Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:34
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2023-10-16 08:34:30
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1651.32 | 789.98 | 789.98 |
Net Site Energy | 1651.32 | 789.98 | 789.98 |
Total Source Energy | 5229.72 | 2501.88 | 2501.88 |
Net Source Energy | 5229.72 | 2501.88 | 2501.88 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 496.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 126.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1651.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 496.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 100.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 126.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 741.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 496.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 100.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 126.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 285.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 442.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 789.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 285.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 442.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 789.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1651.318 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1651.318 | 100.00 |
Total On-Site and Utility Electric Sources | 1651.318 | 100.00 |
Total Electricity End Uses | 1651.318 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 2.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3233.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:34 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 20.1123 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 23.1025 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 20.9200 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 20.9200 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 20.9200 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 13.4438 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 17.2687 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 17.2687 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 20.1123 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 23.1025 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 20.9200 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 20.9200 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 20.9200 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 13.4438 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 13.5625 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 13.5625 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 13.5625 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 13.5625 | 6.19 | 4.3000 | |
Total | 2090.32 | 17.2687 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 17.2687 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 17.2687 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-JUN-12:50 | - | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 81266.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 30804.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 12725.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5431.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 138287.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 81266.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 30804.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 12725.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5431.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2348.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 319.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 400.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 182.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5229.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1123.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 752.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 152.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 191.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2501.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1123.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 752.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 152.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 191.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2501.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.49 |
SMSTORE1 DIRECT AIR | 1.27 |
SMSTORE2 DIRECT AIR | 1.26 |
SMSTORE3 DIRECT AIR | 1.25 |
SMSTORE4 DIRECT AIR | 1.25 |
LGSTORE2 DIRECT AIR | 2.22 |
SMSTORE5 DIRECT AIR | 1.16 |
SMSTORE6 DIRECT AIR | 1.16 |
SMSTORE7 DIRECT AIR | 1.16 |
SMSTORE8 DIRECT AIR | 1.34 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.49 | 2.49 | 2.49 | 2.49 | 2.49 | 2.49 | 1.00 | 1.00 | 2.49 |
PSZ-AC_2:2 | 1.27 | 1.27 | 1.27 | 1.27 | 1.27 | 1.27 | 1.00 | 1.000000 | 1.27 |
PSZ-AC_3:3 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.00 | 0.993156 | 1.26 |
PSZ-AC_4:4 | 1.25 | 1.25 | 1.25 | 1.25 | 1.27 | 1.27 | 1.00 | 0.984445 | 1.27 |
PSZ-AC_5:5 | 1.25 | 1.25 | 1.25 | 1.25 | 1.26 | 1.26 | 1.00 | 0.992447 | 1.26 |
PSZ-AC_6:6 | 2.22 | 2.22 | 2.22 | 2.22 | 2.22 | 2.22 | 1.00 | 1.00 | 2.22 |
PSZ-AC_7:7 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.00 | 1.00 | 1.16 |
PSZ-AC_8:8 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.00 | 1.00 | 1.16 |
PSZ-AC_9:9 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.00 | 0.999969 | 1.16 |
PSZ-AC_10:10 | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.00 | 1.000000 | 1.34 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.49 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.27 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.26 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.27 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.26 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.22 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.16 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.16 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.16 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.34 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.49 | 2662.87 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.27 | 1406.44 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.26 | 1399.70 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.27 | 1402.51 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.26 | 1392.75 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.22 | 2374.56 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.16 | 1289.06 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.16 | 1283.56 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.16 | 1288.27 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.34 | 1486.05 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.49 | 2.49 | 2.49 | 1.64 | 61796.67 | 57354.63 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.27 | 1.27 | 1.27 | 0.838410 | 31545.02 | 29272.33 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.26 | 1.26 | 1.26 | 0.834391 | 31393.81 | 28935.24 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.27 | 1.27 | 1.27 | 0.836062 | 31456.69 | 28740.59 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.26 | 1.26 | 1.26 | 0.830246 | 31237.87 | 28772.27 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.22 | 2.22 | 2.22 | 1.46 | 55106.00 | 51198.76 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.16 | 1.16 | 1.16 | 0.768434 | 28912.21 | 26849.84 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.16 | 1.16 | 1.16 | 0.765157 | 28788.91 | 27177.85 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.16 | 1.16 | 1.16 | 0.767963 | 28894.47 | 26832.61 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.34 | 1.34 | 1.34 | 0.885864 | 33330.48 | 31515.77 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.49 | 1.24 | 1.66 | 61796.67 | 30898.33 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.27 | 0.635159 | 0.846880 | 31545.02 | 15772.51 | 0.701080 | 0.701080 |
PSZ-AC_3:3 COOLING COIL | 1.26 | 0.632114 | 0.842820 | 31393.81 | 15696.91 | 0.701080 | 0.701080 |
PSZ-AC_4:4 COOLING COIL | 1.27 | 0.633381 | 0.844507 | 31456.69 | 15728.34 | 0.701080 | 0.701080 |
PSZ-AC_5:5 COOLING COIL | 1.26 | 0.628975 | 0.838633 | 31237.87 | 15618.93 | 0.701080 | 0.701080 |
PSZ-AC_6:6 COOLING COIL | 2.22 | 1.11 | 1.48 | 55106.00 | 27553.00 | 0.701080 | 0.701080 |
PSZ-AC_7:7 COOLING COIL | 1.16 | 0.582147 | 0.776193 | 28912.21 | 14456.10 | 0.701080 | 0.701080 |
PSZ-AC_8:8 COOLING COIL | 1.16 | 0.579665 | 0.772887 | 28788.91 | 14394.45 | 0.701080 | 0.701080 |
PSZ-AC_9:9 COOLING COIL | 1.16 | 0.581790 | 0.775720 | 28894.47 | 14447.24 | 0.701080 | 0.701080 |
PSZ-AC_10:10 COOLING COIL | 1.34 | 0.671109 | 0.894813 | 33330.48 | 16665.24 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 57354.63 |
PSZ-AC_2:2 HEATING COIL | 29272.33 |
PSZ-AC_3:3 HEATING COIL | 28935.24 |
PSZ-AC_4:4 HEATING COIL | 28740.59 |
PSZ-AC_5:5 HEATING COIL | 28772.27 |
PSZ-AC_6:6 HEATING COIL | 51198.76 |
PSZ-AC_7:7 HEATING COIL | 26849.84 |
PSZ-AC_8:8 HEATING COIL | 27177.85 |
PSZ-AC_9:9 HEATING COIL | 26832.61 |
PSZ-AC_10:10 HEATING COIL | 31515.77 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 20.112 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.412 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 23.103 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 27.403 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 20.920 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.220 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 20.920 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.220 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 20.920 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.220 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 4694.002 | 13.474 | 83.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4694.002 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 2312.850 | 6.639 | 41.117 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2312.850 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2367.672 | 13.592 | 84.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2367.672 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1656.630 | 9.510 | 58.904 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1656.630 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1281.630 | 7.358 | 45.570 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1281.630 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1281.630 | 7.358 | 45.570 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1281.630 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1281.630 | 7.358 | 45.570 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1281.630 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 4683.651 | 13.444 | 83.264 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4683.651 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7383 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.27626373E-12 | 0.13670118E-14 | -0.80430638E-13 | 0.78416590E-16 |
23 | 6 | 0.25658824E-07 | 0.27941242E-09 | 0.59030768E-08 | -0.11909973E-12 |
24 | 5 | -0.17468948E-03 | 0.24402707E-05 | -0.90039107E-04 | 0.58437388E-08 |
25 | 4 | 0.27392503 | 0.12091412E-02 | 0.93138911E-01 | -0.31018751E-04 |
26 | 3 | -6.9050330 | 0.38055846E-01 | -2.2317352 | 0.27239655E-01 |
27 | 2 | 39.679098 | 0.13717309 | 14.824430 | -0.32006664 |
28 | 1 | -79.631803 | 0.62641324E-01 | -28.746304 | 1.0591428 |
29 | 0 | 46.824345 | 0.12749544E-02 | 16.300917 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 35 | 1 | VerySmooth | 3.235 | 3.235 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60218 | 0.60218 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43216E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 28230.72187 | 33876.86624 | 2.07379 | 2.48855 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 34.94500 | 1.71577E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 2164.47901 | 2597.37481 | 9.12039E-002 | 0.41148 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 14410.84025 | 17293.00830 | 1.05860 | 1.27032 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:40:00 | 35.05833 | 1.71579E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 1012.65728 | 1215.18873 | 4.28278E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 14597.47909 | 17516.97491 | 1.04631 | 1.25558 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:00:00 | 30.52500 | 1.71492E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 1090.20271 | 1308.24326 | 4.60894E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 14500.60477 | 17400.72572 | 1.03921 | 1.24706 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:00:00 | 30.52500 | 1.71492E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 1125.65867 | 1350.79041 | 4.75524E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 14515.77502 | 17418.93003 | 1.04037 | 1.24845 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:00:00 | 30.52500 | 1.71492E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 1275.86799 | 1531.04159 | 5.37747E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 25175.95568 | 30211.14681 | 1.84927 | 2.21912 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 34.98750 | 1.71577E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 2399.63090 | 2879.55708 | 0.10076 | 0.41148 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 13209.15608 | 15850.98729 | 0.97025 | 1.16429 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 34.91667 | 1.71576E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 1209.83701 | 1451.80441 | 5.10480E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 13152.82695 | 15783.39234 | 0.96611 | 1.15933 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 34.91667 | 1.71576E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 1204.57698 | 1445.49238 | 5.08308E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 13201.52426 | 15841.82911 | 0.96962 | 1.16354 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 34.84583 | 1.71575E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 1326.85503 | 1592.22603 | 5.58611E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 15229.20975 | 18275.05170 | 1.11852 | 1.34222 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 34.77500 | 1.71573E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 1434.21875 | 1721.06250 | 6.04117E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 38926.50 | 2.48855 | 2.48855 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 9903.44 | 0.41148 | 0.41148 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 19836.46 | 1.27032 | 1.27032 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 19745.83 | 1.26423 | 1.26423 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 19777.73 | 1.26676 | 1.26676 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 19659.92 | 1.25795 | 1.25795 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 35341.57 | 2.21912 | 2.21912 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 9903.44 | 0.41148 | 0.41148 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 18400.02 | 1.16429 | 1.16429 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 18333.03 | 1.15933 | 1.15933 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:30:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 18382.60 | 1.16358 | 1.16358 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 20702.54 | 1.34222 | 1.34222 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.48855 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.27032 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.25558 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.24706 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.24845 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.21912 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.16429 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.15933 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.16354 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.34222 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.48855 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.48855 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.48855 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.48855 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.48855 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.48855 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.27032 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.27032 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.27032 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.27032 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.27032 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.27032 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.25558 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.25558 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.25558 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.25558 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.26423 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.26423 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 0.99316 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.24706 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.24706 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.24706 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.24706 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.26676 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.26676 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 0.98444 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.24845 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.24845 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.24845 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.24845 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.25795 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.25795 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 0.99245 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.21912 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.21912 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.21912 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.21912 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.21912 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.21912 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.16429 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.16429 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.16429 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.16429 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.16429 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.16429 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.15933 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.15933 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.15933 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.15933 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.15933 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.15933 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.16354 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.16354 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.16354 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.16354 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.16358 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.16358 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.99997 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.34222 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.34222 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.34222 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.34222 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.34222 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.34222 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.48855 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.27032 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.26423 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.26676 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.25795 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.21912 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.16429 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.15933 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.16358 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.34222 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.48855 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.48855 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2662.86816 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.48855 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.48855 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.48855 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.64244 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.48855 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.24428 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.65903 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 61796.67000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 30898.33500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 61796.67000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 57354.62801 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 57354.62801 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.27032 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.27032 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1406.44373 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.27032 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.27032 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.27032 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.83841 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.27032 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63516 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.84688 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31545.02000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15772.51000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31545.02000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29272.32695 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 29272.32695 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.26423 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.26423 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1399.70188 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.26423 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.26423 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.26423 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.83439 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.26423 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63211 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.84282 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31393.81000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15696.90500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31393.81000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28935.23620 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 28935.23620 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.26676 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.26676 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1402.50561 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.26676 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.26676 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.26676 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.83606 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.26676 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63338 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.84451 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31456.69000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15728.34500 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31456.69000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28740.59064 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 28740.59064 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.25795 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.25795 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1392.74942 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.25795 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.25795 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.25795 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.83025 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.25795 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62897 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.83863 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31237.87000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15618.93500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31237.87000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28772.27384 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 28772.27384 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.21912 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.21912 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2374.56163 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.21912 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.21912 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.21912 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.46462 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.21912 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.10956 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.47941 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 55106.00000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 27553.00000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 55106.00000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 51198.75886 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 51198.75886 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.16429 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.16429 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1289.05897 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.16429 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.16429 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.16429 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76843 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.16429 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58215 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.77619 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28912.21000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14456.10500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28912.21000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26849.84270 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 26849.84270 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.15933 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.15933 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1283.56164 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.15933 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.15933 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.15933 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76516 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.15933 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57966 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.77289 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28788.91000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14394.45500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28788.91000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27177.84534 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 27177.84534 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.16358 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.16358 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1288.26792 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.16358 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.16358 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.16358 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76796 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.16358 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58179 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.77572 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28894.47000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14447.23500 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28894.47000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26832.61345 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 26832.61345 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.34222 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.34222 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1486.04868 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.34222 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.34222 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.34222 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.88586 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.34222 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67111 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.89481 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33330.48000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16665.24000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33330.48000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31515.77037 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 31515.77037 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 59833.4 | 11.77 | 11.77 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 30542.8 | 11.95 | 11.95 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 30396.4 | 11.95 | 11.95 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 30457.3 | 11.95 | 11.95 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 30245.5 | 11.95 | 11.95 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 53355.3 | 11.77 | 11.77 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 27993.7 | 11.95 | 11.95 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 27874.3 | 11.95 | 11.95 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 27976.5 | 11.95 | 11.95 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 32271.6 | 11.95 | 11.95 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.569_SHGC_0.25 | N/A | 3.235 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 3.1241917794E-002 | 0.1812042612 | Pass | Pass | 4.0927341797E-002 | 0.2150772298 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 3.2853343923E-002 | 0.2088839439 | Pass | Pass | 5.5427290473E-002 | 0.3668823047 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 4.4443994859E-002 | 0.2279892532 | Pass | Pass | 0.1670373433 | 1.1115999577 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 4.4467551976E-002 | 0.2307239290 | Pass | Pass | 0.1631651533 | 1.0911837709 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 4.3410278000E-002 | 0.2217472103 | Pass | Pass | 0.1736173059 | 1.1496903598 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.2717770781E-002 | 0.2130450010 | Pass | Pass | 0.1368238477 | 0.9166855689 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.1887594012E-002 | 0.2104325721 | Pass | Pass | 0.1971263636 | 1.3612216036 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.1704260882E-002 | 0.2090078623 | Pass | Pass | 0.1915141571 | 1.3128862113 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.1579407668E-002 | 0.2049217287 | Pass | Pass | 0.1955483381 | 1.3609992952 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 4.5882180246E-002 | 0.2158780952 | Pass | Pass | 0.3406285480 | 2.8333748120 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3402.16 | -618.0 | 0.00 | -1562.9 | 3835.63 | 5056.92 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 57.00 | 12 | |||
Feb | 0.00 | 0 | |||
Mar | 153.60 | 31 | |||
Apr | 87.00 | 59 | |||
May | 227.22 | 128 | |||
Jun | 144.58 | 109 | |||
Jul | 42.40 | 24 | |||
Aug | 164.90 | 163 | |||
Sep | 119.60 | 50 | |||
Oct | 365.70 | 188 | |||
Nov | 70.90 | 67 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.235 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.235 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 3.235 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.235 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.235 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.235 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.235 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.235 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.235 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.235 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.235 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 3.235 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.569_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 3.235 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 3.235 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 3.235 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 13.4735 | 348.39 | 4694.00 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 83.90 | 0.0000 | Y | 73.93 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 6.6387 | 348.39 | 2312.85 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 42.32 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 13.5922 | 174.19 | 2367.67 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 85.39 | 0.0000 | Y | 37.95 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 9.5103 | 174.19 | 1656.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 30.31 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 30.25 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 7.3575 | 174.19 | 1281.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.76 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 30.25 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 7.3575 | 174.19 | 1281.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.76 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 30.25 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 7.3575 | 174.19 | 1281.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.76 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 13.4438 | 348.39 | 4683.65 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 54.16 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 8.6344 | 4180.64 | 36097.17 | 496.92 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 458.42 | AstronomicalClock | - | 41.93 | 41.93 | 3.61 | |
EXTERIOR_LIGHTS_B | 7264.83 | AstronomicalClock | - | 83.83 | 71.26 | 97.18 | |
Exterior Lighting Total | 7723.25 | 100.79 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 61796.67 | 43324.41 | 18472.26 | 0.70 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31545.02 | 22115.58 | 9429.44 | 0.70 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31393.81 | 22009.57 | 9384.24 | 0.70 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31456.69 | 22053.66 | 9403.03 | 0.70 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31237.87 | 21900.25 | 9337.62 | 0.70 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 55106.00 | 38633.71 | 16472.29 | 0.70 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28912.21 | 20269.77 | 8642.44 | 0.70 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28788.91 | 20183.33 | 8605.58 | 0.70 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28894.47 | 20257.34 | 8637.13 | 0.70 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33330.48 | 23367.33 | 9963.15 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 59833.4 | 11.77 | 11.77 | ||||
PSZ-AC_2:2 COOLING COIL | 30542.8 | 11.95 | 11.95 | ||||
PSZ-AC_3:3 COOLING COIL | 30396.4 | 11.95 | 11.95 | ||||
PSZ-AC_4:4 COOLING COIL | 30457.3 | 11.95 | 11.95 | ||||
PSZ-AC_5:5 COOLING COIL | 30245.5 | 11.95 | 11.95 | ||||
PSZ-AC_6:6 COOLING COIL | 53355.3 | 11.77 | 11.77 | ||||
PSZ-AC_7:7 COOLING COIL | 27993.7 | 11.95 | 11.95 | ||||
PSZ-AC_8:8 COOLING COIL | 27874.3 | 11.95 | 11.95 | ||||
PSZ-AC_9:9 COOLING COIL | 27976.5 | 11.95 | 11.95 | ||||
PSZ-AC_10:10 COOLING COIL | 32271.6 | 11.95 | 11.95 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 57354.63 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 29272.33 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 28935.24 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 28740.59 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 28772.27 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 51198.76 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 26849.84 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 27177.85 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 26832.61 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 31515.77 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.49 | 2662.87 | 1070.05 | 1.00 | 1.29 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.27 | 1406.44 | 1107.16 | 1.00 | 1.35 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:40:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.26 | 1399.70 | 1107.16 | 1.00 | 1.35 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.27 | 1402.51 | 1107.16 | 1.00 | 1.35 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.26 | 1392.75 | 1107.16 | 1.00 | 1.35 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.22 | 2374.56 | 1070.05 | 1.00 | 1.30 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:10:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.16 | 1289.06 | 1107.16 | 1.00 | 1.37 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.16 | 1283.56 | 1107.16 | 1.00 | 1.37 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:30:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.16 | 1288.27 | 1107.16 | 1.00 | 1.37 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.34 | 1486.05 | 1107.16 | 1.00 | 1.34 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 28230.72 | 33876.87 | 97.24 | 2.074 | 2.489 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 23.89 | 23.88 | 0.01026 | 34.95 | 0.01716 | 0.411 | 0.00 |
SMSTORE1 | 14410.84 | 17293.01 | 99.27 | 1.059 | 1.270 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:40:00 | 23.89 | 23.88 | 0.01033 | 35.06 | 0.01716 | 0.206 | 0.00 |
SMSTORE2 | 14597.48 | 17516.97 | 100.56 | 1.046 | 1.256 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:00:00 | 23.89 | 23.89 | 0.00941 | 30.53 | 0.01715 | 0.206 | 0.00 |
SMSTORE3 | 14500.60 | 17400.73 | 99.89 | 1.039 | 1.247 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:00:00 | 23.89 | 23.89 | 0.00941 | 30.53 | 0.01715 | 0.206 | 0.00 |
SMSTORE4 | 14515.78 | 17418.93 | 100.00 | 1.040 | 1.248 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:00:00 | 23.89 | 23.89 | 0.00941 | 30.53 | 0.01715 | 0.206 | 0.00 |
LGSTORE2 | 25175.96 | 30211.15 | 86.72 | 1.849 | 2.219 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 23.89 | 23.88 | 0.01039 | 34.99 | 0.01716 | 0.411 | 0.00 |
SMSTORE5 | 13209.16 | 15850.99 | 91.00 | 0.970 | 1.164 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 23.89 | 23.88 | 0.01046 | 34.92 | 0.01716 | 0.206 | 0.00 |
SMSTORE6 | 13152.83 | 15783.39 | 90.61 | 0.966 | 1.159 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 23.89 | 23.88 | 0.01047 | 34.92 | 0.01716 | 0.206 | 0.00 |
SMSTORE7 | 13201.52 | 15841.83 | 90.94 | 0.970 | 1.164 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 23.89 | 23.88 | 0.01046 | 34.85 | 0.01716 | 0.206 | 0.00 |
SMSTORE8 | 15229.21 | 18275.05 | 104.91 | 1.119 | 1.342 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 23.89 | 23.88 | 0.01034 | 34.78 | 0.01716 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 2164.48 | 2597.37 | 7.46 | 0.091 | 0.411 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01195 | 20.10 | 0.01480 | 0.411 | 0.00 |
SMSTORE1 | 1012.66 | 1215.19 | 6.98 | 0.043 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01180 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE2 | 1090.20 | 1308.24 | 7.51 | 0.046 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.11 | 21.11 | 0.01257 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE3 | 1125.66 | 1350.79 | 7.75 | 0.048 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.11 | 21.11 | 0.01253 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE4 | 1275.87 | 1531.04 | 8.79 | 0.054 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.11 | 21.11 | 0.01234 | 20.10 | 0.01480 | 0.206 | 0.00 |
LGSTORE2 | 2399.63 | 2879.56 | 8.27 | 0.101 | 0.411 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01244 | 20.10 | 0.01480 | 0.411 | 0.00 |
SMSTORE5 | 1209.84 | 1451.80 | 8.33 | 0.051 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01255 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE6 | 1204.58 | 1445.49 | 8.30 | 0.051 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01256 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE7 | 1326.86 | 1592.23 | 9.14 | 0.056 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01240 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE8 | 1434.22 | 1721.06 | 9.88 | 0.060 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01278 | 20.10 | 0.01480 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.49 | 2.49 | 0.41 | 0.41 | 2.4886 | 2.4886 | 2.4886 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.27 | 1.27 | 0.21 | 0.21 | 1.2703 | 1.2703 | 1.2703 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.26 | 1.26 | 0.21 | 0.21 | 1.2642 | 1.2556 | 1.2642 | 0.9932 | 1.0000 |
PSZ-AC_4:4 | 1.27 | 1.27 | 0.21 | 0.21 | 1.2668 | 1.2471 | 1.2668 | 0.9844 | 1.0000 |
PSZ-AC_5:5 | 1.26 | 1.26 | 0.21 | 0.21 | 1.2579 | 1.2484 | 1.2579 | 0.9924 | 1.0000 |
PSZ-AC_6:6 | 2.22 | 2.22 | 0.41 | 0.41 | 2.2191 | 2.2191 | 2.2191 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.16 | 1.16 | 0.21 | 0.21 | 1.1643 | 1.1643 | 1.1643 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.16 | 1.16 | 0.21 | 0.21 | 1.1593 | 1.1593 | 1.1593 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.16 | 1.16 | 0.21 | 0.21 | 1.1636 | 1.1635 | 1.1636 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.34 | 1.34 | 0.21 | 0.21 | 1.3422 | 1.3422 | 1.3422 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 61796.670 | 43324.409 | 2.488550 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 30898.33 | 20827.44 | 1.659033 | 26.62 | 19.61 | 0.01140869 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 24.8023 | 23.88 | 0.01026727 | 55.4823 | 28180.59 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 57354.628 | 57354.628 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 57354.63 | 57354.63 | 2.488552 | 20.94 | 18.28 | 0.01206813 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 16.5349 | 21.11 | 0.01152727 | 73.5668 | 1219.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 31545.020 | 22115.583 | 1.270320 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:40:00 | 15772.51 | 10595.36 | 0.846880 | 26.61 | 19.63 | 0.01143711 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 24.2938 | 23.88 | 0.01033106 | 55.8218 | 14406.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 29272.327 | 29272.327 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 29272.33 | 29272.33 | 1.270318 | 20.95 | 18.34 | 0.01214237 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 16.1959 | 21.11 | 0.01162909 | 74.2050 | 567.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 31393.810 | 22009.572 | 1.264230 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 15696.91 | 10531.71 | 0.842820 | 26.62 | 19.64 | 0.01144994 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 24.4108 | 23.88 | 0.01033931 | 55.8656 | 14329.46 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 28935.236 | 28935.236 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 28935.24 | 28935.24 | 1.264229 | 20.95 | 19.07 | 0.01307656 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 16.2739 | 20.41 | 0.01274191 | 84.7651 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 31456.690 | 22053.656 | 1.266760 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 15728.34 | 10557.28 | 0.844507 | 26.62 | 19.63 | 0.01144547 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 24.3621 | 23.88 | 0.01033646 | 55.8504 | 14356.46 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 28740.591 | 28740.591 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:30:00 | 28740.59 | 28740.59 | 1.266761 | 20.95 | 19.05 | 0.01305009 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 16.2414 | 20.38 | 0.01271110 | 84.7215 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 31237.870 | 21900.246 | 1.257950 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 15618.93 | 10467.32 | 0.838633 | 26.63 | 19.65 | 0.01146211 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 24.5327 | 23.88 | 0.01034709 | 55.9069 | 14256.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 28772.274 | 28772.274 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 28772.27 | 28772.27 | 1.257949 | 20.95 | 18.94 | 0.01290828 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 16.3551 | 20.28 | 0.01253872 | 84.0783 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 55106.000 | 38633.714 | 2.219120 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 27553.00 | 18175.49 | 1.479413 | 26.85 | 19.86 | 0.01164978 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 27.8136 | 23.88 | 0.01039415 | 56.1556 | 25146.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 51198.759 | 51198.759 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:10:00 | 51198.76 | 51198.76 | 2.219118 | 20.92 | 18.95 | 0.01292154 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 18.5424 | 20.24 | 0.01249432 | 83.9936 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 28912.210 | 20269.772 | 1.164290 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 14456.10 | 9518.70 | 0.776193 | 26.78 | 19.84 | 0.01165256 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 26.5062 | 23.88 | 0.01046895 | 56.5543 | 13190.34 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 26849.843 | 26849.843 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 26849.84 | 26849.84 | 1.164295 | 20.93 | 19.01 | 0.01299761 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 17.6707 | 20.34 | 0.01261112 | 84.2685 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 28788.910 | 20183.329 | 1.159330 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 14394.45 | 9468.84 | 0.772887 | 26.79 | 19.85 | 0.01166337 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 26.6196 | 23.88 | 0.01047588 | 56.5911 | 13133.64 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 27177.845 | 27177.845 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:30:00 | 27177.85 | 27177.85 | 1.159329 | 20.62 | 18.88 | 0.01297147 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 17.7464 | 21.50 | 0.01257733 | 78.2543 | 641.89 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 28894.470 | 20257.335 | 1.163580 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 14447.24 | 9510.40 | 0.775720 | 26.78 | 19.84 | 0.01165542 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 26.5224 | 23.88 | 0.01047081 | 56.5642 | 13175.60 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 26832.613 | 26832.613 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 26832.61 | 26832.61 | 1.163580 | 20.93 | 18.91 | 0.01287776 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 17.6816 | 20.25 | 0.01246523 | 83.7472 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 33330.480 | 23367.333 | 1.342220 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 16665.24 | 11225.36 | 0.894813 | 26.45 | 19.53 | 0.01138187 | 12.80 | 12.09 | 0.00850000 | 34.78 | 0.01715734 | 25.72 | 22.9924 | 23.88 | 0.01033633 | 55.8504 | 15229.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 31515.770 | 31515.770 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 31515.77 | 31515.77 | 1.342218 | 20.59 | 18.97 | 0.01309321 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 15.3283 | 21.11 | 0.01278454 | 81.4241 | 1434.22 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 61796.670 | 43324.409 | 2.488550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.0482 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.488552 | 2.99520856 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | Sensible | 30898.33 | 20827.44 | 1.0000 | 1.99680419 | 1.659033 | 26.62 | 19.61 | 0.01140869 | 55848.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30898.33 | 35.20 | 0.01715815 | 25.83 | 0.41147883 | 24.8023 | 23.88 | 0.01026727 | 23.88 | 0.01026727 | 55.4823 | 28180.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 57354.628 | 57354.628 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.488552 | 2.99520856 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 57354.63 | 57354.63 | 1.0000 | 2.99520856 | 2.488552 | 20.94 | 18.28 | 0.01206813 | 51696.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 57354.63 | 20.10 | 0.01479830 | 20.10 | 0.41147883 | 16.5349 | 21.11 | 0.01152727 | 21.11 | 0.01152727 | 73.5668 | 1219.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31545.020 | 22115.583 | 1.270320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.1010 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.270318 | 1.52894843 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:40:00 | Sensible | 15772.51 | 10595.36 | 1.0000 | 1.01930052 | 0.846880 | 26.61 | 19.63 | 0.01143711 | 55909.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15772.51 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 24.2938 | 23.88 | 0.01033106 | 23.88 | 0.01033106 | 55.8218 | 14406.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29272.327 | 29272.327 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.270318 | 1.52894843 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 29272.33 | 29272.33 | 1.0000 | 1.52894843 | 1.270318 | 20.95 | 18.34 | 0.01214237 | 51888.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29272.33 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 16.1959 | 21.11 | 0.01162909 | 21.11 | 0.01162909 | 74.2050 | 567.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31393.810 | 22009.572 | 1.264230 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.1249 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.264229 | 1.52161935 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | Sensible | 15696.91 | 10531.71 | 1.0000 | 1.01441392 | 0.842820 | 26.62 | 19.64 | 0.01144994 | 55952.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15696.91 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 24.4108 | 23.88 | 0.01033931 | 23.88 | 0.01033931 | 55.8656 | 14329.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28935.236 | 28935.236 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.264229 | 1.52161935 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 28935.24 | 28935.24 | 1.0000 | 1.52161935 | 1.264229 | 20.95 | 19.07 | 0.01307656 | 54260.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28935.24 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 16.2739 | 21.11 | 0.01274191 | 20.41 | 0.01274191 | 84.7651 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31456.690 | 22053.656 | 1.266760 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.1166 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.266761 | 1.52466729 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | Sensible | 15728.34 | 10557.28 | 1.0000 | 1.01644399 | 0.844507 | 26.62 | 19.63 | 0.01144547 | 55937.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15728.34 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 24.3621 | 23.88 | 0.01033646 | 23.88 | 0.01033646 | 55.8504 | 14356.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28740.591 | 28740.591 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.266761 | 1.52466729 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:30:00 | Sensible | 28740.59 | 28740.59 | 1.0000 | 1.52466729 | 1.266761 | 20.95 | 19.05 | 0.01305009 | 54194.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28740.59 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 16.2414 | 21.11 | 0.01271110 | 20.38 | 0.01271110 | 84.7215 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31237.870 | 21900.246 | 1.257950 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.1475 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.257949 | 1.51406131 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | Sensible | 15618.93 | 10467.32 | 1.0000 | 1.00937487 | 0.838633 | 26.63 | 19.65 | 0.01146211 | 55993.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15618.93 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 24.5327 | 23.88 | 0.01034709 | 23.88 | 0.01034709 | 55.9069 | 14256.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28772.274 | 28772.274 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.257949 | 1.51406131 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 28772.27 | 28772.27 | 1.0000 | 1.51406131 | 1.257949 | 20.95 | 18.94 | 0.01290828 | 53832.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28772.27 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 16.3551 | 21.11 | 0.01253872 | 20.28 | 0.01253872 | 84.0783 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 55106.000 | 38633.714 | 2.219120 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.4964 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.219118 | 2.67091981 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | Sensible | 27553.00 | 18175.49 | 1.0000 | 1.78061446 | 1.479413 | 26.85 | 19.86 | 0.01164978 | 56695.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27553.00 | 35.20 | 0.01715815 | 25.83 | 0.41147883 | 27.8136 | 23.88 | 0.01039415 | 23.88 | 0.01039415 | 56.1556 | 25146.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 51198.759 | 51198.759 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.219118 | 2.67091981 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:10:00 | Sensible | 51198.76 | 51198.76 | 1.0000 | 2.67091981 | 2.219118 | 20.92 | 18.95 | 0.01292154 | 53843.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51198.76 | 20.10 | 0.01479830 | 20.10 | 0.41147883 | 18.5424 | 21.11 | 0.01249432 | 20.24 | 0.01249432 | 83.9936 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28912.210 | 20269.772 | 1.164290 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.5015 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.164295 | 1.40133917 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | Sensible | 14456.10 | 9518.70 | 1.0000 | 0.93422240 | 0.776193 | 26.78 | 19.84 | 0.01165256 | 56632.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14456.10 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 26.5062 | 23.88 | 0.01046895 | 23.88 | 0.01046895 | 56.5543 | 13190.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26849.843 | 26849.843 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.164295 | 1.40133917 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 26849.84 | 26849.84 | 1.0000 | 1.40133917 | 1.164295 | 20.93 | 19.01 | 0.01299761 | 54045.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26849.84 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 17.6707 | 21.11 | 0.01261112 | 20.34 | 0.01261112 | 84.2685 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28788.910 | 20183.329 | 1.159330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.5216 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.159329 | 1.39536301 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | Sensible | 14394.45 | 9468.84 | 1.0000 | 0.93024251 | 0.772887 | 26.79 | 19.85 | 0.01166337 | 56668.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14394.45 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 26.6196 | 23.88 | 0.01047588 | 23.88 | 0.01047588 | 56.5911 | 13133.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27177.845 | 27177.845 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.159329 | 1.39536301 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:30:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:30:00 | Sensible | 27177.85 | 27177.85 | 1.0000 | 1.39536301 | 1.159329 | 20.62 | 18.88 | 0.01297147 | 53654.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27177.85 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 17.7464 | 20.73 | 0.01257733 | 21.50 | 0.01257733 | 78.2543 | 641.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28894.470 | 20257.335 | 1.163580 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.5068 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.163580 | 1.40047921 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | Sensible | 14447.24 | 9510.40 | 1.0000 | 0.93365270 | 0.775720 | 26.78 | 19.84 | 0.01165542 | 56642.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14447.24 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 26.5224 | 23.88 | 0.01047081 | 23.88 | 0.01047081 | 56.5642 | 13175.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26832.613 | 26832.613 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.163580 | 1.40047921 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 26832.61 | 26832.61 | 1.0000 | 1.40047921 | 1.163580 | 20.93 | 18.91 | 0.01287776 | 53741.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26832.61 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 17.6816 | 21.11 | 0.01246523 | 20.25 | 0.01246523 | 83.7472 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33330.480 | 23367.333 | 1.342220 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.9983 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.342218 | 1.61548717 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | Sensible | 16665.24 | 11225.36 | 1.0000 | 1.07699284 | 0.894813 | 26.45 | 19.53 | 0.01138187 | 55602.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16665.24 | 34.78 | 0.01715734 | 25.72 | 0.20573941 | 22.9924 | 23.88 | 0.01033633 | 23.88 | 0.01033633 | 55.8504 | 15229.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31515.770 | 31515.770 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.342218 | 1.61548717 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | Sensible | 31515.77 | 31515.77 | 1.0000 | 1.61548717 | 1.342218 | 20.59 | 18.97 | 0.01309321 | 53931.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31515.77 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 15.3283 | 20.67 | 0.01278454 | 21.11 | 0.01278454 | 81.4241 | 1434.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 5840.00 | 2245.33 | 2245.33 |
SMSTORE1 | 5836.50 | 1803.00 | 1803.00 |
SMSTORE2 | 4395.00 | 2232.67 | 2232.67 |
SMSTORE3 | 4395.00 | 2213.17 | 2213.17 |
SMSTORE4 | 4395.00 | 2295.00 | 2295.00 |
LGSTORE2 | 4030.00 | 2502.00 | 2502.00 |
SMSTORE5 | 4030.00 | 2533.67 | 2533.67 |
SMSTORE6 | 4030.00 | 2549.33 | 2549.33 |
SMSTORE7 | 4030.00 | 2535.83 | 2535.83 |
SMSTORE8 | 4030.00 | 1921.00 | 1921.00 |
Facility | 5943.00 | 3233.67 | 3233.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 3.50 | 0.00 | 2.67 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 7.83 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 9.33 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 7.50 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 9.67 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 7.83 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 7.67 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 6.50 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 10.67 | 0.00 | 0.00 |
Facility | 0.00 | 20.83 | 0.00 | 2.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.850 | 0.335 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.711 | 0.374 | 0.000 | 0.000 |
SMSTORE2 | 7.10 | 28.12 | 902.60 | 0.851 | 0.492 | 0.000 | 0.000 |
SMSTORE3 | 7.10 | 28.12 | 902.60 | 0.851 | 0.492 | 0.000 | 0.000 |
SMSTORE4 | 7.10 | 28.12 | 902.60 | 0.851 | 0.492 | 0.000 | 0.000 |
LGSTORE2 | 24.82 | 56.25 | 1805.20 | 0.851 | 0.460 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.851 | 0.524 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.851 | 0.524 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.851 | 0.524 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.851 | 0.538 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.831 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.124 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.10 | 28.12 | 902.60 | 0.831 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.10 | 28.12 | 902.60 | 0.831 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.10 | 28.12 | 902.60 | 0.831 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.82 | 56.25 | 1805.20 | 0.833 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.833 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.833 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.833 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.833 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.82 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 121.13 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 8803647.52 | 0.00 | 8803647.52 | 3601967.37 | 12405614.90 | 12976396.34 | 2817.00 | 5943.00 | 0.00 | 103.00 |
SMSTORE1 | 3694508.86 | 0.00 | 3694508.86 | 1965043.96 | 5659552.81 | 6488198.17 | 4303.00 | 4457.00 | 0.00 | 103.00 |
SMSTORE2 | 3525611.90 | 0.00 | 3525611.90 | 1989485.12 | 5515097.02 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE3 | 3525609.86 | 0.00 | 3525609.86 | 1989485.12 | 5515094.99 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE4 | 3525613.51 | 0.00 | 3525613.51 | 1989485.12 | 5515098.63 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
LGSTORE2 | 6510586.69 | 0.00 | 6510586.69 | 3520231.44 | 10030818.13 | 12976396.34 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE5 | 3255275.53 | 0.00 | 3255275.53 | 1994519.00 | 5249794.52 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE6 | 3255275.93 | 0.00 | 3255275.93 | 1994519.00 | 5249794.93 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE7 | 3255275.49 | 0.00 | 3255275.49 | 1994519.00 | 5249794.48 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE8 | 3255251.52 | 0.00 | 3255251.52 | 2179417.57 | 5434669.09 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
Total Facility | 42606656.80 | 0.00 | 42606656.80 | 23218672.70 | 65825329.51 | 77858378.04 | 4365.00 | 6246.00 | 0.00 | 730.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4115 | 0.0000 | 0.4115 | 0.1619 | 0.5734 | 0.4115 | 0.00 | 5840.00 | 0.00 |
SMSTORE1 | 0.1721 | 0.0000 | 0.1721 | 0.0905 | 0.2626 | 0.2057 | 1486.00 | 4354.00 | 0.00 |
SMSTORE2 | 0.2057 | 0.0000 | 0.2057 | 0.1188 | 0.3245 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE3 | 0.2057 | 0.0000 | 0.2057 | 0.1188 | 0.3245 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE4 | 0.2057 | 0.0000 | 0.2057 | 0.1188 | 0.3245 | 0.2057 | 0.00 | 4395.00 | 0.00 |
LGSTORE2 | 0.4115 | 0.0000 | 0.4115 | 0.2221 | 0.6336 | 0.4115 | 0.00 | 4030.00 | 0.00 |
SMSTORE5 | 0.2057 | 0.0000 | 0.2057 | 0.1267 | 0.3324 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE6 | 0.2057 | 0.0000 | 0.2057 | 0.1267 | 0.3324 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE7 | 0.2057 | 0.0000 | 0.2057 | 0.1267 | 0.3324 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE8 | 0.2057 | 0.0000 | 0.2057 | 0.1299 | 0.3357 | 0.2057 | 0.00 | 4030.00 | 0.00 |
Total Facility | 2.4353 | 0.0000 | 2.4353 | 1.3408 | 3.7761 | 2.4689 | 1486.00 | 5943.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 12753120.48 | 0.00 | 12753120.48 | 12976396.34 | 2817.00 | 0.00 | 5943.00 | 103.00 |
PSZ-AC_2:2 | 5351926.82 | 0.00 | 5351926.82 | 6488198.17 | 4301.67 | 1.00 | 4457.33 | 103.00 |
PSZ-AC_3:3 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_4:4 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_5:5 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_6:6 | 9431257.70 | 0.00 | 9431257.70 | 12976396.34 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_7:7 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_8:8 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_9:9 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_10:10 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5961 | 0.0000 | 0.5961 | 0.4115 | 0.00 | 0.00 | 5840.00 |
PSZ-AC_2:2 | 0.2493 | 0.0000 | 0.2493 | 0.2057 | 1484.67 | 1.00 | 4354.33 |
PSZ-AC_3:3 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.5961 | 0.0000 | 0.5961 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.5961 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2493 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.5962 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 759 |
Defaulted Fields | 823 |
Fields with Defaults | 2681 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1651.32 | 3274.06 | 01-JAN-06:20 | 138287.20 | 16-JUN-12:50 |
Electricity:Building | 625.08 | 2063.06 | 01-JAN-00:10 | 38863.50 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 142.50 | 391.26 | 01-JAN-00:10 | 7378.51 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 625.08 | 2063.06 | 01-JAN-00:10 | 38863.50 | 01-JAN-11:10 |
InteriorLights:Electricity | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 116.25 | 317.63 | 01-JAN-00:10 | 6035.26 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 116.25 | 317.63 | 01-JAN-00:10 | 6035.26 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 81.39 | 223.36 | 01-JAN-00:10 | 4215.80 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 68.27 | 186.54 | 01-JAN-00:10 | 3544.17 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 68.27 | 186.54 | 01-JAN-00:10 | 3544.17 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 59.43 | 204.26 | 01-JAN-00:10 | 3853.00 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 59.43 | 204.26 | 01-JAN-00:10 | 3853.00 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 59.43 | 204.26 | 01-JAN-00:10 | 3853.00 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 73.33 | 274.94 | 01-JAN-00:10 | 5168.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 54.16 | 201.30 | 01-JAN-00:10 | 3825.14 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 54.16 | 201.30 | 01-JAN-00:10 | 3825.14 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1651.32 | 3274.06 | 01-JAN-06:20 | 138287.20 | 16-JUN-12:50 |
ElectricityPurchased:Plant | 1651.32 | 3274.06 | 01-JAN-06:20 | 138287.20 | 16-JUN-12:50 |
Cogeneration:ElectricityPurchased | 1651.32 | 3274.06 | 01-JAN-06:20 | 138287.20 | 16-JUN-12:50 |
General:Cogeneration:ElectricityPurchased | 1651.32 | 3274.06 | 01-JAN-06:20 | 138287.20 | 16-JUN-12:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1651.32 | 3274.06 | 01-JAN-06:20 | 138287.20 | 16-JUN-12:50 |
ElectricityNet:Plant | 1651.32 | 3274.06 | 01-JAN-06:20 | 138287.20 | 16-JUN-12:50 |
Cogeneration:ElectricityNet | 1651.32 | 3274.06 | 01-JAN-06:20 | 138287.20 | 16-JUN-12:50 |
General:Cogeneration:ElectricityNet | 1651.32 | 3274.06 | 01-JAN-06:20 | 138287.20 | 16-JUN-12:50 |
Electricity:HVAC | 867.96 | 0.00 | 01-JAN-00:10 | 95037.67 | 16-JUN-13:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 741.46 | 0.00 | 01-JAN-00:10 | 82170.95 | 16-JUN-13:00 |
General:Cooling:Electricity | 741.46 | 0.00 | 01-JAN-00:10 | 82170.95 | 16-JUN-13:00 |
Fans:Electricity | 126.50 | 0.00 | 01-JAN-00:10 | 12866.73 | 16-JUN-13:00 |
General:Fans:Electricity | 126.50 | 0.00 | 01-JAN-00:10 | 12866.73 | 16-JUN-13:00 |
ExteriorLights:Electricity | 100.79 | 0.00 | 01-JAN-06:20 | 7723.25 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 100.79 | 0.00 | 01-JAN-06:20 | 7723.25 | 01-JAN-06:10 |
Electricity:Plant | 57.50 | 1211.00 | 01-JAN-08:10 | 11769.61 | 02-JAN-13:20 |
WaterSystems:Electricity | 57.50 | 1211.00 | 01-JAN-08:10 | 11769.61 | 02-JAN-13:20 |
Water Heater:WaterSystems:Electricity | 57.50 | 1211.00 | 01-JAN-08:10 | 11769.61 | 02-JAN-13:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 4419.02 | 0.00 | 01-JAN-00:10 | 450446.18 | 16-JUN-13:00 |
EnergyTransfer:Building | 1324.85 | 0.00 | 01-JAN-00:10 | 134589.06 | 06-MAY-13:00 |
EnergyTransfer:Zone:LGSTORE1 | 271.40 | 0.00 | 01-JAN-00:10 | 22611.57 | 06-MAY-13:00 |
Heating:EnergyTransfer | 6.20 | 0.00 | 01-JAN-00:10 | 20964.53 | 29-MAY-16:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.31 | 0.00 | 01-JAN-00:10 | 2157.92 | 22-APR-07:20 |
General:Heating:EnergyTransfer | 6.20 | 0.00 | 01-JAN-00:10 | 20964.53 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 0.31 | 0.00 | 01-JAN-00:10 | 2157.92 | 22-APR-07:20 |
Cooling:EnergyTransfer | 1318.65 | 0.00 | 01-JAN-00:10 | 134589.06 | 06-MAY-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 271.09 | 0.00 | 01-JAN-00:10 | 22611.57 | 06-MAY-13:00 |
General:Cooling:EnergyTransfer | 1318.65 | 0.00 | 01-JAN-00:10 | 134589.06 | 06-MAY-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 271.09 | 0.00 | 01-JAN-00:10 | 22611.57 | 06-MAY-13:00 |
EnergyTransfer:Zone:SMSTORE1 | 139.84 | 0.00 | 01-JAN-00:10 | 11618.66 | 06-MAY-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.15 | 0.00 | 01-JAN-00:10 | 1029.78 | 04-NOV-07:20 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.15 | 0.00 | 01-JAN-00:10 | 1029.78 | 04-NOV-07:20 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 139.69 | 0.00 | 01-JAN-00:10 | 11618.66 | 06-MAY-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 139.69 | 0.00 | 01-JAN-00:10 | 11618.66 | 06-MAY-13:00 |
EnergyTransfer:Zone:SMSTORE2 | 109.53 | 0.00 | 01-JAN-00:10 | 11633.56 | 06-MAY-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 0.96 | 0.00 | 01-JAN-00:10 | 2317.61 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 0.96 | 0.00 | 01-JAN-00:10 | 2317.61 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 108.57 | 0.00 | 01-JAN-00:10 | 11633.56 | 06-MAY-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 108.57 | 0.00 | 01-JAN-00:10 | 11633.56 | 06-MAY-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 109.97 | 0.00 | 01-JAN-00:10 | 11670.06 | 06-MAY-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 0.96 | 0.00 | 01-JAN-00:10 | 2315.92 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 0.96 | 0.00 | 01-JAN-00:10 | 2315.92 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 109.02 | 0.00 | 01-JAN-00:10 | 11670.06 | 06-MAY-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 109.02 | 0.00 | 01-JAN-00:10 | 11670.06 | 06-MAY-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 107.96 | 0.00 | 01-JAN-00:10 | 11536.66 | 06-MAY-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 0.97 | 0.00 | 01-JAN-00:10 | 2322.41 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 0.97 | 0.00 | 01-JAN-00:10 | 2322.41 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 106.99 | 0.00 | 01-JAN-00:10 | 11536.66 | 06-MAY-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 106.99 | 0.00 | 01-JAN-00:10 | 11536.66 | 06-MAY-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 184.08 | 0.00 | 01-JAN-00:10 | 20378.01 | 06-MAY-13:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 0.98 | 0.00 | 01-JAN-00:10 | 4694.62 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 0.98 | 0.00 | 01-JAN-00:10 | 4694.62 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 183.11 | 0.00 | 01-JAN-00:10 | 20378.01 | 06-MAY-13:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 183.11 | 0.00 | 01-JAN-00:10 | 20378.01 | 06-MAY-13:10 |
EnergyTransfer:Zone:SMSTORE5 | 96.14 | 0.00 | 01-JAN-00:10 | 10786.54 | 06-MAY-13:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.48 | 0.00 | 01-JAN-00:10 | 2354.00 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 0.48 | 0.00 | 01-JAN-00:10 | 2354.00 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 95.66 | 0.00 | 01-JAN-00:10 | 10786.54 | 06-MAY-13:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 95.66 | 0.00 | 01-JAN-00:10 | 10786.54 | 06-MAY-13:10 |
EnergyTransfer:Zone:SMSTORE6 | 95.56 | 0.00 | 01-JAN-00:10 | 10746.37 | 06-MAY-13:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.48 | 0.00 | 01-JAN-00:10 | 2355.91 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 0.48 | 0.00 | 01-JAN-00:10 | 2355.91 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 95.08 | 0.00 | 01-JAN-00:10 | 10746.37 | 06-MAY-13:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 95.08 | 0.00 | 01-JAN-00:10 | 10746.37 | 06-MAY-13:10 |
EnergyTransfer:Zone:SMSTORE7 | 95.98 | 0.00 | 01-JAN-00:10 | 10848.63 | 06-MAY-13:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.48 | 0.00 | 01-JAN-00:10 | 2352.04 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 0.48 | 0.00 | 01-JAN-00:10 | 2352.04 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 95.49 | 0.00 | 01-JAN-00:10 | 10848.63 | 06-MAY-13:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 95.49 | 0.00 | 01-JAN-00:10 | 10848.63 | 06-MAY-13:10 |
EnergyTransfer:Zone:SMSTORE8 | 114.39 | 0.00 | 01-JAN-00:10 | 12963.34 | 06-MAY-13:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 0.42 | 0.00 | 01-JAN-00:10 | 2252.01 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 0.42 | 0.00 | 01-JAN-00:10 | 2252.01 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 113.97 | 0.00 | 01-JAN-00:10 | 12963.34 | 06-MAY-13:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 113.97 | 0.00 | 01-JAN-00:10 | 12963.34 | 06-MAY-13:10 |
EnergyTransfer:HVAC | 3094.17 | 0.00 | 01-JAN-00:10 | 322997.60 | 16-JUN-13:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 3094.17 | 0.00 | 01-JAN-00:10 | 322997.60 | 16-JUN-13:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.311 | -271.087 | 0.000 | 0.000 | 23.214 | 116.248 | 26.249 | 17.607 | 0.000 | 28.334 | 60.687 | 0.000 | -1.322 | 0.000 | -0.241 | -0.001 |
SMSTORE1 | 0.000 | 0.000 | 0.152 | -139.684 | 0.000 | 0.000 | 11.607 | 68.266 | 13.125 | 8.879 | 0.000 | 15.884 | 22.497 | 0.000 | -0.649 | 0.000 | -0.076 | -0.001 |
SMSTORE2 | 0.000 | 0.000 | 0.960 | -108.564 | 0.000 | 0.000 | 6.966 | 49.007 | 10.421 | 8.764 | 0.000 | 15.588 | 17.853 | 0.000 | -0.860 | 0.000 | -0.135 | -0.002 |
SMSTORE3 | 0.000 | 0.000 | 0.956 | -109.011 | 0.000 | 0.000 | 6.966 | 49.007 | 10.421 | 8.758 | 0.000 | 15.583 | 18.339 | 0.000 | -0.879 | 0.000 | -0.140 | -0.002 |
SMSTORE4 | 0.000 | 0.000 | 0.973 | -106.982 | 0.000 | 0.000 | 6.967 | 49.007 | 10.421 | 8.772 | 0.000 | 15.591 | 16.230 | 0.000 | -0.848 | 0.000 | -0.129 | -0.002 |
LGSTORE2 | 0.000 | 0.000 | 0.978 | -183.102 | 0.000 | 0.000 | 23.921 | 54.161 | 19.173 | 17.525 | 0.000 | 27.377 | 41.690 | 0.000 | -1.495 | 0.000 | -0.229 | -0.003 |
SMSTORE5 | 0.000 | 0.000 | 0.481 | -95.657 | 0.000 | 0.000 | 11.961 | 27.807 | 9.586 | 8.802 | 0.000 | 15.614 | 22.225 | 0.000 | -0.707 | 0.000 | -0.111 | -0.002 |
SMSTORE6 | 0.000 | 0.000 | 0.482 | -95.078 | 0.000 | 0.000 | 11.961 | 27.807 | 9.586 | 8.809 | 0.000 | 15.616 | 21.627 | 0.000 | -0.700 | 0.000 | -0.109 | -0.002 |
SMSTORE7 | 0.000 | 0.000 | 0.483 | -95.492 | 0.000 | 0.000 | 11.961 | 27.807 | 9.586 | 8.799 | 0.000 | 15.616 | 22.053 | 0.000 | -0.705 | 0.000 | -0.107 | -0.002 |
SMSTORE8 | 0.000 | 0.000 | 0.423 | -113.965 | 0.000 | 0.000 | 11.959 | 27.807 | 9.586 | 8.649 | 0.000 | 16.025 | 40.535 | 0.000 | -0.765 | 0.000 | -0.254 | -0.001 |
Total Facility | 0.000 | 0.000 | 6.199 | -1318.623 | 0.000 | 0.000 | 127.483 | 496.921 | 128.154 | 105.364 | 0.000 | 181.228 | 283.736 | 0.000 | -8.932 | 0.000 | -1.531 | -0.017 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 21-FEB-08:61 | 0.00 | 0.00 | 0.00 | -42745.35 | 0.00 | 0.00 | 162.54 | 317.63 | 74.62 | 1187.26 | 0.00 | 52.84 | 40950.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 21-FEB-08:61 | 0.00 | 0.00 | 0.00 | -24501.60 | 0.00 | 0.00 | 80.56 | 186.54 | 37.31 | 592.17 | 0.00 | 30.08 | 23574.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25-FEB-07:01 | 0.00 | 0.00 | 0.00 | -21036.79 | 0.00 | 0.00 | 0.00 | 167.44 | 36.82 | 177.16 | 0.00 | 0.00 | 20656.14 | 0.00 | -0.00 | 0.00 | -0.77 | 0.00 |
SMSTORE3 | 25-FEB-07:01 | 0.00 | 0.00 | 0.00 | -21125.23 | 0.00 | 0.00 | 0.00 | 167.44 | 36.82 | 176.00 | 0.00 | 0.00 | 20745.75 | 0.00 | -0.00 | 0.00 | -0.78 | 0.00 |
SMSTORE4 | 25-FEB-07:01 | 0.00 | 0.00 | 0.00 | -20830.75 | 0.00 | 0.00 | 0.00 | 167.44 | 36.82 | 178.58 | 0.00 | 0.00 | 20448.66 | 0.00 | -0.00 | 0.00 | -0.75 | 0.00 |
LGSTORE2 | 25-FEB-08:61 | 0.00 | 0.00 | 0.00 | -37490.32 | 0.00 | 0.00 | 0.00 | 201.30 | 73.64 | 967.08 | 0.00 | 99.44 | 36148.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 25-FEB-08:61 | 0.00 | 0.00 | 0.00 | -19568.92 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 485.77 | 0.00 | 61.07 | 18881.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 25-FEB-08:61 | 0.00 | 0.00 | 0.00 | -19454.73 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 486.49 | 0.00 | 61.88 | 18766.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 25-FEB-08:61 | 0.00 | 0.00 | 0.00 | -19467.24 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 486.82 | 0.00 | 64.41 | 18775.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 23-FEB-08:61 | 0.00 | 0.00 | 0.00 | -22327.33 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 499.51 | 0.00 | 0.00 | 21765.61 | 0.00 | -0.00 | 0.00 | -77.96 | 0.00 |
Total Facility | 23-FEB-08:61 | 0.00 | 0.00 | 0.00 | -195515.09 | 0.00 | 0.00 | 542.99 | 6142.12 | 1452.23 | 6113.73 | 0.00 | 0.00 | 181991.82 | 0.00 | 0.00 | 0.00 | -727.80 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 28-MAY-07:06 | 0.00 | 0.00 | 5528.15 | 0.00 | 0.00 | 0.00 | 157.31 | 317.63 | 74.62 | 621.58 | 0.00 | 580.84 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7280.13 |
SMSTORE1 | 28-MAY-07:05 | 0.00 | 0.00 | 2948.76 | 0.00 | 0.00 | 0.00 | 78.67 | 186.54 | 37.31 | 311.90 | 0.00 | 323.55 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3886.72 |
SMSTORE2 | 29-MAY-16:01 | 0.00 | 0.00 | 2801.56 | 0.00 | 0.00 | 0.00 | 98.50 | 1674.41 | 373.13 | 437.49 | 0.00 | 2598.35 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7983.44 |
SMSTORE3 | 29-MAY-16:01 | 0.00 | 0.00 | 2800.66 | 0.00 | 0.00 | 0.00 | 98.50 | 1674.41 | 373.13 | 437.27 | 0.00 | 2598.09 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7982.06 |
SMSTORE4 | 29-MAY-16:01 | 0.00 | 0.00 | 2803.83 | 0.00 | 0.00 | 0.00 | 98.50 | 1674.41 | 373.13 | 437.65 | 0.00 | 2599.02 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7986.54 |
LGSTORE2 | 29-MAY-16:01 | 0.00 | 0.00 | 5626.27 | 0.00 | 0.00 | 0.00 | 433.43 | 2013.22 | 746.25 | 872.98 | 0.00 | 4567.07 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14259.23 |
SMSTORE5 | 29-MAY-16:01 | 0.00 | 0.00 | 2817.53 | 0.00 | 0.00 | 0.00 | 216.71 | 1033.59 | 373.13 | 440.21 | 0.00 | 2604.38 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7485.55 |
SMSTORE6 | 29-MAY-16:01 | 0.00 | 0.00 | 2818.31 | 0.00 | 0.00 | 0.00 | 216.71 | 1033.59 | 373.13 | 440.45 | 0.00 | 2604.70 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7486.90 |
SMSTORE7 | 29-MAY-16:01 | 0.00 | 0.00 | 2816.19 | 0.00 | 0.00 | 0.00 | 216.71 | 1033.59 | 373.13 | 439.62 | 0.00 | 2604.04 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7483.27 |
SMSTORE8 | 29-MAY-16:01 | 0.00 | 0.00 | 2766.65 | 0.00 | 0.00 | 0.00 | 216.71 | 1033.59 | 373.13 | 428.80 | 0.00 | 2603.70 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7422.57 |
Total Facility | 29-MAY-16:01 | -31443.19 | 31443.19 | 25251.02 | -31443.19 | 0.00 | 0.00 | 5142.03 | 20750.25 | 5373.00 | 5262.42 | 0.00 | 30273.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -60609.22 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.4886 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.4886 | 0.1653 | 1.0000 | Not calculated | 0.4115 | 0.1653 | ||
PSZ-AC_2:2 | 1.2703 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2703 | 0.1620 | 1.0000 | Not calculated | 0.2057 | 0.1620 | ||
PSZ-AC_3:3 | 1.2556 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2642 | 0.1627 | 1.0000 | Not calculated | 0.2057 | 0.1627 | ||
PSZ-AC_4:4 | 1.2471 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2668 | 0.1624 | 1.0000 | Not calculated | 0.2057 | 0.1624 | ||
PSZ-AC_5:5 | 1.2484 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2579 | 0.1636 | 1.0000 | Not calculated | 0.2057 | 0.1636 | ||
PSZ-AC_6:6 | 2.2191 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.2191 | 0.1854 | 1.0000 | Not calculated | 0.4115 | 0.1854 | ||
PSZ-AC_7:7 | 1.1643 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1643 | 0.1767 | 1.0000 | Not calculated | 0.2057 | 0.1767 | ||
PSZ-AC_8:8 | 1.1593 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1593 | 0.1775 | 1.0000 | Not calculated | 0.2057 | 0.1775 | ||
PSZ-AC_9:9 | 1.1635 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1636 | 0.1768 | 1.0000 | Not calculated | 0.2057 | 0.1768 | ||
PSZ-AC_10:10 | 1.3422 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3422 | 0.1533 | 1.0000 | Not calculated | 0.2057 | 0.1533 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.4886 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.4886 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1653 | ||
PSZ-AC_2:2 | 1.2703 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2703 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1620 | ||
PSZ-AC_3:3 | 1.2556 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2556 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1639 | ||
PSZ-AC_4:4 | 1.2471 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2471 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1650 | ||
PSZ-AC_5:5 | 1.2484 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2484 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1648 | ||
PSZ-AC_6:6 | 2.2191 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.2191 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1854 | ||
PSZ-AC_7:7 | 1.1643 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1643 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1767 | ||
PSZ-AC_8:8 | 1.1593 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1593 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1775 | ||
PSZ-AC_9:9 | 1.1635 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1635 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1768 | ||
PSZ-AC_10:10 | 1.3422 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3422 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1533 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4886 | 2.4886 | 2.4886 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2703 | 1.2703 | 1.2703 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2556 | 1.2556 | 1.2556 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2471 | 1.2471 | 1.2471 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2484 | 1.2484 | 1.2484 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2191 | 2.2191 | 2.2191 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1643 | 1.1643 | 1.1643 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1593 | 1.1593 | 1.1593 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1635 | 1.1635 | 1.1635 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3422 | 1.3422 | 1.3422 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.4886 | 2.4886 | 2.4886 | 2.4886 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.2703 | 1.2703 | 1.2703 | 1.2703 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.2556 | 1.2642 | 1.2556 | 1.2556 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.2471 | 1.2668 | 1.2471 | 1.2471 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.2484 | 1.2579 | 1.2484 | 1.2484 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.2191 | 2.2191 | 2.2191 | 2.2191 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.1643 | 1.1643 | 1.1643 | 1.1643 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.1593 | 1.1593 | 1.1593 | 1.1593 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.1635 | 1.1636 | 1.1635 | 1.1635 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.3422 | 1.3422 | 1.3422 | 1.3422 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4886 | 2.4886 | 2.4886 | No | 0.4115 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2703 | 1.2703 | 1.2703 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2556 | 1.2556 | 1.2556 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2471 | 1.2471 | 1.2471 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2484 | 1.2484 | 1.2484 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2191 | 2.2191 | 2.2191 | No | 0.4115 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1643 | 1.1643 | 1.1643 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1593 | 1.1593 | 1.1593 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1635 | 1.1635 | 1.1635 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3422 | 1.3422 | 1.3422 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.4886 | 2.4886 | 2.4886 | 2.4886 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.2703 | 1.2703 | 1.2703 | 1.2703 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.2556 | 1.2556 | 1.2556 | 1.2556 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.2471 | 1.2471 | 1.2471 | 1.2471 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.2484 | 1.2484 | 1.2484 | 1.2484 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.2191 | 2.2191 | 2.2191 | 2.2191 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.1643 | 1.1643 | 1.1643 | 1.1643 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.1593 | 1.1593 | 1.1593 | 1.1593 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.1635 | 1.1635 | 1.1635 | 1.1635 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.3422 | 1.3422 | 1.3422 | 1.3422 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 2090.32 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 2.67 |
Number of hours not met | 2.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 741.46 | 82170.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 496.92 | 30804.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 100.79 | 7723.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 126.50 | 12866.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 57.50 | 11769.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 1651.32 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1651.32 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 237.73 |
Space Heating | 0.00 |
Space Cooling | 354.71 |
Fans (All) | 60.51 |
Service Water Heating | 27.51 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 789.98 |
Subtotal | 789.98 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 30.09 |
Space Heating | 0.00 |
Space Cooling | 44.90 |
Fans (All) | 7.66 |
Service Water Heating | 3.48 |
Receptacle Equipment | 7.76 |
Miscellaneous | 6.10 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8287.33 | 472.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8665.00 | 95.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 5337.67 | 3416.17 | 6.17 | 0.00 | 0.00 |
SMSTORE3 | 5226.67 | 3526.17 | 7.17 | 0.00 | 0.00 |
SMSTORE4 | 5578.17 | 3175.33 | 6.50 | 0.00 | 0.00 |
LGSTORE2 | 7063.67 | 1690.33 | 6.00 | 0.00 | 0.00 |
SMSTORE5 | 7243.17 | 1511.50 | 5.33 | 0.00 | 0.00 |
SMSTORE6 | 7278.67 | 1476.33 | 5.00 | 0.00 | 0.00 |
SMSTORE7 | 7311.67 | 1443.00 | 5.33 | 0.00 | 0.00 |
SMSTORE8 | 6718.17 | 1989.50 | 52.33 | 0.00 | 0.00 |
Min | 5226.67 | 95.00 | 0.00 | 0.00 | 0.00 |
Max | 8665.00 | 3526.17 | 52.33 | 0.00 | 0.00 |
Average | 6871.02 | 1879.60 | 9.38 | 0.00 | 0.00 |
Sum | 68710.17 | 18796.00 | 93.83 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25282.17 | 191.00 | 1.83 | 0.00 | 0.00 |
SMSTORE3 | 25282.17 | 191.00 | 1.83 | 0.00 | 0.00 |
SMSTORE4 | 25288.00 | 185.17 | 1.83 | 0.00 | 0.00 |
LGSTORE2 | 92774.00 | 426.00 | 11.00 | 0.00 | 0.00 |
SMSTORE5 | 45692.50 | 214.00 | 5.50 | 0.00 | 0.00 |
SMSTORE6 | 45693.50 | 213.00 | 5.50 | 0.00 | 0.00 |
SMSTORE7 | 45694.50 | 212.00 | 5.50 | 0.00 | 0.00 |
SMSTORE8 | 45672.50 | 232.50 | 7.00 | 0.00 | 0.00 |
Min | 25282.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 92774.00 | 426.00 | 11.00 | 0.00 | 0.00 |
Average | 48419.73 | 186.47 | 4.00 | 0.00 | 0.00 |
Sum | 484197.33 | 1864.67 | 40.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 3608.00 | 5152.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 5728.83 | 3031.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 2114.17 | 6645.67 | 0.17 | 0.00 | 0.00 |
SMSTORE3 | 2132.50 | 6626.83 | 0.67 | 0.00 | 0.00 |
SMSTORE4 | 2052.67 | 6707.00 | 0.33 | 0.00 | 0.00 |
LGSTORE2 | 1562.67 | 7197.17 | 0.17 | 0.00 | 0.00 |
SMSTORE5 | 1538.67 | 7220.50 | 0.83 | 0.00 | 0.00 |
SMSTORE6 | 1518.50 | 7240.67 | 0.83 | 0.00 | 0.00 |
SMSTORE7 | 1533.67 | 7225.83 | 0.50 | 0.00 | 0.00 |
SMSTORE8 | 2147.33 | 6559.33 | 53.33 | 0.00 | 0.00 |
Min | 1518.50 | 3031.17 | 0.00 | 0.00 | 0.00 |
Max | 5728.83 | 7240.67 | 53.33 | 0.00 | 0.00 |
Average | 2393.70 | 6360.62 | 5.68 | 0.00 | 0.00 |
Sum | 23937.00 | 63606.17 | 56.83 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 56777.17 | 32263.83 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 28061.83 | 15715.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 12487.67 | 12987.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 12537.17 | 12937.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 12131.17 | 13343.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 34686.67 | 58524.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 16508.67 | 29402.83 | 0.50 | 0.00 | 0.00 |
SMSTORE6 | 16313.67 | 29597.83 | 0.50 | 0.00 | 0.00 |
SMSTORE7 | 16490.67 | 29420.83 | 0.50 | 0.00 | 0.00 |
SMSTORE8 | 23277.17 | 22634.33 | 0.50 | 0.00 | 0.00 |
Min | 12131.17 | 12937.83 | 0.00 | 0.00 | 0.00 |
Max | 56777.17 | 58524.33 | 0.50 | 0.00 | 0.00 |
Average | 22927.18 | 25682.82 | 0.20 | 0.00 | 0.00 |
Sum | 229271.83 | 256828.17 | 2.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:30
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Environment
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Environment
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225757E+11 | 42335.91 | 24-JAN-08:62 | 19.83 | 17.92 | 0.140997E+10 | 1686.14 | 08-JAN-13:00 | 19.83 | 17.92 |
February | 0.213907E+11 | 42752.29 | 21-FEB-08:61 | 26.33 | 21.23 | 0.127288E+10 | 1686.11 | 03-FEB-13:20 | 26.33 | 21.23 |
March | 0.241042E+11 | 39167.00 | 04-MAR-08:62 | 26.50 | 20.59 | 0.139786E+10 | 1686.11 | 05-MAR-13:30 | 31.70 | 23.89 |
April | 0.235945E+11 | 35539.11 | 27-APR-07:01 | 27.08 | 24.31 | 0.136197E+10 | 1686.10 | 23-APR-12:09 | 27.08 | 24.31 |
May | 0.242788E+11 | 33073.30 | 11-MAY-07:01 | 26.50 | 26.26 | 0.140199E+10 | 1686.01 | 21-MAY-12:30 | 27.70 | 25.64 |
June | 0.242696E+11 | 34868.57 | 25-JUN-07:01 | 25.75 | 24.65 | 0.135491E+10 | 1686.05 | 30-JUN-12:20 | 28.47 | 26.13 |
July | 0.226580E+11 | 39056.24 | 09-JUL-07:01 | 26.50 | 23.81 | 0.141304E+10 | 1686.09 | 22-JUL-12:39 | 30.83 | 24.41 |
August | 0.220566E+11 | 35030.86 | 24-AUG-07:01 | 25.75 | 25.32 | 0.139434E+10 | 1686.05 | 06-AUG-16:49 | 25.75 | 25.32 |
September | 0.218431E+11 | 35768.57 | 10-SEP-07:01 | 26.50 | 25.49 | 0.136546E+10 | 1686.06 | 16-SEP-12:20 | 27.47 | 25.47 |
October | 0.212930E+11 | 35670.51 | 08-OCT-07:01 | 25.75 | 24.25 | 0.141000E+10 | 1686.05 | 29-OCT-17:00 | 25.50 | 24.34 |
November | 0.210763E+11 | 39991.97 | 25-NOV-08:62 | 22.25 | 19.45 | 0.136349E+10 | 1686.07 | 05-NOV-16:10 | 22.25 | 19.45 |
December | 0.219504E+11 | 40429.72 | 27-DEC-08:62 | 23.50 | 19.75 | 0.141702E+10 | 1686.08 | 02-DEC-13:00 | 23.50 | 19.75 |
Annual Sum or Average | 0.271091E+12 | 0.165629E+11 | ||||||||
Minimum of Months | 0.210763E+11 | 33073.30 | 19.83 | 17.92 | 0.127288E+10 | 1686.01 | 19.83 | 17.92 | ||
Maximum of Months | 0.242788E+11 | 42752.29 | 27.08 | 26.26 | 0.141702E+10 | 1686.14 | 31.70 | 26.13 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117296E+11 | 23910.88 | 16-JAN-08:61 | 22.05 | 20.01 | 0.704976E+09 | 843.04 | 29-JAN-13:39 | 31.50 | 23.30 |
February | 0.110064E+11 | 24502.03 | 21-FEB-08:61 | 26.33 | 21.23 | 0.636430E+09 | 843.01 | 04-FEB-13:20 | 26.33 | 21.23 |
March | 0.122747E+11 | 22723.95 | 03-MAR-08:62 | 26.17 | 20.16 | 0.698915E+09 | 842.99 | 05-MAR-13:09 | 31.50 | 23.79 |
April | 0.120023E+11 | 20968.38 | 23-APR-07:01 | 25.42 | 24.10 | 0.680967E+09 | 842.99 | 23-APR-17:19 | 31.50 | 24.87 |
May | 0.124617E+11 | 20604.14 | 12-MAY-07:02 | 25.75 | 25.62 | 0.700974E+09 | 842.99 | 07-MAY-17:19 | 25.75 | 25.62 |
June | 0.123824E+11 | 21350.40 | 25-JUN-07:01 | 25.75 | 24.65 | 0.677434E+09 | 843.00 | 11-JUN-17:40 | 25.75 | 24.65 |
July | 0.116599E+11 | 22722.70 | 08-JUL-07:01 | 25.08 | 22.66 | 0.706505E+09 | 843.02 | 09-JUL-12:09 | 30.08 | 24.85 |
August | 0.113813E+11 | 21242.23 | 24-AUG-07:01 | 25.75 | 25.32 | 0.697153E+09 | 843.00 | 13-AUG-17:00 | 25.75 | 25.32 |
September | 0.112449E+11 | 21294.88 | 18-SEP-07:01 | 23.75 | 23.65 | 0.682713E+09 | 843.00 | 16-SEP-12:09 | 23.75 | 23.65 |
October | 0.111222E+11 | 21660.08 | 09-OCT-07:01 | 25.50 | 24.67 | 0.704984E+09 | 843.00 | 15-OCT-17:30 | 28.25 | 25.80 |
November | 0.109789E+11 | 23318.49 | 25-NOV-08:62 | 22.25 | 19.45 | 0.681735E+09 | 843.00 | 05-NOV-16:10 | 22.25 | 19.45 |
December | 0.114423E+11 | 23359.96 | 27-DEC-08:62 | 23.50 | 19.75 | 0.708501E+09 | 843.03 | 02-DEC-13:00 | 23.50 | 19.75 |
Annual Sum or Average | 0.139687E+12 | 0.828129E+10 | ||||||||
Minimum of Months | 0.109789E+11 | 20604.14 | 22.05 | 19.45 | 0.636430E+09 | 842.99 | 22.25 | 19.45 | ||
Maximum of Months | 0.124617E+11 | 24502.03 | 26.33 | 25.62 | 0.708501E+09 | 843.04 | 31.50 | 25.80 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.909351E+10 | 19849.46 | 24-JAN-07:02 | 19.50 | 17.57 | 0.421004E+09 | 843.01 | 14-JAN-13:50 | 19.50 | 17.57 |
February | 0.860736E+10 | 21043.08 | 25-FEB-07:01 | 22.83 | 19.10 | 0.382484E+09 | 843.03 | 04-FEB-13:20 | 22.83 | 19.10 |
March | 0.971119E+10 | 19278.40 | 04-MAR-07:02 | 24.83 | 20.47 | 0.432217E+09 | 842.98 | 04-MAR-13:50 | 33.05 | 21.97 |
April | 0.934638E+10 | 17513.93 | 27-APR-06:01 | 26.15 | 23.95 | 0.411549E+09 | 842.90 | 08-APR-12:09 | 26.15 | 23.95 |
May | 0.979638E+10 | 15675.51 | 11-MAY-06:01 | 24.37 | 24.37 | 0.426773E+09 | 842.90 | 27-MAY-12:09 | 33.22 | 26.33 |
June | 0.979714E+10 | 15810.66 | 27-JUN-06:01 | 23.42 | 23.24 | 0.417637E+09 | 842.90 | 03-JUN-12:00 | 23.42 | 23.24 |
July | 0.889408E+10 | 17451.28 | 14-JUL-06:01 | 24.23 | 23.40 | 0.420561E+09 | 843.01 | 08-JUL-12:20 | 24.23 | 23.40 |
August | 0.888163E+10 | 16091.37 | 24-AUG-06:01 | 24.25 | 24.17 | 0.432069E+09 | 842.92 | 19-AUG-12:09 | 24.25 | 24.17 |
September | 0.865155E+10 | 15752.79 | 13-SEP-06:01 | 25.18 | 24.36 | 0.411349E+09 | 842.97 | 16-SEP-12:00 | 24.40 | 24.15 |
October | 0.851718E+10 | 16048.27 | 11-OCT-06:01 | 24.10 | 23.71 | 0.420910E+09 | 842.90 | 14-OCT-12:09 | 30.33 | 26.72 |
November | 0.849778E+10 | 19000.26 | 25-NOV-07:02 | 21.17 | 18.84 | 0.406622E+09 | 843.00 | 25-NOV-13:39 | 26.33 | 21.82 |
December | 0.877386E+10 | 20641.32 | 21-DEC-07:02 | 18.83 | 17.79 | 0.420345E+09 | 843.03 | 02-DEC-13:00 | 18.83 | 17.79 |
Annual Sum or Average | 0.108568E+12 | 0.500352E+10 | ||||||||
Minimum of Months | 0.849778E+10 | 15675.51 | 18.83 | 17.57 | 0.382484E+09 | 842.90 | 18.83 | 17.57 | ||
Maximum of Months | 0.979714E+10 | 21043.08 | 26.15 | 24.37 | 0.432217E+09 | 843.03 | 33.22 | 26.72 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.912649E+10 | 19926.40 | 24-JAN-07:02 | 19.50 | 17.57 | 0.421004E+09 | 843.01 | 14-JAN-13:50 | 19.50 | 17.57 |
February | 0.864088E+10 | 21131.55 | 25-FEB-07:01 | 22.83 | 19.10 | 0.382484E+09 | 843.02 | 04-FEB-13:20 | 22.83 | 19.10 |
March | 0.974817E+10 | 19334.13 | 04-MAR-07:02 | 24.83 | 20.47 | 0.432217E+09 | 842.98 | 04-MAR-13:50 | 33.05 | 21.97 |
April | 0.939062E+10 | 17592.26 | 27-APR-06:01 | 26.15 | 23.95 | 0.411551E+09 | 842.90 | 08-APR-12:09 | 26.15 | 23.95 |
May | 0.985380E+10 | 15771.09 | 09-MAY-06:01 | 24.03 | 24.01 | 0.426775E+09 | 842.90 | 27-MAY-12:09 | 33.22 | 26.33 |
June | 0.985132E+10 | 15890.48 | 27-JUN-06:01 | 23.42 | 23.24 | 0.417639E+09 | 842.90 | 03-JUN-12:00 | 23.42 | 23.24 |
July | 0.894240E+10 | 17534.64 | 14-JUL-06:01 | 24.23 | 23.40 | 0.420563E+09 | 843.01 | 08-JUL-12:20 | 24.23 | 23.40 |
August | 0.891153E+10 | 16139.70 | 24-AUG-06:01 | 24.25 | 24.17 | 0.432069E+09 | 842.92 | 19-AUG-12:09 | 24.25 | 24.17 |
September | 0.868812E+10 | 15859.81 | 06-SEP-06:01 | 25.30 | 24.45 | 0.411350E+09 | 842.98 | 16-SEP-12:00 | 24.40 | 24.15 |
October | 0.854891E+10 | 16132.37 | 11-OCT-06:01 | 24.10 | 23.71 | 0.420910E+09 | 842.90 | 14-OCT-12:09 | 30.33 | 26.72 |
November | 0.851865E+10 | 19080.64 | 25-NOV-07:02 | 21.17 | 18.84 | 0.406620E+09 | 843.00 | 25-NOV-13:39 | 26.33 | 21.82 |
December | 0.879440E+10 | 20679.01 | 21-DEC-07:02 | 18.83 | 17.79 | 0.420343E+09 | 843.03 | 02-DEC-13:00 | 18.83 | 17.79 |
Annual Sum or Average | 0.109015E+12 | 0.500353E+10 | ||||||||
Minimum of Months | 0.851865E+10 | 15771.09 | 18.83 | 17.57 | 0.382484E+09 | 842.90 | 18.83 | 17.57 | ||
Maximum of Months | 0.985380E+10 | 21131.55 | 26.15 | 24.45 | 0.432217E+09 | 843.03 | 33.22 | 26.72 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.895586E+10 | 19660.89 | 24-JAN-07:02 | 19.50 | 17.57 | 0.420970E+09 | 843.01 | 14-JAN-13:50 | 19.50 | 17.57 |
February | 0.848769E+10 | 20837.02 | 25-FEB-07:01 | 22.83 | 19.10 | 0.382454E+09 | 843.02 | 04-FEB-13:20 | 22.83 | 19.10 |
March | 0.957096E+10 | 19048.38 | 04-MAR-07:02 | 24.83 | 20.47 | 0.432183E+09 | 842.98 | 04-MAR-13:50 | 33.05 | 21.97 |
April | 0.922049E+10 | 17276.48 | 27-APR-06:01 | 26.15 | 23.95 | 0.411519E+09 | 842.90 | 08-APR-12:09 | 26.15 | 23.95 |
May | 0.968940E+10 | 15518.85 | 09-MAY-06:01 | 24.03 | 24.01 | 0.426744E+09 | 842.90 | 27-MAY-12:09 | 33.22 | 26.33 |
June | 0.968877E+10 | 15635.31 | 27-JUN-06:01 | 23.42 | 23.24 | 0.417608E+09 | 842.90 | 03-JUN-12:00 | 23.42 | 23.24 |
July | 0.877559E+10 | 17247.81 | 14-JUL-06:01 | 24.23 | 23.40 | 0.420532E+09 | 843.02 | 08-JUL-12:30 | 24.23 | 23.40 |
August | 0.873177E+10 | 15834.49 | 24-AUG-06:01 | 24.25 | 24.17 | 0.432036E+09 | 842.99 | 05-AUG-12:00 | 24.25 | 24.17 |
September | 0.851851E+10 | 15602.58 | 06-SEP-06:01 | 25.30 | 24.45 | 0.411317E+09 | 842.98 | 16-SEP-12:00 | 24.40 | 24.15 |
October | 0.837632E+10 | 15874.13 | 11-OCT-06:01 | 24.10 | 23.71 | 0.420877E+09 | 842.90 | 21-OCT-12:09 | 30.90 | 25.78 |
November | 0.835025E+10 | 18813.85 | 25-NOV-07:02 | 21.17 | 18.84 | 0.406589E+09 | 843.00 | 25-NOV-13:39 | 26.33 | 21.82 |
December | 0.862028E+10 | 20404.74 | 21-DEC-07:02 | 18.83 | 17.79 | 0.420310E+09 | 843.02 | 02-DEC-13:00 | 18.83 | 17.79 |
Annual Sum or Average | 0.106986E+12 | 0.500314E+10 | ||||||||
Minimum of Months | 0.835025E+10 | 15518.85 | 18.83 | 17.57 | 0.382454E+09 | 842.90 | 18.83 | 17.57 | ||
Maximum of Months | 0.968940E+10 | 20837.02 | 26.15 | 24.45 | 0.432183E+09 | 843.02 | 33.22 | 26.33 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153441E+11 | 36487.93 | 24-JAN-08:62 | 19.83 | 17.92 | 0.143616E+10 | 2248.04 | 07-JAN-15:09 | 19.83 | 17.92 |
February | 0.145690E+11 | 37497.92 | 25-FEB-08:61 | 26.67 | 20.13 | 0.130772E+10 | 2248.13 | 18-FEB-15:09 | 26.67 | 20.13 |
March | 0.164386E+11 | 34573.51 | 04-MAR-08:62 | 26.50 | 20.59 | 0.148081E+10 | 2248.14 | 04-MAR-15:09 | 33.87 | 22.25 |
April | 0.157990E+11 | 31535.36 | 27-APR-07:01 | 27.08 | 24.31 | 0.141114E+10 | 2247.81 | 22-APR-14:00 | 27.08 | 24.31 |
May | 0.166652E+11 | 29513.24 | 09-MAY-07:01 | 24.50 | 24.40 | 0.145887E+10 | 2247.81 | 13-MAY-14:00 | 31.50 | 26.17 |
June | 0.167401E+11 | 30707.14 | 20-JUN-07:01 | 24.58 | 24.46 | 0.143063E+10 | 2247.81 | 03-JUN-14:00 | 24.58 | 24.46 |
July | 0.149716E+11 | 32940.87 | 06-JUL-07:01 | 25.92 | 23.26 | 0.143919E+10 | 2247.81 | 29-JUL-14:09 | 32.00 | 24.80 |
August | 0.149045E+11 | 29717.59 | 24-AUG-07:01 | 25.75 | 25.32 | 0.148047E+10 | 2247.95 | 19-AUG-14:30 | 25.75 | 25.32 |
September | 0.145191E+11 | 29873.74 | 06-SEP-07:01 | 27.17 | 25.69 | 0.141075E+10 | 2247.98 | 16-SEP-14:39 | 26.50 | 25.13 |
October | 0.142215E+11 | 30294.77 | 11-OCT-07:02 | 24.92 | 24.20 | 0.143604E+10 | 2247.81 | 14-OCT-14:09 | 30.58 | 26.79 |
November | 0.142310E+11 | 34737.90 | 25-NOV-08:62 | 22.25 | 19.45 | 0.138278E+10 | 2248.05 | 25-NOV-15:30 | 25.65 | 22.42 |
December | 0.147025E+11 | 36261.67 | 27-DEC-08:62 | 23.50 | 19.75 | 0.143854E+10 | 2248.09 | 02-DEC-15:20 | 23.50 | 19.75 |
Annual Sum or Average | 0.183106E+12 | 0.171131E+11 | ||||||||
Minimum of Months | 0.142215E+11 | 29513.24 | 19.83 | 17.92 | 0.130772E+10 | 2247.81 | 19.83 | 17.92 | ||
Maximum of Months | 0.167401E+11 | 37497.92 | 27.17 | 25.69 | 0.148081E+10 | 2248.14 | 33.87 | 26.79 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.801465E+10 | 19023.62 | 24-JAN-08:62 | 19.83 | 17.92 | 0.718045E+09 | 1123.98 | 07-JAN-15:09 | 19.83 | 17.92 |
February | 0.761825E+10 | 19573.07 | 25-FEB-08:61 | 26.67 | 20.13 | 0.653821E+09 | 1124.03 | 18-FEB-15:09 | 26.67 | 20.13 |
March | 0.859971E+10 | 18059.11 | 04-MAR-08:62 | 26.50 | 20.59 | 0.740370E+09 | 1124.04 | 04-MAR-15:09 | 33.87 | 22.25 |
April | 0.827477E+10 | 16492.11 | 27-APR-07:01 | 27.08 | 24.31 | 0.705532E+09 | 1123.87 | 22-APR-14:00 | 27.08 | 24.31 |
May | 0.872796E+10 | 15420.90 | 09-MAY-07:01 | 24.50 | 24.40 | 0.729394E+09 | 1123.87 | 13-MAY-14:00 | 31.50 | 26.17 |
June | 0.874995E+10 | 16050.43 | 20-JUN-07:01 | 24.58 | 24.46 | 0.715283E+09 | 1123.87 | 03-JUN-14:00 | 24.58 | 24.46 |
July | 0.780997E+10 | 17220.63 | 06-JUL-07:01 | 25.92 | 23.26 | 0.719547E+09 | 1123.87 | 29-JUL-14:30 | 32.00 | 24.80 |
August | 0.777696E+10 | 15556.76 | 24-AUG-07:01 | 25.75 | 25.32 | 0.740196E+09 | 1123.94 | 19-AUG-14:50 | 25.75 | 25.32 |
September | 0.758033E+10 | 15648.17 | 06-SEP-07:01 | 27.17 | 25.69 | 0.705337E+09 | 1123.95 | 16-SEP-14:39 | 26.50 | 25.13 |
October | 0.741776E+10 | 15850.66 | 11-OCT-07:02 | 24.92 | 24.20 | 0.717983E+09 | 1123.87 | 14-OCT-14:09 | 30.58 | 26.79 |
November | 0.741877E+10 | 18103.89 | 25-NOV-08:62 | 22.25 | 19.45 | 0.691361E+09 | 1123.99 | 25-NOV-15:20 | 25.73 | 22.40 |
December | 0.767015E+10 | 18921.26 | 27-DEC-08:62 | 23.50 | 19.75 | 0.719239E+09 | 1124.01 | 02-DEC-15:20 | 23.50 | 19.75 |
Annual Sum or Average | 0.956592E+11 | 0.855611E+10 | ||||||||
Minimum of Months | 0.741776E+10 | 15420.90 | 19.83 | 17.92 | 0.653821E+09 | 1123.87 | 19.83 | 17.92 | ||
Maximum of Months | 0.874995E+10 | 19573.07 | 27.17 | 25.69 | 0.740370E+09 | 1124.04 | 33.87 | 26.79 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.796017E+10 | 18909.66 | 24-JAN-08:62 | 19.83 | 17.92 | 0.718038E+09 | 1123.98 | 07-JAN-15:09 | 19.83 | 17.92 |
February | 0.757209E+10 | 19458.86 | 25-FEB-08:61 | 26.67 | 20.13 | 0.653815E+09 | 1124.03 | 18-FEB-15:09 | 26.67 | 20.13 |
March | 0.855015E+10 | 17950.89 | 04-MAR-08:62 | 26.50 | 20.59 | 0.740366E+09 | 1124.04 | 04-MAR-15:09 | 33.87 | 22.25 |
April | 0.823029E+10 | 16387.04 | 27-APR-07:01 | 27.08 | 24.31 | 0.705526E+09 | 1123.87 | 22-APR-14:00 | 27.08 | 24.31 |
May | 0.868149E+10 | 15326.12 | 09-MAY-07:01 | 24.50 | 24.40 | 0.729389E+09 | 1123.87 | 13-MAY-14:00 | 31.50 | 26.17 |
June | 0.870292E+10 | 15953.86 | 20-JUN-07:01 | 24.58 | 24.46 | 0.715279E+09 | 1123.87 | 03-JUN-14:00 | 24.58 | 24.46 |
July | 0.776460E+10 | 17116.25 | 06-JUL-07:01 | 25.92 | 23.26 | 0.719541E+09 | 1123.87 | 29-JUL-14:20 | 32.00 | 24.80 |
August | 0.772976E+10 | 15446.44 | 24-AUG-07:01 | 25.75 | 25.32 | 0.740192E+09 | 1123.94 | 19-AUG-14:50 | 25.75 | 25.32 |
September | 0.753615E+10 | 15555.38 | 06-SEP-07:01 | 27.17 | 25.69 | 0.705332E+09 | 1123.95 | 16-SEP-14:39 | 26.50 | 25.13 |
October | 0.736866E+10 | 15744.87 | 11-OCT-07:02 | 24.92 | 24.20 | 0.717977E+09 | 1123.87 | 14-OCT-14:09 | 30.58 | 26.79 |
November | 0.736768E+10 | 17992.52 | 25-NOV-08:62 | 22.25 | 19.45 | 0.691355E+09 | 1123.99 | 25-NOV-15:09 | 25.82 | 22.39 |
December | 0.761575E+10 | 18803.36 | 27-DEC-08:62 | 23.50 | 19.75 | 0.719231E+09 | 1124.01 | 02-DEC-15:20 | 23.50 | 19.75 |
Annual Sum or Average | 0.950797E+11 | 0.855604E+10 | ||||||||
Minimum of Months | 0.736768E+10 | 15326.12 | 19.83 | 17.92 | 0.653815E+09 | 1123.87 | 19.83 | 17.92 | ||
Maximum of Months | 0.870292E+10 | 19458.86 | 27.17 | 25.69 | 0.740366E+09 | 1124.04 | 33.87 | 26.79 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.796807E+10 | 18897.33 | 24-JAN-08:62 | 19.83 | 17.92 | 0.718037E+09 | 1123.98 | 07-JAN-15:09 | 19.83 | 17.92 |
February | 0.760283E+10 | 19471.40 | 25-FEB-08:61 | 26.67 | 20.13 | 0.653817E+09 | 1124.03 | 18-FEB-15:09 | 26.67 | 20.13 |
March | 0.859504E+10 | 17919.55 | 04-MAR-08:62 | 26.50 | 20.59 | 0.740368E+09 | 1124.04 | 04-MAR-15:09 | 33.87 | 22.25 |
April | 0.829192E+10 | 16419.19 | 27-APR-07:01 | 27.08 | 24.31 | 0.705531E+09 | 1123.87 | 22-APR-14:00 | 27.08 | 24.31 |
May | 0.874037E+10 | 15359.96 | 09-MAY-07:01 | 24.50 | 24.40 | 0.729395E+09 | 1123.87 | 13-MAY-14:00 | 31.50 | 26.17 |
June | 0.877096E+10 | 16017.01 | 20-JUN-07:01 | 24.58 | 24.46 | 0.715283E+09 | 1123.87 | 03-JUN-14:00 | 24.58 | 24.46 |
July | 0.780894E+10 | 17157.51 | 06-JUL-07:01 | 25.92 | 23.26 | 0.719545E+09 | 1123.87 | 29-JUL-14:20 | 32.00 | 24.80 |
August | 0.776793E+10 | 15470.22 | 24-AUG-07:01 | 25.75 | 25.32 | 0.740193E+09 | 1123.95 | 19-AUG-14:50 | 25.75 | 25.32 |
September | 0.758018E+10 | 15625.38 | 06-SEP-07:01 | 27.17 | 25.69 | 0.705335E+09 | 1123.95 | 16-SEP-14:50 | 26.75 | 25.33 |
October | 0.737826E+10 | 15751.02 | 11-OCT-07:02 | 24.92 | 24.20 | 0.717977E+09 | 1123.87 | 14-OCT-14:09 | 30.58 | 26.79 |
November | 0.737538E+10 | 18000.73 | 25-NOV-08:62 | 22.25 | 19.45 | 0.691354E+09 | 1123.89 | 25-NOV-15:09 | 25.82 | 22.39 |
December | 0.761411E+10 | 18803.79 | 27-DEC-08:62 | 23.50 | 19.75 | 0.719228E+09 | 1124.01 | 23-DEC-15:09 | 23.50 | 19.75 |
Annual Sum or Average | 0.954940E+11 | 0.855606E+10 | ||||||||
Minimum of Months | 0.737538E+10 | 15359.96 | 19.83 | 17.92 | 0.653817E+09 | 1123.87 | 19.83 | 17.92 | ||
Maximum of Months | 0.877096E+10 | 19471.40 | 27.17 | 25.69 | 0.740368E+09 | 1124.04 | 33.87 | 26.79 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.931305E+10 | 20598.48 | 28-JAN-08:62 | 21.50 | 19.17 | 0.718179E+09 | 1123.93 | 07-JAN-15:20 | 21.50 | 19.17 |
February | 0.905585E+10 | 22333.13 | 23-FEB-08:61 | 23.33 | 20.35 | 0.653970E+09 | 1124.01 | 18-FEB-15:00 | 23.33 | 20.35 |
March | 0.103620E+11 | 19702.41 | 04-MAR-08:62 | 26.50 | 20.59 | 0.740520E+09 | 1124.01 | 04-MAR-15:09 | 33.87 | 22.25 |
April | 0.101244E+11 | 17646.86 | 27-APR-07:01 | 27.08 | 24.31 | 0.705712E+09 | 1123.87 | 22-APR-14:00 | 27.08 | 24.31 |
May | 0.104962E+11 | 16849.32 | 11-MAY-07:01 | 26.50 | 26.26 | 0.729559E+09 | 1123.87 | 13-MAY-14:00 | 31.50 | 26.17 |
June | 0.106499E+11 | 17635.51 | 20-JUN-07:01 | 24.58 | 24.46 | 0.715424E+09 | 1123.87 | 03-JUN-14:00 | 24.58 | 24.46 |
July | 0.935992E+10 | 19750.09 | 11-JUL-07:01 | 24.67 | 23.95 | 0.719760E+09 | 1123.90 | 08-JUL-14:09 | 24.67 | 23.95 |
August | 0.934023E+10 | 17394.33 | 24-AUG-07:01 | 25.75 | 25.32 | 0.740318E+09 | 1123.97 | 19-AUG-14:39 | 25.75 | 25.32 |
September | 0.914355E+10 | 17636.63 | 12-SEP-07:01 | 26.13 | 25.27 | 0.705511E+09 | 1123.87 | 23-SEP-14:09 | 31.00 | 26.41 |
October | 0.861568E+10 | 17484.14 | 11-OCT-07:02 | 24.92 | 24.20 | 0.718129E+09 | 1123.87 | 14-OCT-14:09 | 30.58 | 26.79 |
November | 0.863451E+10 | 20100.22 | 25-NOV-08:62 | 22.25 | 19.45 | 0.691463E+09 | 1123.87 | 04-NOV-14:20 | 22.25 | 19.45 |
December | 0.887327E+10 | 20760.48 | 27-DEC-08:62 | 23.50 | 19.75 | 0.719369E+09 | 1123.97 | 02-DEC-15:09 | 23.50 | 19.75 |
Annual Sum or Average | 0.113968E+12 | 0.855791E+10 | ||||||||
Minimum of Months | 0.861568E+10 | 16849.32 | 21.50 | 19.17 | 0.653970E+09 | 1123.87 | 21.50 | 19.17 | ||
Maximum of Months | 0.106499E+11 | 22333.13 | 27.08 | 26.26 | 0.740520E+09 | 1124.01 | 33.87 | 26.79 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 23597040.63 | 3449.40 | 03-JAN-08:04 | 27.00 |
February | 27664157.23 | 3613.89 | 18-FEB-08:04 | 27.33 |
March | 25095725.88 | 3669.71 | 08-MAR-08:05 | 27.17 |
April | 26997673.22 | 3819.48 | 15-APR-07:05 | 27.62 |
May | 22303581.32 | 5528.30 | 28-MAY-07:06 | 32.25 |
June | 18928561.56 | 4317.99 | 15-JUN-07:06 | 29.50 |
July | 29854614.52 | 3471.12 | 29-JUL-07:05 | 26.73 |
August | 29707215.58 | 4121.69 | 09-AUG-07:06 | 28.75 |
September | 29133246.23 | 3717.18 | 11-SEP-07:05 | 27.83 |
October | 31585329.16 | 3447.00 | 05-OCT-07:06 | 27.75 |
November | 19904313.03 | 3426.59 | 15-NOV-08:05 | 27.25 |
December | 26560758.65 | 3246.96 | 08-DEC-08:04 | 26.50 |
Annual Sum or Average | 0.311332E+09 | |||
Minimum of Months | 18928561.56 | 3246.96 | 26.50 | |
Maximum of Months | 31585329.16 | 5528.30 | 32.25 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12880149.50 | 2397.73 | 11-JAN-08:04 | 29.33 |
February | 13756254.73 | 1974.18 | 18-FEB-08:04 | 27.33 |
March | 14797600.40 | 1994.14 | 09-MAR-08:04 | 27.50 |
April | 9754116.75 | 2017.24 | 28-APR-07:04 | 27.75 |
May | 11754503.43 | 2948.53 | 28-MAY-07:05 | 32.25 |
June | 10019241.16 | 2248.84 | 15-JUN-07:05 | 29.50 |
July | 14225795.02 | 1780.63 | 15-JUL-07:04 | 26.75 |
August | 12634457.80 | 2061.79 | 17-AUG-07:04 | 28.08 |
September | 12658345.38 | 2045.58 | 01-SEP-07:04 | 28.17 |
October | 13740715.32 | 1923.91 | 06-OCT-07:04 | 27.50 |
November | 12416461.27 | 1927.71 | 14-NOV-08:04 | 27.67 |
December | 13362794.89 | 1940.09 | 09-DEC-08:04 | 27.33 |
Annual Sum or Average | 0.152000E+09 | |||
Minimum of Months | 9754116.75 | 1780.63 | 26.75 | |
Maximum of Months | 14797600.40 | 2948.53 | 32.25 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 65514190.13 | 1882.56 | 29-JAN-17:02 | 30.83 |
February | 76615289.57 | 1866.72 | 12-FEB-17:02 | 30.67 |
March | 91591290.50 | 2730.38 | 19-MAR-16:01 | 34.25 |
April | 0.115886E+09 | 2510.27 | 02-APR-16:01 | 33.25 |
May | 0.103092E+09 | 2800.73 | 29-MAY-16:01 | 34.50 |
June | 99916786.22 | 2735.57 | 11-JUN-16:01 | 34.25 |
July | 81737011.59 | 2442.70 | 15-JUL-17:02 | 32.83 |
August | 71474866.90 | 2411.94 | 27-AUG-16:01 | 32.83 |
September | 78809079.82 | 2421.28 | 04-SEP-16:01 | 32.83 |
October | 66189267.83 | 1633.19 | 08-OCT-16:02 | 29.72 |
November | 57224184.91 | 1702.89 | 23-NOV-08:05 | 27.25 |
December | 51445380.44 | 1411.09 | 10-DEC-17:02 | 29.00 |
Annual Sum or Average | 0.959496E+09 | |||
Minimum of Months | 51445380.44 | 1411.09 | 27.25 | |
Maximum of Months | 0.115886E+09 | 2800.73 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 65323898.68 | 1882.89 | 29-JAN-17:02 | 30.83 |
February | 75647182.86 | 1867.15 | 12-FEB-17:02 | 30.67 |
March | 91442519.35 | 2730.04 | 19-MAR-16:01 | 34.25 |
April | 0.115732E+09 | 2509.70 | 02-APR-16:01 | 33.25 |
May | 0.102537E+09 | 2799.83 | 29-MAY-16:01 | 34.50 |
June | 99169473.99 | 2734.53 | 11-JUN-16:01 | 34.25 |
July | 81628439.04 | 2442.74 | 15-JUL-17:02 | 32.83 |
August | 71314242.01 | 2411.61 | 27-AUG-16:01 | 32.83 |
September | 78774662.56 | 2420.70 | 04-SEP-16:01 | 32.83 |
October | 65851378.34 | 1633.31 | 08-OCT-16:02 | 29.72 |
November | 57127941.49 | 1702.77 | 23-NOV-08:05 | 27.25 |
December | 51547122.51 | 1411.80 | 10-DEC-17:12 | 29.00 |
Annual Sum or Average | 0.956095E+09 | |||
Minimum of Months | 51547122.51 | 1411.80 | 27.25 | |
Maximum of Months | 0.115732E+09 | 2799.83 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66703535.80 | 1887.24 | 29-JAN-17:02 | 30.83 |
February | 77061678.39 | 1871.42 | 12-FEB-17:02 | 30.67 |
March | 92534389.15 | 2733.61 | 19-MAR-16:01 | 34.25 |
April | 0.117307E+09 | 2513.00 | 02-APR-16:01 | 33.25 |
May | 0.104637E+09 | 2803.00 | 29-MAY-16:01 | 34.50 |
June | 0.101631E+09 | 2737.72 | 11-JUN-16:01 | 34.25 |
July | 82344366.11 | 2447.24 | 15-JUL-17:02 | 32.83 |
August | 72979442.65 | 2415.01 | 27-AUG-16:01 | 32.83 |
September | 79789022.12 | 2423.60 | 04-SEP-16:01 | 32.83 |
October | 67625378.51 | 1637.23 | 08-OCT-16:02 | 29.72 |
November | 58302174.37 | 1735.28 | 23-NOV-08:05 | 27.25 |
December | 52280238.90 | 1416.50 | 10-DEC-17:02 | 29.00 |
Annual Sum or Average | 0.973195E+09 | |||
Minimum of Months | 52280238.90 | 1416.50 | 27.25 | |
Maximum of Months | 0.117307E+09 | 2803.00 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66049175.26 | 3854.11 | 11-JAN-08:06 | 29.33 |
February | 83400783.26 | 3752.90 | 12-FEB-17:02 | 30.67 |
March | 86146510.40 | 5486.27 | 19-MAR-16:01 | 34.25 |
April | 0.103534E+09 | 5037.56 | 02-APR-16:01 | 33.25 |
May | 97496633.18 | 5624.73 | 29-MAY-16:01 | 34.50 |
June | 78495822.68 | 5495.38 | 11-JUN-16:01 | 34.25 |
July | 0.106549E+09 | 4893.68 | 15-JUL-17:02 | 32.83 |
August | 70691076.01 | 4837.27 | 27-AUG-16:01 | 32.83 |
September | 80994545.02 | 4850.98 | 04-SEP-16:01 | 32.83 |
October | 79681330.83 | 3429.14 | 08-OCT-08:06 | 28.25 |
November | 56728286.01 | 3618.10 | 23-NOV-09:06 | 28.57 |
December | 67651685.03 | 3566.07 | 31-DEC-09:06 | 28.47 |
Annual Sum or Average | 0.977419E+09 | |||
Minimum of Months | 56728286.01 | 3429.14 | 28.25 | |
Maximum of Months | 0.106549E+09 | 5624.73 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34154346.83 | 1903.97 | 29-JAN-17:02 | 30.83 |
February | 41681525.24 | 1886.62 | 12-FEB-17:02 | 30.67 |
March | 41792588.22 | 2749.08 | 19-MAR-16:01 | 34.25 |
April | 49834838.95 | 2526.42 | 02-APR-16:01 | 33.25 |
May | 49441901.34 | 2816.72 | 29-MAY-16:01 | 34.50 |
June | 37780851.39 | 2753.04 | 11-JUN-16:01 | 34.25 |
July | 52604183.58 | 2465.43 | 15-JUL-17:02 | 32.83 |
August | 34102288.96 | 2427.71 | 27-AUG-16:01 | 32.83 |
September | 40353239.36 | 2434.24 | 04-SEP-16:01 | 32.83 |
October | 39111230.45 | 1690.55 | 08-OCT-08:06 | 28.25 |
November | 26576557.99 | 1750.78 | 23-NOV-09:06 | 28.57 |
December | 33293795.92 | 1784.48 | 31-DEC-09:06 | 28.47 |
Annual Sum or Average | 0.480727E+09 | |||
Minimum of Months | 26576557.99 | 1690.55 | 28.25 | |
Maximum of Months | 52604183.58 | 2816.72 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33909392.90 | 1905.28 | 29-JAN-17:02 | 30.83 |
February | 41668715.31 | 1887.56 | 12-FEB-17:02 | 30.67 |
March | 41873332.68 | 2749.96 | 19-MAR-16:01 | 34.25 |
April | 49922854.35 | 2527.14 | 02-APR-16:01 | 33.25 |
May | 49605353.56 | 2817.50 | 29-MAY-16:01 | 34.50 |
June | 37919952.41 | 2753.93 | 11-JUN-16:01 | 34.25 |
July | 52688116.62 | 2466.22 | 15-JUL-17:02 | 32.83 |
August | 34184730.79 | 2428.37 | 27-AUG-16:01 | 32.83 |
September | 40415873.26 | 2434.80 | 04-SEP-16:01 | 32.83 |
October | 39104159.24 | 1685.36 | 08-OCT-08:06 | 28.25 |
November | 26672811.22 | 1742.79 | 23-NOV-09:06 | 28.57 |
December | 33503706.38 | 1776.14 | 31-DEC-09:06 | 28.47 |
Annual Sum or Average | 0.481469E+09 | |||
Minimum of Months | 26672811.22 | 1685.36 | 28.25 | |
Maximum of Months | 52688116.62 | 2817.50 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34122560.98 | 1905.21 | 29-JAN-17:02 | 30.83 |
February | 41328289.24 | 1887.29 | 12-FEB-17:02 | 30.67 |
March | 42044870.49 | 2748.30 | 19-MAR-16:01 | 34.25 |
April | 49816763.76 | 2525.13 | 02-APR-16:01 | 33.25 |
May | 49686564.59 | 2815.38 | 29-MAY-16:01 | 34.50 |
June | 37701222.37 | 2751.26 | 11-JUN-16:01 | 34.25 |
July | 53281621.96 | 2464.59 | 15-JUL-17:02 | 32.83 |
August | 34838063.11 | 2426.44 | 27-AUG-16:01 | 32.83 |
September | 40677418.12 | 2432.84 | 04-SEP-16:01 | 32.83 |
October | 38876835.99 | 1663.02 | 08-OCT-08:06 | 28.25 |
November | 27431828.29 | 1728.52 | 23-NOV-09:06 | 28.57 |
December | 33285762.81 | 1753.46 | 31-DEC-09:06 | 28.47 |
Annual Sum or Average | 0.483092E+09 | |||
Minimum of Months | 27431828.29 | 1663.02 | 28.25 | |
Maximum of Months | 53281621.96 | 2815.38 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30351243.07 | 2323.65 | 11-JAN-08:04 | 29.33 |
February | 35596989.99 | 1941.21 | 18-FEB-08:04 | 27.33 |
March | 35401544.38 | 2701.62 | 19-MAR-16:01 | 34.25 |
April | 44096997.48 | 2480.74 | 02-APR-16:01 | 33.25 |
May | 43314509.04 | 2765.80 | 29-MAY-16:01 | 34.50 |
June | 33560337.64 | 2697.10 | 11-JUN-16:01 | 34.25 |
July | 47492420.64 | 2424.20 | 15-JUL-17:02 | 32.83 |
August | 30649864.14 | 2384.53 | 27-AUG-16:01 | 32.83 |
September | 35522903.97 | 2392.85 | 04-SEP-16:01 | 32.83 |
October | 34102332.21 | 1769.98 | 08-OCT-08:06 | 28.25 |
November | 24507681.21 | 1963.94 | 23-NOV-09:06 | 28.57 |
December | 28259283.95 | 1855.14 | 31-DEC-09:06 | 28.47 |
Annual Sum or Average | 0.422856E+09 | |||
Minimum of Months | 24507681.21 | 1769.98 | 27.33 | |
Maximum of Months | 47492420.64 | 2765.80 | 34.50 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.986629E+10 | 6035.26 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.891946E+10 | 6035.26 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.987658E+10 | 6035.26 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.956097E+10 | 6035.26 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.986629E+10 | 6035.26 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.956097E+10 | 6035.26 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.987658E+10 | 6035.26 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.986629E+10 | 6035.26 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.957126E+10 | 6035.26 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.986629E+10 | 6035.26 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.953010E+10 | 6035.26 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.988687E+10 | 6035.26 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.116248E+12 | 0.262491E+11 | ||||
Minimum of Months | 0.891946E+10 | 6035.26 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.988687E+10 | 6035.26 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.579394E+10 | 3544.17 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.523792E+10 | 3544.17 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.579999E+10 | 3544.17 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.561464E+10 | 3544.17 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.579394E+10 | 3544.17 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.561464E+10 | 3544.17 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.579999E+10 | 3544.17 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.579394E+10 | 3544.17 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.562069E+10 | 3544.17 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.579394E+10 | 3544.17 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.559651E+10 | 3544.17 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.580603E+10 | 3544.17 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.682662E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.523792E+10 | 3544.17 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.580603E+10 | 3544.17 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.413753E+10 | 3181.37 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.374692E+10 | 3181.37 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.422433E+10 | 3181.37 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.401456E+10 | 3181.37 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.418093E+10 | 3181.37 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.407966E+10 | 3181.37 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.411583E+10 | 3181.37 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.422433E+10 | 3181.37 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.401456E+10 | 3181.37 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.413753E+10 | 3181.37 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.401456E+10 | 3181.37 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.411583E+10 | 3181.37 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.490066E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.374692E+10 | 3181.37 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.422433E+10 | 3181.37 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.413753E+10 | 3181.37 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.374692E+10 | 3181.37 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.422433E+10 | 3181.37 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.401456E+10 | 3181.37 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.418093E+10 | 3181.37 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.407966E+10 | 3181.37 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.411583E+10 | 3181.37 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.422433E+10 | 3181.37 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.401456E+10 | 3181.37 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.413753E+10 | 3181.37 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.401456E+10 | 3181.37 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.411583E+10 | 3181.37 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.490066E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.374692E+10 | 3181.37 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.422433E+10 | 3181.37 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.413753E+10 | 3181.37 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.374692E+10 | 3181.37 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.422433E+10 | 3181.37 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.401456E+10 | 3181.37 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.418093E+10 | 3181.37 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.407966E+10 | 3181.37 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.411583E+10 | 3181.37 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.422433E+10 | 3181.37 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.401456E+10 | 3181.37 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.413753E+10 | 3181.37 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.401456E+10 | 3181.37 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.411583E+10 | 3181.37 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.490066E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.374692E+10 | 3181.37 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.422433E+10 | 3181.37 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.457032E+10 | 3825.14 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.413982E+10 | 3825.14 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.467469E+10 | 3825.14 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.443552E+10 | 3825.14 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.462251E+10 | 3825.14 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.451379E+10 | 3825.14 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.454423E+10 | 3825.14 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.467469E+10 | 3825.14 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.443552E+10 | 3825.14 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.457032E+10 | 3825.14 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.443552E+10 | 3825.14 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.454423E+10 | 3825.14 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.541612E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.413982E+10 | 3825.14 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.467469E+10 | 3825.14 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.986629E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222787E+10 | 51721299.92 |
February | 0.305697E+10 | 0.891946E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240543E+10 | 12971458.58 |
March | 0.335708E+10 | 0.987658E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290551E+10 | 21157353.06 |
April | 0.327081E+10 | 0.956097E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288428E+10 | 3692511.36 |
May | 0.336680E+10 | 0.986629E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291727E+10 | 9405421.65 |
June | 0.325380E+10 | 0.956097E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284845E+10 | 9877355.22 |
July | 0.339353E+10 | 0.987658E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214113E+10 | 8523625.33 |
August | 0.334857E+10 | 0.986629E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217489E+10 | 19990265.69 |
September | 0.327932E+10 | 0.957126E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214070E+10 | 9374052.71 |
October | 0.338624E+10 | 0.986629E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188666E+10 | 18900251.33 |
November | 0.327446E+10 | 0.953010E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182078E+10 | 24643691.35 |
December | 0.340325E+10 | 0.988687E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198101E+10 | 50787095.33 |
Annual Sum or Average | 0.397770E+11 | 0.116248E+12 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283340E+11 | 0.241044E+09 |
Minimum of Months | 0.305697E+10 | 0.891946E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182078E+10 | 3692511.36 |
Maximum of Months | 0.340325E+10 | 0.988687E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291727E+10 | 51721299.92 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.579394E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125633E+10 | 17116169.15 |
February | 0.152844E+10 | 0.523792E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135225E+10 | 4110578.45 |
March | 0.167849E+10 | 0.579999E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162298E+10 | 6301150.91 |
April | 0.163536E+10 | 0.561464E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161221E+10 | 1207563.12 |
May | 0.168335E+10 | 0.579394E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162542E+10 | 2822546.47 |
June | 0.162685E+10 | 0.561464E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159053E+10 | 2914819.56 |
July | 0.169671E+10 | 0.579999E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120032E+10 | 2631909.98 |
August | 0.167424E+10 | 0.579394E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121397E+10 | 6840559.12 |
September | 0.163961E+10 | 0.562069E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120254E+10 | 2864623.60 |
October | 0.169307E+10 | 0.579394E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106096E+10 | 6253890.59 |
November | 0.163718E+10 | 0.559651E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102697E+10 | 7644003.65 |
December | 0.170157E+10 | 0.580603E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111913E+10 | 15280717.78 |
Annual Sum or Average | 0.198880E+11 | 0.682662E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158836E+11 | 75988532.37 |
Minimum of Months | 0.152844E+10 | 0.523792E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102697E+10 | 1207563.12 |
Maximum of Months | 0.170157E+10 | 0.580603E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162542E+10 | 17116169.15 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122941E+10 | 24201596.06 |
February | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132478E+10 | 6985324.76 |
March | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159757E+10 | 10183569.07 |
April | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158449E+10 | 2659528.49 |
May | 0.102058E+10 | 0.418093E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159816E+10 | 5099387.12 |
June | 0.998711E+09 | 0.407966E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156675E+10 | 6351738.08 |
July | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117194E+10 | 7296275.95 |
August | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119390E+10 | 12207232.17 |
September | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117957E+10 | 7857040.79 |
October | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103832E+10 | 13994966.62 |
November | 0.973196E+09 | 0.401456E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100750E+10 | 14210476.47 |
December | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109546E+10 | 23982003.25 |
Annual Sum or Average | 0.119700E+11 | 0.490066E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155879E+11 | 0.135029E+09 |
Minimum of Months | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100750E+10 | 2659528.49 |
Maximum of Months | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159816E+10 | 24201596.06 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122934E+10 | 24737000.37 |
February | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132458E+10 | 7356944.08 |
March | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159709E+10 | 10809000.93 |
April | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158364E+10 | 2839851.71 |
May | 0.102058E+10 | 0.418093E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159724E+10 | 5368044.18 |
June | 0.998711E+09 | 0.407966E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156601E+10 | 6739247.46 |
July | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117161E+10 | 7658609.53 |
August | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119363E+10 | 12649346.65 |
September | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117929E+10 | 8160442.75 |
October | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103820E+10 | 14405939.65 |
November | 0.973196E+09 | 0.401456E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100741E+10 | 14498315.74 |
December | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109543E+10 | 24345936.97 |
Annual Sum or Average | 0.119700E+11 | 0.490066E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155835E+11 | 0.139569E+09 |
Minimum of Months | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100741E+10 | 2839851.71 |
Maximum of Months | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159724E+10 | 24737000.37 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122962E+10 | 23549878.04 |
February | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132500E+10 | 6624555.46 |
March | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159791E+10 | 9509716.29 |
April | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158502E+10 | 2474116.08 |
May | 0.102058E+10 | 0.418093E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159838E+10 | 4859925.62 |
June | 0.998711E+09 | 0.407966E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156704E+10 | 6187375.29 |
July | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117217E+10 | 7061696.24 |
August | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119413E+10 | 11467567.84 |
September | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117979E+10 | 7445875.94 |
October | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103853E+10 | 13449111.51 |
November | 0.973196E+09 | 0.401456E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100771E+10 | 13569669.28 |
December | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109562E+10 | 23221155.47 |
Annual Sum or Average | 0.119700E+11 | 0.490066E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155909E+11 | 0.129421E+09 |
Minimum of Months | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100771E+10 | 2474116.08 |
Maximum of Months | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159838E+10 | 23549878.04 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.457032E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215863E+10 | 45922820.33 |
February | 0.313522E+10 | 0.413982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232484E+10 | 11821284.49 |
March | 0.355148E+10 | 0.467469E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280936E+10 | 14712293.00 |
April | 0.338259E+10 | 0.443552E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278802E+10 | 3739958.34 |
May | 0.349753E+10 | 0.462251E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281092E+10 | 7800086.30 |
June | 0.343071E+10 | 0.451379E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275539E+10 | 10648532.69 |
July | 0.344942E+10 | 0.454423E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205683E+10 | 11946902.66 |
August | 0.355148E+10 | 0.467469E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209794E+10 | 17796903.83 |
September | 0.338259E+10 | 0.443552E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206958E+10 | 12038084.92 |
October | 0.344359E+10 | 0.457032E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182030E+10 | 23399388.88 |
November | 0.331698E+10 | 0.443552E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176579E+10 | 24407589.45 |
December | 0.344942E+10 | 0.454423E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191972E+10 | 44322006.57 |
Annual Sum or Average | 0.410346E+11 | 0.541612E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273773E+11 | 0.228556E+09 |
Minimum of Months | 0.313522E+10 | 0.413982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176579E+10 | 3739958.34 |
Maximum of Months | 0.355148E+10 | 0.467469E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281092E+10 | 45922820.33 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123192E+10 | 22892463.10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132660E+10 | 5569861.72 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160164E+10 | 6691383.26 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158956E+10 | 1773793.77 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160176E+10 | 3591989.48 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157068E+10 | 5093410.87 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117317E+10 | 5782286.99 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119587E+10 | 8560306.51 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118071E+10 | 5795314.88 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103858E+10 | 11562996.07 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100786E+10 | 12077503.49 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109577E+10 | 21644992.44 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156141E+11 | 0.111036E+09 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100786E+10 | 1773793.77 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160176E+10 | 22892463.10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123205E+10 | 22644615.79 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132675E+10 | 5460726.22 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160188E+10 | 6529422.36 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158984E+10 | 1725310.18 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160202E+10 | 3527529.39 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157092E+10 | 5018761.97 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117332E+10 | 5685284.96 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119603E+10 | 8400426.58 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118086E+10 | 5695848.64 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103869E+10 | 11386149.30 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100798E+10 | 11899624.99 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109587E+10 | 21393060.26 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156162E+11 | 0.109367E+09 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100798E+10 | 1725310.18 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160202E+10 | 22644615.79 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123208E+10 | 22278607.11 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132673E+10 | 5330732.57 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160194E+10 | 6308242.65 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158977E+10 | 1657872.67 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160189E+10 | 3457554.31 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157079E+10 | 4969572.45 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117323E+10 | 5644362.70 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119603E+10 | 8162003.96 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118081E+10 | 5611923.03 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103874E+10 | 11152084.66 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100807E+10 | 11594976.97 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109591E+10 | 21002272.12 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156160E+11 | 0.107170E+09 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100807E+10 | 1657872.67 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160194E+10 | 22278607.11 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125420E+10 | 48188466.66 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135503E+10 | 14037235.66 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165147E+10 | 18526180.13 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163896E+10 | 3869720.34 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165927E+10 | 9906946.13 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162124E+10 | 13006675.81 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120247E+10 | 13925869.99 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123477E+10 | 19558030.25 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120760E+10 | 13882690.36 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106102E+10 | 23933682.62 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102596E+10 | 24984374.25 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111278E+10 | 49775454.13 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160248E+11 | 0.253595E+09 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102596E+10 | 3869720.34 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165927E+10 | 49775454.13 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 6035.26 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4731.04 | 04-JAN-13:00 | 728.70 | 07-JAN-05:00 |
February | 4050.04 | 03-FEB-13:09 | 6035.26 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5173.90 | 28-FEB-15:00 | 266.83 | 21-FEB-10:00 |
March | 4050.04 | 03-MAR-13:09 | 6035.26 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5729.16 | 21-MAR-13:00 | 136.02 | 03-MAR-05:30 |
April | 4050.04 | 01-APR-12:09 | 6035.26 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5251.38 | 01-APR-14:00 | 473.24 | 14-APR-16:00 |
May | 4050.04 | 05-MAY-12:09 | 6035.26 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6228.77 | 06-MAY-13:00 | 235.33 | 21-MAY-13:00 |
June | 4050.04 | 02-JUN-12:09 | 6035.26 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5565.03 | 13-JUN-15:00 | 232.33 | 30-JUN-13:00 |
July | 4050.04 | 01-JUL-12:09 | 6035.26 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4232.33 | 28-JUL-13:00 | 339.58 | 03-JUL-13:00 |
August | 4050.04 | 04-AUG-12:09 | 6035.26 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4680.03 | 27-AUG-14:00 | 834.24 | 20-AUG-11:10 |
September | 4050.04 | 01-SEP-12:09 | 6035.26 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4652.55 | 06-SEP-14:00 | 441.40 | 15-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 6035.26 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4209.81 | 04-OCT-14:00 | 427.94 | 30-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 6035.26 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4758.05 | 18-NOV-13:00 | 196.39 | 25-NOV-08:62 |
December | 4050.04 | 01-DEC-13:09 | 6035.26 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4174.27 | 07-DEC-14:00 | 265.53 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4174.27 | 136.02 | |||||
Maximum of Months | 4050.04 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6228.77 | 834.24 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3544.17 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2661.66 | 04-JAN-13:00 | 222.05 | 07-JAN-05:00 |
February | 2024.96 | 03-FEB-13:09 | 3544.17 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2900.06 | 28-FEB-15:00 | 146.20 | 21-FEB-10:00 |
March | 2024.96 | 03-MAR-13:09 | 3544.17 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3223.19 | 21-MAR-13:00 | 40.29 | 03-MAR-05:30 |
April | 2024.96 | 01-APR-12:09 | 3544.17 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2977.67 | 01-APR-14:00 | 267.91 | 14-APR-16:00 |
May | 2024.96 | 05-MAY-12:09 | 3544.17 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 06-MAY-13:00 | 133.22 | 21-MAY-13:00 |
June | 2024.96 | 02-JUN-12:09 | 3544.17 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3130.85 | 13-JUN-15:00 | 132.37 | 30-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 3544.17 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.71 | 15-JUL-16:00 | 189.87 | 03-JUL-13:00 |
August | 2024.96 | 04-AUG-12:09 | 3544.17 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.96 | 27-AUG-14:00 | 469.34 | 20-AUG-11:10 |
September | 2024.96 | 01-SEP-12:09 | 3544.17 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2625.67 | 06-SEP-14:00 | 245.32 | 15-SEP-17:00 |
October | 2024.96 | 01-OCT-12:09 | 3544.17 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2375.81 | 04-OCT-14:00 | 241.51 | 30-OCT-17:00 |
November | 2024.96 | 03-NOV-12:09 | 3544.17 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.67 | 18-NOV-13:00 | 105.16 | 25-NOV-08:62 |
December | 2024.96 | 01-DEC-13:09 | 3544.17 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 07-DEC-14:00 | 119.06 | 21-DEC-08:62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3544.17 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 40.29 | |||||
Maximum of Months | 2024.96 | 3544.17 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 469.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3181.37 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2661.66 | 04-JAN-13:00 | 286.02 | 01-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 3181.37 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2900.06 | 28-FEB-15:00 | 216.74 | 05-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3181.37 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3223.19 | 21-MAR-13:00 | 145.16 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 3181.37 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2977.67 | 01-APR-14:00 | 267.91 | 14-APR-16:00 |
May | 2024.96 | 06-MAY-12:09 | 3181.37 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 06-MAY-13:00 | 133.22 | 21-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 3181.37 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3130.85 | 13-JUN-15:00 | 206.54 | 25-JUN-19:00 |
July | 2024.96 | 01-JUL-12:09 | 3181.37 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.71 | 15-JUL-16:00 | 485.26 | 16-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 3181.37 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.96 | 27-AUG-14:00 | 469.34 | 20-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 3181.37 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2625.67 | 06-SEP-14:00 | 514.60 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 3181.37 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2375.81 | 04-OCT-14:00 | 410.05 | 09-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 3181.37 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.67 | 18-NOV-13:00 | 563.56 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 3181.37 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 07-DEC-14:00 | 407.05 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 133.22 | |||||
Maximum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 563.56 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3181.37 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2661.66 | 04-JAN-13:00 | 288.01 | 01-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 3181.37 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2900.06 | 28-FEB-15:00 | 222.09 | 05-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3181.37 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3223.19 | 21-MAR-13:00 | 147.96 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 3181.37 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2977.67 | 01-APR-14:00 | 267.91 | 14-APR-16:00 |
May | 2024.96 | 06-MAY-12:09 | 3181.37 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 06-MAY-13:00 | 133.22 | 21-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 3181.37 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3130.85 | 13-JUN-15:00 | 211.23 | 25-JUN-19:00 |
July | 2024.96 | 01-JUL-12:09 | 3181.37 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.71 | 15-JUL-16:00 | 490.48 | 16-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 3181.37 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.96 | 27-AUG-14:00 | 469.34 | 20-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 3181.37 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2625.67 | 06-SEP-14:00 | 518.02 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 3181.37 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2375.81 | 04-OCT-14:00 | 416.00 | 09-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 3181.37 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.67 | 18-NOV-13:00 | 563.58 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 3181.37 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 07-DEC-14:00 | 407.71 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 133.22 | |||||
Maximum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 563.58 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3181.37 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2661.66 | 04-JAN-13:00 | 274.51 | 01-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 3181.37 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2900.06 | 28-FEB-15:00 | 208.61 | 05-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3181.37 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3223.19 | 21-MAR-13:00 | 134.32 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 3181.37 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2977.67 | 01-APR-14:00 | 267.91 | 14-APR-16:00 |
May | 2024.96 | 06-MAY-12:09 | 3181.37 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 06-MAY-13:00 | 133.22 | 21-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 3181.37 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3130.85 | 13-JUN-15:00 | 207.13 | 25-JUN-19:00 |
July | 2024.96 | 01-JUL-12:09 | 3181.37 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.71 | 15-JUL-16:00 | 478.15 | 16-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 3181.37 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.96 | 27-AUG-14:00 | 469.34 | 20-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 3181.37 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2625.67 | 06-SEP-14:00 | 505.08 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 3181.37 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2375.81 | 04-OCT-14:00 | 403.74 | 09-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 3181.37 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.67 | 18-NOV-13:00 | 549.51 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 3181.37 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 07-DEC-14:00 | 393.27 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 133.22 | |||||
Maximum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 549.51 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3825.14 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4667.16 | 04-JAN-13:00 | 423.92 | 01-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 3825.14 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5087.92 | 28-FEB-15:00 | 311.29 | 05-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3825.14 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5651.80 | 21-MAR-13:00 | 175.43 | 05-MAR-18:00 |
April | 5400.05 | 01-APR-14:09 | 3825.14 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5215.36 | 01-APR-14:00 | 469.36 | 14-APR-16:00 |
May | 5400.05 | 06-MAY-14:09 | 3825.14 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6161.06 | 06-MAY-13:00 | 233.39 | 21-MAY-13:00 |
June | 5400.05 | 03-JUN-14:09 | 3825.14 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5489.88 | 13-JUN-15:00 | 365.53 | 25-JUN-19:00 |
July | 5400.05 | 01-JUL-14:09 | 3825.14 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4203.86 | 15-JUL-16:00 | 777.18 | 16-JUL-17:00 |
August | 5400.05 | 05-AUG-14:09 | 3825.14 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4616.83 | 27-AUG-14:00 | 822.98 | 20-AUG-11:10 |
September | 5400.05 | 02-SEP-14:09 | 3825.14 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4601.97 | 06-SEP-14:00 | 833.22 | 03-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 3825.14 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4164.05 | 04-OCT-14:00 | 662.03 | 09-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 3825.14 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4719.01 | 18-NOV-13:00 | 887.13 | 26-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 3825.14 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4140.04 | 07-DEC-14:00 | 619.53 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4140.04 | 175.43 | |||||
Maximum of Months | 5400.05 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6161.06 | 887.13 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2661.66 | 04-JAN-13:00 | 229.61 | 01-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2900.06 | 28-FEB-15:00 | 146.20 | 21-FEB-10:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3223.19 | 21-MAR-13:00 | 76.31 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2977.67 | 01-APR-14:00 | 267.91 | 14-APR-16:00 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 06-MAY-13:00 | 133.22 | 21-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3130.85 | 13-JUN-15:00 | 195.49 | 25-JUN-19:00 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.71 | 15-JUL-16:00 | 421.98 | 16-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.96 | 27-AUG-14:00 | 469.34 | 20-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2625.67 | 06-SEP-14:00 | 452.46 | 03-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2375.81 | 04-OCT-14:00 | 356.59 | 09-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.67 | 18-NOV-13:00 | 490.35 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 07-DEC-14:00 | 342.35 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 76.31 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 490.35 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2661.66 | 04-JAN-13:00 | 226.34 | 01-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2900.06 | 28-FEB-15:00 | 146.20 | 21-FEB-10:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3223.19 | 21-MAR-13:00 | 72.31 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2977.67 | 01-APR-14:00 | 267.91 | 14-APR-16:00 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 06-MAY-13:00 | 133.22 | 21-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3130.85 | 13-JUN-15:00 | 194.45 | 25-JUN-19:00 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.71 | 15-JUL-16:00 | 418.82 | 16-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.96 | 27-AUG-14:00 | 469.34 | 20-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2625.67 | 06-SEP-14:00 | 449.87 | 03-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2375.81 | 04-OCT-14:00 | 353.40 | 09-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.67 | 18-NOV-13:00 | 486.22 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 07-DEC-14:00 | 338.89 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 72.31 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 486.22 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2661.66 | 04-JAN-13:00 | 223.92 | 01-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2900.06 | 28-FEB-15:00 | 146.20 | 21-FEB-10:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3223.19 | 21-MAR-13:00 | 74.33 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2977.67 | 01-APR-14:00 | 267.91 | 14-APR-16:00 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 06-MAY-13:00 | 133.22 | 21-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3130.85 | 13-JUN-15:00 | 195.55 | 25-JUN-19:00 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.71 | 15-JUL-16:00 | 422.68 | 16-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.96 | 27-AUG-14:00 | 469.34 | 20-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2625.67 | 06-SEP-14:00 | 453.70 | 03-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2375.81 | 04-OCT-14:00 | 355.85 | 09-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.67 | 18-NOV-13:00 | 482.65 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 07-DEC-14:00 | 334.02 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 74.33 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 482.65 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2725.54 | 04-JAN-13:00 | 470.86 | 07-JAN-05:00 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2986.04 | 28-FEB-15:00 | 260.23 | 05-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3300.56 | 21-MAR-13:00 | 171.74 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3013.69 | 01-APR-14:00 | 271.80 | 14-APR-16:00 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.92 | 06-MAY-13:00 | 207.31 | 08-MAY-22:00 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3206.00 | 13-JUN-15:00 | 306.34 | 25-JUN-19:00 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2438.23 | 28-JUL-13:00 | 535.86 | 16-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2696.15 | 27-AUG-14:00 | 480.61 | 20-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2676.25 | 06-SEP-14:00 | 587.94 | 03-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2421.57 | 04-OCT-14:00 | 475.21 | 09-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2732.71 | 18-NOV-13:00 | 540.28 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2397.44 | 07-DEC-14:00 | 398.30 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2397.44 | 171.74 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.92 | 587.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 42335.91 | 24-JAN-08:62 | 1687.52 | 1588.13 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.12 |
February | 42752.29 | 21-FEB-08:61 | 2700.03 | 2541.00 | 597.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.84 | 0.00 |
March | 39167.00 | 04-MAR-08:62 | 0.00 | 1905.75 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 137.53 | 0.00 |
April | 35539.11 | 27-APR-07:01 | 2362.52 | 2223.38 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 95.42 | 0.00 |
May | 33073.30 | 11-MAY-07:01 | 2362.52 | 2223.38 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 63.94 | 0.00 |
June | 34868.57 | 25-JUN-07:01 | 2362.52 | 2223.38 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 13.51 | 0.00 |
July | 39056.24 | 09-JUL-07:01 | 2700.03 | 2541.00 | 597.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.25 | 0.00 |
August | 35030.86 | 24-AUG-07:01 | 2362.52 | 2223.38 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 20.74 | 0.00 |
September | 35768.57 | 10-SEP-07:01 | 2362.52 | 2223.38 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 73.15 | 0.00 |
October | 35670.51 | 08-OCT-07:01 | 2362.52 | 2223.38 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 30.55 | 0.00 |
November | 39991.97 | 25-NOV-08:62 | 0.00 | 1905.75 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.39 |
December | 40429.72 | 27-DEC-08:62 | 2025.02 | 1905.75 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 33073.30 | 0.00 | 1588.13 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42752.29 | 2700.03 | 2541.00 | 597.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.53 | 318.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23910.88 | 16-JAN-08:61 | 1181.23 | 1305.75 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.77 |
February | 24502.03 | 21-FEB-08:61 | 1349.97 | 1492.28 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 30.08 | 0.00 |
March | 22723.95 | 03-MAR-08:62 | 0.00 | 1119.21 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 52.15 | 0.00 |
April | 20968.38 | 23-APR-07:01 | 1181.23 | 1305.75 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 | 0.00 |
May | 20604.14 | 12-MAY-07:02 | 0.00 | 1119.21 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 25.59 | 0.00 |
June | 21350.40 | 25-JUN-07:01 | 1181.23 | 1305.75 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 10.49 | 0.00 |
July | 22722.70 | 08-JUL-07:01 | 0.00 | 1305.75 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.08 |
August | 21242.23 | 24-AUG-07:01 | 1181.23 | 1305.75 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 17.21 | 0.00 |
September | 21294.88 | 18-SEP-07:01 | 1181.23 | 1305.75 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.48 |
October | 21660.08 | 09-OCT-07:01 | 1349.97 | 1492.28 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 |
November | 23318.49 | 25-NOV-08:62 | 0.00 | 1119.21 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.16 |
December | 23359.96 | 27-DEC-08:62 | 1012.48 | 1119.21 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20604.14 | 0.00 | 1119.21 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24502.03 | 1349.97 | 1492.28 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 52.15 | 112.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19849.46 | 24-JAN-07:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 |
February | 21043.08 | 25-FEB-07:01 | 0.00 | 1172.09 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 |
March | 19278.40 | 04-MAR-07:02 | 0.00 | 1004.64 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
April | 17513.93 | 27-APR-06:01 | 0.00 | 1339.53 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 0.00 |
May | 15675.51 | 11-MAY-06:01 | 0.00 | 1172.09 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 |
June | 15810.66 | 27-JUN-06:01 | 0.00 | 1172.09 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.55 |
July | 17451.28 | 14-JUL-06:01 | 0.00 | 1172.09 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.44 |
August | 16091.37 | 24-AUG-06:01 | 0.00 | 1172.09 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
September | 15752.79 | 13-SEP-06:01 | 0.00 | 1172.09 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 |
October | 16048.27 | 11-OCT-06:01 | 0.00 | 1172.09 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 |
November | 19000.26 | 25-NOV-07:02 | 0.00 | 1004.64 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.31 |
December | 20641.32 | 21-DEC-07:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15675.51 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21043.08 | 0.00 | 1339.53 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 14.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19926.40 | 24-JAN-07:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.15 |
February | 21131.55 | 25-FEB-07:01 | 0.00 | 1172.09 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 |
March | 19334.13 | 04-MAR-07:02 | 0.00 | 1004.64 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
April | 17592.26 | 27-APR-06:01 | 0.00 | 1339.53 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | 0.00 |
May | 15771.09 | 09-MAY-06:01 | 0.00 | 1339.53 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
June | 15890.48 | 27-JUN-06:01 | 0.00 | 1172.09 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 |
July | 17534.64 | 14-JUL-06:01 | 0.00 | 1172.09 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 |
August | 16139.70 | 24-AUG-06:01 | 0.00 | 1172.09 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
September | 15859.81 | 06-SEP-06:01 | 0.00 | 1339.53 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 |
October | 16132.37 | 11-OCT-06:01 | 0.00 | 1172.09 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 |
November | 19080.64 | 25-NOV-07:02 | 0.00 | 1004.64 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.38 |
December | 20679.01 | 21-DEC-07:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15771.09 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21131.55 | 0.00 | 1339.53 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | 14.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19660.89 | 24-JAN-07:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.05 |
February | 20837.02 | 25-FEB-07:01 | 0.00 | 1172.09 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 |
March | 19048.38 | 04-MAR-07:02 | 0.00 | 1004.64 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 | 0.00 |
April | 17276.48 | 27-APR-06:01 | 0.00 | 1339.53 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 | 0.00 |
May | 15518.85 | 09-MAY-06:01 | 0.00 | 1339.53 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 15635.31 | 27-JUN-06:01 | 0.00 | 1172.09 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.45 |
July | 17247.81 | 14-JUL-06:01 | 0.00 | 1172.09 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.29 |
August | 15834.49 | 24-AUG-06:01 | 0.00 | 1172.09 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
September | 15602.58 | 06-SEP-06:01 | 0.00 | 1339.53 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
October | 15874.13 | 11-OCT-06:01 | 0.00 | 1172.09 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
November | 18813.85 | 25-NOV-07:02 | 0.00 | 1004.64 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 |
December | 20404.74 | 21-DEC-07:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15518.85 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20837.02 | 0.00 | 1339.53 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 | 14.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36487.93 | 24-JAN-08:62 | 0.00 | 1006.52 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.18 |
February | 37497.92 | 25-FEB-08:61 | 0.00 | 1409.12 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 99.44 | 0.00 |
March | 34573.51 | 04-MAR-08:62 | 0.00 | 1207.82 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 128.52 | 0.00 |
April | 31535.36 | 27-APR-07:01 | 0.00 | 1409.12 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 102.55 | 0.00 |
May | 29513.24 | 09-MAY-07:01 | 0.00 | 1409.12 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.49 |
June | 30707.14 | 20-JUN-07:01 | 0.00 | 1409.12 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.73 |
July | 32940.87 | 06-JUL-07:01 | 0.00 | 1409.12 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 22.04 | 0.00 |
August | 29717.59 | 24-AUG-07:01 | 0.00 | 1409.12 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 31.12 | 0.00 |
September | 29873.74 | 06-SEP-07:01 | 0.00 | 1409.12 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 91.24 | 0.00 |
October | 30294.77 | 11-OCT-07:02 | 0.00 | 1207.82 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.40 |
November | 34737.90 | 25-NOV-08:62 | 0.00 | 1207.82 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.17 |
December | 36261.67 | 27-DEC-08:62 | 0.00 | 1207.82 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 29513.24 | 0.00 | 1006.52 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37497.92 | 0.00 | 1409.12 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 128.52 | 324.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19023.62 | 24-JAN-08:62 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.78 |
February | 19573.07 | 25-FEB-08:61 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 61.07 | 0.00 |
March | 18059.11 | 04-MAR-08:62 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 76.44 | 0.00 |
April | 16492.11 | 27-APR-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 62.51 | 0.00 |
May | 15420.90 | 09-MAY-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.23 |
June | 16050.43 | 20-JUN-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.15 |
July | 17220.63 | 06-JUL-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 16.80 | 0.00 |
August | 15556.76 | 24-AUG-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 22.02 | 0.00 |
September | 15648.17 | 06-SEP-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 55.71 | 0.00 |
October | 15850.66 | 11-OCT-07:02 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.58 |
November | 18103.89 | 25-NOV-08:62 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.67 |
December | 18921.26 | 27-DEC-08:62 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15420.90 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19573.07 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 76.44 | 179.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18909.66 | 24-JAN-08:62 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.88 |
February | 19458.86 | 25-FEB-08:61 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 61.88 | 0.00 |
March | 17950.89 | 04-MAR-08:62 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 77.35 | 0.00 |
April | 16387.04 | 27-APR-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 63.27 | 0.00 |
May | 15326.12 | 09-MAY-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.57 |
June | 15953.86 | 20-JUN-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.71 |
July | 17116.25 | 06-JUL-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 17.34 | 0.00 |
August | 15446.44 | 24-AUG-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 22.82 | 0.00 |
September | 15555.38 | 06-SEP-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 56.06 | 0.00 |
October | 15744.87 | 11-OCT-07:02 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.89 |
November | 17992.52 | 25-NOV-08:62 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.83 |
December | 18803.36 | 27-DEC-08:62 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15326.12 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19458.86 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 77.35 | 178.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18897.33 | 24-JAN-08:62 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.74 |
February | 19471.40 | 25-FEB-08:61 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 64.41 | 0.00 |
March | 17919.55 | 04-MAR-08:62 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 81.13 | 0.00 |
April | 16419.19 | 27-APR-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 64.89 | 0.00 |
May | 15359.96 | 09-MAY-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.89 |
June | 16017.01 | 20-JUN-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.69 |
July | 17157.51 | 06-JUL-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 18.82 | 0.00 |
August | 15470.22 | 24-AUG-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 24.76 | 0.00 |
September | 15625.38 | 06-SEP-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 56.75 | 0.00 |
October | 15751.02 | 11-OCT-07:02 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.57 |
November | 18000.73 | 25-NOV-08:62 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.44 |
December | 18803.79 | 27-DEC-08:62 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15359.96 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19471.40 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 81.13 | 175.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20598.48 | 28-JAN-08:62 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.34 |
February | 22333.13 | 23-FEB-08:61 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.96 |
March | 19702.41 | 04-MAR-08:62 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 93.75 | 0.00 |
April | 17646.86 | 27-APR-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 | 0.00 |
May | 16849.32 | 11-MAY-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 47.36 | 0.00 |
June | 17635.51 | 20-JUN-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.94 |
July | 19750.09 | 11-JUL-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.51 |
August | 17394.33 | 24-AUG-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 24.56 | 0.00 |
September | 17636.63 | 12-SEP-07:01 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 22.21 | 0.00 |
October | 17484.14 | 11-OCT-07:02 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 |
November | 20100.22 | 25-NOV-08:62 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.02 |
December | 20760.48 | 27-DEC-08:62 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16849.32 | 0.00 | 620.16 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22333.13 | 0.00 | 723.51 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 93.75 | 120.34 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.130833E+12 | 114358.61 | 12-JAN-13:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.122717E+12 | 116809.48 | 28-FEB-14:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.140191E+12 | 119998.16 | 27-MAR-12:39 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.141011E+12 | 125301.28 | 01-APR-14:39 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.151703E+12 | 133962.14 | 06-MAY-15:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.149970E+12 | 138287.20 | 16-JUN-12:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.134970E+12 | 113858.37 | 15-JUL-15:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.144149E+12 | 131973.43 | 13-AUG-14:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.137537E+12 | 125316.44 | 30-SEP-11:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.137105E+12 | 118732.42 | 28-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.130640E+12 | 116698.66 | 18-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.130491E+12 | 114467.31 | 30-DEC-13:39 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.165132E+13 | 0.00 | ||||
Minimum of Months | 0.122717E+12 | 113858.37 | 0.00 | 0.00 | ||
Maximum of Months | 0.151703E+12 | 138287.20 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.420288E+11 | 0.905859E+10 | 0.108325E+11 | 0.00 | 0.979686E+10 | 0.00 | 0.00 | 0.542047E+11 | 0.00 | 0.00 | 0.00 | 0.491158E+10 | 0.00 |
February | 0.380395E+11 | 0.802933E+10 | 0.980803E+10 | 0.00 | 0.931031E+10 | 0.00 | 0.00 | 0.530951E+11 | 0.00 | 0.00 | 0.00 | 0.443514E+10 | 0.00 |
March | 0.426243E+11 | 0.856276E+10 | 0.110075E+11 | 0.00 | 0.106432E+11 | 0.00 | 0.00 | 0.624319E+11 | 0.00 | 0.00 | 0.00 | 0.492160E+10 | 0.00 |
April | 0.407637E+11 | 0.804976E+10 | 0.105079E+11 | 0.00 | 0.108270E+11 | 0.00 | 0.00 | 0.661403E+11 | 0.00 | 0.00 | 0.00 | 0.472203E+10 | 0.00 |
May | 0.423184E+11 | 0.814570E+10 | 0.109147E+11 | 0.00 | 0.118851E+11 | 0.00 | 0.00 | 0.735751E+11 | 0.00 | 0.00 | 0.00 | 0.486429E+10 | 0.00 |
June | 0.411980E+11 | 0.777172E+10 | 0.106386E+11 | 0.00 | 0.119160E+11 | 0.00 | 0.00 | 0.737380E+11 | 0.00 | 0.00 | 0.00 | 0.470785E+10 | 0.00 |
July | 0.419004E+11 | 0.810863E+10 | 0.107945E+11 | 0.00 | 0.102511E+11 | 0.00 | 0.00 | 0.590845E+11 | 0.00 | 0.00 | 0.00 | 0.483112E+10 | 0.00 |
August | 0.426079E+11 | 0.823375E+10 | 0.110006E+11 | 0.00 | 0.111673E+11 | 0.00 | 0.00 | 0.662679E+11 | 0.00 | 0.00 | 0.00 | 0.487181E+10 | 0.00 |
September | 0.407800E+11 | 0.821658E+10 | 0.105148E+11 | 0.00 | 0.106127E+11 | 0.00 | 0.00 | 0.627054E+11 | 0.00 | 0.00 | 0.00 | 0.470799E+10 | 0.00 |
October | 0.420288E+11 | 0.875738E+10 | 0.108325E+11 | 0.00 | 0.104619E+11 | 0.00 | 0.00 | 0.601474E+11 | 0.00 | 0.00 | 0.00 | 0.487697E+10 | 0.00 |
November | 0.407147E+11 | 0.872429E+10 | 0.104978E+11 | 0.00 | 0.984480E+10 | 0.00 | 0.00 | 0.561169E+11 | 0.00 | 0.00 | 0.00 | 0.474111E+10 | 0.00 |
December | 0.419167E+11 | 0.912968E+10 | 0.108050E+11 | 0.00 | 0.977868E+10 | 0.00 | 0.00 | 0.539545E+11 | 0.00 | 0.00 | 0.00 | 0.490642E+10 | 0.00 |
Annual Sum or Average | 0.496921E+12 | 0.100788E+12 | 0.128154E+12 | 0.00 | 0.126495E+12 | 0.00 | 0.00 | 0.741462E+12 | 0.00 | 0.00 | 0.00 | 0.574979E+11 | 0.00 |
Minimum of Months | 0.380395E+11 | 0.777172E+10 | 0.980803E+10 | 0.00 | 0.931031E+10 | 0.00 | 0.00 | 0.530951E+11 | 0.00 | 0.00 | 0.00 | 0.443514E+10 | 0.00 |
Maximum of Months | 0.426243E+11 | 0.912968E+10 | 0.110075E+11 | 0.00 | 0.119160E+11 | 0.00 | 0.00 | 0.737380E+11 | 0.00 | 0.00 | 0.00 | 0.492160E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30804.00 | 01-JAN-11:09 | 7723.25 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 8893.20 | 09-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30804.00 | 01-FEB-10:09 | 7723.25 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 9867.18 | 15-FEB-13:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 30804.00 | 01-MAR-10:09 | 7723.25 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 10337.42 | 27-MAR-12:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 30804.00 | 01-APR-09:09 | 7723.25 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 10961.66 | 02-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 30804.00 | 01-MAY-09:09 | 7723.25 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 12442.90 | 04-MAY-12:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 30804.00 | 01-JUN-09:09 | 7723.25 | 01-JUN-05:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 12866.73 | 16-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 30804.00 | 01-JUL-09:09 | 7723.25 | 01-JUL-05:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 9507.12 | 28-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 30804.00 | 01-AUG-09:09 | 7723.25 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 12016.42 | 13-AUG-14:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 30804.00 | 01-SEP-09:09 | 7723.25 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 11183.18 | 30-SEP-11:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 30804.00 | 01-OCT-10:09 | 7723.25 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 10296.18 | 28-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30804.00 | 01-NOV-09:09 | 7723.25 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 9686.03 | 10-NOV-13:39 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30804.00 | 01-DEC-10:09 | 7723.25 | 01-DEC-17:30 | 8059.50 | 01-DEC-10:09 | 0.00 | 9135.03 | 30-DEC-13:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30804.00 | 7723.25 | 8059.50 | 0.00 | 8893.20 | 0.00 | 0.00 | |||||
Maximum of Months | 30804.00 | 7723.25 | 8059.50 | 0.00 | 12866.73 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 58298.25 | 12-JAN-13:09 | 0.00 | 0.00 | 0.00 | 11769.61 | 02-JAN-13:20 | 0.00 |
February | 65030.32 | 15-FEB-13:00 | 0.00 | 0.00 | 0.00 | 7546.03 | 01-FEB-13:39 | 0.00 |
March | 67556.34 | 27-MAR-12:00 | 0.00 | 0.00 | 0.00 | 8352.44 | 17-MAR-13:20 | 0.00 |
April | 71681.43 | 01-APR-13:00 | 0.00 | 0.00 | 0.00 | 7529.69 | 26-APR-11:30 | 0.00 |
May | 80429.06 | 04-MAY-12:00 | 0.00 | 0.00 | 0.00 | 7524.32 | 01-MAY-16:40 | 0.00 |
June | 82170.95 | 16-JUN-12:00 | 0.00 | 0.00 | 0.00 | 7540.16 | 07-JUN-12:39 | 0.00 |
July | 62453.83 | 28-JUL-12:00 | 0.00 | 0.00 | 0.00 | 7539.39 | 12-JUL-12:00 | 0.00 |
August | 75757.52 | 13-AUG-14:30 | 0.00 | 0.00 | 0.00 | 8626.76 | 30-AUG-09:30 | 0.00 |
September | 70545.95 | 30-SEP-11:39 | 0.00 | 0.00 | 0.00 | 8258.58 | 16-SEP-15:00 | 0.00 |
October | 66252.09 | 28-OCT-12:00 | 0.00 | 0.00 | 0.00 | 8020.01 | 06-OCT-12:39 | 0.00 |
November | 62995.28 | 18-NOV-12:00 | 0.00 | 0.00 | 0.00 | 7543.51 | 27-NOV-14:50 | 0.00 |
December | 59794.68 | 30-DEC-13:00 | 0.00 | 0.00 | 0.00 | 7545.77 | 16-DEC-13:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 58298.25 | 0.00 | 0.00 | 0.00 | 7524.32 | 0.00 | ||
Maximum of Months | 82170.95 | 0.00 | 0.00 | 0.00 | 11769.61 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 114358.61 | 12-JAN-13:00 | 30804.00 | 8059.50 | 0.00 | 0.00 | 8370.97 | 0.00 | 0.00 | 55354.53 | 0.00 |
February | 116809.48 | 28-FEB-14:50 | 30804.00 | 8059.50 | 0.00 | 0.00 | 9352.14 | 0.00 | 0.00 | 63161.27 | 0.00 |
March | 119998.16 | 27-MAR-12:39 | 30804.00 | 8059.50 | 0.00 | 0.00 | 10031.15 | 0.00 | 0.00 | 65670.73 | 0.00 |
April | 125301.28 | 01-APR-14:39 | 30804.00 | 8059.50 | 0.00 | 0.00 | 10702.62 | 0.00 | 0.00 | 70312.66 | 0.00 |
May | 133962.14 | 06-MAY-15:09 | 30804.00 | 8059.50 | 0.00 | 0.00 | 11881.07 | 0.00 | 0.00 | 77798.54 | 0.00 |
June | 138287.20 | 16-JUN-12:50 | 30804.00 | 8059.50 | 0.00 | 0.00 | 12725.44 | 0.00 | 0.00 | 81266.92 | 0.00 |
July | 113858.37 | 15-JUL-15:39 | 30804.00 | 8059.50 | 0.00 | 0.00 | 9092.19 | 0.00 | 0.00 | 60483.53 | 0.00 |
August | 131973.43 | 13-AUG-14:09 | 30804.00 | 8059.50 | 0.00 | 0.00 | 12004.77 | 0.00 | 0.00 | 75696.21 | 0.00 |
September | 125316.44 | 30-SEP-11:30 | 30804.00 | 8059.50 | 0.00 | 0.00 | 11069.05 | 0.00 | 0.00 | 69958.57 | 0.00 |
October | 118732.42 | 28-OCT-12:00 | 30804.00 | 8059.50 | 0.00 | 0.00 | 10296.18 | 0.00 | 0.00 | 66252.09 | 0.00 |
November | 116698.66 | 18-NOV-12:00 | 30804.00 | 8059.50 | 0.00 | 0.00 | 9418.41 | 0.00 | 0.00 | 62995.28 | 0.00 |
December | 114467.31 | 30-DEC-13:39 | 30804.00 | 8059.50 | 0.00 | 0.00 | 9053.73 | 0.00 | 0.00 | 59344.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 113858.37 | 30804.00 | 8059.50 | 0.00 | 0.00 | 8370.97 | 0.00 | 0.00 | 55354.53 | 0.00 | |
Maximum of Months | 138287.20 | 30804.00 | 8059.50 | 0.00 | 0.00 | 12725.44 | 0.00 | 0.00 | 81266.92 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.49 | 1.33 | 24.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.50 | 1.33 | 24.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.50 | 24.49 | 2.67 | 24.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.50 | 1.33 | 24.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.55 | 0.00 | 24.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.66 | 0.00 | 24.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.61 | 0.00 | 24.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 24.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.55 | 0.00 | 24.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.56 | 0.00 | 24.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 24.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.83 | 24.60 | 0.00 | 24.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.66 | 0.00 | 24.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 24.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.59 | 0.00 | 24.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.68 | 0.00 | 24.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.63 | 0.00 | 24.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.46 | 0.00 | 24.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.56 | 0.00 | 24.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.57 | 0.00 | 24.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.46 | 0.00 | 24.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.33 | 24.61 | 0.00 | 24.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.68 | 0.00 | 24.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 24.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.52 | 0.00 | 24.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.64 | 0.00 | 24.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.60 | 0.00 | 24.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.57 | 0.00 | 24.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.56 | 0.00 | 24.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 24.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.50 | 24.59 | 0.00 | 24.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.64 | 0.00 | 24.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.56 | 0.00 | 24.56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.00 | 24.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.65 | 0.00 | 24.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.82 | 0.00 | 24.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.65 | 0.00 | 24.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.55 | 0.00 | 24.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.69 | 0.00 | 24.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.62 | 0.00 | 24.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.53 | 0.00 | 24.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.49 | 0.00 | 24.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.56 | 0.00 | 24.56 |
Annual Sum or Average | 0.00 | 0.00 | 9.67 | 24.66 | 0.00 | 24.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.82 | 0.00 | 24.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.51 | 0.00 | 24.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 24.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.63 | 0.00 | 24.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.86 | 0.00 | 24.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.67 | 0.00 | 24.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.49 | 0.00 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.65 | 0.00 | 24.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.59 | 0.00 | 24.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.49 | 0.00 | 24.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.49 | 0.00 | 24.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.58 | 0.00 | 24.58 |
Annual Sum or Average | 0.00 | 0.00 | 7.83 | 24.66 | 0.00 | 24.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.86 | 0.00 | 24.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.51 | 0.00 | 24.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 24.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.63 | 0.00 | 24.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.86 | 0.00 | 24.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.69 | 0.00 | 24.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.49 | 0.00 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.64 | 0.00 | 24.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.59 | 0.00 | 24.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.48 | 0.00 | 24.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.48 | 0.00 | 24.48 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.57 | 0.00 | 24.57 |
Annual Sum or Average | 0.00 | 0.00 | 7.67 | 24.66 | 0.00 | 24.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.86 | 0.00 | 24.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.49 | 0.00 | 24.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.62 | 0.00 | 24.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.89 | 0.00 | 24.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.70 | 0.00 | 24.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 24.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.68 | 0.00 | 24.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.57 | 0.00 | 24.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.49 | 0.00 | 24.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.46 | 0.00 | 24.46 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.55 | 0.00 | 24.55 |
Annual Sum or Average | 0.00 | 0.00 | 6.50 | 24.68 | 0.00 | 24.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.89 | 0.00 | 24.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.57 | 0.00 | 24.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.50 | 0.00 | 24.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.72 | 0.00 | 24.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.91 | 0.00 | 24.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.78 | 0.00 | 24.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.48 | 0.00 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.75 | 0.00 | 24.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.63 | 0.00 | 24.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.53 | 0.00 | 24.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.50 | 0.00 | 24.50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.59 | 0.00 | 24.59 |
Annual Sum or Average | 0.00 | 0.00 | 10.67 | 24.73 | 0.00 | 24.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.91 | 0.00 | 24.91 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.17 | 23.90 | 496.00 | 23.89 | 18.17 | 23.89 |
February | 12.17 | 23.91 | 448.00 | 23.89 | 12.17 | 23.89 |
March | 30.33 | 23.92 | 497.00 | 23.89 | 30.33 | 23.90 |
April | 152.83 | 23.90 | 479.00 | 23.89 | 152.83 | 23.90 |
May | 326.17 | 23.90 | 496.00 | 23.89 | 326.17 | 23.90 |
June | 323.67 | 23.90 | 481.00 | 23.89 | 323.67 | 23.89 |
July | 131.33 | 23.89 | 495.00 | 23.89 | 131.33 | 23.89 |
August | 371.50 | 23.89 | 497.00 | 23.89 | 371.50 | 23.89 |
September | 315.17 | 23.89 | 479.00 | 23.89 | 315.17 | 23.89 |
October | 325.17 | 23.89 | 496.00 | 23.89 | 325.17 | 23.89 |
November | 171.00 | 23.90 | 480.00 | 23.89 | 171.00 | 23.89 |
December | 67.83 | 23.90 | 496.00 | 23.89 | 67.83 | 23.89 |
Annual Sum or Average | 2245.33 | 23.90 | 5840.00 | 23.89 | 2245.33 | 23.89 |
Minimum of Months | 12.17 | 23.89 | 448.00 | 23.89 | 12.17 | 23.89 |
Maximum of Months | 371.50 | 23.92 | 497.00 | 23.89 | 371.50 | 23.90 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.00 | 23.89 | 495.83 | 23.89 | 6.00 | 23.89 |
February | 9.83 | 23.89 | 447.50 | 23.89 | 9.83 | 23.89 |
March | 5.00 | 23.89 | 496.50 | 23.89 | 5.00 | 23.89 |
April | 127.67 | 23.89 | 479.00 | 23.89 | 127.67 | 23.89 |
May | 269.67 | 23.89 | 496.00 | 23.89 | 269.67 | 23.89 |
June | 271.00 | 23.89 | 481.00 | 23.89 | 271.00 | 23.89 |
July | 104.00 | 23.89 | 495.00 | 23.89 | 104.00 | 23.89 |
August | 311.50 | 23.89 | 497.00 | 23.89 | 311.50 | 23.89 |
September | 263.67 | 23.89 | 479.00 | 23.89 | 263.67 | 23.89 |
October | 259.67 | 23.89 | 496.00 | 23.89 | 259.67 | 23.89 |
November | 134.67 | 23.89 | 480.00 | 23.89 | 134.67 | 23.89 |
December | 40.33 | 23.89 | 493.67 | 23.89 | 40.33 | 23.89 |
Annual Sum or Average | 1803.00 | 23.89 | 5836.50 | 23.89 | 1803.00 | 23.89 |
Minimum of Months | 5.00 | 23.89 | 447.50 | 23.89 | 5.00 | 23.89 |
Maximum of Months | 311.50 | 23.89 | 497.00 | 23.89 | 311.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.67 | 25.53 | 371.00 | 24.22 | 32.67 | 24.32 |
February | 34.17 | 25.35 | 336.00 | 24.23 | 34.17 | 24.32 |
March | 39.33 | 25.42 | 379.00 | 24.23 | 39.33 | 24.33 |
April | 168.67 | 24.36 | 360.00 | 24.20 | 168.67 | 24.24 |
May | 294.17 | 24.18 | 375.00 | 24.15 | 294.17 | 24.16 |
June | 297.00 | 24.17 | 366.00 | 24.15 | 297.00 | 24.15 |
July | 162.00 | 24.35 | 369.00 | 24.18 | 162.00 | 24.22 |
August | 346.00 | 24.11 | 379.00 | 24.10 | 346.00 | 24.10 |
September | 302.33 | 24.14 | 360.00 | 24.12 | 302.33 | 24.13 |
October | 297.33 | 24.14 | 371.00 | 24.11 | 297.33 | 24.12 |
November | 181.50 | 24.26 | 360.00 | 24.14 | 181.50 | 24.17 |
December | 77.50 | 24.64 | 369.00 | 24.18 | 77.50 | 24.25 |
Annual Sum or Average | 2232.67 | 24.27 | 4395.00 | 24.16 | 2232.67 | 24.19 |
Minimum of Months | 32.67 | 24.11 | 336.00 | 24.10 | 32.67 | 24.10 |
Maximum of Months | 346.00 | 25.53 | 379.00 | 24.23 | 346.00 | 24.33 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.50 | 25.54 | 371.00 | 24.22 | 32.50 | 24.32 |
February | 33.83 | 25.37 | 336.00 | 24.23 | 33.83 | 24.32 |
March | 38.83 | 25.44 | 379.00 | 24.23 | 38.83 | 24.33 |
April | 166.83 | 24.36 | 360.00 | 24.20 | 166.83 | 24.24 |
May | 292.50 | 24.18 | 375.00 | 24.15 | 292.50 | 24.16 |
June | 294.33 | 24.18 | 366.00 | 24.15 | 294.33 | 24.16 |
July | 159.33 | 24.36 | 369.00 | 24.19 | 159.33 | 24.23 |
August | 344.67 | 24.11 | 379.00 | 24.10 | 344.67 | 24.10 |
September | 298.67 | 24.15 | 360.00 | 24.12 | 298.67 | 24.13 |
October | 293.83 | 24.14 | 371.00 | 24.12 | 293.83 | 24.12 |
November | 180.50 | 24.27 | 360.00 | 24.14 | 180.50 | 24.17 |
December | 77.33 | 24.64 | 369.00 | 24.18 | 77.33 | 24.25 |
Annual Sum or Average | 2213.17 | 24.27 | 4395.00 | 24.16 | 2213.17 | 24.19 |
Minimum of Months | 32.50 | 24.11 | 336.00 | 24.10 | 32.50 | 24.10 |
Maximum of Months | 344.67 | 25.54 | 379.00 | 24.23 | 344.67 | 24.33 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 35.50 | 25.41 | 371.00 | 24.21 | 35.50 | 24.31 |
February | 37.33 | 25.18 | 336.00 | 24.22 | 37.33 | 24.30 |
March | 42.17 | 25.32 | 379.00 | 24.22 | 42.17 | 24.32 |
April | 175.83 | 24.33 | 360.00 | 24.19 | 175.83 | 24.23 |
May | 298.17 | 24.17 | 375.00 | 24.14 | 298.17 | 24.15 |
June | 303.50 | 24.16 | 366.00 | 24.14 | 303.50 | 24.15 |
July | 167.33 | 24.33 | 369.00 | 24.18 | 167.33 | 24.21 |
August | 350.67 | 24.10 | 379.00 | 24.09 | 350.67 | 24.10 |
September | 308.50 | 24.13 | 360.00 | 24.11 | 308.50 | 24.12 |
October | 303.33 | 24.13 | 371.00 | 24.11 | 303.33 | 24.12 |
November | 190.17 | 24.24 | 360.00 | 24.14 | 190.17 | 24.16 |
December | 82.50 | 24.59 | 369.00 | 24.17 | 82.50 | 24.24 |
Annual Sum or Average | 2295.00 | 24.25 | 4395.00 | 24.15 | 2295.00 | 24.18 |
Minimum of Months | 35.50 | 24.10 | 336.00 | 24.09 | 35.50 | 24.10 |
Maximum of Months | 350.67 | 25.41 | 379.00 | 24.22 | 350.67 | 24.32 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.00 | 24.48 | 340.00 | 24.03 | 42.00 | 24.07 |
February | 49.83 | 24.38 | 308.00 | 24.03 | 49.83 | 24.08 |
March | 42.83 | 24.43 | 348.00 | 24.01 | 42.83 | 24.05 |
April | 211.17 | 24.03 | 330.00 | 24.00 | 211.17 | 24.01 |
May | 306.67 | 23.99 | 344.00 | 23.98 | 306.67 | 23.98 |
June | 322.33 | 23.97 | 336.00 | 23.97 | 322.33 | 23.97 |
July | 211.33 | 24.05 | 338.00 | 24.01 | 211.33 | 24.02 |
August | 346.17 | 23.95 | 348.00 | 23.95 | 346.17 | 23.95 |
September | 318.83 | 23.98 | 330.00 | 23.97 | 318.83 | 23.97 |
October | 327.00 | 23.97 | 340.00 | 23.97 | 327.00 | 23.97 |
November | 229.50 | 23.98 | 330.00 | 23.96 | 229.50 | 23.97 |
December | 94.33 | 24.17 | 338.00 | 24.02 | 94.33 | 24.04 |
Annual Sum or Average | 2502.00 | 24.02 | 4030.00 | 23.99 | 2502.00 | 23.99 |
Minimum of Months | 42.00 | 23.95 | 308.00 | 23.95 | 42.00 | 23.95 |
Maximum of Months | 346.17 | 24.48 | 348.00 | 24.03 | 346.17 | 24.08 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.50 | 24.44 | 340.00 | 24.02 | 42.50 | 24.06 |
February | 54.83 | 24.33 | 308.00 | 24.03 | 54.83 | 24.07 |
March | 45.17 | 24.40 | 348.00 | 24.01 | 45.17 | 24.05 |
April | 220.00 | 24.03 | 330.00 | 24.00 | 220.00 | 24.01 |
May | 307.33 | 23.98 | 344.00 | 23.98 | 307.33 | 23.98 |
June | 321.50 | 23.97 | 336.00 | 23.97 | 321.50 | 23.97 |
July | 218.00 | 24.04 | 338.00 | 24.01 | 218.00 | 24.02 |
August | 346.17 | 23.95 | 348.00 | 23.95 | 346.17 | 23.95 |
September | 318.17 | 23.97 | 330.00 | 23.97 | 318.17 | 23.97 |
October | 327.17 | 23.97 | 340.00 | 23.97 | 327.17 | 23.97 |
November | 232.00 | 23.98 | 330.00 | 23.96 | 232.00 | 23.97 |
December | 100.83 | 24.15 | 338.00 | 24.01 | 100.83 | 24.04 |
Annual Sum or Average | 2533.67 | 24.01 | 4030.00 | 23.99 | 2533.67 | 23.99 |
Minimum of Months | 42.50 | 23.95 | 308.00 | 23.95 | 42.50 | 23.95 |
Maximum of Months | 346.17 | 24.44 | 348.00 | 24.03 | 346.17 | 24.07 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 44.67 | 24.41 | 340.00 | 24.02 | 44.67 | 24.06 |
February | 55.67 | 24.32 | 308.00 | 24.03 | 55.67 | 24.07 |
March | 47.17 | 24.37 | 348.00 | 24.01 | 47.17 | 24.05 |
April | 222.67 | 24.03 | 330.00 | 24.00 | 222.67 | 24.01 |
May | 308.33 | 23.98 | 344.00 | 23.98 | 308.33 | 23.98 |
June | 322.17 | 23.97 | 336.00 | 23.97 | 322.17 | 23.97 |
July | 220.33 | 24.04 | 338.00 | 24.01 | 220.33 | 24.02 |
August | 346.17 | 23.95 | 348.00 | 23.95 | 346.17 | 23.95 |
September | 318.67 | 23.97 | 330.00 | 23.97 | 318.67 | 23.97 |
October | 327.83 | 23.97 | 340.00 | 23.97 | 327.83 | 23.97 |
November | 233.50 | 23.98 | 330.00 | 23.96 | 233.50 | 23.97 |
December | 102.17 | 24.15 | 338.00 | 24.01 | 102.17 | 24.04 |
Annual Sum or Average | 2549.33 | 24.01 | 4030.00 | 23.98 | 2549.33 | 23.99 |
Minimum of Months | 44.67 | 23.95 | 308.00 | 23.95 | 44.67 | 23.95 |
Maximum of Months | 346.17 | 24.41 | 348.00 | 24.03 | 346.17 | 24.07 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 45.00 | 24.41 | 340.00 | 24.02 | 45.00 | 24.06 |
February | 55.33 | 24.32 | 308.00 | 24.03 | 55.33 | 24.07 |
March | 45.83 | 24.39 | 348.00 | 24.01 | 45.83 | 24.05 |
April | 218.33 | 24.03 | 330.00 | 24.00 | 218.33 | 24.01 |
May | 305.83 | 23.98 | 344.00 | 23.98 | 305.83 | 23.98 |
June | 320.50 | 23.97 | 336.00 | 23.97 | 320.50 | 23.97 |
July | 217.67 | 24.04 | 338.00 | 24.01 | 217.67 | 24.02 |
August | 346.00 | 23.95 | 348.00 | 23.95 | 346.00 | 23.95 |
September | 317.67 | 23.97 | 330.00 | 23.97 | 317.67 | 23.97 |
October | 327.67 | 23.97 | 340.00 | 23.97 | 327.67 | 23.97 |
November | 233.50 | 23.98 | 330.00 | 23.96 | 233.50 | 23.97 |
December | 102.50 | 24.15 | 338.00 | 24.01 | 102.50 | 24.04 |
Annual Sum or Average | 2535.83 | 24.01 | 4030.00 | 23.99 | 2535.83 | 23.99 |
Minimum of Months | 45.00 | 23.95 | 308.00 | 23.95 | 45.00 | 23.95 |
Maximum of Months | 346.00 | 24.41 | 348.00 | 24.03 | 346.00 | 24.07 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.83 | 25.08 | 340.00 | 24.05 | 22.83 | 24.11 |
February | 24.33 | 25.00 | 308.00 | 24.06 | 24.33 | 24.12 |
March | 18.67 | 25.19 | 348.00 | 24.03 | 18.67 | 24.09 |
April | 118.17 | 24.17 | 330.00 | 24.04 | 118.17 | 24.07 |
May | 246.50 | 24.02 | 344.00 | 24.00 | 246.50 | 24.00 |
June | 249.50 | 24.00 | 336.00 | 23.98 | 249.50 | 23.99 |
July | 131.00 | 24.16 | 338.00 | 24.04 | 131.00 | 24.07 |
August | 307.50 | 23.97 | 348.00 | 23.96 | 307.50 | 23.96 |
September | 267.33 | 24.00 | 330.00 | 23.99 | 267.33 | 23.99 |
October | 283.33 | 23.99 | 340.00 | 23.98 | 283.33 | 23.99 |
November | 183.17 | 24.01 | 330.00 | 23.98 | 183.17 | 23.99 |
December | 68.67 | 24.31 | 338.00 | 24.03 | 68.67 | 24.07 |
Annual Sum or Average | 1921.00 | 24.07 | 4030.00 | 24.01 | 1921.00 | 24.02 |
Minimum of Months | 18.67 | 23.97 | 308.00 | 23.96 | 18.67 | 23.96 |
Maximum of Months | 307.50 | 25.19 | 348.00 | 24.06 | 307.50 | 24.12 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.89089 | 57.58377 | 0.65723 | 14.13321 |
February | 448.00000 | 23.89114 | 57.75417 | 0.66737 | 14.43082 |
March | 497.00000 | 23.89220 | 58.78111 | 0.67679 | 14.69479 |
April | 479.00000 | 23.89298 | 63.03758 | 0.70960 | 15.64654 |
May | 496.00000 | 23.89396 | 66.49257 | -0.0929 | 5.28526 |
June | 481.00000 | 23.89383 | 66.20527 | -0.0826 | 5.26879 |
July | 495.00000 | 23.89198 | 62.23680 | -0.1368 | 5.48708 |
August | 497.00000 | 23.89266 | 67.57213 | -0.1132 | 5.38520 |
September | 479.00000 | 23.89240 | 66.29421 | -0.1128 | 5.37702 |
October | 496.00000 | 23.89206 | 66.22778 | 0.70454 | 15.50449 |
November | 480.00000 | 23.89237 | 63.35443 | 0.69131 | 15.10950 |
December | 496.00000 | 23.89098 | 59.85451 | 0.66695 | 14.40995 |
Annual Sum or Average | 5840.00000 | 23.89229 | 62.97296 | 0.35094 | 10.87108 |
Minimum of Months | 448.00000 | 23.89089 | 57.58377 | -0.1368 | 5.26879 |
Maximum of Months | 497.00000 | 23.89396 | 67.57213 | 0.70960 | 15.64654 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.89036 | 54.73693 | 0.61514 | 13.03535 |
February | 448.00000 | 23.89073 | 55.15893 | 0.62341 | 13.26467 |
March | 497.00000 | 23.89152 | 56.36722 | 0.63090 | 13.45173 |
April | 479.00000 | 23.89241 | 60.49426 | 0.66212 | 14.30445 |
May | 496.00000 | 23.89298 | 63.73631 | -0.1505 | 5.61259 |
June | 481.00000 | 23.89262 | 63.57486 | -0.1429 | 5.59152 |
July | 495.00000 | 23.89138 | 59.46015 | -0.1917 | 5.90639 |
August | 497.00000 | 23.89203 | 64.55651 | -0.1673 | 5.74805 |
September | 479.00000 | 23.89160 | 63.31914 | -0.1688 | 5.75643 |
October | 496.00000 | 23.89140 | 62.86113 | 0.66137 | 14.31543 |
November | 480.00000 | 23.89180 | 60.19881 | 0.64825 | 13.93893 |
December | 496.00000 | 23.89055 | 56.61885 | 0.62360 | 13.27092 |
Annual Sum or Average | 5840.00000 | 23.89162 | 60.11120 | 0.30158 | 10.33050 |
Minimum of Months | 448.00000 | 23.89036 | 54.73693 | -0.1917 | 5.59152 |
Maximum of Months | 497.00000 | 23.89298 | 64.55651 | 0.66212 | 14.31543 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 24.10301 | 57.46739 | 0.68296 | 15.08642 |
February | 336.00000 | 24.11278 | 57.88800 | 0.69317 | 15.42060 |
March | 379.00000 | 24.10614 | 58.96367 | 0.69623 | 15.49908 |
April | 360.00000 | 24.12317 | 63.66346 | 0.73381 | 16.69604 |
May | 375.00000 | 24.12021 | 67.20301 | -0.0587 | 5.78171 |
June | 366.00000 | 24.12171 | 67.22268 | -0.0479 | 5.76682 |
July | 369.00000 | 24.10897 | 63.32238 | -0.1019 | 5.82825 |
August | 379.00000 | 24.09122 | 68.77472 | -0.0808 | 5.68846 |
September | 360.00000 | 24.10216 | 67.59128 | -0.0778 | 5.72790 |
October | 371.00000 | 24.09244 | 67.28712 | 0.73551 | 16.67576 |
November | 360.00000 | 24.08298 | 63.83357 | 0.71695 | 16.07561 |
December | 369.00000 | 24.08672 | 59.74342 | 0.69091 | 15.30995 |
Annual Sum or Average | 4395.00000 | 24.10422 | 63.61658 | 0.37871 | 11.58903 |
Minimum of Months | 336.00000 | 24.08298 | 57.46739 | -0.1019 | 5.68846 |
Maximum of Months | 379.00000 | 24.12317 | 68.77472 | 0.73551 | 16.69604 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 24.10313 | 57.42240 | 0.68355 | 15.10418 |
February | 336.00000 | 24.11298 | 57.84051 | 0.69389 | 15.44251 |
March | 379.00000 | 24.10629 | 58.91644 | 0.69689 | 15.51961 |
April | 360.00000 | 24.12349 | 63.59551 | 0.73460 | 16.72242 |
May | 375.00000 | 24.12062 | 67.11427 | -0.0571 | 5.78298 |
June | 366.00000 | 24.12209 | 67.13619 | -0.0464 | 5.76875 |
July | 369.00000 | 24.10929 | 63.24401 | -0.1005 | 5.82592 |
August | 379.00000 | 24.09128 | 68.72646 | -0.0801 | 5.68849 |
September | 360.00000 | 24.10232 | 67.52971 | -0.0768 | 5.72777 |
October | 371.00000 | 24.09253 | 67.23346 | 0.73599 | 16.69165 |
November | 360.00000 | 24.08290 | 63.80498 | 0.71726 | 16.08517 |
December | 369.00000 | 24.08664 | 59.71520 | 0.69123 | 15.31961 |
Annual Sum or Average | 4395.00000 | 24.10439 | 63.55971 | 0.37956 | 11.59914 |
Minimum of Months | 336.00000 | 24.08290 | 57.42240 | -0.1005 | 5.68849 |
Maximum of Months | 379.00000 | 24.12349 | 68.72646 | 0.73599 | 16.72242 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 24.09907 | 57.65826 | 0.68084 | 15.01504 |
February | 336.00000 | 24.10897 | 58.06938 | 0.69119 | 15.35257 |
March | 379.00000 | 24.10235 | 59.15467 | 0.69422 | 15.43027 |
April | 360.00000 | 24.11965 | 63.86031 | 0.73226 | 16.63815 |
May | 375.00000 | 24.11689 | 67.38491 | -0.0607 | 5.76745 |
June | 366.00000 | 24.11834 | 67.40666 | -0.0500 | 5.75082 |
July | 369.00000 | 24.10550 | 63.51841 | -0.1044 | 5.81996 |
August | 379.00000 | 24.08734 | 69.06166 | -0.0840 | 5.67977 |
September | 360.00000 | 24.09839 | 67.84737 | -0.0806 | 5.71750 |
October | 371.00000 | 24.08855 | 67.55714 | 0.73387 | 16.61498 |
November | 360.00000 | 24.07892 | 64.09708 | 0.71492 | 16.00391 |
December | 369.00000 | 24.08260 | 59.97839 | 0.68855 | 15.23166 |
Annual Sum or Average | 4395.00000 | 24.10047 | 63.83627 | 0.37652 | 11.54471 |
Minimum of Months | 336.00000 | 24.07892 | 57.65826 | -0.1044 | 5.67977 |
Maximum of Months | 379.00000 | 24.11965 | 69.06166 | 0.73387 | 16.63815 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.97128 | 59.22109 | 0.66001 | 14.30419 |
February | 308.00000 | 23.97690 | 59.73962 | 0.67107 | 14.65709 |
March | 348.00000 | 23.96016 | 60.77389 | 0.67160 | 14.64466 |
April | 330.00000 | 23.98363 | 65.54888 | 0.71066 | 15.83224 |
May | 344.00000 | 23.97512 | 69.01986 | -0.0959 | 5.59315 |
June | 336.00000 | 23.96472 | 69.05145 | -0.0867 | 5.52403 |
July | 338.00000 | 23.98837 | 65.24002 | -0.1333 | 5.75580 |
August | 348.00000 | 23.95193 | 70.96867 | -0.1199 | 5.58894 |
September | 330.00000 | 23.97299 | 69.66451 | -0.1129 | 5.61137 |
October | 340.00000 | 23.96816 | 69.41888 | 0.71387 | 15.89145 |
November | 330.00000 | 23.95360 | 65.92413 | 0.69384 | 15.25224 |
December | 338.00000 | 23.97145 | 61.57083 | 0.66930 | 14.58427 |
Annual Sum or Average | 4030.00000 | 23.96975 | 65.54972 | 0.35014 | 11.06374 |
Minimum of Months | 308.00000 | 23.95193 | 59.22109 | -0.1333 | 5.52403 |
Maximum of Months | 348.00000 | 23.98837 | 70.96867 | 0.71387 | 15.89145 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.97041 | 59.29603 | 0.64002 | 13.75279 |
February | 308.00000 | 23.97549 | 59.82582 | 0.65031 | 14.07413 |
March | 348.00000 | 23.95938 | 60.84813 | 0.65090 | 14.06194 |
April | 330.00000 | 23.98243 | 65.69463 | 0.69038 | 15.22971 |
May | 344.00000 | 23.97416 | 69.22773 | -0.1245 | 5.71515 |
June | 336.00000 | 23.96415 | 69.29110 | -0.1164 | 5.64374 |
July | 338.00000 | 23.98686 | 65.42359 | -0.1614 | 5.91692 |
August | 348.00000 | 23.95101 | 71.22837 | -0.1458 | 5.72186 |
September | 330.00000 | 23.97189 | 69.91423 | -0.1398 | 5.74443 |
October | 340.00000 | 23.96714 | 69.66047 | 0.69619 | 15.36116 |
November | 330.00000 | 23.95292 | 66.12296 | 0.67534 | 14.71562 |
December | 338.00000 | 23.97060 | 61.70015 | 0.65017 | 14.05025 |
Annual Sum or Average | 4030.00000 | 23.96876 | 65.72448 | 0.32710 | 10.79582 |
Minimum of Months | 308.00000 | 23.95101 | 59.29603 | -0.1614 | 5.64374 |
Maximum of Months | 348.00000 | 23.98686 | 71.22837 | 0.69619 | 15.36116 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.97002 | 59.37603 | 0.63867 | 13.71468 |
February | 308.00000 | 23.97513 | 59.89994 | 0.64904 | 14.03774 |
March | 348.00000 | 23.95912 | 60.92008 | 0.64971 | 14.02819 |
April | 330.00000 | 23.98211 | 65.77066 | 0.68931 | 15.19701 |
May | 344.00000 | 23.97389 | 69.31062 | -0.1262 | 5.72141 |
June | 336.00000 | 23.96390 | 69.37504 | -0.1181 | 5.64986 |
July | 338.00000 | 23.98651 | 65.50477 | -0.1631 | 5.92584 |
August | 348.00000 | 23.95076 | 71.32233 | -0.1475 | 5.72997 |
September | 330.00000 | 23.97157 | 70.00385 | -0.1415 | 5.75170 |
October | 340.00000 | 23.96681 | 69.76031 | 0.69512 | 15.32828 |
November | 330.00000 | 23.95260 | 66.21916 | 0.67417 | 14.68103 |
December | 338.00000 | 23.97018 | 61.78893 | 0.64884 | 14.01204 |
Annual Sum or Average | 4030.00000 | 23.96844 | 65.80941 | 0.32568 | 10.77851 |
Minimum of Months | 308.00000 | 23.95076 | 59.37603 | -0.1631 | 5.64986 |
Maximum of Months | 348.00000 | 23.98651 | 71.32233 | 0.69512 | 15.32828 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.96996 | 59.37239 | 0.64099 | 13.77796 |
February | 308.00000 | 23.97529 | 59.85746 | 0.65194 | 14.11880 |
March | 348.00000 | 23.95930 | 60.85991 | 0.65291 | 14.11826 |
April | 330.00000 | 23.98239 | 65.66374 | 0.69292 | 15.30460 |
May | 344.00000 | 23.97418 | 69.21510 | -0.1211 | 5.70130 |
June | 336.00000 | 23.96411 | 69.25520 | -0.1128 | 5.62879 |
July | 338.00000 | 23.98679 | 65.42796 | -0.1584 | 5.89894 |
August | 348.00000 | 23.95082 | 71.25388 | -0.1431 | 5.70762 |
September | 330.00000 | 23.97175 | 69.91883 | -0.1368 | 5.72887 |
October | 340.00000 | 23.96684 | 69.75094 | 0.69758 | 15.40202 |
November | 330.00000 | 23.95251 | 66.21065 | 0.67653 | 14.74887 |
December | 338.00000 | 23.97000 | 61.79961 | 0.65095 | 14.07051 |
Annual Sum or Average | 4030.00000 | 23.96855 | 65.75386 | 0.32928 | 10.81379 |
Minimum of Months | 308.00000 | 23.95082 | 59.37239 | -0.1584 | 5.62879 |
Maximum of Months | 348.00000 | 23.98679 | 71.25388 | 0.69758 | 15.40202 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.97762 | 57.79843 | 0.67522 | 14.76046 |
February | 308.00000 | 23.98435 | 57.99999 | 0.69145 | 15.27722 |
March | 348.00000 | 23.96702 | 58.92244 | 0.69542 | 15.37227 |
April | 330.00000 | 23.99224 | 63.22356 | 0.73711 | 16.68144 |
May | 344.00000 | 23.98271 | 66.94840 | -0.0587 | 5.58029 |
June | 336.00000 | 23.97155 | 66.68556 | -0.0456 | 5.50065 |
July | 338.00000 | 23.99844 | 63.24116 | -0.0987 | 5.68955 |
August | 348.00000 | 23.95732 | 68.95313 | -0.0881 | 5.54236 |
September | 330.00000 | 23.98159 | 67.47702 | -0.0779 | 5.57165 |
October | 340.00000 | 23.97519 | 67.89387 | 0.72692 | 16.32916 |
November | 330.00000 | 23.95865 | 64.36635 | 0.70653 | 15.65331 |
December | 338.00000 | 23.97785 | 60.18544 | 0.68258 | 14.99113 |
Annual Sum or Average | 4030.00000 | 23.97692 | 63.67915 | 0.37558 | 11.37002 |
Minimum of Months | 308.00000 | 23.95732 | 57.79843 | -0.0987 | 5.50065 |
Maximum of Months | 348.00000 | 23.99844 | 68.95313 | 0.73711 | 16.68144 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.447425E+11 | 0.111346E+11 | 499.72 | 0.283259E+11 | 0.164166E+11 | 0.00 | 1.00 | 01-JAN-08:61 | 0.00 | 01-JAN-00:03 | 68646.50 | 10-JAN-08:61 | 45800.11 | 24-JAN-08:62 | 31346.62 | 10-JAN-08:03 | 15542.52 | 11-JAN-08:61 | 0.00 | 01-JAN-00:03 |
February | 0.433619E+11 | 0.108718E+11 | 452.48 | 0.274864E+11 | 0.158755E+11 | 0.00 | 1.00 | 01-FEB-08:61 | 0.00 | 01-FEB-00:03 | 68395.96 | 16-FEB-08:61 | 47692.76 | 21-FEB-08:61 | 30151.74 | 16-FEB-08:03 | 15168.47 | 18-FEB-08:61 | 0.00 | 01-FEB-00:03 |
March | 0.504549E+11 | 0.126907E+11 | 504.57 | 0.315596E+11 | 0.188953E+11 | 0.00 | 1.00 | 01-MAR-08:61 | 0.00 | 01-MAR-00:03 | 69433.25 | 28-MAR-07:01 | 44953.13 | 04-MAR-08:62 | 33617.06 | 27-MAR-07:04 | 15250.27 | 30-MAR-07:01 | 0.00 | 01-MAR-00:03 |
April | 0.552384E+11 | 0.136003E+11 | 486.69 | 0.314718E+11 | 0.237666E+11 | 0.00 | 1.00 | 01-APR-07:01 | 0.00 | 01-APR-00:03 | 69664.15 | 12-APR-07:01 | 40631.31 | 27-APR-07:01 | 34243.99 | 01-APR-07:03 | 15379.39 | 11-APR-07:03 | 0.00 | 01-APR-00:03 |
May | 0.616471E+11 | 0.148905E+11 | 503.00 | 0.324104E+11 | 0.292366E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 70962.53 | 19-MAY-07:01 | 37849.48 | 11-MAY-07:01 | 41605.71 | 22-MAY-07:04 | 16063.49 | 28-MAY-07:04 | 0.00 | 01-MAY-00:10 |
June | 0.614259E+11 | 0.147989E+11 | 489.18 | 0.321730E+11 | 0.292529E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 70935.92 | 11-JUN-07:01 | 39355.52 | 25-JUN-07:01 | 40350.28 | 10-JUN-07:05 | 15573.19 | 15-JUN-07:13 | 0.00 | 01-JUN-00:10 |
July | 0.505521E+11 | 0.122573E+11 | 501.12 | 0.287333E+11 | 0.218188E+11 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 69247.63 | 01-JUL-07:02 | 43884.43 | 09-JUL-07:01 | 33827.83 | 01-JUL-07:03 | 15094.66 | 15-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.565095E+11 | 0.133920E+11 | 503.37 | 0.285185E+11 | 0.279910E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 70915.80 | 11-AUG-07:01 | 39588.39 | 24-AUG-07:01 | 39140.34 | 11-AUG-07:04 | 15425.30 | 09-AUG-07:04 | 0.00 | 01-AUG-00:10 |
September | 0.539763E+11 | 0.128577E+11 | 487.03 | 0.281104E+11 | 0.258659E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 70026.47 | 01-SEP-07:01 | 40758.52 | 10-SEP-07:01 | 35930.88 | 01-SEP-07:03 | 15318.05 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 |
October | 0.518810E+11 | 0.123312E+11 | 501.45 | 0.270058E+11 | 0.248753E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 69515.45 | 14-OCT-07:02 | 40300.65 | 08-OCT-07:01 | 35337.22 | 14-OCT-07:03 | 15261.82 | 05-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.478105E+11 | 0.115108E+11 | 484.96 | 0.264943E+11 | 0.213162E+11 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 69092.60 | 12-NOV-08:61 | 43661.15 | 25-NOV-08:62 | 32718.86 | 12-NOV-08:03 | 15249.96 | 14-NOV-08:03 | 0.00 | 01-NOV-00:10 |
December | 0.454951E+11 | 0.111601E+11 | 502.37 | 0.273267E+11 | 0.181683E+11 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-01:05 | 68433.95 | 30-DEC-08:61 | 44778.24 | 27-DEC-08:62 | 30436.25 | 01-DEC-08:62 | 15191.33 | 09-DEC-08:61 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.623095E+12 | 0.151496E+12 | 5915.92 | 0.349616E+12 | 0.273479E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.433619E+11 | 0.108718E+11 | 452.48 | 0.264943E+11 | 0.158755E+11 | 0.00 | 1.00 | 0.00 | 68395.96 | 37849.48 | 30151.74 | 15094.66 | 0.00 | |||||||
Maximum of Months | 0.616471E+11 | 0.148905E+11 | 504.57 | 0.324104E+11 | 0.292529E+11 | 0.00 | 1.00 | 0.00 | 70962.53 | 47692.76 | 41605.71 | 16063.49 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.221220E+11 | 0.544478E+10 | 500.08 | 0.144222E+11 | 0.769985E+10 | 0.00 | 1.00 | 01-JAN-08:61 | 0.00 | 01-JAN-00:03 | 33803.28 | 10-JAN-08:61 | 26070.53 | 23-JAN-08:62 | 11391.76 | 10-JAN-08:03 | 7749.57 | 11-JAN-08:61 | 0.00 | 01-JAN-00:03 |
February | 0.212692E+11 | 0.527867E+10 | 453.13 | 0.138247E+11 | 0.744451E+10 | 0.00 | 1.00 | 01-FEB-08:61 | 0.00 | 01-FEB-00:03 | 33712.65 | 16-FEB-08:61 | 27276.98 | 21-FEB-08:61 | 11009.69 | 16-FEB-08:03 | 7535.13 | 18-FEB-08:61 | 0.00 | 01-FEB-00:03 |
March | 0.245288E+11 | 0.612100E+10 | 503.99 | 0.157336E+11 | 0.879518E+10 | 0.00 | 1.00 | 01-MAR-08:61 | 0.00 | 01-MAR-00:03 | 34174.18 | 28-MAR-07:01 | 25871.99 | 03-MAR-08:62 | 12458.91 | 28-MAR-07:03 | 7621.15 | 30-MAR-07:01 | 0.00 | 01-MAR-00:03 |
April | 0.266533E+11 | 0.652740E+10 | 486.85 | 0.156220E+11 | 0.110314E+11 | 0.00 | 1.00 | 01-APR-07:01 | 0.00 | 01-APR-00:03 | 34300.59 | 12-APR-07:01 | 23922.49 | 28-APR-07:01 | 12772.52 | 12-APR-07:02 | 7696.65 | 11-APR-07:01 | 0.00 | 01-APR-00:03 |
May | 0.299138E+11 | 0.718665E+10 | 502.89 | 0.162440E+11 | 0.136699E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 35111.84 | 22-MAY-07:01 | 23487.31 | 12-MAY-07:02 | 15875.78 | 22-MAY-07:03 | 8084.89 | 28-MAY-07:04 | 0.00 | 01-MAY-00:10 |
June | 0.298065E+11 | 0.713636E+10 | 488.76 | 0.160900E+11 | 0.137165E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 35135.48 | 14-JUN-07:01 | 23978.91 | 25-JUN-07:01 | 16068.54 | 11-JUN-07:12 | 7812.46 | 15-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.246774E+11 | 0.593236E+10 | 500.94 | 0.144493E+11 | 0.102280E+11 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 33846.31 | 01-JUL-07:02 | 25324.64 | 08-JUL-07:01 | 11253.05 | 01-JUL-07:02 | 7518.24 | 15-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.276084E+11 | 0.648946E+10 | 503.44 | 0.144064E+11 | 0.132020E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 34804.88 | 13-AUG-07:01 | 23913.90 | 24-AUG-07:01 | 14543.11 | 13-AUG-07:02 | 7741.37 | 09-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.262955E+11 | 0.621661E+10 | 487.07 | 0.141561E+11 | 0.121393E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 34152.16 | 03-SEP-07:01 | 24092.67 | 15-SEP-07:02 | 12671.35 | 01-SEP-07:03 | 7678.36 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 |
October | 0.255324E+11 | 0.601018E+10 | 501.93 | 0.137870E+11 | 0.117454E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 34082.65 | 05-OCT-07:01 | 24206.46 | 08-OCT-07:01 | 12282.41 | 05-OCT-07:03 | 7638.13 | 05-OCT-07:01 | 0.00 | 01-OCT-00:10 |
November | 0.235463E+11 | 0.561233E+10 | 484.54 | 0.135134E+11 | 0.100329E+11 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 33741.38 | 12-NOV-08:61 | 25817.05 | 24-NOV-08:61 | 11508.20 | 10-NOV-13:30 | 7612.68 | 14-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.224989E+11 | 0.546173E+10 | 502.92 | 0.140031E+11 | 0.849581E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-01:05 | 33525.80 | 10-DEC-08:61 | 25892.52 | 27-DEC-08:62 | 10469.51 | 10-DEC-18:00 | 7559.72 | 09-DEC-08:61 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.304453E+12 | 0.734175E+11 | 5916.57 | 0.176252E+12 | 0.128201E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.212692E+11 | 0.527867E+10 | 453.13 | 0.135134E+11 | 0.744451E+10 | 0.00 | 1.00 | 0.00 | 33525.80 | 23487.31 | 10469.51 | 7518.24 | 0.00 | |||||||
Maximum of Months | 0.299138E+11 | 0.718665E+10 | 503.99 | 0.162440E+11 | 0.137165E+11 | 0.00 | 1.00 | 0.00 | 35135.48 | 27276.98 | 16068.54 | 8084.89 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.180302E+11 | 0.439223E+10 | 367.08 | 0.114728E+11 | 0.655747E+10 | 0.00 | 1.00 | 01-JAN-08:61 | 0.00 | 01-JAN-00:03 | 35926.03 | 02-JAN-07:01 | 21359.70 | 24-JAN-07:02 | 19850.07 | 02-JAN-07:03 | 7444.23 | 11-JAN-07:01 | 0.00 | 01-JAN-00:03 |
February | 0.174841E+11 | 0.429255E+10 | 332.20 | 0.110971E+11 | 0.638708E+10 | 0.00 | 1.00 | 01-FEB-07:01 | 0.00 | 01-FEB-00:03 | 35651.32 | 06-FEB-07:01 | 22855.03 | 25-FEB-07:01 | 18636.23 | 06-FEB-07:03 | 7505.11 | 18-FEB-07:01 | 0.00 | 01-FEB-00:03 |
March | 0.204908E+11 | 0.506451E+10 | 377.54 | 0.128288E+11 | 0.766202E+10 | 0.00 | 1.00 | 01-MAR-07:01 | 0.00 | 01-MAR-00:03 | 36117.42 | 27-MAR-06:01 | 21785.08 | 04-MAR-07:02 | 19670.50 | 27-MAR-06:04 | 7568.41 | 26-MAR-07:04 | 0.00 | 01-MAR-00:03 |
April | 0.220651E+11 | 0.533207E+10 | 359.23 | 0.125176E+11 | 0.954747E+10 | 0.00 | 1.00 | 01-APR-06:01 | 0.00 | 01-APR-00:03 | 36198.19 | 10-APR-06:01 | 19711.31 | 27-APR-06:01 | 21763.79 | 03-APR-06:05 | 7646.77 | 30-APR-07:13 | 0.00 | 01-APR-00:03 |
May | 0.251592E+11 | 0.595801E+10 | 374.47 | 0.131336E+11 | 0.120256E+11 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 36240.02 | 17-MAY-06:01 | 17481.81 | 11-MAY-06:01 | 24891.33 | 22-MAY-06:01 | 7987.45 | 28-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.252657E+11 | 0.596930E+10 | 365.54 | 0.131010E+11 | 0.121647E+11 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 36236.03 | 26-JUN-06:01 | 17388.78 | 27-JUN-06:01 | 23654.29 | 05-JUN-06:04 | 7651.99 | 18-JUN-07:13 | 0.00 | 01-JUN-00:10 |
July | 0.201913E+11 | 0.477318E+10 | 367.90 | 0.113022E+11 | 0.888911E+10 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:05 | 36184.21 | 02-JUL-07:01 | 19523.22 | 06-JUL-06:01 | 20452.87 | 02-JUL-07:04 | 7516.31 | 09-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.233292E+11 | 0.539942E+10 | 378.04 | 0.115951E+11 | 0.117341E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 36238.06 | 21-AUG-06:02 | 17920.68 | 24-AUG-06:01 | 23357.96 | 14-AUG-06:05 | 7597.56 | 13-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.218589E+11 | 0.508443E+10 | 358.96 | 0.112134E+11 | 0.106455E+11 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:05 | 36238.65 | 18-SEP-06:03 | 17788.30 | 13-SEP-06:01 | 22779.02 | 05-SEP-06:05 | 7587.09 | 03-SEP-07:13 | 0.00 | 01-SEP-00:05 |
October | 0.211564E+11 | 0.490022E+10 | 369.63 | 0.108756E+11 | 0.102808E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 36239.54 | 02-OCT-06:01 | 17860.47 | 11-OCT-06:01 | 21741.14 | 16-OCT-06:04 | 7524.05 | 05-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.194246E+11 | 0.456860E+10 | 357.78 | 0.107597E+11 | 0.866488E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 36235.78 | 20-NOV-07:01 | 20503.59 | 25-NOV-07:02 | 21756.60 | 13-NOV-07:04 | 7576.76 | 23-NOV-08:02 | 0.00 | 01-NOV-00:10 |
December | 0.182298E+11 | 0.438310E+10 | 364.10 | 0.110608E+11 | 0.716898E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 36233.05 | 11-DEC-07:01 | 22106.22 | 21-DEC-07:02 | 22045.14 | 11-DEC-07:04 | 7491.63 | 10-DEC-08:04 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.252685E+12 | 0.601176E+11 | 4372.49 | 0.140958E+12 | 0.111728E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.174841E+11 | 0.429255E+10 | 332.20 | 0.107597E+11 | 0.638708E+10 | 0.00 | 1.00 | 0.00 | 35651.32 | 17388.78 | 18636.23 | 7444.23 | 0.00 | |||||||
Maximum of Months | 0.252657E+11 | 0.596930E+10 | 378.04 | 0.131336E+11 | 0.121647E+11 | 0.00 | 1.00 | 0.00 | 36240.02 | 22855.03 | 24891.33 | 7987.45 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.180756E+11 | 0.440322E+10 | 367.08 | 0.115074E+11 | 0.656818E+10 | 0.00 | 1.00 | 01-JAN-08:61 | 0.00 | 01-JAN-00:03 | 36004.99 | 02-JAN-07:01 | 21435.50 | 24-JAN-07:02 | 19851.73 | 02-JAN-07:03 | 7459.15 | 11-JAN-07:01 | 0.00 | 01-JAN-00:03 |
February | 0.175304E+11 | 0.430384E+10 | 332.39 | 0.111329E+11 | 0.639749E+10 | 0.00 | 1.00 | 01-FEB-07:01 | 0.00 | 01-FEB-00:03 | 35733.39 | 06-FEB-07:01 | 22942.83 | 25-FEB-07:01 | 18620.80 | 06-FEB-07:03 | 7520.28 | 18-FEB-07:01 | 0.00 | 01-FEB-00:03 |
March | 0.205413E+11 | 0.507692E+10 | 377.54 | 0.128676E+11 | 0.767379E+10 | 0.00 | 1.00 | 01-MAR-07:01 | 0.00 | 01-MAR-00:03 | 36206.39 | 27-MAR-06:01 | 21847.25 | 04-MAR-07:02 | 19637.55 | 27-MAR-06:04 | 7583.49 | 26-MAR-07:04 | 0.00 | 01-MAR-00:03 |
April | 0.221278E+11 | 0.534702E+10 | 359.17 | 0.125637E+11 | 0.956409E+10 | 0.00 | 1.00 | 01-APR-06:01 | 0.00 | 01-APR-00:03 | 36275.44 | 10-APR-06:01 | 19788.05 | 27-APR-06:01 | 21728.87 | 03-APR-06:05 | 7662.09 | 30-APR-07:13 | 0.00 | 01-APR-00:03 |
May | 0.252431E+11 | 0.597807E+10 | 374.63 | 0.131941E+11 | 0.120490E+11 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 36312.62 | 17-MAY-06:01 | 17554.01 | 11-MAY-06:01 | 24863.44 | 22-MAY-06:01 | 8003.44 | 28-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.253447E+11 | 0.598855E+10 | 365.67 | 0.131585E+11 | 0.121862E+11 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 36308.63 | 26-JUN-06:01 | 17471.91 | 27-JUN-06:01 | 23636.08 | 05-JUN-06:04 | 7667.25 | 18-JUN-07:13 | 0.00 | 01-JUN-00:10 |
July | 0.202610E+11 | 0.478913E+10 | 367.84 | 0.113524E+11 | 0.890853E+10 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:05 | 36256.70 | 02-JUL-07:01 | 19619.06 | 06-JUL-06:01 | 20457.80 | 02-JUL-07:04 | 7531.34 | 09-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.233732E+11 | 0.541011E+10 | 378.15 | 0.116268E+11 | 0.117464E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 36310.65 | 21-AUG-06:02 | 17971.70 | 24-AUG-06:01 | 23330.47 | 14-AUG-06:05 | 7612.78 | 13-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.219123E+11 | 0.509702E+10 | 358.92 | 0.112517E+11 | 0.106606E+11 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:05 | 36311.25 | 18-SEP-06:01 | 17855.22 | 13-SEP-06:01 | 22732.16 | 05-SEP-06:05 | 7602.39 | 03-SEP-07:13 | 0.00 | 01-SEP-00:05 |
October | 0.212036E+11 | 0.491135E+10 | 369.64 | 0.109093E+11 | 0.102943E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 36312.14 | 02-OCT-06:01 | 17948.10 | 11-OCT-06:01 | 21731.67 | 16-OCT-06:04 | 7539.02 | 05-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.194540E+11 | 0.457600E+10 | 357.93 | 0.107821E+11 | 0.867188E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 36308.38 | 20-NOV-07:01 | 20580.44 | 25-NOV-07:02 | 21771.09 | 12-NOV-08:04 | 7591.94 | 23-NOV-08:02 | 0.00 | 01-NOV-00:10 |
December | 0.182584E+11 | 0.439049E+10 | 364.33 | 0.110828E+11 | 0.717561E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 36305.64 | 11-DEC-07:01 | 22151.12 | 21-DEC-07:02 | 22041.84 | 11-DEC-07:04 | 7506.52 | 10-DEC-08:04 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.253325E+12 | 0.602717E+11 | 4373.29 | 0.141429E+12 | 0.111896E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.175304E+11 | 0.430384E+10 | 332.39 | 0.107821E+11 | 0.639749E+10 | 0.00 | 1.00 | 0.00 | 35733.39 | 17471.91 | 18620.80 | 7459.15 | 0.00 | |||||||
Maximum of Months | 0.253447E+11 | 0.598855E+10 | 378.15 | 0.131941E+11 | 0.121862E+11 | 0.00 | 1.00 | 0.00 | 36312.62 | 22942.83 | 24863.44 | 8003.44 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.178435E+11 | 0.434870E+10 | 367.11 | 0.113300E+11 | 0.651358E+10 | 0.00 | 1.00 | 01-JAN-08:61 | 0.00 | 01-JAN-00:03 | 35741.83 | 02-JAN-07:01 | 21156.45 | 24-JAN-07:02 | 19807.38 | 02-JAN-07:03 | 7407.23 | 11-JAN-07:01 | 0.00 | 01-JAN-00:03 |
February | 0.173224E+11 | 0.425367E+10 | 332.45 | 0.109728E+11 | 0.634951E+10 | 0.00 | 1.00 | 01-FEB-07:01 | 0.00 | 01-FEB-00:03 | 35472.03 | 06-FEB-07:01 | 22639.29 | 25-FEB-07:01 | 18573.03 | 06-FEB-07:03 | 7467.75 | 18-FEB-07:01 | 0.00 | 01-FEB-00:03 |
March | 0.202992E+11 | 0.501816E+10 | 377.92 | 0.126829E+11 | 0.761625E+10 | 0.00 | 1.00 | 01-MAR-07:01 | 0.00 | 01-MAR-00:03 | 35942.70 | 27-MAR-06:01 | 21547.37 | 04-MAR-07:02 | 19567.92 | 27-MAR-06:04 | 7530.87 | 26-MAR-07:04 | 0.00 | 01-MAR-00:03 |
April | 0.218829E+11 | 0.528743E+10 | 359.09 | 0.123853E+11 | 0.949768E+10 | 0.00 | 1.00 | 01-APR-06:01 | 0.00 | 01-APR-00:03 | 36013.39 | 10-APR-06:01 | 19476.90 | 27-APR-06:01 | 21657.83 | 03-APR-06:05 | 7608.28 | 30-APR-07:13 | 0.00 | 01-APR-00:03 |
May | 0.249979E+11 | 0.591789E+10 | 374.43 | 0.130205E+11 | 0.119774E+11 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 36060.01 | 17-MAY-06:01 | 17268.31 | 11-MAY-06:01 | 24801.83 | 22-MAY-06:01 | 7947.77 | 28-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.251042E+11 | 0.592919E+10 | 365.57 | 0.129863E+11 | 0.121179E+11 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 36056.04 | 26-JUN-06:03 | 17206.37 | 27-JUN-06:01 | 23566.50 | 05-JUN-06:04 | 7613.82 | 11-JUN-07:12 | 0.00 | 01-JUN-00:10 |
July | 0.200209E+11 | 0.473301E+10 | 367.85 | 0.111787E+11 | 0.884223E+10 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:05 | 36004.48 | 02-JUL-07:01 | 19335.08 | 06-JUL-06:01 | 20433.04 | 02-JUL-07:04 | 7478.98 | 09-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.230997E+11 | 0.534639E+10 | 378.06 | 0.114385E+11 | 0.116612E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 36058.06 | 21-AUG-06:02 | 17666.66 | 24-AUG-06:01 | 23238.93 | 14-AUG-06:05 | 7559.83 | 13-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.216588E+11 | 0.503791E+10 | 359.07 | 0.110745E+11 | 0.105843E+11 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:05 | 36058.65 | 18-SEP-06:01 | 17572.45 | 13-SEP-06:01 | 22651.62 | 05-SEP-06:05 | 7548.52 | 03-SEP-07:13 | 0.00 | 01-SEP-00:05 |
October | 0.209435E+11 | 0.485127E+10 | 369.44 | 0.107284E+11 | 0.102151E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 36059.54 | 02-OCT-06:01 | 17677.96 | 11-OCT-06:01 | 21666.02 | 16-OCT-06:04 | 7486.76 | 05-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.192098E+11 | 0.451950E+10 | 357.88 | 0.106064E+11 | 0.860333E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 36055.80 | 20-NOV-07:01 | 20305.09 | 25-NOV-07:02 | 21743.93 | 12-NOV-08:04 | 7539.13 | 23-NOV-08:02 | 0.00 | 01-NOV-00:10 |
December | 0.180173E+11 | 0.433482E+10 | 364.18 | 0.109026E+11 | 0.711477E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 36053.08 | 11-DEC-07:01 | 21861.79 | 21-DEC-07:02 | 21965.01 | 11-DEC-07:03 | 7454.52 | 10-DEC-08:04 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.250400E+12 | 0.595779E+11 | 4373.04 | 0.139307E+12 | 0.111093E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.173224E+11 | 0.425367E+10 | 332.45 | 0.106064E+11 | 0.634951E+10 | 0.00 | 1.00 | 0.00 | 35472.03 | 17206.37 | 18573.03 | 7407.23 | 0.00 | |||||||
Maximum of Months | 0.251042E+11 | 0.592919E+10 | 378.06 | 0.130205E+11 | 0.121179E+11 | 0.00 | 1.00 | 0.00 | 36060.01 | 22639.29 | 24801.83 | 7947.77 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.319758E+11 | 0.788814E+10 | 356.45 | 0.199808E+11 | 0.119949E+11 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:03 | 63067.62 | 02-JAN-08:62 | 38776.99 | 24-JAN-08:62 | 34945.34 | 02-JAN-08:03 | 13863.40 | 11-JAN-08:61 | 0.00 | 01-JAN-00:03 |
February | 0.311245E+11 | 0.774239E+10 | 323.20 | 0.194049E+11 | 0.117196E+11 | 0.00 | 1.00 | 01-FEB-08:61 | 0.00 | 01-FEB-00:03 | 62576.78 | 06-FEB-08:61 | 42219.10 | 25-FEB-08:61 | 32423.06 | 06-FEB-08:03 | 13722.97 | 20-FEB-09:13 | 0.00 | 01-FEB-00:03 |
March | 0.364637E+11 | 0.913021E+10 | 369.53 | 0.224537E+11 | 0.140099E+11 | 0.00 | 1.00 | 01-MAR-08:61 | 0.00 | 01-MAR-00:03 | 63404.95 | 27-MAR-07:01 | 39546.40 | 04-MAR-08:62 | 34575.00 | 27-MAR-07:05 | 13915.26 | 26-MAR-08:13 | 0.00 | 01-MAR-00:03 |
April | 0.393843E+11 | 0.962796E+10 | 349.05 | 0.219075E+11 | 0.174768E+11 | 0.00 | 1.00 | 01-APR-07:01 | 0.00 | 01-APR-00:03 | 63440.33 | 10-APR-07:02 | 36004.18 | 27-APR-07:01 | 38143.95 | 03-APR-07:05 | 13826.79 | 30-APR-08:13 | 0.00 | 01-APR-00:03 |
May | 0.451327E+11 | 0.108114E+11 | 365.19 | 0.230513E+11 | 0.220814E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 63404.95 | 15-MAY-07:01 | 33282.80 | 31-MAY-07:01 | 43342.53 | 22-MAY-07:01 | 14133.83 | 07-MAY-08:14 | 0.00 | 01-MAY-00:10 |
June | 0.455658E+11 | 0.108942E+11 | 357.41 | 0.231200E+11 | 0.224459E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 63472.48 | 26-JUN-07:04 | 33749.76 | 20-JUN-07:01 | 41419.93 | 05-JUN-07:04 | 13954.68 | 18-JUN-08:14 | 0.00 | 01-JUN-00:10 |
July | 0.357452E+11 | 0.854875E+10 | 355.09 | 0.195593E+11 | 0.161859E+11 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 63462.15 | 05-JUL-07:01 | 36893.46 | 06-JUL-07:01 | 36223.76 | 02-JUL-08:04 | 13598.94 | 30-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.415915E+11 | 0.972961E+10 | 369.75 | 0.200723E+11 | 0.215193E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 63544.28 | 21-AUG-07:02 | 33621.30 | 16-AUG-07:01 | 40553.22 | 14-AUG-07:05 | 13834.53 | 13-AUG-08:12 | 0.00 | 01-AUG-00:10 |
September | 0.388391E+11 | 0.913459E+10 | 348.50 | 0.194022E+11 | 0.194369E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 63616.30 | 18-SEP-07:03 | 34204.82 | 06-SEP-07:01 | 40165.65 | 25-SEP-07:06 | 13741.16 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.374369E+11 | 0.876493E+10 | 358.47 | 0.186934E+11 | 0.187435E+11 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 63615.46 | 23-OCT-07:02 | 34021.33 | 11-OCT-07:02 | 38345.12 | 23-OCT-07:02 | 13710.97 | 29-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.343702E+11 | 0.817482E+10 | 348.94 | 0.185287E+11 | 0.158415E+11 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 63501.41 | 20-NOV-08:61 | 37444.79 | 25-NOV-08:62 | 38307.92 | 12-NOV-09:06 | 13738.93 | 23-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.321369E+11 | 0.781467E+10 | 353.83 | 0.190834E+11 | 0.130535E+11 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 63514.67 | 11-DEC-08:61 | 39727.25 | 27-DEC-08:62 | 38521.09 | 11-DEC-08:04 | 13793.79 | 31-DEC-09:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.449767E+12 | 0.108262E+12 | 4255.42 | 0.245258E+12 | 0.204509E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.311245E+11 | 0.774239E+10 | 323.20 | 0.185287E+11 | 0.117196E+11 | 0.00 | 1.00 | 0.00 | 62576.78 | 33282.80 | 32423.06 | 13598.94 | 0.00 | |||||||
Maximum of Months | 0.455658E+11 | 0.108942E+11 | 369.75 | 0.231200E+11 | 0.224459E+11 | 0.00 | 1.00 | 0.00 | 63616.30 | 42219.10 | 43342.53 | 14133.83 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.166043E+11 | 0.403332E+10 | 357.07 | 0.103872E+11 | 0.621706E+10 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:03 | 33120.75 | 02-JAN-08:62 | 20415.27 | 24-JAN-08:62 | 18422.59 | 02-JAN-08:03 | 7146.08 | 11-JAN-08:61 | 0.00 | 01-JAN-00:03 |
February | 0.161706E+11 | 0.396135E+10 | 324.28 | 0.100893E+11 | 0.608124E+10 | 0.00 | 1.00 | 01-FEB-08:61 | 0.00 | 01-FEB-00:03 | 32852.50 | 06-FEB-08:61 | 22149.47 | 25-FEB-08:61 | 17097.13 | 06-FEB-08:03 | 7073.76 | 20-FEB-09:13 | 0.00 | 01-FEB-00:03 |
March | 0.189350E+11 | 0.467047E+10 | 369.64 | 0.116696E+11 | 0.726543E+10 | 0.00 | 1.00 | 01-MAR-08:61 | 0.00 | 01-MAR-00:03 | 33266.41 | 27-MAR-07:01 | 20762.52 | 04-MAR-08:62 | 18169.74 | 27-MAR-07:04 | 7172.92 | 26-MAR-08:13 | 0.00 | 01-MAR-00:03 |
April | 0.204570E+11 | 0.492809E+10 | 349.15 | 0.113928E+11 | 0.906426E+10 | 0.00 | 1.00 | 01-APR-07:01 | 0.00 | 01-APR-00:03 | 33284.97 | 10-APR-07:02 | 18928.67 | 27-APR-07:01 | 20087.01 | 03-APR-07:05 | 7128.25 | 30-APR-08:13 | 0.00 | 01-APR-00:03 |
May | 0.234314E+11 | 0.552976E+10 | 365.25 | 0.119866E+11 | 0.114449E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 33266.41 | 15-MAY-07:01 | 17550.20 | 31-MAY-07:01 | 22863.09 | 22-MAY-07:01 | 7287.12 | 07-MAY-08:14 | 0.00 | 01-MAY-00:10 |
June | 0.236340E+11 | 0.556600E+10 | 357.59 | 0.120059E+11 | 0.116282E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 33301.84 | 26-JUN-07:03 | 17772.56 | 20-JUN-07:01 | 21867.37 | 05-JUN-07:04 | 7194.53 | 18-JUN-08:14 | 0.00 | 01-JUN-00:10 |
July | 0.185467E+11 | 0.436872E+10 | 355.98 | 0.101619E+11 | 0.838482E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 33337.81 | 05-JUL-07:01 | 19405.51 | 06-JUL-07:01 | 19069.83 | 02-JUL-08:04 | 7009.85 | 30-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.215623E+11 | 0.496956E+10 | 369.70 | 0.104240E+11 | 0.111383E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 33339.52 | 21-AUG-07:02 | 17690.46 | 24-AUG-07:01 | 21344.47 | 14-AUG-07:05 | 7131.27 | 13-AUG-08:12 | 0.00 | 01-AUG-00:10 |
September | 0.201505E+11 | 0.466846E+10 | 348.62 | 0.100813E+11 | 0.100692E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 33377.30 | 18-SEP-07:01 | 18009.55 | 06-SEP-07:01 | 21136.12 | 25-SEP-07:06 | 7083.40 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.194209E+11 | 0.447853E+10 | 359.07 | 0.971299E+10 | 0.970792E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 33376.86 | 23-OCT-07:02 | 17928.59 | 11-OCT-07:02 | 20210.99 | 16-OCT-07:04 | 7067.80 | 29-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.178280E+11 | 0.417687E+10 | 349.11 | 0.962459E+10 | 0.820345E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 33317.02 | 20-NOV-08:61 | 19686.55 | 25-NOV-08:62 | 20193.11 | 12-NOV-09:04 | 7081.96 | 23-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.166793E+11 | 0.399434E+10 | 355.35 | 0.991589E+10 | 0.676342E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 33323.98 | 11-DEC-08:61 | 20887.56 | 27-DEC-08:62 | 20365.12 | 11-DEC-08:04 | 7110.35 | 31-DEC-09:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.233420E+12 | 0.553455E+11 | 4260.81 | 0.127452E+12 | 0.105968E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.161706E+11 | 0.396135E+10 | 324.28 | 0.962459E+10 | 0.608124E+10 | 0.00 | 1.00 | 0.00 | 32852.50 | 17550.20 | 17097.13 | 7009.85 | 0.00 | |||||||
Maximum of Months | 0.236340E+11 | 0.556600E+10 | 369.70 | 0.120059E+11 | 0.116282E+11 | 0.00 | 1.00 | 0.00 | 33377.30 | 22149.47 | 22863.09 | 7287.12 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.165279E+11 | 0.401438E+10 | 357.21 | 0.103302E+11 | 0.619763E+10 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:03 | 32977.96 | 02-JAN-08:62 | 20287.55 | 24-JAN-08:62 | 18363.11 | 02-JAN-08:03 | 7115.61 | 11-JAN-08:61 | 0.00 | 01-JAN-00:03 |
February | 0.161058E+11 | 0.394487E+10 | 324.30 | 0.100407E+11 | 0.606513E+10 | 0.00 | 1.00 | 01-FEB-08:61 | 0.00 | 01-FEB-00:03 | 32710.67 | 06-FEB-08:61 | 22023.37 | 25-FEB-08:61 | 17040.30 | 06-FEB-08:03 | 7043.59 | 20-FEB-09:13 | 0.00 | 01-FEB-00:03 |
March | 0.188645E+11 | 0.465217E+10 | 369.64 | 0.116172E+11 | 0.724728E+10 | 0.00 | 1.00 | 01-MAR-08:61 | 0.00 | 01-MAR-00:03 | 33124.51 | 27-MAR-07:01 | 20642.05 | 04-MAR-08:62 | 18103.49 | 27-MAR-07:04 | 7142.29 | 26-MAR-08:13 | 0.00 | 01-MAR-00:03 |
April | 0.203915E+11 | 0.491094E+10 | 349.17 | 0.113456E+11 | 0.904592E+10 | 0.00 | 1.00 | 01-APR-07:01 | 0.00 | 01-APR-00:03 | 33143.00 | 10-APR-07:02 | 18813.58 | 27-APR-07:01 | 20008.86 | 03-APR-07:05 | 7097.60 | 30-APR-08:13 | 0.00 | 01-APR-00:03 |
May | 0.233611E+11 | 0.551142E+10 | 365.27 | 0.119373E+11 | 0.114238E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 33124.51 | 15-MAY-07:01 | 17443.55 | 31-MAY-07:01 | 22784.17 | 22-MAY-07:01 | 7255.72 | 07-MAY-08:14 | 0.00 | 01-MAY-00:10 |
June | 0.235635E+11 | 0.554765E+10 | 357.59 | 0.119560E+11 | 0.116075E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 33159.79 | 26-JUN-07:03 | 17663.65 | 20-JUN-07:01 | 21792.49 | 05-JUN-07:04 | 7163.54 | 18-JUN-08:14 | 0.00 | 01-JUN-00:10 |
July | 0.184789E+11 | 0.435176E+10 | 356.03 | 0.101138E+11 | 0.836512E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 33195.09 | 05-JUL-07:01 | 19289.25 | 06-JUL-07:01 | 19006.10 | 02-JUL-08:04 | 6979.95 | 30-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.214883E+11 | 0.495102E+10 | 369.68 | 0.103739E+11 | 0.111144E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 33197.30 | 21-AUG-07:02 | 17573.72 | 16-AUG-07:01 | 21264.08 | 14-AUG-07:05 | 7100.85 | 13-AUG-08:12 | 0.00 | 01-AUG-00:10 |
September | 0.200824E+11 | 0.465137E+10 | 348.62 | 0.100345E+11 | 0.100480E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 33234.93 | 18-SEP-07:03 | 17904.55 | 06-SEP-07:01 | 21057.04 | 25-SEP-07:06 | 7052.93 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.193447E+11 | 0.445987E+10 | 359.08 | 0.966106E+10 | 0.968364E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 33234.49 | 23-OCT-07:02 | 17809.72 | 11-OCT-07:02 | 20141.93 | 16-OCT-07:04 | 7037.46 | 29-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.177512E+11 | 0.415806E+10 | 349.09 | 0.957058E+10 | 0.818058E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 33174.91 | 20-NOV-08:61 | 19563.85 | 25-NOV-08:62 | 20127.59 | 12-NOV-09:04 | 7051.76 | 23-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.166004E+11 | 0.397497E+10 | 355.43 | 0.985841E+10 | 0.674200E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 33181.83 | 11-DEC-08:03 | 20757.38 | 27-DEC-08:62 | 20296.65 | 11-DEC-08:04 | 7079.96 | 31-DEC-09:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.232560E+12 | 0.551285E+11 | 4261.11 | 0.126839E+12 | 0.105721E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.161058E+11 | 0.394487E+10 | 324.30 | 0.957058E+10 | 0.606513E+10 | 0.00 | 1.00 | 0.00 | 32710.67 | 17443.55 | 17040.30 | 6979.95 | 0.00 | |||||||
Maximum of Months | 0.235635E+11 | 0.554765E+10 | 369.68 | 0.119560E+11 | 0.116075E+11 | 0.00 | 1.00 | 0.00 | 33234.93 | 22023.37 | 22784.17 | 7255.72 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.165397E+11 | 0.401898E+10 | 357.50 | 0.103397E+11 | 0.619992E+10 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:03 | 33088.13 | 02-JAN-08:62 | 20305.35 | 24-JAN-08:62 | 18475.35 | 02-JAN-08:03 | 7141.66 | 11-JAN-08:61 | 0.00 | 01-JAN-00:03 |
February | 0.161487E+11 | 0.395643E+10 | 324.46 | 0.100737E+11 | 0.607505E+10 | 0.00 | 1.00 | 01-FEB-08:61 | 0.00 | 01-FEB-00:03 | 32822.91 | 06-FEB-08:61 | 22063.59 | 25-FEB-08:61 | 17127.13 | 06-FEB-08:03 | 7069.41 | 20-FEB-09:13 | 0.00 | 01-FEB-00:03 |
March | 0.189264E+11 | 0.466868E+10 | 369.51 | 0.116648E+11 | 0.726155E+10 | 0.00 | 1.00 | 01-MAR-08:61 | 0.00 | 01-MAR-00:03 | 33245.97 | 27-MAR-07:01 | 20643.41 | 04-MAR-08:62 | 18183.12 | 27-MAR-07:04 | 7168.46 | 26-MAR-08:13 | 0.00 | 01-MAR-00:03 |
April | 0.204781E+11 | 0.493331E+10 | 349.15 | 0.114108E+11 | 0.906729E+10 | 0.00 | 1.00 | 01-APR-07:01 | 0.00 | 01-APR-00:03 | 33264.53 | 10-APR-07:02 | 18871.25 | 27-APR-07:01 | 20106.26 | 03-APR-07:05 | 7123.64 | 30-APR-08:13 | 0.00 | 01-APR-00:03 |
May | 0.234445E+11 | 0.553368E+10 | 365.22 | 0.119998E+11 | 0.114447E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 33245.97 | 15-MAY-07:01 | 17513.36 | 31-MAY-07:01 | 22898.04 | 22-MAY-07:01 | 7282.43 | 07-MAY-08:14 | 0.00 | 01-MAY-00:10 |
June | 0.236618E+11 | 0.557346E+10 | 357.50 | 0.120285E+11 | 0.116333E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 33281.39 | 26-JUN-07:01 | 17747.16 | 20-JUN-07:01 | 21915.26 | 05-JUN-07:04 | 7189.94 | 18-JUN-08:14 | 0.00 | 01-JUN-00:10 |
July | 0.185429E+11 | 0.436766E+10 | 355.84 | 0.101603E+11 | 0.838261E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 33311.22 | 05-JUL-07:01 | 19355.96 | 06-JUL-07:01 | 19086.13 | 02-JUL-08:04 | 7005.57 | 30-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.215423E+11 | 0.496558E+10 | 369.58 | 0.104144E+11 | 0.111279E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 33319.03 | 21-AUG-07:02 | 17643.06 | 16-AUG-07:01 | 21358.08 | 14-AUG-07:05 | 7126.89 | 13-AUG-08:12 | 0.00 | 01-AUG-00:10 |
September | 0.201457E+11 | 0.466776E+10 | 348.12 | 0.100813E+11 | 0.100644E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 33356.80 | 18-SEP-07:01 | 17991.64 | 06-SEP-07:01 | 21117.84 | 25-SEP-07:04 | 7078.73 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.193576E+11 | 0.446497E+10 | 359.10 | 0.967254E+10 | 0.968508E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 33356.35 | 23-OCT-07:02 | 17840.85 | 11-OCT-07:02 | 20252.70 | 16-OCT-07:04 | 7063.23 | 29-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.177602E+11 | 0.416190E+10 | 349.08 | 0.957920E+10 | 0.818101E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 33296.55 | 20-NOV-08:61 | 19587.78 | 25-NOV-08:62 | 20240.81 | 12-NOV-09:04 | 7077.60 | 23-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.165992E+11 | 0.397678E+10 | 355.69 | 0.985864E+10 | 0.674059E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 33303.51 | 11-DEC-08:61 | 20779.43 | 27-DEC-08:62 | 20398.39 | 11-DEC-08:04 | 7105.87 | 31-DEC-09:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.233147E+12 | 0.552892E+11 | 4260.74 | 0.127284E+12 | 0.105863E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.161487E+11 | 0.395643E+10 | 324.46 | 0.957920E+10 | 0.607505E+10 | 0.00 | 1.00 | 0.00 | 32822.91 | 17513.36 | 17127.13 | 7005.57 | 0.00 | |||||||
Maximum of Months | 0.236618E+11 | 0.557346E+10 | 369.58 | 0.120285E+11 | 0.116333E+11 | 0.00 | 1.00 | 0.00 | 33356.80 | 22063.59 | 22898.04 | 7282.43 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.184822E+11 | 0.452642E+10 | 358.30 | 0.117807E+11 | 0.670155E+10 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:03 | 38367.31 | 09-JAN-08:61 | 22917.24 | 18-JAN-08:62 | 21658.32 | 09-JAN-08:03 | 8237.51 | 11-JAN-08:03 | 0.00 | 01-JAN-00:03 |
February | 0.182116E+11 | 0.448956E+10 | 325.64 | 0.116174E+11 | 0.659421E+10 | 0.00 | 1.00 | 01-FEB-08:61 | 0.00 | 01-FEB-00:03 | 38035.55 | 20-FEB-09:01 | 24591.77 | 25-FEB-08:61 | 19963.53 | 06-FEB-08:03 | 8154.63 | 20-FEB-09:13 | 0.00 | 01-FEB-00:03 |
March | 0.215065E+11 | 0.533908E+10 | 370.34 | 0.135445E+11 | 0.796194E+10 | 0.00 | 1.00 | 01-MAR-08:61 | 0.00 | 01-MAR-00:03 | 38350.04 | 27-MAR-07:01 | 22902.48 | 04-MAR-08:62 | 22100.89 | 27-MAR-07:04 | 8264.66 | 26-MAR-08:13 | 0.00 | 01-MAR-00:03 |
April | 0.232432E+11 | 0.564577E+10 | 349.66 | 0.133561E+11 | 0.988710E+10 | 0.00 | 1.00 | 01-APR-07:01 | 0.00 | 01-APR-00:03 | 38423.93 | 24-APR-07:01 | 20436.11 | 27-APR-07:01 | 23420.80 | 03-APR-07:05 | 8208.57 | 30-APR-08:13 | 0.00 | 01-APR-00:03 |
May | 0.262181E+11 | 0.625772E+10 | 365.88 | 0.138762E+11 | 0.123418E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 38405.08 | 17-MAY-07:01 | 19547.39 | 11-MAY-07:01 | 26708.12 | 22-MAY-07:01 | 8436.02 | 07-MAY-08:25 | 0.00 | 01-MAY-00:10 |
June | 0.266046E+11 | 0.633442E+10 | 357.81 | 0.140288E+11 | 0.125758E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 38390.88 | 26-JUN-07:01 | 19759.30 | 20-JUN-07:01 | 25503.53 | 05-JUN-07:03 | 8297.32 | 18-JUN-08:16 | 0.00 | 01-JUN-00:10 |
July | 0.208979E+11 | 0.496263E+10 | 356.64 | 0.118147E+11 | 0.908324E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 38434.31 | 05-JUL-07:01 | 22156.10 | 11-JUL-07:01 | 22202.22 | 02-JUL-08:04 | 8079.78 | 09-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.240915E+11 | 0.561475E+10 | 370.09 | 0.121001E+11 | 0.119914E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 38434.31 | 21-AUG-07:02 | 19974.22 | 16-AUG-07:01 | 24718.93 | 14-AUG-07:04 | 8221.04 | 13-AUG-08:12 | 0.00 | 01-AUG-00:10 |
September | 0.225942E+11 | 0.528949E+10 | 349.15 | 0.117508E+11 | 0.108433E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 38477.87 | 18-SEP-07:03 | 20207.92 | 12-SEP-07:01 | 24493.34 | 25-SEP-07:04 | 8168.37 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.213263E+11 | 0.497488E+10 | 359.58 | 0.110083E+11 | 0.103180E+11 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 38477.36 | 23-OCT-07:02 | 20056.56 | 11-OCT-07:02 | 23597.55 | 16-OCT-07:04 | 8145.70 | 29-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.196859E+11 | 0.465807E+10 | 349.90 | 0.109309E+11 | 0.875508E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 38446.45 | 05-NOV-08:61 | 22194.02 | 25-NOV-08:62 | 23479.76 | 12-NOV-09:04 | 8164.05 | 23-NOV-09:03 | 0.00 | 01-NOV-00:10 |
December | 0.184576E+11 | 0.446353E+10 | 356.17 | 0.112153E+11 | 0.724230E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 38416.40 | 11-DEC-08:61 | 23265.11 | 27-DEC-08:62 | 23503.14 | 11-DEC-08:04 | 8197.26 | 31-DEC-09:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.261320E+12 | 0.625563E+11 | 4269.17 | 0.147024E+12 | 0.114296E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.182116E+11 | 0.446353E+10 | 325.64 | 0.109309E+11 | 0.659421E+10 | 0.00 | 1.00 | 0.00 | 38035.55 | 19547.39 | 19963.53 | 8079.78 | 0.00 | |||||||
Maximum of Months | 0.266046E+11 | 0.633442E+10 | 370.34 | 0.140288E+11 | 0.125758E+11 | 0.00 | 1.00 | 0.00 | 38477.87 | 24591.77 | 26708.12 | 8436.02 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 128.92 | 10.85 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 117.40 | 8.30 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 87.50 | 5.88 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 68.07 | 2.86 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 69.95 | 3.42 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 68.92 | 3.74 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 62.72 | 6.41 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 60.28 | 5.10 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 69.13 | 5.18 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 83.88 | 6.48 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.34 | 7.77 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 126.90 | 12.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 87.36 | 6.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 60.28 | 2.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 128.92 | 12.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 128.92 | 10.85 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 117.40 | 8.30 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 87.50 | 5.88 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 68.07 | 2.86 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 69.95 | 3.42 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 68.92 | 3.74 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 62.72 | 6.41 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 60.28 | 5.10 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 69.13 | 5.18 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 83.88 | 6.48 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.34 | 7.77 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 126.90 | 12.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 87.36 | 6.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 60.28 | 2.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 128.92 | 12.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 128.92 | 10.85 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 117.40 | 8.30 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 87.50 | 5.88 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 68.07 | 2.86 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 69.95 | 3.42 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 68.92 | 3.74 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 62.72 | 6.41 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 60.28 | 5.10 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 69.13 | 5.18 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 83.88 | 6.48 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.34 | 7.77 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 126.90 | 12.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 87.36 | 6.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 60.28 | 2.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 128.92 | 12.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 128.92 | 10.85 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 117.40 | 8.30 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 87.50 | 5.88 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 68.07 | 2.86 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 69.95 | 3.42 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 68.92 | 3.74 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 62.72 | 6.41 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 60.28 | 5.10 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 69.13 | 5.18 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 83.88 | 6.48 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.34 | 7.77 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 126.90 | 12.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 87.36 | 6.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 60.28 | 2.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 128.92 | 12.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.18 | 32.62 | 45.56 | 154.46 | 13.06 | 0.00 | 0.00 | 0.00 |
February | 66.39 | 21.65 | 44.74 | 140.53 | 10.05 | 0.00 | 0.00 | 0.00 |
March | 45.31 | 6.08 | 39.22 | 104.53 | 7.19 | 0.00 | 0.00 | 0.00 |
April | 33.78 | 0.02 | 33.76 | 81.01 | 3.49 | 0.00 | 0.00 | 0.00 |
May | 33.80 | 0.00 | 33.80 | 83.32 | 4.13 | 0.00 | 0.00 | 0.00 |
June | 33.68 | 0.00 | 33.68 | 82.08 | 4.51 | 0.00 | 0.00 | 0.00 |
July | 34.70 | 0.00 | 34.70 | 74.93 | 7.70 | 0.00 | 0.00 | 0.00 |
August | 33.78 | 0.05 | 33.72 | 71.96 | 6.17 | 0.00 | 0.00 | 0.00 |
September | 37.39 | 1.22 | 36.17 | 82.61 | 6.23 | 0.00 | 0.00 | 0.00 |
October | 48.92 | 7.80 | 41.12 | 100.42 | 7.78 | 0.00 | 0.00 | 0.00 |
November | 63.61 | 19.41 | 44.21 | 127.36 | 9.34 | 0.00 | 0.00 | 0.00 |
December | 78.14 | 33.25 | 44.90 | 152.08 | 14.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.91 | 10.13 | 38.77 | 104.44 | 7.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.68 | 0.00 | 33.68 | 71.96 | 3.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.18 | 33.25 | 45.56 | 154.46 | 14.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.18 | 32.62 | 45.56 | 154.46 | 13.06 | 0.00 | 0.00 | 0.00 |
February | 66.39 | 21.65 | 44.74 | 140.53 | 10.05 | 0.00 | 0.00 | 0.00 |
March | 45.31 | 6.08 | 39.22 | 104.53 | 7.19 | 0.00 | 0.00 | 0.00 |
April | 33.78 | 0.02 | 33.76 | 81.01 | 3.49 | 0.00 | 0.00 | 0.00 |
May | 33.80 | 0.00 | 33.80 | 83.32 | 4.13 | 0.00 | 0.00 | 0.00 |
June | 33.68 | 0.00 | 33.68 | 82.08 | 4.51 | 0.00 | 0.00 | 0.00 |
July | 34.70 | 0.00 | 34.70 | 74.93 | 7.70 | 0.00 | 0.00 | 0.00 |
August | 33.78 | 0.05 | 33.72 | 71.96 | 6.17 | 0.00 | 0.00 | 0.00 |
September | 37.39 | 1.22 | 36.17 | 82.61 | 6.23 | 0.00 | 0.00 | 0.00 |
October | 48.92 | 7.80 | 41.12 | 100.42 | 7.78 | 0.00 | 0.00 | 0.00 |
November | 63.61 | 19.41 | 44.21 | 127.36 | 9.34 | 0.00 | 0.00 | 0.00 |
December | 78.14 | 33.25 | 44.90 | 152.08 | 14.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.91 | 10.13 | 38.77 | 104.44 | 7.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.68 | 0.00 | 33.68 | 71.96 | 3.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.18 | 33.25 | 45.56 | 154.46 | 14.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 129.34 | 10.78 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 118.04 | 8.15 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 88.41 | 5.67 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 69.25 | 2.70 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 71.02 | 3.33 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 70.06 | 3.59 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 63.48 | 6.27 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 61.07 | 4.97 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 69.91 | 5.05 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 84.39 | 6.42 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.83 | 7.72 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 127.24 | 12.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 88.11 | 6.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 61.07 | 2.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 129.34 | 12.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 129.34 | 10.78 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 118.04 | 8.15 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 88.41 | 5.67 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 69.25 | 2.70 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 71.02 | 3.33 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 70.06 | 3.59 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 63.48 | 6.27 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 61.07 | 4.97 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 69.91 | 5.05 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 84.39 | 6.42 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.83 | 7.72 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 127.24 | 12.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 88.11 | 6.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 61.07 | 2.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 129.34 | 12.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.18 | 32.62 | 45.56 | 154.98 | 12.96 | 0.00 | 0.00 | 0.00 |
February | 66.39 | 21.65 | 44.74 | 141.30 | 9.86 | 0.00 | 0.00 | 0.00 |
March | 45.31 | 6.08 | 39.22 | 105.60 | 6.93 | 0.00 | 0.00 | 0.00 |
April | 33.78 | 0.02 | 33.76 | 82.41 | 3.31 | 0.00 | 0.00 | 0.00 |
May | 33.80 | 0.00 | 33.80 | 84.58 | 4.02 | 0.00 | 0.00 | 0.00 |
June | 33.68 | 0.00 | 33.68 | 83.43 | 4.33 | 0.00 | 0.00 | 0.00 |
July | 34.70 | 0.00 | 34.70 | 75.84 | 7.52 | 0.00 | 0.00 | 0.00 |
August | 33.78 | 0.05 | 33.72 | 72.90 | 6.00 | 0.00 | 0.00 | 0.00 |
September | 37.39 | 1.22 | 36.17 | 83.55 | 6.07 | 0.00 | 0.00 | 0.00 |
October | 48.92 | 7.80 | 41.12 | 101.05 | 7.71 | 0.00 | 0.00 | 0.00 |
November | 63.61 | 19.41 | 44.21 | 127.98 | 9.27 | 0.00 | 0.00 | 0.00 |
December | 78.14 | 33.25 | 44.90 | 152.51 | 14.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.91 | 10.13 | 38.77 | 105.34 | 7.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.68 | 0.00 | 33.68 | 72.90 | 3.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.18 | 33.25 | 45.56 | 154.98 | 14.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 129.06 | 13.43 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 117.61 | 10.78 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 87.75 | 8.07 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 67.13 | 4.04 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 68.84 | 4.71 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 68.12 | 5.15 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 62.19 | 8.38 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 60.39 | 7.10 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 68.79 | 7.06 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 83.78 | 8.72 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.50 | 10.01 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 127.12 | 14.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 87.13 | 8.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 60.39 | 4.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 129.06 | 14.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 129.06 | 13.43 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 117.61 | 10.78 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 87.75 | 8.07 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 67.13 | 4.04 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 68.84 | 4.71 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 68.12 | 5.15 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 62.19 | 8.38 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 60.39 | 7.10 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 68.79 | 7.06 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 83.78 | 8.72 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.50 | 10.01 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 127.12 | 14.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 87.13 | 8.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 60.39 | 4.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 129.06 | 14.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.76 | 32.44 | 45.32 | 153.82 | 15.98 | 0.00 | 0.00 | 0.00 |
February | 66.03 | 21.53 | 44.50 | 140.05 | 12.89 | 0.00 | 0.00 | 0.00 |
March | 45.06 | 6.05 | 39.01 | 104.31 | 9.73 | 0.00 | 0.00 | 0.00 |
April | 33.59 | 0.02 | 33.58 | 79.56 | 4.91 | 0.00 | 0.00 | 0.00 |
May | 33.62 | 0.00 | 33.62 | 81.63 | 5.64 | 0.00 | 0.00 | 0.00 |
June | 33.50 | 0.00 | 33.50 | 80.76 | 6.16 | 0.00 | 0.00 | 0.00 |
July | 34.51 | 0.00 | 34.51 | 73.95 | 9.97 | 0.00 | 0.00 | 0.00 |
August | 33.59 | 0.05 | 33.54 | 71.74 | 8.48 | 0.00 | 0.00 | 0.00 |
September | 37.19 | 1.21 | 35.97 | 81.81 | 8.40 | 0.00 | 0.00 | 0.00 |
October | 48.65 | 7.76 | 40.90 | 99.80 | 10.36 | 0.00 | 0.00 | 0.00 |
November | 63.27 | 19.30 | 43.96 | 126.90 | 11.90 | 0.00 | 0.00 | 0.00 |
December | 77.72 | 33.07 | 44.65 | 151.54 | 17.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.64 | 10.08 | 38.56 | 103.65 | 10.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.50 | 0.00 | 33.50 | 71.74 | 4.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.76 | 33.07 | 45.32 | 153.82 | 17.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 129.01 | 13.62 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 117.56 | 10.98 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 87.70 | 8.29 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 67.04 | 4.26 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 68.70 | 4.92 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 68.02 | 5.39 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 62.12 | 8.62 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 60.35 | 7.28 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 68.73 | 7.26 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 83.74 | 8.91 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.46 | 10.16 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 127.09 | 15.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 87.06 | 8.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 60.35 | 4.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 129.01 | 15.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 129.01 | 13.62 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 117.56 | 10.98 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 87.70 | 8.29 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 67.04 | 4.26 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 68.70 | 4.92 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 68.02 | 5.39 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 62.12 | 8.62 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 60.35 | 7.28 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 68.73 | 7.26 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 83.74 | 8.91 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.46 | 10.16 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 127.09 | 15.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 87.06 | 8.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 60.35 | 4.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 129.01 | 15.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.76 | 32.44 | 45.32 | 153.76 | 16.20 | 0.00 | 0.00 | 0.00 |
February | 66.03 | 21.53 | 44.50 | 139.99 | 13.13 | 0.00 | 0.00 | 0.00 |
March | 45.06 | 6.05 | 39.01 | 104.26 | 9.99 | 0.00 | 0.00 | 0.00 |
April | 33.59 | 0.02 | 33.58 | 79.46 | 5.17 | 0.00 | 0.00 | 0.00 |
May | 33.62 | 0.00 | 33.62 | 81.46 | 5.88 | 0.00 | 0.00 | 0.00 |
June | 33.50 | 0.00 | 33.50 | 80.64 | 6.45 | 0.00 | 0.00 | 0.00 |
July | 34.51 | 0.00 | 34.51 | 73.87 | 10.25 | 0.00 | 0.00 | 0.00 |
August | 33.59 | 0.05 | 33.54 | 71.69 | 8.70 | 0.00 | 0.00 | 0.00 |
September | 37.19 | 1.21 | 35.97 | 81.75 | 8.65 | 0.00 | 0.00 | 0.00 |
October | 48.65 | 7.76 | 40.90 | 99.76 | 10.58 | 0.00 | 0.00 | 0.00 |
November | 63.27 | 19.30 | 43.96 | 126.86 | 12.07 | 0.00 | 0.00 | 0.00 |
December | 77.72 | 33.07 | 44.65 | 151.50 | 17.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.64 | 10.08 | 38.56 | 103.58 | 10.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.50 | 0.00 | 33.50 | 71.69 | 5.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.76 | 33.07 | 45.32 | 153.76 | 17.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 129.14 | 13.30 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 117.69 | 10.66 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 87.83 | 7.95 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 67.20 | 3.97 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 68.87 | 4.67 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 68.18 | 5.12 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 62.24 | 8.31 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 60.48 | 6.95 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 68.87 | 6.95 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 83.87 | 8.58 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.60 | 9.84 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 127.22 | 14.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 87.20 | 8.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 60.48 | 3.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 129.14 | 14.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 129.14 | 13.30 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 117.69 | 10.66 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 87.83 | 7.95 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 67.20 | 3.97 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 68.87 | 4.67 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 68.18 | 5.12 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 62.24 | 8.31 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 60.48 | 6.95 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 68.87 | 6.95 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 83.87 | 8.58 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.60 | 9.84 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 127.22 | 14.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 87.20 | 8.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 60.48 | 3.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 129.14 | 14.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.76 | 32.44 | 45.32 | 153.92 | 15.83 | 0.00 | 0.00 | 0.00 |
February | 66.03 | 21.53 | 44.50 | 140.14 | 12.76 | 0.00 | 0.00 | 0.00 |
March | 45.06 | 6.05 | 39.01 | 104.41 | 9.59 | 0.00 | 0.00 | 0.00 |
April | 33.59 | 0.02 | 33.58 | 79.65 | 4.83 | 0.00 | 0.00 | 0.00 |
May | 33.62 | 0.00 | 33.62 | 81.66 | 5.59 | 0.00 | 0.00 | 0.00 |
June | 33.50 | 0.00 | 33.50 | 80.83 | 6.13 | 0.00 | 0.00 | 0.00 |
July | 34.51 | 0.00 | 34.51 | 74.01 | 9.89 | 0.00 | 0.00 | 0.00 |
August | 33.59 | 0.05 | 33.54 | 71.85 | 8.30 | 0.00 | 0.00 | 0.00 |
September | 37.19 | 1.21 | 35.97 | 81.91 | 8.27 | 0.00 | 0.00 | 0.00 |
October | 48.65 | 7.76 | 40.90 | 99.91 | 10.19 | 0.00 | 0.00 | 0.00 |
November | 63.27 | 19.30 | 43.96 | 127.03 | 11.71 | 0.00 | 0.00 | 0.00 |
December | 77.72 | 33.07 | 44.65 | 151.66 | 17.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.64 | 10.08 | 38.56 | 103.74 | 10.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.50 | 0.00 | 33.50 | 71.85 | 4.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.76 | 33.07 | 45.32 | 153.92 | 17.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 129.02 | 12.18 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 117.47 | 9.52 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 87.65 | 6.81 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 67.23 | 3.20 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 68.86 | 3.90 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 68.17 | 4.31 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 62.08 | 7.32 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 60.36 | 5.83 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 68.82 | 5.97 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 83.82 | 7.52 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.47 | 8.80 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 127.11 | 13.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 87.11 | 7.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 60.36 | 3.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 129.02 | 13.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 129.02 | 12.18 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 117.47 | 9.52 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 87.65 | 6.81 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 67.23 | 3.20 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 68.86 | 3.90 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 68.17 | 4.31 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 62.08 | 7.32 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 60.36 | 5.83 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 68.82 | 5.97 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 83.82 | 7.52 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.47 | 8.80 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 127.11 | 13.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 87.11 | 7.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 60.36 | 3.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 129.02 | 13.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 129.02 | 12.18 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 117.47 | 9.52 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 87.65 | 6.81 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 67.23 | 3.20 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 68.86 | 3.90 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 68.17 | 4.31 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 62.08 | 7.32 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 60.36 | 5.83 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 68.82 | 5.97 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 83.82 | 7.52 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.47 | 8.80 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 127.11 | 13.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 87.11 | 7.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 60.36 | 3.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 129.02 | 13.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 129.02 | 12.18 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 117.47 | 9.52 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 87.65 | 6.81 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 67.23 | 3.20 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 68.86 | 3.90 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 68.17 | 4.31 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 62.08 | 7.32 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 60.36 | 5.83 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 68.82 | 5.97 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 83.82 | 7.52 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.47 | 8.80 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 127.11 | 13.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 87.11 | 7.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 60.36 | 3.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 129.02 | 13.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.76 | 32.44 | 45.32 | 153.77 | 14.51 | 0.00 | 0.00 | 0.00 |
February | 66.03 | 21.53 | 44.50 | 139.89 | 11.41 | 0.00 | 0.00 | 0.00 |
March | 45.06 | 6.05 | 39.01 | 104.20 | 8.23 | 0.00 | 0.00 | 0.00 |
April | 33.59 | 0.02 | 33.58 | 79.69 | 3.89 | 0.00 | 0.00 | 0.00 |
May | 33.62 | 0.00 | 33.62 | 81.66 | 4.66 | 0.00 | 0.00 | 0.00 |
June | 33.50 | 0.00 | 33.50 | 80.83 | 5.16 | 0.00 | 0.00 | 0.00 |
July | 34.51 | 0.00 | 34.51 | 73.83 | 8.71 | 0.00 | 0.00 | 0.00 |
August | 33.59 | 0.05 | 33.54 | 71.72 | 6.98 | 0.00 | 0.00 | 0.00 |
September | 37.19 | 1.21 | 35.97 | 81.86 | 7.11 | 0.00 | 0.00 | 0.00 |
October | 48.65 | 7.76 | 40.90 | 99.85 | 8.93 | 0.00 | 0.00 | 0.00 |
November | 63.27 | 19.30 | 43.96 | 126.87 | 10.47 | 0.00 | 0.00 | 0.00 |
December | 77.72 | 33.07 | 44.65 | 151.53 | 16.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.64 | 10.08 | 38.56 | 103.64 | 8.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.50 | 0.00 | 33.50 | 71.72 | 3.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.76 | 33.07 | 45.32 | 153.77 | 16.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.76 | 32.44 | 45.32 | 153.77 | 14.51 | 0.00 | 0.00 | 0.00 |
February | 66.03 | 21.53 | 44.50 | 139.89 | 11.41 | 0.00 | 0.00 | 0.00 |
March | 45.06 | 6.05 | 39.01 | 104.20 | 8.23 | 0.00 | 0.00 | 0.00 |
April | 33.59 | 0.02 | 33.58 | 79.69 | 3.89 | 0.00 | 0.00 | 0.00 |
May | 33.62 | 0.00 | 33.62 | 81.66 | 4.66 | 0.00 | 0.00 | 0.00 |
June | 33.50 | 0.00 | 33.50 | 80.83 | 5.16 | 0.00 | 0.00 | 0.00 |
July | 34.51 | 0.00 | 34.51 | 73.83 | 8.71 | 0.00 | 0.00 | 0.00 |
August | 33.59 | 0.05 | 33.54 | 71.72 | 6.98 | 0.00 | 0.00 | 0.00 |
September | 37.19 | 1.21 | 35.97 | 81.86 | 7.11 | 0.00 | 0.00 | 0.00 |
October | 48.65 | 7.76 | 40.90 | 99.85 | 8.93 | 0.00 | 0.00 | 0.00 |
November | 63.27 | 19.30 | 43.96 | 126.87 | 10.47 | 0.00 | 0.00 | 0.00 |
December | 77.72 | 33.07 | 44.65 | 151.53 | 16.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.64 | 10.08 | 38.56 | 103.64 | 8.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.50 | 0.00 | 33.50 | 71.72 | 3.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.76 | 33.07 | 45.32 | 153.77 | 16.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 129.24 | 11.75 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 117.76 | 9.06 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 88.05 | 6.32 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 67.88 | 2.85 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 69.51 | 3.58 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 68.82 | 3.95 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 62.45 | 6.91 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 60.77 | 5.39 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 69.21 | 5.58 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 84.10 | 7.10 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.72 | 8.40 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 127.30 | 13.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 87.51 | 7.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 60.77 | 2.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 129.24 | 13.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 129.24 | 11.75 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 117.76 | 9.06 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 88.05 | 6.32 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 67.88 | 2.85 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 69.51 | 3.58 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 68.82 | 3.95 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 62.45 | 6.91 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 60.77 | 5.39 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 69.21 | 5.58 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 84.10 | 7.10 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.72 | 8.40 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 127.30 | 13.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 87.51 | 7.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 60.77 | 2.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 129.24 | 13.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.76 | 32.44 | 45.32 | 154.05 | 14.01 | 0.00 | 0.00 | 0.00 |
February | 66.03 | 21.53 | 44.50 | 140.25 | 10.87 | 0.00 | 0.00 | 0.00 |
March | 45.06 | 6.05 | 39.01 | 104.67 | 7.66 | 0.00 | 0.00 | 0.00 |
April | 33.59 | 0.02 | 33.58 | 80.43 | 3.48 | 0.00 | 0.00 | 0.00 |
May | 33.62 | 0.00 | 33.62 | 82.42 | 4.29 | 0.00 | 0.00 | 0.00 |
June | 33.50 | 0.00 | 33.50 | 81.58 | 4.74 | 0.00 | 0.00 | 0.00 |
July | 34.51 | 0.00 | 34.51 | 74.27 | 8.23 | 0.00 | 0.00 | 0.00 |
August | 33.59 | 0.05 | 33.54 | 72.20 | 6.47 | 0.00 | 0.00 | 0.00 |
September | 37.19 | 1.21 | 35.97 | 82.32 | 6.65 | 0.00 | 0.00 | 0.00 |
October | 48.65 | 7.76 | 40.90 | 100.20 | 8.44 | 0.00 | 0.00 | 0.00 |
November | 63.27 | 19.30 | 43.96 | 127.19 | 9.99 | 0.00 | 0.00 | 0.00 |
December | 77.72 | 33.07 | 44.65 | 151.78 | 15.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.64 | 10.08 | 38.56 | 104.11 | 8.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.50 | 0.00 | 33.50 | 72.20 | 3.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.76 | 33.07 | 45.32 | 154.05 | 15.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 129.30 | 11.67 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 117.83 | 8.99 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 88.11 | 6.25 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 67.95 | 2.80 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 69.59 | 3.53 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 68.89 | 3.90 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 62.51 | 6.84 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 60.83 | 5.32 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 69.27 | 5.51 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 84.16 | 7.02 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.79 | 8.32 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 127.37 | 13.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 87.57 | 6.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 60.83 | 2.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 129.30 | 13.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 129.30 | 11.67 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 117.83 | 8.99 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 88.11 | 6.25 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 67.95 | 2.80 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 69.59 | 3.53 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 68.89 | 3.90 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 62.51 | 6.84 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 60.83 | 5.32 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 69.27 | 5.51 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 84.16 | 7.02 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.79 | 8.32 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 127.37 | 13.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 87.57 | 6.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 60.83 | 2.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 129.30 | 13.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.76 | 32.44 | 45.32 | 154.13 | 13.91 | 0.00 | 0.00 | 0.00 |
February | 66.03 | 21.53 | 44.50 | 140.33 | 10.78 | 0.00 | 0.00 | 0.00 |
March | 45.06 | 6.05 | 39.01 | 104.74 | 7.57 | 0.00 | 0.00 | 0.00 |
April | 33.59 | 0.02 | 33.58 | 80.52 | 3.42 | 0.00 | 0.00 | 0.00 |
May | 33.62 | 0.00 | 33.62 | 82.51 | 4.24 | 0.00 | 0.00 | 0.00 |
June | 33.50 | 0.00 | 33.50 | 81.67 | 4.67 | 0.00 | 0.00 | 0.00 |
July | 34.51 | 0.00 | 34.51 | 74.34 | 8.15 | 0.00 | 0.00 | 0.00 |
August | 33.59 | 0.05 | 33.54 | 72.27 | 6.39 | 0.00 | 0.00 | 0.00 |
September | 37.19 | 1.21 | 35.97 | 82.39 | 6.57 | 0.00 | 0.00 | 0.00 |
October | 48.65 | 7.76 | 40.90 | 100.27 | 8.35 | 0.00 | 0.00 | 0.00 |
November | 63.27 | 19.30 | 43.96 | 127.28 | 9.90 | 0.00 | 0.00 | 0.00 |
December | 77.72 | 33.07 | 44.65 | 151.86 | 15.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.64 | 10.08 | 38.56 | 104.19 | 8.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.50 | 0.00 | 33.50 | 72.27 | 3.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.76 | 33.07 | 45.32 | 154.13 | 15.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 129.27 | 11.67 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 117.75 | 9.02 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 88.01 | 6.31 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 67.78 | 2.87 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 69.40 | 3.59 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 68.72 | 3.98 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 62.39 | 6.93 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 60.72 | 5.38 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 69.14 | 5.58 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 84.09 | 7.04 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.74 | 8.32 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 127.35 | 13.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 87.47 | 6.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 60.72 | 2.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 129.27 | 13.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 129.27 | 11.67 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 117.75 | 9.02 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 88.01 | 6.31 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 67.78 | 2.87 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 69.40 | 3.59 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 68.72 | 3.98 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 62.39 | 6.93 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 60.72 | 5.38 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 69.14 | 5.58 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 84.09 | 7.04 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 106.74 | 8.32 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 127.35 | 13.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 87.47 | 6.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 60.72 | 2.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 129.27 | 13.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.76 | 32.44 | 45.32 | 154.08 | 13.91 | 0.00 | 0.00 | 0.00 |
February | 66.03 | 21.53 | 44.50 | 140.23 | 10.82 | 0.00 | 0.00 | 0.00 |
March | 45.06 | 6.05 | 39.01 | 104.62 | 7.65 | 0.00 | 0.00 | 0.00 |
April | 33.59 | 0.02 | 33.58 | 80.32 | 3.50 | 0.00 | 0.00 | 0.00 |
May | 33.62 | 0.00 | 33.62 | 82.29 | 4.31 | 0.00 | 0.00 | 0.00 |
June | 33.50 | 0.00 | 33.50 | 81.46 | 4.77 | 0.00 | 0.00 | 0.00 |
July | 34.51 | 0.00 | 34.51 | 74.20 | 8.26 | 0.00 | 0.00 | 0.00 |
August | 33.59 | 0.05 | 33.54 | 72.15 | 6.46 | 0.00 | 0.00 | 0.00 |
September | 37.19 | 1.21 | 35.97 | 82.25 | 6.66 | 0.00 | 0.00 | 0.00 |
October | 48.65 | 7.76 | 40.90 | 100.19 | 8.37 | 0.00 | 0.00 | 0.00 |
November | 63.27 | 19.30 | 43.96 | 127.22 | 9.91 | 0.00 | 0.00 | 0.00 |
December | 77.72 | 33.07 | 44.65 | 151.83 | 15.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.64 | 10.08 | 38.56 | 104.07 | 8.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.50 | 0.00 | 33.50 | 72.15 | 3.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.76 | 33.07 | 45.32 | 154.08 | 15.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 128.19 | 12.05 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 116.38 | 9.60 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 86.47 | 6.99 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 65.75 | 3.53 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 67.39 | 4.16 | 0.67 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 66.70 | 4.71 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 60.87 | 7.76 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 59.25 | 6.11 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 67.58 | 6.36 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.96 | 7.57 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 105.62 | 8.75 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 126.38 | 13.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 85.99 | 7.60 | 0.67 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 59.25 | 3.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 128.19 | 13.52 | 0.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 128.19 | 12.05 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 116.38 | 9.60 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 86.47 | 6.99 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 65.75 | 3.53 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 67.39 | 4.16 | 0.67 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 66.70 | 4.71 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 60.87 | 7.76 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 59.25 | 6.11 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 67.58 | 6.36 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.96 | 7.57 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 105.62 | 8.75 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 126.38 | 13.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 85.99 | 7.60 | 0.67 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 59.25 | 3.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 128.19 | 13.52 | 0.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.76 | 32.44 | 45.32 | 152.79 | 14.37 | 0.00 | 0.00 | 0.00 |
February | 66.03 | 21.53 | 44.50 | 138.59 | 11.52 | 0.00 | 0.00 | 0.00 |
March | 45.06 | 6.05 | 39.01 | 102.79 | 8.46 | 0.00 | 0.00 | 0.00 |
April | 33.59 | 0.02 | 33.58 | 77.91 | 4.30 | 0.00 | 0.00 | 0.00 |
May | 33.62 | 0.00 | 33.62 | 79.91 | 5.00 | 0.83 | 0.00 | 0.00 |
June | 33.50 | 0.00 | 33.50 | 79.06 | 5.65 | 0.00 | 0.00 | 0.00 |
July | 34.51 | 0.00 | 34.51 | 72.38 | 9.24 | 0.00 | 0.00 | 0.00 |
August | 33.59 | 0.05 | 33.54 | 70.39 | 7.32 | 0.00 | 0.00 | 0.00 |
September | 37.19 | 1.21 | 35.97 | 80.38 | 7.59 | 0.00 | 0.00 | 0.00 |
October | 48.65 | 7.76 | 40.90 | 98.84 | 9.00 | 0.00 | 0.00 | 0.00 |
November | 63.27 | 19.30 | 43.96 | 125.87 | 10.42 | 0.00 | 0.00 | 0.00 |
December | 77.72 | 33.07 | 44.65 | 150.67 | 16.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.64 | 10.08 | 38.56 | 102.30 | 9.08 | 0.83 | 0.00 | 0.00 |
Minimum of Months | 33.50 | 0.00 | 33.50 | 70.39 | 4.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.76 | 33.07 | 45.32 | 152.79 | 16.08 | 0.83 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.345305E+09 | 29072356.23 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.284010E+09 | 20079154.00 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.234360E+09 | 15757212.05 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.176425E+09 | 7407992.95 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.187363E+09 | 9173380.06 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.178650E+09 | 9697118.85 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.167998E+09 | 17180851.05 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.161465E+09 | 13669995.24 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.179177E+09 | 13425976.82 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.224664E+09 | 17354342.41 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.275624E+09 | 20144924.49 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.339886E+09 | 33254756.79 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.275493E+10 | 0.206218E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.161465E+09 | 7407992.95 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.345305E+09 | 33254756.79 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.345305E+09 | 29072356.23 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.284010E+09 | 20079154.00 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.234360E+09 | 15757212.05 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.176425E+09 | 7407992.95 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.187363E+09 | 9173380.06 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.178650E+09 | 9697118.85 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.167998E+09 | 17180851.05 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.161465E+09 | 13669995.24 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.179177E+09 | 13425976.82 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.224664E+09 | 17354342.41 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.275624E+09 | 20144924.49 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.339886E+09 | 33254756.79 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.275493E+10 | 0.206218E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.161465E+09 | 7407992.95 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.345305E+09 | 33254756.79 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.345305E+09 | 29072356.23 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.284010E+09 | 20079154.00 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.234360E+09 | 15757212.05 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.176425E+09 | 7407992.95 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.187363E+09 | 9173380.06 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.178650E+09 | 9697118.85 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.167998E+09 | 17180851.05 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.161465E+09 | 13669995.24 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.179177E+09 | 13425976.82 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.224664E+09 | 17354342.41 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.275624E+09 | 20144924.49 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.339886E+09 | 33254756.79 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.275493E+10 | 0.206218E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.161465E+09 | 7407992.95 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.345305E+09 | 33254756.79 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.345305E+09 | 29072356.23 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.284010E+09 | 20079154.00 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.234360E+09 | 15757212.05 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.176425E+09 | 7407992.95 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.187363E+09 | 9173380.06 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.178650E+09 | 9697118.85 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.167998E+09 | 17180851.05 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.161465E+09 | 13669995.24 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.179177E+09 | 13425976.82 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.224664E+09 | 17354342.41 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.275624E+09 | 20144924.49 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.339886E+09 | 33254756.79 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.275493E+10 | 0.206218E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.161465E+09 | 7407992.95 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.345305E+09 | 33254756.79 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209406E+09 | 87366389.65 | 0.122039E+09 | 0.413712E+09 | 34975808.76 |
February | 0.160609E+09 | 52364500.94 | 0.108244E+09 | 0.339958E+09 | 24320577.50 |
March | 0.121350E+09 | 16297375.08 | 0.105052E+09 | 0.279967E+09 | 19257310.10 |
April | 87553716.91 | 39303.53 | 87514413.39 | 0.209972E+09 | 9047303.91 |
May | 90533949.20 | 0.00 | 90533949.20 | 0.223154E+09 | 11072498.92 |
June | 87298096.43 | 0.00 | 87298096.43 | 0.212749E+09 | 11700895.44 |
July | 92927874.03 | 0.00 | 92927874.03 | 0.200690E+09 | 20624580.08 |
August | 90465989.17 | 139817.09 | 90326172.08 | 0.192733E+09 | 16523770.15 |
September | 96921591.97 | 3165530.57 | 93756061.40 | 0.214117E+09 | 16150031.49 |
October | 0.131028E+09 | 20891455.15 | 0.110137E+09 | 0.268973E+09 | 20833936.28 |
November | 0.164884E+09 | 50303904.00 | 0.114580E+09 | 0.330127E+09 | 24201644.62 |
December | 0.209298E+09 | 89047898.11 | 0.120250E+09 | 0.407323E+09 | 39920080.92 |
Annual Sum or Average | 0.154228E+10 | 0.319616E+09 | 0.122266E+10 | 0.329348E+10 | 0.248628E+09 |
Minimum of Months | 87298096.43 | 0.00 | 87298096.43 | 0.192733E+09 | 9047303.91 |
Maximum of Months | 0.209406E+09 | 89047898.11 | 0.122039E+09 | 0.413712E+09 | 39920080.92 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209406E+09 | 87366389.65 | 0.122039E+09 | 0.413712E+09 | 34975808.76 |
February | 0.160609E+09 | 52364500.94 | 0.108244E+09 | 0.339958E+09 | 24320577.50 |
March | 0.121350E+09 | 16297375.08 | 0.105052E+09 | 0.279967E+09 | 19257310.10 |
April | 87553716.91 | 39303.53 | 87514413.39 | 0.209972E+09 | 9047303.91 |
May | 90533949.20 | 0.00 | 90533949.20 | 0.223154E+09 | 11072498.92 |
June | 87298096.43 | 0.00 | 87298096.43 | 0.212749E+09 | 11700895.44 |
July | 92927874.03 | 0.00 | 92927874.03 | 0.200690E+09 | 20624580.08 |
August | 90465989.17 | 139817.09 | 90326172.08 | 0.192733E+09 | 16523770.15 |
September | 96921591.97 | 3165530.57 | 93756061.40 | 0.214117E+09 | 16150031.49 |
October | 0.131028E+09 | 20891455.15 | 0.110137E+09 | 0.268973E+09 | 20833936.28 |
November | 0.164884E+09 | 50303904.00 | 0.114580E+09 | 0.330127E+09 | 24201644.62 |
December | 0.209298E+09 | 89047898.11 | 0.120250E+09 | 0.407323E+09 | 39920080.92 |
Annual Sum or Average | 0.154228E+10 | 0.319616E+09 | 0.122266E+10 | 0.329348E+10 | 0.248628E+09 |
Minimum of Months | 87298096.43 | 0.00 | 87298096.43 | 0.192733E+09 | 9047303.91 |
Maximum of Months | 0.209406E+09 | 89047898.11 | 0.122039E+09 | 0.413712E+09 | 39920080.92 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.346418E+09 | 28865068.05 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.285559E+09 | 19705212.25 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.236799E+09 | 15196740.13 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.179503E+09 | 7010607.50 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.190219E+09 | 8917628.57 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.181607E+09 | 9306210.95 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.170028E+09 | 16785366.40 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.163582E+09 | 13308890.10 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.181201E+09 | 13076663.89 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.226023E+09 | 17207733.09 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.276907E+09 | 20013086.13 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.340805E+09 | 33110787.85 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.277865E+10 | 0.202504E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.163582E+09 | 7010607.50 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.346418E+09 | 33110787.85 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.346418E+09 | 28865068.05 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.285559E+09 | 19705212.25 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.236799E+09 | 15196740.13 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.179503E+09 | 7010607.50 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.190219E+09 | 8917628.57 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.181607E+09 | 9306210.95 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.170028E+09 | 16785366.40 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.163582E+09 | 13308890.10 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.181201E+09 | 13076663.89 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.226023E+09 | 17207733.09 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.276907E+09 | 20013086.13 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.340805E+09 | 33110787.85 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.277865E+10 | 0.202504E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.163582E+09 | 7010607.50 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.346418E+09 | 33110787.85 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209406E+09 | 87366389.65 | 0.122039E+09 | 0.415104E+09 | 34710846.69 |
February | 0.160609E+09 | 52364500.94 | 0.108244E+09 | 0.341831E+09 | 23856881.24 |
March | 0.121350E+09 | 16297375.08 | 0.105052E+09 | 0.282832E+09 | 18553897.08 |
April | 87553716.91 | 39303.53 | 87514413.39 | 0.213613E+09 | 8587550.62 |
May | 90533949.20 | 0.00 | 90533949.20 | 0.226537E+09 | 10768013.43 |
June | 87298096.43 | 0.00 | 87298096.43 | 0.216252E+09 | 11230004.07 |
July | 92927874.03 | 0.00 | 92927874.03 | 0.203132E+09 | 20150628.00 |
August | 90465989.17 | 139817.09 | 90326172.08 | 0.195248E+09 | 16082461.83 |
September | 96921591.97 | 3165530.57 | 93756061.40 | 0.216556E+09 | 15730123.44 |
October | 0.131028E+09 | 20891455.15 | 0.110137E+09 | 0.270645E+09 | 20650981.49 |
November | 0.164884E+09 | 50303904.00 | 0.114580E+09 | 0.331724E+09 | 24035358.53 |
December | 0.209298E+09 | 89047898.11 | 0.120250E+09 | 0.408475E+09 | 39707223.64 |
Annual Sum or Average | 0.154228E+10 | 0.319616E+09 | 0.122266E+10 | 0.332195E+10 | 0.244064E+09 |
Minimum of Months | 87298096.43 | 0.00 | 87298096.43 | 0.195248E+09 | 8587550.62 |
Maximum of Months | 0.209406E+09 | 89047898.11 | 0.122039E+09 | 0.415104E+09 | 39707223.64 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.345662E+09 | 35973278.74 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.284522E+09 | 26080923.44 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.235017E+09 | 21621138.37 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.173992E+09 | 10470992.85 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.184393E+09 | 12619902.12 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.176555E+09 | 13339992.62 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.166567E+09 | 22449832.91 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.161739E+09 | 19010569.01 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.178296E+09 | 18294349.73 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.224399E+09 | 23365204.38 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.276041E+09 | 25939689.60 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.340474E+09 | 40009669.47 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.274766E+10 | 0.269176E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.161739E+09 | 10470992.85 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.345662E+09 | 40009669.47 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.345662E+09 | 35973278.74 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.284522E+09 | 26080923.44 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.235017E+09 | 21621138.37 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.173992E+09 | 10470992.85 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.184393E+09 | 12619902.12 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.176555E+09 | 13339992.62 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.166567E+09 | 22449832.91 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.161739E+09 | 19010569.01 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.178296E+09 | 18294349.73 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.224399E+09 | 23365204.38 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.276041E+09 | 25939689.60 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.340474E+09 | 40009669.47 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.274766E+10 | 0.269176E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.161739E+09 | 10470992.85 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.345662E+09 | 40009669.47 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208261E+09 | 86888977.69 | 0.121372E+09 | 0.411983E+09 | 42810328.74 |
February | 0.159731E+09 | 52078356.13 | 0.107653E+09 | 0.338809E+09 | 31193534.52 |
March | 0.120687E+09 | 16208318.39 | 0.104478E+09 | 0.279387E+09 | 26072078.37 |
April | 87075281.30 | 39088.75 | 87036192.55 | 0.206228E+09 | 12725591.42 |
May | 90039228.17 | 0.00 | 90039228.17 | 0.218642E+09 | 15109810.43 |
June | 86821057.65 | 0.00 | 86821057.65 | 0.209320E+09 | 15965256.12 |
July | 92420071.44 | 0.00 | 92420071.44 | 0.198068E+09 | 26691499.00 |
August | 89971639.51 | 139053.06 | 89832586.44 | 0.192140E+09 | 22718388.74 |
September | 96391965.79 | 3148232.59 | 93243733.19 | 0.212064E+09 | 21779443.36 |
October | 0.130312E+09 | 20777294.20 | 0.109535E+09 | 0.267315E+09 | 27743357.61 |
November | 0.163983E+09 | 50029019.28 | 0.113954E+09 | 0.328937E+09 | 30841991.34 |
December | 0.208155E+09 | 88561297.57 | 0.119593E+09 | 0.405875E+09 | 47537239.11 |
Annual Sum or Average | 0.153385E+10 | 0.317870E+09 | 0.121598E+10 | 0.326877E+10 | 0.321189E+09 |
Minimum of Months | 86821057.65 | 0.00 | 86821057.65 | 0.192140E+09 | 12725591.42 |
Maximum of Months | 0.208261E+09 | 88561297.57 | 0.121372E+09 | 0.411983E+09 | 47537239.11 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.345542E+09 | 36470672.59 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.284390E+09 | 26572124.02 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.234902E+09 | 22211445.14 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.173760E+09 | 11043770.73 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.183994E+09 | 13165030.04 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.176295E+09 | 13982269.39 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.166377E+09 | 23086576.59 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.161633E+09 | 19503984.74 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.178156E+09 | 18827839.11 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.224292E+09 | 23873957.34 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.275953E+09 | 26323490.18 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.340387E+09 | 40384841.38 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.274568E+10 | 0.275446E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.161633E+09 | 11043770.73 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.345542E+09 | 40384841.38 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.345542E+09 | 36470672.59 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.284390E+09 | 26572124.02 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.234902E+09 | 22211445.14 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.173760E+09 | 11043770.73 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.183994E+09 | 13165030.04 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.176295E+09 | 13982269.39 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.166377E+09 | 23086576.59 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.161633E+09 | 19503984.74 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.178156E+09 | 18827839.11 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.224292E+09 | 23873957.34 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.275953E+09 | 26323490.18 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.340387E+09 | 40384841.38 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.274568E+10 | 0.275446E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.161633E+09 | 11043770.73 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.345542E+09 | 40384841.38 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208261E+09 | 86888977.69 | 0.121372E+09 | 0.411838E+09 | 43396547.21 |
February | 0.159731E+09 | 52078356.13 | 0.107653E+09 | 0.338652E+09 | 31772666.81 |
March | 0.120687E+09 | 16208318.39 | 0.104478E+09 | 0.279251E+09 | 26766743.23 |
April | 87075281.30 | 39088.75 | 87036192.55 | 0.205959E+09 | 13407296.97 |
May | 90039228.17 | 0.00 | 90039228.17 | 0.218174E+09 | 15757893.40 |
June | 86821057.65 | 0.00 | 86821057.65 | 0.209018E+09 | 16728097.39 |
July | 92420071.44 | 0.00 | 92420071.44 | 0.197842E+09 | 27445901.26 |
August | 89971639.51 | 139053.06 | 89832586.44 | 0.192015E+09 | 23298436.27 |
September | 96391965.79 | 3148232.59 | 93243733.19 | 0.211897E+09 | 22408814.57 |
October | 0.130312E+09 | 20777294.20 | 0.109535E+09 | 0.267187E+09 | 28344139.67 |
November | 0.163983E+09 | 50029019.28 | 0.113954E+09 | 0.328832E+09 | 31294805.75 |
December | 0.208155E+09 | 88561297.57 | 0.119593E+09 | 0.405770E+09 | 47979632.70 |
Annual Sum or Average | 0.153385E+10 | 0.317870E+09 | 0.121598E+10 | 0.326644E+10 | 0.328601E+09 |
Minimum of Months | 86821057.65 | 0.00 | 86821057.65 | 0.192015E+09 | 13407296.97 |
Maximum of Months | 0.208261E+09 | 88561297.57 | 0.121372E+09 | 0.411838E+09 | 47979632.70 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.345891E+09 | 35614520.44 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.284706E+09 | 25799375.29 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.235231E+09 | 21282498.46 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.174182E+09 | 10296485.52 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.184464E+09 | 12498510.42 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.176711E+09 | 13272377.64 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.166706E+09 | 22265650.34 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.161991E+09 | 18602037.58 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.178505E+09 | 18007687.20 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.224635E+09 | 22986163.96 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.276309E+09 | 25511805.42 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.340753E+09 | 39544848.69 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.275008E+10 | 0.265682E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.161991E+09 | 10296485.52 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.345891E+09 | 39544848.69 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.345891E+09 | 35614520.44 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.284706E+09 | 25799375.29 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.235231E+09 | 21282498.46 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.174182E+09 | 10296485.52 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.184464E+09 | 12498510.42 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.176711E+09 | 13272377.64 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.166706E+09 | 22265650.34 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.161991E+09 | 18602037.58 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.178505E+09 | 18007687.20 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.224635E+09 | 22986163.96 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.276309E+09 | 25511805.42 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.340753E+09 | 39544848.69 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.275008E+10 | 0.265682E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.161991E+09 | 10296485.52 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.345891E+09 | 39544848.69 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208261E+09 | 86888977.69 | 0.121372E+09 | 0.412257E+09 | 42394330.97 |
February | 0.159731E+09 | 52078356.13 | 0.107653E+09 | 0.339028E+09 | 30865091.31 |
March | 0.120687E+09 | 16208318.39 | 0.104478E+09 | 0.279643E+09 | 25679631.60 |
April | 87075281.30 | 39088.75 | 87036192.55 | 0.206454E+09 | 12523527.41 |
May | 90039228.17 | 0.00 | 90039228.17 | 0.218728E+09 | 14972235.86 |
June | 86821057.65 | 0.00 | 86821057.65 | 0.209504E+09 | 15891011.42 |
July | 92420071.44 | 0.00 | 92420071.44 | 0.198234E+09 | 26482499.39 |
August | 89971639.51 | 139053.06 | 89832586.44 | 0.192441E+09 | 22243782.14 |
September | 96391965.79 | 3148232.59 | 93243733.19 | 0.212314E+09 | 21446529.54 |
October | 0.130312E+09 | 20777294.20 | 0.109535E+09 | 0.267597E+09 | 27301876.42 |
November | 0.163983E+09 | 50029019.28 | 0.113954E+09 | 0.329259E+09 | 30341772.28 |
December | 0.208155E+09 | 88561297.57 | 0.119593E+09 | 0.406207E+09 | 46994642.94 |
Annual Sum or Average | 0.153385E+10 | 0.317870E+09 | 0.121598E+10 | 0.327166E+10 | 0.317137E+09 |
Minimum of Months | 86821057.65 | 0.00 | 86821057.65 | 0.192441E+09 | 12523527.41 |
Maximum of Months | 0.208261E+09 | 88561297.57 | 0.121372E+09 | 0.412257E+09 | 46994642.94 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.345568E+09 | 32617533.82 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.284191E+09 | 23042156.45 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.234763E+09 | 18248281.97 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.174268E+09 | 8294644.47 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.184436E+09 | 10434324.66 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.176692E+09 | 11172292.52 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.166269E+09 | 19596219.30 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.161667E+09 | 15606919.05 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.178392E+09 | 15464782.46 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.224503E+09 | 20130236.12 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.275975E+09 | 22803549.39 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.340462E+09 | 36670292.48 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.274719E+10 | 0.234081E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.161667E+09 | 8294644.47 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.345568E+09 | 36670292.48 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.345568E+09 | 32617533.82 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.284191E+09 | 23042156.45 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.234763E+09 | 18248281.97 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.174268E+09 | 8294644.47 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.184436E+09 | 10434324.66 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.176692E+09 | 11172292.52 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.166269E+09 | 19596219.30 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.161667E+09 | 15606919.05 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.178392E+09 | 15464782.46 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.224503E+09 | 20130236.12 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.275975E+09 | 22803549.39 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.340462E+09 | 36670292.48 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.274719E+10 | 0.234081E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.161667E+09 | 8294644.47 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.345568E+09 | 36670292.48 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.345568E+09 | 32617533.82 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.284191E+09 | 23042156.45 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.234763E+09 | 18248281.97 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.174268E+09 | 8294644.47 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.184436E+09 | 10434324.66 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.176692E+09 | 11172292.52 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.166269E+09 | 19596219.30 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.161667E+09 | 15606919.05 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.178392E+09 | 15464782.46 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.224503E+09 | 20130236.12 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.275975E+09 | 22803549.39 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.340462E+09 | 36670292.48 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.274719E+10 | 0.234081E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.161667E+09 | 8294644.47 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.345568E+09 | 36670292.48 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.345568E+09 | 32617533.82 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.284191E+09 | 23042156.45 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.234763E+09 | 18248281.97 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.174268E+09 | 8294644.47 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.184436E+09 | 10434324.66 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.176692E+09 | 11172292.52 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.166269E+09 | 19596219.30 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.161667E+09 | 15606919.05 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.178392E+09 | 15464782.46 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.224503E+09 | 20130236.12 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.275975E+09 | 22803549.39 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.340462E+09 | 36670292.48 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.274719E+10 | 0.234081E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.161667E+09 | 8294644.47 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.345568E+09 | 36670292.48 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208261E+09 | 86888977.69 | 0.121372E+09 | 0.411850E+09 | 38852194.54 |
February | 0.159731E+09 | 52078356.13 | 0.107653E+09 | 0.338420E+09 | 27596340.41 |
March | 0.120687E+09 | 16208318.39 | 0.104478E+09 | 0.279090E+09 | 22053808.28 |
April | 87075281.30 | 39088.75 | 87036192.55 | 0.206564E+09 | 10082940.24 |
May | 90039228.17 | 0.00 | 90039228.17 | 0.218726E+09 | 12494185.16 |
June | 86821057.65 | 0.00 | 86821057.65 | 0.209499E+09 | 13368837.27 |
July | 92420071.44 | 0.00 | 92420071.44 | 0.197733E+09 | 23317765.42 |
August | 89971639.51 | 139053.06 | 89832586.44 | 0.192096E+09 | 18697064.43 |
September | 96391965.79 | 3148232.59 | 93243733.19 | 0.212193E+09 | 18423739.38 |
October | 0.130312E+09 | 20777294.20 | 0.109535E+09 | 0.267445E+09 | 23920586.67 |
November | 0.163983E+09 | 50029019.28 | 0.113954E+09 | 0.328859E+09 | 27135474.51 |
December | 0.208155E+09 | 88561297.57 | 0.119593E+09 | 0.405849E+09 | 43603318.38 |
Annual Sum or Average | 0.153385E+10 | 0.317870E+09 | 0.121598E+10 | 0.326832E+10 | 0.279546E+09 |
Minimum of Months | 86821057.65 | 0.00 | 86821057.65 | 0.192096E+09 | 10082940.24 |
Maximum of Months | 0.208261E+09 | 88561297.57 | 0.121372E+09 | 0.411850E+09 | 43603318.38 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208261E+09 | 86888977.69 | 0.121372E+09 | 0.411850E+09 | 38852194.54 |
February | 0.159731E+09 | 52078356.13 | 0.107653E+09 | 0.338420E+09 | 27596340.41 |
March | 0.120687E+09 | 16208318.39 | 0.104478E+09 | 0.279090E+09 | 22053808.28 |
April | 87075281.30 | 39088.75 | 87036192.55 | 0.206564E+09 | 10082940.24 |
May | 90039228.17 | 0.00 | 90039228.17 | 0.218726E+09 | 12494185.16 |
June | 86821057.65 | 0.00 | 86821057.65 | 0.209499E+09 | 13368837.27 |
July | 92420071.44 | 0.00 | 92420071.44 | 0.197733E+09 | 23317765.42 |
August | 89971639.51 | 139053.06 | 89832586.44 | 0.192096E+09 | 18697064.43 |
September | 96391965.79 | 3148232.59 | 93243733.19 | 0.212193E+09 | 18423739.38 |
October | 0.130312E+09 | 20777294.20 | 0.109535E+09 | 0.267445E+09 | 23920586.67 |
November | 0.163983E+09 | 50029019.28 | 0.113954E+09 | 0.328859E+09 | 27135474.51 |
December | 0.208155E+09 | 88561297.57 | 0.119593E+09 | 0.405849E+09 | 43603318.38 |
Annual Sum or Average | 0.153385E+10 | 0.317870E+09 | 0.121598E+10 | 0.326832E+10 | 0.279546E+09 |
Minimum of Months | 86821057.65 | 0.00 | 86821057.65 | 0.192096E+09 | 10082940.24 |
Maximum of Months | 0.208261E+09 | 88561297.57 | 0.121372E+09 | 0.411850E+09 | 43603318.38 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.346145E+09 | 31483409.84 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.284897E+09 | 21926827.10 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.235823E+09 | 16929774.06 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.175944E+09 | 7396232.42 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.186170E+09 | 9591048.12 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.178372E+09 | 10246892.49 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.167265E+09 | 18511889.59 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.162757E+09 | 14444099.09 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.179381E+09 | 14454433.09 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.225241E+09 | 19022419.21 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.276622E+09 | 21761027.07 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.340962E+09 | 35581225.12 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.275958E+10 | 0.221349E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.162757E+09 | 7396232.42 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.346145E+09 | 35581225.12 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.346145E+09 | 31483409.84 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.284897E+09 | 21926827.10 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.235823E+09 | 16929774.06 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.175944E+09 | 7396232.42 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.186170E+09 | 9591048.12 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.178372E+09 | 10246892.49 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.167265E+09 | 18511889.59 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.162757E+09 | 14444099.09 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.179381E+09 | 14454433.09 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.225241E+09 | 19022419.21 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.276622E+09 | 21761027.07 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.340962E+09 | 35581225.12 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.275958E+10 | 0.221349E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.162757E+09 | 7396232.42 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.346145E+09 | 35581225.12 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208261E+09 | 86888977.69 | 0.121372E+09 | 0.412603E+09 | 37518013.43 |
February | 0.159731E+09 | 52078356.13 | 0.107653E+09 | 0.339294E+09 | 26290192.73 |
March | 0.120687E+09 | 16208318.39 | 0.104478E+09 | 0.280335E+09 | 20516455.94 |
April | 87075281.30 | 39088.75 | 87036192.55 | 0.208486E+09 | 9019483.88 |
May | 90039228.17 | 0.00 | 90039228.17 | 0.220742E+09 | 11500434.17 |
June | 86821057.65 | 0.00 | 86821057.65 | 0.211447E+09 | 12276043.76 |
July | 92420071.44 | 0.00 | 92420071.44 | 0.198923E+09 | 22040943.02 |
August | 89971639.51 | 139053.06 | 89832586.44 | 0.193383E+09 | 17337313.06 |
September | 96391965.79 | 3148232.59 | 93243733.19 | 0.213376E+09 | 17234067.82 |
October | 0.130312E+09 | 20777294.20 | 0.109535E+09 | 0.268367E+09 | 22611992.30 |
November | 0.163983E+09 | 50029019.28 | 0.113954E+09 | 0.329689E+09 | 25906012.35 |
December | 0.208155E+09 | 88561297.57 | 0.119593E+09 | 0.406521E+09 | 42316427.88 |
Annual Sum or Average | 0.153385E+10 | 0.317870E+09 | 0.121598E+10 | 0.328317E+10 | 0.264567E+09 |
Minimum of Months | 86821057.65 | 0.00 | 86821057.65 | 0.193383E+09 | 9019483.88 |
Maximum of Months | 0.208261E+09 | 88561297.57 | 0.121372E+09 | 0.412603E+09 | 42316427.88 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.346326E+09 | 31261899.50 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.285051E+09 | 21743199.78 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.235985E+09 | 16731694.54 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.176137E+09 | 7261921.85 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.186378E+09 | 9461269.04 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.178567E+09 | 10106080.22 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.167420E+09 | 18333217.46 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.162918E+09 | 14253762.03 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.179536E+09 | 14283508.07 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.225409E+09 | 18806079.26 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.276796E+09 | 21554483.72 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.341143E+09 | 35353192.82 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.276166E+10 | 0.219150E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.162918E+09 | 7261921.85 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.346326E+09 | 35353192.82 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.346326E+09 | 31261899.50 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.285051E+09 | 21743199.78 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.235985E+09 | 16731694.54 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.176137E+09 | 7261921.85 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.186378E+09 | 9461269.04 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.178567E+09 | 10106080.22 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.167420E+09 | 18333217.46 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.162918E+09 | 14253762.03 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.179536E+09 | 14283508.07 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.225409E+09 | 18806079.26 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.276796E+09 | 21554483.72 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.341143E+09 | 35353192.82 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.276166E+10 | 0.219150E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.162918E+09 | 7261921.85 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.346326E+09 | 35353192.82 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208261E+09 | 86888977.69 | 0.121372E+09 | 0.412820E+09 | 37256265.55 |
February | 0.159731E+09 | 52078356.13 | 0.107653E+09 | 0.339477E+09 | 26070767.85 |
March | 0.120687E+09 | 16208318.39 | 0.104478E+09 | 0.280527E+09 | 20281664.37 |
April | 87075281.30 | 39088.75 | 87036192.55 | 0.208713E+09 | 8859196.05 |
May | 90039228.17 | 0.00 | 90039228.17 | 0.220987E+09 | 11344873.80 |
June | 86821057.65 | 0.00 | 86821057.65 | 0.211678E+09 | 12108097.95 |
July | 92420071.44 | 0.00 | 92420071.44 | 0.199107E+09 | 21829111.11 |
August | 89971639.51 | 139053.06 | 89832586.44 | 0.193574E+09 | 17111872.12 |
September | 96391965.79 | 3148232.59 | 93243733.19 | 0.213562E+09 | 17031897.23 |
October | 0.130312E+09 | 20777294.20 | 0.109535E+09 | 0.268568E+09 | 22355602.77 |
November | 0.163983E+09 | 50029019.28 | 0.113954E+09 | 0.329897E+09 | 25661886.28 |
December | 0.208155E+09 | 88561297.57 | 0.119593E+09 | 0.406736E+09 | 42046253.34 |
Annual Sum or Average | 0.153385E+10 | 0.317870E+09 | 0.121598E+10 | 0.328565E+10 | 0.261957E+09 |
Minimum of Months | 86821057.65 | 0.00 | 86821057.65 | 0.193574E+09 | 8859196.05 |
Maximum of Months | 0.208261E+09 | 88561297.57 | 0.121372E+09 | 0.412820E+09 | 42046253.34 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.346227E+09 | 31257498.83 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.284867E+09 | 21833141.07 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.235719E+09 | 16890614.84 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.175687E+09 | 7441730.23 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.185890E+09 | 9620115.84 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.178111E+09 | 10316748.16 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.167103E+09 | 18565540.81 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.162635E+09 | 14415939.62 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.179220E+09 | 14473904.32 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.225236E+09 | 18857440.03 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.276676E+09 | 21562465.90 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.341085E+09 | 35313387.23 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.275846E+10 | 0.220549E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.162635E+09 | 7441730.23 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.346227E+09 | 35313387.23 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.346227E+09 | 31257498.83 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.284867E+09 | 21833141.07 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.235719E+09 | 16890614.84 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.175687E+09 | 7441730.23 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.185890E+09 | 9620115.84 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.178111E+09 | 10316748.16 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.167103E+09 | 18565540.81 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.162635E+09 | 14415939.62 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.179220E+09 | 14473904.32 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.225236E+09 | 18857440.03 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.276676E+09 | 21562465.90 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.341085E+09 | 35313387.23 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.275846E+10 | 0.220549E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.162635E+09 | 7441730.23 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.346227E+09 | 35313387.23 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208261E+09 | 86888977.69 | 0.121372E+09 | 0.412698E+09 | 37258733.53 |
February | 0.159731E+09 | 52078356.13 | 0.107653E+09 | 0.339256E+09 | 26185613.79 |
March | 0.120687E+09 | 16208318.39 | 0.104478E+09 | 0.280208E+09 | 20477717.55 |
April | 87075281.30 | 39088.75 | 87036192.55 | 0.208178E+09 | 9081002.01 |
May | 90039228.17 | 0.00 | 90039228.17 | 0.220407E+09 | 11540441.48 |
June | 86821057.65 | 0.00 | 86821057.65 | 0.211136E+09 | 12367098.20 |
July | 92420071.44 | 0.00 | 92420071.44 | 0.198726E+09 | 22112024.33 |
August | 89971639.51 | 139053.06 | 89832586.44 | 0.193235E+09 | 17311888.47 |
September | 96391965.79 | 3148232.59 | 93243733.19 | 0.213183E+09 | 17263320.79 |
October | 0.130312E+09 | 20777294.20 | 0.109535E+09 | 0.268360E+09 | 22425115.29 |
November | 0.163983E+09 | 50029019.28 | 0.113954E+09 | 0.329750E+09 | 25678565.64 |
December | 0.208155E+09 | 88561297.57 | 0.119593E+09 | 0.406665E+09 | 42007608.12 |
Annual Sum or Average | 0.153385E+10 | 0.317870E+09 | 0.121598E+10 | 0.328180E+10 | 0.263709E+09 |
Minimum of Months | 86821057.65 | 0.00 | 86821057.65 | 0.193235E+09 | 9081002.01 |
Maximum of Months | 0.208261E+09 | 88561297.57 | 0.121372E+09 | 0.412698E+09 | 42007608.12 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.343350E+09 | 32287399.31 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.281550E+09 | 23234383.47 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.231602E+09 | 18717385.39 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.170429E+09 | 9151792.73 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.180511E+09 | 11144662.79 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.172877E+09 | 12214753.80 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.163032E+09 | 20785623.49 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.158704E+09 | 16355122.27 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.175173E+09 | 16492143.82 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.222206E+09 | 20264097.26 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.273770E+09 | 22683813.70 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.338488E+09 | 36207227.35 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.271169E+10 | 0.239538E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.158704E+09 | 9151792.73 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.343350E+09 | 36207227.35 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.343350E+09 | 32287399.31 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.281550E+09 | 23234383.47 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.231602E+09 | 18717385.39 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.170429E+09 | 9151792.73 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.180511E+09 | 11144662.79 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.172877E+09 | 12214753.80 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.163032E+09 | 20785623.49 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.158704E+09 | 16355122.27 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.175173E+09 | 16492143.82 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.222206E+09 | 20264097.26 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.273770E+09 | 22683813.70 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.338488E+09 | 36207227.35 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.271169E+10 | 0.239538E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.158704E+09 | 9151792.73 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.343350E+09 | 36207227.35 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208261E+09 | 86888977.69 | 0.121372E+09 | 0.409243E+09 | 38492429.12 |
February | 0.159731E+09 | 52078356.13 | 0.107653E+09 | 0.335287E+09 | 27864983.67 |
March | 0.120687E+09 | 16208318.39 | 0.104478E+09 | 0.275300E+09 | 22660283.46 |
April | 87075281.30 | 39088.75 | 87036192.55 | 0.201949E+09 | 11156127.01 |
May | 90039228.17 | 0.00 | 90039228.17 | 0.214023E+09 | 13386712.35 |
June | 86821057.65 | 0.00 | 86821057.65 | 0.204914E+09 | 14640036.78 |
July | 92420071.44 | 0.00 | 92420071.44 | 0.193863E+09 | 24747341.38 |
August | 89971639.51 | 139053.06 | 89832586.44 | 0.188542E+09 | 19615282.70 |
September | 96391965.79 | 3148232.59 | 93243733.19 | 0.208342E+09 | 19665241.13 |
October | 0.130312E+09 | 20777294.20 | 0.109535E+09 | 0.264725E+09 | 24098126.65 |
November | 0.163983E+09 | 50029019.28 | 0.113954E+09 | 0.326251E+09 | 27010935.17 |
December | 0.208155E+09 | 88561297.57 | 0.119593E+09 | 0.403542E+09 | 43079695.20 |
Annual Sum or Average | 0.153385E+10 | 0.317870E+09 | 0.121598E+10 | 0.322598E+10 | 0.286417E+09 |
Minimum of Months | 86821057.65 | 0.00 | 86821057.65 | 0.188542E+09 | 11156127.01 |
Maximum of Months | 0.208261E+09 | 88561297.57 | 0.121372E+09 | 0.409243E+09 | 43079695.20 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 824.61 | 69.53 | 416.51 | 173.77 | 242.74 | 0.00 | 0.00 |
February | 750.64 | 53.30 | 353.68 | 115.31 | 238.37 | 0.00 | 0.00 |
March | 559.05 | 37.91 | 241.37 | 32.42 | 208.95 | 0.00 | 0.00 |
April | 434.28 | 18.41 | 179.95 | 0.08 | 179.87 | 0.00 | 0.00 |
May | 446.44 | 21.97 | 180.07 | 0.00 | 180.07 | 0.00 | 0.00 |
June | 439.85 | 23.99 | 179.42 | 0.00 | 179.42 | 0.00 | 0.00 |
July | 400.75 | 41.06 | 184.83 | 0.00 | 184.83 | 0.00 | 0.00 |
August | 385.05 | 32.75 | 179.94 | 0.28 | 179.66 | 0.00 | 0.00 |
September | 441.72 | 33.18 | 199.20 | 6.51 | 192.70 | 0.00 | 0.00 |
October | 536.37 | 41.47 | 260.62 | 41.55 | 219.06 | 0.00 | 0.00 |
November | 680.07 | 49.76 | 338.89 | 103.39 | 235.50 | 0.00 | 0.00 |
December | 811.75 | 79.47 | 416.30 | 177.12 | 239.18 | 0.00 | 0.00 |
Annual Sum or Average | 558.30 | 41.92 | 260.54 | 53.99 | 206.54 | 0.00 | 0.00 |
Minimum of Months | 385.05 | 18.41 | 179.42 | 0.00 | 179.42 | 0.00 | 0.00 |
Maximum of Months | 824.61 | 79.47 | 416.51 | 177.12 | 242.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 413.66 | 34.51 | 208.25 | 86.89 | 121.37 | 0.00 | 0.00 |
February | 377.37 | 26.15 | 176.84 | 57.66 | 119.18 | 0.00 | 0.00 |
March | 282.41 | 18.27 | 120.68 | 16.21 | 104.48 | 0.00 | 0.00 |
April | 220.92 | 8.72 | 89.97 | 0.04 | 89.93 | 0.00 | 0.00 |
May | 226.62 | 10.68 | 90.04 | 0.00 | 90.04 | 0.00 | 0.00 |
June | 223.56 | 11.51 | 89.71 | 0.00 | 89.71 | 0.00 | 0.00 |
July | 202.80 | 20.06 | 92.42 | 0.00 | 92.42 | 0.00 | 0.00 |
August | 195.05 | 15.94 | 89.97 | 0.14 | 89.83 | 0.00 | 0.00 |
September | 223.36 | 16.16 | 99.60 | 3.25 | 96.35 | 0.00 | 0.00 |
October | 269.82 | 20.56 | 130.31 | 20.78 | 109.53 | 0.00 | 0.00 |
November | 341.64 | 24.71 | 169.44 | 51.70 | 117.75 | 0.00 | 0.00 |
December | 406.99 | 39.55 | 208.15 | 88.56 | 119.59 | 0.00 | 0.00 |
Annual Sum or Average | 281.56 | 20.58 | 130.27 | 27.00 | 103.27 | 0.00 | 0.00 |
Minimum of Months | 195.05 | 8.72 | 89.71 | 0.00 | 89.71 | 0.00 | 0.00 |
Maximum of Months | 413.66 | 39.55 | 208.25 | 88.56 | 121.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 411.93 | 42.84 | 207.83 | 86.71 | 121.12 | 0.00 | 0.00 |
February | 375.27 | 34.45 | 176.48 | 57.54 | 118.94 | 0.00 | 0.00 |
March | 279.80 | 25.88 | 120.44 | 16.17 | 104.26 | 0.00 | 0.00 |
April | 213.82 | 12.99 | 89.79 | 0.04 | 89.75 | 0.00 | 0.00 |
May | 219.32 | 15.06 | 89.85 | 0.00 | 89.85 | 0.00 | 0.00 |
June | 216.99 | 16.45 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
July | 198.33 | 26.73 | 92.23 | 0.00 | 92.23 | 0.00 | 0.00 |
August | 192.51 | 22.68 | 89.78 | 0.14 | 89.65 | 0.00 | 0.00 |
September | 219.39 | 22.52 | 99.40 | 3.25 | 96.15 | 0.00 | 0.00 |
October | 267.37 | 27.81 | 130.04 | 20.73 | 109.31 | 0.00 | 0.00 |
November | 339.90 | 31.91 | 169.10 | 51.59 | 117.51 | 0.00 | 0.00 |
December | 405.77 | 47.62 | 207.72 | 88.38 | 119.34 | 0.00 | 0.00 |
Annual Sum or Average | 277.91 | 27.26 | 130.00 | 26.94 | 103.06 | 0.00 | 0.00 |
Minimum of Months | 192.51 | 12.99 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
Maximum of Months | 411.93 | 47.62 | 207.83 | 88.38 | 121.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 411.78 | 43.44 | 207.83 | 86.71 | 121.12 | 0.00 | 0.00 |
February | 375.10 | 35.10 | 176.48 | 57.54 | 118.94 | 0.00 | 0.00 |
March | 279.66 | 26.58 | 120.44 | 16.17 | 104.26 | 0.00 | 0.00 |
April | 213.53 | 13.69 | 89.79 | 0.04 | 89.75 | 0.00 | 0.00 |
May | 218.85 | 15.71 | 89.85 | 0.00 | 89.85 | 0.00 | 0.00 |
June | 216.67 | 17.24 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
July | 198.10 | 27.49 | 92.23 | 0.00 | 92.23 | 0.00 | 0.00 |
August | 192.38 | 23.26 | 89.78 | 0.14 | 89.65 | 0.00 | 0.00 |
September | 219.22 | 23.17 | 99.40 | 3.25 | 96.15 | 0.00 | 0.00 |
October | 267.24 | 28.41 | 130.04 | 20.73 | 109.31 | 0.00 | 0.00 |
November | 339.79 | 32.38 | 169.10 | 51.59 | 117.51 | 0.00 | 0.00 |
December | 405.67 | 48.07 | 207.72 | 88.38 | 119.34 | 0.00 | 0.00 |
Annual Sum or Average | 277.71 | 27.89 | 130.00 | 26.94 | 103.06 | 0.00 | 0.00 |
Minimum of Months | 192.38 | 13.69 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
Maximum of Months | 411.78 | 48.07 | 207.83 | 88.38 | 121.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 412.20 | 42.42 | 207.83 | 86.71 | 121.12 | 0.00 | 0.00 |
February | 375.51 | 34.09 | 176.48 | 57.54 | 118.94 | 0.00 | 0.00 |
March | 280.06 | 25.48 | 120.44 | 16.17 | 104.26 | 0.00 | 0.00 |
April | 214.05 | 12.78 | 89.79 | 0.04 | 89.75 | 0.00 | 0.00 |
May | 219.40 | 14.92 | 89.85 | 0.00 | 89.85 | 0.00 | 0.00 |
June | 217.18 | 16.37 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
July | 198.49 | 26.51 | 92.23 | 0.00 | 92.23 | 0.00 | 0.00 |
August | 192.81 | 22.20 | 89.78 | 0.14 | 89.65 | 0.00 | 0.00 |
September | 219.65 | 22.17 | 99.40 | 3.25 | 96.15 | 0.00 | 0.00 |
October | 267.65 | 27.36 | 130.04 | 20.73 | 109.31 | 0.00 | 0.00 |
November | 340.23 | 31.39 | 169.10 | 51.59 | 117.51 | 0.00 | 0.00 |
December | 406.10 | 47.07 | 207.72 | 88.38 | 119.34 | 0.00 | 0.00 |
Annual Sum or Average | 278.15 | 26.91 | 130.00 | 26.94 | 103.06 | 0.00 | 0.00 |
Minimum of Months | 192.81 | 12.78 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
Maximum of Months | 412.20 | 47.07 | 207.83 | 88.38 | 121.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 823.61 | 77.72 | 415.65 | 173.42 | 242.24 | 0.00 | 0.00 |
February | 749.67 | 60.91 | 352.95 | 115.08 | 237.88 | 0.00 | 0.00 |
March | 559.00 | 43.72 | 240.87 | 32.35 | 208.52 | 0.00 | 0.00 |
April | 428.32 | 20.58 | 179.58 | 0.08 | 179.50 | 0.00 | 0.00 |
May | 438.77 | 24.91 | 179.70 | 0.00 | 179.70 | 0.00 | 0.00 |
June | 434.32 | 27.56 | 179.06 | 0.00 | 179.06 | 0.00 | 0.00 |
July | 395.96 | 46.68 | 184.46 | 0.00 | 184.46 | 0.00 | 0.00 |
August | 384.88 | 37.27 | 179.57 | 0.28 | 179.29 | 0.00 | 0.00 |
September | 439.02 | 38.08 | 198.80 | 6.49 | 192.30 | 0.00 | 0.00 |
October | 534.98 | 47.92 | 260.08 | 41.47 | 218.61 | 0.00 | 0.00 |
November | 679.64 | 56.13 | 338.19 | 103.18 | 235.01 | 0.00 | 0.00 |
December | 811.51 | 87.32 | 415.44 | 176.75 | 238.69 | 0.00 | 0.00 |
Annual Sum or Average | 555.73 | 47.42 | 260.00 | 53.88 | 206.12 | 0.00 | 0.00 |
Minimum of Months | 384.88 | 20.58 | 179.06 | 0.00 | 179.06 | 0.00 | 0.00 |
Maximum of Months | 823.61 | 87.32 | 415.65 | 176.75 | 242.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 412.52 | 37.52 | 207.83 | 86.71 | 121.12 | 0.00 | 0.00 |
February | 375.78 | 28.99 | 176.48 | 57.54 | 118.94 | 0.00 | 0.00 |
March | 280.76 | 20.30 | 120.44 | 16.17 | 104.26 | 0.00 | 0.00 |
April | 216.19 | 9.19 | 89.79 | 0.04 | 89.75 | 0.00 | 0.00 |
May | 221.43 | 11.45 | 89.85 | 0.00 | 89.85 | 0.00 | 0.00 |
June | 219.21 | 12.64 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
July | 199.17 | 22.05 | 92.23 | 0.00 | 92.23 | 0.00 | 0.00 |
August | 193.73 | 17.26 | 89.78 | 0.14 | 89.65 | 0.00 | 0.00 |
September | 220.73 | 17.80 | 99.40 | 3.25 | 96.15 | 0.00 | 0.00 |
October | 268.39 | 22.65 | 130.04 | 20.73 | 109.31 | 0.00 | 0.00 |
November | 340.64 | 26.79 | 169.10 | 51.59 | 117.51 | 0.00 | 0.00 |
December | 406.38 | 42.37 | 207.72 | 88.38 | 119.34 | 0.00 | 0.00 |
Annual Sum or Average | 279.12 | 22.43 | 130.00 | 26.94 | 103.06 | 0.00 | 0.00 |
Minimum of Months | 193.73 | 9.19 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
Maximum of Months | 412.52 | 42.37 | 207.83 | 88.38 | 121.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 412.74 | 37.25 | 207.83 | 86.71 | 121.12 | 0.00 | 0.00 |
February | 375.98 | 28.75 | 176.48 | 57.54 | 118.94 | 0.00 | 0.00 |
March | 280.95 | 20.07 | 120.44 | 16.17 | 104.26 | 0.00 | 0.00 |
April | 216.43 | 9.02 | 89.79 | 0.04 | 89.75 | 0.00 | 0.00 |
May | 221.68 | 11.30 | 89.85 | 0.00 | 89.85 | 0.00 | 0.00 |
June | 219.45 | 12.47 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
July | 199.35 | 21.84 | 92.23 | 0.00 | 92.23 | 0.00 | 0.00 |
August | 193.92 | 17.03 | 89.78 | 0.14 | 89.65 | 0.00 | 0.00 |
September | 220.92 | 17.59 | 99.40 | 3.25 | 96.15 | 0.00 | 0.00 |
October | 268.59 | 22.39 | 130.04 | 20.73 | 109.31 | 0.00 | 0.00 |
November | 340.85 | 26.53 | 169.10 | 51.59 | 117.51 | 0.00 | 0.00 |
December | 406.59 | 42.10 | 207.72 | 88.38 | 119.34 | 0.00 | 0.00 |
Annual Sum or Average | 279.33 | 22.20 | 130.00 | 26.94 | 103.06 | 0.00 | 0.00 |
Minimum of Months | 193.92 | 9.02 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
Maximum of Months | 412.74 | 42.10 | 207.83 | 88.38 | 121.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 412.62 | 37.25 | 207.83 | 86.71 | 121.12 | 0.00 | 0.00 |
February | 375.74 | 28.87 | 176.48 | 57.54 | 118.94 | 0.00 | 0.00 |
March | 280.63 | 20.26 | 120.44 | 16.17 | 104.26 | 0.00 | 0.00 |
April | 215.88 | 9.24 | 89.79 | 0.04 | 89.75 | 0.00 | 0.00 |
May | 221.10 | 11.49 | 89.85 | 0.00 | 89.85 | 0.00 | 0.00 |
June | 218.89 | 12.73 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
July | 198.97 | 22.12 | 92.23 | 0.00 | 92.23 | 0.00 | 0.00 |
August | 193.59 | 17.23 | 89.78 | 0.14 | 89.65 | 0.00 | 0.00 |
September | 220.53 | 17.83 | 99.40 | 3.25 | 96.15 | 0.00 | 0.00 |
October | 268.38 | 22.45 | 130.04 | 20.73 | 109.31 | 0.00 | 0.00 |
November | 340.70 | 26.54 | 169.10 | 51.59 | 117.51 | 0.00 | 0.00 |
December | 406.52 | 42.05 | 207.72 | 88.38 | 119.34 | 0.00 | 0.00 |
Annual Sum or Average | 279.00 | 22.35 | 130.00 | 26.94 | 103.06 | 0.00 | 0.00 |
Minimum of Months | 193.59 | 9.24 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
Maximum of Months | 412.62 | 42.05 | 207.83 | 88.38 | 121.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 409.18 | 38.48 | 207.83 | 86.71 | 121.12 | 0.00 | 0.00 |
February | 371.36 | 30.72 | 176.48 | 57.54 | 118.94 | 0.00 | 0.00 |
March | 275.72 | 22.44 | 120.44 | 16.17 | 104.26 | 0.00 | 0.00 |
April | 209.42 | 11.36 | 89.79 | 0.04 | 89.75 | 0.00 | 0.00 |
May | 214.70 | 13.32 | 89.85 | 0.00 | 89.85 | 0.00 | 0.00 |
June | 212.45 | 15.07 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
July | 194.12 | 24.76 | 92.23 | 0.00 | 92.23 | 0.00 | 0.00 |
August | 188.90 | 19.54 | 89.78 | 0.14 | 89.65 | 0.00 | 0.00 |
September | 215.54 | 20.31 | 99.40 | 3.25 | 96.15 | 0.00 | 0.00 |
October | 264.76 | 24.13 | 130.04 | 20.73 | 109.31 | 0.00 | 0.00 |
November | 337.11 | 27.92 | 169.10 | 51.59 | 117.51 | 0.00 | 0.00 |
December | 403.42 | 43.12 | 207.72 | 88.38 | 119.34 | 0.00 | 0.00 |
Annual Sum or Average | 274.27 | 24.27 | 130.00 | 26.94 | 103.06 | 0.00 | 0.00 |
Minimum of Months | 188.90 | 11.36 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
Maximum of Months | 409.18 | 43.12 | 207.83 | 88.38 | 121.12 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.220864E+10 | 0.186235E+09 | 0.111558E+10 | 0.465432E+09 | 0.650147E+09 | 0.00 | 0.00 |
February | 0.181595E+10 | 0.128951E+09 | 0.855621E+09 | 0.278965E+09 | 0.576656E+09 | 0.00 | 0.00 |
March | 0.149736E+10 | 0.101528E+09 | 0.646475E+09 | 86821998.08 | 0.559653E+09 | 0.00 | 0.00 |
April | 0.112564E+10 | 47724793.81 | 0.466430E+09 | 209384.06 | 0.466221E+09 | 0.00 | 0.00 |
May | 0.119576E+10 | 58835514.44 | 0.482307E+09 | 0.00 | 0.482307E+09 | 0.00 | 0.00 |
June | 0.114010E+10 | 62187812.53 | 0.465068E+09 | 0.00 | 0.465068E+09 | 0.00 | 0.00 |
July | 0.107337E+10 | 0.109971E+09 | 0.495060E+09 | 0.00 | 0.495060E+09 | 0.00 | 0.00 |
August | 0.103132E+10 | 87719712.09 | 0.481945E+09 | 744856.10 | 0.481200E+09 | 0.00 | 0.00 |
September | 0.114494E+10 | 86002565.20 | 0.516336E+09 | 16863923.66 | 0.499472E+09 | 0.00 | 0.00 |
October | 0.143660E+10 | 0.111084E+09 | 0.698036E+09 | 0.111296E+09 | 0.586740E+09 | 0.00 | 0.00 |
November | 0.176275E+10 | 0.128980E+09 | 0.878397E+09 | 0.267987E+09 | 0.610409E+09 | 0.00 | 0.00 |
December | 0.217418E+10 | 0.212851E+09 | 0.111501E+10 | 0.474390E+09 | 0.640618E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.176066E+11 | 0.132207E+10 | 0.821626E+10 | 0.170271E+10 | 0.651355E+10 | 0.00 | 0.00 |
Minimum of Months | 0.103132E+10 | 47724793.81 | 0.465068E+09 | 0.00 | 0.465068E+09 | 0.00 | 0.00 |
Maximum of Months | 0.220864E+10 | 0.212851E+09 | 0.111558E+10 | 0.474390E+09 | 0.650147E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.110794E+10 | 92438992.02 | 0.557789E+09 | 0.232716E+09 | 0.325073E+09 | 0.00 | 0.00 |
February | 0.912943E+09 | 63261063.14 | 0.427810E+09 | 0.139482E+09 | 0.288328E+09 | 0.00 | 0.00 |
March | 0.756419E+09 | 48937121.05 | 0.323237E+09 | 43410999.04 | 0.279826E+09 | 0.00 | 0.00 |
April | 0.572619E+09 | 22607570.58 | 0.233215E+09 | 104692.03 | 0.233110E+09 | 0.00 | 0.00 |
May | 0.606974E+09 | 28602078.70 | 0.241154E+09 | 0.00 | 0.241154E+09 | 0.00 | 0.00 |
June | 0.579464E+09 | 29841014.68 | 0.232534E+09 | 0.00 | 0.232534E+09 | 0.00 | 0.00 |
July | 0.543187E+09 | 53719991.01 | 0.247530E+09 | 0.00 | 0.247530E+09 | 0.00 | 0.00 |
August | 0.522409E+09 | 42697729.10 | 0.240972E+09 | 372428.05 | 0.240600E+09 | 0.00 | 0.00 |
September | 0.578957E+09 | 41882607.82 | 0.258168E+09 | 8431961.83 | 0.249736E+09 | 0.00 | 0.00 |
October | 0.722690E+09 | 55065367.38 | 0.349018E+09 | 55648160.21 | 0.293370E+09 | 0.00 | 0.00 |
November | 0.885538E+09 | 64060663.18 | 0.439198E+09 | 0.133994E+09 | 0.305205E+09 | 0.00 | 0.00 |
December | 0.109008E+10 | 0.105927E+09 | 0.557504E+09 | 0.237195E+09 | 0.320309E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.887922E+10 | 0.649042E+09 | 0.410813E+10 | 0.851355E+09 | 0.325678E+10 | 0.00 | 0.00 |
Minimum of Months | 0.522409E+09 | 22607570.58 | 0.232534E+09 | 0.00 | 0.232534E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110794E+10 | 0.105927E+09 | 0.557789E+09 | 0.237195E+09 | 0.325073E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.110331E+10 | 0.114756E+09 | 0.556645E+09 | 0.232239E+09 | 0.324406E+09 | 0.00 | 0.00 |
February | 0.907852E+09 | 83353519.32 | 0.426933E+09 | 0.139196E+09 | 0.287737E+09 | 0.00 | 0.00 |
March | 0.749420E+09 | 69313257.81 | 0.322574E+09 | 43321942.35 | 0.279252E+09 | 0.00 | 0.00 |
April | 0.554210E+09 | 33666046.17 | 0.232737E+09 | 104477.26 | 0.232632E+09 | 0.00 | 0.00 |
May | 0.587428E+09 | 40349114.68 | 0.240659E+09 | 0.00 | 0.240659E+09 | 0.00 | 0.00 |
June | 0.562428E+09 | 42643984.17 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
July | 0.531202E+09 | 71590800.79 | 0.247022E+09 | 0.00 | 0.247022E+09 | 0.00 | 0.00 |
August | 0.515618E+09 | 60739119.97 | 0.240478E+09 | 371664.02 | 0.240106E+09 | 0.00 | 0.00 |
September | 0.568655E+09 | 58367759.18 | 0.257639E+09 | 8414663.85 | 0.249224E+09 | 0.00 | 0.00 |
October | 0.716113E+09 | 74473482.70 | 0.348302E+09 | 55533999.25 | 0.292768E+09 | 0.00 | 0.00 |
November | 0.881018E+09 | 82720935.39 | 0.438297E+09 | 0.133719E+09 | 0.304579E+09 | 0.00 | 0.00 |
December | 0.108682E+10 | 0.127556E+09 | 0.556360E+09 | 0.236709E+09 | 0.319652E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.876407E+10 | 0.859529E+09 | 0.409970E+10 | 0.849609E+09 | 0.325009E+10 | 0.00 | 0.00 |
Minimum of Months | 0.515618E+09 | 33666046.17 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110331E+10 | 0.127556E+09 | 0.556645E+09 | 0.236709E+09 | 0.324406E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.110292E+10 | 0.116337E+09 | 0.556645E+09 | 0.232239E+09 | 0.324406E+09 | 0.00 | 0.00 |
February | 0.907431E+09 | 84915081.83 | 0.426933E+09 | 0.139196E+09 | 0.287737E+09 | 0.00 | 0.00 |
March | 0.749054E+09 | 71188694.44 | 0.322574E+09 | 43321942.35 | 0.279252E+09 | 0.00 | 0.00 |
April | 0.553476E+09 | 35492547.85 | 0.232737E+09 | 104477.26 | 0.232632E+09 | 0.00 | 0.00 |
May | 0.586161E+09 | 42086664.78 | 0.240659E+09 | 0.00 | 0.240659E+09 | 0.00 | 0.00 |
June | 0.561606E+09 | 44690675.92 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
July | 0.530595E+09 | 73618677.42 | 0.247022E+09 | 0.00 | 0.247022E+09 | 0.00 | 0.00 |
August | 0.515281E+09 | 62306003.48 | 0.240478E+09 | 371664.02 | 0.240106E+09 | 0.00 | 0.00 |
September | 0.568209E+09 | 60064174.34 | 0.257639E+09 | 8414663.85 | 0.249224E+09 | 0.00 | 0.00 |
October | 0.715770E+09 | 76091736.99 | 0.348302E+09 | 55533999.25 | 0.292768E+09 | 0.00 | 0.00 |
November | 0.880737E+09 | 83941485.41 | 0.438297E+09 | 0.133719E+09 | 0.304579E+09 | 0.00 | 0.00 |
December | 0.108654E+10 | 0.128748E+09 | 0.556360E+09 | 0.236709E+09 | 0.319652E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.875779E+10 | 0.879481E+09 | 0.409970E+10 | 0.849609E+09 | 0.325009E+10 | 0.00 | 0.00 |
Minimum of Months | 0.515281E+09 | 35492547.85 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110292E+10 | 0.128748E+09 | 0.556645E+09 | 0.236709E+09 | 0.324406E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.110404E+10 | 0.113623E+09 | 0.556645E+09 | 0.232239E+09 | 0.324406E+09 | 0.00 | 0.00 |
February | 0.908439E+09 | 82461742.87 | 0.426933E+09 | 0.139196E+09 | 0.287737E+09 | 0.00 | 0.00 |
March | 0.750104E+09 | 68243415.56 | 0.322574E+09 | 43321942.35 | 0.279252E+09 | 0.00 | 0.00 |
April | 0.554816E+09 | 33114915.53 | 0.232737E+09 | 104477.26 | 0.232632E+09 | 0.00 | 0.00 |
May | 0.587654E+09 | 39967920.96 | 0.240659E+09 | 0.00 | 0.240659E+09 | 0.00 | 0.00 |
June | 0.562925E+09 | 42434921.01 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
July | 0.531647E+09 | 71013500.40 | 0.247022E+09 | 0.00 | 0.247022E+09 | 0.00 | 0.00 |
August | 0.516422E+09 | 59447558.92 | 0.240478E+09 | 371664.02 | 0.240106E+09 | 0.00 | 0.00 |
September | 0.569324E+09 | 57461650.72 | 0.257639E+09 | 8414663.85 | 0.249224E+09 | 0.00 | 0.00 |
October | 0.716865E+09 | 73273593.11 | 0.348302E+09 | 55533999.25 | 0.292768E+09 | 0.00 | 0.00 |
November | 0.881877E+09 | 81365057.51 | 0.438297E+09 | 0.133719E+09 | 0.304579E+09 | 0.00 | 0.00 |
December | 0.108771E+10 | 0.126084E+09 | 0.556360E+09 | 0.236709E+09 | 0.319652E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.877182E+10 | 0.848491E+09 | 0.409970E+10 | 0.849609E+09 | 0.325009E+10 | 0.00 | 0.00 |
Minimum of Months | 0.516422E+09 | 33114915.53 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110404E+10 | 0.126084E+09 | 0.556645E+09 | 0.236709E+09 | 0.324406E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.220597E+10 | 0.208170E+09 | 0.111329E+10 | 0.464477E+09 | 0.648813E+09 | 0.00 | 0.00 |
February | 0.181360E+10 | 0.147357E+09 | 0.853866E+09 | 0.278392E+09 | 0.575473E+09 | 0.00 | 0.00 |
March | 0.149723E+10 | 0.117094E+09 | 0.645148E+09 | 86643884.70 | 0.558504E+09 | 0.00 | 0.00 |
April | 0.111020E+10 | 53341323.72 | 0.465473E+09 | 208954.51 | 0.465264E+09 | 0.00 | 0.00 |
May | 0.117519E+10 | 66723459.53 | 0.481318E+09 | 0.00 | 0.481318E+09 | 0.00 | 0.00 |
June | 0.112576E+10 | 71424851.00 | 0.464114E+09 | 0.00 | 0.464114E+09 | 0.00 | 0.00 |
July | 0.106054E+10 | 0.125020E+09 | 0.494045E+09 | 0.00 | 0.494045E+09 | 0.00 | 0.00 |
August | 0.103086E+10 | 99819675.68 | 0.480956E+09 | 743328.04 | 0.480213E+09 | 0.00 | 0.00 |
September | 0.113795E+10 | 98705793.16 | 0.515277E+09 | 16829327.70 | 0.498448E+09 | 0.00 | 0.00 |
October | 0.143290E+10 | 0.128361E+09 | 0.696604E+09 | 0.111068E+09 | 0.585536E+09 | 0.00 | 0.00 |
November | 0.176162E+10 | 0.145485E+09 | 0.876594E+09 | 0.267437E+09 | 0.609157E+09 | 0.00 | 0.00 |
December | 0.217354E+10 | 0.233887E+09 | 0.111272E+10 | 0.473417E+09 | 0.639304E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.175254E+11 | 0.149539E+10 | 0.819941E+10 | 0.169922E+10 | 0.650019E+10 | 0.00 | 0.00 |
Minimum of Months | 0.103086E+10 | 53341323.72 | 0.464114E+09 | 0.00 | 0.464114E+09 | 0.00 | 0.00 |
Maximum of Months | 0.220597E+10 | 0.233887E+09 | 0.111329E+10 | 0.473417E+09 | 0.648813E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.110489E+10 | 0.100484E+09 | 0.556645E+09 | 0.232239E+09 | 0.324406E+09 | 0.00 | 0.00 |
February | 0.909085E+09 | 70141579.22 | 0.426933E+09 | 0.139196E+09 | 0.287737E+09 | 0.00 | 0.00 |
March | 0.751979E+09 | 54373743.28 | 0.322574E+09 | 43321942.35 | 0.279252E+09 | 0.00 | 0.00 |
April | 0.560373E+09 | 23810143.96 | 0.232737E+09 | 104477.26 | 0.232632E+09 | 0.00 | 0.00 |
May | 0.593080E+09 | 30680160.55 | 0.240659E+09 | 0.00 | 0.240659E+09 | 0.00 | 0.00 |
June | 0.568190E+09 | 32768397.74 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
July | 0.533454E+09 | 59064418.31 | 0.247022E+09 | 0.00 | 0.247022E+09 | 0.00 | 0.00 |
August | 0.518897E+09 | 46224852.64 | 0.240478E+09 | 371664.02 | 0.240106E+09 | 0.00 | 0.00 |
September | 0.572138E+09 | 46142560.28 | 0.257639E+09 | 8414663.85 | 0.249224E+09 | 0.00 | 0.00 |
October | 0.718849E+09 | 60656041.85 | 0.348302E+09 | 55533999.25 | 0.292768E+09 | 0.00 | 0.00 |
November | 0.882934E+09 | 69427775.36 | 0.438297E+09 | 0.133719E+09 | 0.304579E+09 | 0.00 | 0.00 |
December | 0.108844E+10 | 0.113478E+09 | 0.556360E+09 | 0.236709E+09 | 0.319652E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.880231E+10 | 0.707252E+09 | 0.409970E+10 | 0.849609E+09 | 0.325009E+10 | 0.00 | 0.00 |
Minimum of Months | 0.518897E+09 | 23810143.96 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110489E+10 | 0.113478E+09 | 0.556645E+09 | 0.236709E+09 | 0.324406E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.110547E+10 | 99778502.37 | 0.556645E+09 | 0.232239E+09 | 0.324406E+09 | 0.00 | 0.00 |
February | 0.909578E+09 | 69555320.53 | 0.426933E+09 | 0.139196E+09 | 0.287737E+09 | 0.00 | 0.00 |
March | 0.752495E+09 | 53743059.43 | 0.322574E+09 | 43321942.35 | 0.279252E+09 | 0.00 | 0.00 |
April | 0.560985E+09 | 23381786.12 | 0.232737E+09 | 104477.26 | 0.232632E+09 | 0.00 | 0.00 |
May | 0.593741E+09 | 30265424.39 | 0.240659E+09 | 0.00 | 0.240659E+09 | 0.00 | 0.00 |
June | 0.568810E+09 | 32319154.95 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
July | 0.533946E+09 | 58495151.21 | 0.247022E+09 | 0.00 | 0.247022E+09 | 0.00 | 0.00 |
August | 0.519408E+09 | 45618793.07 | 0.240478E+09 | 371664.02 | 0.240106E+09 | 0.00 | 0.00 |
September | 0.572633E+09 | 45598484.60 | 0.257639E+09 | 8414663.85 | 0.249224E+09 | 0.00 | 0.00 |
October | 0.719385E+09 | 59967318.32 | 0.348302E+09 | 55533999.25 | 0.292768E+09 | 0.00 | 0.00 |
November | 0.883489E+09 | 68770543.24 | 0.438297E+09 | 0.133719E+09 | 0.304579E+09 | 0.00 | 0.00 |
December | 0.108902E+10 | 0.112752E+09 | 0.556360E+09 | 0.236709E+09 | 0.319652E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.880896E+10 | 0.700246E+09 | 0.409970E+10 | 0.849609E+09 | 0.325009E+10 | 0.00 | 0.00 |
Minimum of Months | 0.519408E+09 | 23381786.12 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110547E+10 | 0.112752E+09 | 0.556645E+09 | 0.236709E+09 | 0.324406E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.110515E+10 | 99772897.80 | 0.556645E+09 | 0.232239E+09 | 0.324406E+09 | 0.00 | 0.00 |
February | 0.908987E+09 | 69849342.12 | 0.426933E+09 | 0.139196E+09 | 0.287737E+09 | 0.00 | 0.00 |
March | 0.751643E+09 | 54256695.65 | 0.322574E+09 | 43321942.35 | 0.279252E+09 | 0.00 | 0.00 |
April | 0.559551E+09 | 23962817.43 | 0.232737E+09 | 104477.26 | 0.232632E+09 | 0.00 | 0.00 |
May | 0.592185E+09 | 30779596.45 | 0.240659E+09 | 0.00 | 0.240659E+09 | 0.00 | 0.00 |
June | 0.567357E+09 | 32999743.56 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
July | 0.532931E+09 | 59242857.13 | 0.247022E+09 | 0.00 | 0.247022E+09 | 0.00 | 0.00 |
August | 0.518505E+09 | 46142774.86 | 0.240478E+09 | 371664.02 | 0.240106E+09 | 0.00 | 0.00 |
September | 0.571624E+09 | 46210696.03 | 0.257639E+09 | 8414663.85 | 0.249224E+09 | 0.00 | 0.00 |
October | 0.718831E+09 | 60139152.35 | 0.348302E+09 | 55533999.25 | 0.292768E+09 | 0.00 | 0.00 |
November | 0.883102E+09 | 68803298.24 | 0.438297E+09 | 0.133719E+09 | 0.304579E+09 | 0.00 | 0.00 |
December | 0.108883E+10 | 0.112634E+09 | 0.556360E+09 | 0.236709E+09 | 0.319652E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.879870E+10 | 0.704794E+09 | 0.409970E+10 | 0.849609E+09 | 0.325009E+10 | 0.00 | 0.00 |
Minimum of Months | 0.518505E+09 | 23962817.43 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110515E+10 | 0.112634E+09 | 0.556645E+09 | 0.236709E+09 | 0.324406E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.109594E+10 | 0.103066E+09 | 0.556645E+09 | 0.232239E+09 | 0.324406E+09 | 0.00 | 0.00 |
February | 0.898384E+09 | 74329192.67 | 0.426933E+09 | 0.139196E+09 | 0.287737E+09 | 0.00 | 0.00 |
March | 0.738500E+09 | 60092473.57 | 0.322574E+09 | 43321942.35 | 0.279252E+09 | 0.00 | 0.00 |
April | 0.542805E+09 | 29457535.90 | 0.232737E+09 | 104477.26 | 0.232632E+09 | 0.00 | 0.00 |
May | 0.575042E+09 | 35672972.46 | 0.240659E+09 | 0.00 | 0.240659E+09 | 0.00 | 0.00 |
June | 0.550668E+09 | 39068492.56 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
July | 0.519928E+09 | 66318312.83 | 0.247022E+09 | 0.00 | 0.247022E+09 | 0.00 | 0.00 |
August | 0.505949E+09 | 52324009.66 | 0.240478E+09 | 371664.02 | 0.240106E+09 | 0.00 | 0.00 |
September | 0.558686E+09 | 52649004.41 | 0.257639E+09 | 8414663.85 | 0.249224E+09 | 0.00 | 0.00 |
October | 0.709138E+09 | 64626002.48 | 0.348302E+09 | 55533999.25 | 0.292768E+09 | 0.00 | 0.00 |
November | 0.873790E+09 | 72378220.85 | 0.438297E+09 | 0.133719E+09 | 0.304579E+09 | 0.00 | 0.00 |
December | 0.108052E+10 | 0.115491E+09 | 0.556360E+09 | 0.236709E+09 | 0.319652E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.864935E+10 | 0.765473E+09 | 0.409970E+10 | 0.849609E+09 | 0.325009E+10 | 0.00 | 0.00 |
Minimum of Months | 0.505949E+09 | 29457535.90 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109594E+10 | 0.115491E+09 | 0.556645E+09 | 0.236709E+09 | 0.324406E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.66 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.91 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.37 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 23.00 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.55 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.01 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.14 | 23.20 | 1.94 | 20.29 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.60 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 23.00 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.67 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.02 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 23.01 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.96 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.43 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.60 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.63 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.86 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.51 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.23 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.34 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.23 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.02 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.86 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.94 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.53 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.17 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.28 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.93 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.70 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.11 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.43 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.06 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.56 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.53 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.11 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.87 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.11 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.06 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.04 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.56 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.11 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.255223E+09 | -143755817.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111467188.9 | 58.99 | 0.00 | 0.00 |
February | 0.230251E+09 | -129709404.5 | 0.00 | 0.00 | 672.00 | 0.00 | -100541138.0 | 58.99 | 0.00 | 0.00 |
March | 0.254842E+09 | -143667885.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111173956.7 | 58.99 | 0.00 | 0.00 |
April | 0.241632E+09 | -134264433.0 | 0.00 | 0.00 | 720.00 | 0.00 | -107367809.4 | 58.99 | 0.00 | 0.00 |
May | 0.246832E+09 | -135937275.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110894790.7 | 58.99 | 0.00 | 0.00 |
June | 0.238091E+09 | -130789624.9 | 0.00 | 0.00 | 720.00 | 0.00 | -107301403.3 | 58.99 | 0.00 | 0.00 |
July | 0.242823E+09 | -131713762.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111108871.3 | 58.99 | 0.00 | 0.00 |
August | 0.246587E+09 | -135469604.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111117242.4 | 58.99 | 0.00 | 0.00 |
September | 0.239391E+09 | -131877352.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107514093.1 | 58.99 | 0.00 | 0.00 |
October | 0.249272E+09 | -138053031.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111219239.3 | 58.99 | 0.00 | 0.00 |
November | 0.243815E+09 | -136106682.9 | 0.00 | 0.00 | 720.00 | 0.00 | -107707933.7 | 58.99 | 0.00 | 0.00 |
December | 0.254859E+09 | -143308895.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111550299.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.294362E+10 | -0.163465E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130896E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.230251E+09 | -143755817.9 | 0.00 | 0.00 | 672.00 | 0.00 | -111550299.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.255223E+09 | -129709404.5 | 0.00 | 0.00 | 744.00 | 0.00 | -100541138.0 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.255126E+09 | -143758050.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111367697.9 | 58.99 | 0.00 | 0.00 |
February | 0.230198E+09 | -129714795.3 | 0.00 | 0.00 | 672.00 | 0.00 | -100482889.6 | 58.99 | 0.00 | 0.00 |
March | 0.254817E+09 | -143658218.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111159118.7 | 58.99 | 0.00 | 0.00 |
April | 0.241648E+09 | -134268569.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107379015.2 | 58.99 | 0.00 | 0.00 |
May | 0.246837E+09 | -135931988.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110905276.2 | 58.99 | 0.00 | 0.00 |
June | 0.238111E+09 | -130792495.3 | 0.00 | 0.00 | 720.00 | 0.00 | -107318840.7 | 58.99 | 0.00 | 0.00 |
July | 0.242805E+09 | -131714027.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111091017.3 | 58.99 | 0.00 | 0.00 |
August | 0.246570E+09 | -135468799.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111101199.4 | 58.99 | 0.00 | 0.00 |
September | 0.239382E+09 | -131873310.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107509110.5 | 58.99 | 0.00 | 0.00 |
October | 0.249220E+09 | -138051754.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111168409.7 | 58.99 | 0.00 | 0.00 |
November | 0.243745E+09 | -136105499.4 | 0.00 | 0.00 | 720.00 | 0.00 | -107639066.2 | 58.99 | 0.00 | 0.00 |
December | 0.254757E+09 | -143312434.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111445010.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.294322E+10 | -0.163465E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130857E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.230198E+09 | -143758050.0 | 0.00 | 0.00 | 672.00 | 0.00 | -111445010.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.255126E+09 | -129714795.3 | 0.00 | 0.00 | 744.00 | 0.00 | -100482889.6 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.235729E+09 | -126417991.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109310761.5 | 58.99 | 0.00 | 0.00 |
February | 0.212722E+09 | -114158223.2 | 0.00 | 0.00 | 672.00 | 0.00 | -98563505.9 | 58.99 | 0.00 | 0.00 |
March | 0.237310E+09 | -128223871.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109086618.6 | 58.99 | 0.00 | 0.00 |
April | 0.223243E+09 | -118074358.1 | 0.00 | 0.00 | 720.00 | 0.00 | -105168303.0 | 58.99 | 0.00 | 0.00 |
May | 0.229174E+09 | -120545581.7 | 0.00 | 0.00 | 744.00 | 0.00 | -108628105.6 | 58.99 | 0.00 | 0.00 |
June | 0.221611E+09 | -116511138.2 | 0.00 | 0.00 | 720.00 | 0.00 | -105100237.4 | 58.99 | 0.00 | 0.00 |
July | 0.223984E+09 | -115140474.7 | 0.00 | 0.00 | 744.00 | 0.00 | -108843344.1 | 58.99 | 0.00 | 0.00 |
August | 0.230150E+09 | -120988765.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109161380.6 | 58.99 | 0.00 | 0.00 |
September | 0.221347E+09 | -115910485.5 | 0.00 | 0.00 | 720.00 | 0.00 | -105436753.6 | 58.99 | 0.00 | 0.00 |
October | 0.230549E+09 | -121387586.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109161187.8 | 58.99 | 0.00 | 0.00 |
November | 0.225972E+09 | -120169260.8 | 0.00 | 0.00 | 720.00 | 0.00 | -105802938.4 | 58.99 | 0.00 | 0.00 |
December | 0.234618E+09 | -125137110.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109481039.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.272641E+10 | -0.144266E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.128374E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.212722E+09 | -128223871.2 | 0.00 | 0.00 | 672.00 | 0.00 | -109481039.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.237310E+09 | -114158223.2 | 0.00 | 0.00 | 744.00 | 0.00 | -98563505.9 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.235645E+09 | -126414463.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109230239.5 | 58.99 | 0.00 | 0.00 |
February | 0.212639E+09 | -114150665.0 | 0.00 | 0.00 | 672.00 | 0.00 | -98488625.3 | 58.99 | 0.00 | 0.00 |
March | 0.237215E+09 | -128223381.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108991990.3 | 58.99 | 0.00 | 0.00 |
April | 0.223144E+09 | -118097948.9 | 0.00 | 0.00 | 720.00 | 0.00 | -105045996.0 | 58.99 | 0.00 | 0.00 |
May | 0.229050E+09 | -120547387.4 | 0.00 | 0.00 | 744.00 | 0.00 | -108502631.8 | 58.99 | 0.00 | 0.00 |
June | 0.221488E+09 | -116494535.6 | 0.00 | 0.00 | 720.00 | 0.00 | -104992970.7 | 58.99 | 0.00 | 0.00 |
July | 0.223875E+09 | -115178390.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108696586.6 | 58.98 | 0.00 | 0.00 |
August | 0.230060E+09 | -120986286.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109073307.7 | 58.99 | 0.00 | 0.00 |
September | 0.221254E+09 | -115896382.5 | 0.00 | 0.00 | 720.00 | 0.00 | -105357432.0 | 58.99 | 0.00 | 0.00 |
October | 0.230464E+09 | -121387251.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109077184.1 | 58.99 | 0.00 | 0.00 |
November | 0.225912E+09 | -120174770.6 | 0.00 | 0.00 | 720.00 | 0.00 | -105737519.0 | 58.99 | 0.00 | 0.00 |
December | 0.234551E+09 | -125135911.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109415093.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.272530E+10 | -0.144269E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.128261E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.212639E+09 | -128223381.2 | 0.00 | 0.00 | 672.00 | 0.00 | -109415093.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.237215E+09 | -114150665.0 | 0.00 | 0.00 | 744.00 | 0.00 | -98488625.3 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.229367E+09 | -119480525.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109886186.8 | 58.99 | 0.00 | 0.00 |
February | 0.207040E+09 | -107948140.2 | 0.00 | 0.00 | 672.00 | 0.00 | -99092108.9 | 58.99 | 0.00 | 0.00 |
March | 0.231004E+09 | -121318161.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109686135.0 | 58.99 | 0.00 | 0.00 |
April | 0.217427E+09 | -111726173.1 | 0.00 | 0.00 | 720.00 | 0.00 | -105700709.8 | 59.00 | 0.00 | 0.00 |
May | 0.223090E+09 | -113997375.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109093010.0 | 58.99 | 0.00 | 0.00 |
June | 0.215858E+09 | -110204888.9 | 0.00 | 0.00 | 720.00 | 0.00 | -105653350.6 | 59.00 | 0.00 | 0.00 |
July | 0.218202E+09 | -108932593.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109269211.4 | 58.98 | 0.00 | 0.00 |
August | 0.224212E+09 | -114475698.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109736729.7 | 58.99 | 0.00 | 0.00 |
September | 0.215634E+09 | -109682324.4 | 0.00 | 0.00 | 720.00 | 0.00 | -105951426.2 | 58.99 | 0.00 | 0.00 |
October | 0.224413E+09 | -114751793.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109661679.3 | 58.99 | 0.00 | 0.00 |
November | 0.219828E+09 | -113505059.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106322791.9 | 58.99 | 0.00 | 0.00 |
December | 0.228371E+09 | -118323904.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110046608.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.265445E+10 | -0.136435E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.129010E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.207040E+09 | -121318161.7 | 0.00 | 0.00 | 672.00 | 0.00 | -110046608.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.231004E+09 | -107948140.2 | 0.00 | 0.00 | 744.00 | 0.00 | -99092108.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.229511E+09 | -119477265.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110033937.9 | 58.99 | 0.00 | 0.00 |
February | 0.207171E+09 | -107957073.5 | 0.00 | 0.00 | 672.00 | 0.00 | -99213919.5 | 58.99 | 0.00 | 0.00 |
March | 0.231163E+09 | -121343073.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109820192.6 | 58.99 | 0.00 | 0.00 |
April | 0.217577E+09 | -111754779.5 | 0.00 | 0.00 | 720.00 | 0.00 | -105822047.0 | 58.98 | 0.00 | 0.00 |
May | 0.223262E+09 | -113998400.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109263481.6 | 58.99 | 0.00 | 0.00 |
June | 0.216018E+09 | -110236915.7 | 0.00 | 0.00 | 720.00 | 0.00 | -105780979.6 | 58.99 | 0.00 | 0.00 |
July | 0.218371E+09 | -108952710.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109418306.3 | 58.98 | 0.00 | 0.00 |
August | 0.224353E+09 | -114450112.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109902533.6 | 59.00 | 0.00 | 0.00 |
September | 0.215783E+09 | -109682489.0 | 0.00 | 0.00 | 720.00 | 0.00 | -106100795.0 | 58.99 | 0.00 | 0.00 |
October | 0.224557E+09 | -114765758.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109790912.5 | 58.98 | 0.00 | 0.00 |
November | 0.219977E+09 | -113511018.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106465864.8 | 58.99 | 0.00 | 0.00 |
December | 0.228504E+09 | -118325877.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110177950.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.265625E+10 | -0.136446E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.129179E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.207171E+09 | -121343073.6 | 0.00 | 0.00 | 672.00 | 0.00 | -110177950.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.231163E+09 | -107957073.5 | 0.00 | 0.00 | 744.00 | 0.00 | -99213919.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.229551E+09 | -119476974.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110073715.9 | 58.99 | 0.00 | 0.00 |
February | 0.207201E+09 | -107956594.6 | 0.00 | 0.00 | 672.00 | 0.00 | -99244725.0 | 58.99 | 0.00 | 0.00 |
March | 0.231196E+09 | -121334888.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109861568.7 | 58.99 | 0.00 | 0.00 |
April | 0.217611E+09 | -111759002.2 | 0.00 | 0.00 | 720.00 | 0.00 | -105851640.3 | 58.98 | 0.00 | 0.00 |
May | 0.223288E+09 | -113993737.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109294672.2 | 58.99 | 0.00 | 0.00 |
June | 0.216048E+09 | -110196584.6 | 0.00 | 0.00 | 720.00 | 0.00 | -105851295.7 | 59.00 | 0.00 | 0.00 |
July | 0.218389E+09 | -108935753.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109453080.3 | 58.98 | 0.00 | 0.00 |
August | 0.224410E+09 | -114536657.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109873005.2 | 58.98 | 0.00 | 0.00 |
September | 0.215812E+09 | -109667162.3 | 0.00 | 0.00 | 720.00 | 0.00 | -106144689.8 | 58.99 | 0.00 | 0.00 |
October | 0.224580E+09 | -114737565.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109842020.6 | 58.99 | 0.00 | 0.00 |
November | 0.220017E+09 | -113490964.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106526375.9 | 58.99 | 0.00 | 0.00 |
December | 0.228550E+09 | -118341799.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110207775.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.265665E+10 | -0.136443E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.129222E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.207201E+09 | -121334888.4 | 0.00 | 0.00 | 672.00 | 0.00 | -110207775.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.231196E+09 | -107956594.6 | 0.00 | 0.00 | 744.00 | 0.00 | -99244725.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 350.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 361.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 376.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 370.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 383.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 357.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 356.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 349.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4292.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 383.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.447425E+11 | 0.283259E+11 | 68646.50 | 10-JAN-08:61 | 37748.29 | 0.00 |
February | 0.00 | 0.00 | 0.433619E+11 | 0.274864E+11 | 68395.96 | 16-FEB-08:61 | 38757.02 | 0.00 |
March | 0.00 | 0.00 | 0.504549E+11 | 0.315596E+11 | 69433.25 | 28-MAR-07:01 | 36718.81 | 0.00 |
April | 0.00 | 0.00 | 0.552384E+11 | 0.314718E+11 | 69664.15 | 12-APR-07:01 | 36358.11 | 0.00 |
May | 0.00 | 0.00 | 0.616471E+11 | 0.324104E+11 | 70962.53 | 19-MAY-07:01 | 30738.15 | 0.00 |
June | 0.00 | 0.00 | 0.614259E+11 | 0.321730E+11 | 70935.92 | 11-JUN-07:01 | 33391.15 | 0.00 |
July | 0.00 | 0.00 | 0.505521E+11 | 0.287333E+11 | 69247.63 | 01-JUL-07:02 | 35810.62 | 0.00 |
August | 0.00 | 0.00 | 0.565095E+11 | 0.285185E+11 | 70915.80 | 11-AUG-07:01 | 32268.00 | 0.00 |
September | 0.00 | 0.00 | 0.539763E+11 | 0.281104E+11 | 70026.47 | 01-SEP-07:01 | 34392.46 | 0.00 |
October | 0.00 | 0.00 | 0.518810E+11 | 0.270058E+11 | 69515.45 | 14-OCT-07:02 | 34509.88 | 0.00 |
November | 0.00 | 0.00 | 0.478105E+11 | 0.264943E+11 | 69092.60 | 12-NOV-08:61 | 36810.42 | 0.00 |
December | 0.00 | 0.00 | 0.454951E+11 | 0.273267E+11 | 68433.95 | 30-DEC-08:61 | 39004.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.623095E+12 | 0.349616E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.433619E+11 | 0.264943E+11 | 68395.96 | 30738.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.616471E+11 | 0.324104E+11 | 70962.53 | 39004.39 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.221220E+11 | 0.144222E+11 | 33803.28 | 10-JAN-08:61 | 22871.78 | 0.00 |
February | 0.00 | 0.00 | 0.212692E+11 | 0.138247E+11 | 33712.65 | 16-FEB-08:61 | 23182.74 | 0.00 |
March | 0.00 | 0.00 | 0.245288E+11 | 0.157336E+11 | 34174.18 | 28-MAR-07:01 | 22135.86 | 0.00 |
April | 0.00 | 0.00 | 0.266533E+11 | 0.156220E+11 | 34300.59 | 12-APR-07:01 | 21876.58 | 0.00 |
May | 0.00 | 0.00 | 0.299138E+11 | 0.162440E+11 | 35111.84 | 22-MAY-07:01 | 19537.23 | 0.00 |
June | 0.00 | 0.00 | 0.298065E+11 | 0.160900E+11 | 35135.48 | 14-JUN-07:01 | 19941.19 | 0.00 |
July | 0.00 | 0.00 | 0.246774E+11 | 0.144493E+11 | 33846.31 | 01-JUL-07:02 | 22593.26 | 0.00 |
August | 0.00 | 0.00 | 0.276084E+11 | 0.144064E+11 | 34804.88 | 13-AUG-07:01 | 20563.52 | 0.00 |
September | 0.00 | 0.00 | 0.262955E+11 | 0.141561E+11 | 34152.16 | 03-SEP-07:01 | 22349.95 | 0.00 |
October | 0.00 | 0.00 | 0.255324E+11 | 0.137870E+11 | 34082.65 | 05-OCT-07:01 | 22227.95 | 0.00 |
November | 0.00 | 0.00 | 0.235463E+11 | 0.135134E+11 | 33741.38 | 12-NOV-08:61 | 23144.16 | 0.00 |
December | 0.00 | 0.00 | 0.224989E+11 | 0.140031E+11 | 33525.80 | 10-DEC-08:61 | 23971.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.304453E+12 | 0.176252E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.212692E+11 | 0.135134E+11 | 33525.80 | 19537.23 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.299138E+11 | 0.162440E+11 | 35135.48 | 23971.65 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.180302E+11 | 0.114728E+11 | 35926.03 | 02-JAN-07:01 | 16116.32 | 0.00 |
February | 0.00 | 0.00 | 0.174841E+11 | 0.110971E+11 | 35651.32 | 06-FEB-07:01 | 17090.14 | 0.00 |
March | 0.00 | 0.00 | 0.204908E+11 | 0.128288E+11 | 36117.42 | 27-MAR-06:01 | 16575.41 | 0.00 |
April | 0.00 | 0.00 | 0.220651E+11 | 0.125176E+11 | 36198.19 | 10-APR-06:01 | 15481.04 | 0.00 |
May | 0.00 | 0.00 | 0.251592E+11 | 0.131336E+11 | 36240.02 | 17-MAY-06:01 | 15062.73 | 0.00 |
June | 0.00 | 0.00 | 0.252657E+11 | 0.131010E+11 | 36236.03 | 26-JUN-06:01 | 13849.67 | 0.00 |
July | 0.00 | 0.00 | 0.201913E+11 | 0.113022E+11 | 36184.21 | 02-JUL-07:01 | 15903.97 | 0.00 |
August | 0.00 | 0.00 | 0.233292E+11 | 0.115951E+11 | 36238.06 | 21-AUG-06:02 | 13859.95 | 0.00 |
September | 0.00 | 0.00 | 0.218589E+11 | 0.112134E+11 | 36238.65 | 18-SEP-06:03 | 13946.50 | 0.00 |
October | 0.00 | 0.00 | 0.211564E+11 | 0.108756E+11 | 36239.54 | 02-OCT-06:01 | 15041.76 | 0.00 |
November | 0.00 | 0.00 | 0.194246E+11 | 0.107597E+11 | 36235.78 | 20-NOV-07:01 | 15673.17 | 0.00 |
December | 0.00 | 0.00 | 0.182298E+11 | 0.110608E+11 | 36233.05 | 11-DEC-07:01 | 14263.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.252685E+12 | 0.140958E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.174841E+11 | 0.107597E+11 | 35651.32 | 13849.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.252657E+11 | 0.131336E+11 | 36240.02 | 17090.14 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.180756E+11 | 0.115074E+11 | 36004.99 | 02-JAN-07:01 | 16196.90 | 0.00 |
February | 0.00 | 0.00 | 0.175304E+11 | 0.111329E+11 | 35733.39 | 06-FEB-07:01 | 17192.54 | 0.00 |
March | 0.00 | 0.00 | 0.205413E+11 | 0.128676E+11 | 36206.39 | 27-MAR-06:01 | 16715.25 | 0.00 |
April | 0.00 | 0.00 | 0.221278E+11 | 0.125637E+11 | 36275.44 | 10-APR-06:01 | 15563.60 | 0.00 |
May | 0.00 | 0.00 | 0.252431E+11 | 0.131941E+11 | 36312.62 | 17-MAY-06:01 | 15137.56 | 0.00 |
June | 0.00 | 0.00 | 0.253447E+11 | 0.131585E+11 | 36308.63 | 26-JUN-06:01 | 13954.76 | 0.00 |
July | 0.00 | 0.00 | 0.202610E+11 | 0.113524E+11 | 36256.70 | 02-JUL-07:01 | 15984.80 | 0.00 |
August | 0.00 | 0.00 | 0.233732E+11 | 0.116268E+11 | 36310.65 | 21-AUG-06:02 | 13891.58 | 0.00 |
September | 0.00 | 0.00 | 0.219123E+11 | 0.112517E+11 | 36311.25 | 18-SEP-06:01 | 14087.33 | 0.00 |
October | 0.00 | 0.00 | 0.212036E+11 | 0.109093E+11 | 36312.14 | 02-OCT-06:01 | 15138.07 | 0.00 |
November | 0.00 | 0.00 | 0.194540E+11 | 0.107821E+11 | 36308.38 | 20-NOV-07:01 | 15776.17 | 0.00 |
December | 0.00 | 0.00 | 0.182584E+11 | 0.110828E+11 | 36305.64 | 11-DEC-07:01 | 14358.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.253325E+12 | 0.141429E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.175304E+11 | 0.107821E+11 | 35733.39 | 13891.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.253447E+11 | 0.131941E+11 | 36312.62 | 17192.54 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.178435E+11 | 0.113300E+11 | 35741.83 | 02-JAN-07:01 | 15969.29 | 0.00 |
February | 0.00 | 0.00 | 0.173224E+11 | 0.109728E+11 | 35472.03 | 06-FEB-07:01 | 16970.23 | 0.00 |
March | 0.00 | 0.00 | 0.202992E+11 | 0.126829E+11 | 35942.70 | 27-MAR-06:01 | 16500.29 | 0.00 |
April | 0.00 | 0.00 | 0.218829E+11 | 0.123853E+11 | 36013.39 | 10-APR-06:01 | 15341.22 | 0.00 |
May | 0.00 | 0.00 | 0.249979E+11 | 0.130205E+11 | 36060.01 | 17-MAY-06:01 | 14881.04 | 0.00 |
June | 0.00 | 0.00 | 0.251042E+11 | 0.129863E+11 | 36056.04 | 26-JUN-06:03 | 13686.54 | 0.00 |
July | 0.00 | 0.00 | 0.200209E+11 | 0.111787E+11 | 36004.48 | 02-JUL-07:01 | 15737.72 | 0.00 |
August | 0.00 | 0.00 | 0.230997E+11 | 0.114385E+11 | 36058.06 | 21-AUG-06:02 | 13652.41 | 0.00 |
September | 0.00 | 0.00 | 0.216588E+11 | 0.110745E+11 | 36058.65 | 18-SEP-06:01 | 13854.92 | 0.00 |
October | 0.00 | 0.00 | 0.209435E+11 | 0.107284E+11 | 36059.54 | 02-OCT-06:01 | 14934.08 | 0.00 |
November | 0.00 | 0.00 | 0.192098E+11 | 0.106064E+11 | 36055.80 | 20-NOV-07:01 | 15564.77 | 0.00 |
December | 0.00 | 0.00 | 0.180173E+11 | 0.109026E+11 | 36053.08 | 11-DEC-07:01 | 14159.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.250400E+12 | 0.139307E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.173224E+11 | 0.106064E+11 | 35472.03 | 13652.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.251042E+11 | 0.130205E+11 | 36060.01 | 16970.23 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.319758E+11 | 0.199808E+11 | 63067.62 | 02-JAN-08:62 | 28188.84 | 0.00 |
February | 0.00 | 0.00 | 0.311245E+11 | 0.194049E+11 | 62576.78 | 06-FEB-08:61 | 30268.18 | 0.00 |
March | 0.00 | 0.00 | 0.364637E+11 | 0.224537E+11 | 63404.95 | 27-MAR-07:01 | 29087.52 | 0.00 |
April | 0.00 | 0.00 | 0.393843E+11 | 0.219075E+11 | 63440.33 | 10-APR-07:02 | 26759.28 | 0.00 |
May | 0.00 | 0.00 | 0.451327E+11 | 0.230513E+11 | 63404.95 | 15-MAY-07:01 | 24393.72 | 0.00 |
June | 0.00 | 0.00 | 0.455658E+11 | 0.231200E+11 | 63472.48 | 26-JUN-07:04 | 23838.42 | 0.00 |
July | 0.00 | 0.00 | 0.357452E+11 | 0.195593E+11 | 63462.15 | 05-JUL-07:01 | 28138.39 | 0.00 |
August | 0.00 | 0.00 | 0.415915E+11 | 0.200723E+11 | 63544.28 | 21-AUG-07:02 | 23600.45 | 0.00 |
September | 0.00 | 0.00 | 0.388391E+11 | 0.194022E+11 | 63616.30 | 18-SEP-07:03 | 24016.94 | 0.00 |
October | 0.00 | 0.00 | 0.374369E+11 | 0.186934E+11 | 63615.46 | 23-OCT-07:02 | 25270.34 | 0.00 |
November | 0.00 | 0.00 | 0.343702E+11 | 0.185287E+11 | 63501.41 | 20-NOV-08:61 | 28038.85 | 0.00 |
December | 0.00 | 0.00 | 0.321369E+11 | 0.190834E+11 | 63514.67 | 11-DEC-08:61 | 25266.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.449767E+12 | 0.245258E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.311245E+11 | 0.185287E+11 | 62576.78 | 23600.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.455658E+11 | 0.231200E+11 | 63616.30 | 30268.18 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.166043E+11 | 0.103872E+11 | 33120.75 | 02-JAN-08:62 | 14727.53 | 0.00 |
February | 0.00 | 0.00 | 0.161706E+11 | 0.100893E+11 | 32852.50 | 06-FEB-08:61 | 15815.00 | 0.00 |
March | 0.00 | 0.00 | 0.189350E+11 | 0.116696E+11 | 33266.41 | 27-MAR-07:01 | 15206.25 | 0.00 |
April | 0.00 | 0.00 | 0.204570E+11 | 0.113928E+11 | 33284.97 | 10-APR-07:02 | 13948.79 | 0.00 |
May | 0.00 | 0.00 | 0.234314E+11 | 0.119866E+11 | 33266.41 | 15-MAY-07:01 | 12681.30 | 0.00 |
June | 0.00 | 0.00 | 0.236340E+11 | 0.120059E+11 | 33301.84 | 26-JUN-07:03 | 12477.62 | 0.00 |
July | 0.00 | 0.00 | 0.185467E+11 | 0.101619E+11 | 33337.81 | 05-JUL-07:01 | 14643.67 | 0.00 |
August | 0.00 | 0.00 | 0.215623E+11 | 0.104240E+11 | 33339.52 | 21-AUG-07:02 | 12304.02 | 0.00 |
September | 0.00 | 0.00 | 0.201505E+11 | 0.100813E+11 | 33377.30 | 18-SEP-07:01 | 12522.10 | 0.00 |
October | 0.00 | 0.00 | 0.194209E+11 | 0.971299E+10 | 33376.86 | 23-OCT-07:02 | 13217.16 | 0.00 |
November | 0.00 | 0.00 | 0.178280E+11 | 0.962459E+10 | 33317.02 | 20-NOV-08:61 | 14533.34 | 0.00 |
December | 0.00 | 0.00 | 0.166793E+11 | 0.991589E+10 | 33323.98 | 11-DEC-08:61 | 13088.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.233420E+12 | 0.127452E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.161706E+11 | 0.962459E+10 | 32852.50 | 12304.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.236340E+11 | 0.120059E+11 | 33377.30 | 15815.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.165279E+11 | 0.103302E+11 | 32977.96 | 02-JAN-08:62 | 14642.43 | 0.00 |
February | 0.00 | 0.00 | 0.161058E+11 | 0.100407E+11 | 32710.67 | 06-FEB-08:61 | 15727.83 | 0.00 |
March | 0.00 | 0.00 | 0.188645E+11 | 0.116172E+11 | 33124.51 | 27-MAR-07:01 | 15127.83 | 0.00 |
April | 0.00 | 0.00 | 0.203915E+11 | 0.113456E+11 | 33143.00 | 10-APR-07:02 | 13870.42 | 0.00 |
May | 0.00 | 0.00 | 0.233611E+11 | 0.119373E+11 | 33124.51 | 15-MAY-07:01 | 12612.80 | 0.00 |
June | 0.00 | 0.00 | 0.235635E+11 | 0.119560E+11 | 33159.79 | 26-JUN-07:03 | 12404.60 | 0.00 |
July | 0.00 | 0.00 | 0.184789E+11 | 0.101138E+11 | 33195.09 | 05-JUL-07:01 | 14565.07 | 0.00 |
August | 0.00 | 0.00 | 0.214883E+11 | 0.103739E+11 | 33197.30 | 21-AUG-07:02 | 12220.76 | 0.00 |
September | 0.00 | 0.00 | 0.200824E+11 | 0.100345E+11 | 33234.93 | 18-SEP-07:03 | 12402.34 | 0.00 |
October | 0.00 | 0.00 | 0.193447E+11 | 0.966106E+10 | 33234.49 | 23-OCT-07:02 | 13135.96 | 0.00 |
November | 0.00 | 0.00 | 0.177512E+11 | 0.957058E+10 | 33174.91 | 20-NOV-08:61 | 14448.86 | 0.00 |
December | 0.00 | 0.00 | 0.166004E+11 | 0.985841E+10 | 33181.83 | 11-DEC-08:03 | 12949.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.232560E+12 | 0.126839E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.161058E+11 | 0.957058E+10 | 32710.67 | 12220.76 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.235635E+11 | 0.119560E+11 | 33234.93 | 15727.83 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.165397E+11 | 0.103397E+11 | 33088.13 | 02-JAN-08:62 | 14634.55 | 0.00 |
February | 0.00 | 0.00 | 0.161487E+11 | 0.100737E+11 | 32822.91 | 06-FEB-08:61 | 15748.79 | 0.00 |
March | 0.00 | 0.00 | 0.189264E+11 | 0.116648E+11 | 33245.97 | 27-MAR-07:01 | 15168.68 | 0.00 |
April | 0.00 | 0.00 | 0.204781E+11 | 0.114108E+11 | 33264.53 | 10-APR-07:02 | 13879.55 | 0.00 |
May | 0.00 | 0.00 | 0.234445E+11 | 0.119998E+11 | 33245.97 | 15-MAY-07:01 | 12664.54 | 0.00 |
June | 0.00 | 0.00 | 0.236618E+11 | 0.120285E+11 | 33281.39 | 26-JUN-07:01 | 12484.05 | 0.00 |
July | 0.00 | 0.00 | 0.185429E+11 | 0.101603E+11 | 33311.22 | 05-JUL-07:01 | 14596.80 | 0.00 |
August | 0.00 | 0.00 | 0.215423E+11 | 0.104144E+11 | 33319.03 | 21-AUG-07:02 | 12181.17 | 0.00 |
September | 0.00 | 0.00 | 0.201457E+11 | 0.100813E+11 | 33356.80 | 18-SEP-07:01 | 12445.76 | 0.00 |
October | 0.00 | 0.00 | 0.193576E+11 | 0.967254E+10 | 33356.35 | 23-OCT-07:02 | 13118.89 | 0.00 |
November | 0.00 | 0.00 | 0.177602E+11 | 0.957920E+10 | 33296.55 | 20-NOV-08:61 | 14458.30 | 0.00 |
December | 0.00 | 0.00 | 0.165992E+11 | 0.985864E+10 | 33303.51 | 11-DEC-08:61 | 13016.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.233147E+12 | 0.127284E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.161487E+11 | 0.957920E+10 | 32822.91 | 12181.17 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.236618E+11 | 0.120285E+11 | 33356.80 | 15748.79 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.184822E+11 | 0.117807E+11 | 38367.31 | 09-JAN-08:61 | 16714.99 | 0.00 |
February | 0.00 | 0.00 | 0.182116E+11 | 0.116174E+11 | 38035.55 | 20-FEB-09:01 | 19578.70 | 0.00 |
March | 0.00 | 0.00 | 0.215065E+11 | 0.135445E+11 | 38350.04 | 27-MAR-07:01 | 16511.81 | 0.00 |
April | 0.00 | 0.00 | 0.232432E+11 | 0.133561E+11 | 38423.93 | 24-APR-07:01 | 16443.32 | 0.00 |
May | 0.00 | 0.00 | 0.262181E+11 | 0.138762E+11 | 38405.08 | 17-MAY-07:01 | 16032.37 | 0.00 |
June | 0.00 | 0.00 | 0.266046E+11 | 0.140288E+11 | 38390.88 | 26-JUN-07:01 | 14781.07 | 0.00 |
July | 0.00 | 0.00 | 0.208979E+11 | 0.118147E+11 | 38434.31 | 05-JUL-07:01 | 16665.42 | 0.00 |
August | 0.00 | 0.00 | 0.240915E+11 | 0.121001E+11 | 38434.31 | 21-AUG-07:02 | 13982.86 | 0.00 |
September | 0.00 | 0.00 | 0.225942E+11 | 0.117508E+11 | 38477.87 | 18-SEP-07:03 | 14321.16 | 0.00 |
October | 0.00 | 0.00 | 0.213263E+11 | 0.110083E+11 | 38477.36 | 23-OCT-07:02 | 14960.98 | 0.00 |
November | 0.00 | 0.00 | 0.196859E+11 | 0.109309E+11 | 38446.45 | 05-NOV-08:61 | 16566.65 | 0.00 |
December | 0.00 | 0.00 | 0.184576E+11 | 0.112153E+11 | 38416.40 | 11-DEC-08:61 | 15046.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.261320E+12 | 0.147024E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.182116E+11 | 0.109309E+11 | 38035.55 | 13982.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.266046E+11 | 0.140288E+11 | 38477.87 | 19578.70 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.199104E+10 | 0.36 | 2662.87 | 01-JAN-08:61 | 0.86 |
February | 0.187357E+10 | 0.37 | 2662.87 | 01-FEB-08:61 | 0.87 |
March | 0.211296E+10 | 0.38 | 2662.87 | 01-MAR-08:61 | 0.86 |
April | 0.214251E+10 | 0.38 | 2662.87 | 01-APR-07:01 | 0.86 |
May | 0.230717E+10 | 0.39 | 2662.87 | 01-MAY-07:01 | 0.86 |
June | 0.230167E+10 | 0.40 | 2662.87 | 01-JUN-07:01 | 0.86 |
July | 0.206166E+10 | 0.37 | 2662.87 | 01-JUL-07:02 | 0.86 |
August | 0.218899E+10 | 0.38 | 2662.87 | 01-AUG-07:01 | 0.86 |
September | 0.210505E+10 | 0.38 | 2662.87 | 01-SEP-07:01 | 0.86 |
October | 0.209248E+10 | 0.37 | 2662.87 | 01-OCT-07:01 | 0.86 |
November | 0.198003E+10 | 0.37 | 2662.87 | 01-NOV-07:02 | 0.86 |
December | 0.200081E+10 | 0.36 | 2662.87 | 01-DEC-08:62 | 0.86 |
Annual Sum or Average | 0.251579E+11 | 0.38 | |||
Minimum of Months | 0.187357E+10 | 0.36 | 2662.87 | 0.86 | |
Maximum of Months | 0.230717E+10 | 0.40 | 2662.87 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.936875E+09 | 0.39 | 1406.44 | 01-JAN-08:61 | 0.90 |
February | 0.886185E+09 | 0.40 | 1406.44 | 01-FEB-08:61 | 0.90 |
March | 0.100704E+10 | 0.40 | 1406.44 | 01-MAR-08:61 | 0.90 |
April | 0.103723E+10 | 0.41 | 1406.44 | 01-APR-07:01 | 0.89 |
May | 0.113169E+10 | 0.41 | 1406.44 | 01-MAY-07:01 | 0.89 |
June | 0.112746E+10 | 0.42 | 1406.44 | 01-JUN-07:01 | 0.90 |
July | 0.987520E+09 | 0.39 | 1406.44 | 01-JUL-07:02 | 0.90 |
August | 0.105864E+10 | 0.40 | 1406.44 | 01-AUG-07:01 | 0.89 |
September | 0.101626E+10 | 0.40 | 1406.44 | 01-SEP-07:01 | 0.89 |
October | 0.100265E+10 | 0.40 | 1406.44 | 01-OCT-07:01 | 0.90 |
November | 0.943531E+09 | 0.39 | 1406.44 | 01-NOV-07:02 | 0.90 |
December | 0.938971E+09 | 0.39 | 1406.44 | 01-DEC-08:62 | 0.90 |
Annual Sum or Average | 0.120741E+11 | 0.40 | |||
Minimum of Months | 0.886185E+09 | 0.39 | 1406.44 | 0.89 | |
Maximum of Months | 0.113169E+10 | 0.42 | 1406.44 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.838887E+09 | 0.30 | 1399.70 | 01-JAN-08:61 | 0.89 |
February | 0.793666E+09 | 0.31 | 1399.70 | 01-FEB-07:01 | 0.90 |
March | 0.908904E+09 | 0.32 | 1399.70 | 01-MAR-07:01 | 0.89 |
April | 0.919296E+09 | 0.32 | 1399.70 | 01-APR-06:01 | 0.89 |
May | 0.100781E+10 | 0.33 | 1399.70 | 01-MAY-06:01 | 0.88 |
June | 0.101026E+10 | 0.34 | 1399.70 | 01-JUN-06:01 | 0.89 |
July | 0.872460E+09 | 0.31 | 1399.70 | 01-JUL-06:01 | 0.89 |
August | 0.954238E+09 | 0.32 | 1399.70 | 01-AUG-06:01 | 0.89 |
September | 0.902815E+09 | 0.32 | 1399.70 | 01-SEP-06:01 | 0.89 |
October | 0.893209E+09 | 0.31 | 1399.70 | 01-OCT-07:01 | 0.89 |
November | 0.842426E+09 | 0.31 | 1399.70 | 01-NOV-06:02 | 0.89 |
December | 0.836829E+09 | 0.30 | 1399.70 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.107808E+11 | 0.31 | |||
Minimum of Months | 0.793666E+09 | 0.30 | 1399.70 | 0.88 | |
Maximum of Months | 0.101026E+10 | 0.34 | 1399.70 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.840416E+09 | 0.30 | 1402.51 | 01-JAN-08:61 | 0.89 |
February | 0.795106E+09 | 0.31 | 1402.51 | 01-FEB-07:01 | 0.90 |
March | 0.910593E+09 | 0.32 | 1402.51 | 01-MAR-07:01 | 0.89 |
April | 0.921107E+09 | 0.32 | 1402.51 | 01-APR-06:01 | 0.89 |
May | 0.101052E+10 | 0.33 | 1402.51 | 01-MAY-06:01 | 0.88 |
June | 0.101293E+10 | 0.34 | 1402.51 | 01-JUN-06:01 | 0.89 |
July | 0.874387E+09 | 0.31 | 1402.51 | 01-JUL-06:01 | 0.89 |
August | 0.955842E+09 | 0.32 | 1402.51 | 01-AUG-06:01 | 0.89 |
September | 0.904514E+09 | 0.32 | 1402.51 | 01-SEP-06:01 | 0.89 |
October | 0.894750E+09 | 0.31 | 1402.51 | 01-OCT-07:01 | 0.89 |
November | 0.843721E+09 | 0.31 | 1402.51 | 01-NOV-06:02 | 0.89 |
December | 0.838317E+09 | 0.30 | 1402.51 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.108022E+11 | 0.31 | |||
Minimum of Months | 0.795106E+09 | 0.30 | 1402.51 | 0.88 | |
Maximum of Months | 0.101293E+10 | 0.34 | 1402.51 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.833186E+09 | 0.30 | 1392.75 | 01-JAN-08:61 | 0.89 |
February | 0.788000E+09 | 0.31 | 1392.75 | 01-FEB-07:01 | 0.90 |
March | 0.902480E+09 | 0.32 | 1392.75 | 01-MAR-07:01 | 0.89 |
April | 0.912782E+09 | 0.32 | 1392.75 | 01-APR-06:01 | 0.89 |
May | 0.100175E+10 | 0.33 | 1392.75 | 01-MAY-06:01 | 0.88 |
June | 0.100407E+10 | 0.34 | 1392.75 | 01-JUN-06:01 | 0.89 |
July | 0.866446E+09 | 0.30 | 1392.75 | 01-JUL-06:01 | 0.89 |
August | 0.947136E+09 | 0.32 | 1392.75 | 01-AUG-06:01 | 0.89 |
September | 0.896265E+09 | 0.32 | 1392.75 | 01-SEP-06:01 | 0.89 |
October | 0.886429E+09 | 0.31 | 1392.75 | 01-OCT-07:01 | 0.89 |
November | 0.835903E+09 | 0.30 | 1392.75 | 01-NOV-06:02 | 0.89 |
December | 0.831121E+09 | 0.30 | 1392.75 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.107056E+11 | 0.31 | |||
Minimum of Months | 0.788000E+09 | 0.30 | 1392.75 | 0.88 | |
Maximum of Months | 0.100407E+10 | 0.34 | 1392.75 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134656E+10 | 0.27 | 2374.56 | 01-JAN-09:01 | 0.86 |
February | 0.129051E+10 | 0.28 | 2374.56 | 01-FEB-08:61 | 0.87 |
March | 0.148128E+10 | 0.29 | 2374.56 | 01-MAR-08:61 | 0.86 |
April | 0.150973E+10 | 0.29 | 2374.56 | 01-APR-07:01 | 0.86 |
May | 0.167836E+10 | 0.31 | 2374.56 | 01-MAY-07:01 | 0.85 |
June | 0.169024E+10 | 0.31 | 2374.56 | 01-JUN-07:01 | 0.86 |
July | 0.141760E+10 | 0.28 | 2374.56 | 01-JUL-07:02 | 0.86 |
August | 0.156580E+10 | 0.30 | 2374.56 | 01-AUG-07:01 | 0.86 |
September | 0.147998E+10 | 0.29 | 2374.56 | 01-SEP-07:01 | 0.86 |
October | 0.145317E+10 | 0.28 | 2374.56 | 01-OCT-08:61 | 0.86 |
November | 0.136195E+10 | 0.28 | 2374.56 | 01-NOV-07:02 | 0.86 |
December | 0.133926E+10 | 0.27 | 2374.56 | 01-DEC-08:62 | 0.86 |
Annual Sum or Average | 0.176144E+11 | 0.29 | |||
Minimum of Months | 0.129051E+10 | 0.27 | 2374.56 | 0.85 | |
Maximum of Months | 0.169024E+10 | 0.31 | 2374.56 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.729682E+09 | 0.28 | 1289.06 | 01-JAN-09:01 | 0.89 |
February | 0.699365E+09 | 0.29 | 1289.06 | 01-FEB-08:61 | 0.90 |
March | 0.802858E+09 | 0.30 | 1289.06 | 01-MAR-08:61 | 0.89 |
April | 0.818064E+09 | 0.30 | 1289.06 | 01-APR-07:01 | 0.89 |
May | 0.907273E+09 | 0.32 | 1289.06 | 01-MAY-07:01 | 0.88 |
June | 0.911710E+09 | 0.32 | 1289.06 | 01-JUN-07:01 | 0.89 |
July | 0.767294E+09 | 0.29 | 1289.06 | 01-JUL-07:02 | 0.89 |
August | 0.846419E+09 | 0.31 | 1289.06 | 01-AUG-07:01 | 0.89 |
September | 0.800714E+09 | 0.30 | 1289.06 | 01-SEP-07:01 | 0.89 |
October | 0.786510E+09 | 0.29 | 1289.06 | 01-OCT-08:61 | 0.89 |
November | 0.737473E+09 | 0.29 | 1289.06 | 01-NOV-07:02 | 0.89 |
December | 0.725617E+09 | 0.28 | 1289.06 | 01-DEC-08:62 | 0.89 |
Annual Sum or Average | 0.953298E+10 | 0.30 | |||
Minimum of Months | 0.699365E+09 | 0.28 | 1289.06 | 0.88 | |
Maximum of Months | 0.911710E+09 | 0.32 | 1289.06 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.726710E+09 | 0.28 | 1283.56 | 01-JAN-09:01 | 0.89 |
February | 0.696738E+09 | 0.29 | 1283.56 | 01-FEB-08:61 | 0.90 |
March | 0.799976E+09 | 0.30 | 1283.56 | 01-MAR-08:61 | 0.89 |
April | 0.815390E+09 | 0.30 | 1283.56 | 01-APR-07:01 | 0.89 |
May | 0.904540E+09 | 0.32 | 1283.56 | 01-MAY-07:01 | 0.88 |
June | 0.909000E+09 | 0.32 | 1283.56 | 01-JUN-07:01 | 0.89 |
July | 0.764517E+09 | 0.29 | 1283.56 | 01-JUL-07:02 | 0.89 |
August | 0.843543E+09 | 0.31 | 1283.56 | 01-AUG-07:01 | 0.89 |
September | 0.798017E+09 | 0.30 | 1283.56 | 01-SEP-07:01 | 0.89 |
October | 0.783555E+09 | 0.29 | 1283.56 | 01-OCT-08:61 | 0.89 |
November | 0.734541E+09 | 0.29 | 1283.56 | 01-NOV-07:02 | 0.89 |
December | 0.722608E+09 | 0.28 | 1283.56 | 01-DEC-08:62 | 0.89 |
Annual Sum or Average | 0.949914E+10 | 0.30 | |||
Minimum of Months | 0.696738E+09 | 0.28 | 1283.56 | 0.88 | |
Maximum of Months | 0.909000E+09 | 0.32 | 1283.56 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.728629E+09 | 0.28 | 1288.27 | 01-JAN-09:01 | 0.89 |
February | 0.698944E+09 | 0.29 | 1288.27 | 01-FEB-08:61 | 0.90 |
March | 0.803173E+09 | 0.30 | 1288.27 | 01-MAR-08:61 | 0.89 |
April | 0.819170E+09 | 0.30 | 1288.27 | 01-APR-07:01 | 0.89 |
May | 0.908600E+09 | 0.32 | 1288.27 | 01-MAY-07:01 | 0.88 |
June | 0.913532E+09 | 0.32 | 1288.27 | 01-JUN-07:01 | 0.89 |
July | 0.767549E+09 | 0.29 | 1288.27 | 01-JUL-07:02 | 0.89 |
August | 0.846720E+09 | 0.31 | 1288.27 | 01-AUG-07:01 | 0.89 |
September | 0.801311E+09 | 0.30 | 1288.27 | 01-SEP-07:01 | 0.89 |
October | 0.785492E+09 | 0.29 | 1288.27 | 01-OCT-08:61 | 0.89 |
November | 0.736321E+09 | 0.29 | 1288.27 | 01-NOV-07:02 | 0.89 |
December | 0.724347E+09 | 0.28 | 1288.27 | 01-DEC-08:62 | 0.89 |
Annual Sum or Average | 0.953379E+10 | 0.30 | |||
Minimum of Months | 0.698944E+09 | 0.28 | 1288.27 | 0.88 | |
Maximum of Months | 0.913532E+09 | 0.32 | 1288.27 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.824876E+09 | 0.28 | 1486.05 | 01-JAN-09:01 | 0.89 |
February | 0.788229E+09 | 0.29 | 1486.05 | 01-FEB-08:61 | 0.90 |
March | 0.913949E+09 | 0.30 | 1486.05 | 01-MAR-08:61 | 0.89 |
April | 0.931727E+09 | 0.30 | 1486.05 | 01-APR-07:01 | 0.89 |
May | 0.102736E+10 | 0.31 | 1486.05 | 01-MAY-07:01 | 0.88 |
June | 0.103517E+10 | 0.32 | 1486.05 | 01-JUN-07:01 | 0.89 |
July | 0.871713E+09 | 0.28 | 1486.05 | 01-JUL-07:02 | 0.89 |
August | 0.959962E+09 | 0.30 | 1486.05 | 01-AUG-07:01 | 0.89 |
September | 0.907802E+09 | 0.30 | 1486.05 | 01-SEP-07:01 | 0.89 |
October | 0.883625E+09 | 0.29 | 1486.05 | 01-OCT-08:61 | 0.89 |
November | 0.828903E+09 | 0.28 | 1486.05 | 01-NOV-07:02 | 0.89 |
December | 0.820803E+09 | 0.28 | 1486.05 | 01-DEC-08:62 | 0.89 |
Annual Sum or Average | 0.107941E+11 | 0.29 | |||
Minimum of Months | 0.788229E+09 | 0.28 | 1486.05 | 0.88 | |
Maximum of Months | 0.103517E+10 | 0.32 | 1486.05 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.131256E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.127454E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.148036E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.157428E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.171977E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.171006E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.143189E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.155810E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.149628E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.144237E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.134908E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.131609E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.176654E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.127454E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.171977E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.638165E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.616485E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.712804E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.756463E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.831834E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.826382E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.691988E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.754810E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.723286E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.701283E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.655586E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.640070E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.854916E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.616485E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.831834E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.523112E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.508622E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.597341E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.625136E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.696581E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.697956E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.564564E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.635366E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.598725E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.579343E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.541103E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.521993E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.708984E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.508622E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.697956E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.524364E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.509895E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.598751E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.626813E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.698859E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.700148E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.566351E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.636595E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.600154E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.580610E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.541972E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.522881E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.710739E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.509895E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.700148E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.518188E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.504167E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.592064E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.620021E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.691964E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.693326E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.559945E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.629353E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.593418E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.573770E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.535540E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.516594E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.702835E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.504167E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.693326E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.923470E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.903290E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.106115E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.111377E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.124897E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.125844E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.996635E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.112954E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.106146E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.102181E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.953677E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.915394E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.125876E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.903290E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.125844E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.476300E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.466072E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.547333E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.574615E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.643703E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.647771E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.513602E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.581598E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.546917E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.526504E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.491434E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.471996E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.648785E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.466072E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.647771E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.474109E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.464161E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.545214E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.572633E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.641596E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.645665E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.511627E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.579456E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.544938E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.524342E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.489260E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.469758E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.646276E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.464161E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.645665E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.474761E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.465537E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.547185E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.575248E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.644228E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.648699E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.513521E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.581230E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.546907E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.525046E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.489822E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.470113E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.648230E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.465537E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.648699E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.535129E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.527779E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.625303E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.657750E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.728508E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.736959E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.583434E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.657471E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.619730E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.585851E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.548698E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.528433E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.733504E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.527779E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.736959E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.199104E+10 | 0.447425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187357E+10 | 0.433619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211296E+10 | 0.504549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214251E+10 | 0.552384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.230717E+10 | 0.616471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.230167E+10 | 0.614259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.206166E+10 | 0.505521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.218899E+10 | 0.565095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.210505E+10 | 0.539763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.209248E+10 | 0.518810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198003E+10 | 0.478105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200081E+10 | 0.454951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.251579E+11 | 0.623095E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.187357E+10 | 0.433619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.230717E+10 | 0.616471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.936875E+09 | 0.221220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.886185E+09 | 0.212692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.100704E+10 | 0.245288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103723E+10 | 0.266533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113169E+10 | 0.299138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112746E+10 | 0.298065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.987520E+09 | 0.246774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.105864E+10 | 0.276084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101626E+10 | 0.262955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100265E+10 | 0.255324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.943531E+09 | 0.235463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.938971E+09 | 0.224989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120741E+11 | 0.304453E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.886185E+09 | 0.212692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113169E+10 | 0.299138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.838887E+09 | 0.180302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.793666E+09 | 0.174841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.908904E+09 | 0.204908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.919296E+09 | 0.220651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100781E+10 | 0.251592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101026E+10 | 0.252657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.872460E+09 | 0.201913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.954238E+09 | 0.233292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.902815E+09 | 0.218589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.893209E+09 | 0.211564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.842426E+09 | 0.194246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.836829E+09 | 0.182298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107808E+11 | 0.252685E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.793666E+09 | 0.174841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101026E+10 | 0.252657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.840416E+09 | 0.180756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.795106E+09 | 0.175304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.910593E+09 | 0.205413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.921107E+09 | 0.221278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101052E+10 | 0.252431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101293E+10 | 0.253447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.874387E+09 | 0.202610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.955842E+09 | 0.233732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.904514E+09 | 0.219123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.894750E+09 | 0.212036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.843721E+09 | 0.194540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.838317E+09 | 0.182584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108022E+11 | 0.253325E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.795106E+09 | 0.175304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101293E+10 | 0.253447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.833186E+09 | 0.178435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.788000E+09 | 0.173224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.902480E+09 | 0.202992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.912782E+09 | 0.218829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100175E+10 | 0.249979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100407E+10 | 0.251042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.866446E+09 | 0.200209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.947136E+09 | 0.230997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.896265E+09 | 0.216588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.886429E+09 | 0.209435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.835903E+09 | 0.192098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.831121E+09 | 0.180173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107056E+11 | 0.250400E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.788000E+09 | 0.173224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100407E+10 | 0.251042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.134656E+10 | 0.319758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129051E+10 | 0.311245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148128E+10 | 0.364637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150973E+10 | 0.393843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167836E+10 | 0.451327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.169024E+10 | 0.455658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141760E+10 | 0.357452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156580E+10 | 0.415915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147998E+10 | 0.388391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145317E+10 | 0.374369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136195E+10 | 0.343702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133926E+10 | 0.321369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176144E+11 | 0.449767E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129051E+10 | 0.311245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169024E+10 | 0.455658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.729682E+09 | 0.166043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.699365E+09 | 0.161706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.802858E+09 | 0.189350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.818064E+09 | 0.204570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.907273E+09 | 0.234314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.911710E+09 | 0.236340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.767294E+09 | 0.185467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.846419E+09 | 0.215623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.800714E+09 | 0.201505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.786510E+09 | 0.194209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.737473E+09 | 0.178280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.725617E+09 | 0.166793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.953298E+10 | 0.233420E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.699365E+09 | 0.161706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.911710E+09 | 0.236340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.726710E+09 | 0.165279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.696738E+09 | 0.161058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.799976E+09 | 0.188645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.815390E+09 | 0.203915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.904540E+09 | 0.233611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.909000E+09 | 0.235635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.764517E+09 | 0.184789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.843543E+09 | 0.214883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.798017E+09 | 0.200824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.783555E+09 | 0.193447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.734541E+09 | 0.177512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.722608E+09 | 0.166004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.949914E+10 | 0.232560E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.696738E+09 | 0.161058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.909000E+09 | 0.235635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.728629E+09 | 0.165397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.698944E+09 | 0.161487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.803173E+09 | 0.189264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.819170E+09 | 0.204781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.908600E+09 | 0.234445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.913532E+09 | 0.236618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.767549E+09 | 0.185429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.846720E+09 | 0.215423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.801311E+09 | 0.201457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.785492E+09 | 0.193576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.736321E+09 | 0.177602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.724347E+09 | 0.165992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.953379E+10 | 0.233147E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.698944E+09 | 0.161487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.913532E+09 | 0.236618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.824876E+09 | 0.184822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.788229E+09 | 0.182116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.913949E+09 | 0.215065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.931727E+09 | 0.232432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102736E+10 | 0.262181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103517E+10 | 0.266046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.871713E+09 | 0.208979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.959962E+09 | 0.240915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.907802E+09 | 0.225942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.883625E+09 | 0.213263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.828903E+09 | 0.196859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.820803E+09 | 0.184576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107941E+11 | 0.261320E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.788229E+09 | 0.182116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103517E+10 | 0.266046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.199104E+10 | 0.00 | 0.00 | 0.00 | 0.111346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187357E+10 | 0.00 | 0.00 | 0.00 | 0.108718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211296E+10 | 0.00 | 0.00 | 0.00 | 0.126907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214251E+10 | 0.00 | 0.00 | 0.00 | 0.136003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.230717E+10 | 0.00 | 0.00 | 0.00 | 0.148905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.230167E+10 | 0.00 | 0.00 | 0.00 | 0.147989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.206166E+10 | 0.00 | 0.00 | 0.00 | 0.122573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.218899E+10 | 0.00 | 0.00 | 0.00 | 0.133920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.210505E+10 | 0.00 | 0.00 | 0.00 | 0.128577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.209248E+10 | 0.00 | 0.00 | 0.00 | 0.123312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198003E+10 | 0.00 | 0.00 | 0.00 | 0.115108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200081E+10 | 0.00 | 0.00 | 0.00 | 0.111601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.251579E+11 | 0.00 | 0.00 | 0.00 | 0.151496E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.187357E+10 | 0.00 | 0.00 | 0.00 | 0.108718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.230717E+10 | 0.00 | 0.00 | 0.00 | 0.148905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.936875E+09 | 0.00 | 0.00 | 0.00 | 0.544478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.886185E+09 | 0.00 | 0.00 | 0.00 | 0.527867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.612100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103723E+10 | 0.00 | 0.00 | 0.00 | 0.652740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113169E+10 | 0.00 | 0.00 | 0.00 | 0.718665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112746E+10 | 0.00 | 0.00 | 0.00 | 0.713636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.987520E+09 | 0.00 | 0.00 | 0.00 | 0.593236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.105864E+10 | 0.00 | 0.00 | 0.00 | 0.648946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101626E+10 | 0.00 | 0.00 | 0.00 | 0.621661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100265E+10 | 0.00 | 0.00 | 0.00 | 0.601018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.943531E+09 | 0.00 | 0.00 | 0.00 | 0.561233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.938971E+09 | 0.00 | 0.00 | 0.00 | 0.546173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120741E+11 | 0.00 | 0.00 | 0.00 | 0.734175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.886185E+09 | 0.00 | 0.00 | 0.00 | 0.527867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113169E+10 | 0.00 | 0.00 | 0.00 | 0.718665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.838887E+09 | 0.00 | 0.00 | 0.00 | 0.439223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.793666E+09 | 0.00 | 0.00 | 0.00 | 0.429255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.908904E+09 | 0.00 | 0.00 | 0.00 | 0.506451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.919296E+09 | 0.00 | 0.00 | 0.00 | 0.533207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100781E+10 | 0.00 | 0.00 | 0.00 | 0.595801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101026E+10 | 0.00 | 0.00 | 0.00 | 0.596930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.872460E+09 | 0.00 | 0.00 | 0.00 | 0.477318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.954238E+09 | 0.00 | 0.00 | 0.00 | 0.539942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.902815E+09 | 0.00 | 0.00 | 0.00 | 0.508443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.893209E+09 | 0.00 | 0.00 | 0.00 | 0.490022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.842426E+09 | 0.00 | 0.00 | 0.00 | 0.456860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.836829E+09 | 0.00 | 0.00 | 0.00 | 0.438310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107808E+11 | 0.00 | 0.00 | 0.00 | 0.601176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.793666E+09 | 0.00 | 0.00 | 0.00 | 0.429255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101026E+10 | 0.00 | 0.00 | 0.00 | 0.596930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.840416E+09 | 0.00 | 0.00 | 0.00 | 0.440322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.795106E+09 | 0.00 | 0.00 | 0.00 | 0.430384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.910593E+09 | 0.00 | 0.00 | 0.00 | 0.507692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.921107E+09 | 0.00 | 0.00 | 0.00 | 0.534702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101052E+10 | 0.00 | 0.00 | 0.00 | 0.597807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101293E+10 | 0.00 | 0.00 | 0.00 | 0.598855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.874387E+09 | 0.00 | 0.00 | 0.00 | 0.478913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.955842E+09 | 0.00 | 0.00 | 0.00 | 0.541011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.904514E+09 | 0.00 | 0.00 | 0.00 | 0.509702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.894750E+09 | 0.00 | 0.00 | 0.00 | 0.491135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.843721E+09 | 0.00 | 0.00 | 0.00 | 0.457600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.838317E+09 | 0.00 | 0.00 | 0.00 | 0.439049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108022E+11 | 0.00 | 0.00 | 0.00 | 0.602717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.795106E+09 | 0.00 | 0.00 | 0.00 | 0.430384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101293E+10 | 0.00 | 0.00 | 0.00 | 0.598855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.833186E+09 | 0.00 | 0.00 | 0.00 | 0.434870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.788000E+09 | 0.00 | 0.00 | 0.00 | 0.425367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.902480E+09 | 0.00 | 0.00 | 0.00 | 0.501816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.912782E+09 | 0.00 | 0.00 | 0.00 | 0.528743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100175E+10 | 0.00 | 0.00 | 0.00 | 0.591789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100407E+10 | 0.00 | 0.00 | 0.00 | 0.592919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.866446E+09 | 0.00 | 0.00 | 0.00 | 0.473301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.947136E+09 | 0.00 | 0.00 | 0.00 | 0.534639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.896265E+09 | 0.00 | 0.00 | 0.00 | 0.503791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.886429E+09 | 0.00 | 0.00 | 0.00 | 0.485127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.835903E+09 | 0.00 | 0.00 | 0.00 | 0.451950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.831121E+09 | 0.00 | 0.00 | 0.00 | 0.433482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107056E+11 | 0.00 | 0.00 | 0.00 | 0.595779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.788000E+09 | 0.00 | 0.00 | 0.00 | 0.425367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100407E+10 | 0.00 | 0.00 | 0.00 | 0.592919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.134656E+10 | 0.00 | 0.00 | 0.00 | 0.788814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129051E+10 | 0.00 | 0.00 | 0.00 | 0.774239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148128E+10 | 0.00 | 0.00 | 0.00 | 0.913021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150973E+10 | 0.00 | 0.00 | 0.00 | 0.962796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167836E+10 | 0.00 | 0.00 | 0.00 | 0.108114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.169024E+10 | 0.00 | 0.00 | 0.00 | 0.108942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141760E+10 | 0.00 | 0.00 | 0.00 | 0.854875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156580E+10 | 0.00 | 0.00 | 0.00 | 0.972961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147998E+10 | 0.00 | 0.00 | 0.00 | 0.913459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145317E+10 | 0.00 | 0.00 | 0.00 | 0.876493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136195E+10 | 0.00 | 0.00 | 0.00 | 0.817482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133926E+10 | 0.00 | 0.00 | 0.00 | 0.781467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176144E+11 | 0.00 | 0.00 | 0.00 | 0.108262E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129051E+10 | 0.00 | 0.00 | 0.00 | 0.774239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169024E+10 | 0.00 | 0.00 | 0.00 | 0.108942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.729682E+09 | 0.00 | 0.00 | 0.00 | 0.403332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.699365E+09 | 0.00 | 0.00 | 0.00 | 0.396135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.802858E+09 | 0.00 | 0.00 | 0.00 | 0.467047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.818064E+09 | 0.00 | 0.00 | 0.00 | 0.492809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.907273E+09 | 0.00 | 0.00 | 0.00 | 0.552976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.911710E+09 | 0.00 | 0.00 | 0.00 | 0.556600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.767294E+09 | 0.00 | 0.00 | 0.00 | 0.436872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.846419E+09 | 0.00 | 0.00 | 0.00 | 0.496956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.800714E+09 | 0.00 | 0.00 | 0.00 | 0.466846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.786510E+09 | 0.00 | 0.00 | 0.00 | 0.447853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.737473E+09 | 0.00 | 0.00 | 0.00 | 0.417687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.725617E+09 | 0.00 | 0.00 | 0.00 | 0.399434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.953298E+10 | 0.00 | 0.00 | 0.00 | 0.553455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.699365E+09 | 0.00 | 0.00 | 0.00 | 0.396135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.911710E+09 | 0.00 | 0.00 | 0.00 | 0.556600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.726710E+09 | 0.00 | 0.00 | 0.00 | 0.401438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.696738E+09 | 0.00 | 0.00 | 0.00 | 0.394487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.799976E+09 | 0.00 | 0.00 | 0.00 | 0.465217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.815390E+09 | 0.00 | 0.00 | 0.00 | 0.491094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.904540E+09 | 0.00 | 0.00 | 0.00 | 0.551142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.909000E+09 | 0.00 | 0.00 | 0.00 | 0.554765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.764517E+09 | 0.00 | 0.00 | 0.00 | 0.435176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.843543E+09 | 0.00 | 0.00 | 0.00 | 0.495102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.798017E+09 | 0.00 | 0.00 | 0.00 | 0.465137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.783555E+09 | 0.00 | 0.00 | 0.00 | 0.445987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.734541E+09 | 0.00 | 0.00 | 0.00 | 0.415806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.722608E+09 | 0.00 | 0.00 | 0.00 | 0.397497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.949914E+10 | 0.00 | 0.00 | 0.00 | 0.551285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.696738E+09 | 0.00 | 0.00 | 0.00 | 0.394487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.909000E+09 | 0.00 | 0.00 | 0.00 | 0.554765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.728629E+09 | 0.00 | 0.00 | 0.00 | 0.401898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.698944E+09 | 0.00 | 0.00 | 0.00 | 0.395643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.803173E+09 | 0.00 | 0.00 | 0.00 | 0.466868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.819170E+09 | 0.00 | 0.00 | 0.00 | 0.493331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.908600E+09 | 0.00 | 0.00 | 0.00 | 0.553368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.913532E+09 | 0.00 | 0.00 | 0.00 | 0.557346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.767549E+09 | 0.00 | 0.00 | 0.00 | 0.436766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.846720E+09 | 0.00 | 0.00 | 0.00 | 0.496558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.801311E+09 | 0.00 | 0.00 | 0.00 | 0.466776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.785492E+09 | 0.00 | 0.00 | 0.00 | 0.446497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.736321E+09 | 0.00 | 0.00 | 0.00 | 0.416190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.724347E+09 | 0.00 | 0.00 | 0.00 | 0.397678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.953379E+10 | 0.00 | 0.00 | 0.00 | 0.552892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.698944E+09 | 0.00 | 0.00 | 0.00 | 0.395643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.913532E+09 | 0.00 | 0.00 | 0.00 | 0.557346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.824876E+09 | 0.00 | 0.00 | 0.00 | 0.452642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.788229E+09 | 0.00 | 0.00 | 0.00 | 0.448956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.913949E+09 | 0.00 | 0.00 | 0.00 | 0.533908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.931727E+09 | 0.00 | 0.00 | 0.00 | 0.564577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102736E+10 | 0.00 | 0.00 | 0.00 | 0.625772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103517E+10 | 0.00 | 0.00 | 0.00 | 0.633442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.871713E+09 | 0.00 | 0.00 | 0.00 | 0.496263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.959962E+09 | 0.00 | 0.00 | 0.00 | 0.561475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.907802E+09 | 0.00 | 0.00 | 0.00 | 0.528949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.883625E+09 | 0.00 | 0.00 | 0.00 | 0.497488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.828903E+09 | 0.00 | 0.00 | 0.00 | 0.465807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.820803E+09 | 0.00 | 0.00 | 0.00 | 0.446353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107941E+11 | 0.00 | 0.00 | 0.00 | 0.625563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.788229E+09 | 0.00 | 0.00 | 0.00 | 0.446353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103517E+10 | 0.00 | 0.00 | 0.00 | 0.633442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2825.59 | 0.145497E+11 | 0.00 | 239514.92 | 0.112153E+09 | 0.00 | 2292181.45 | 0.00 | 0.57 |
February | 0.00 | 0.146589E+11 | 0.00 | 128114.18 | 0.118929E+09 | 0.00 | 1633713.42 | 0.00 | 0.57 |
March | 0.00 | 0.176684E+11 | 0.00 | 0.00 | 0.117604E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
April | 0.00 | 0.217461E+11 | 0.00 | 0.00 | 0.134306E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
May | 0.00 | 0.256610E+11 | 0.00 | 0.00 | 0.139342E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.254644E+11 | 0.00 | 0.00 | 0.118938E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.186664E+11 | 0.00 | 0.00 | 0.163261E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.231346E+11 | 0.00 | 0.00 | 0.171089E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.216827E+11 | 0.00 | 0.00 | 0.170076E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
October | 0.00 | 0.203401E+11 | 0.00 | 0.00 | 0.175603E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
November | 0.00 | 0.177240E+11 | 0.00 | 0.00 | 0.115062E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
December | 0.00 | 0.154377E+11 | 0.00 | 5597.79 | 0.130594E+09 | 0.00 | 147393.49 | 0.00 | 0.58 |
Annual Sum or Average | 2825.59 | 0.236734E+12 | 0.00 | 373226.89 | 0.166696E+10 | 0.00 | 4073288.37 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.145497E+11 | 0.00 | 0.00 | 0.112153E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 2825.59 | 0.256610E+11 | 0.00 | 239514.92 | 0.175603E+09 | 0.00 | 2292181.45 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.641394E+10 | 0.00 | 0.00 | 81724280.24 | 0.00 | 0.00 | 0.00 | 0.48 |
February | 0.00 | 0.644159E+10 | 0.00 | 0.00 | 78936853.18 | 0.00 | 0.00 | 0.00 | 0.48 |
March | 0.00 | 0.773952E+10 | 0.00 | 0.00 | 92937324.75 | 0.00 | 0.00 | 0.00 | 0.48 |
April | 0.00 | 0.948320E+10 | 0.00 | 0.00 | 87552312.91 | 0.00 | 0.00 | 0.00 | 0.49 |
May | 0.00 | 0.113032E+11 | 0.00 | 0.00 | 99842319.53 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.112920E+11 | 0.00 | 0.00 | 83520876.60 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.815677E+10 | 0.00 | 0.00 | 0.105755E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.102517E+11 | 0.00 | 0.00 | 0.114766E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.952684E+10 | 0.00 | 0.00 | 0.112369E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.897222E+10 | 0.00 | 0.00 | 0.119266E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
November | 0.00 | 0.781761E+10 | 0.00 | 0.00 | 85778252.20 | 0.00 | 0.00 | 0.00 | 0.48 |
December | 0.00 | 0.680148E+10 | 0.00 | 0.00 | 97196230.23 | 0.00 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.00 | 0.104200E+12 | 0.00 | 0.00 | 0.115965E+10 | 0.00 | 0.00 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.641394E+10 | 0.00 | 0.00 | 78936853.18 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.00 | 0.113032E+11 | 0.00 | 0.00 | 0.119266E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3274515.70 | 0.531337E+10 | 0.00 | 459172.60 | 0.327806E+09 | 0.00 | 7139615.70 | 0.00 | 0.46 |
February | 1255957.64 | 0.536324E+10 | 0.00 | 438225.20 | 0.332707E+09 | 0.00 | 1055579.40 | 0.00 | 0.46 |
March | 0.00 | 0.662257E+10 | 0.00 | 57562.72 | 0.403650E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
April | 0.00 | 0.784488E+10 | 0.00 | 0.00 | 0.536858E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 0.00 | 0.947390E+10 | 0.00 | 0.00 | 0.577123E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.954881E+10 | 0.00 | 16507.65 | 0.582651E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.673624E+10 | 0.00 | 0.00 | 0.439975E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.874326E+10 | 0.00 | 13899.89 | 0.521922E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.794680E+10 | 0.00 | 24884.55 | 0.503274E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 0.00 | 0.750157E+10 | 0.00 | 84157.43 | 0.468542E+09 | 0.00 | 3032.86 | 0.00 | 0.46 |
November | 452449.00 | 0.647999E+10 | 0.00 | 359529.04 | 0.411291E+09 | 0.00 | 826781.75 | 0.00 | 0.46 |
December | 41686.95 | 0.557487E+10 | 0.00 | 579782.56 | 0.344400E+09 | 0.00 | 393938.92 | 0.00 | 0.46 |
Annual Sum or Average | 5024609.29 | 0.871495E+11 | 0.00 | 2033721.65 | 0.545020E+10 | 0.00 | 9418948.63 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.531337E+10 | 0.00 | 0.00 | 0.327806E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 3274515.70 | 0.954881E+10 | 0.00 | 579782.56 | 0.582651E+09 | 0.00 | 7139615.70 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3258877.42 | 0.532213E+10 | 0.00 | 470017.53 | 0.327340E+09 | 0.00 | 6941743.64 | 0.00 | 0.46 |
February | 1250814.89 | 0.537371E+10 | 0.00 | 455207.17 | 0.330349E+09 | 0.00 | 1052832.79 | 0.00 | 0.46 |
March | 0.00 | 0.663211E+10 | 0.00 | 63038.95 | 0.403345E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
April | 0.00 | 0.785792E+10 | 0.00 | 0.00 | 0.536323E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 0.00 | 0.949207E+10 | 0.00 | 0.00 | 0.575970E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.956574E+10 | 0.00 | 18334.17 | 0.581914E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.675015E+10 | 0.00 | 0.00 | 0.440614E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.875346E+10 | 0.00 | 15241.80 | 0.521425E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.795851E+10 | 0.00 | 25863.19 | 0.503090E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 0.00 | 0.751280E+10 | 0.00 | 90135.05 | 0.467720E+09 | 0.00 | 3198.51 | 0.00 | 0.46 |
November | 430891.08 | 0.648739E+10 | 0.00 | 373897.17 | 0.409679E+09 | 0.00 | 820691.25 | 0.00 | 0.46 |
December | 40815.30 | 0.558082E+10 | 0.00 | 597211.56 | 0.344161E+09 | 0.00 | 392359.91 | 0.00 | 0.46 |
Annual Sum or Average | 4981398.69 | 0.872868E+11 | 0.00 | 2108946.59 | 0.544193E+10 | 0.00 | 9210826.10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.532213E+10 | 0.00 | 0.00 | 0.327340E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 3258877.42 | 0.956574E+10 | 0.00 | 597211.56 | 0.581914E+09 | 0.00 | 6941743.64 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3363067.03 | 0.528464E+10 | 0.00 | 447568.41 | 0.327083E+09 | 0.00 | 7632583.68 | 0.00 | 0.46 |
February | 1275769.06 | 0.534141E+10 | 0.00 | 424332.41 | 0.329058E+09 | 0.00 | 1156912.62 | 0.00 | 0.46 |
March | 0.00 | 0.659087E+10 | 0.00 | 57728.15 | 0.404329E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
April | 0.00 | 0.781381E+10 | 0.00 | 0.00 | 0.536488E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 0.00 | 0.944392E+10 | 0.00 | 0.00 | 0.577614E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.951935E+10 | 0.00 | 16821.44 | 0.582884E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.670839E+10 | 0.00 | 0.00 | 0.436709E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.869368E+10 | 0.00 | 13301.96 | 0.523224E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.790976E+10 | 0.00 | 23800.06 | 0.499429E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 0.00 | 0.745862E+10 | 0.00 | 81308.45 | 0.467376E+09 | 0.00 | 3245.21 | 0.00 | 0.46 |
November | 464447.67 | 0.644201E+10 | 0.00 | 352514.15 | 0.407626E+09 | 0.00 | 861070.42 | 0.00 | 0.46 |
December | 41054.87 | 0.553961E+10 | 0.00 | 563292.90 | 0.342106E+09 | 0.00 | 403507.77 | 0.00 | 0.46 |
Annual Sum or Average | 5144338.63 | 0.867461E+11 | 0.00 | 1980667.93 | 0.543393E+10 | 0.00 | 10057319.71 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.528464E+10 | 0.00 | 0.00 | 0.327083E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 3363067.03 | 0.951935E+10 | 0.00 | 563292.90 | 0.582884E+09 | 0.00 | 7632583.68 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1990777.45 | 0.101220E+11 | 0.00 | 807342.13 | 0.239963E+09 | 0.00 | 7130981.64 | 0.00 | 0.42 |
February | 0.00 | 0.102480E+11 | 0.00 | 302538.46 | 0.274658E+09 | 0.00 | 80257.80 | 0.00 | 0.42 |
March | 0.00 | 0.125600E+11 | 0.00 | 0.00 | 0.283958E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
April | 0.00 | 0.149662E+11 | 0.00 | 0.00 | 0.395109E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.00 | 0.180097E+11 | 0.00 | 0.00 | 0.401270E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.183501E+11 | 0.00 | 0.00 | 0.362308E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.126849E+11 | 0.00 | 0.00 | 0.388491E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.166482E+11 | 0.00 | 0.00 | 0.350468E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.150735E+11 | 0.00 | 161771.09 | 0.396260E+09 | 0.00 | 9338.27 | 0.00 | 0.43 |
October | 0.00 | 0.141508E+11 | 0.00 | 42332.64 | 0.387698E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 255152.90 | 0.123291E+11 | 0.00 | 487135.86 | 0.270513E+09 | 0.00 | 1020691.28 | 0.00 | 0.43 |
December | 2935.39 | 0.104975E+11 | 0.00 | 392153.45 | 0.312530E+09 | 0.00 | 392846.09 | 0.00 | 0.42 |
Annual Sum or Average | 2248865.74 | 0.165640E+12 | 0.00 | 2193273.63 | 0.406323E+10 | 0.00 | 8634115.08 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.101220E+11 | 0.00 | 0.00 | 0.239963E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 1990777.45 | 0.183501E+11 | 0.00 | 807342.13 | 0.401270E+09 | 0.00 | 7130981.64 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1009511.89 | 0.505231E+10 | 0.00 | 391909.16 | 0.119357E+09 | 0.00 | 3548028.72 | 0.00 | 0.42 |
February | 0.00 | 0.511859E+10 | 0.00 | 145652.43 | 0.133671E+09 | 0.00 | 40885.39 | 0.00 | 0.42 |
March | 0.00 | 0.627696E+10 | 0.00 | 0.00 | 0.137300E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
April | 0.00 | 0.747150E+10 | 0.00 | 0.00 | 0.192857E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.00 | 0.898215E+10 | 0.00 | 0.00 | 0.197582E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.914736E+10 | 0.00 | 0.00 | 0.177958E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.632286E+10 | 0.00 | 0.00 | 0.190647E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.828957E+10 | 0.00 | 0.00 | 0.175165E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.750920E+10 | 0.00 | 85198.85 | 0.193956E+09 | 0.00 | 14404.31 | 0.00 | 0.43 |
October | 0.00 | 0.705215E+10 | 0.00 | 25223.41 | 0.185290E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 163240.49 | 0.614529E+10 | 0.00 | 254339.12 | 0.129151E+09 | 0.00 | 528632.41 | 0.00 | 0.43 |
December | 1998.87 | 0.523523E+10 | 0.00 | 183177.86 | 0.152746E+09 | 0.00 | 224194.72 | 0.00 | 0.42 |
Annual Sum or Average | 1174751.26 | 0.826032E+11 | 0.00 | 1085500.85 | 0.198568E+10 | 0.00 | 4356145.55 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.505231E+10 | 0.00 | 0.00 | 0.119357E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 1009511.89 | 0.914736E+10 | 0.00 | 391909.16 | 0.197582E+09 | 0.00 | 3548028.72 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1023444.12 | 0.503873E+10 | 0.00 | 384878.22 | 0.120384E+09 | 0.00 | 3672347.54 | 0.00 | 0.42 |
February | 0.00 | 0.510576E+10 | 0.00 | 144070.82 | 0.135856E+09 | 0.00 | 42584.67 | 0.00 | 0.42 |
March | 0.00 | 0.626563E+10 | 0.00 | 0.00 | 0.136955E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
April | 0.00 | 0.746068E+10 | 0.00 | 0.00 | 0.191856E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.00 | 0.896933E+10 | 0.00 | 0.00 | 0.196880E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.913422E+10 | 0.00 | 0.00 | 0.177736E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.630906E+10 | 0.00 | 0.00 | 0.191632E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.827484E+10 | 0.00 | 0.00 | 0.174424E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.749562E+10 | 0.00 | 84282.30 | 0.193625E+09 | 0.00 | 15055.90 | 0.00 | 0.43 |
October | 0.00 | 0.703614E+10 | 0.00 | 25008.82 | 0.185315E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 167029.20 | 0.613062E+10 | 0.00 | 251783.90 | 0.128816E+09 | 0.00 | 531297.03 | 0.00 | 0.43 |
December | 2117.93 | 0.522099E+10 | 0.00 | 183550.20 | 0.152794E+09 | 0.00 | 228822.96 | 0.00 | 0.42 |
Annual Sum or Average | 1192591.25 | 0.824416E+11 | 0.00 | 1073574.26 | 0.198627E+10 | 0.00 | 4490108.10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.503873E+10 | 0.00 | 0.00 | 0.120384E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 1023444.12 | 0.913422E+10 | 0.00 | 384878.22 | 0.196880E+09 | 0.00 | 3672347.54 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 942968.44 | 0.504071E+10 | 0.00 | 367792.09 | 0.117949E+09 | 0.00 | 3923634.72 | 0.00 | 0.42 |
February | 0.00 | 0.511399E+10 | 0.00 | 136597.07 | 0.132675E+09 | 0.00 | 39937.54 | 0.00 | 0.42 |
March | 0.00 | 0.626841E+10 | 0.00 | 0.00 | 0.142325E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
April | 0.00 | 0.747358E+10 | 0.00 | 0.00 | 0.193759E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.00 | 0.898140E+10 | 0.00 | 0.00 | 0.198805E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.915065E+10 | 0.00 | 0.00 | 0.178968E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.631622E+10 | 0.00 | 0.00 | 0.194911E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.828098E+10 | 0.00 | 0.00 | 0.177257E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.750531E+10 | 0.00 | 81365.08 | 0.195283E+09 | 0.00 | 15070.91 | 0.00 | 0.43 |
October | 0.00 | 0.703196E+10 | 0.00 | 23950.15 | 0.188772E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 167854.35 | 0.612317E+10 | 0.00 | 238493.06 | 0.135520E+09 | 0.00 | 527761.81 | 0.00 | 0.43 |
December | 1336.56 | 0.521512E+10 | 0.00 | 176829.92 | 0.155634E+09 | 0.00 | 235588.23 | 0.00 | 0.42 |
Annual Sum or Average | 1112159.34 | 0.825015E+11 | 0.00 | 1025027.37 | 0.201186E+10 | 0.00 | 4741993.21 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.504071E+10 | 0.00 | 0.00 | 0.117949E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 942968.44 | 0.915065E+10 | 0.00 | 367792.09 | 0.198805E+09 | 0.00 | 3923634.72 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 691015.19 | 0.525142E+10 | 0.00 | 463549.10 | 0.107929E+09 | 0.00 | 4159856.69 | 0.00 | 0.42 |
February | 8351.73 | 0.535282E+10 | 0.00 | 258554.71 | 0.121156E+09 | 0.00 | 133619.79 | 0.00 | 0.42 |
March | 0.00 | 0.653565E+10 | 0.00 | 1297.23 | 0.110599E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
April | 0.00 | 0.779610E+10 | 0.00 | 0.00 | 0.166963E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.00 | 0.928558E+10 | 0.00 | 0.00 | 0.175820E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.949651E+10 | 0.00 | 0.00 | 0.152508E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.662826E+10 | 0.00 | 0.00 | 0.174743E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.860088E+10 | 0.00 | 0.00 | 0.154730E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.783628E+10 | 0.00 | 83646.97 | 0.179734E+09 | 0.00 | 23726.34 | 0.00 | 0.43 |
October | 0.00 | 0.728418E+10 | 0.00 | 33151.22 | 0.174379E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
November | 25257.53 | 0.638490E+10 | 0.00 | 278980.25 | 0.114296E+09 | 0.00 | 349392.12 | 0.00 | 0.43 |
December | 0.00 | 0.545098E+10 | 0.00 | 212292.47 | 0.131659E+09 | 0.00 | 430457.91 | 0.00 | 0.42 |
Annual Sum or Average | 724624.45 | 0.859036E+11 | 0.00 | 1331471.95 | 0.176452E+10 | 0.00 | 5097052.84 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.525142E+10 | 0.00 | 0.00 | 0.107929E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 691015.19 | 0.949651E+10 | 0.00 | 463549.10 | 0.179734E+09 | 0.00 | 4159856.69 | 0.00 | 0.43 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:34:30
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.242880E+12 | -0.389586E+11 | 0.00 | -0.887631E+11 | 0.275148E+12 |
February | 0.241545E+12 | -0.402461E+11 | 0.00 | -0.932853E+11 | 0.267824E+12 |
March | 0.316765E+12 | -0.485187E+11 | 0.00 | -0.119066E+12 | 0.313443E+12 |
April | 0.317260E+12 | -0.562102E+11 | 0.00 | -0.146353E+12 | 0.338062E+12 |
May | 0.317920E+12 | -0.660209E+11 | 0.00 | -0.176126E+12 | 0.382124E+12 |
June | 0.331277E+12 | -0.662636E+11 | 0.00 | -0.172442E+12 | 0.383715E+12 |
July | 0.275215E+12 | -0.481781E+11 | 0.00 | -0.125633E+12 | 0.306999E+12 |
August | 0.338680E+12 | -0.598473E+11 | 0.00 | -0.156265E+12 | 0.350464E+12 |
September | 0.267789E+12 | -0.556346E+11 | 0.00 | -0.145074E+12 | 0.330219E+12 |
October | 0.287976E+12 | -0.524594E+11 | 0.00 | -0.134786E+12 | 0.317751E+12 |
November | 0.236138E+12 | -0.454558E+11 | 0.00 | -0.113473E+12 | 0.292958E+12 |
December | 0.228713E+12 | -0.402308E+11 | 0.00 | -0.915870E+11 | 0.276927E+12 |
Annual Sum or Average | 0.340216E+13 | -0.618024E+12 | 0.00 | -0.156285E+13 | 0.383563E+13 |
Minimum of Months | 0.228713E+12 | -0.662636E+11 | 0.00 | -0.176126E+12 | 0.267824E+12 |
Maximum of Months | 0.338680E+12 | -0.389586E+11 | 0.00 | -0.887631E+11 | 0.383715E+12 |