 0.288313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.867812E+09 | 0.00 | 0.00 | 0.00 | 0.244056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.892655E+09 | 0.00 | 0.00 | 0.00 | 0.119571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.868249E+09 | 0.00 | 0.00 | 0.00 | 0.154626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.905472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106212E+11 | 0.00 | 0.00 | 0.00 | 0.162664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.812406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.913516E+09 | 0.00 | 0.00 | 0.00 | 0.324579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.899360E+09 | 0.00 | 0.00 | 0.00 | 1894971.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.808311E+09 | 0.00 | 0.00 | 0.00 | 67804457.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.906778E+09 | 0.00 | 0.00 | 0.00 | 0.196547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.859986E+09 | 0.00 | 0.00 | 0.00 | 0.106436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.895936E+09 | 0.00 | 0.00 | 0.00 | 0.204577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.881309E+09 | 0.00 | 0.00 | 0.00 | 0.294483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.888249E+09 | 0.00 | 0.00 | 0.00 | 0.325198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.907792E+09 | 0.00 | 0.00 | 0.00 | 0.289030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.862233E+09 | 0.00 | 0.00 | 0.00 | 0.244389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.886884E+09 | 0.00 | 0.00 | 0.00 | 0.119052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.863396E+09 | 0.00 | 0.00 | 0.00 | 0.146982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.903364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105636E+11 | 0.00 | 0.00 | 0.00 | 0.162449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.808311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.907792E+09 | 0.00 | 0.00 | 0.00 | 0.325198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.904630E+09 | 0.00 | 0.00 | 0.00 | 569707.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.811112E+09 | 0.00 | 0.00 | 0.00 | 55809840.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.908604E+09 | 0.00 | 0.00 | 0.00 | 0.171035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.860553E+09 | 0.00 | 0.00 | 0.00 | 0.102134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.896352E+09 | 0.00 | 0.00 | 0.00 | 0.199706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.880158E+09 | 0.00 | 0.00 | 0.00 | 0.289704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.887944E+09 | 0.00 | 0.00 | 0.00 | 0.320688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.908102E+09 | 0.00 | 0.00 | 0.00 | 0.284339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.862689E+09 | 0.00 | 0.00 | 0.00 | 0.239943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.887425E+09 | 0.00 | 0.00 | 0.00 | 0.115150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.864950E+09 | 0.00 | 0.00 | 0.00 | 0.130187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.909423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105819E+11 | 0.00 | 0.00 | 0.00 | 0.158743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.811112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.909423E+09 | 0.00 | 0.00 | 0.00 | 0.320688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.139735E+10 | 0.00 | 0.00 | 0.00 | 113613.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124638E+10 | 0.00 | 0.00 | 0.00 | 79715156.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139243E+10 | 0.00 | 0.00 | 0.00 | 0.253898E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131309E+10 | 0.00 | 0.00 | 0.00 | 0.176675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136841E+10 | 0.00 | 0.00 | 0.00 | 0.356803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135391E+10 | 0.00 | 0.00 | 0.00 | 0.524615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136275E+10 | 0.00 | 0.00 | 0.00 | 0.570837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139168E+10 | 0.00 | 0.00 | 0.00 | 0.510629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131632E+10 | 0.00 | 0.00 | 0.00 | 0.431901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135374E+10 | 0.00 | 0.00 | 0.00 | 0.201986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132434E+10 | 0.00 | 0.00 | 0.00 | 0.200586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162290E+11 | 0.00 | 0.00 | 0.00 | 0.282688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140858E+10 | 0.00 | 0.00 | 0.00 | 0.570837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.752367E+09 | 0.00 | 0.00 | 0.00 | 2468.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.670794E+09 | 0.00 | 0.00 | 0.00 | 37325339.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.749150E+09 | 0.00 | 0.00 | 0.00 | 0.121480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.706181E+09 | 0.00 | 0.00 | 0.00 | 0.889617E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.735886E+09 | 0.00 | 0.00 | 0.00 | 0.180485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.728432E+09 | 0.00 | 0.00 | 0.00 | 0.265490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.733091E+09 | 0.00 | 0.00 | 0.00 | 0.289144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.748400E+09 | 0.00 | 0.00 | 0.00 | 0.258452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.707773E+09 | 0.00 | 0.00 | 0.00 | 0.218602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.728026E+09 | 0.00 | 0.00 | 0.00 | 0.102043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.712344E+09 | 0.00 | 0.00 | 0.00 | 98691990.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.758251E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.873070E+10 | 0.00 | 0.00 | 0.00 | 0.142893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.670794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.758251E+09 | 0.00 | 0.00 | 0.00 | 0.289144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.750893E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.668892E+09 | 0.00 | 0.00 | 0.00 | 34499691.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.746258E+09 | 0.00 | 0.00 | 0.00 | 0.114037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.702760E+09 | 0.00 | 0.00 | 0.00 | 0.874161E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.732284E+09 | 0.00 | 0.00 | 0.00 | 0.178791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.724744E+09 | 0.00 | 0.00 | 0.00 | 0.263756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.729364E+09 | 0.00 | 0.00 | 0.00 | 0.287242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.744652E+09 | 0.00 | 0.00 | 0.00 | 0.256726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.704293E+09 | 0.00 | 0.00 | 0.00 | 0.217017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.724475E+09 | 0.00 | 0.00 | 0.00 | 0.100745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.709275E+09 | 0.00 | 0.00 | 0.00 | 94002216.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.756645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.869453E+10 | 0.00 | 0.00 | 0.00 | 0.141595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.668892E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.756645E+09 | 0.00 | 0.00 | 0.00 | 0.287242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.758006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.673877E+09 | 0.00 | 0.00 | 0.00 | 28241427.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.749717E+09 | 0.00 | 0.00 | 0.00 | 96845352.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.703542E+09 | 0.00 | 0.00 | 0.00 | 0.840163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.732969E+09 | 0.00 | 0.00 | 0.00 | 0.176094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.725129E+09 | 0.00 | 0.00 | 0.00 | 0.262689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.730087E+09 | 0.00 | 0.00 | 0.00 | 0.286773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.745453E+09 | 0.00 | 0.00 | 0.00 | 0.256443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.704917E+09 | 0.00 | 0.00 | 0.00 | 0.216411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.725195E+09 | 0.00 | 0.00 | 0.00 | 0.985978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.711286E+09 | 0.00 | 0.00 | 0.00 | 84006992.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.763703E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.872388E+10 | 0.00 | 0.00 | 0.00 | 0.140193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.673877E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.763703E+09 | 0.00 | 0.00 | 0.00 | 0.286773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.868713E+09 | 0.00 | 0.00 | 0.00 | 12.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.770400E+09 | 0.00 | 0.00 | 0.00 | 20926508.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.852899E+09 | 0.00 | 0.00 | 0.00 | 80095911.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.792572E+09 | 0.00 | 0.00 | 0.00 | 0.873415E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.824944E+09 | 0.00 | 0.00 | 0.00 | 0.190605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.816887E+09 | 0.00 | 0.00 | 0.00 | 0.291004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.825873E+09 | 0.00 | 0.00 | 0.00 | 0.321313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.842691E+09 | 0.00 | 0.00 | 0.00 | 0.289267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.793324E+09 | 0.00 | 0.00 | 0.00 | 0.244470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.816211E+09 | 0.00 | 0.00 | 0.00 | 0.106235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.804261E+09 | 0.00 | 0.00 | 0.00 | 77774768.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.872787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.988156E+10 | 0.00 | 0.00 | 0.00 | 0.154812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.770400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.872787E+09 | 0.00 | 0.00 | 0.00 | 0.321313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.861994E+10 | 0.00 | 0.00 | 896092.20 | 0.00 | 0.201944E+09 | 0.974104E+09 | 0.00 | 0.55 |
February | 0.562749E+10 | 0.00 | 0.00 | 3607270.88 | 0.00 | 0.124353E+09 | 0.237020E+10 | 0.00 | 0.69 |
March | 0.367831E+10 | 273168.19 | 0.00 | 7616674.62 | 0.00 | 69381120.31 | 0.468571E+10 | 0.00 | 0.83 |
April | 0.549980E+09 | 0.491959E+09 | 0.00 | 17457189.67 | 24953.18 | 0.00 | 0.383406E+10 | 0.00 | 0.92 |
May | 26939723.10 | 0.204490E+10 | 0.00 | 12008238.09 | 512224.60 | 0.00 | 0.159504E+10 | 0.00 | 0.80 |
June | 213381.43 | 0.452407E+10 | 0.00 | 2313026.53 | 0.00 | 0.00 | 0.148578E+09 | 0.00 | 0.63 |
July | 33088.79 | 0.739043E+10 | 0.00 | 331815.61 | 15166542.63 | 0.00 | 13918089.43 | 0.00 | 0.60 |
August | 487.88 | 0.479679E+10 | 0.00 | 2906423.49 | 2276767.14 | 0.00 | 0.416524E+09 | 0.00 | 0.74 |
September | 1277957.30 | 0.334813E+10 | 0.00 | 12311396.22 | 1576324.91 | 0.00 | 0.147627E+10 | 0.00 | 0.87 |
October | 0.189481E+09 | 0.786184E+09 | 0.00 | 23907484.62 | 262473.08 | 0.00 | 0.655019E+10 | 0.00 | 1.12 |
November | 0.350347E+10 | 0.00 | 0.00 | 9652432.99 | 0.00 | 43183890.21 | 0.680373E+10 | 0.00 | 0.84 |
December | 0.937433E+10 | 0.00 | 0.00 | 361548.94 | 0.00 | 0.518286E+09 | 0.561781E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.315715E+11 | 0.233827E+11 | 0.00 | 93369593.87 | 19819285.55 | 0.957149E+09 | 0.294301E+11 | 0.00 | 0.76 |
Minimum of Months | 487.88 | 0.00 | 0.00 | 331815.61 | 0.00 | 0.00 | 13918089.43 | 0.00 | 0.53 |
Maximum of Months | 0.937433E+10 | 0.739043E+10 | 0.00 | 23907484.62 | 15166542.63 | 0.518286E+09 | 0.680373E+10 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.268736E+10 | 0.00 | 0.00 | 1751524.95 | 0.00 | 12181398.35 | 0.158174E+10 | 0.00 | 0.49 |
February | 0.172573E+10 | 0.00 | 0.00 | 3146600.98 | 0.00 | 3720789.70 | 0.217799E+10 | 0.00 | 0.70 |
March | 0.969280E+09 | 156119.42 | 0.00 | 5797609.34 | 0.00 | 3156910.78 | 0.349653E+10 | 0.00 | 0.90 |
April | 0.134880E+09 | 0.235929E+09 | 0.00 | 7633872.59 | 0.00 | 0.00 | 0.207619E+10 | 0.00 | 0.82 |
May | 4243327.93 | 0.975746E+09 | 0.00 | 5098755.34 | 0.00 | 0.00 | 0.706466E+09 | 0.00 | 0.66 |
June | 203377.29 | 0.202659E+10 | 0.00 | 898172.27 | 87986.21 | 0.00 | 63194871.85 | 0.00 | 0.52 |
July | 0.00 | 0.336673E+10 | 0.00 | 21604.55 | 27304439.55 | 0.00 | 32312.23 | 0.00 | 0.49 |
August | 0.00 | 0.220843E+10 | 0.00 | 1146549.98 | 7433425.55 | 0.00 | 0.147773E+09 | 0.00 | 0.62 |
September | 558489.09 | 0.167723E+10 | 0.00 | 4067464.42 | 4800941.48 | 0.00 | 0.507115E+09 | 0.00 | 0.70 |
October | 40510444.22 | 0.403089E+09 | 0.00 | 10429941.08 | 234924.51 | 0.00 | 0.320772E+10 | 0.00 | 1.05 |
November | 0.872198E+09 | 0.00 | 0.00 | 6822908.14 | 0.00 | 0.00 | 0.448995E+10 | 0.00 | 0.89 |
December | 0.310096E+10 | 0.00 | 0.00 | 1238990.71 | 0.00 | 29040801.01 | 0.118975E+10 | 0.00 | 0.45 |
Annual Sum or Average | 0.953592E+10 | 0.108939E+11 | 0.00 | 48053994.35 | 39861717.29 | 48099899.84 | 0.196444E+11 | 0.00 | 0.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21604.55 | 0.00 | 0.00 | 32312.23 | 0.00 | 0.45 |
Maximum of Months | 0.310096E+10 | 0.336673E+10 | 0.00 | 10429941.08 | 27304439.55 | 29040801.01 | 0.448995E+10 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.307702E+10 | 0.00 | 0.00 | 552428.28 | 0.00 | 76465554.22 | 0.581979E+09 | 0.00 | 0.45 |
February | 0.208238E+10 | 0.00 | 0.00 | 1407833.02 | 0.00 | 45725113.95 | 0.100690E+10 | 0.00 | 0.59 |
March | 0.143592E+10 | 313189.68 | 0.00 | 3042918.98 | 0.00 | 21532803.22 | 0.184449E+10 | 0.00 | 0.74 |
April | 0.330282E+09 | 0.230434E+09 | 0.00 | 3206521.40 | 6777397.52 | 0.00 | 0.139784E+10 | 0.00 | 0.71 |
May | 43059756.71 | 0.894684E+09 | 0.00 | 2162055.39 | 36084506.04 | 0.00 | 0.613409E+09 | 0.00 | 0.64 |
June | 1627464.49 | 0.181556E+10 | 0.00 | 1298814.41 | 0.104919E+09 | 0.00 | 0.125282E+09 | 0.00 | 0.54 |
July | 18095.03 | 0.284686E+10 | 0.00 | 363780.65 | 0.190632E+09 | 0.00 | 9952946.07 | 0.00 | 0.49 |
August | 5478828.21 | 0.188893E+10 | 0.00 | 1434330.98 | 98513855.06 | 0.00 | 0.229578E+09 | 0.00 | 0.63 |
September | 30215660.14 | 0.137343E+10 | 0.00 | 1858473.61 | 39674075.91 | 0.00 | 0.353823E+09 | 0.00 | 0.64 |
October | 0.222753E+09 | 0.327876E+09 | 0.00 | 6015213.43 | 13776799.97 | 0.00 | 0.222723E+10 | 0.00 | 0.87 |
November | 0.132168E+10 | 0.00 | 0.00 | 3990209.60 | 0.00 | 16507711.44 | 0.263203E+10 | 0.00 | 0.74 |
December | 0.329782E+10 | 0.00 | 0.00 | 293284.35 | 0.00 | 0.233366E+09 | 0.353997E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.118483E+11 | 0.937810E+10 | 0.00 | 25625864.11 | 0.490378E+09 | 0.393598E+09 | 0.113765E+11 | 0.00 | 0.62 |
Minimum of Months | 18095.03 | 0.00 | 0.00 | 293284.35 | 0.00 | 0.00 | 9952946.07 | 0.00 | 0.42 |
Maximum of Months | 0.329782E+10 | 0.284686E+10 | 0.00 | 6015213.43 | 0.190632E+09 | 0.233366E+09 | 0.263203E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.308884E+10 | 0.00 | 0.00 | 399163.11 | 0.00 | 0.129961E+09 | 0.444025E+09 | 0.00 | 0.44 |
February | 0.212639E+10 | 0.00 | 0.00 | 1229061.14 | 0.00 | 57385678.16 | 0.877578E+09 | 0.00 | 0.58 |
March | 0.146230E+10 | 310748.35 | 0.00 | 2798348.94 | 0.00 | 23545911.05 | 0.173207E+10 | 0.00 | 0.72 |
April | 0.334447E+09 | 0.230377E+09 | 0.00 | 3154464.32 | 6848050.98 | 0.00 | 0.137509E+10 | 0.00 | 0.71 |
May | 42876294.96 | 0.895218E+09 | 0.00 | 2178158.52 | 36089809.77 | 0.00 | 0.612548E+09 | 0.00 | 0.64 |
June | 1841378.99 | 0.181675E+10 | 0.00 | 1329634.43 | 0.104075E+09 | 0.00 | 0.124402E+09 | 0.00 | 0.54 |
July | 27723.06 | 0.285371E+10 | 0.00 | 392327.93 | 0.188802E+09 | 0.00 | 9976996.33 | 0.00 | 0.49 |
August | 5552572.15 | 0.189291E+10 | 0.00 | 1462756.42 | 97662658.34 | 0.00 | 0.225814E+09 | 0.00 | 0.63 |
September | 30136421.06 | 0.137660E+10 | 0.00 | 1873071.67 | 39756216.87 | 0.00 | 0.353155E+09 | 0.00 | 0.64 |
October | 0.226412E+09 | 0.327902E+09 | 0.00 | 5969748.50 | 13601639.24 | 0.00 | 0.220895E+10 | 0.00 | 0.87 |
November | 0.135891E+10 | 0.00 | 0.00 | 3771868.31 | 0.00 | 21087684.71 | 0.250825E+10 | 0.00 | 0.72 |
December | 0.328693E+10 | 0.00 | 0.00 | 190704.97 | 0.00 | 0.289062E+09 | 0.250817E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.119647E+11 | 0.939378E+10 | 0.00 | 24749308.25 | 0.486835E+09 | 0.521042E+09 | 0.107227E+11 | 0.00 | 0.62 |
Minimum of Months | 27723.06 | 0.00 | 0.00 | 190704.97 | 0.00 | 0.00 | 9976996.33 | 0.00 | 0.42 |
Maximum of Months | 0.328693E+10 | 0.285371E+10 | 0.00 | 5969748.50 | 0.188802E+09 | 0.289062E+09 | 0.250825E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.307578E+10 | 0.00 | 0.00 | 264327.47 | 0.00 | 0.209195E+09 | 0.288747E+09 | 0.00 | 0.44 |
February | 0.212426E+10 | 0.00 | 0.00 | 980328.66 | 0.00 | 93552150.91 | 0.737710E+09 | 0.00 | 0.56 |
March | 0.151827E+10 | 311123.91 | 0.00 | 2331377.79 | 0.00 | 36534129.39 | 0.151988E+10 | 0.00 | 0.69 |
April | 0.355747E+09 | 0.230284E+09 | 0.00 | 2863257.05 | 7071203.61 | 0.00 | 0.127494E+10 | 0.00 | 0.69 |
May | 47053854.84 | 0.891900E+09 | 0.00 | 2010843.59 | 36559648.61 | 0.00 | 0.586412E+09 | 0.00 | 0.63 |
June | 1587993.36 | 0.181284E+10 | 0.00 | 1215494.67 | 0.105741E+09 | 0.00 | 0.124061E+09 | 0.00 | 0.54 |
July | 25894.11 | 0.282948E+10 | 0.00 | 358102.70 | 0.191689E+09 | 0.00 | 9983955.63 | 0.00 | 0.49 |
August | 5427332.96 | 0.187779E+10 | 0.00 | 1395249.19 | 98887823.89 | 0.00 | 0.229810E+09 | 0.00 | 0.63 |
September | 29877898.65 | 0.136214E+10 | 0.00 | 1756104.11 | 39899905.86 | 0.00 | 0.344986E+09 | 0.00 | 0.63 |
October | 0.249427E+09 | 0.322137E+09 | 0.00 | 5637858.30 | 14100250.37 | 0.00 | 0.212160E+10 | 0.00 | 0.85 |
November | 0.143404E+10 | 0.00 | 0.00 | 3316027.50 | 0.00 | 32559774.83 | 0.227750E+10 | 0.00 | 0.70 |
December | 0.325812E+10 | 0.00 | 0.00 | 97107.42 | 0.00 | 0.364724E+09 | 0.132563E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.120996E+11 | 0.932689E+10 | 0.00 | 22226078.48 | 0.493949E+09 | 0.736564E+09 | 0.964819E+10 | 0.00 | 0.61 |
Minimum of Months | 25894.11 | 0.00 | 0.00 | 97107.42 | 0.00 | 0.00 | 9983955.63 | 0.00 | 0.41 |
Maximum of Months | 0.325812E+10 | 0.282948E+10 | 0.00 | 5637858.30 | 0.191689E+09 | 0.364724E+09 | 0.227750E+10 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.572116E+10 | 0.00 | 0.00 | 220803.58 | 0.00 | 0.380013E+09 | 0.306569E+09 | 0.00 | 0.39 |
February | 0.400186E+10 | 0.00 | 0.00 | 1239666.38 | 0.00 | 0.130733E+09 | 0.107136E+10 | 0.00 | 0.47 |
March | 0.292444E+10 | 0.00 | 0.00 | 3081477.00 | 0.00 | 77632433.40 | 0.228451E+10 | 0.00 | 0.57 |
April | 0.484477E+09 | 0.272876E+09 | 0.00 | 5458480.49 | 7354087.32 | 0.00 | 0.203746E+10 | 0.00 | 0.57 |
May | 27338619.95 | 0.148160E+10 | 0.00 | 3050138.29 | 46528254.88 | 0.00 | 0.763897E+09 | 0.00 | 0.52 |
June | 0.00 | 0.335999E+10 | 0.00 | 855523.10 | 59068538.39 | 0.00 | 86914234.21 | 0.00 | 0.44 |
July | 0.00 | 0.514588E+10 | 0.00 | 316308.21 | 0.116634E+09 | 0.00 | 2740363.07 | 0.00 | 0.41 |
August | 50653.95 | 0.342018E+10 | 0.00 | 1397325.85 | 54079952.24 | 0.00 | 0.288202E+09 | 0.00 | 0.51 |
September | 22353462.84 | 0.246714E+10 | 0.00 | 2860061.69 | 30888186.26 | 0.00 | 0.427297E+09 | 0.00 | 0.53 |
October | 0.284499E+09 | 0.565229E+09 | 0.00 | 9091986.34 | 8006058.23 | 0.00 | 0.361796E+10 | 0.00 | 0.71 |
November | 0.288081E+10 | 0.00 | 0.00 | 4474418.14 | 0.00 | 0.108158E+09 | 0.339175E+10 | 0.00 | 0.57 |
December | 0.593119E+10 | 0.00 | 0.00 | 56508.45 | 0.00 | 0.775137E+09 | 99613929.81 | 0.00 | 0.37 |
Annual Sum or Average | 0.222782E+11 | 0.167129E+11 | 0.00 | 32102697.51 | 0.322559E+09 | 0.147167E+10 | 0.143783E+11 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 56508.45 | 0.00 | 0.00 | 2740363.07 | 0.00 | 0.37 |
Maximum of Months | 0.593119E+10 | 0.514588E+10 | 0.00 | 9091986.34 | 0.116634E+09 | 0.775137E+09 | 0.361796E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.278432E+10 | 0.00 | 0.00 | 88822.69 | 0.00 | 0.257284E+09 | 0.133888E+09 | 0.00 | 0.39 |
February | 0.197273E+10 | 0.00 | 0.00 | 576415.46 | 0.00 | 89518321.60 | 0.514440E+09 | 0.00 | 0.47 |
March | 0.148283E+10 | 0.00 | 0.00 | 1452180.22 | 0.00 | 50314377.36 | 0.108235E+10 | 0.00 | 0.57 |
April | 0.247937E+09 | 0.142618E+09 | 0.00 | 2655522.86 | 4031963.40 | 0.00 | 0.100960E+10 | 0.00 | 0.58 |
May | 16274797.21 | 0.750724E+09 | 0.00 | 1518157.03 | 24151658.40 | 0.00 | 0.384683E+09 | 0.00 | 0.53 |
June | 0.00 | 0.169124E+10 | 0.00 | 408634.45 | 30318129.52 | 0.00 | 45594111.66 | 0.00 | 0.44 |
July | 0.00 | 0.257748E+10 | 0.00 | 147430.17 | 65493586.14 | 0.00 | 1140340.76 | 0.00 | 0.41 |
August | 46414.93 | 0.171312E+10 | 0.00 | 709102.44 | 34707226.33 | 0.00 | 0.153064E+09 | 0.00 | 0.52 |
September | 11413531.38 | 0.123969E+10 | 0.00 | 1431028.53 | 16855083.70 | 0.00 | 0.218025E+09 | 0.00 | 0.53 |
October | 0.147407E+09 | 0.283926E+09 | 0.00 | 4619918.19 | 4396486.60 | 0.00 | 0.183102E+10 | 0.00 | 0.73 |
November | 0.144760E+10 | 0.00 | 0.00 | 2200700.41 | 0.00 | 60913540.72 | 0.168050E+10 | 0.00 | 0.58 |
December | 0.290210E+10 | 0.00 | 0.00 | 14270.86 | 0.00 | 0.445714E+09 | 32745992.98 | 0.00 | 0.37 |
Annual Sum or Average | 0.110127E+11 | 0.839880E+10 | 0.00 | 15822183.33 | 0.179954E+09 | 0.903745E+09 | 0.708705E+10 | 0.00 | 0.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 14270.86 | 0.00 | 0.00 | 1140340.76 | 0.00 | 0.37 |
Maximum of Months | 0.290210E+10 | 0.257748E+10 | 0.00 | 4619918.19 | 65493586.14 | 0.445714E+09 | 0.183102E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.273533E+10 | 0.00 | 0.00 | 71357.76 | 0.00 | 0.309982E+09 | 0.111652E+09 | 0.00 | 0.39 |
February | 0.196684E+10 | 0.00 | 0.00 | 528494.62 | 0.00 | 0.103703E+09 | 0.480979E+09 | 0.00 | 0.47 |
March | 0.150373E+10 | 0.00 | 0.00 | 1340483.72 | 0.00 | 59161116.13 | 0.101027E+10 | 0.00 | 0.56 |
April | 0.255288E+09 | 0.142484E+09 | 0.00 | 2555209.73 | 4098229.24 | 0.00 | 0.977912E+09 | 0.00 | 0.57 |
May | 21171959.65 | 0.748520E+09 | 0.00 | 1479728.86 | 24242070.54 | 0.00 | 0.373962E+09 | 0.00 | 0.52 |
June | 0.00 | 0.168784E+10 | 0.00 | 393950.83 | 30365804.79 | 0.00 | 45397642.09 | 0.00 | 0.44 |
July | 0.00 | 0.256630E+10 | 0.00 | 142818.13 | 63921174.76 | 0.00 | 1108752.41 | 0.00 | 0.41 |
August | 44919.29 | 0.170509E+10 | 0.00 | 696592.62 | 34009083.84 | 0.00 | 0.153016E+09 | 0.00 | 0.52 |
September | 11463971.40 | 0.123204E+10 | 0.00 | 1414348.79 | 16587856.36 | 0.00 | 0.216131E+09 | 0.00 | 0.53 |
October | 0.154078E+09 | 0.280992E+09 | 0.00 | 4523485.24 | 4386044.47 | 0.00 | 0.180191E+10 | 0.00 | 0.72 |
November | 0.148812E+10 | 0.00 | 0.00 | 2072047.00 | 0.00 | 64293921.86 | 0.158856E+10 | 0.00 | 0.57 |
December | 0.285675E+10 | 0.00 | 0.00 | 6829.86 | 0.00 | 0.486476E+09 | 26300307.17 | 0.00 | 0.37 |
Annual Sum or Average | 0.109928E+11 | 0.836327E+10 | 0.00 | 15225347.16 | 0.177610E+09 | 0.102362E+10 | 0.678720E+10 | 0.00 | 0.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 6829.86 | 0.00 | 0.00 | 1108752.41 | 0.00 | 0.37 |
Maximum of Months | 0.285675E+10 | 0.256630E+10 | 0.00 | 4523485.24 | 63921174.76 | 0.486476E+09 | 0.180191E+10 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.263669E+10 | 0.00 | 0.00 | 44364.56 | 0.00 | 0.407613E+09 | 76100317.03 | 0.00 | 0.38 |
February | 0.191891E+10 | 0.00 | 0.00 | 414007.74 | 0.00 | 0.169460E+09 | 0.404603E+09 | 0.00 | 0.46 |
March | 0.151084E+10 | 0.00 | 0.00 | 1079774.97 | 0.00 | 89723256.75 | 0.877796E+09 | 0.00 | 0.54 |
April | 0.293682E+09 | 0.142471E+09 | 0.00 | 2297916.76 | 4239150.86 | 0.00 | 0.880705E+09 | 0.00 | 0.56 |
May | 30107849.68 | 0.746286E+09 | 0.00 | 1354647.48 | 24441585.59 | 0.00 | 0.350438E+09 | 0.00 | 0.52 |
June | 0.00 | 0.168583E+10 | 0.00 | 366164.46 | 30427554.39 | 0.00 | 45276792.03 | 0.00 | 0.44 |
July | 0.00 | 0.255872E+10 | 0.00 | 126469.42 | 66618637.88 | 0.00 | 1039145.27 | 0.00 | 0.41 |
August | 45414.25 | 0.170130E+10 | 0.00 | 670331.83 | 35418699.25 | 0.00 | 0.154004E+09 | 0.00 | 0.52 |
September | 11963798.21 | 0.122883E+10 | 0.00 | 1378467.05 | 16756458.39 | 0.00 | 0.211627E+09 | 0.00 | 0.53 |
October | 0.179114E+09 | 0.277874E+09 | 0.00 | 4298759.18 | 4592342.45 | 0.00 | 0.172736E+10 | 0.00 | 0.71 |
November | 0.153923E+10 | 0.00 | 0.00 | 1800146.62 | 0.00 | 0.101786E+09 | 0.139800E+10 | 0.00 | 0.55 |
December | 0.270369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643649E+09 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.108243E+11 | 0.834131E+10 | 0.00 | 13831050.07 | 0.182494E+09 | 0.141223E+10 | 0.612695E+10 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.270369E+10 | 0.255872E+10 | 0.00 | 4298759.18 | 66618637.88 | 0.643649E+09 | 0.172736E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.199059E+10 | 0.00 | 0.00 | 17093.66 | 0.00 | 0.102198E+10 | 42124513.46 | 0.00 | 0.38 |
February | 0.166203E+10 | 0.00 | 0.00 | 289139.78 | 0.00 | 0.463723E+09 | 0.306466E+09 | 0.00 | 0.46 |
March | 0.135901E+10 | 0.00 | 0.00 | 797427.43 | 0.00 | 0.316837E+09 | 0.695685E+09 | 0.00 | 0.54 |
April | 0.345765E+09 | 0.146836E+09 | 0.00 | 2155753.98 | 4326097.90 | 3018353.31 | 0.798156E+09 | 0.00 | 0.57 |
May | 27958396.05 | 0.766878E+09 | 0.00 | 1295422.15 | 26193040.80 | 0.00 | 0.345667E+09 | 0.00 | 0.54 |
June | 1002279.42 | 0.170656E+10 | 0.00 | 337355.86 | 30518819.70 | 0.00 | 54498084.53 | 0.00 | 0.45 |
July | 0.00 | 0.262718E+10 | 0.00 | 163281.94 | 64219620.74 | 0.00 | 2864188.75 | 0.00 | 0.42 |
August | 452815.15 | 0.176497E+10 | 0.00 | 768784.66 | 27494977.58 | 0.00 | 0.175912E+09 | 0.00 | 0.54 |
September | 12845055.80 | 0.127793E+10 | 0.00 | 1492206.82 | 16413819.30 | 0.00 | 0.230363E+09 | 0.00 | 0.55 |
October | 0.240422E+09 | 0.290312E+09 | 0.00 | 4344211.42 | 4376553.09 | 0.00 | 0.168828E+10 | 0.00 | 0.75 |
November | 0.139290E+10 | 0.00 | 0.00 | 1608516.44 | 0.00 | 0.279218E+09 | 0.129944E+10 | 0.00 | 0.56 |
December | 0.211905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118488E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.915203E+10 | 0.858066E+10 | 0.00 | 13269194.15 | 0.173543E+09 | 0.326965E+10 | 0.563945E+10 | 0.00 | 0.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.211905E+10 | 0.262718E+10 | 0.00 | 4344211.42 | 64219620.74 | 0.118488E+10 | 0.168828E+10 | 0.00 | 0.75 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:34:43
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.179204E+12 | 0.177617E+11 | 0.00 | 0.444412E+11 | 0.247054E+10 |
February | 0.190524E+12 | 0.130524E+11 | 0.00 | 0.367690E+11 | 0.439668E+10 |
March | 0.294900E+12 | 0.117656E+11 | 0.00 | 0.379703E+11 | 0.970124E+10 |
April | 0.321846E+12 | 0.344443E+10 | 0.00 | 0.168329E+11 | 0.595258E+11 |
May | 0.348426E+12 | -0.311528E+10 | 0.00 | -0.374843E+10 | 0.115683E+12 |
June | 0.348396E+12 | -0.895832E+10 | 0.00 | -0.217518E+11 | 0.163314E+12 |
July | 0.344278E+12 | -0.133041E+11 | 0.00 | -0.357211E+11 | 0.190376E+12 |
August | 0.313876E+12 | -0.871235E+10 | 0.00 | -0.212928E+11 | 0.168907E+12 |
September | 0.283844E+12 | -0.596429E+10 | 0.00 | -0.122870E+11 | 0.144810E+12 |
October | 0.246764E+12 | 0.381937E+10 | 0.00 | 0.251143E+11 | 0.696185E+11 |
November | 0.185266E+12 | 0.137349E+11 | 0.00 | 0.462359E+11 | 0.775763E+10 |
December | 0.145886E+12 | 0.184954E+11 | 0.00 | 0.472247E+11 | 0.339168E+10 |
Annual Sum or Average | 0.320321E+13 | 0.420193E+11 | 0.00 | 0.159787E+12 | 0.939952E+12 |
Minimum of Months | 0.145886E+12 | -0.133041E+11 | 0.00 | -0.357211E+11 | 0.247054E+10 |
Maximum of Months | 0.348426E+12 | 0.184954E+11 | 0.00 | 0.472247E+11 | 0.190376E+12 |