Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:34
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 08:34:29
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1333.59 | 637.99 | 637.99 |
Net Site Energy | 1333.59 | 637.99 | 637.99 |
Total Source Energy | 3553.43 | 1699.95 | 1699.95 |
Net Source Energy | 3553.43 | 1699.95 | 1699.95 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 321.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 97.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 496.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 123.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 64.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1011.91 | 321.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 321.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 97.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 496.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 100.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 123.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 64.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 321.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 97.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 496.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 100.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 123.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 64.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 285.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 136.84 | 153.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 484.09 | 153.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 285.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 136.84 | 153.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 484.09 | 153.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1011.912 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1011.912 | 100.00 |
Total On-Site and Utility Electric Sources | 1011.912 | 100.00 |
Total Electricity End Uses | 1011.912 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.33 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1519.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:34 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 20.1123 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 23.1025 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 20.9200 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 20.9200 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 20.9200 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 13.4438 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 13.5625 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 17.2687 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 17.2687 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 20.1123 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 23.1025 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 20.9200 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 20.9200 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 20.9200 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 13.4438 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 13.5625 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 13.5625 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 13.5625 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 13.5625 | 6.19 | 4.3000 | |
Total | 2090.32 | 17.2687 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 17.2687 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 17.2687 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUN-14:00 | 21-DEC-17:00 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 222253.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 46744.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 30804.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10378.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3326.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 99313.67 | 222253.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 222253.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 46744.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 30804.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 10378.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 3326.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 348.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 310.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1573.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 319.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 391.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 204.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3204.73 | 348.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 166.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 148.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 752.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 152.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 187.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 97.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1533.13 | 166.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 166.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 148.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 752.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 152.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 187.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 97.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1533.13 | 166.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.53 |
SMSTORE1 DIRECT AIR | 1.37 |
SMSTORE2 DIRECT AIR | 1.43 |
SMSTORE3 DIRECT AIR | 1.42 |
SMSTORE4 DIRECT AIR | 1.42 |
LGSTORE2 DIRECT AIR | 2.38 |
SMSTORE5 DIRECT AIR | 1.22 |
SMSTORE6 DIRECT AIR | 1.21 |
SMSTORE7 DIRECT AIR | 1.20 |
SMSTORE8 DIRECT AIR | 1.29 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.53 | 2.53 | 2.53 | 2.53 | 2.53 | 2.53 | 1.00 | 1.00 | 2.53 |
PSZ-AC_2:2 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.00 | 1.00 | 1.37 |
PSZ-AC_3:3 | 1.43 | 1.43 | 1.43 | 1.43 | 1.43 | 1.43 | 1.00 | 1.000000 | 1.43 |
PSZ-AC_4:4 | 1.42 | 1.42 | 1.42 | 1.42 | 1.42 | 1.42 | 1.00 | 1.00 | 1.42 |
PSZ-AC_5:5 | 1.42 | 1.42 | 1.42 | 1.42 | 1.42 | 1.42 | 1.00 | 1.00 | 1.42 |
PSZ-AC_6:6 | 2.38 | 2.38 | 2.38 | 2.38 | 2.38 | 2.38 | 1.00 | 1.00 | 2.38 |
PSZ-AC_7:7 | 1.22 | 1.22 | 1.22 | 1.22 | 1.24 | 1.24 | 1.00 | 0.986962 | 1.24 |
PSZ-AC_8:8 | 1.21 | 1.21 | 1.21 | 1.21 | 1.23 | 1.23 | 1.00 | 0.987219 | 1.23 |
PSZ-AC_9:9 | 1.20 | 1.20 | 1.20 | 1.20 | 1.22 | 1.22 | 1.00 | 0.983867 | 1.22 |
PSZ-AC_10:10 | 1.29 | 1.29 | 1.29 | 1.29 | 1.29 | 1.29 | 1.00 | 1.00 | 1.29 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.53 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.37 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.43 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.42 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.42 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.38 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.24 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.23 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.22 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.29 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.53 | 2712.05 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.37 | 1512.57 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.43 | 1526.98 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.42 | 1517.01 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.42 | 1516.89 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.38 | 2551.93 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.24 | 1367.58 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.23 | 1359.49 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.22 | 1353.51 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.29 | 1423.51 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.53 | 2.53 | 2.53 | 1.67 | 41955.14 | 62797.89 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.37 | 1.37 | 1.37 | 0.901673 | 22615.00 | 33234.47 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.43 | 1.43 | 1.43 | 0.941836 | 23622.33 | 34363.73 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.42 | 1.42 | 1.42 | 0.935684 | 23468.01 | 34190.73 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.42 | 1.42 | 1.42 | 0.935611 | 23466.18 | 34188.68 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.38 | 2.38 | 2.38 | 1.57 | 39478.22 | 60020.47 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.24 | 1.24 | 1.24 | 0.815245 | 20447.27 | 30505.48 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.23 | 1.23 | 1.23 | 0.810421 | 20326.27 | 30377.45 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.22 | 1.22 | 1.22 | 0.806856 | 20236.86 | 30202.47 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.29 | 1.29 | 1.29 | 0.848582 | 21283.39 | 31742.33 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.53 | 1.27 | 1.69 | 41955.14 | 20977.57 | 0.800660 | 0.800660 |
PSZ-AC_2:2 COOLING COIL | 1.37 | 0.683086 | 0.910780 | 22615.00 | 11307.50 | 0.800660 | 0.800660 |
PSZ-AC_3:3 COOLING COIL | 1.43 | 0.713512 | 0.951347 | 23622.33 | 11811.17 | 0.800660 | 0.800660 |
PSZ-AC_4:4 COOLING COIL | 1.42 | 0.708851 | 0.945133 | 23468.01 | 11734.00 | 0.800660 | 0.800660 |
PSZ-AC_5:5 COOLING COIL | 1.42 | 0.708796 | 0.945060 | 23466.18 | 11733.09 | 0.800660 | 0.800660 |
PSZ-AC_6:6 COOLING COIL | 2.38 | 1.19 | 1.59 | 39478.22 | 19739.11 | 0.800660 | 0.800660 |
PSZ-AC_7:7 COOLING COIL | 1.24 | 0.617610 | 0.823480 | 20447.27 | 10223.64 | 0.800660 | 0.800660 |
PSZ-AC_8:8 COOLING COIL | 1.23 | 0.613955 | 0.818607 | 20326.27 | 10163.14 | 0.800660 | 0.800660 |
PSZ-AC_9:9 COOLING COIL | 1.22 | 0.611254 | 0.815007 | 20236.86 | 10118.43 | 0.800660 | 0.800660 |
PSZ-AC_10:10 COOLING COIL | 1.29 | 0.642865 | 0.857153 | 21283.39 | 10641.69 | 0.800660 | 0.800660 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 62797.89 |
PSZ-AC_2:2 HEATING COIL | 33234.47 |
PSZ-AC_3:3 HEATING COIL | 34363.73 |
PSZ-AC_4:4 HEATING COIL | 34190.73 |
PSZ-AC_5:5 HEATING COIL | 34188.68 |
PSZ-AC_6:6 HEATING COIL | 60020.47 |
PSZ-AC_7:7 HEATING COIL | 30505.48 |
PSZ-AC_8:8 HEATING COIL | 30377.45 |
PSZ-AC_9:9 HEATING COIL | 30202.47 |
PSZ-AC_10:10 HEATING COIL | 31742.33 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 20.112 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 24.412 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 23.103 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 27.403 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 20.920 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.220 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 20.920 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.220 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 20.920 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.220 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 13.444 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.744 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 13.563 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.863 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 4694.002 | 13.474 | 83.448 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4694.002 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 2312.850 | 6.639 | 41.117 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2312.850 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2367.672 | 13.592 | 84.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2367.672 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1656.630 | 9.510 | 58.904 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1656.630 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1281.630 | 7.358 | 45.570 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1281.630 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1281.630 | 7.358 | 45.570 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1281.630 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1281.630 | 7.358 | 45.570 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1281.630 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 4683.651 | 13.444 | 83.264 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4683.651 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2362.497 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2362.497 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5398 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1408 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2031 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.619 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.024 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.847 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8391315 | 2.8391315 | 2.8391315 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.34329049E-12 | 0.74065570E-15 | -0.11060681E-12 | 0.10726285E-15 |
23 | 6 | 0.31458623E-07 | 0.15582808E-09 | 0.71832143E-08 | -0.15023289E-12 |
24 | 5 | -0.20415818E-03 | 0.13111101E-05 | -0.10480723E-03 | 0.70917048E-08 |
25 | 4 | 0.30843928 | 0.62847427E-03 | 0.10555000 | -0.35885187E-04 |
26 | 3 | -7.5886440 | 0.19208290E-01 | -2.4345797 | 0.30589548E-01 |
27 | 2 | 41.933758 | 0.67466625E-01 | 15.656649 | -0.34517733 |
28 | 1 | -81.359657 | 0.30121645E-01 | -29.492494 | 1.0959638 |
29 | 0 | 46.824334 | 0.59962785E-03 | 16.283006 | |
30 | 7 | -0.30155247E-08 | -0.19705740E-14 | 0.18469307E-14 | -0.46079768E-16 |
31 | 6 | 0.40551627E-05 | 0.26926011E-08 | 0.31944497E-02 | -0.26797721E-04 |
32 | 5 | -0.28496186E-03 | 0.15923452E-05 | -0.22398486 | 0.19584477E-02 |
33 | 4 | 0.65115693E-02 | 0.72427529E-04 | 4.8338806 | -0.45306652E-01 |
34 | 3 | -0.57046066E-01 | 0.57554694E-03 | -38.045903 | 0.39892442 |
35 | 2 | 0.20237164 | 0.95689144E-03 | 116.53161 | -1.4185768 |
36 | 1 | -0.29197338 | 0.29127682E-03 | -143.93536 | 2.0495010 |
37 | 0 | 0.14232195 | 0.70641069E-05 | 60.838472 | |
38 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
39 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
40 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
41 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
42 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
43 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
44 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
45 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
46 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
47 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
48 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
49 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
50 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
51 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
52 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
53 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
54 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521549E-14 | -0.37274185E-16 |
55 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
56 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
57 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
58 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
59 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
60 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
61 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
62 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521548E-14 | -0.37274183E-16 |
63 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
64 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
65 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
66 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
67 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
68 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
69 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
70 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
71 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
72 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
73 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
74 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
75 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
76 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
77 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
78 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274181E-16 |
79 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
80 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
81 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
82 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
83 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
84 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
85 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
86 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
87 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
88 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
89 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
90 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
91 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
92 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
93 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
94 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
95 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
96 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
97 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
98 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
99 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
100 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
101 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
102 | 7 | -0.20778300E-08 | -0.65167512E-15 | 0.79548166E-14 | -0.12010680E-15 |
103 | 6 | 0.57088823E-05 | 0.38884884E-08 | 0.31895855E-02 | -0.26756916E-04 |
104 | 5 | -0.40892418E-03 | 0.23023551E-05 | -0.22370841 | 0.19560076E-02 |
105 | 4 | 0.93961169E-02 | 0.10478953E-03 | 4.8292766 | -0.45262394E-01 |
106 | 3 | -0.82481111E-01 | 0.83319714E-03 | -38.019897 | 0.39863696 |
107 | 2 | 0.29283299 | 0.13859693E-02 | 116.48099 | -1.4178998 |
108 | 1 | -0.42263540 | 0.42218679E-03 | -143.90557 | 2.0490113 |
109 | 0 | 0.20604930 | 0.10232106E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 35 | 1 | VerySmooth | 2.375 | 2.375 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.05070E-002 | 0.31435 | 0.47518 | 0.47518 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12234 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 23300.37424 | 27960.44909 | 2.11209 | 2.53451 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90000 | 5.47527E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 24963.95573 | 29956.74687 | 1.32564 | 1.59077 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 12559.62821 | 15071.55385 | 1.13848 | 1.36617 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.47489E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 11942.02055 | 14330.42467 | 0.63415 | 0.76098 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 13412.78447 | 16095.34137 | 1.18919 | 1.42702 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.76000 | 5.46288E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 12096.47304 | 14515.76764 | 0.64235 | 0.77082 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 13327.17280 | 15992.60736 | 1.18142 | 1.41770 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.76000 | 5.46288E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 12187.80192 | 14625.36231 | 0.64720 | 0.77664 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 13325.74623 | 15990.89548 | 1.18133 | 1.41759 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.76000 | 5.46288E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 12339.97561 | 14807.97073 | 0.65528 | 0.78634 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 21924.44698 | 26309.33638 | 1.98740 | 2.38488 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 23721.30530 | 28465.56636 | 1.25968 | 1.51162 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11489.15972 | 13786.99166 | 1.01593 | 1.21911 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 28.27600 | 5.46666E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 12674.00182 | 15208.80218 | 0.67302 | 0.80763 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11425.12099 | 13710.14518 | 1.01018 | 1.21222 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 28.27600 | 5.46666E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 12659.74562 | 15191.69474 | 0.67227 | 0.80672 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 11337.40591 | 13604.88710 | 1.00232 | 1.20279 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 28.27600 | 5.46666E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 12866.45797 | 15439.74957 | 0.68324 | 0.81989 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 11819.71143 | 14183.65372 | 1.07144 | 1.28573 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 33.16000 | 5.47412E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 15339.15187 | 18406.98224 | 0.81452 | 0.97743 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 31649.60 | 2.53451 | 2.53451 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 45284.71 | 1.59077 | 1.59077 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 16891.47 | 1.36617 | 1.36617 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 22003.86 | 0.76098 | 0.76098 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 16847.94 | 1.42702 | 1.42702 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 22186.51 | 0.77082 | 0.77082 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 16884.66 | 1.41770 | 1.41770 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 22294.51 | 0.77664 | 0.77664 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 16759.37 | 1.41759 | 1.41759 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 22474.45 | 0.78634 | 0.78634 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 29979.16 | 2.38488 | 2.38488 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 43815.40 | 1.51162 | 1.51162 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 15452.96 | 1.23522 | 1.23522 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 22869.45 | 0.80763 | 0.80763 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 15373.40 | 1.22791 | 1.22791 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 22852.60 | 0.80672 | 0.80672 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 15313.05 | 1.22251 | 1.22251 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 23097.04 | 0.81989 | 0.81989 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 15888.90 | 1.28573 | 1.28573 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 26020.92 | 0.97743 | 0.97743 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.53451 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.36617 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.42702 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.41770 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.41759 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.38488 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.21911 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.21222 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.20279 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.28573 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.53451 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.53451 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.53451 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.53451 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.53451 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.53451 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.36617 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.36617 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.36617 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.36617 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.36617 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.36617 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.42702 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.42702 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.42702 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.42702 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.42702 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.42702 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.41770 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.41770 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.41770 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.41770 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.41770 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.41770 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.41759 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.41759 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.41759 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.41759 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.41759 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.41759 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.38488 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.38488 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.38488 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.38488 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.38488 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.38488 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.21911 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.21911 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.21911 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.21911 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.23522 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.23522 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.98696 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.21222 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.21222 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.21222 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.21222 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.22791 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.22791 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.98722 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.20279 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.20279 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.20279 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20279 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.22251 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.22251 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.98387 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.28573 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.28573 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.28573 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.28573 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.28573 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.28573 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.53451 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.36617 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.42702 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.41770 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.41759 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.38488 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.23522 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.22791 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.22251 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.28573 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.53451 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.53451 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2712.04525 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.53451 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.53451 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.53451 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.67278 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.53451 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.26725 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.68967 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 41955.14000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20977.57000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 41955.14000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 62797.88958 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 62797.88958 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.36617 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.36617 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1512.56912 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.36617 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.36617 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.36617 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.90167 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.36617 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68309 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.91078 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22615.00000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11307.50000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22615.00000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33234.47306 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 33234.47306 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.42702 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.42702 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1526.98402 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.42702 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.42702 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.42702 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.94184 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.42702 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.71351 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.95135 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23622.33000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11811.16500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23622.33000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34363.73184 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 34363.73184 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.41770 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.41770 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1517.00853 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.41770 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.41770 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.41770 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.93568 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.41770 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.70885 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.94513 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23468.01000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11734.00500 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23468.01000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34190.73223 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 34190.73223 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.41759 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.41759 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1516.89020 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.41759 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.41759 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.41759 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.93561 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.41759 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.70880 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.94506 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23466.18000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11733.09000 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23466.18000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34188.67659 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 34188.67659 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.38488 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.38488 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2551.93372 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.38488 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.38488 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.38488 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.57402 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.38488 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.19244 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.58992 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 39478.22000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19739.11000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 39478.22000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 60020.47478 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 60020.47478 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.23522 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.23522 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1367.58392 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.23522 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.23522 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.23522 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.81524 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.23522 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61761 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.82348 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20447.27000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10223.63500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20447.27000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30505.48007 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 30505.48007 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.22791 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.22791 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1359.49126 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.22791 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.22791 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.22791 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.81042 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.22791 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61395 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.81861 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20326.27000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10163.13500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20326.27000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30377.45161 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 30377.45161 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.22251 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.22251 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1353.51108 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.22251 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.22251 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.22251 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.80686 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.22251 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61125 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.81501 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20236.86000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10118.43000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20236.86000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30202.46728 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 30202.46728 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.28573 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.28573 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1423.50701 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.28573 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.28573 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.28573 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.84858 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.28573 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64286 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.85715 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21283.39000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10641.69500 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21283.39000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31742.33280 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 31742.33280 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 39968.8 | 10.95 | 10.95 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 21544.3 | 11.11 | 11.11 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 22504.0 | 11.11 | 11.11 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 22356.9 | 11.11 | 11.11 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 22355.2 | 11.11 | 11.11 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 37609.2 | 11.11 | 11.11 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 19479.2 | 11.11 | 11.11 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 19363.9 | 11.11 | 11.11 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 19278.8 | 11.11 | 11.11 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 20275.8 | 11.11 | 11.11 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.141 | 0.136 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.418_SHGC_0.4 | N/A | 2.375 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.203 | 0.194 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 3.2117516750E-002 | 0.1915620740 | Pass | Pass | 0.2114830698 | 0.6832735549 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 6.8788676592E-002 | 0.1201827083 | Pass | Pass | 6.2897246977E-002 | 0.1800407547 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 2.8754682704E-002 | 0.1427190223 | Pass | Pass | 0.1447835712 | 0.5016778420 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.3816400113E-002 | 0.1843920333 | Pass | Pass | 0.3123805021 | 1.7257107900 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.7528210207E-002 | 0.2079610448 | Pass | Pass | 0.1803250262 | 0.5381894388 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.0280056451E-002 | 0.1899996901 | Pass | Pass | 0.3493523793 | 1.2913769139 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.1035903077E-002 | 0.1975936665 | Pass | Pass | 0.2540031248 | 0.9249021030 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.3004525915E-002 | 0.2129947745 | Pass | Pass | 0.2900481929 | 1.7584660473 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 5.2283759845E-002 | 0.2510495948 | Pass | Pass | 0.3914566427 | 1.3415447633 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 7.3738144002E-002 | 0.3674111374 | Pass | Pass | 0.1001619544 | 0.4936872446 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4702.65 | 180.20 | 0.00 | 486.49 | 531.97 | 5901.32 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.197 | 0.203 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.375 | 0.401 | 0.442 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.375 | 0.401 | 0.442 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.375 | 0.401 | 0.442 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.375 | 0.401 | 0.442 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.375 | 0.401 | 0.442 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.375 | 0.401 | 0.442 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.375 | 0.401 | 0.442 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.375 | 0.401 | 0.442 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.375 | 0.401 | 0.442 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.375 | 0.401 | 0.442 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.375 | 0.401 | 0.442 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.375 | 0.401 | 0.442 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.418_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.375 | 0.401 | 0.442 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.375 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.375 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.992 | 2.839 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.992 | 2.839 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 13.4735 | 348.39 | 4694.00 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 83.90 | 0.0000 | Y | 73.93 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 6.6387 | 348.39 | 2312.85 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 42.32 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 13.5922 | 174.19 | 2367.67 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 85.39 | 0.0000 | Y | 37.95 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 9.5103 | 174.19 | 1656.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 30.31 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 30.25 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 7.3575 | 174.19 | 1281.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.76 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 30.25 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 7.3575 | 174.19 | 1281.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.76 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 30.25 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 7.3575 | 174.19 | 1281.63 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 18.76 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 13.4438 | 348.39 | 4683.65 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 54.16 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 13.5625 | 174.19 | 2362.50 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 27.81 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 8.6344 | 4180.64 | 36097.17 | 496.92 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 458.42 | AstronomicalClock | - | 42.26 | 42.26 | 3.64 | |
EXTERIOR_LIGHTS_B | 7264.83 | AstronomicalClock | - | 83.67 | 71.25 | 97.16 | |
Exterior Lighting Total | 7723.25 | 100.80 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 41955.14 | 33591.80 | 8363.34 | 0.80 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22615.00 | 18106.93 | 4508.07 | 0.80 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23622.33 | 18913.45 | 4708.88 | 0.80 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23468.01 | 18789.90 | 4678.11 | 0.80 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23466.18 | 18788.43 | 4677.75 | 0.80 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 39478.22 | 31608.63 | 7869.59 | 0.80 | 3.80 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20447.27 | 16371.31 | 4075.96 | 0.80 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20326.27 | 16274.43 | 4051.84 | 0.80 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20236.86 | 16202.84 | 4034.02 | 0.80 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21283.39 | 17040.76 | 4242.63 | 0.80 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 39968.8 | 10.95 | 10.95 | ||||
PSZ-AC_2:2 COOLING COIL | 21544.3 | 11.11 | 11.11 | ||||
PSZ-AC_3:3 COOLING COIL | 22504.0 | 11.11 | 11.11 | ||||
PSZ-AC_4:4 COOLING COIL | 22356.9 | 11.11 | 11.11 | ||||
PSZ-AC_5:5 COOLING COIL | 22355.2 | 11.11 | 11.11 | ||||
PSZ-AC_6:6 COOLING COIL | 37609.2 | 11.11 | 11.11 | ||||
PSZ-AC_7:7 COOLING COIL | 19479.2 | 11.11 | 11.11 | ||||
PSZ-AC_8:8 COOLING COIL | 19363.9 | 11.11 | 11.11 | ||||
PSZ-AC_9:9 COOLING COIL | 19278.8 | 11.11 | 11.11 | ||||
PSZ-AC_10:10 COOLING COIL | 20275.8 | 11.11 | 11.11 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 62797.89 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 33234.47 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 34363.73 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 34190.73 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 34188.68 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 60020.47 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 30505.48 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 30377.45 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 30202.47 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 31742.33 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.53 | 2712.05 | 1070.05 | 1.00 | 1.28 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.37 | 1512.57 | 1107.16 | 1.00 | 1.33 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.43 | 1526.98 | 1070.05 | 1.00 | 1.37 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.42 | 1517.01 | 1070.05 | 1.00 | 1.37 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.42 | 1516.89 | 1070.05 | 1.00 | 1.37 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.38 | 2551.93 | 1070.05 | 1.00 | 1.29 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.24 | 1367.58 | 1107.16 | 1.00 | 1.35 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.23 | 1359.49 | 1107.16 | 1.00 | 1.36 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.22 | 1353.51 | 1107.16 | 1.00 | 1.36 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.29 | 1423.51 | 1107.16 | 1.00 | 1.35 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 23300.37 | 27960.45 | 80.26 | 2.112 | 2.535 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 23.89 | 23.89 | 0.00731 | 33.90 | 0.00548 | 0.411 | 0.00 |
SMSTORE1 | 12559.63 | 15071.55 | 86.52 | 1.138 | 1.366 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00728 | 33.65 | 0.00547 | 0.206 | 0.00 |
SMSTORE2 | 13412.78 | 16095.34 | 92.40 | 1.189 | 1.427 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00755 | 25.76 | 0.00546 | 0.206 | 0.00 |
SMSTORE3 | 13327.17 | 15992.61 | 91.81 | 1.181 | 1.418 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00755 | 25.76 | 0.00546 | 0.206 | 0.00 |
SMSTORE4 | 13325.75 | 15990.90 | 91.80 | 1.181 | 1.418 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00756 | 25.76 | 0.00546 | 0.206 | 0.00 |
LGSTORE2 | 21924.45 | 26309.34 | 75.52 | 1.987 | 2.385 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.89 | 0.00734 | 33.53 | 0.00547 | 0.411 | 0.00 |
SMSTORE5 | 11489.16 | 13786.99 | 79.15 | 1.016 | 1.219 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00760 | 28.28 | 0.00547 | 0.206 | 0.00 |
SMSTORE6 | 11425.12 | 13710.15 | 78.71 | 1.010 | 1.212 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00761 | 28.28 | 0.00547 | 0.206 | 0.00 |
SMSTORE7 | 11337.41 | 13604.89 | 78.10 | 1.002 | 1.203 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00763 | 28.28 | 0.00547 | 0.206 | 0.00 |
SMSTORE8 | 11819.71 | 14183.65 | 81.42 | 1.071 | 1.286 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 23.89 | 23.89 | 0.00727 | 33.16 | 0.00547 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 24963.96 | 29956.75 | 85.99 | 1.326 | 1.591 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00674 | -17.90 | 0.00096 | 0.411 | 0.00 |
SMSTORE1 | 11942.02 | 14330.42 | 82.27 | 0.634 | 0.761 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00663 | -17.90 | 0.00096 | 0.206 | 0.00 |
SMSTORE2 | 12096.47 | 14515.77 | 83.33 | 0.642 | 0.771 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00664 | -17.90 | 0.00096 | 0.206 | 0.00 |
SMSTORE3 | 12187.80 | 14625.36 | 83.96 | 0.647 | 0.777 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00665 | -17.90 | 0.00096 | 0.206 | 0.00 |
SMSTORE4 | 12339.98 | 14807.97 | 85.01 | 0.655 | 0.786 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00666 | -17.90 | 0.00096 | 0.206 | 0.00 |
LGSTORE2 | 23721.31 | 28465.57 | 81.71 | 1.260 | 1.512 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00674 | -17.90 | 0.00096 | 0.411 | 0.00 |
SMSTORE5 | 12674.00 | 15208.80 | 87.31 | 0.673 | 0.808 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00669 | -17.90 | 0.00096 | 0.206 | 0.00 |
SMSTORE6 | 12659.75 | 15191.69 | 87.21 | 0.672 | 0.807 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00669 | -17.90 | 0.00096 | 0.206 | 0.00 |
SMSTORE7 | 12866.46 | 15439.75 | 88.64 | 0.683 | 0.820 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00670 | -17.90 | 0.00096 | 0.206 | 0.00 |
SMSTORE8 | 15339.15 | 18406.98 | 105.67 | 0.815 | 0.977 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00678 | -17.90 | 0.00096 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.53 | 2.53 | 1.59 | 1.59 | 2.5345 | 2.5345 | 2.5345 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.37 | 1.37 | 0.76 | 0.76 | 1.3662 | 1.3662 | 1.3662 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.43 | 1.43 | 0.77 | 0.77 | 1.4270 | 1.4270 | 1.4270 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.42 | 1.42 | 0.78 | 0.78 | 1.4177 | 1.4177 | 1.4177 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.42 | 1.42 | 0.79 | 0.79 | 1.4176 | 1.4176 | 1.4176 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.38 | 2.38 | 1.51 | 1.51 | 2.3849 | 2.3849 | 2.3849 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.24 | 1.24 | 0.81 | 0.81 | 1.2352 | 1.2191 | 1.2352 | 0.9870 | 1.0000 |
PSZ-AC_8:8 | 1.23 | 1.23 | 0.81 | 0.81 | 1.2279 | 1.2122 | 1.2279 | 0.9872 | 1.0000 |
PSZ-AC_9:9 | 1.22 | 1.22 | 0.82 | 0.82 | 1.2225 | 1.2028 | 1.2225 | 0.9839 | 1.0000 |
PSZ-AC_10:10 | 1.29 | 1.29 | 0.98 | 0.98 | 1.2857 | 1.2857 | 1.2857 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 41955.140 | 33591.802 | 2.534510 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 20977.57 | 20954.05 | 1.689673 | 26.59 | 13.90 | 0.00700936 | 12.80 | 8.76 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | 24.3526 | 23.89 | 0.00730669 | 32.2022 | 23300.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 62797.890 | 62797.890 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 62797.89 | 62797.89 | 2.534510 | 14.77 | 8.36 | 0.00579852 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 16.2350 | 21.10 | 0.00673723 | 35.1985 | 24963.96 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 22615.000 | 18106.926 | 1.366170 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 11307.50 | 11298.15 | 0.910780 | 26.51 | 13.87 | 0.00700688 | 12.80 | 8.76 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | 22.5894 | 23.89 | 0.00727866 | 32.0798 | 12550.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 33234.473 | 33234.473 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 33234.47 | 33234.47 | 1.366172 | 15.23 | 8.53 | 0.00577767 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 15.0596 | 21.10 | 0.00663267 | 34.6581 | 11942.02 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 23622.330 | 18913.455 | 1.427020 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11811.17 | 11801.61 | 0.951347 | 26.48 | 13.86 | 0.00700672 | 12.80 | 8.76 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | 21.6261 | 23.89 | 0.00727941 | 32.0831 | 12513.84 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 34363.732 | 34363.732 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 34363.73 | 34363.73 | 1.427025 | 15.48 | 8.68 | 0.00582450 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 14.4174 | 21.10 | 0.00664478 | 34.7207 | 12096.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 23468.010 | 18789.897 | 1.417700 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11734.00 | 11724.29 | 0.945133 | 26.47 | 13.86 | 0.00700687 | 12.80 | 8.76 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | 21.7683 | 23.89 | 0.00727880 | 32.0805 | 12544.84 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 34190.732 | 34190.732 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 34190.73 | 34190.73 | 1.417702 | 15.45 | 8.66 | 0.00582512 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 14.5122 | 21.10 | 0.00665181 | 34.7571 | 12187.80 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 23466.180 | 18788.432 | 1.417590 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11733.09 | 11724.11 | 0.945060 | 26.49 | 13.86 | 0.00700636 | 12.80 | 8.76 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | 21.7700 | 23.89 | 0.00728091 | 32.0897 | 12439.08 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 34188.677 | 34188.677 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 34188.68 | 34188.68 | 1.417592 | 15.45 | 8.67 | 0.00583501 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 14.5133 | 21.10 | 0.00666346 | 34.8174 | 12339.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 39478.220 | 31608.632 | 2.384880 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 19739.11 | 19704.39 | 1.589920 | 26.69 | 13.94 | 0.00701477 | 12.80 | 8.76 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | 25.8805 | 23.89 | 0.00733639 | 32.3316 | 21890.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 60020.475 | 60020.475 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 60020.47 | 60020.47 | 2.384879 | 14.38 | 8.14 | 0.00574344 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 17.2537 | 21.10 | 0.00674184 | 35.2216 | 23721.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 20447.270 | 16371.311 | 1.235220 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 10223.64 | 10223.64 | 0.823480 | 26.67 | 13.92 | 0.00699976 | 12.80 | 8.76 | 0.00699976 | 33.90 | 0.00547527 | 15.07 | 24.9841 | 23.89 | 0.00730506 | 32.1948 | 11336.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 30505.480 | 30505.480 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30505.48 | 30505.48 | 1.235219 | 14.61 | 8.22 | 0.00573339 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 16.6561 | 21.10 | 0.00668830 | 34.9458 | 12674.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 20326.270 | 16274.431 | 1.227910 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 10163.14 | 10163.13 | 0.818607 | 26.68 | 13.92 | 0.00699928 | 12.80 | 8.76 | 0.00699928 | 33.90 | 0.00547527 | 15.07 | 25.1329 | 23.89 | 0.00730666 | 32.2018 | 11269.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 30377.452 | 30377.452 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30377.45 | 30377.45 | 1.227910 | 14.57 | 8.20 | 0.00572685 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 16.7553 | 21.10 | 0.00668727 | 34.9404 | 12659.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 20236.860 | 16202.844 | 1.222510 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 10118.43 | 10118.43 | 0.815007 | 26.69 | 13.92 | 0.00699891 | 12.80 | 8.76 | 0.00699891 | 33.90 | 0.00547527 | 15.07 | 25.2439 | 23.89 | 0.00730789 | 32.2072 | 11218.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 30202.467 | 30202.467 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30202.47 | 30202.47 | 1.222509 | 14.54 | 8.20 | 0.00573495 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 16.8293 | 21.10 | 0.00670211 | 35.0172 | 12866.46 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 21283.390 | 17040.759 | 1.285730 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 10641.69 | 10641.69 | 0.857153 | 26.53 | 13.86 | 0.00698506 | 12.80 | 8.74 | 0.00698506 | 33.41 | 0.00547451 | 14.91 | 24.0026 | 23.89 | 0.00727374 | 32.0582 | 11788.44 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 31742.333 | 31742.333 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 31742.33 | 31742.33 | 1.285730 | 14.86 | 8.45 | 0.00584721 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 16.0018 | 21.10 | 0.00677914 | 35.4167 | 15339.15 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 41955.140 | 33591.802 | 2.534510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8701 | 1004.8586 | 0.9774 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.534510 | 2.47732516 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | Sensible | 20977.57 | 20954.05 | 1.0000 | 1.65155027 | 1.689673 | 26.59 | 13.90 | 0.00700936 | 44594.6 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20977.57 | 33.90 | 0.00547527 | 15.07 | 0.41147883 | 24.3526 | 23.89 | 0.00730669 | 23.89 | 0.00730669 | 32.2022 | 23300.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 62797.890 | 62797.890 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.534510 | 2.47732516 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 62797.89 | 62797.89 | 1.0000 | 2.47732516 | 2.534510 | 14.77 | 8.36 | 0.00579852 | 29506.0 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 62797.89 | -17.90 | 0.00095524 | -17.90 | 0.41147883 | 16.2350 | 21.11 | 0.00673723 | 21.10 | 0.00673723 | 35.1985 | 24963.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22615.000 | 18106.926 | 1.366170 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8654 | 1004.8586 | 0.9774 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.366172 | 1.33534777 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 11307.50 | 11298.15 | 1.0000 | 0.89023063 | 0.910780 | 26.51 | 13.87 | 0.00700688 | 44507.7 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11307.50 | 33.90 | 0.00547527 | 15.07 | 0.20573941 | 22.5894 | 23.89 | 0.00727866 | 23.89 | 0.00727866 | 32.0798 | 12550.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33234.473 | 33234.473 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.366172 | 1.33534777 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 33234.47 | 33234.47 | 1.0000 | 1.33534777 | 1.366172 | 15.23 | 8.53 | 0.00577767 | 29919.0 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33234.47 | -17.90 | 0.00095524 | -17.90 | 0.20573941 | 15.0596 | 21.11 | 0.00663267 | 21.10 | 0.00663267 | 34.6581 | 11942.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23622.330 | 18913.455 | 1.427020 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8651 | 1004.8586 | 0.9774 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.427025 | 1.39482774 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 11811.17 | 11801.61 | 1.0000 | 0.92988201 | 0.951347 | 26.48 | 13.86 | 0.00700672 | 44473.8 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11811.17 | 33.90 | 0.00547527 | 15.07 | 0.20573941 | 21.6261 | 23.89 | 0.00727941 | 23.89 | 0.00727941 | 32.0831 | 12513.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34363.732 | 34363.732 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.427025 | 1.39482774 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 34363.73 | 34363.73 | 1.0000 | 1.39482774 | 1.427025 | 15.48 | 8.68 | 0.00582450 | 30291.9 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34363.73 | -17.90 | 0.00095524 | -17.90 | 0.20573941 | 14.4174 | 21.11 | 0.00664478 | 21.10 | 0.00664478 | 34.7207 | 12096.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23468.010 | 18789.897 | 1.417700 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8654 | 1004.8586 | 0.9774 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.417702 | 1.38571560 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 11734.00 | 11724.29 | 1.0000 | 0.92380887 | 0.945133 | 26.47 | 13.86 | 0.00700687 | 44470.4 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11734.00 | 33.90 | 0.00547527 | 15.07 | 0.20573941 | 21.7683 | 23.89 | 0.00727880 | 23.89 | 0.00727880 | 32.0805 | 12544.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34190.732 | 34190.732 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.417702 | 1.38571560 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 34190.73 | 34190.73 | 1.0000 | 1.38571560 | 1.417702 | 15.45 | 8.66 | 0.00582512 | 30255.9 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34190.73 | -17.90 | 0.00095524 | -17.90 | 0.20573941 | 14.5122 | 21.11 | 0.00665181 | 21.10 | 0.00665181 | 34.7571 | 12187.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23466.180 | 18788.432 | 1.417590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8645 | 1004.8586 | 0.9774 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.417592 | 1.38560751 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 11733.09 | 11724.11 | 1.0000 | 0.92373719 | 0.945060 | 26.49 | 13.86 | 0.00700636 | 44482.1 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11733.09 | 33.90 | 0.00547527 | 15.07 | 0.20573941 | 21.7700 | 23.89 | 0.00728091 | 23.89 | 0.00728091 | 32.0897 | 12439.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34188.677 | 34188.677 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.417592 | 1.38560751 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 34188.68 | 34188.68 | 1.0000 | 1.38560751 | 1.417592 | 15.45 | 8.67 | 0.00583501 | 30280.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34188.68 | -17.90 | 0.00095524 | -17.90 | 0.20573941 | 14.5133 | 21.11 | 0.00666346 | 21.10 | 0.00666346 | 34.8174 | 12339.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 39478.220 | 31608.632 | 2.384880 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8801 | 1004.8586 | 0.9774 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.384879 | 2.33107085 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 19739.11 | 19704.39 | 1.0000 | 1.55404761 | 1.589920 | 26.69 | 13.94 | 0.00701477 | 44714.9 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19739.11 | 33.90 | 0.00547527 | 15.07 | 0.41147883 | 25.8805 | 23.89 | 0.00733639 | 23.89 | 0.00733639 | 32.3316 | 21890.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 60020.475 | 60020.475 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.384879 | 2.33107085 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 60020.47 | 60020.47 | 1.0000 | 2.33107085 | 2.384879 | 14.38 | 8.14 | 0.00574344 | 28963.5 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 60020.47 | -17.90 | 0.00095524 | -17.90 | 0.41147883 | 17.2537 | 21.11 | 0.00674184 | 21.10 | 0.00674184 | 35.2216 | 23721.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20447.270 | 16371.311 | 1.235220 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8522 | 1004.8586 | 0.9774 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.235219 | 1.20734987 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 10223.64 | 10223.64 | 1.0000 | 0.80490032 | 0.823480 | 26.67 | 13.92 | 0.00699976 | 44654.0 | 12.80 | 8.76 | 0.00699976 | 30534.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10223.64 | 33.90 | 0.00547527 | 15.07 | 0.20573941 | 24.9841 | 23.89 | 0.00730506 | 23.89 | 0.00730506 | 32.1948 | 11336.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30505.480 | 30505.480 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.235219 | 1.20734987 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30505.48 | 30505.48 | 1.0000 | 1.20734987 | 1.235219 | 14.61 | 8.22 | 0.00573339 | 29174.6 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30505.48 | -17.90 | 0.00095524 | -17.90 | 0.20573941 | 16.6561 | 21.11 | 0.00668830 | 21.10 | 0.00668830 | 34.9458 | 12674.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20326.270 | 16274.431 | 1.227910 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8513 | 1004.8586 | 0.9774 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.227910 | 1.20020539 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 10163.14 | 10163.13 | 1.0000 | 0.80013695 | 0.818607 | 26.68 | 13.92 | 0.00699928 | 44662.9 | 12.80 | 8.76 | 0.00699928 | 30533.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10163.14 | 33.90 | 0.00547527 | 15.07 | 0.20573941 | 25.1329 | 23.89 | 0.00730666 | 23.89 | 0.00730666 | 32.2018 | 11269.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30377.452 | 30377.452 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.227910 | 1.20020539 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30377.45 | 30377.45 | 1.0000 | 1.20020539 | 1.227910 | 14.57 | 8.20 | 0.00572685 | 29118.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30377.45 | -17.90 | 0.00095524 | -17.90 | 0.20573941 | 16.7553 | 21.11 | 0.00668727 | 21.10 | 0.00668727 | 34.9404 | 12659.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20236.860 | 16202.844 | 1.222510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8506 | 1004.8586 | 0.9774 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.222509 | 1.19492589 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 10118.43 | 10118.43 | 1.0000 | 0.79661817 | 0.815007 | 26.69 | 13.92 | 0.00699891 | 44669.7 | 12.80 | 8.76 | 0.00699891 | 30532.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10118.43 | 33.90 | 0.00547527 | 15.07 | 0.20573941 | 25.2439 | 23.89 | 0.00730789 | 23.89 | 0.00730789 | 32.2072 | 11218.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30202.467 | 30202.467 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.222509 | 1.19492589 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30202.47 | 30202.47 | 1.0000 | 1.19492589 | 1.222509 | 14.54 | 8.20 | 0.00573495 | 29110.0 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30202.47 | -17.90 | 0.00095524 | -17.90 | 0.20573941 | 16.8293 | 21.11 | 0.00670211 | 21.10 | 0.00670211 | 35.0172 | 12866.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21283.390 | 17040.759 | 1.285730 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8249 | 1004.8586 | 0.9774 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.285730 | 1.25672069 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 10641.69 | 10641.69 | 1.0000 | 0.83781391 | 0.857153 | 26.53 | 13.86 | 0.00698506 | 44470.7 | 12.80 | 8.74 | 0.00698506 | 30497.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10641.69 | 33.41 | 0.00547451 | 14.91 | 0.20573941 | 24.0026 | 23.89 | 0.00727374 | 23.89 | 0.00727374 | 32.0582 | 11788.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31742.333 | 31742.333 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.285730 | 1.25672069 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 31742.33 | 31742.33 | 1.0000 | 1.25672069 | 1.285730 | 14.86 | 8.45 | 0.00584721 | 29721.1 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31742.33 | -17.90 | 0.00095524 | -17.90 | 0.20573941 | 16.0018 | 21.11 | 0.00677914 | 21.10 | 0.00677914 | 35.4167 | 15339.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.53 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.37 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.43 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.42 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.42 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.38 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.24 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.23 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.22 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.29 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 1826.33 | 3502.50 | 768.67 |
SMSTORE1 | 1315.17 | 3226.33 | 277.00 |
SMSTORE2 | 1228.00 | 2441.50 | 353.50 |
SMSTORE3 | 1264.83 | 2483.33 | 398.00 |
SMSTORE4 | 1270.67 | 2561.33 | 451.33 |
LGSTORE2 | 1226.17 | 2509.33 | 577.83 |
SMSTORE5 | 1149.50 | 2575.50 | 596.50 |
SMSTORE6 | 1163.67 | 2602.50 | 628.50 |
SMSTORE7 | 1250.17 | 2661.50 | 736.67 |
SMSTORE8 | 1701.00 | 2737.00 | 1156.17 |
Facility | 2713.00 | 4053.83 | 1519.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 6.00 | 0.00 | 0.33 | 0.00 |
SMSTORE1 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 1.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 2.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 20.67 | 0.00 | 0.00 | 0.00 |
Facility | 26.83 | 0.00 | 0.33 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 1.129 | 0.230 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 1.025 | 0.245 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 1.193 | 0.320 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 1.182 | 0.320 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 1.165 | 0.320 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 1.078 | 0.307 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 1.087 | 0.341 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 1.078 | 0.341 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 1.062 | 0.341 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 1.053 | 0.359 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.47 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.76 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.91 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 11837370.83 | 0.00 | 11837370.83 | 2812665.34 | 14650036.17 | 12976396.34 | 3129.74 | 3990.00 | 1640.26 | 24.51 |
SMSTORE1 | 5384368.44 | 0.00 | 5384368.44 | 1400999.48 | 6785367.92 | 6488198.17 | 4202.16 | 2840.02 | 1717.82 | 32.67 |
SMSTORE2 | 4821273.37 | 0.00 | 4821273.37 | 1437500.89 | 6258774.25 | 6488198.17 | 4293.60 | 3242.50 | 1223.90 | 125.06 |
SMSTORE3 | 4777879.96 | 0.00 | 4777879.96 | 1437500.89 | 6215380.85 | 6488198.17 | 4293.90 | 3274.17 | 1191.93 | 119.48 |
SMSTORE4 | 4703205.49 | 0.00 | 4703205.49 | 1437500.89 | 6140706.38 | 6488198.17 | 4298.69 | 3329.83 | 1131.48 | 112.18 |
LGSTORE2 | 7957587.23 | 0.00 | 7957587.23 | 2643892.63 | 10601479.86 | 12976396.34 | 4679.02 | 3138.33 | 942.65 | 83.87 |
SMSTORE5 | 4013886.88 | 0.00 | 4013886.88 | 1448728.57 | 5462615.45 | 6488198.17 | 4678.85 | 3155.83 | 925.31 | 84.80 |
SMSTORE6 | 3981675.49 | 0.00 | 3981675.49 | 1448728.57 | 5430404.06 | 6488198.17 | 4680.55 | 3178.42 | 901.04 | 84.08 |
SMSTORE7 | 3915378.99 | 0.00 | 3915378.99 | 1448728.57 | 5364107.56 | 6488198.17 | 4686.02 | 3224.17 | 849.81 | 84.81 |
SMSTORE8 | 3877821.34 | 0.00 | 3877821.34 | 1784553.10 | 5662374.44 | 6488198.17 | 4690.68 | 3311.83 | 757.48 | 75.20 |
Total Facility | 55270448.01 | 0.00 | 55270448.01 | 17300798.94 | 72571246.95 | 77858378.04 | 4697.68 | 4603.27 | 2034.58 | 242.61 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.5605 | 0.0000 | 0.5605 | 0.1144 | 0.6749 | 0.4115 | 224.07 | 3989.50 | 1626.43 |
SMSTORE1 | 0.2544 | 0.0000 | 0.2544 | 0.0609 | 0.3154 | 0.2057 | 1299.74 | 2840.02 | 1700.24 |
SMSTORE2 | 0.2962 | 0.0000 | 0.2962 | 0.0795 | 0.3757 | 0.2057 | 0.00 | 3242.00 | 1153.00 |
SMSTORE3 | 0.2935 | 0.0000 | 0.2935 | 0.0795 | 0.3730 | 0.2057 | 0.00 | 3273.83 | 1121.17 |
SMSTORE4 | 0.2893 | 0.0000 | 0.2893 | 0.0795 | 0.3688 | 0.2057 | 0.00 | 3328.50 | 1066.50 |
LGSTORE2 | 0.5353 | 0.0000 | 0.5353 | 0.1526 | 0.6879 | 0.4115 | 0.00 | 3137.17 | 892.83 |
SMSTORE5 | 0.2699 | 0.0000 | 0.2699 | 0.0848 | 0.3547 | 0.2057 | 0.00 | 3155.00 | 875.00 |
SMSTORE6 | 0.2679 | 0.0000 | 0.2679 | 0.0848 | 0.3526 | 0.2057 | 0.00 | 3177.58 | 852.42 |
SMSTORE7 | 0.2638 | 0.0000 | 0.2638 | 0.0848 | 0.3485 | 0.2057 | 0.00 | 3223.50 | 806.50 |
SMSTORE8 | 0.2616 | 0.0000 | 0.2616 | 0.0893 | 0.3509 | 0.2057 | 0.00 | 3311.67 | 718.33 |
Total Facility | 3.2924 | 0.0000 | 3.2924 | 0.9099 | 4.2024 | 2.4689 | 1400.36 | 4597.94 | 1972.99 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 11309452.31 | 0.00 | 11309452.31 | 12976396.34 | 7131.91 | 10.83 | 1617.26 | 24.51 |
PSZ-AC_2:2 | 5144193.48 | 0.00 | 5144193.48 | 6488198.17 | 7057.68 | 14.25 | 1688.07 | 32.67 |
PSZ-AC_3:3 | 4606227.56 | 0.00 | 4606227.56 | 6488198.17 | 7544.35 | 5.50 | 1210.15 | 124.73 |
PSZ-AC_4:4 | 4564771.84 | 0.00 | 4564771.84 | 6488198.17 | 7574.40 | 6.00 | 1179.60 | 118.77 |
PSZ-AC_5:5 | 4493429.00 | 0.00 | 4493429.00 | 6488198.17 | 7635.35 | 4.08 | 1120.56 | 111.76 |
PSZ-AC_6:6 | 7602708.89 | 0.00 | 7602708.89 | 12976396.34 | 7827.02 | 4.33 | 928.65 | 83.87 |
PSZ-AC_7:7 | 3834873.76 | 0.00 | 3834873.76 | 6488198.17 | 7843.27 | 3.25 | 913.48 | 84.74 |
PSZ-AC_8:8 | 3804098.33 | 0.00 | 3804098.33 | 6488198.17 | 7864.63 | 4.00 | 891.37 | 83.91 |
PSZ-AC_9:9 | 3740750.39 | 0.00 | 3740750.39 | 6488198.17 | 7915.44 | 4.25 | 840.31 | 84.81 |
PSZ-AC_10:10 | 3704831.53 | 0.00 | 3704831.53 | 6488198.17 | 8006.10 | 3.94 | 749.96 | 75.20 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5355 | 0.0000 | 0.5355 | 0.4115 | 4225.32 | 10.00 | 1604.68 |
PSZ-AC_2:2 | 0.2431 | 0.0000 | 0.2431 | 0.2057 | 4155.26 | 14.08 | 1670.65 |
PSZ-AC_3:3 | 0.2830 | 0.0000 | 0.2830 | 0.2057 | 3249.42 | 4.17 | 1141.42 |
PSZ-AC_4:4 | 0.2805 | 0.0000 | 0.2805 | 0.2057 | 3279.50 | 4.67 | 1110.83 |
PSZ-AC_5:5 | 0.2764 | 0.0000 | 0.2764 | 0.2057 | 3333.83 | 3.25 | 1057.92 |
PSZ-AC_6:6 | 0.5114 | 0.0000 | 0.5114 | 0.4115 | 3145.67 | 4.00 | 880.33 |
PSZ-AC_7:7 | 0.2579 | 0.0000 | 0.2579 | 0.2057 | 3162.58 | 2.83 | 864.58 |
PSZ-AC_8:8 | 0.2559 | 0.0000 | 0.2559 | 0.2057 | 3182.58 | 3.33 | 844.08 |
PSZ-AC_9:9 | 0.2520 | 0.0000 | 0.2520 | 0.2057 | 3228.17 | 3.33 | 798.50 |
PSZ-AC_10:10 | 0.2499 | 0.0000 | 0.2499 | 0.2057 | 3314.17 | 3.33 | 712.50 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 4962.47 | 712.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 3920.85 | 1200.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 3933.64 | 586.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 3956.86 | 556.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 3977.64 | 529.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3732.56 | 381.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3735.84 | 378.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3747.87 | 366.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3763.09 | 351.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3789.36 | 315.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.5354 | 0.6824 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2797 | 0.2767 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.2707 | 0.3818 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.2685 | 0.3825 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.2646 | 0.3834 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.4947 | 0.7035 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.2488 | 0.3634 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.2472 | 0.3622 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2439 | 0.3575 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.2418 | 0.3693 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 759 |
Defaulted Fields | 823 |
Fields with Defaults | 2681 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1011.91 | 3274.06 | 01-JAN-08:00 | 99313.67 | 26-JUN-15:00 |
Electricity:Building | 625.08 | 2063.06 | 01-JAN-00:10 | 38863.50 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 142.50 | 391.26 | 01-JAN-00:10 | 7378.51 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 625.08 | 2063.06 | 01-JAN-00:10 | 38863.50 | 01-JAN-11:10 |
InteriorLights:Electricity | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 116.25 | 317.63 | 01-JAN-00:10 | 6035.26 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 116.25 | 317.63 | 01-JAN-00:10 | 6035.26 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 496.92 | 1621.22 | 01-JAN-00:10 | 30804.00 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 81.39 | 223.36 | 01-JAN-00:10 | 4215.80 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 68.27 | 186.54 | 01-JAN-00:10 | 3544.17 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 68.27 | 186.54 | 01-JAN-00:10 | 3544.17 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 59.43 | 204.26 | 01-JAN-00:10 | 3853.00 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 59.43 | 204.26 | 01-JAN-00:10 | 3853.00 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 59.43 | 204.26 | 01-JAN-00:10 | 3853.00 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 49.01 | 167.44 | 01-JAN-00:10 | 3181.37 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 73.33 | 274.94 | 01-JAN-00:10 | 5168.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 54.16 | 201.30 | 01-JAN-00:10 | 3825.14 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 54.16 | 201.30 | 01-JAN-00:10 | 3825.14 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 37.39 | 140.18 | 01-JAN-00:10 | 2635.45 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 27.81 | 103.36 | 01-JAN-00:10 | 1963.83 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1011.91 | 3274.06 | 01-JAN-08:00 | 99313.67 | 26-JUN-15:00 |
ElectricityPurchased:Plant | 1011.91 | 3274.06 | 01-JAN-08:00 | 99313.67 | 26-JUN-15:00 |
Cogeneration:ElectricityPurchased | 1011.91 | 3274.06 | 01-JAN-08:00 | 99313.67 | 26-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 1011.91 | 3274.06 | 01-JAN-08:00 | 99313.67 | 26-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1011.91 | 3274.06 | 01-JAN-08:00 | 99313.67 | 26-JUN-15:00 |
ElectricityNet:Plant | 1011.91 | 3274.06 | 01-JAN-08:00 | 99313.67 | 26-JUN-15:00 |
Cogeneration:ElectricityNet | 1011.91 | 3274.06 | 01-JAN-08:00 | 99313.67 | 26-JUN-15:00 |
General:Cogeneration:ElectricityNet | 1011.91 | 3274.06 | 01-JAN-08:00 | 99313.67 | 26-JUN-15:00 |
Electricity:HVAC | 221.46 | 0.00 | 01-JAN-00:10 | 57123.26 | 26-JUN-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 97.93 | 0.00 | 01-JAN-00:10 | 46744.75 | 26-JUN-15:00 |
General:Cooling:Electricity | 97.93 | 0.00 | 01-JAN-00:10 | 46744.75 | 26-JUN-15:00 |
Fans:Electricity | 123.53 | 0.00 | 01-JAN-00:10 | 11444.21 | 21-DEC-18:00 |
General:Fans:Electricity | 123.53 | 0.00 | 01-JAN-00:10 | 11444.21 | 21-DEC-18:00 |
ExteriorLights:Electricity | 100.80 | 0.00 | 01-JAN-07:30 | 7723.25 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 100.80 | 0.00 | 01-JAN-07:30 | 7723.25 | 01-JAN-06:10 |
Electricity:Plant | 64.58 | 1211.00 | 06-JAN-00:10 | 12501.16 | 16-JAN-12:20 |
WaterSystems:Electricity | 64.58 | 1211.00 | 06-JAN-00:10 | 12501.16 | 16-JAN-12:20 |
Water Heater:WaterSystems:Electricity | 64.58 | 1211.00 | 06-JAN-00:10 | 12501.16 | 16-JAN-12:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 321.68 | 0.00 | 01-JAN-00:10 | 222253.60 | 21-DEC-18:00 |
NaturalGas:HVAC | 321.68 | 0.00 | 01-JAN-00:10 | 222253.60 | 21-DEC-18:00 |
Heating:NaturalGas | 321.68 | 0.00 | 01-JAN-00:10 | 222253.60 | 21-DEC-18:00 |
General:Heating:NaturalGas | 321.68 | 0.00 | 01-JAN-00:10 | 222253.60 | 21-DEC-18:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1181.98 | 0.00 | 01-JAN-00:10 | 317321.88 | 23-DEC-08:10 |
EnergyTransfer:Building | 554.93 | 0.00 | 01-JAN-00:10 | 148945.91 | 23-DEC-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 115.75 | 0.00 | 01-JAN-00:10 | 31119.90 | 23-DEC-08:10 |
Heating:EnergyTransfer | 76.66 | 0.00 | 01-JAN-00:10 | 148945.91 | 23-DEC-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 10.84 | 0.00 | 01-JAN-00:10 | 31119.90 | 23-DEC-08:10 |
General:Heating:EnergyTransfer | 76.66 | 0.00 | 01-JAN-00:10 | 148945.91 | 23-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 10.84 | 0.00 | 01-JAN-00:10 | 31119.90 | 23-DEC-08:10 |
Cooling:EnergyTransfer | 478.27 | 0.00 | 01-JAN-00:10 | 96940.10 | 16-AUG-14:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 104.92 | 0.00 | 01-JAN-00:10 | 16704.30 | 16-AUG-16:10 |
General:Cooling:EnergyTransfer | 478.27 | 0.00 | 01-JAN-00:10 | 96940.10 | 16-AUG-14:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 104.92 | 0.00 | 01-JAN-00:10 | 16704.30 | 16-AUG-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 62.85 | 0.00 | 01-JAN-00:10 | 11064.68 | 23-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 2.76 | 0.00 | 01-JAN-00:10 | 11064.68 | 23-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 2.76 | 0.00 | 01-JAN-00:10 | 11064.68 | 23-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 60.09 | 0.00 | 01-JAN-00:10 | 9646.87 | 12-MAR-17:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 60.09 | 0.00 | 01-JAN-00:10 | 9646.87 | 12-MAR-17:40 |
EnergyTransfer:Zone:SMSTORE2 | 48.43 | 0.00 | 01-JAN-00:10 | 12021.41 | 24-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 3.91 | 0.00 | 01-JAN-00:10 | 12021.41 | 24-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 3.91 | 0.00 | 01-JAN-00:10 | 12021.41 | 24-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 44.52 | 0.00 | 01-JAN-00:10 | 8579.39 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 44.52 | 0.00 | 01-JAN-00:10 | 8579.39 | 16-AUG-14:00 |
EnergyTransfer:Zone:SMSTORE3 | 47.83 | 0.00 | 01-JAN-00:10 | 12767.24 | 24-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 4.38 | 0.00 | 01-JAN-00:10 | 12767.24 | 24-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 4.38 | 0.00 | 01-JAN-00:10 | 12767.24 | 24-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 43.44 | 0.00 | 01-JAN-00:10 | 8586.84 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 43.44 | 0.00 | 01-JAN-00:10 | 8586.84 | 16-AUG-14:00 |
EnergyTransfer:Zone:SMSTORE4 | 46.00 | 0.00 | 01-JAN-00:10 | 13570.44 | 24-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 5.16 | 0.00 | 01-JAN-00:10 | 13570.44 | 24-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 5.16 | 0.00 | 01-JAN-00:10 | 13570.44 | 24-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 40.84 | 0.00 | 01-JAN-00:10 | 8433.77 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 40.84 | 0.00 | 01-JAN-00:10 | 8433.77 | 16-AUG-14:00 |
EnergyTransfer:Zone:LGSTORE2 | 75.56 | 0.00 | 01-JAN-00:10 | 28311.94 | 23-DEC-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 11.36 | 0.00 | 01-JAN-00:10 | 28311.94 | 23-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 11.36 | 0.00 | 01-JAN-00:10 | 28311.94 | 23-DEC-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 64.20 | 0.00 | 01-JAN-00:10 | 15375.30 | 26-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 64.20 | 0.00 | 01-JAN-00:10 | 15375.30 | 26-JUN-15:00 |
EnergyTransfer:Zone:SMSTORE5 | 38.89 | 0.00 | 01-JAN-00:10 | 14724.05 | 23-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 6.64 | 0.00 | 01-JAN-00:10 | 14724.05 | 23-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 6.64 | 0.00 | 01-JAN-00:10 | 14724.05 | 23-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 32.26 | 0.00 | 01-JAN-00:10 | 8071.61 | 26-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 32.26 | 0.00 | 01-JAN-00:10 | 8071.61 | 26-JUN-15:00 |
EnergyTransfer:Zone:SMSTORE6 | 38.40 | 0.00 | 01-JAN-00:10 | 14871.71 | 23-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 6.98 | 0.00 | 01-JAN-00:10 | 14871.71 | 23-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 6.98 | 0.00 | 01-JAN-00:10 | 14871.71 | 23-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 31.41 | 0.00 | 01-JAN-00:10 | 8009.74 | 26-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 31.41 | 0.00 | 01-JAN-00:10 | 8009.74 | 26-JUN-15:00 |
EnergyTransfer:Zone:SMSTORE7 | 37.76 | 0.00 | 01-JAN-00:10 | 15687.32 | 23-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 8.42 | 0.00 | 01-JAN-00:10 | 15687.32 | 23-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 8.42 | 0.00 | 01-JAN-00:10 | 15687.32 | 23-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 29.35 | 0.00 | 01-JAN-00:10 | 7924.02 | 26-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 29.35 | 0.00 | 01-JAN-00:10 | 7924.02 | 26-JUN-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 43.44 | 0.00 | 01-JAN-00:10 | 18643.21 | 21-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 16.20 | 0.00 | 01-JAN-00:10 | 18643.21 | 21-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 16.20 | 0.00 | 01-JAN-00:10 | 18643.21 | 21-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 27.24 | 0.00 | 01-JAN-00:10 | 8432.23 | 16-AUG-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 27.24 | 0.00 | 01-JAN-00:10 | 8432.23 | 16-AUG-14:10 |
EnergyTransfer:HVAC | 627.05 | 0.00 | 01-JAN-00:10 | 177802.88 | 21-DEC-18:00 |
HeatingCoils:EnergyTransfer | 257.34 | 0.00 | 01-JAN-00:10 | 177802.88 | 21-DEC-18:00 |
CoolingCoils:EnergyTransfer | 369.71 | 0.00 | 01-JAN-00:10 | 144882.86 | 26-JUN-15:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 10.837 | -104.917 | 0.000 | 0.000 | 24.906 | 116.248 | 26.249 | 33.099 | 0.000 | 3.048 | 0.002 | 0.000 | -12.709 | 0.000 | -30.004 | -66.756 |
SMSTORE1 | 0.000 | 0.000 | 2.763 | -60.088 | 0.000 | 0.000 | 12.234 | 68.266 | 13.125 | 16.431 | 0.000 | 1.650 | 0.000 | 0.000 | -6.658 | 0.000 | -14.663 | -33.060 |
SMSTORE2 | 0.000 | 0.000 | 3.914 | -44.520 | 0.000 | 0.000 | 7.437 | 49.007 | 10.421 | 16.408 | 0.000 | 1.623 | 0.001 | 0.000 | -6.602 | 0.000 | -15.098 | -22.589 |
SMSTORE3 | 0.000 | 0.000 | 4.382 | -43.443 | 0.000 | 0.000 | 7.449 | 49.007 | 10.421 | 16.424 | 0.000 | 1.623 | 0.001 | 0.000 | -6.545 | 0.000 | -15.040 | -24.277 |
SMSTORE4 | 0.000 | 0.000 | 5.162 | -40.839 | 0.000 | 0.000 | 7.465 | 49.007 | 10.421 | 16.451 | 0.000 | 1.623 | 0.003 | 0.000 | -6.475 | 0.000 | -14.960 | -27.854 |
LGSTORE2 | 0.000 | 0.000 | 11.365 | -64.196 | 0.000 | 0.000 | 25.697 | 54.161 | 19.173 | 33.047 | 0.000 | 2.925 | 0.003 | 0.000 | -12.563 | 0.000 | -27.436 | -42.173 |
SMSTORE5 | 0.000 | 0.000 | 6.636 | -32.258 | 0.000 | 0.000 | 12.855 | 27.807 | 9.586 | 16.511 | 0.000 | 1.626 | 0.001 | 0.000 | -6.279 | 0.000 | -14.920 | -21.566 |
SMSTORE6 | 0.000 | 0.000 | 6.984 | -31.414 | 0.000 | 0.000 | 12.867 | 27.807 | 9.586 | 16.525 | 0.000 | 1.627 | 0.001 | 0.000 | -6.248 | 0.000 | -14.885 | -22.848 |
SMSTORE7 | 0.000 | 0.000 | 8.419 | -29.345 | 0.000 | 0.000 | 12.898 | 27.807 | 9.586 | 16.562 | 0.000 | 1.627 | 0.000 | 0.000 | -6.156 | 0.000 | -14.785 | -26.613 |
SMSTORE8 | 0.000 | 0.000 | 16.200 | -27.244 | 0.000 | 0.000 | 12.952 | 27.807 | 9.586 | 16.655 | 0.000 | 1.705 | 0.001 | 0.000 | -5.807 | 0.000 | -18.781 | -33.075 |
Total Facility | 0.000 | 0.000 | 76.661 | -478.265 | 0.000 | 0.000 | 136.761 | 496.921 | 128.154 | 198.113 | 0.000 | 19.078 | 0.015 | 0.000 | -76.042 | 0.000 | -180.571 | -320.811 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 13-SEP-07:02 | 0.00 | 0.00 | 0.00 | -38529.26 | 0.00 | 0.00 | 177.01 | 317.63 | 74.62 | 505.87 | 0.00 | 0.00 | 37607.53 | 0.00 | -0.00 | 0.00 | -153.41 | 0.00 |
SMSTORE1 | 13-SEP-07:02 | 0.00 | 0.00 | 0.00 | -21603.14 | 0.00 | 0.00 | 87.05 | 186.54 | 37.31 | 250.23 | 0.00 | 0.00 | 21119.31 | 0.00 | -0.00 | 0.00 | -77.30 | 0.00 |
SMSTORE2 | 11-SEP-06:02 | 0.00 | 0.00 | 0.00 | -23693.33 | 0.00 | 0.00 | 0.00 | 167.44 | 36.82 | 0.00 | 0.00 | 0.00 | 23588.38 | 0.00 | -87.73 | 0.00 | -11.58 | 0.00 |
SMSTORE3 | 11-SEP-06:02 | 0.00 | 0.00 | 0.00 | -24578.29 | 0.00 | 0.00 | 0.00 | 167.44 | 36.82 | 0.00 | 0.00 | 0.00 | 24474.97 | 0.00 | -89.34 | 0.00 | -11.60 | 0.00 |
SMSTORE4 | 11-SEP-06:02 | 0.00 | 0.00 | 0.00 | -23310.81 | 0.00 | 0.00 | 0.00 | 167.44 | 36.82 | 0.00 | 0.00 | 0.00 | 23205.77 | 0.00 | -87.65 | 0.00 | -11.56 | 0.00 |
LGSTORE2 | 11-SEP-07:02 | 0.00 | 0.00 | 0.00 | -39338.12 | 0.00 | 0.00 | 0.00 | 201.30 | 73.64 | 356.48 | 0.00 | 0.00 | 38837.09 | 0.00 | -0.00 | 0.00 | -130.39 | 0.00 |
SMSTORE5 | 11-SEP-07:02 | 0.00 | 0.00 | 0.00 | -20245.43 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 178.97 | 0.00 | 0.00 | 19996.10 | 0.00 | -0.00 | 0.00 | -69.82 | 0.00 |
SMSTORE6 | 11-SEP-07:02 | 0.00 | 0.00 | 0.00 | -20037.50 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 179.85 | 0.00 | 0.00 | 19786.71 | 0.00 | -0.00 | 0.00 | -69.23 | 0.00 |
SMSTORE7 | 11-SEP-07:02 | 0.00 | 0.00 | 0.00 | -18527.47 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 181.89 | 0.00 | 0.00 | 18274.31 | 0.00 | -0.00 | 0.00 | -68.90 | 0.00 |
SMSTORE8 | 23-JUL-08:62 | 0.00 | 0.00 | 0.00 | -16986.04 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 426.24 | 0.00 | 23.37 | 16396.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-SEP-07:02 | 0.00 | 0.00 | 0.00 | -173433.03 | 0.00 | 0.00 | 563.25 | 6142.12 | 1452.23 | 2222.26 | 0.00 | 0.00 | 163884.18 | 0.00 | 0.00 | 0.00 | -831.01 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 22-DEC-08:61 | 0.00 | 0.00 | 62803.88 | 0.00 | 0.00 | 0.00 | 0.00 | 317.63 | 73.64 | 2164.96 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1597.64 | -63762.47 |
SMSTORE1 | 22-DEC-08:61 | 0.00 | 0.00 | 33203.74 | 0.00 | 0.00 | 0.00 | 0.00 | 186.54 | 36.82 | 1045.40 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -854.67 | -33617.84 |
SMSTORE2 | 24-DEC-08:61 | 0.00 | 0.00 | 34236.25 | 0.00 | 0.00 | 0.00 | 0.00 | 167.44 | 37.31 | 1074.82 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -754.39 | -34761.44 |
SMSTORE3 | 24-DEC-08:61 | 0.00 | 0.00 | 34073.04 | 0.00 | 0.00 | 0.00 | 0.00 | 167.44 | 37.31 | 1080.85 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -747.83 | -34610.81 |
SMSTORE4 | 24-DEC-08:61 | 0.00 | 0.00 | 34072.37 | 0.00 | 0.00 | 0.00 | 0.00 | 167.44 | 37.31 | 1086.61 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -741.16 | -34622.58 |
LGSTORE2 | 22-DEC-08:61 | 0.00 | 0.00 | 60137.60 | 0.00 | 0.00 | 0.00 | 0.00 | 201.30 | 73.64 | 2150.97 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1486.34 | -61077.18 |
SMSTORE5 | 22-DEC-08:61 | 0.00 | 0.00 | 30597.47 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 1072.66 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -820.46 | -30989.85 |
SMSTORE6 | 22-DEC-08:61 | 0.00 | 0.00 | 30474.05 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 1074.14 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -818.84 | -30869.52 |
SMSTORE7 | 22-DEC-08:61 | 0.00 | 0.00 | 30305.12 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 1081.31 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -810.71 | -30715.90 |
SMSTORE8 | 21-DEC-08:61 | 0.00 | 0.00 | 31976.28 | 0.00 | 0.00 | 0.00 | 0.00 | 103.36 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -865.30 | 0.00 | -1026.10 | -30225.05 |
Total Facility | 21-DEC-08:61 | 0.00 | 0.00 | 295785.21 | 0.00 | 0.00 | 0.00 | 766.39 | 6142.12 | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11072.16 | 0.00 | -10628.05 | -282445.74 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.5345 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.5345 | 0.1624 | 1.0000 | Not calculated | 0.4115 | 0.1624 | ||
PSZ-AC_2:2 | 1.3662 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3662 | 0.1506 | 1.0000 | Not calculated | 0.2057 | 0.1506 | ||
PSZ-AC_3:3 | 1.4270 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4270 | 0.1442 | 1.0000 | Not calculated | 0.2057 | 0.1442 | ||
PSZ-AC_4:4 | 1.4177 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4177 | 0.1451 | 1.0000 | Not calculated | 0.2057 | 0.1451 | ||
PSZ-AC_5:5 | 1.4176 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4176 | 0.1451 | 1.0000 | Not calculated | 0.2057 | 0.1451 | ||
PSZ-AC_6:6 | 2.3849 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.3849 | 0.1725 | 1.0000 | Not calculated | 0.4115 | 0.1725 | ||
PSZ-AC_7:7 | 1.2191 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2352 | 0.1666 | 1.0000 | Not calculated | 0.2057 | 0.1666 | ||
PSZ-AC_8:8 | 1.2122 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2279 | 0.1676 | 1.0000 | Not calculated | 0.2057 | 0.1676 | ||
PSZ-AC_9:9 | 1.2028 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2225 | 0.1683 | 1.0000 | Not calculated | 0.2057 | 0.1683 | ||
PSZ-AC_10:10 | 1.2857 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2857 | 0.1600 | 1.0000 | Not calculated | 0.2057 | 0.1600 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.5345 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.5345 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1624 | ||
PSZ-AC_2:2 | 1.3662 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3662 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1506 | ||
PSZ-AC_3:3 | 1.4270 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4270 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1442 | ||
PSZ-AC_4:4 | 1.4177 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4177 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1451 | ||
PSZ-AC_5:5 | 1.4176 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4176 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1451 | ||
PSZ-AC_6:6 | 2.3849 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.3849 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1725 | ||
PSZ-AC_7:7 | 1.2191 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2191 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1688 | ||
PSZ-AC_8:8 | 1.2122 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2122 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1697 | ||
PSZ-AC_9:9 | 1.2028 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2028 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1711 | ||
PSZ-AC_10:10 | 1.2857 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2857 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1600 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.5345 | 2.5345 | 2.5345 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3662 | 1.3662 | 1.3662 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4270 | 1.4270 | 1.4270 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4177 | 1.4177 | 1.4177 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4176 | 1.4176 | 1.4176 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.3849 | 2.3849 | 2.3849 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2191 | 1.2191 | 1.2191 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2122 | 1.2122 | 1.2122 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2028 | 1.2028 | 1.2028 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2857 | 1.2857 | 1.2857 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.5345 | 2.5345 | 2.5345 | 2.5345 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.3662 | 1.3662 | 1.3662 | 1.3662 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.4270 | 1.4270 | 1.4270 | 1.4270 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.4177 | 1.4177 | 1.4177 | 1.4177 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.4176 | 1.4176 | 1.4176 | 1.4176 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.3849 | 2.3849 | 2.3849 | 2.3849 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.2191 | 1.2352 | 1.2191 | 1.2191 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.2122 | 1.2279 | 1.2122 | 1.2122 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.2028 | 1.2225 | 1.2028 | 1.2028 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2857 | 1.2857 | 1.2857 | 1.2857 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.5345 | 2.5345 | 2.5345 | No | 0.4115 | 0.2587 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3662 | 1.3662 | 1.3662 | No | 0.2057 | 0.2704 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4270 | 1.4270 | 1.4270 | No | 0.2057 | 0.2669 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4177 | 1.4177 | 1.4177 | No | 0.2057 | 0.2649 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4176 | 1.4176 | 1.4176 | No | 0.2057 | 0.2616 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.3849 | 2.3849 | 2.3849 | No | 0.4115 | 0.2722 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2191 | 1.2191 | 1.2191 | No | 0.2057 | 0.2547 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2122 | 1.2122 | 1.2122 | No | 0.2057 | 0.2550 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2028 | 1.2028 | 1.2028 | No | 0.2057 | 0.2509 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2857 | 1.2857 | 1.2857 | No | 0.2057 | 0.2105 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.5345 | 2.5345 | 2.5345 | 2.5345 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.3662 | 1.3662 | 1.3662 | 1.3662 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.4270 | 1.4270 | 1.4270 | 1.4270 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.4177 | 1.4177 | 1.4177 | 1.4177 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.4176 | 1.4176 | 1.4176 | 1.4176 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.3849 | 2.3849 | 2.3849 | 2.3849 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.2191 | 1.2191 | 1.2191 | 1.2191 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.2122 | 1.2122 | 1.2122 | 1.2122 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.2028 | 1.2028 | 1.2028 | 1.2028 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2857 | 1.2857 | 1.2857 | 1.2857 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.33 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 321.68 | 222253.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 97.93 | 46744.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 496.92 | 30804.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 100.80 | 7723.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 123.53 | 11444.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 64.58 | 12501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 1011.91 |
Natural Gas | 0.00 | 321.68 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1333.59 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 237.73 |
Space Heating | 0.00 |
Space Cooling | 46.85 |
Fans (All) | 59.10 |
Service Water Heating | 30.89 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 484.09 |
Subtotal | 484.09 |
Natural Gas [MJ/m2] | |
Space Heating | 153.89 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 153.89 |
Subtotal | 153.89 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 37.26 |
Space Heating | 24.12 |
Space Cooling | 7.34 |
Fans (All) | 9.26 |
Service Water Heating | 4.84 |
Receptacle Equipment | 9.61 |
Miscellaneous | 7.56 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8756.17 | 3.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8755.83 | 4.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8756.67 | 3.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Min | 8755.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 4.17 | 0.00 | 0.00 | 0.00 |
Average | 8758.30 | 1.70 | 0.00 | 0.00 | 0.00 |
Sum | 87583.00 | 17.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25472.33 | 2.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25472.33 | 2.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25472.83 | 2.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93203.00 | 8.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45909.50 | 2.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45909.50 | 2.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45909.50 | 2.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45909.50 | 2.50 | 0.00 | 0.00 | 0.00 |
Min | 25472.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93203.00 | 8.00 | 0.00 | 0.00 | 0.00 |
Average | 48607.65 | 2.55 | 0.00 | 0.00 | 0.00 |
Sum | 486076.50 | 25.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8736.33 | 23.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8751.00 | 9.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8700.67 | 59.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8701.67 | 58.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8711.00 | 49.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8732.00 | 28.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8734.67 | 25.33 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8735.17 | 24.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8736.50 | 23.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
Min | 8700.67 | 9.00 | 0.00 | 0.00 | 0.00 |
Max | 8751.00 | 59.33 | 0.00 | 0.00 | 0.00 |
Average | 8728.68 | 31.32 | 0.00 | 0.00 | 0.00 |
Sum | 87286.83 | 313.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 89030.50 | 10.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25469.83 | 5.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25469.83 | 5.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25470.00 | 5.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93185.83 | 25.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45894.83 | 17.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45892.50 | 19.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45879.50 | 32.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45875.33 | 36.67 | 0.00 | 0.00 | 0.00 |
Min | 25469.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93185.83 | 36.67 | 0.00 | 0.00 | 0.00 |
Average | 48594.52 | 15.68 | 0.00 | 0.00 | 0.00 |
Sum | 485945.17 | 156.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:34:29
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Environment
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.425797E+10 | 13148.01 | 06-JAN-00:01 | -15.8 | -15.8 | 0.111593E+10 | 1685.85 | 20-JAN-13:00 | 21.00 | 6.96 |
February | 0.334751E+10 | 10055.08 | 10-FEB-00:02 | -8.0 | -8.7 | 0.998555E+09 | 1685.85 | 18-FEB-13:00 | 20.00 | 7.73 |
March | 0.476129E+10 | 10524.92 | 04-MAR-23:52 | -9.0 | -9.0 | 0.117243E+10 | 1685.85 | 12-MAR-17:30 | 17.00 | 5.34 |
April | 0.445832E+10 | 7535.50 | 14-APR-23:25 | -1.5 | -1.7 | 0.115855E+10 | 1685.85 | 07-APR-12:00 | -1.5 | -1.7 |
May | 0.829557E+10 | 10693.49 | 31-MAY-16:10 | 27.83 | 14.82 | 0.136802E+10 | 1685.90 | 21-MAY-16:10 | 27.83 | 14.82 |
June | 0.150431E+11 | 34383.17 | 27-JUN-07:02 | 22.47 | 9.00 | 0.135454E+10 | 1686.00 | 18-JUN-17:00 | 22.47 | 9.00 |
July | 0.156877E+11 | 35687.31 | 18-JUL-07:02 | 24.33 | 12.85 | 0.141271E+10 | 1686.00 | 29-JUL-12:30 | 24.50 | 18.54 |
August | 0.162719E+11 | 34486.44 | 03-AUG-07:02 | 21.33 | 15.03 | 0.139400E+10 | 1686.01 | 27-AUG-16:00 | 21.00 | 14.60 |
September | 0.144564E+11 | 38530.36 | 13-SEP-07:02 | 20.18 | 12.26 | 0.135579E+10 | 1685.95 | 01-SEP-12:00 | 20.18 | 12.26 |
October | 0.849552E+10 | 13104.61 | 11-OCT-14:00 | 27.00 | 9.73 | 0.129098E+10 | 1685.86 | 01-OCT-12:00 | 27.00 | 9.73 |
November | 0.604115E+10 | 12535.28 | 29-NOV-22:32 | -14.0 | -14.0 | 0.112346E+10 | 1685.85 | 05-NOV-16:10 | -14.0 | -14.0 |
December | 0.380017E+10 | 14881.80 | 22-DEC-00:01 | -20.2 | -20.3 | 0.112584E+10 | 1685.85 | 02-DEC-13:00 | -20.2 | -20.3 |
Annual Sum or Average | 0.104917E+12 | 0.148708E+11 | ||||||||
Minimum of Months | 0.334751E+10 | 7535.50 | -20.2 | -20.3 | 0.998555E+09 | 1685.85 | -20.2 | -20.3 | ||
Maximum of Months | 0.162719E+11 | 38530.36 | 27.83 | 15.03 | 0.141271E+10 | 1686.01 | 27.83 | 18.54 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243388E+10 | 4346.02 | 20-JAN-14:00 | 21.00 | 6.96 | 0.599423E+09 | 842.90 | 20-JAN-13:09 | 21.00 | 6.96 |
February | 0.191253E+10 | 4113.93 | 04-FEB-10:13 | -3.7 | -3.7 | 0.529471E+09 | 842.90 | 18-FEB-13:00 | 20.00 | 7.73 |
March | 0.287385E+10 | 17216.73 | 12-MAR-17:27 | 17.00 | 5.34 | 0.612349E+09 | 842.90 | 12-MAR-16:10 | 17.00 | 5.34 |
April | 0.262092E+10 | 4177.72 | 20-APR-13:00 | 22.00 | 9.15 | 0.611340E+09 | 842.90 | 07-APR-12:00 | 22.00 | 9.15 |
May | 0.520872E+10 | 17269.87 | 13-MAY-18:07 | 17.00 | 8.21 | 0.692302E+09 | 842.93 | 21-MAY-16:10 | 21.83 | 12.79 |
June | 0.859256E+10 | 20622.55 | 27-JUN-07:02 | 22.47 | 9.00 | 0.674304E+09 | 842.99 | 04-JUN-17:49 | 22.47 | 9.00 |
July | 0.899598E+10 | 19635.55 | 19-JUL-07:02 | 21.33 | 14.20 | 0.703029E+09 | 843.19 | 04-JUL-17:40 | 21.33 | 14.20 |
August | 0.919432E+10 | 19685.78 | 21-AUG-07:02 | 21.17 | 13.07 | 0.693876E+09 | 842.98 | 27-AUG-16:49 | 21.00 | 14.68 |
September | 0.818009E+10 | 21603.75 | 13-SEP-07:02 | 20.18 | 12.26 | 0.676901E+09 | 843.00 | 10-SEP-17:49 | 20.18 | 12.26 |
October | 0.480528E+10 | 17669.67 | 08-OCT-17:07 | 16.50 | 8.02 | 0.664252E+09 | 842.91 | 01-OCT-12:50 | 16.50 | 8.02 |
November | 0.319611E+10 | 5665.16 | 07-NOV-14:30 | 22.00 | 7.34 | 0.601909E+09 | 842.90 | 05-NOV-16:10 | 22.00 | 7.34 |
December | 0.207335E+10 | 6371.67 | 22-DEC-11:52 | -15.0 | -15.6 | 0.594339E+09 | 842.90 | 02-DEC-13:00 | -15.0 | -15.6 |
Annual Sum or Average | 0.600876E+11 | 0.765350E+10 | ||||||||
Minimum of Months | 0.191253E+10 | 4113.93 | -15.0 | -15.6 | 0.529471E+09 | 842.90 | -15.0 | -15.6 | ||
Maximum of Months | 0.919432E+10 | 21603.75 | 22.47 | 14.20 | 0.703029E+09 | 843.19 | 22.47 | 14.68 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186590E+10 | 4405.46 | 04-JAN-10:13 | -5.3 | -5.3 | 0.342315E+09 | 842.89 | 21-JAN-13:09 | 13.00 | 4.66 |
February | 0.148267E+10 | 6056.64 | 11-FEB-18:42 | -13.7 | -13.7 | 0.303496E+09 | 842.90 | 18-FEB-13:00 | 20.00 | 7.73 |
March | 0.216573E+10 | 5457.47 | 14-MAR-13:00 | 24.00 | 7.90 | 0.365672E+09 | 842.90 | 11-MAR-13:00 | 24.00 | 7.90 |
April | 0.196601E+10 | 3856.12 | 22-APR-07:02 | 0.00 | -0.0 | 0.356003E+09 | 842.89 | 08-APR-12:09 | 0.00 | -0.0 |
May | 0.359444E+10 | 5631.99 | 17-MAY-13:00 | 29.00 | 11.92 | 0.417478E+09 | 842.90 | 06-MAY-12:00 | 29.00 | 11.92 |
June | 0.637944E+10 | 22696.62 | 27-JUN-06:02 | 20.78 | 8.99 | 0.417103E+09 | 842.98 | 03-JUN-12:09 | 20.78 | 8.99 |
July | 0.660129E+10 | 22221.29 | 18-JUL-06:02 | 22.33 | 11.85 | 0.420240E+09 | 842.98 | 29-JUL-12:30 | 24.50 | 18.54 |
August | 0.690692E+10 | 22185.20 | 21-AUG-06:02 | 19.75 | 12.40 | 0.431708E+09 | 842.93 | 12-AUG-12:09 | 19.75 | 12.40 |
September | 0.600714E+10 | 23691.20 | 11-SEP-06:02 | 19.00 | 9.04 | 0.408466E+09 | 842.92 | 09-SEP-12:00 | 19.00 | 9.04 |
October | 0.352396E+10 | 6958.71 | 11-OCT-14:00 | 27.00 | 9.73 | 0.387813E+09 | 842.90 | 07-OCT-12:39 | 27.00 | 9.73 |
November | 0.246852E+10 | 5266.32 | 07-NOV-14:00 | 22.00 | 7.34 | 0.343978E+09 | 842.86 | 18-NOV-13:00 | 10.00 | 5.07 |
December | 0.155861E+10 | 7046.62 | 19-DEC-20:02 | -18.6 | -18.7 | 0.338508E+09 | 842.90 | 02-DEC-13:00 | -18.6 | -18.7 |
Annual Sum or Average | 0.445206E+11 | 0.453278E+10 | ||||||||
Minimum of Months | 0.148267E+10 | 3856.12 | -18.6 | -18.7 | 0.303496E+09 | 842.86 | -18.6 | -18.7 | ||
Maximum of Months | 0.690692E+10 | 23691.20 | 29.00 | 12.40 | 0.431708E+09 | 842.98 | 29.00 | 18.54 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169647E+10 | 5929.35 | 04-JAN-19:12 | -13.0 | -13.0 | 0.340511E+09 | 842.89 | 21-JAN-13:00 | 13.00 | 4.88 |
February | 0.135666E+10 | 3923.43 | 28-FEB-08:61 | -0.7 | -1.2 | 0.302022E+09 | 842.90 | 18-FEB-13:00 | -0.7 | -1.2 |
March | 0.202906E+10 | 5346.10 | 14-MAR-13:00 | 24.00 | 7.90 | 0.364493E+09 | 842.90 | 11-MAR-13:00 | 24.00 | 7.90 |
April | 0.181305E+10 | 3834.32 | 22-APR-07:02 | 0.00 | -0.0 | 0.354558E+09 | 842.89 | 08-APR-12:09 | 0.00 | -0.0 |
May | 0.347691E+10 | 5575.67 | 17-MAY-13:00 | 29.00 | 11.92 | 0.416553E+09 | 842.90 | 06-MAY-12:20 | 29.00 | 11.92 |
June | 0.638312E+10 | 23121.78 | 27-JUN-06:02 | 20.78 | 8.99 | 0.417098E+09 | 842.98 | 17-JUN-12:09 | 20.78 | 8.99 |
July | 0.662441E+10 | 22136.78 | 18-JUL-06:02 | 22.33 | 11.85 | 0.420238E+09 | 842.98 | 29-JUL-12:30 | 24.50 | 18.54 |
August | 0.691577E+10 | 22496.43 | 21-AUG-06:02 | 19.75 | 12.40 | 0.431703E+09 | 842.93 | 12-AUG-12:09 | 19.75 | 12.40 |
September | 0.599684E+10 | 24576.04 | 11-SEP-06:02 | 19.00 | 9.04 | 0.408374E+09 | 842.93 | 09-SEP-12:00 | 19.00 | 9.04 |
October | 0.342303E+10 | 6917.61 | 11-OCT-14:00 | 27.00 | 9.73 | 0.386766E+09 | 842.90 | 07-OCT-12:00 | 27.00 | 9.73 |
November | 0.230840E+10 | 5078.50 | 07-NOV-14:00 | 22.00 | 7.34 | 0.341846E+09 | 833.66 | 18-NOV-13:00 | 10.00 | 5.07 |
December | 0.141972E+10 | 4186.94 | 18-DEC-08:61 | -2.5 | -4.2 | 0.337148E+09 | 842.90 | 02-DEC-13:00 | -2.5 | -4.2 |
Annual Sum or Average | 0.434435E+11 | 0.452131E+10 | ||||||||
Minimum of Months | 0.135666E+10 | 3834.32 | -13.0 | -13.0 | 0.302022E+09 | 833.66 | -2.5 | -4.2 | ||
Maximum of Months | 0.691577E+10 | 24576.04 | 29.00 | 12.40 | 0.431703E+09 | 842.98 | 29.00 | 18.54 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146704E+10 | 3924.35 | 03-JAN-09:02 | -2.7 | -2.7 | 0.337977E+09 | 842.82 | 21-JAN-13:00 | 13.00 | 4.88 |
February | 0.118555E+10 | 3848.25 | 28-FEB-08:61 | -0.7 | -1.2 | 0.300496E+09 | 842.90 | 18-FEB-13:00 | -0.7 | -1.2 |
March | 0.181362E+10 | 5090.79 | 14-MAR-13:00 | 24.00 | 7.90 | 0.362755E+09 | 842.90 | 11-MAR-13:00 | 24.00 | 7.90 |
April | 0.157025E+10 | 3779.97 | 22-APR-07:02 | 0.00 | -0.0 | 0.352274E+09 | 842.89 | 08-APR-12:20 | 0.00 | -0.0 |
May | 0.320797E+10 | 5367.36 | 17-MAY-13:00 | 29.00 | 11.92 | 0.414915E+09 | 842.90 | 13-MAY-12:50 | 29.00 | 11.92 |
June | 0.615852E+10 | 21698.31 | 27-JUN-06:02 | 20.78 | 8.99 | 0.417054E+09 | 842.98 | 17-JUN-12:09 | 20.78 | 8.99 |
July | 0.641374E+10 | 22009.43 | 18-JUL-06:02 | 22.33 | 11.85 | 0.420196E+09 | 842.98 | 29-JUL-12:30 | 24.50 | 18.54 |
August | 0.669538E+10 | 21477.25 | 21-AUG-06:02 | 19.75 | 12.40 | 0.431662E+09 | 842.93 | 12-AUG-12:09 | 19.75 | 12.40 |
September | 0.578501E+10 | 23308.75 | 11-SEP-06:02 | 19.00 | 9.04 | 0.408106E+09 | 842.92 | 09-SEP-12:39 | 19.00 | 9.04 |
October | 0.321559E+10 | 6751.20 | 11-OCT-14:00 | 27.00 | 9.73 | 0.384987E+09 | 842.90 | 07-OCT-12:39 | 27.00 | 9.73 |
November | 0.209319E+10 | 4916.53 | 28-NOV-20:23 | -8.0 | -8.0 | 0.338975E+09 | 811.18 | 25-NOV-13:00 | -8.0 | -8.0 |
December | 0.123330E+10 | 4123.07 | 18-DEC-08:61 | -2.5 | -4.2 | 0.335346E+09 | 842.90 | 02-DEC-13:00 | -2.5 | -4.2 |
Annual Sum or Average | 0.408392E+11 | 0.450474E+10 | ||||||||
Minimum of Months | 0.118555E+10 | 3779.97 | -8.0 | -8.0 | 0.300496E+09 | 811.18 | -8.0 | -8.0 | ||
Maximum of Months | 0.669538E+10 | 23308.75 | 29.00 | 12.40 | 0.431662E+09 | 842.98 | 29.00 | 18.54 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.196500E+10 | 6147.05 | 22-JAN-10:03 | 3.17 | 1.71 | 0.114418E+10 | 2247.26 | 21-JAN-15:20 | 3.17 | 1.71 |
February | 0.154556E+10 | 7461.51 | 14-FEB-20:42 | -1.0 | -3.1 | 0.102376E+10 | 2247.74 | 18-FEB-15:09 | 18.83 | 7.90 |
March | 0.257152E+10 | 8688.68 | 14-MAR-13:00 | 24.00 | 7.90 | 0.123439E+10 | 2247.80 | 11-MAR-15:00 | 24.00 | 7.90 |
April | 0.216582E+10 | 7370.34 | 22-APR-08:62 | 0.00 | -0.1 | 0.119218E+10 | 2247.73 | 08-APR-14:09 | 0.00 | -0.1 |
May | 0.485381E+10 | 9226.58 | 17-MAY-14:10 | 28.67 | 11.73 | 0.140788E+10 | 2247.80 | 13-MAY-14:20 | 28.67 | 11.73 |
June | 0.101953E+11 | 36875.35 | 26-JUN-07:02 | 22.07 | 12.41 | 0.142988E+10 | 2247.92 | 03-JUN-14:00 | 22.07 | 12.41 |
July | 0.106074E+11 | 34232.44 | 19-JUL-07:02 | 21.33 | 14.20 | 0.143855E+10 | 2247.96 | 15-JUL-14:30 | 21.33 | 14.20 |
August | 0.111760E+11 | 36493.42 | 21-AUG-07:02 | 21.17 | 13.07 | 0.147986E+10 | 2247.98 | 05-AUG-14:39 | 21.17 | 13.07 |
September | 0.951556E+10 | 39333.64 | 11-SEP-07:02 | 20.63 | 10.22 | 0.139955E+10 | 2247.84 | 30-SEP-14:00 | 17.20 | 13.90 |
October | 0.498220E+10 | 12083.00 | 11-OCT-14:10 | 26.83 | 9.68 | 0.130430E+10 | 2247.80 | 07-OCT-14:20 | 26.83 | 9.68 |
November | 0.300423E+10 | 7847.21 | 07-NOV-14:00 | 22.00 | 7.34 | 0.114048E+10 | 2098.56 | 25-NOV-15:09 | 13.50 | 4.91 |
December | 0.161369E+10 | 7069.48 | 05-DEC-09:03 | 0.33 | -3.1 | 0.114249E+10 | 2247.80 | 02-DEC-15:20 | 0.33 | -3.1 |
Annual Sum or Average | 0.641961E+11 | 0.153375E+11 | ||||||||
Minimum of Months | 0.154556E+10 | 6147.05 | -1.0 | -3.1 | 0.102376E+10 | 2098.56 | 0.00 | -3.1 | ||
Maximum of Months | 0.111760E+11 | 39333.64 | 28.67 | 14.20 | 0.147986E+10 | 2247.98 | 28.67 | 14.20 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.928927E+09 | 4577.24 | 16-JAN-11:32 | -5.7 | -5.7 | 0.571309E+09 | 1121.38 | 21-JAN-15:20 | 13.67 | 5.40 |
February | 0.721502E+09 | 4475.16 | 09-FEB-19:03 | -5.2 | -7.1 | 0.511332E+09 | 1123.84 | 18-FEB-15:20 | 18.67 | 7.82 |
March | 0.123494E+10 | 4451.48 | 27-MAR-19:42 | -5.0 | -5.0 | 0.616325E+09 | 1123.87 | 11-MAR-15:00 | -5.0 | -5.0 |
April | 0.100424E+10 | 3622.82 | 22-APR-08:62 | 0.00 | -0.1 | 0.594399E+09 | 1123.84 | 08-APR-14:09 | 0.00 | -0.1 |
May | 0.238037E+10 | 4758.32 | 17-MAY-14:10 | 28.67 | 11.73 | 0.702784E+09 | 1123.87 | 06-MAY-14:00 | 28.67 | 11.73 |
June | 0.523102E+10 | 18549.79 | 26-JUN-07:02 | 22.07 | 12.41 | 0.714895E+09 | 1123.93 | 03-JUN-14:00 | 22.07 | 12.41 |
July | 0.545559E+10 | 17456.74 | 18-JUL-07:02 | 24.33 | 12.85 | 0.719224E+09 | 1123.95 | 15-JUL-14:30 | 24.33 | 12.85 |
August | 0.574292E+10 | 18789.17 | 21-AUG-07:02 | 21.17 | 13.07 | 0.739893E+09 | 1123.96 | 05-AUG-14:39 | 21.17 | 13.07 |
September | 0.487097E+10 | 20243.00 | 11-SEP-07:02 | 20.63 | 10.22 | 0.699631E+09 | 1123.88 | 30-SEP-14:00 | 17.20 | 13.90 |
October | 0.246952E+10 | 6276.25 | 11-OCT-14:10 | 26.83 | 9.68 | 0.651423E+09 | 1123.87 | 07-OCT-14:50 | 26.83 | 9.68 |
November | 0.145073E+10 | 4019.47 | 07-NOV-14:00 | 22.00 | 7.34 | 0.569468E+09 | 1044.56 | 25-NOV-15:09 | 13.50 | 4.91 |
December | 0.767062E+09 | 3879.21 | 09-DEC-10:43 | -2.0 | -4.1 | 0.570867E+09 | 1123.87 | 02-DEC-15:30 | -2.0 | -4.1 |
Annual Sum or Average | 0.322578E+11 | 0.766155E+10 | ||||||||
Minimum of Months | 0.721502E+09 | 3622.82 | -5.7 | -7.1 | 0.511332E+09 | 1044.56 | -5.0 | -5.0 | ||
Maximum of Months | 0.574292E+10 | 20243.00 | 28.67 | 13.07 | 0.739893E+09 | 1123.96 | 28.67 | 13.90 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.872231E+09 | 4521.50 | 16-JAN-11:43 | -5.3 | -5.3 | 0.569623E+09 | 1109.53 | 21-JAN-15:20 | 13.67 | 5.40 |
February | 0.670763E+09 | 4885.47 | 01-FEB-18:52 | -7.0 | -7.7 | 0.510434E+09 | 1123.84 | 18-FEB-15:20 | 18.67 | 7.82 |
March | 0.117372E+10 | 4227.56 | 14-MAR-13:00 | 24.00 | 7.90 | 0.615001E+09 | 1123.87 | 11-MAR-15:00 | 24.00 | 7.90 |
April | 0.940946E+09 | 3602.06 | 22-APR-08:62 | 0.00 | -0.1 | 0.592554E+09 | 1123.84 | 08-APR-14:09 | 0.00 | -0.1 |
May | 0.227686E+10 | 4661.84 | 17-MAY-14:10 | 28.67 | 11.73 | 0.700895E+09 | 1123.87 | 13-MAY-14:50 | 28.67 | 11.73 |
June | 0.514749E+10 | 17965.43 | 26-JUN-07:02 | 22.07 | 12.41 | 0.714883E+09 | 1123.93 | 03-JUN-14:00 | 22.07 | 12.41 |
July | 0.537884E+10 | 17323.47 | 18-JUL-07:02 | 24.33 | 12.85 | 0.719212E+09 | 1123.95 | 15-JUL-14:30 | 24.33 | 12.85 |
August | 0.566535E+10 | 18310.62 | 21-AUG-07:02 | 21.17 | 13.07 | 0.739884E+09 | 1123.96 | 05-AUG-14:39 | 21.17 | 13.07 |
September | 0.479586E+10 | 20035.12 | 11-SEP-07:02 | 20.63 | 10.22 | 0.699419E+09 | 1123.88 | 30-SEP-14:00 | 17.20 | 13.90 |
October | 0.239333E+10 | 6195.65 | 11-OCT-14:10 | 26.83 | 9.68 | 0.649893E+09 | 1123.87 | 07-OCT-14:30 | 26.83 | 9.68 |
November | 0.138005E+10 | 3882.45 | 07-NOV-14:00 | 22.00 | 7.34 | 0.567823E+09 | 1036.83 | 25-NOV-15:09 | 13.50 | 4.91 |
December | 0.719085E+09 | 4134.74 | 10-DEC-11:32 | -3.3 | -5.6 | 0.569878E+09 | 1123.87 | 02-DEC-15:09 | -3.3 | -5.6 |
Annual Sum or Average | 0.314145E+11 | 0.764950E+10 | ||||||||
Minimum of Months | 0.670763E+09 | 3602.06 | -7.0 | -7.7 | 0.510434E+09 | 1036.83 | -3.3 | -5.6 | ||
Maximum of Months | 0.566535E+10 | 20035.12 | 28.67 | 13.07 | 0.739884E+09 | 1123.96 | 28.67 | 13.90 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.694690E+09 | 4258.18 | 13-JAN-20:23 | -4.0 | -6.5 | 0.565809E+09 | 1081.73 | 21-JAN-15:20 | 13.67 | 5.40 |
February | 0.517938E+09 | 4325.35 | 09-FEB-18:33 | -4.3 | -6.6 | 0.508272E+09 | 1123.85 | 18-FEB-15:00 | 18.00 | 7.48 |
March | 0.991168E+09 | 3847.47 | 15-MAR-14:10 | 20.83 | 6.19 | 0.611493E+09 | 1123.87 | 11-MAR-15:00 | 20.83 | 6.19 |
April | 0.778369E+09 | 3268.21 | 01-APR-17:53 | 1.00 | 0.54 | 0.587845E+09 | 1123.85 | 08-APR-14:30 | 16.00 | 5.48 |
May | 0.202047E+10 | 4432.75 | 17-MAY-14:10 | 28.67 | 11.73 | 0.695588E+09 | 1123.87 | 13-MAY-14:20 | 28.67 | 11.73 |
June | 0.497216E+10 | 16138.49 | 27-JUN-07:02 | 22.47 | 9.00 | 0.714849E+09 | 1123.93 | 17-JUN-14:00 | 22.47 | 9.00 |
July | 0.522080E+10 | 17151.36 | 18-JUL-07:02 | 24.33 | 12.85 | 0.719185E+09 | 1123.95 | 15-JUL-14:30 | 24.33 | 12.85 |
August | 0.552002E+10 | 16926.82 | 20-AUG-08:62 | 23.50 | 14.21 | 0.739861E+09 | 1123.96 | 05-AUG-14:39 | 23.50 | 14.21 |
September | 0.464628E+10 | 18525.38 | 11-SEP-07:02 | 20.63 | 10.22 | 0.698820E+09 | 1123.88 | 30-SEP-14:00 | 17.20 | 13.90 |
October | 0.220367E+10 | 6036.84 | 11-OCT-14:10 | 26.83 | 9.68 | 0.645825E+09 | 1123.87 | 07-OCT-14:50 | 26.83 | 9.68 |
November | 0.120041E+10 | 4074.74 | 30-NOV-18:53 | -3.0 | -5.0 | 0.563988E+09 | 1015.76 | 25-NOV-15:09 | -3.0 | -5.0 |
December | 0.579540E+09 | 4294.64 | 08-DEC-20:03 | -4.2 | -6.0 | 0.567312E+09 | 1123.87 | 02-DEC-15:20 | -4.2 | -6.0 |
Annual Sum or Average | 0.293455E+11 | 0.761885E+10 | ||||||||
Minimum of Months | 0.517938E+09 | 3268.21 | -4.3 | -6.6 | 0.508272E+09 | 1015.76 | -4.2 | -6.0 | ||
Maximum of Months | 0.552002E+10 | 18525.38 | 28.67 | 14.21 | 0.739861E+09 | 1123.96 | 28.67 | 14.21 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342186E+09 | 2697.02 | 26-JAN-20:43 | 3.83 | 1.53 | 0.559557E+09 | 1023.49 | 21-JAN-15:20 | 3.83 | 1.53 |
February | 0.231914E+09 | 2982.40 | 23-FEB-19:33 | 2.33 | 1.70 | 0.504572E+09 | 1123.86 | 18-FEB-15:00 | 2.33 | 1.70 |
March | 0.645963E+09 | 3478.40 | 14-MAR-13:00 | 24.00 | 7.90 | 0.605623E+09 | 1123.84 | 11-MAR-15:20 | 24.00 | 7.90 |
April | 0.499114E+09 | 3164.32 | 14-APR-17:43 | 1.33 | 0.13 | 0.580304E+09 | 1092.47 | 08-APR-14:00 | 1.33 | 0.13 |
May | 0.162255E+10 | 4349.63 | 17-MAY-14:10 | 28.67 | 11.73 | 0.683700E+09 | 1123.87 | 06-MAY-14:09 | 28.67 | 11.73 |
June | 0.507469E+10 | 16746.83 | 25-JUN-08:62 | 28.08 | 13.27 | 0.714765E+09 | 1123.95 | 17-JUN-14:00 | 28.08 | 13.27 |
July | 0.532552E+10 | 16986.78 | 23-JUL-08:62 | 25.00 | 14.93 | 0.719158E+09 | 1123.95 | 15-JUL-14:20 | 25.00 | 14.93 |
August | 0.575610E+10 | 13040.34 | 20-AUG-08:62 | 23.50 | 14.21 | 0.739832E+09 | 1123.95 | 05-AUG-14:39 | 23.50 | 14.21 |
September | 0.474048E+10 | 12923.58 | 11-SEP-07:02 | 20.63 | 10.22 | 0.697576E+09 | 1123.89 | 09-SEP-14:09 | 20.63 | 10.22 |
October | 0.186843E+10 | 6083.35 | 11-OCT-14:10 | 26.83 | 9.68 | 0.638836E+09 | 1123.87 | 07-OCT-14:30 | 26.83 | 9.68 |
November | 0.831406E+09 | 3261.90 | 07-NOV-14:00 | 22.00 | 7.34 | 0.558065E+09 | 997.43 | 09-NOV-13:00 | 20.00 | 8.60 |
December | 0.305446E+09 | 2666.42 | 18-DEC-12:53 | 4.00 | -0.6 | 0.562960E+09 | 1123.87 | 02-DEC-15:30 | 4.00 | -0.6 |
Annual Sum or Average | 0.272438E+11 | 0.756495E+10 | ||||||||
Minimum of Months | 0.231914E+09 | 2666.42 | 1.33 | -0.6 | 0.504572E+09 | 997.43 | 1.33 | -0.6 | ||
Maximum of Months | 0.575610E+10 | 16986.78 | 28.67 | 14.93 | 0.739832E+09 | 1123.95 | 28.67 | 14.93 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144872E+10 | 62795.44 | 05-JAN-08:61 | -17.0 |
February | 0.219918E+10 | 62792.84 | 12-FEB-08:61 | -16.5 |
March | 0.147064E+10 | 62771.74 | 29-MAR-07:01 | -5.5 |
April | 0.912392E+09 | 62766.52 | 17-APR-07:01 | -5.5 |
May | 0.119832E+09 | 62734.40 | 03-MAY-07:01 | 4.33 |
June | 25985929.90 | 2053.45 | 25-JUN-07:04 | 25.87 |
July | 29014795.16 | 2144.22 | 18-JUL-07:04 | 24.33 |
August | 30741972.90 | 2072.90 | 03-AUG-07:04 | 21.33 |
September | 32600866.63 | 2199.15 | 13-SEP-07:04 | 20.18 |
October | 0.770637E+09 | 62780.29 | 31-OCT-07:01 | -9.0 |
November | 0.866275E+09 | 62778.97 | 29-NOV-08:61 | -9.8 |
December | 0.293060E+10 | 62803.89 | 22-DEC-08:61 | -20.0 |
Annual Sum or Average | 0.108366E+11 | |||
Minimum of Months | 25985929.90 | 2053.45 | -20.0 | |
Maximum of Months | 0.293060E+10 | 62803.89 | 25.87 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.353452E+09 | 33193.00 | 05-JAN-08:61 | -17.0 |
February | 0.562174E+09 | 33193.75 | 12-FEB-08:61 | -16.5 |
March | 0.300843E+09 | 33186.99 | 29-MAR-07:01 | -5.5 |
April | 0.180824E+09 | 33179.87 | 17-APR-07:01 | -5.5 |
May | 23417452.43 | 1432.10 | 03-MAY-07:01 | 4.33 |
June | 17702636.59 | 1255.88 | 27-JUN-07:04 | 22.47 |
July | 18433792.64 | 1230.00 | 18-JUL-07:04 | 24.33 |
August | 19814247.22 | 1229.47 | 21-AUG-07:04 | 21.17 |
September | 17968921.08 | 1286.47 | 13-SEP-07:04 | 20.18 |
October | 0.202576E+09 | 33187.93 | 31-OCT-07:01 | -9.0 |
November | 0.211493E+09 | 33187.24 | 29-NOV-08:61 | -9.8 |
December | 0.854167E+09 | 33203.78 | 22-DEC-08:61 | -20.0 |
Annual Sum or Average | 0.276287E+10 | |||
Minimum of Months | 17702636.59 | 1229.47 | -20.0 | |
Maximum of Months | 0.854167E+09 | 33203.78 | 24.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.504783E+09 | 34188.54 | 05-JAN-07:01 | -17.0 |
February | 0.773081E+09 | 34234.31 | 12-FEB-08:61 | -16.5 |
March | 0.435043E+09 | 34204.06 | 19-MAR-07:01 | -15.2 |
April | 0.299649E+09 | 34198.86 | 17-APR-06:01 | -7.7 |
May | 32020405.00 | 6692.00 | 03-MAY-06:03 | 2.33 |
June | 57038437.91 | 2440.41 | 26-JUN-19:02 | 35.03 |
July | 69758505.11 | 2294.39 | 16-JUL-16:02 | 34.33 |
August | 44882461.94 | 1637.03 | 26-AUG-17:12 | 30.67 |
September | 32739748.16 | 1819.03 | 10-SEP-16:02 | 31.92 |
October | 0.277147E+09 | 33816.42 | 31-OCT-06:01 | -9.0 |
November | 0.286827E+09 | 34015.62 | 30-NOV-07:01 | -11.3 |
December | 0.110114E+10 | 34236.26 | 24-DEC-08:61 | -15.7 |
Annual Sum or Average | 0.391411E+10 | |||
Minimum of Months | 32020405.00 | 1637.03 | -17.0 | |
Maximum of Months | 0.110114E+10 | 34236.26 | 35.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.582614E+09 | 34025.48 | 05-JAN-07:01 | -17.0 |
February | 0.857347E+09 | 34070.97 | 12-FEB-08:61 | -16.5 |
March | 0.499583E+09 | 34041.16 | 19-MAR-07:01 | -15.2 |
April | 0.350307E+09 | 34036.60 | 17-APR-06:01 | -7.7 |
May | 40491272.56 | 10401.06 | 02-MAY-06:03 | 0.17 |
June | 56734224.54 | 2438.69 | 26-JUN-19:02 | 35.03 |
July | 69219542.95 | 2292.75 | 16-JUL-16:02 | 34.33 |
August | 44664458.41 | 1634.29 | 26-AUG-17:12 | 30.67 |
September | 33193412.19 | 1817.94 | 10-SEP-16:02 | 31.92 |
October | 0.313441E+09 | 33657.83 | 31-OCT-06:01 | -9.0 |
November | 0.332434E+09 | 33854.48 | 30-NOV-07:01 | -11.3 |
December | 0.120199E+10 | 34073.04 | 24-DEC-08:61 | -15.7 |
Annual Sum or Average | 0.438202E+10 | |||
Minimum of Months | 33193412.19 | 1634.29 | -17.0 | |
Maximum of Months | 0.120199E+10 | 34073.04 | 35.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.694878E+09 | 34024.71 | 05-JAN-07:01 | -17.0 |
February | 0.100873E+10 | 34070.12 | 12-FEB-08:61 | -16.5 |
March | 0.620039E+09 | 34040.45 | 19-MAR-07:01 | -15.2 |
April | 0.425575E+09 | 34036.28 | 17-APR-06:01 | -7.7 |
May | 58517850.35 | 14376.72 | 02-MAY-06:03 | 0.17 |
June | 56616061.69 | 2445.52 | 26-JUN-19:02 | 35.03 |
July | 69831893.64 | 2298.74 | 16-JUL-16:02 | 34.33 |
August | 44785604.31 | 1640.64 | 26-AUG-17:12 | 30.67 |
September | 33682199.98 | 1824.03 | 10-SEP-16:02 | 31.92 |
October | 0.367168E+09 | 33657.35 | 31-OCT-06:01 | -9.0 |
November | 0.412875E+09 | 33853.92 | 30-NOV-07:01 | -11.3 |
December | 0.136891E+10 | 34072.38 | 24-DEC-08:61 | -15.7 |
Annual Sum or Average | 0.516161E+10 | |||
Minimum of Months | 33682199.98 | 1640.64 | -17.0 | |
Maximum of Months | 0.136891E+10 | 34072.38 | 35.03 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159365E+10 | 60125.96 | 05-JAN-08:61 | -17.0 |
February | 0.221009E+10 | 60124.53 | 06-FEB-08:61 | -7.5 |
March | 0.142739E+10 | 60116.02 | 29-MAR-07:01 | -5.5 |
April | 0.100896E+10 | 60113.92 | 17-APR-07:01 | -5.5 |
May | 0.136970E+09 | 60080.77 | 03-MAY-07:01 | 4.33 |
June | 61808506.01 | 3993.84 | 25-JUN-16:02 | 32.70 |
July | 95717282.84 | 4616.34 | 16-JUL-16:02 | 34.33 |
August | 55071309.65 | 3257.05 | 26-AUG-17:02 | 30.83 |
September | 61666975.79 | 3662.76 | 10-SEP-16:02 | 31.92 |
October | 0.826922E+09 | 60120.51 | 31-OCT-07:01 | -9.0 |
November | 0.945729E+09 | 60116.99 | 29-NOV-08:61 | -9.8 |
December | 0.294063E+10 | 60137.61 | 22-DEC-08:61 | -20.0 |
Annual Sum or Average | 0.113646E+11 | |||
Minimum of Months | 55071309.65 | 3257.05 | -20.0 | |
Maximum of Months | 0.294063E+10 | 60137.61 | 34.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.947186E+09 | 30590.58 | 05-JAN-08:61 | -17.0 |
February | 0.127066E+10 | 30589.18 | 06-FEB-08:61 | -7.5 |
March | 0.857671E+09 | 30584.88 | 29-MAR-07:01 | -5.5 |
April | 0.609130E+09 | 30584.24 | 17-APR-07:01 | -5.5 |
May | 80289143.94 | 30564.94 | 03-MAY-07:01 | 4.33 |
June | 31953504.77 | 2013.08 | 25-JUN-16:02 | 32.70 |
July | 49249179.17 | 2322.95 | 16-JUL-16:02 | 34.33 |
August | 28341576.97 | 1648.93 | 26-AUG-17:02 | 30.83 |
September | 32646264.55 | 1846.53 | 10-SEP-16:02 | 31.92 |
October | 0.482777E+09 | 30586.89 | 30-OCT-07:01 | -10.0 |
November | 0.565299E+09 | 30584.85 | 29-NOV-08:61 | -9.8 |
December | 0.168106E+10 | 30597.47 | 22-DEC-08:61 | -20.0 |
Annual Sum or Average | 0.663627E+10 | |||
Minimum of Months | 28341576.97 | 1648.93 | -20.0 | |
Maximum of Months | 0.168106E+10 | 30597.47 | 34.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101836E+10 | 30466.80 | 05-JAN-08:61 | -17.0 |
February | 0.132742E+10 | 30465.76 | 06-FEB-08:61 | -7.5 |
March | 0.913681E+09 | 30461.37 | 29-MAR-07:01 | -5.5 |
April | 0.650862E+09 | 30460.79 | 17-APR-07:01 | -5.5 |
May | 85805001.57 | 30440.22 | 03-MAY-07:01 | 4.33 |
June | 32098919.14 | 2014.18 | 25-JUN-16:02 | 32.70 |
July | 49173619.95 | 2323.97 | 16-JUL-16:02 | 34.33 |
August | 28022374.96 | 1650.04 | 26-AUG-17:02 | 30.83 |
September | 32732411.25 | 1847.44 | 10-SEP-16:02 | 31.92 |
October | 0.504620E+09 | 30463.19 | 30-OCT-07:01 | -10.0 |
November | 0.598794E+09 | 30461.13 | 29-NOV-08:61 | -9.8 |
December | 0.174228E+10 | 30474.05 | 22-DEC-08:61 | -20.0 |
Annual Sum or Average | 0.698385E+10 | |||
Minimum of Months | 28022374.96 | 1650.04 | -20.0 | |
Maximum of Months | 0.174228E+10 | 30474.05 | 34.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127341E+10 | 30302.99 | 05-JAN-08:61 | -17.0 |
February | 0.158052E+10 | 30297.86 | 06-FEB-08:61 | -7.5 |
March | 0.113664E+10 | 30297.19 | 29-MAR-07:01 | -5.5 |
April | 0.841509E+09 | 30295.88 | 17-APR-07:01 | -5.5 |
May | 0.106176E+09 | 30278.59 | 03-MAY-07:01 | 4.33 |
June | 32605109.04 | 2017.30 | 25-JUN-16:02 | 32.70 |
July | 47426252.14 | 2325.73 | 16-JUL-16:02 | 34.33 |
August | 26383409.45 | 1652.35 | 26-AUG-17:02 | 30.83 |
September | 33762954.14 | 1849.24 | 10-SEP-16:02 | 31.92 |
October | 0.591644E+09 | 30299.52 | 30-OCT-07:01 | -10.0 |
November | 0.744823E+09 | 30297.46 | 29-NOV-08:61 | -9.8 |
December | 0.200389E+10 | 30305.13 | 22-DEC-08:61 | -20.0 |
Annual Sum or Average | 0.841879E+10 | |||
Minimum of Months | 26383409.45 | 1652.35 | -20.0 | |
Maximum of Months | 0.200389E+10 | 30305.13 | 34.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255800E+10 | 31828.70 | 06-JAN-08:61 | -6.5 |
February | 0.305718E+10 | 31944.58 | 06-FEB-08:61 | -7.5 |
March | 0.230841E+10 | 31856.02 | 19-MAR-08:61 | -13.0 |
April | 0.180209E+10 | 31786.62 | 03-APR-07:01 | -5.8 |
May | 0.204499E+09 | 31756.95 | 03-MAY-07:01 | 4.33 |
June | 35768684.76 | 2020.88 | 25-JUN-16:02 | 32.70 |
July | 47155392.57 | 2314.61 | 16-JUL-16:02 | 34.33 |
August | 22194502.14 | 1651.68 | 26-AUG-17:02 | 30.83 |
September | 44062284.32 | 15532.00 | 22-SEP-07:03 | 0.37 |
October | 0.104191E+10 | 31786.75 | 31-OCT-07:01 | -9.0 |
November | 0.146185E+10 | 31785.60 | 29-NOV-08:61 | -9.8 |
December | 0.361731E+10 | 31976.27 | 21-DEC-08:61 | -20.0 |
Annual Sum or Average | 0.162004E+11 | |||
Minimum of Months | 22194502.14 | 1651.68 | -20.0 | |
Maximum of Months | 0.361731E+10 | 31976.27 | 34.33 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.986629E+10 | 6035.26 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.891946E+10 | 6035.26 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.987658E+10 | 6035.26 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.956097E+10 | 6035.26 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.986629E+10 | 6035.26 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.956097E+10 | 6035.26 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.987658E+10 | 6035.26 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.986629E+10 | 6035.26 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.957126E+10 | 6035.26 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.986629E+10 | 6035.26 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.953010E+10 | 6035.26 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.988687E+10 | 6035.26 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.116248E+12 | 0.262491E+11 | ||||
Minimum of Months | 0.891946E+10 | 6035.26 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.988687E+10 | 6035.26 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.579394E+10 | 3544.17 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.523792E+10 | 3544.17 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.579999E+10 | 3544.17 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.561464E+10 | 3544.17 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.579394E+10 | 3544.17 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.561464E+10 | 3544.17 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.579999E+10 | 3544.17 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.579394E+10 | 3544.17 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.562069E+10 | 3544.17 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.579394E+10 | 3544.17 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.559651E+10 | 3544.17 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.580603E+10 | 3544.17 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.682662E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.523792E+10 | 3544.17 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.580603E+10 | 3544.17 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.413753E+10 | 3181.37 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.374692E+10 | 3181.37 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.422433E+10 | 3181.37 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.401456E+10 | 3181.37 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.418093E+10 | 3181.37 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.407966E+10 | 3181.37 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.411583E+10 | 3181.37 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.422433E+10 | 3181.37 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.401456E+10 | 3181.37 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.413753E+10 | 3181.37 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.401456E+10 | 3181.37 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.411583E+10 | 3181.37 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.490066E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.374692E+10 | 3181.37 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.422433E+10 | 3181.37 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.413753E+10 | 3181.37 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.374692E+10 | 3181.37 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.422433E+10 | 3181.37 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.401456E+10 | 3181.37 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.418093E+10 | 3181.37 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.407966E+10 | 3181.37 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.411583E+10 | 3181.37 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.422433E+10 | 3181.37 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.401456E+10 | 3181.37 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.413753E+10 | 3181.37 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.401456E+10 | 3181.37 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.411583E+10 | 3181.37 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.490066E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.374692E+10 | 3181.37 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.422433E+10 | 3181.37 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.413753E+10 | 3181.37 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.374692E+10 | 3181.37 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.422433E+10 | 3181.37 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.401456E+10 | 3181.37 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.418093E+10 | 3181.37 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.407966E+10 | 3181.37 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.411583E+10 | 3181.37 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.422433E+10 | 3181.37 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.401456E+10 | 3181.37 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.413753E+10 | 3181.37 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.401456E+10 | 3181.37 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.411583E+10 | 3181.37 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.490066E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.374692E+10 | 3181.37 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.422433E+10 | 3181.37 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.457032E+10 | 3825.14 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.413982E+10 | 3825.14 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.467469E+10 | 3825.14 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.443552E+10 | 3825.14 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.462251E+10 | 3825.14 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.451379E+10 | 3825.14 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.454423E+10 | 3825.14 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.467469E+10 | 3825.14 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.443552E+10 | 3825.14 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.457032E+10 | 3825.14 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.443552E+10 | 3825.14 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.454423E+10 | 3825.14 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.541612E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.413982E+10 | 3825.14 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.467469E+10 | 3825.14 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.234642E+10 | 1963.83 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.212540E+10 | 1963.83 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.240000E+10 | 1963.83 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.227721E+10 | 1963.83 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.237321E+10 | 1963.83 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.231740E+10 | 1963.83 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.233302E+10 | 1963.83 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.240000E+10 | 1963.83 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.227721E+10 | 1963.83 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.234642E+10 | 1963.83 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.227721E+10 | 1963.83 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.233302E+10 | 1963.83 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.278065E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.212540E+10 | 1963.83 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.240000E+10 | 1963.83 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.986629E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384091E+10 |
February | 0.305697E+10 | 0.891946E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407226E+10 |
March | 0.335708E+10 | 0.987658E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14988.76 | 0.362675E+10 |
April | 0.327081E+10 | 0.956097E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334441E+10 |
May | 0.336680E+10 | 0.986629E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62243837.49 | 0.158449E+10 |
June | 0.325380E+10 | 0.956097E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.858695E+09 | 0.370209E+09 |
July | 0.339353E+10 | 0.987658E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913722E+09 | 0.372298E+09 |
August | 0.334857E+10 | 0.986629E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778289E+09 | 0.416108E+09 |
September | 0.327932E+10 | 0.957126E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424057E+09 | 0.781835E+09 |
October | 0.338624E+10 | 0.986629E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11031803.90 | 0.298439E+10 |
November | 0.327446E+10 | 0.953010E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354523E+10 |
December | 0.340325E+10 | 0.988687E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506522E+10 |
Annual Sum or Average | 0.397770E+11 | 0.116248E+12 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304805E+10 | 0.300041E+11 |
Minimum of Months | 0.305697E+10 | 0.891946E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370209E+09 |
Maximum of Months | 0.340325E+10 | 0.988687E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913722E+09 | 0.506522E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.579394E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200405E+10 |
February | 0.152844E+10 | 0.523792E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204322E+10 |
March | 0.167849E+10 | 0.579999E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.175984E+10 |
April | 0.163536E+10 | 0.561464E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160847E+10 |
May | 0.168335E+10 | 0.579394E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33847368.31 | 0.737435E+09 |
June | 0.162685E+10 | 0.561464E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463433E+09 | 0.133621E+09 |
July | 0.169671E+10 | 0.579999E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493049E+09 | 0.135615E+09 |
August | 0.167424E+10 | 0.579394E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422701E+09 | 0.157758E+09 |
September | 0.163961E+10 | 0.562069E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231134E+09 | 0.323799E+09 |
October | 0.169307E+10 | 0.579394E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.146483E+10 |
November | 0.163718E+10 | 0.559651E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181011E+10 |
December | 0.170157E+10 | 0.580603E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248413E+10 |
Annual Sum or Average | 0.198880E+11 | 0.682662E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165020E+10 | 0.146629E+11 |
Minimum of Months | 0.152844E+10 | 0.523792E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133621E+09 |
Maximum of Months | 0.170157E+10 | 0.580603E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493049E+09 | 0.248413E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202478E+10 |
February | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208983E+10 |
March | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.180468E+10 |
April | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166346E+10 |
May | 0.102058E+10 | 0.418093E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33842329.39 | 0.771014E+09 |
June | 0.998711E+09 | 0.407966E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456835E+09 | 0.157892E+09 |
July | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482844E+09 | 0.157084E+09 |
August | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418515E+09 | 0.180475E+09 |
September | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224715E+09 | 0.353943E+09 |
October | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.150992E+10 |
November | 0.973196E+09 | 0.401456E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182806E+10 |
December | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255642E+10 |
Annual Sum or Average | 0.119700E+11 | 0.490066E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162279E+10 | 0.150976E+11 |
Minimum of Months | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157084E+09 |
Maximum of Months | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482844E+09 | 0.255642E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201753E+10 |
February | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208178E+10 |
March | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.179741E+10 |
April | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165496E+10 |
May | 0.102058E+10 | 0.418093E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33842373.82 | 0.766160E+09 |
June | 0.998711E+09 | 0.407966E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456812E+09 | 0.158098E+09 |
July | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482771E+09 | 0.157556E+09 |
August | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418511E+09 | 0.180748E+09 |
September | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224694E+09 | 0.353634E+09 |
October | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.150500E+10 |
November | 0.973196E+09 | 0.401456E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181939E+10 |
December | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254742E+10 |
Annual Sum or Average | 0.119700E+11 | 0.490066E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162267E+10 | 0.150397E+11 |
Minimum of Months | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157556E+09 |
Maximum of Months | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482771E+09 | 0.254742E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200890E+10 |
February | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207423E+10 |
March | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.178871E+10 |
April | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164409E+10 |
May | 0.102058E+10 | 0.418093E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33842462.68 | 0.758113E+09 |
June | 0.998711E+09 | 0.407966E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456966E+09 | 0.156158E+09 |
July | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483005E+09 | 0.155635E+09 |
August | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418582E+09 | 0.178907E+09 |
September | 0.984131E+09 | 0.401456E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224770E+09 | 0.350900E+09 |
October | 0.100722E+10 | 0.413753E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.149765E+10 |
November | 0.973196E+09 | 0.401456E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180887E+10 |
December | 0.100600E+10 | 0.411583E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253794E+10 |
Annual Sum or Average | 0.119700E+11 | 0.490066E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162320E+10 | 0.149601E+11 |
Minimum of Months | 0.914877E+09 | 0.374692E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155635E+09 |
Maximum of Months | 0.103395E+10 | 0.422433E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483005E+09 | 0.253794E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.457032E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363659E+10 |
February | 0.313522E+10 | 0.413982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379411E+10 |
March | 0.355148E+10 | 0.467469E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14786.40 | 0.328991E+10 |
April | 0.338259E+10 | 0.443552E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302210E+10 |
May | 0.349753E+10 | 0.462251E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60868032.04 | 0.139003E+10 |
June | 0.343071E+10 | 0.451379E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824096E+09 | 0.300141E+09 |
July | 0.344942E+10 | 0.454423E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.871256E+09 | 0.299795E+09 |
August | 0.355148E+10 | 0.467469E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753802E+09 | 0.344220E+09 |
September | 0.338259E+10 | 0.443552E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404616E+09 | 0.667253E+09 |
October | 0.344359E+10 | 0.457032E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10835055.43 | 0.274751E+10 |
November | 0.331698E+10 | 0.443552E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328556E+10 |
December | 0.344942E+10 | 0.454423E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465874E+10 |
Annual Sum or Average | 0.410346E+11 | 0.541612E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292549E+10 | 0.274359E+11 |
Minimum of Months | 0.313522E+10 | 0.413982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299795E+09 |
Maximum of Months | 0.355148E+10 | 0.467469E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.871256E+09 | 0.465874E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200003E+10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207404E+10 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.178805E+10 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163618E+10 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33842731.47 | 0.746474E+09 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457962E+09 | 0.154559E+09 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484252E+09 | 0.154592E+09 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419142E+09 | 0.179089E+09 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225131E+09 | 0.352444E+09 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.149536E+10 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179963E+10 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253933E+10 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162637E+10 | 0.149198E+11 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154559E+09 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484252E+09 | 0.253933E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199621E+10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207117E+10 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.178418E+10 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163106E+10 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33842766.18 | 0.741489E+09 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458038E+09 | 0.153874E+09 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484353E+09 | 0.153940E+09 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419171E+09 | 0.178496E+09 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225164E+09 | 0.351335E+09 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.149166E+10 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179591E+10 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253593E+10 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162660E+10 | 0.148853E+11 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153874E+09 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484353E+09 | 0.253593E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198628E+10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206230E+10 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.177218E+10 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161619E+10 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33842849.59 | 0.726949E+09 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458221E+09 | 0.151753E+09 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484553E+09 | 0.151942E+09 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419222E+09 | 0.176797E+09 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225218E+09 | 0.348183E+09 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.148109E+10 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178611E+10 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252510E+10 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162709E+10 | 0.147849E+11 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151753E+09 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484553E+09 | 0.252510E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227583E+10 |
February | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252632E+10 |
March | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8433.60 | 0.226426E+10 |
April | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210677E+10 |
May | 0.174872E+10 | 0.237321E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35209692.98 | 0.978534E+09 |
June | 0.171530E+10 | 0.231740E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483312E+09 | 0.279758E+09 |
July | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510548E+09 | 0.277630E+09 |
August | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436852E+09 | 0.309247E+09 |
September | 0.169125E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233301E+09 | 0.558284E+09 |
October | 0.172174E+10 | 0.234642E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6224638.93 | 0.187158E+10 |
November | 0.165844E+10 | 0.227721E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213432E+10 |
December | 0.172466E+10 | 0.233302E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319805E+10 |
Annual Sum or Average | 0.205167E+11 | 0.278065E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170546E+10 | 0.187806E+11 |
Minimum of Months | 0.156756E+10 | 0.212540E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277630E+09 |
Maximum of Months | 0.177569E+10 | 0.240000E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510548E+09 | 0.319805E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 6035.26 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 10692.65 | 05-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 6035.26 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 9042.84 | 11-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 6035.26 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.98 | 14-MAR-13:00 | 8386.82 | 04-MAR-13:00 |
April | 4050.04 | 01-APR-12:09 | 6035.26 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 6954.34 | 16-APR-15:30 |
May | 4050.04 | 05-MAY-12:09 | 6035.26 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1251.05 | 17-MAY-13:00 | 3842.85 | 26-MAY-11:05 |
June | 4050.04 | 02-JUN-12:09 | 6035.26 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3669.00 | 26-JUN-15:00 | 2016.29 | 02-JUN-15:00 |
July | 4050.04 | 01-JUL-12:09 | 6035.26 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3092.85 | 16-JUL-13:00 | 1777.14 | 19-JUL-16:00 |
August | 4050.04 | 04-AUG-12:09 | 6035.26 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3091.41 | 16-AUG-14:00 | 2079.24 | 29-AUG-16:00 |
September | 4050.04 | 01-SEP-12:09 | 6035.26 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2110.22 | 10-SEP-13:00 | 5629.75 | 21-SEP-16:00 |
October | 4050.04 | 01-OCT-12:09 | 6035.26 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 758.05 | 11-OCT-14:00 | 8111.92 | 31-OCT-15:00 |
November | 4050.04 | 03-NOV-12:09 | 6035.26 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 9331.47 | 29-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 6035.26 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 12802.01 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1777.14 | |||||
Maximum of Months | 4050.04 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3669.00 | 12802.01 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3544.17 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 3544.17 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4990.43 | 11-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 3544.17 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2024.96 | 01-APR-12:09 | 3544.17 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3707.84 | 02-APR-13:00 |
May | 2024.96 | 05-MAY-12:09 | 3544.17 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 2156.63 | 26-MAY-11:05 |
June | 2024.96 | 02-JUN-12:09 | 3544.17 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.36 | 26-JUN-15:00 | 1093.60 | 02-JUN-15:00 |
July | 2024.96 | 01-JUL-12:09 | 3544.17 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.47 | 16-JUL-13:00 | 963.88 | 19-JUL-16:00 |
August | 2024.96 | 04-AUG-12:09 | 3544.17 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.56 | 16-AUG-14:00 | 1117.38 | 29-AUG-16:00 |
September | 2024.96 | 01-SEP-12:09 | 3544.17 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.05 | 10-SEP-13:00 | 3129.73 | 21-SEP-16:00 |
October | 2024.96 | 01-OCT-12:09 | 3544.17 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2024.96 | 03-NOV-12:09 | 3544.17 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 5137.04 | 29-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 3544.17 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3544.17 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 963.88 | |||||
Maximum of Months | 2024.96 | 3544.17 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.36 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3181.37 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 3181.37 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4990.43 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3181.37 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2024.96 | 01-APR-12:09 | 3181.37 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3707.84 | 02-APR-13:00 |
May | 2024.96 | 06-MAY-12:09 | 3181.37 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 2153.51 | 26-MAY-11:05 |
June | 2024.96 | 03-JUN-12:09 | 3181.37 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.37 | 26-JUN-15:00 | 1093.59 | 02-JUN-15:00 |
July | 2024.96 | 01-JUL-12:09 | 3181.37 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.51 | 16-JUL-13:00 | 1114.16 | 30-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 3181.37 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.58 | 16-AUG-14:00 | 1117.38 | 29-AUG-16:00 |
September | 2024.96 | 02-SEP-12:09 | 3181.37 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.09 | 10-SEP-13:00 | 3112.82 | 21-SEP-16:00 |
October | 2024.96 | 07-OCT-12:09 | 3181.37 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2024.96 | 04-NOV-12:09 | 3181.37 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 5137.04 | 29-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 3181.37 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.59 | |||||
Maximum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.37 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3181.37 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 3181.37 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4990.43 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3181.37 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2024.96 | 01-APR-12:09 | 3181.37 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3707.84 | 02-APR-13:00 |
May | 2024.96 | 06-MAY-12:09 | 3181.37 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 2148.39 | 26-MAY-11:05 |
June | 2024.96 | 03-JUN-12:09 | 3181.37 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.37 | 26-JUN-15:00 | 1093.59 | 02-JUN-15:00 |
July | 2024.96 | 01-JUL-12:09 | 3181.37 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.50 | 16-JUL-13:00 | 1111.71 | 30-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 3181.37 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.58 | 16-AUG-14:00 | 1117.38 | 29-AUG-16:00 |
September | 2024.96 | 02-SEP-12:09 | 3181.37 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.08 | 10-SEP-13:00 | 3108.07 | 21-SEP-16:00 |
October | 2024.96 | 07-OCT-12:09 | 3181.37 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2024.96 | 04-NOV-12:09 | 3181.37 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 5137.04 | 29-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 3181.37 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.59 | |||||
Maximum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.37 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 3181.37 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 3181.37 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4990.43 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 3181.37 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2024.96 | 01-APR-12:09 | 3181.37 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3707.84 | 02-APR-13:00 |
May | 2024.96 | 06-MAY-12:09 | 3181.37 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 2124.54 | 26-MAY-11:05 |
June | 2024.96 | 03-JUN-12:09 | 3181.37 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.37 | 26-JUN-15:00 | 1093.59 | 02-JUN-15:00 |
July | 2024.96 | 01-JUL-12:09 | 3181.37 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.51 | 16-JUL-13:00 | 1101.38 | 30-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 3181.37 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.58 | 16-AUG-14:00 | 1117.38 | 29-AUG-16:00 |
September | 2024.96 | 02-SEP-12:09 | 3181.37 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.10 | 10-SEP-13:00 | 3092.59 | 21-SEP-16:00 |
October | 2024.96 | 07-OCT-12:09 | 3181.37 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2024.96 | 04-NOV-12:09 | 3181.37 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 5137.04 | 29-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 3181.37 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.59 | |||||
Maximum of Months | 2024.96 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.37 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3825.14 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 10621.64 | 05-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 3825.14 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 8959.29 | 11-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3825.14 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.64 | 14-MAR-13:00 | 8255.99 | 04-MAR-13:00 |
April | 5400.05 | 01-APR-14:09 | 3825.14 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 6670.90 | 02-APR-13:00 |
May | 5400.05 | 06-MAY-14:09 | 3825.14 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1223.82 | 17-MAY-13:00 | 3703.60 | 26-MAY-11:05 |
June | 5400.05 | 03-JUN-14:09 | 3825.14 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3596.61 | 26-JUN-15:00 | 1967.50 | 02-JUN-15:00 |
July | 5400.05 | 01-JUL-14:09 | 3825.14 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3051.14 | 16-JUL-13:00 | 1900.25 | 30-JUL-17:00 |
August | 5400.05 | 05-AUG-14:09 | 3825.14 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3043.21 | 16-AUG-14:00 | 2012.58 | 29-AUG-16:00 |
September | 5400.05 | 02-SEP-14:09 | 3825.14 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2077.38 | 10-SEP-13:00 | 5480.08 | 21-SEP-16:00 |
October | 5400.05 | 07-OCT-14:09 | 3825.14 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 743.09 | 11-OCT-14:00 | 7915.73 | 31-OCT-15:00 |
November | 5400.05 | 04-NOV-14:09 | 3825.14 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 9225.27 | 29-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 3825.14 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 12441.64 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1900.25 | |||||
Maximum of Months | 5400.05 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3596.61 | 12441.64 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4990.43 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3707.84 | 02-APR-13:00 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 2046.90 | 26-MAY-11:05 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.36 | 26-JUN-15:00 | 1093.58 | 02-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.49 | 16-JUL-13:00 | 1051.90 | 30-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.57 | 16-AUG-14:00 | 1117.35 | 29-AUG-16:00 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.08 | 10-SEP-13:00 | 3047.23 | 21-SEP-16:00 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 5137.04 | 29-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1051.90 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.36 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4990.43 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3707.84 | 02-APR-13:00 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 2030.50 | 26-MAY-11:05 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.36 | 26-JUN-15:00 | 1093.58 | 02-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.49 | 16-JUL-13:00 | 1047.46 | 30-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.57 | 16-AUG-14:00 | 1117.35 | 29-AUG-16:00 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.08 | 10-SEP-13:00 | 3045.86 | 21-SEP-16:00 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 5137.04 | 29-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1047.46 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.36 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4990.43 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3707.84 | 02-APR-13:00 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 1987.34 | 26-MAY-11:05 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.36 | 26-JUN-15:00 | 1093.58 | 02-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.49 | 16-JUL-13:00 | 1037.27 | 30-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.58 | 16-AUG-14:00 | 1117.35 | 29-AUG-16:00 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.08 | 10-SEP-13:00 | 3044.24 | 21-SEP-16:00 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 5137.04 | 29-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1037.27 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.36 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1963.83 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5989.55 | 05-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1963.83 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5073.99 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1963.83 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 14-MAR-13:00 | 4725.37 | 04-MAR-13:00 |
April | 2699.95 | 01-APR-14:09 | 1963.83 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3989.46 | 16-APR-15:00 |
May | 2699.95 | 06-MAY-14:09 | 1963.83 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 707.70 | 17-MAY-13:00 | 2064.36 | 02-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1963.83 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2072.75 | 26-JUN-15:00 | 1142.34 | 02-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1963.83 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1740.24 | 16-JUL-13:00 | 1061.97 | 30-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1963.83 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1741.79 | 16-AUG-14:00 | 1183.97 | 29-AUG-16:00 |
September | 2699.95 | 02-SEP-14:09 | 1963.83 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1188.99 | 10-SEP-13:00 | 3177.34 | 21-SEP-16:00 |
October | 2699.95 | 07-OCT-14:09 | 1963.83 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 428.25 | 11-OCT-14:00 | 4595.92 | 31-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1963.83 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 5243.24 | 29-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1963.83 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7271.71 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1061.97 | |||||
Maximum of Months | 2699.95 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2072.75 | 7271.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13148.01 | 06-JAN-00:01 | 2362.52 | 2223.38 | 5223.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.29 |
February | 10055.08 | 10-FEB-00:02 | 1687.52 | 1588.13 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.01 |
March | 10524.92 | 04-MAR-23:52 | 6750.06 | 30176.29 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.96 |
April | 7535.50 | 14-APR-23:25 | 675.01 | 6352.88 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.60 |
May | 10693.49 | 31-MAY-16:10 | 3375.03 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 970.07 | 0.00 |
June | 34383.17 | 27-JUN-07:02 | 1687.52 | 1588.13 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.29 |
July | 35687.31 | 18-JUL-07:02 | 1687.52 | 1588.13 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 | 0.00 |
August | 34486.44 | 03-AUG-07:02 | 1687.52 | 1588.13 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.52 |
September | 38530.36 | 13-SEP-07:02 | 1687.52 | 1588.13 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.41 |
October | 13104.61 | 11-OCT-14:00 | 2700.03 | 6035.26 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 758.05 | 0.00 |
November | 12535.28 | 29-NOV-22:32 | 12150.11 | 36211.55 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.94 |
December | 14881.80 | 22-DEC-00:01 | 2700.03 | 2541.00 | 5970.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7535.50 | 675.01 | 1588.13 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38530.36 | 12150.11 | 36211.55 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 970.07 | 542.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4346.02 | 20-JAN-14:00 | 2024.96 | 3544.17 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.72 |
February | 4113.93 | 04-FEB-10:13 | 1349.97 | 14176.70 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.60 |
March | 17216.73 | 12-MAR-17:27 | 12149.77 | 21265.05 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.33 |
April | 4177.72 | 20-APR-13:00 | 1349.97 | 3544.17 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.74 |
May | 17269.87 | 13-MAY-18:07 | 11812.27 | 24809.22 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.57 |
June | 20622.55 | 27-JUN-07:02 | 843.73 | 932.68 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.88 |
July | 19635.55 | 19-JUL-07:02 | 843.73 | 932.68 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.09 |
August | 19685.78 | 21-AUG-07:02 | 843.73 | 932.68 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.89 |
September | 21603.75 | 13-SEP-07:02 | 843.73 | 932.68 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.30 |
October | 17669.67 | 08-OCT-17:07 | 12149.77 | 21265.05 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.55 |
November | 5665.16 | 07-NOV-14:30 | 1349.97 | 3544.17 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.60 |
December | 6371.67 | 22-DEC-11:52 | 2024.96 | 21265.05 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 849.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4113.93 | 843.73 | 932.68 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.88 | |
Maximum of Months | 21603.75 | 12149.77 | 24809.22 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 849.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4405.46 | 04-JAN-10:13 | 1349.97 | 12725.50 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575.38 |
February | 6056.64 | 11-FEB-18:42 | 843.73 | 8372.04 | 1865.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 720.36 |
March | 5457.47 | 14-MAR-13:00 | 1349.97 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 0.00 |
April | 3856.12 | 22-APR-07:02 | 843.73 | 8372.04 | 1865.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.05 |
May | 5631.99 | 17-MAY-13:00 | 1349.97 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 0.00 |
June | 22696.62 | 27-JUN-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.81 |
July | 22221.29 | 18-JUL-06:02 | 0.00 | 1004.64 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.62 |
August | 22185.20 | 21-AUG-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.39 |
September | 23691.20 | 11-SEP-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.58 |
October | 6958.71 | 11-OCT-14:00 | 1012.48 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 0.00 |
November | 5266.32 | 07-NOV-14:00 | 1349.97 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.43 |
December | 7046.62 | 19-DEC-20:02 | 1012.48 | 10046.44 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3856.12 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23691.20 | 1349.97 | 12725.50 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 720.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5929.35 | 04-JAN-19:12 | 3374.94 | 15906.87 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 719.41 |
February | 3923.43 | 28-FEB-08:61 | 1349.97 | 13395.26 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.81 |
March | 5346.10 | 14-MAR-13:00 | 1349.97 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 0.00 |
April | 3834.32 | 22-APR-07:02 | 843.73 | 8372.04 | 1865.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.92 |
May | 5575.67 | 17-MAY-13:00 | 1349.97 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 0.00 |
June | 23121.78 | 27-JUN-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.89 |
July | 22136.78 | 18-JUL-06:02 | 0.00 | 1004.64 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.80 |
August | 22496.43 | 21-AUG-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.48 |
September | 24576.04 | 11-SEP-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.60 |
October | 6917.61 | 11-OCT-14:00 | 1012.48 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 0.00 |
November | 5078.50 | 07-NOV-14:00 | 1349.97 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.43 |
December | 4186.94 | 18-DEC-08:61 | 1349.97 | 13395.26 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3834.32 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24576.04 | 3374.94 | 15906.87 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 719.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3924.35 | 03-JAN-09:02 | 1349.97 | 12725.50 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.03 |
February | 3848.25 | 28-FEB-08:61 | 1349.97 | 13395.26 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.14 |
March | 5090.79 | 14-MAR-13:00 | 1349.97 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 0.00 |
April | 3779.97 | 22-APR-07:02 | 843.73 | 8372.04 | 1865.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.87 |
May | 5367.36 | 17-MAY-13:00 | 1349.97 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 0.00 |
June | 21698.31 | 27-JUN-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.77 |
July | 22009.43 | 18-JUL-06:02 | 0.00 | 1004.64 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 |
August | 21477.25 | 21-AUG-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.36 |
September | 23308.75 | 11-SEP-06:02 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.56 |
October | 6751.20 | 11-OCT-14:00 | 1012.48 | 3181.37 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 0.00 |
November | 4916.53 | 28-NOV-20:23 | 674.99 | 6697.63 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.39 |
December | 4123.07 | 18-DEC-08:61 | 1349.97 | 13395.26 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3779.97 | 0.00 | 837.20 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23308.75 | 1349.97 | 13395.26 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 498.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6147.05 | 22-JAN-10:03 | 2227.52 | 6039.66 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 739.37 |
February | 7461.51 | 14-FEB-20:42 | 2970.03 | 8052.88 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.20 |
March | 8688.68 | 14-MAR-13:00 | 4792.55 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 24.64 | 0.00 |
April | 7370.34 | 22-APR-08:62 | 2970.03 | 8052.88 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 878.72 |
May | 9226.58 | 17-MAY-14:10 | 4657.54 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1145.96 | 0.00 |
June | 36875.35 | 26-JUN-07:02 | 0.00 | 1006.52 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.48 |
July | 34232.44 | 19-JUL-07:02 | 0.00 | 1006.52 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.37 |
August | 36493.42 | 21-AUG-07:02 | 0.00 | 1006.52 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.57 |
September | 39333.64 | 11-SEP-07:02 | 0.00 | 1006.52 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.39 |
October | 12083.00 | 11-OCT-14:10 | 4657.54 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 704.33 | 0.00 |
November | 7847.21 | 07-NOV-14:00 | 4792.55 | 3825.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.52 |
December | 7069.48 | 05-DEC-09:03 | 2227.52 | 6039.66 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 887.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6147.05 | 0.00 | 1006.52 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39333.64 | 4792.55 | 8052.88 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1145.96 | 887.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4577.24 | 16-JAN-11:32 | 1484.97 | 7855.30 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.23 |
February | 4475.16 | 09-FEB-19:03 | 3509.93 | 7855.30 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 555.76 |
March | 4451.48 | 27-MAR-19:42 | 1484.97 | 4134.37 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.94 |
April | 3622.82 | 22-APR-08:62 | 1484.97 | 4134.37 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.28 |
May | 4758.32 | 17-MAY-14:10 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 637.03 | 0.00 |
June | 18549.79 | 26-JUN-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.63 |
July | 17456.74 | 18-JUL-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.91 | 0.00 |
August | 18789.17 | 21-AUG-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.81 |
September | 20243.00 | 11-SEP-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.82 |
October | 6276.25 | 11-OCT-14:10 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 391.69 | 0.00 |
November | 4019.47 | 07-NOV-14:00 | 2396.20 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.43 |
December | 3879.21 | 09-DEC-10:43 | 1484.97 | 7855.30 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3622.82 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20243.00 | 3509.93 | 7855.30 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 637.03 | 583.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4521.50 | 16-JAN-11:43 | 1484.97 | 7855.30 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.74 |
February | 4885.47 | 01-FEB-18:52 | 5737.39 | 9819.13 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.79 |
March | 4227.56 | 14-MAR-13:00 | 2396.20 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 0.00 |
April | 3602.06 | 22-APR-08:62 | 1484.97 | 4134.37 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.33 |
May | 4661.84 | 17-MAY-14:10 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 637.03 | 0.00 |
June | 17965.43 | 26-JUN-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.50 |
July | 17323.47 | 18-JUL-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 | 0.00 |
August | 18310.62 | 21-AUG-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.50 |
September | 20035.12 | 11-SEP-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.23 |
October | 6195.65 | 11-OCT-14:10 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 391.69 | 0.00 |
November | 3882.45 | 07-NOV-14:00 | 2396.20 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.43 |
December | 4134.74 | 10-DEC-11:32 | 1484.97 | 7855.30 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3602.06 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20035.12 | 5737.39 | 9819.13 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 637.03 | 583.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4258.18 | 13-JAN-20:23 | 1484.97 | 4134.37 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.10 |
February | 4325.35 | 09-FEB-18:33 | 4589.91 | 7855.30 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.85 |
March | 3847.47 | 15-MAR-14:10 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.14 |
April | 3268.21 | 01-APR-17:53 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.85 |
May | 4432.75 | 17-MAY-14:10 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 637.03 | 0.00 |
June | 16138.49 | 27-JUN-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.42 |
July | 17151.36 | 18-JUL-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.03 | 0.00 |
August | 16926.82 | 20-AUG-08:62 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.62 |
September | 18525.38 | 11-SEP-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.90 |
October | 6036.84 | 11-OCT-14:10 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 391.69 | 0.00 |
November | 4074.74 | 30-NOV-18:53 | 4589.91 | 7855.30 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.43 |
December | 4294.64 | 08-DEC-20:03 | 1484.97 | 4134.37 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3268.21 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18525.38 | 4589.91 | 7855.30 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 637.03 | 534.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2697.02 | 26-JAN-20:43 | 1113.73 | 3100.78 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.03 |
February | 2982.40 | 23-FEB-19:33 | 2632.45 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537.51 |
March | 3478.40 | 14-MAR-13:00 | 2396.20 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 0.00 |
April | 3164.32 | 14-APR-17:43 | 3442.43 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 621.63 |
May | 4349.63 | 17-MAY-14:10 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 664.31 | 0.00 |
June | 16746.83 | 25-JUN-08:62 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.81 | 0.00 |
July | 16986.78 | 23-JUL-08:62 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 0.00 |
August | 13040.34 | 20-AUG-08:62 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.68 |
September | 12923.58 | 11-SEP-07:02 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.86 |
October | 6083.35 | 11-OCT-14:10 | 2328.71 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 406.42 | 0.00 |
November | 3261.90 | 07-NOV-14:00 | 2396.20 | 1963.83 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.79 |
December | 2666.42 | 18-DEC-12:53 | 4657.41 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2532.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2666.42 | 0.00 | 516.80 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16986.78 | 4657.41 | 5891.48 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 664.31 | 2532.90 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.801460E+11 | 66083.43 | 04-JAN-17:00 | 0.542771E+11 | 188323.63 | 05-JAN-12:09 |
February | 0.720166E+11 | 63751.52 | 15-FEB-19:40 | 0.603381E+11 | 180891.15 | 06-FEB-08:09 |
March | 0.796692E+11 | 68146.72 | 14-MAR-13:20 | 0.419631E+11 | 169790.77 | 19-MAR-08:09 |
April | 0.744254E+11 | 59588.44 | 25-APR-18:49 | 0.302966E+11 | 141087.90 | 17-APR-07:10 |
May | 0.801125E+11 | 72741.79 | 17-MAY-13:50 | 0.157326E+10 | 64119.49 | 02-MAY-07:10 |
June | 0.967327E+11 | 99313.67 | 26-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.995870E+11 | 91530.11 | 17-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.100265E+12 | 94938.26 | 16-AUG-14:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.907059E+11 | 84867.66 | 10-SEP-15:30 | 0.149239E+09 | 20919.17 | 22-SEP-08:20 |
October | 0.802840E+11 | 73408.57 | 11-OCT-14:30 | 0.221759E+11 | 139789.97 | 31-OCT-11:09 |
November | 0.772714E+11 | 63496.89 | 28-NOV-17:40 | 0.353488E+11 | 149668.06 | 29-NOV-17:00 |
December | 0.806964E+11 | 64301.86 | 22-DEC-18:30 | 0.755583E+11 | 222253.60 | 21-DEC-17:00 |
Annual Sum or Average | 0.101191E+13 | 0.321680E+12 | ||||
Minimum of Months | 0.720166E+11 | 59588.44 | 0.00 | 0.00 | ||
Maximum of Months | 0.100265E+12 | 99313.67 | 0.755583E+11 | 222253.60 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.420288E+11 | 0.106944E+11 | 0.108325E+11 | 0.00 | 0.108994E+11 | 0.00 | 0.00 | 43293480.57 | 0.00 | 0.00 | 0.00 | 0.564771E+10 | 0.00 |
February | 0.380395E+11 | 0.889588E+10 | 0.980803E+10 | 0.00 | 0.101224E+11 | 0.00 | 0.00 | 14246735.92 | 0.00 | 0.00 | 0.00 | 0.513653E+10 | 0.00 |
March | 0.426243E+11 | 0.877129E+10 | 0.110075E+11 | 0.00 | 0.108596E+11 | 0.00 | 0.00 | 0.717855E+09 | 0.00 | 0.00 | 0.00 | 0.568868E+10 | 0.00 |
April | 0.407637E+11 | 0.739637E+10 | 0.105079E+11 | 0.00 | 0.101560E+11 | 0.00 | 0.00 | 0.195712E+09 | 0.00 | 0.00 | 0.00 | 0.540574E+10 | 0.00 |
May | 0.423184E+11 | 0.676808E+10 | 0.109147E+11 | 0.00 | 0.100547E+11 | 0.00 | 0.00 | 0.458280E+10 | 0.00 | 0.00 | 0.00 | 0.547376E+10 | 0.00 |
June | 0.411980E+11 | 0.612083E+10 | 0.106386E+11 | 0.00 | 0.982453E+10 | 0.00 | 0.00 | 0.237396E+11 | 0.00 | 0.00 | 0.00 | 0.521117E+10 | 0.00 |
July | 0.419004E+11 | 0.648089E+10 | 0.107945E+11 | 0.00 | 0.992954E+10 | 0.00 | 0.00 | 0.252045E+11 | 0.00 | 0.00 | 0.00 | 0.527712E+10 | 0.00 |
August | 0.426079E+11 | 0.722355E+10 | 0.110006E+11 | 0.00 | 0.101180E+11 | 0.00 | 0.00 | 0.240129E+11 | 0.00 | 0.00 | 0.00 | 0.530250E+10 | 0.00 |
September | 0.407800E+11 | 0.801269E+10 | 0.105148E+11 | 0.00 | 0.962809E+10 | 0.00 | 0.00 | 0.166356E+11 | 0.00 | 0.00 | 0.00 | 0.513480E+10 | 0.00 |
October | 0.420288E+11 | 0.940614E+10 | 0.108325E+11 | 0.00 | 0.103703E+11 | 0.00 | 0.00 | 0.225785E+10 | 0.00 | 0.00 | 0.00 | 0.538837E+10 | 0.00 |
November | 0.407147E+11 | 0.100655E+11 | 0.104978E+11 | 0.00 | 0.102378E+11 | 0.00 | 0.00 | 0.439668E+09 | 0.00 | 0.00 | 0.00 | 0.531587E+10 | 0.00 |
December | 0.419167E+11 | 0.109631E+11 | 0.108050E+11 | 0.00 | 0.113336E+11 | 0.00 | 0.00 | 85005355.18 | 0.00 | 0.00 | 0.00 | 0.559297E+10 | 0.00 |
Annual Sum or Average | 0.496921E+12 | 0.100799E+12 | 0.128154E+12 | 0.00 | 0.123534E+12 | 0.00 | 0.00 | 0.979291E+11 | 0.00 | 0.00 | 0.00 | 0.645752E+11 | 0.00 |
Minimum of Months | 0.380395E+11 | 0.612083E+10 | 0.980803E+10 | 0.00 | 0.962809E+10 | 0.00 | 0.00 | 14246735.92 | 0.00 | 0.00 | 0.00 | 0.513480E+10 | 0.00 |
Maximum of Months | 0.426243E+11 | 0.109631E+11 | 0.110075E+11 | 0.00 | 0.113336E+11 | 0.00 | 0.00 | 0.252045E+11 | 0.00 | 0.00 | 0.00 | 0.568868E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.542771E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.603381E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.419631E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.302966E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.157326E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.149239E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.221759E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.353488E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.755583E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.321680E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.755583E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30804.00 | 01-JAN-11:09 | 7723.25 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 10725.56 | 05-JAN-12:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30804.00 | 01-FEB-10:09 | 7723.25 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 10565.20 | 06-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 30804.00 | 01-MAR-10:09 | 7723.25 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 10332.94 | 19-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 30804.00 | 01-APR-09:09 | 7723.25 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 9723.88 | 17-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 30804.00 | 01-MAY-09:09 | 7723.25 | 01-MAY-18:49 | 8059.50 | 01-MAY-09:09 | 0.00 | 8095.27 | 02-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 30804.00 | 01-JUN-09:09 | 7723.25 | 01-JUN-19:19 | 8059.50 | 01-JUN-09:09 | 0.00 | 10378.52 | 26-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 30804.00 | 01-JUL-09:09 | 7723.25 | 01-JUL-19:30 | 8059.50 | 01-JUL-09:09 | 0.00 | 8603.10 | 17-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 30804.00 | 01-AUG-09:09 | 7723.25 | 01-AUG-19:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 9533.05 | 16-AUG-13:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 30804.00 | 01-SEP-09:09 | 7723.25 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 7883.79 | 13-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 30804.00 | 01-OCT-10:09 | 7723.25 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 9698.11 | 31-OCT-11:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30804.00 | 01-NOV-09:09 | 7723.25 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 9906.78 | 29-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30804.00 | 01-DEC-10:09 | 7723.25 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 11444.21 | 21-DEC-17:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 30804.00 | 7723.25 | 8059.50 | 0.00 | 7883.79 | 0.00 | 0.00 | |||||
Maximum of Months | 30804.00 | 7723.25 | 8059.50 | 0.00 | 11444.21 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 5005.98 | 20-JAN-13:00 | 0.00 | 0.00 | 0.00 | 12501.16 | 16-JAN-12:20 | 0.00 |
February | 2656.44 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 | 9738.42 | 23-FEB-13:39 | 0.00 |
March | 15835.18 | 14-MAR-12:00 | 0.00 | 0.00 | 0.00 | 9737.96 | 06-MAR-13:00 | 0.00 |
April | 7716.58 | 20-APR-12:00 | 0.00 | 0.00 | 0.00 | 9693.31 | 10-APR-11:00 | 0.00 |
May | 21339.01 | 17-MAY-12:00 | 0.00 | 0.00 | 0.00 | 9718.56 | 11-MAY-12:50 | 0.00 |
June | 46744.75 | 26-JUN-14:00 | 0.00 | 0.00 | 0.00 | 7586.43 | 09-JUN-12:30 | 0.00 |
July | 38619.32 | 16-JUL-12:00 | 0.00 | 0.00 | 0.00 | 8385.88 | 19-JUL-13:39 | 0.00 |
August | 41977.90 | 16-AUG-13:00 | 0.00 | 0.00 | 0.00 | 9699.31 | 04-AUG-12:09 | 0.00 |
September | 33406.19 | 09-SEP-12:00 | 0.00 | 0.00 | 0.00 | 9636.58 | 10-SEP-15:30 | 0.00 |
October | 22882.47 | 11-OCT-13:00 | 0.00 | 0.00 | 0.00 | 9644.80 | 22-OCT-13:39 | 0.00 |
November | 11701.02 | 07-NOV-13:00 | 0.00 | 0.00 | 0.00 | 9675.09 | 09-NOV-18:10 | 0.00 |
December | 7100.36 | 02-DEC-14:00 | 0.00 | 0.00 | 0.00 | 9717.49 | 02-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2656.44 | 0.00 | 0.00 | 0.00 | 7586.43 | 0.00 | ||
Maximum of Months | 46744.75 | 0.00 | 0.00 | 0.00 | 12501.16 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 66083.43 | 04-JAN-17:00 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 9808.56 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 63751.52 | 15-FEB-19:40 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 7546.15 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 68146.72 | 14-MAR-13:20 | 30804.00 | 8059.50 | 0.00 | 0.00 | 6736.61 | 0.00 | 0.00 | 14945.12 | 0.00 |
April | 59588.44 | 25-APR-18:49 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 7139.79 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72741.79 | 17-MAY-13:50 | 30804.00 | 8059.50 | 0.00 | 0.00 | 6736.61 | 0.00 | 0.00 | 21147.65 | 0.00 |
June | 99313.67 | 26-JUN-14:00 | 30804.00 | 8059.50 | 0.00 | 0.00 | 10378.52 | 0.00 | 0.00 | 46744.75 | 0.00 |
July | 91530.11 | 17-JUL-12:00 | 30804.00 | 8059.50 | 0.00 | 0.00 | 8603.10 | 0.00 | 0.00 | 38608.18 | 0.00 |
August | 94938.26 | 16-AUG-14:20 | 30804.00 | 8059.50 | 0.00 | 0.00 | 9311.66 | 0.00 | 0.00 | 41320.02 | 0.00 |
September | 84867.66 | 10-SEP-15:30 | 30804.00 | 8059.50 | 0.00 | 0.00 | 6816.32 | 0.00 | 0.00 | 29551.27 | 0.00 |
October | 73408.57 | 11-OCT-14:30 | 30804.00 | 8059.50 | 0.00 | 0.00 | 6736.61 | 0.00 | 0.00 | 22361.76 | 0.00 |
November | 63496.89 | 28-NOV-17:40 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 9344.39 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 64301.86 | 22-DEC-18:30 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 9434.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 59588.44 | 30804.00 | 8059.50 | 0.00 | 0.00 | 6736.61 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 99313.67 | 30804.00 | 8059.50 | 7723.25 | 0.00 | 10378.52 | 0.00 | 0.00 | 46744.75 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 188323.63 | 05-JAN-12:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 180891.15 | 06-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 169790.77 | 19-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 141087.90 | 17-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 64119.49 | 02-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 20919.17 | 22-SEP-08:20 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 139789.97 | 31-OCT-11:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 149668.06 | 29-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 222253.60 | 21-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 222253.60 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
February | 1.50 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
March | 0.50 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
April | 0.67 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
November | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
December | 1.50 | 20.33 | 0.33 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
Annual Sum or Average | 6.00 | 20.45 | 0.33 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 20.52 | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
February | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
November | 0.17 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
December | 0.17 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 1.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
Annual Sum or Average | 1.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Annual Sum or Average | 1.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
March | 0.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
Annual Sum or Average | 1.17 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
February | 1.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
March | 0.17 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 |
Annual Sum or Average | 2.17 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
February | 5.00 | 17.43 | 0.00 | 17.43 | 0.00 | 17.43 | 0.00 | 17.43 |
March | 2.67 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 |
April | 1.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
November | 0.67 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 |
December | 9.17 | 16.14 | 0.00 | 16.14 | 0.00 | 16.14 | 0.00 | 16.14 |
Annual Sum or Average | 20.67 | 17.45 | 0.00 | 17.45 | 0.00 | 17.45 | 0.00 | 17.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.17 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.44 | 101.50 | 21.36 | 101.50 | 21.30 |
February | 448.00 | 21.34 | 157.50 | 21.26 | 157.50 | 21.21 |
March | 464.00 | 21.80 | 85.33 | 21.67 | 85.33 | 21.58 |
April | 458.50 | 21.95 | 66.67 | 21.84 | 66.67 | 21.75 |
May | 209.67 | 22.97 | 44.33 | 23.09 | 4.00 | 23.06 |
June | 17.17 | 23.87 | 268.17 | 23.89 | 9.17 | 23.89 |
July | 68.83 | 23.89 | 326.33 | 23.89 | 62.33 | 23.89 |
August | 21.33 | 23.89 | 336.50 | 23.89 | 14.67 | 23.89 |
September | 59.50 | 23.13 | 169.17 | 23.69 | 0.00 | 23.69 |
October | 321.83 | 22.21 | 43.17 | 22.11 | 39.83 | 22.01 |
November | 444.00 | 21.65 | 53.83 | 21.58 | 53.83 | 21.53 |
December | 493.67 | 21.43 | 173.83 | 21.32 | 173.83 | 21.25 |
Annual Sum or Average | 3502.50 | 21.83 | 1826.33 | 22.17 | 768.67 | 22.06 |
Minimum of Months | 17.17 | 21.34 | 43.17 | 21.26 | 0.00 | 21.21 |
Maximum of Months | 496.00 | 23.89 | 336.50 | 23.89 | 173.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 479.17 | 22.13 | 28.00 | 22.08 | 28.00 | 22.03 |
February | 440.17 | 21.95 | 56.00 | 21.85 | 56.00 | 21.78 |
March | 445.83 | 22.31 | 13.67 | 22.28 | 13.67 | 22.25 |
April | 402.50 | 22.45 | 10.17 | 22.43 | 8.83 | 22.40 |
May | 139.00 | 23.31 | 78.67 | 23.52 | 0.00 | 23.52 |
June | 16.67 | 23.28 | 239.17 | 23.83 | 6.67 | 23.83 |
July | 57.00 | 23.67 | 310.83 | 23.84 | 45.17 | 23.84 |
August | 17.00 | 23.42 | 311.83 | 23.84 | 7.67 | 23.84 |
September | 62.00 | 23.41 | 152.00 | 23.74 | 0.00 | 23.74 |
October | 270.00 | 22.64 | 9.50 | 22.63 | 5.67 | 22.60 |
November | 411.17 | 22.35 | 10.33 | 22.32 | 10.33 | 22.29 |
December | 485.83 | 22.02 | 95.00 | 21.87 | 95.00 | 21.76 |
Annual Sum or Average | 3226.33 | 22.34 | 1315.17 | 22.65 | 277.00 | 22.60 |
Minimum of Months | 16.67 | 21.95 | 9.50 | 21.85 | 0.00 | 21.76 |
Maximum of Months | 485.83 | 23.67 | 311.83 | 23.84 | 95.00 | 23.84 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 360.83 | 21.64 | 46.50 | 21.58 | 46.50 | 21.53 |
February | 332.33 | 21.48 | 71.67 | 21.41 | 71.67 | 21.37 |
March | 333.50 | 21.86 | 31.33 | 21.80 | 31.33 | 21.75 |
April | 323.17 | 22.07 | 19.83 | 22.02 | 19.83 | 21.97 |
May | 116.50 | 23.01 | 52.00 | 23.34 | 0.67 | 23.33 |
June | 7.50 | 24.24 | 211.00 | 24.19 | 5.50 | 24.20 |
July | 36.00 | 24.15 | 260.17 | 24.15 | 35.00 | 24.15 |
August | 7.17 | 23.94 | 260.83 | 24.12 | 6.50 | 24.11 |
September | 35.33 | 23.19 | 132.67 | 23.99 | 0.17 | 24.00 |
October | 207.17 | 22.15 | 27.17 | 22.12 | 21.50 | 22.03 |
November | 316.17 | 21.82 | 17.00 | 21.78 | 17.00 | 21.75 |
December | 365.83 | 21.61 | 97.83 | 21.50 | 97.83 | 21.44 |
Annual Sum or Average | 2441.50 | 21.91 | 1228.00 | 22.41 | 353.50 | 22.33 |
Minimum of Months | 7.17 | 21.48 | 17.00 | 21.41 | 0.17 | 21.37 |
Maximum of Months | 365.83 | 24.24 | 260.83 | 24.19 | 97.83 | 24.20 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 365.33 | 21.62 | 50.17 | 21.56 | 50.17 | 21.51 |
February | 335.00 | 21.46 | 77.00 | 21.39 | 77.00 | 21.35 |
March | 337.67 | 21.85 | 37.83 | 21.78 | 37.83 | 21.72 |
April | 329.33 | 22.05 | 25.17 | 21.99 | 25.17 | 21.93 |
May | 125.50 | 23.00 | 45.50 | 23.27 | 1.67 | 23.25 |
June | 7.50 | 24.24 | 210.50 | 24.19 | 5.50 | 24.20 |
July | 35.83 | 24.15 | 261.67 | 24.15 | 35.00 | 24.15 |
August | 7.17 | 23.94 | 261.50 | 24.12 | 6.50 | 24.11 |
September | 35.83 | 23.17 | 132.00 | 23.98 | 0.17 | 23.99 |
October | 214.33 | 22.15 | 32.17 | 22.08 | 27.67 | 21.98 |
November | 323.00 | 21.80 | 20.33 | 21.76 | 20.33 | 21.72 |
December | 366.83 | 21.58 | 111.00 | 21.47 | 111.00 | 21.40 |
Annual Sum or Average | 2483.33 | 21.89 | 1264.83 | 22.37 | 398.00 | 22.29 |
Minimum of Months | 7.17 | 21.46 | 20.33 | 21.39 | 0.17 | 21.35 |
Maximum of Months | 366.83 | 24.24 | 261.67 | 24.19 | 111.00 | 24.20 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 369.50 | 21.58 | 58.00 | 21.52 | 58.00 | 21.47 |
February | 336.00 | 21.42 | 85.50 | 21.35 | 85.50 | 21.31 |
March | 346.17 | 21.84 | 47.17 | 21.75 | 47.17 | 21.69 |
April | 340.83 | 22.04 | 31.67 | 21.96 | 31.67 | 21.89 |
May | 142.17 | 22.97 | 36.00 | 23.17 | 2.33 | 23.14 |
June | 8.17 | 24.19 | 201.50 | 24.19 | 5.83 | 24.20 |
July | 38.00 | 24.11 | 252.17 | 24.14 | 36.83 | 24.14 |
August | 8.00 | 23.93 | 254.00 | 24.11 | 6.67 | 24.11 |
September | 39.33 | 23.15 | 124.00 | 23.95 | 0.17 | 23.96 |
October | 230.67 | 22.18 | 32.33 | 22.10 | 28.83 | 22.00 |
November | 333.50 | 21.78 | 29.00 | 21.72 | 29.00 | 21.68 |
December | 369.00 | 21.54 | 119.33 | 21.44 | 119.33 | 21.37 |
Annual Sum or Average | 2561.33 | 21.88 | 1270.67 | 22.32 | 451.33 | 22.23 |
Minimum of Months | 8.00 | 21.42 | 29.00 | 21.35 | 0.17 | 21.31 |
Maximum of Months | 369.50 | 24.19 | 254.00 | 24.19 | 119.33 | 24.20 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.47 | 71.17 | 21.41 | 71.17 | 21.37 |
February | 308.00 | 21.35 | 118.33 | 21.28 | 118.33 | 21.25 |
March | 339.67 | 21.87 | 70.33 | 21.74 | 70.33 | 21.65 |
April | 327.33 | 21.99 | 49.50 | 21.88 | 49.50 | 21.79 |
May | 189.33 | 23.05 | 12.67 | 23.06 | 3.33 | 23.03 |
June | 8.33 | 24.06 | 166.83 | 24.01 | 5.83 | 24.01 |
July | 41.67 | 23.95 | 214.33 | 24.00 | 41.00 | 24.00 |
August | 11.33 | 24.01 | 212.33 | 23.97 | 10.00 | 23.97 |
September | 43.83 | 23.17 | 101.33 | 23.79 | 0.00 | 23.79 |
October | 250.00 | 22.30 | 30.17 | 22.19 | 29.17 | 22.09 |
November | 311.83 | 21.68 | 43.83 | 21.61 | 43.83 | 21.55 |
December | 338.00 | 21.46 | 135.33 | 21.36 | 135.33 | 21.31 |
Annual Sum or Average | 2509.33 | 21.90 | 1226.17 | 22.18 | 577.83 | 22.08 |
Minimum of Months | 8.33 | 21.35 | 12.67 | 21.28 | 0.00 | 21.25 |
Maximum of Months | 340.00 | 24.06 | 214.33 | 24.01 | 135.33 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.46 | 73.67 | 21.40 | 73.67 | 21.36 |
February | 308.00 | 21.34 | 120.33 | 21.28 | 120.33 | 21.24 |
March | 344.67 | 21.89 | 73.33 | 21.75 | 73.33 | 21.66 |
April | 329.33 | 21.98 | 53.00 | 21.86 | 53.00 | 21.77 |
May | 210.50 | 23.10 | 10.00 | 23.08 | 4.67 | 23.04 |
June | 11.67 | 23.94 | 144.67 | 24.01 | 5.67 | 24.01 |
July | 43.50 | 23.95 | 183.17 | 24.02 | 41.17 | 24.01 |
August | 13.83 | 23.98 | 193.50 | 23.97 | 9.83 | 23.97 |
September | 51.83 | 23.27 | 82.17 | 23.78 | 0.00 | 23.78 |
October | 266.17 | 22.39 | 31.33 | 22.27 | 30.50 | 22.16 |
November | 318.00 | 21.71 | 45.83 | 21.63 | 45.83 | 21.58 |
December | 338.00 | 21.46 | 138.50 | 21.36 | 138.50 | 21.30 |
Annual Sum or Average | 2575.50 | 21.93 | 1149.50 | 22.16 | 596.50 | 22.05 |
Minimum of Months | 11.67 | 21.34 | 10.00 | 21.28 | 0.00 | 21.24 |
Maximum of Months | 344.67 | 23.98 | 193.50 | 24.02 | 138.50 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.44 | 79.17 | 21.38 | 79.17 | 21.33 |
February | 308.00 | 21.33 | 126.00 | 21.27 | 126.00 | 21.23 |
March | 347.00 | 21.88 | 81.17 | 21.73 | 81.17 | 21.63 |
April | 330.00 | 21.95 | 55.50 | 21.83 | 55.50 | 21.74 |
May | 219.50 | 23.07 | 8.33 | 23.04 | 5.50 | 22.99 |
June | 12.67 | 23.93 | 140.33 | 24.01 | 5.83 | 24.01 |
July | 44.50 | 23.94 | 179.83 | 24.02 | 41.67 | 24.01 |
August | 15.17 | 23.97 | 188.67 | 23.97 | 10.00 | 23.97 |
September | 54.33 | 23.27 | 80.67 | 23.77 | 0.00 | 23.77 |
October | 271.83 | 22.39 | 32.50 | 22.25 | 32.17 | 22.15 |
November | 321.50 | 21.71 | 47.50 | 21.63 | 47.50 | 21.57 |
December | 338.00 | 21.44 | 144.00 | 21.34 | 144.00 | 21.29 |
Annual Sum or Average | 2602.50 | 21.93 | 1163.67 | 22.13 | 628.50 | 22.02 |
Minimum of Months | 12.67 | 21.33 | 8.33 | 21.27 | 0.00 | 21.23 |
Maximum of Months | 347.00 | 23.97 | 188.67 | 24.02 | 144.00 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.39 | 98.67 | 21.33 | 98.67 | 21.29 |
February | 308.00 | 21.30 | 144.33 | 21.24 | 144.33 | 21.21 |
March | 348.00 | 21.82 | 105.17 | 21.66 | 105.17 | 21.55 |
April | 330.00 | 21.88 | 66.00 | 21.75 | 66.00 | 21.66 |
May | 253.83 | 23.03 | 9.50 | 22.97 | 8.67 | 22.91 |
June | 15.83 | 23.86 | 132.67 | 24.01 | 5.83 | 24.00 |
July | 46.67 | 23.94 | 174.83 | 24.02 | 42.67 | 24.00 |
August | 16.67 | 23.96 | 185.67 | 23.97 | 10.50 | 23.97 |
September | 60.50 | 23.27 | 78.50 | 23.74 | 0.00 | 23.74 |
October | 280.00 | 22.34 | 35.67 | 22.20 | 35.67 | 22.09 |
November | 324.00 | 21.66 | 55.33 | 21.58 | 55.33 | 21.52 |
December | 338.00 | 21.40 | 163.83 | 21.31 | 163.83 | 21.26 |
Annual Sum or Average | 2661.50 | 21.90 | 1250.17 | 22.08 | 736.67 | 21.96 |
Minimum of Months | 15.83 | 21.30 | 9.50 | 21.24 | 0.00 | 21.21 |
Maximum of Months | 348.00 | 23.96 | 185.67 | 24.02 | 163.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.31 | 186.33 | 21.24 | 186.33 | 21.20 |
February | 308.00 | 21.25 | 189.00 | 21.19 | 189.00 | 21.17 |
March | 348.00 | 21.72 | 182.17 | 21.51 | 182.17 | 21.41 |
April | 330.00 | 21.75 | 117.50 | 21.58 | 117.50 | 21.48 |
May | 301.83 | 22.89 | 27.33 | 22.74 | 27.33 | 22.62 |
June | 17.50 | 23.86 | 131.17 | 24.00 | 6.33 | 24.00 |
July | 48.83 | 23.91 | 190.17 | 24.00 | 43.67 | 23.99 |
August | 19.67 | 23.92 | 198.33 | 23.96 | 10.83 | 23.96 |
September | 66.83 | 23.21 | 86.50 | 23.70 | 0.50 | 23.69 |
October | 290.17 | 22.22 | 60.33 | 22.03 | 60.33 | 21.90 |
November | 328.17 | 21.60 | 102.50 | 21.48 | 102.50 | 21.41 |
December | 338.00 | 21.34 | 229.67 | 21.25 | 229.67 | 21.21 |
Annual Sum or Average | 2737.00 | 21.85 | 1701.00 | 21.96 | 1156.17 | 21.81 |
Minimum of Months | 17.50 | 21.25 | 27.33 | 21.19 | 0.50 | 21.17 |
Maximum of Months | 348.00 | 23.92 | 229.67 | 24.00 | 229.67 | 24.00 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.43719 | 20.73344 | -0.4037 | 9.51197 |
February | 448.00000 | 21.34442 | 18.20243 | -0.4616 | 10.54817 |
March | 497.00000 | 21.93640 | 18.20290 | -0.3028 | 8.94017 |
April | 479.00000 | 22.02900 | 23.11984 | -0.2445 | 8.09563 |
May | 496.00000 | 23.48615 | 26.70729 | -0.7520 | 18.63987 |
June | 481.00000 | 23.88828 | 31.94392 | -0.4541 | 9.47057 |
July | 495.00000 | 23.88834 | 35.07399 | -0.4301 | 9.04743 |
August | 497.00000 | 23.88887 | 32.86789 | -0.4314 | 9.03987 |
September | 479.00000 | 23.79402 | 24.91159 | -0.5360 | 11.78604 |
October | 496.00000 | 22.79742 | 20.31173 | -0.0152 | 7.26881 |
November | 480.00000 | 21.82046 | 21.98939 | -0.2647 | 8.08460 |
December | 496.00000 | 21.44177 | 14.45264 | -0.4614 | 10.88938 |
Annual Sum or Average | 5840.00000 | 22.65413 | 24.07521 | -0.3961 | 10.11459 |
Minimum of Months | 448.00000 | 21.34442 | 14.45264 | -0.7520 | 7.26881 |
Maximum of Months | 497.00000 | 23.88887 | 35.07399 | -0.0152 | 18.63987 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 22.19349 | 22.47290 | -0.1975 | 7.24615 |
February | 448.00000 | 21.98126 | 19.71377 | -0.2777 | 8.04514 |
March | 497.00000 | 22.47627 | 19.26024 | -0.1457 | 7.12184 |
April | 479.00000 | 22.67808 | 23.85750 | -0.0703 | 6.77185 |
May | 496.00000 | 23.71361 | 26.39056 | -0.6508 | 14.84976 |
June | 481.00000 | 23.82132 | 31.75425 | -0.4701 | 9.81716 |
July | 495.00000 | 23.82151 | 34.67407 | -0.4460 | 9.38814 |
August | 497.00000 | 23.82076 | 32.39189 | -0.4529 | 9.48428 |
September | 479.00000 | 23.79092 | 24.90073 | -0.5330 | 11.36459 |
October | 496.00000 | 23.20609 | 20.46592 | 0.09091 | 6.75880 |
November | 480.00000 | 22.57152 | 22.89737 | -0.0784 | 6.74564 |
December | 496.00000 | 22.05688 | 16.07576 | -0.2858 | 8.37437 |
Annual Sum or Average | 5840.00000 | 23.01717 | 24.59713 | -0.2933 | 8.83862 |
Minimum of Months | 448.00000 | 21.98126 | 16.07576 | -0.6508 | 6.74564 |
Maximum of Months | 497.00000 | 23.82151 | 34.67407 | 0.09091 | 14.84976 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.70499 | 19.49729 | -0.3083 | 8.29543 |
February | 336.00000 | 21.50690 | 17.03477 | -0.3865 | 9.26690 |
March | 379.00000 | 22.11294 | 17.12460 | -0.2292 | 8.02747 |
April | 360.00000 | 22.25651 | 21.60574 | -0.1682 | 7.47109 |
May | 375.00000 | 23.65547 | 24.95578 | -0.6830 | 16.33746 |
June | 366.00000 | 24.06229 | 30.40697 | -0.4132 | 8.99172 |
July | 369.00000 | 24.07220 | 33.65808 | -0.3823 | 8.51583 |
August | 379.00000 | 24.05057 | 31.08659 | -0.3960 | 8.63048 |
September | 360.00000 | 23.95086 | 23.54586 | -0.4950 | 10.91436 |
October | 371.00000 | 22.93581 | 19.04951 | 0.02896 | 7.11904 |
November | 360.00000 | 22.06963 | 20.62572 | -0.1877 | 7.45579 |
December | 369.00000 | 21.62903 | 13.35662 | -0.3870 | 9.54648 |
Annual Sum or Average | 4395.00000 | 22.84530 | 22.71040 | -0.3340 | 9.22211 |
Minimum of Months | 336.00000 | 21.50690 | 13.35662 | -0.6830 | 7.11904 |
Maximum of Months | 379.00000 | 24.07220 | 33.65808 | 0.02896 | 16.33746 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.65719 | 19.55494 | -0.3292 | 8.50434 |
February | 336.00000 | 21.46265 | 17.08885 | -0.4060 | 9.51290 |
March | 379.00000 | 22.07801 | 17.16008 | -0.2455 | 8.19303 |
April | 360.00000 | 22.20901 | 21.68260 | -0.1881 | 7.60479 |
May | 375.00000 | 23.62451 | 25.00891 | -0.6999 | 16.95493 |
June | 366.00000 | 24.06170 | 30.40678 | -0.4133 | 8.98962 |
July | 369.00000 | 24.07197 | 33.65711 | -0.3814 | 8.49745 |
August | 379.00000 | 24.05005 | 31.08490 | -0.3958 | 8.62483 |
September | 360.00000 | 23.94659 | 23.55186 | -0.4971 | 10.98453 |
October | 371.00000 | 22.90223 | 19.10157 | 0.01597 | 7.15994 |
November | 360.00000 | 22.01108 | 20.70509 | -0.2093 | 7.58956 |
December | 369.00000 | 21.59111 | 13.39186 | -0.4056 | 9.78846 |
Annual Sum or Average | 4395.00000 | 22.81706 | 22.74739 | -0.3463 | 9.37473 |
Minimum of Months | 336.00000 | 21.46265 | 13.39186 | -0.6999 | 7.15994 |
Maximum of Months | 379.00000 | 24.07197 | 33.65711 | 0.01597 | 16.95493 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.59217 | 19.63175 | -0.3559 | 8.77741 |
February | 336.00000 | 21.41643 | 17.14415 | -0.4283 | 9.82499 |
March | 379.00000 | 22.02301 | 17.22133 | -0.2693 | 8.42197 |
April | 360.00000 | 22.13373 | 21.80780 | -0.2169 | 7.79222 |
May | 375.00000 | 23.56411 | 25.12890 | -0.7319 | 18.05796 |
June | 366.00000 | 24.05628 | 30.45585 | -0.4223 | 9.13367 |
July | 369.00000 | 24.06690 | 33.71927 | -0.3895 | 8.61244 |
August | 379.00000 | 24.04513 | 31.12682 | -0.4040 | 8.74911 |
September | 360.00000 | 23.93282 | 23.57689 | -0.5087 | 11.27572 |
October | 371.00000 | 22.84223 | 19.19408 | -0.0054 | 7.19983 |
November | 360.00000 | 21.93301 | 20.80835 | -0.2368 | 7.76989 |
December | 369.00000 | 21.54214 | 13.43726 | -0.4291 | 10.11660 |
Annual Sum or Average | 4395.00000 | 22.77398 | 22.81893 | -0.3665 | 9.65276 |
Minimum of Months | 336.00000 | 21.41643 | 13.43726 | -0.7319 | 7.19983 |
Maximum of Months | 379.00000 | 24.06690 | 33.71927 | -0.0054 | 18.05796 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.47218 | 21.25593 | -0.4131 | 9.50203 |
February | 308.00000 | 21.35133 | 18.63614 | -0.4755 | 10.61622 |
March | 348.00000 | 21.92203 | 18.65688 | -0.3207 | 8.99600 |
April | 330.00000 | 22.00627 | 23.37772 | -0.2746 | 8.21312 |
May | 344.00000 | 23.43176 | 26.41958 | -0.8052 | 20.46524 |
June | 336.00000 | 23.94584 | 31.69036 | -0.4645 | 9.75396 |
July | 338.00000 | 23.96996 | 35.05617 | -0.4261 | 9.08750 |
August | 348.00000 | 23.93516 | 32.17660 | -0.4437 | 9.31516 |
September | 330.00000 | 23.85038 | 24.73298 | -0.5437 | 12.06361 |
October | 340.00000 | 22.73212 | 20.44090 | -0.0481 | 7.35042 |
November | 330.00000 | 21.79795 | 22.27563 | -0.2914 | 8.24880 |
December | 338.00000 | 21.46162 | 14.91385 | -0.4824 | 11.00782 |
Annual Sum or Average | 4030.00000 | 22.66804 | 24.18376 | -0.4158 | 10.39576 |
Minimum of Months | 308.00000 | 21.35133 | 14.91385 | -0.8052 | 7.35042 |
Maximum of Months | 348.00000 | 23.96996 | 35.05617 | -0.0481 | 20.46524 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.46358 | 21.17099 | -0.4215 | 9.60099 |
February | 308.00000 | 21.34440 | 18.54915 | -0.4820 | 10.68324 |
March | 348.00000 | 21.91065 | 18.58245 | -0.3313 | 9.06954 |
April | 330.00000 | 21.98528 | 23.32559 | -0.2881 | 8.31585 |
May | 344.00000 | 23.41414 | 26.37715 | -0.8293 | 21.27504 |
June | 336.00000 | 23.94435 | 31.61200 | -0.4895 | 10.24817 |
July | 338.00000 | 23.96833 | 34.98490 | -0.4511 | 9.54125 |
August | 348.00000 | 23.93425 | 32.09335 | -0.4692 | 9.79849 |
September | 330.00000 | 23.84795 | 24.64368 | -0.5683 | 12.61734 |
October | 340.00000 | 22.72635 | 20.36274 | -0.0612 | 7.31046 |
November | 330.00000 | 21.78932 | 22.19158 | -0.3022 | 8.33375 |
December | 338.00000 | 21.45733 | 14.82596 | -0.4872 | 11.05105 |
Annual Sum or Average | 4030.00000 | 22.66049 | 24.10777 | -0.4319 | 10.66667 |
Minimum of Months | 308.00000 | 21.34440 | 14.82596 | -0.8293 | 7.31046 |
Maximum of Months | 348.00000 | 23.96833 | 34.98490 | -0.0612 | 21.27504 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.43964 | 21.19681 | -0.4331 | 9.76130 |
February | 308.00000 | 21.33012 | 18.56383 | -0.4907 | 10.82058 |
March | 348.00000 | 21.88617 | 18.61518 | -0.3424 | 9.18491 |
April | 330.00000 | 21.95428 | 23.37719 | -0.3008 | 8.43433 |
May | 344.00000 | 23.37530 | 26.46636 | -0.8499 | 22.03397 |
June | 336.00000 | 23.94365 | 31.62869 | -0.4940 | 10.34126 |
July | 338.00000 | 23.96762 | 35.00602 | -0.4551 | 9.61610 |
August | 348.00000 | 23.93372 | 32.10939 | -0.4731 | 9.87422 |
September | 330.00000 | 23.84322 | 24.65427 | -0.5739 | 12.77345 |
October | 340.00000 | 22.69669 | 20.41106 | -0.0722 | 7.33995 |
November | 330.00000 | 21.76354 | 22.22430 | -0.3132 | 8.44081 |
December | 338.00000 | 21.44237 | 14.84216 | -0.4957 | 11.19009 |
Annual Sum or Average | 4030.00000 | 22.64299 | 24.13926 | -0.4413 | 10.83142 |
Minimum of Months | 308.00000 | 21.33012 | 14.84216 | -0.8499 | 7.33995 |
Maximum of Months | 348.00000 | 23.96762 | 35.00602 | -0.0722 | 22.03397 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.38779 | 21.25070 | -0.4624 | 10.23274 |
February | 308.00000 | 21.29723 | 18.59670 | -0.5154 | 11.27395 |
March | 348.00000 | 21.82319 | 18.69422 | -0.3725 | 9.56907 |
April | 330.00000 | 21.87546 | 23.49581 | -0.3336 | 8.80509 |
May | 344.00000 | 23.26308 | 26.72161 | -0.9036 | 24.11686 |
June | 336.00000 | 23.94165 | 31.66995 | -0.5006 | 10.47959 |
July | 338.00000 | 23.96606 | 35.05625 | -0.4602 | 9.71300 |
August | 348.00000 | 23.93242 | 32.14511 | -0.4771 | 9.95842 |
September | 330.00000 | 23.82990 | 24.67435 | -0.5834 | 13.08150 |
October | 340.00000 | 22.61721 | 20.53216 | -0.1002 | 7.47760 |
November | 330.00000 | 21.70274 | 22.29564 | -0.3400 | 8.75073 |
December | 338.00000 | 21.40432 | 14.88081 | -0.5195 | 11.62680 |
Annual Sum or Average | 4030.00000 | 22.59825 | 24.21633 | -0.4642 | 11.27295 |
Minimum of Months | 308.00000 | 21.29723 | 14.88081 | -0.9036 | 7.47760 |
Maximum of Months | 348.00000 | 23.96606 | 35.05625 | -0.1002 | 24.11686 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.30849 | 21.16251 | -0.5488 | 12.02076 |
February | 308.00000 | 21.24507 | 18.43123 | -0.5968 | 13.15002 |
March | 348.00000 | 21.71636 | 18.65133 | -0.4552 | 11.04463 |
April | 330.00000 | 21.75216 | 23.45032 | -0.4146 | 10.14500 |
May | 344.00000 | 23.01872 | 27.18821 | -1.0242 | 29.23001 |
June | 336.00000 | 23.93694 | 31.68943 | -0.5001 | 10.47742 |
July | 338.00000 | 23.96444 | 35.13728 | -0.4565 | 9.66128 |
August | 348.00000 | 23.93083 | 32.12044 | -0.4658 | 9.77164 |
September | 330.00000 | 23.80542 | 24.64350 | -0.5868 | 13.45051 |
October | 340.00000 | 22.47425 | 20.63356 | -0.1646 | 8.14019 |
November | 330.00000 | 21.61120 | 22.22748 | -0.4084 | 9.87850 |
December | 338.00000 | 21.34197 | 14.75767 | -0.5943 | 13.37921 |
Annual Sum or Average | 4030.00000 | 22.51994 | 24.22506 | -0.5180 | 12.54557 |
Minimum of Months | 308.00000 | 21.24507 | 14.75767 | -1.0242 | 8.14019 |
Maximum of Months | 348.00000 | 23.96444 | 35.13728 | -0.1646 | 29.23001 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 24828016.62 | 6830967.27 | 4.00 | 24828016.62 | 0.00 | 0.00 | 0.23 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 3663.45 | 20-JAN-14:00 | 3663.45 | 20-JAN-14:00 | 0.00 | 20-JAN-14:00 | 992.50 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 7264502.69 | 2045854.67 | 2.00 | 7264502.69 | 0.00 | 0.00 | 0.12 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 | 1788.69 | 18-FEB-14:00 | 1788.69 | 18-FEB-14:00 | 0.00 | 18-FEB-13:50 | 499.51 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.488296E+09 | 0.129135E+09 | 35.33 | 0.488296E+09 | 0.00 | 0.00 | 0.59 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 10144.18 | 14-MAR-13:00 | 10144.18 | 14-MAR-13:00 | 0.00 | 14-MAR-12:40 | 2623.51 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.145398E+09 | 40225415.38 | 23.50 | 0.145398E+09 | 0.00 | 0.00 | 0.32 | 20-APR-13:00 | 0.00 | 01-APR-00:05 | 5079.59 | 20-APR-13:00 | 5079.59 | 20-APR-13:00 | 0.00 | 20-APR-12:40 | 1366.89 | 20-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.320669E+10 | 0.862291E+09 | 173.32 | 0.316724E+10 | 39449976.62 | 0.00 | 0.77 | 17-MAY-14:00 | 0.00 | 01-MAY-00:10 | 13405.09 | 17-MAY-14:00 | 13405.09 | 17-MAY-14:00 | 877.18 | 30-MAY-17:10 | 3658.31 | 17-MAY-14:00 | 0.00 | 01-MAY-00:10 |
June | 0.168553E+11 | 0.457122E+10 | 438.69 | 0.160259E+11 | 0.829411E+09 | 0.00 | 1.00 | 13-JUN-07:03 | 0.00 | 01-JUN-00:10 | 38689.34 | 25-JUN-07:02 | 38689.34 | 25-JUN-07:02 | 9834.19 | 18-JUN-07:03 | 9431.52 | 14-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.182197E+11 | 0.491169E+10 | 463.98 | 0.170141E+11 | 0.120561E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:02 | 42582.30 | 24-JUL-07:02 | 39684.67 | 18-JUL-07:02 | 9406.30 | 24-JUL-07:02 | 9604.24 | 24-JUL-07:02 | 0.00 | 01-JUL-00:02 |
August | 0.173922E+11 | 0.463143E+10 | 462.11 | 0.165215E+11 | 0.870776E+09 | 0.00 | 1.00 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 | 41565.26 | 03-AUG-07:02 | 33200.54 | 03-AUG-07:02 | 13261.32 | 04-AUG-07:03 | 9038.44 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.121059E+11 | 0.317312E+10 | 366.29 | 0.119395E+11 | 0.166423E+09 | 0.00 | 1.00 | 03-SEP-07:02 | 0.00 | 01-SEP-00:05 | 38133.02 | 13-SEP-07:02 | 35523.77 | 13-SEP-07:02 | 4434.80 | 03-SEP-07:02 | 8229.73 | 13-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.165352E+10 | 0.428750E+09 | 90.25 | 0.165299E+10 | 521251.56 | 0.00 | 0.85 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 | 15446.88 | 11-OCT-14:00 | 15446.88 | 11-OCT-14:00 | 52.40 | 01-OCT-13:00 | 3929.82 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 0.331092E+09 | 88371779.73 | 25.17 | 0.331092E+09 | -0.0 | 0.00 | 0.50 | 07-NOV-15:00 | 0.00 | 01-NOV-00:05 | 8359.55 | 07-NOV-15:00 | 8359.55 | 07-NOV-15:00 | 0.00 | 07-NOV-15:40 | 2139.76 | 07-NOV-15:00 | 0.00 | 01-NOV-00:05 |
December | 58006141.54 | 16047254.39 | 8.17 | 58006141.54 | 0.00 | 0.00 | 0.29 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 4619.96 | 02-DEC-15:00 | 4619.96 | 02-DEC-15:00 | 0.00 | 02-DEC-14:20 | 1252.20 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.704883E+11 | 0.188612E+11 | 2092.82 | 0.673761E+11 | 0.311219E+10 | 0.00 | ||||||||||||||
Minimum of Months | 7264502.69 | 2045854.67 | 2.00 | 7264502.69 | -0.0 | 0.00 | 0.12 | 0.00 | 1788.69 | 1788.69 | 0.00 | 499.51 | 0.00 | |||||||
Maximum of Months | 0.182197E+11 | 0.491169E+10 | 463.98 | 0.170141E+11 | 0.120561E+10 | 0.00 | 1.00 | 0.00 | 42582.30 | 39684.67 | 13261.32 | 9604.24 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 51736789.62 | 13839737.61 | 14.07 | 51665687.23 | 71102.40 | 0.00 | 0.36 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 3150.83 | 20-JAN-14:00 | 3150.83 | 20-JAN-14:00 | 47.51 | 29-JAN-20:20 | 810.48 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 16157100.42 | 4366120.76 | 4.67 | 16145578.67 | 11521.75 | 0.00 | 0.25 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 | 2098.13 | 18-FEB-14:00 | 2098.13 | 18-FEB-14:00 | 17.01 | 19-FEB-18:50 | 556.43 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.386095E+09 | 98425856.97 | 43.88 | 0.386078E+09 | 17862.47 | 0.00 | 1.00 | 12-MAR-17:01 | 0.00 | 01-MAR-00:10 | 21282.15 | 12-MAR-17:01 | 21282.15 | 12-MAR-17:06 | 22.50 | 17-MAR-22:40 | 4505.80 | 12-MAR-17:01 | 0.00 | 01-MAR-00:10 |
April | 0.163662E+09 | 43832281.51 | 36.22 | 0.163428E+09 | 233546.19 | 0.00 | 0.41 | 20-APR-13:00 | 0.00 | 01-APR-00:05 | 3600.05 | 20-APR-13:00 | 3600.05 | 20-APR-13:00 | 151.77 | 13-APR-22:10 | 928.55 | 20-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.240041E+10 | 0.610697E+09 | 199.05 | 0.235461E+10 | 45797198.59 | 0.00 | 1.00 | 06-MAY-18:01 | 0.00 | 01-MAY-00:10 | 21456.05 | 31-MAY-20:40 | 21282.15 | 28-MAY-17:16 | 4478.94 | 31-MAY-20:55 | 4550.30 | 31-MAY-20:40 | 0.00 | 01-MAY-00:10 |
June | 0.102889E+11 | 0.266146E+10 | 408.95 | 0.968766E+10 | 0.601204E+09 | 0.00 | 1.00 | 01-JUN-20:01 | 0.00 | 01-JUN-00:10 | 22770.18 | 17-JUN-18:40 | 21414.58 | 25-JUN-07:02 | 10685.15 | 20-JUN-20:10 | 5037.38 | 14-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.112132E+11 | 0.288351E+10 | 436.67 | 0.103220E+11 | 0.891248E+09 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:02 | 23486.53 | 29-JUL-18:03 | 21436.01 | 18-JUL-07:02 | 12270.22 | 30-JUL-21:50 | 5073.43 | 29-JUL-18:03 | 0.00 | 01-JUL-00:02 |
August | 0.107183E+11 | 0.271926E+10 | 428.25 | 0.100737E+11 | 0.644603E+09 | 0.00 | 1.00 | 01-AUG-20:01 | 0.00 | 01-AUG-00:10 | 22990.15 | 03-AUG-22:50 | 21325.13 | 23-AUG-20:20 | 10558.92 | 29-AUG-20:40 | 4957.87 | 25-AUG-22:08 | 0.00 | 01-AUG-00:10 |
September | 0.761503E+10 | 0.190294E+10 | 351.12 | 0.746886E+10 | 0.146169E+09 | 0.00 | 1.00 | 01-SEP-20:01 | 0.00 | 01-SEP-00:05 | 21941.60 | 02-SEP-19:58 | 21282.15 | 16-SEP-20:15 | 5269.85 | 03-SEP-22:05 | 4817.11 | 02-SEP-19:18 | 0.00 | 01-SEP-00:05 |
October | 0.110082E+10 | 0.276393E+09 | 99.09 | 0.109963E+10 | 1192239.00 | 0.00 | 1.00 | 07-OCT-18:01 | 0.00 | 01-OCT-00:10 | 21282.15 | 08-OCT-17:07 | 21282.15 | 08-OCT-17:07 | 1299.81 | 08-OCT-18:27 | 4505.80 | 07-OCT-18:55 | 0.00 | 01-OCT-00:10 |
November | 0.258423E+09 | 66850400.40 | 32.79 | 0.258210E+09 | 213070.92 | 0.00 | 0.55 | 07-NOV-14:30 | 0.00 | 01-NOV-00:05 | 5091.98 | 07-NOV-14:30 | 5091.98 | 07-NOV-14:30 | 120.37 | 18-NOV-19:20 | 1260.15 | 07-NOV-14:30 | 0.00 | 01-NOV-00:05 |
December | 75927396.34 | 20312486.11 | 17.31 | 75925425.64 | 1970.70 | 0.00 | 0.39 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 3437.95 | 02-DEC-15:00 | 3437.95 | 02-DEC-15:00 | 1.97 | 31-DEC-21:40 | 890.83 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.442887E+11 | 0.113019E+11 | 2072.05 | 0.419579E+11 | 0.233076E+10 | 0.00 | ||||||||||||||
Minimum of Months | 16157100.42 | 4366120.76 | 4.67 | 16145578.67 | 1970.70 | 0.00 | 0.25 | 0.00 | 2098.13 | 2098.13 | 1.97 | 556.43 | 0.00 | |||||||
Maximum of Months | 0.112132E+11 | 0.288351E+10 | 436.67 | 0.103220E+11 | 0.891248E+09 | 0.00 | 1.00 | 0.00 | 23486.53 | 21436.01 | 12270.22 | 5073.43 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 24028503.27 | 6501078.90 | 8.83 | 24028503.27 | -0.0 | 0.00 | 0.26 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 2327.03 | 20-JAN-14:00 | 2327.03 | 20-JAN-14:00 | 0.00 | 20-JAN-13:20 | 614.79 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 9042512.31 | 2468607.34 | 2.67 | 9042512.31 | -0.0 | 0.00 | 0.18 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 | 1580.31 | 18-FEB-14:00 | 1580.31 | 18-FEB-14:00 | 0.00 | 18-FEB-14:20 | 426.45 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.297361E+09 | 77005260.26 | 36.00 | 0.297361E+09 | 0.00 | 0.00 | 0.63 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 6089.71 | 14-MAR-13:00 | 6089.71 | 14-MAR-13:00 | 0.00 | 14-MAR-12:50 | 1532.28 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.101756E+09 | 27550481.71 | 28.33 | 0.101756E+09 | 1.83 | 0.00 | 0.35 | 20-APR-13:00 | 0.00 | 01-APR-00:05 | 3208.31 | 20-APR-13:00 | 3208.31 | 20-APR-13:00 | 0.00 | 27-APR-19:00 | 840.08 | 20-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.173937E+10 | 0.459808E+09 | 163.83 | 0.172326E+10 | 16104164.55 | 0.00 | 0.75 | 17-MAY-13:00 | 0.00 | 01-MAY-00:10 | 7280.28 | 17-MAY-13:00 | 7280.28 | 17-MAY-13:00 | 471.74 | 30-MAY-17:10 | 1965.83 | 17-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.754562E+10 | 0.203546E+10 | 341.93 | 0.719272E+10 | 0.352897E+09 | 0.00 | 1.00 | 06-JUN-06:03 | 0.00 | 01-JUN-00:10 | 22022.97 | 25-JUN-07:02 | 22022.97 | 25-JUN-07:02 | 7567.07 | 18-JUN-07:03 | 5112.50 | 25-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.805115E+10 | 0.215392E+10 | 349.73 | 0.754387E+10 | 0.507285E+09 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:02 | 23615.69 | 24-JUL-06:02 | 22167.58 | 18-JUL-06:02 | 7498.58 | 24-JUL-06:02 | 5191.73 | 16-JUL-07:02 | 0.00 | 01-JUL-00:02 |
August | 0.766307E+10 | 0.202892E+10 | 350.74 | 0.734619E+10 | 0.316888E+09 | 0.00 | 1.00 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 | 23338.29 | 03-AUG-06:02 | 20124.11 | 21-AUG-06:02 | 8931.16 | 04-AUG-06:03 | 4970.02 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.556141E+10 | 0.144509E+10 | 300.90 | 0.550011E+10 | 61307700.60 | 0.00 | 1.00 | 03-SEP-07:02 | 0.00 | 01-SEP-00:05 | 22255.81 | 03-SEP-07:02 | 21008.28 | 11-SEP-06:02 | 3153.71 | 01-SEP-06:03 | 4721.42 | 03-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.856427E+09 | 0.219375E+09 | 86.92 | 0.856252E+09 | 174813.41 | 0.00 | 0.81 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 | 8198.65 | 11-OCT-14:00 | 8198.65 | 11-OCT-14:00 | 30.49 | 09-OCT-10:50 | 2074.56 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 0.190155E+09 | 49918977.36 | 27.17 | 0.190155E+09 | 0.00 | 0.00 | 0.49 | 07-NOV-14:00 | 0.00 | 01-NOV-00:05 | 4645.56 | 07-NOV-14:00 | 4645.56 | 07-NOV-14:00 | 0.00 | 09-NOV-12:10 | 1170.15 | 07-NOV-14:00 | 0.00 | 01-NOV-00:05 |
December | 42809259.70 | 11562296.69 | 9.83 | 42809259.70 | -0.0 | 0.00 | 0.32 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 2928.88 | 02-DEC-15:00 | 2928.88 | 02-DEC-15:00 | 0.00 | 02-DEC-14:40 | 772.85 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.320822E+11 | 0.851758E+10 | 1706.88 | 0.308275E+11 | 0.125466E+10 | 0.00 | ||||||||||||||
Minimum of Months | 9042512.31 | 2468607.34 | 2.67 | 9042512.31 | -0.0 | 0.00 | 0.18 | 0.00 | 1580.31 | 1580.31 | 0.00 | 426.45 | 0.00 | |||||||
Maximum of Months | 0.805115E+10 | 0.215392E+10 | 350.74 | 0.754387E+10 | 0.507285E+09 | 0.00 | 1.00 | 0.00 | 23615.69 | 22167.58 | 8931.16 | 5191.73 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 17803251.55 | 4817832.97 | 7.17 | 17803251.55 | -0.0 | 0.00 | 0.24 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 2090.56 | 20-JAN-14:00 | 2090.56 | 20-JAN-14:00 | 0.00 | 20-JAN-13:40 | 555.79 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 7438073.88 | 2038565.14 | 2.33 | 7438073.88 | 0.00 | 0.00 | 0.16 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 | 1403.90 | 18-FEB-14:00 | 1403.90 | 18-FEB-14:00 | 0.00 | 18-FEB-13:20 | 380.67 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.282438E+09 | 73199956.53 | 34.83 | 0.282438E+09 | -0.0 | 0.00 | 0.62 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 5974.36 | 14-MAR-13:00 | 5974.36 | 14-MAR-13:00 | 0.00 | 13-MAR-14:00 | 1506.20 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 85629944.30 | 23253668.90 | 25.83 | 85629943.25 | 1.05 | 0.00 | 0.34 | 20-APR-13:00 | 0.00 | 01-APR-00:05 | 3016.91 | 20-APR-13:00 | 3016.91 | 20-APR-13:00 | 0.00 | 13-APR-17:20 | 793.71 | 20-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.168111E+10 | 0.445133E+09 | 159.42 | 0.166629E+10 | 14812840.95 | 0.00 | 0.75 | 17-MAY-13:00 | 0.00 | 01-MAY-00:10 | 7219.98 | 17-MAY-13:00 | 7219.98 | 17-MAY-13:00 | 445.96 | 30-MAY-17:10 | 1950.22 | 17-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.754927E+10 | 0.203452E+10 | 341.93 | 0.719639E+10 | 0.352880E+09 | 0.00 | 1.00 | 06-JUN-06:03 | 0.00 | 01-JUN-00:10 | 22084.88 | 27-JUN-06:02 | 22084.88 | 27-JUN-06:02 | 7657.67 | 18-JUN-07:03 | 5080.96 | 25-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.807168E+10 | 0.215664E+10 | 350.45 | 0.756435E+10 | 0.507333E+09 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:02 | 23463.55 | 24-JUL-06:02 | 22026.56 | 18-JUL-06:02 | 7441.13 | 24-JUL-06:02 | 5161.60 | 16-JUL-07:02 | 0.00 | 01-JUL-00:02 |
August | 0.767160E+10 | 0.202887E+10 | 350.88 | 0.735338E+10 | 0.318212E+09 | 0.00 | 1.00 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 | 23186.60 | 03-AUG-06:02 | 20414.30 | 21-AUG-06:02 | 9092.85 | 04-AUG-06:03 | 4937.72 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.555870E+10 | 0.144303E+10 | 300.40 | 0.549655E+10 | 62153201.17 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 | 22304.20 | 03-SEP-07:02 | 21879.02 | 11-SEP-06:02 | 3330.72 | 01-SEP-06:03 | 4731.72 | 03-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.833854E+09 | 0.213636E+09 | 85.25 | 0.833690E+09 | 163708.55 | 0.00 | 0.81 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 | 8153.56 | 11-OCT-14:00 | 8153.56 | 11-OCT-14:00 | 28.35 | 09-OCT-10:50 | 2062.72 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 0.172601E+09 | 45464685.08 | 25.83 | 0.172601E+09 | -0.0 | 0.00 | 0.48 | 07-NOV-14:00 | 0.00 | 01-NOV-00:05 | 4461.89 | 07-NOV-14:00 | 4461.89 | 07-NOV-14:00 | 0.00 | 07-NOV-16:00 | 1128.50 | 07-NOV-14:00 | 0.00 | 01-NOV-00:05 |
December | 35984642.85 | 9750611.38 | 8.83 | 35984642.85 | -0.0 | 0.00 | 0.31 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 2732.91 | 02-DEC-15:00 | 2732.91 | 02-DEC-15:00 | 0.00 | 02-DEC-15:20 | 724.71 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.319681E+11 | 0.848035E+10 | 1693.15 | 0.307125E+11 | 0.125555E+10 | 0.00 | ||||||||||||||
Minimum of Months | 7438073.88 | 2038565.14 | 2.33 | 7438073.88 | -0.0 | 0.00 | 0.16 | 0.00 | 1403.90 | 1403.90 | 0.00 | 380.67 | 0.00 | |||||||
Maximum of Months | 0.807168E+10 | 0.215664E+10 | 350.88 | 0.756435E+10 | 0.507333E+09 | 0.00 | 1.00 | 0.00 | 23463.55 | 22084.88 | 9092.85 | 5161.60 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 12338715.48 | 3354800.26 | 4.17 | 12338715.48 | 0.00 | 0.00 | 0.20 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 1753.13 | 20-JAN-14:00 | 1753.13 | 20-JAN-14:00 | 0.00 | 20-JAN-14:00 | 470.60 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 4929649.46 | 1360393.16 | 2.00 | 4929649.46 | 0.00 | 0.00 | 0.13 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 | 1100.20 | 18-FEB-14:00 | 1100.20 | 18-FEB-14:00 | 0.00 | 18-FEB-14:20 | 300.97 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.250148E+09 | 65036232.69 | 31.83 | 0.250148E+09 | 0.00 | 0.00 | 0.60 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 5719.04 | 14-MAR-13:00 | 5719.04 | 14-MAR-13:00 | 0.00 | 14-MAR-13:00 | 1451.43 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 60454111.16 | 16507380.16 | 20.50 | 60454111.16 | -0.0 | 0.00 | 0.30 | 20-APR-13:00 | 0.00 | 01-APR-00:05 | 2681.25 | 20-APR-13:00 | 2681.25 | 20-APR-13:00 | 0.00 | 20-APR-13:40 | 712.04 | 20-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.154212E+10 | 0.410728E+09 | 148.08 | 0.153021E+10 | 11903763.09 | 0.00 | 0.73 | 17-MAY-13:00 | 0.00 | 01-MAY-00:10 | 7011.70 | 17-MAY-13:00 | 7011.70 | 17-MAY-13:00 | 392.91 | 30-MAY-17:10 | 1904.18 | 17-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.733305E+10 | 0.198470E+10 | 340.43 | 0.699670E+10 | 0.336356E+09 | 0.00 | 1.00 | 13-JUN-13:30 | 0.00 | 01-JUN-00:10 | 21846.66 | 25-JUN-07:02 | 21846.66 | 25-JUN-07:02 | 7002.68 | 18-JUN-07:03 | 5071.57 | 25-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.785372E+10 | 0.210702E+10 | 348.56 | 0.736958E+10 | 0.484145E+09 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:02 | 23456.57 | 24-JUL-06:02 | 22015.34 | 18-JUL-06:02 | 7463.20 | 24-JUL-06:02 | 5152.86 | 16-JUL-07:02 | 0.00 | 01-JUL-00:02 |
August | 0.746645E+10 | 0.198256E+10 | 350.46 | 0.716255E+10 | 0.303902E+09 | 0.00 | 1.00 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 | 23135.40 | 03-AUG-06:02 | 19432.26 | 21-AUG-06:02 | 8219.34 | 04-AUG-06:03 | 4926.81 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.538611E+10 | 0.140393E+10 | 297.17 | 0.532766E+10 | 58447459.94 | 0.00 | 1.00 | 03-SEP-07:02 | 0.00 | 01-SEP-00:05 | 21148.86 | 03-SEP-07:02 | 20647.35 | 11-SEP-06:02 | 2767.81 | 01-SEP-06:03 | 4486.54 | 03-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.770507E+09 | 0.197958E+09 | 79.08 | 0.770390E+09 | 117563.53 | 0.00 | 0.80 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 | 7987.15 | 11-OCT-14:00 | 7987.15 | 11-OCT-14:00 | 20.58 | 09-OCT-10:50 | 2029.01 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 0.146028E+09 | 38693814.76 | 23.00 | 0.146028E+09 | -0.0 | 0.00 | 0.45 | 07-NOV-14:00 | 0.00 | 01-NOV-00:05 | 4159.59 | 07-NOV-14:00 | 4159.59 | 07-NOV-14:00 | 0.00 | 09-NOV-13:20 | 1060.61 | 07-NOV-14:00 | 0.00 | 01-NOV-00:05 |
December | 26602823.71 | 7247787.30 | 7.50 | 26602823.71 | -0.0 | 0.00 | 0.28 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 2434.50 | 02-DEC-15:00 | 2434.50 | 02-DEC-15:00 | 0.00 | 02-DEC-13:50 | 651.03 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.308525E+11 | 0.821909E+10 | 1652.80 | 0.296576E+11 | 0.119487E+10 | 0.00 | ||||||||||||||
Minimum of Months | 4929649.46 | 1360393.16 | 2.00 | 4929649.46 | -0.0 | 0.00 | 0.13 | 0.00 | 1100.20 | 1100.20 | 0.00 | 300.97 | 0.00 | |||||||
Maximum of Months | 0.785372E+10 | 0.210702E+10 | 350.46 | 0.736958E+10 | 0.484145E+09 | 0.00 | 1.00 | 0.00 | 23456.57 | 22015.34 | 8219.34 | 5152.86 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 14006775.01 | 3839880.53 | 2.83 | 14006775.01 | 0.00 | 0.00 | 0.17 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 2451.47 | 20-JAN-14:00 | 2451.47 | 20-JAN-14:00 | 0.00 | 20-JAN-13:10 | 663.70 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 4755583.77 | 1325159.36 | 2.00 | 4755583.77 | -0.0 | 0.00 | 0.08 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 | 1065.37 | 18-FEB-14:00 | 1065.37 | 18-FEB-14:00 | 0.00 | 18-FEB-13:50 | 295.49 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.393378E+09 | 0.102108E+09 | 25.58 | 0.393378E+09 | -0.0 | 0.00 | 0.60 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 9751.16 | 14-MAR-13:00 | 9751.16 | 14-MAR-13:00 | 0.00 | 13-MAR-15:00 | 2469.76 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 76083692.84 | 20872755.57 | 15.83 | 76083692.84 | -0.0 | 0.00 | 0.28 | 20-APR-13:00 | 0.00 | 01-APR-00:05 | 4223.74 | 20-APR-13:00 | 4223.74 | 20-APR-13:00 | 0.00 | 20-APR-12:30 | 1127.07 | 20-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.240689E+10 | 0.642129E+09 | 135.33 | 0.238984E+10 | 17049157.93 | 0.00 | 0.75 | 17-MAY-13:00 | 0.00 | 01-MAY-00:10 | 12297.05 | 17-MAY-13:00 | 12297.05 | 17-MAY-13:00 | 525.56 | 30-MAY-17:00 | 3317.91 | 17-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.127955E+11 | 0.345041E+10 | 333.02 | 0.122050E+11 | 0.590548E+09 | 0.00 | 1.00 | 06-JUN-07:03 | 0.00 | 01-JUN-00:10 | 37114.25 | 26-JUN-07:02 | 37114.25 | 26-JUN-07:02 | 9252.06 | 18-JUN-08:63 | 8871.03 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.135795E+11 | 0.362409E+10 | 335.85 | 0.127511E+11 | 0.828321E+09 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:02 | 39730.48 | 24-JUL-07:02 | 37342.68 | 18-JUL-07:02 | 7779.09 | 26-JUL-07:03 | 9251.71 | 16-JUL-08:62 | 0.00 | 01-JUL-00:02 |
August | 0.131949E+11 | 0.348506E+10 | 343.49 | 0.126442E+11 | 0.550724E+09 | 0.00 | 1.00 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 | 39183.37 | 03-AUG-07:02 | 35676.06 | 20-AUG-08:62 | 11777.78 | 04-AUG-07:03 | 8487.84 | 20-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.923937E+10 | 0.239529E+10 | 287.75 | 0.913744E+10 | 0.101926E+09 | 0.00 | 1.00 | 03-SEP-08:62 | 0.00 | 01-SEP-00:05 | 37151.49 | 11-SEP-07:02 | 37151.49 | 11-SEP-07:02 | 2919.06 | 03-SEP-08:62 | 7865.62 | 11-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.127200E+10 | 0.325033E+09 | 75.25 | 0.127171E+10 | 289736.51 | 0.00 | 0.84 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 | 14292.16 | 11-OCT-14:10 | 14292.16 | 11-OCT-14:10 | 117.72 | 01-OCT-08:70 | 3573.04 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 0.218911E+09 | 58148448.79 | 21.00 | 0.218911E+09 | -0.0 | 0.00 | 0.44 | 07-NOV-14:00 | 0.00 | 01-NOV-00:05 | 6807.23 | 07-NOV-14:00 | 6807.23 | 07-NOV-14:00 | 0.00 | 07-NOV-15:20 | 1741.02 | 07-NOV-14:00 | 0.00 | 01-NOV-00:05 |
December | 32711853.81 | 8956664.03 | 6.67 | 32711853.81 | -0.0 | 0.00 | 0.25 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 3750.62 | 02-DEC-15:00 | 3750.62 | 02-DEC-15:00 | 0.00 | 02-DEC-13:00 | 1008.83 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.532280E+11 | 0.141173E+11 | 1584.61 | 0.511391E+11 | 0.208886E+10 | 0.00 | ||||||||||||||
Minimum of Months | 4755583.77 | 1325159.36 | 2.00 | 4755583.77 | -0.0 | 0.00 | 0.08 | 0.00 | 1065.37 | 1065.37 | 0.00 | 295.49 | 0.00 | |||||||
Maximum of Months | 0.135795E+11 | 0.362409E+10 | 343.49 | 0.127511E+11 | 0.828321E+09 | 0.00 | 1.00 | 0.00 | 39730.48 | 37342.68 | 11777.78 | 9251.71 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 6351898.64 | 1745927.07 | 2.67 | 6351898.64 | -0.0 | 0.00 | 0.16 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 1182.51 | 20-JAN-14:00 | 1182.51 | 20-JAN-14:00 | 0.00 | 20-JAN-14:50 | 321.08 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 1449140.18 | 405391.60 | 1.67 | 1449140.18 | 0.00 | 0.00 | 0.06 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 | 409.69 | 18-FEB-14:00 | 409.69 | 18-FEB-14:00 | 0.00 | 18-FEB-14:00 | 114.18 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.195575E+09 | 50827972.76 | 23.50 | 0.195575E+09 | -0.0 | 0.00 | 0.59 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4956.00 | 14-MAR-13:00 | 4956.00 | 14-MAR-13:00 | 0.00 | 13-MAR-14:40 | 1258.80 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 32032995.71 | 8811633.16 | 13.67 | 32032995.71 | -0.0 | 0.00 | 0.27 | 20-APR-13:00 | 0.00 | 01-APR-00:05 | 2064.40 | 20-APR-13:00 | 2064.40 | 20-APR-13:00 | 0.00 | 19-APR-14:10 | 553.08 | 20-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.120670E+10 | 0.322491E+09 | 132.00 | 0.119879E+10 | 7914525.05 | 0.00 | 0.75 | 17-MAY-13:00 | 0.00 | 01-MAY-00:10 | 6316.97 | 17-MAY-13:00 | 6316.97 | 17-MAY-13:00 | 251.18 | 30-MAY-17:00 | 1706.88 | 17-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.656985E+10 | 0.177386E+10 | 332.08 | 0.627095E+10 | 0.298894E+09 | 0.00 | 1.00 | 13-JUN-07:03 | 0.00 | 01-JUN-00:10 | 18875.55 | 27-JUN-07:02 | 18875.55 | 27-JUN-07:02 | 4179.44 | 18-JUN-08:63 | 4591.86 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.698015E+10 | 0.186499E+10 | 335.33 | 0.655900E+10 | 0.421156E+09 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:02 | 20582.68 | 24-JUL-07:02 | 19343.78 | 18-JUL-07:02 | 3789.34 | 24-JUL-07:02 | 4788.09 | 16-JUL-08:62 | 0.00 | 01-JUL-00:02 |
August | 0.678455E+10 | 0.179374E+10 | 343.22 | 0.650535E+10 | 0.279195E+09 | 0.00 | 1.00 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 | 19870.13 | 20-AUG-08:62 | 18489.70 | 20-AUG-08:62 | 5467.61 | 04-AUG-07:03 | 4396.26 | 20-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.475243E+10 | 0.123287E+10 | 286.08 | 0.470144E+10 | 50990139.70 | 0.00 | 1.00 | 03-SEP-08:62 | 0.00 | 01-SEP-00:05 | 19242.17 | 11-SEP-07:02 | 19242.17 | 11-SEP-07:02 | 1416.87 | 03-SEP-08:62 | 4073.90 | 11-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.645779E+09 | 0.164978E+09 | 72.08 | 0.645656E+09 | 123288.43 | 0.00 | 0.84 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 | 7417.57 | 11-OCT-14:10 | 7417.57 | 11-OCT-14:10 | 44.94 | 01-OCT-08:70 | 1853.60 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 0.108713E+09 | 28895316.22 | 20.17 | 0.108713E+09 | 0.00 | 0.00 | 0.43 | 07-NOV-14:00 | 0.00 | 01-NOV-00:05 | 3499.37 | 07-NOV-14:00 | 3499.37 | 07-NOV-14:00 | 0.00 | 09-NOV-11:40 | 895.73 | 07-NOV-14:00 | 0.00 | 01-NOV-00:05 |
December | 14784463.33 | 4047514.85 | 6.00 | 14784463.33 | -0.0 | 0.00 | 0.25 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 1948.32 | 02-DEC-15:00 | 1948.32 | 02-DEC-15:00 | 0.00 | 02-DEC-15:10 | 523.95 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.272984E+11 | 0.724767E+10 | 1568.46 | 0.262401E+11 | 0.105827E+10 | 0.00 | ||||||||||||||
Minimum of Months | 1449140.18 | 405391.60 | 1.67 | 1449140.18 | -0.0 | 0.00 | 0.06 | 0.00 | 409.69 | 409.69 | 0.00 | 114.18 | 0.00 | |||||||
Maximum of Months | 0.698015E+10 | 0.186499E+10 | 343.22 | 0.655900E+10 | 0.421156E+09 | 0.00 | 1.00 | 0.00 | 20582.68 | 19343.78 | 5467.61 | 4788.09 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 5294680.22 | 1459229.63 | 2.67 | 5294680.22 | 0.00 | 0.00 | 0.14 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 1065.13 | 20-JAN-14:00 | 1065.13 | 20-JAN-14:00 | 0.00 | 20-JAN-13:40 | 290.28 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 843535.90 | 236643.88 | 1.33 | 843535.90 | -0.0 | 0.00 | 0.04 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 | 295.69 | 18-FEB-14:00 | 295.69 | 18-FEB-14:00 | 0.00 | 18-FEB-14:10 | 82.73 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.183678E+09 | 47891014.83 | 21.50 | 0.183678E+09 | -0.0 | 0.00 | 0.58 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4792.33 | 14-MAR-13:00 | 4792.33 | 14-MAR-13:00 | 0.00 | 14-MAR-12:30 | 1222.19 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 27195147.38 | 7498352.20 | 12.33 | 27195147.38 | -0.0 | 0.00 | 0.26 | 20-APR-13:00 | 0.00 | 01-APR-00:05 | 1949.23 | 20-APR-13:00 | 1949.23 | 20-APR-13:00 | 0.00 | 20-APR-12:50 | 523.99 | 20-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.115195E+10 | 0.308654E+09 | 129.67 | 0.114499E+10 | 6956434.93 | 0.00 | 0.74 | 17-MAY-13:00 | 0.00 | 01-MAY-00:10 | 6213.08 | 17-MAY-13:00 | 6213.08 | 17-MAY-13:00 | 227.33 | 31-MAY-19:00 | 1682.15 | 17-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.648732E+10 | 0.175322E+10 | 331.59 | 0.619398E+10 | 0.293338E+09 | 0.00 | 1.00 | 13-JUN-07:03 | 0.00 | 01-JUN-00:10 | 18724.75 | 25-JUN-08:62 | 18724.75 | 25-JUN-08:62 | 3805.00 | 18-JUN-08:63 | 4561.66 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.689887E+10 | 0.184469E+10 | 334.55 | 0.648523E+10 | 0.413642E+09 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:02 | 20459.00 | 24-JUL-07:02 | 19226.64 | 18-JUL-07:02 | 3775.72 | 24-JUL-07:02 | 4756.80 | 16-JUL-08:62 | 0.00 | 01-JUL-00:02 |
August | 0.670935E+10 | 0.177506E+10 | 342.55 | 0.643475E+10 | 0.274605E+09 | 0.00 | 1.00 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 | 19750.53 | 20-AUG-08:62 | 18370.55 | 20-AUG-08:62 | 5234.48 | 04-AUG-07:03 | 4369.84 | 20-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.468895E+10 | 0.121738E+10 | 285.58 | 0.463905E+10 | 49903196.28 | 0.00 | 1.00 | 03-SEP-08:62 | 0.00 | 01-SEP-00:05 | 19059.58 | 11-SEP-07:02 | 19059.58 | 11-SEP-07:02 | 1381.11 | 03-SEP-08:62 | 4035.26 | 11-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.619513E+09 | 0.158408E+09 | 70.08 | 0.619408E+09 | 104985.89 | 0.00 | 0.84 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 | 7333.76 | 11-OCT-14:10 | 7333.76 | 11-OCT-14:10 | 28.43 | 01-OCT-08:70 | 1834.74 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 99963437.97 | 26636831.61 | 19.83 | 99963437.97 | 0.00 | 0.00 | 0.42 | 07-NOV-14:00 | 0.00 | 01-NOV-00:05 | 3365.53 | 07-NOV-14:00 | 3365.53 | 07-NOV-14:00 | 0.00 | 06-NOV-14:20 | 864.53 | 07-NOV-14:00 | 0.00 | 01-NOV-00:05 |
December | 12854455.77 | 3522962.90 | 5.33 | 12854455.77 | -0.0 | 0.00 | 0.24 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 1855.90 | 02-DEC-15:00 | 1855.90 | 02-DEC-15:00 | 0.00 | 02-DEC-15:10 | 500.43 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.268858E+11 | 0.714465E+10 | 1557.03 | 0.258472E+11 | 0.103855E+10 | 0.00 | ||||||||||||||
Minimum of Months | 843535.90 | 236643.88 | 1.33 | 843535.90 | -0.0 | 0.00 | 0.04 | 0.00 | 295.69 | 295.69 | 0.00 | 82.73 | 0.00 | |||||||
Maximum of Months | 0.689887E+10 | 0.184469E+10 | 342.55 | 0.648523E+10 | 0.413642E+09 | 0.00 | 1.00 | 0.00 | 20459.00 | 19226.64 | 5234.48 | 4756.80 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 2824663.15 | 783123.62 | 1.83 | 2824663.15 | 0.00 | 0.00 | 0.10 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 765.18 | 20-JAN-14:00 | 765.18 | 20-JAN-14:00 | 0.00 | 20-JAN-14:00 | 210.64 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.157082E+09 | 41341908.99 | 19.50 | 0.157082E+09 | 0.00 | 0.00 | 0.54 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4402.96 | 14-MAR-13:00 | 4402.96 | 14-MAR-13:00 | 0.00 | 14-MAR-16:20 | 1135.61 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 16578274.67 | 4594151.25 | 9.83 | 16578274.67 | -0.0 | 0.00 | 0.22 | 20-APR-13:00 | 0.00 | 01-APR-00:05 | 1678.79 | 20-APR-13:00 | 1678.79 | 20-APR-13:00 | 0.00 | 19-APR-14:00 | 455.22 | 20-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.102416E+10 | 0.276381E+09 | 119.33 | 0.101925E+10 | 4908544.56 | 0.00 | 0.72 | 17-MAY-13:00 | 0.00 | 01-MAY-00:10 | 5971.76 | 17-MAY-13:00 | 5971.76 | 17-MAY-13:00 | 203.59 | 31-MAY-19:00 | 1627.23 | 17-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.632099E+10 | 0.171337E+10 | 328.17 | 0.604014E+10 | 0.280855E+09 | 0.00 | 1.00 | 13-JUN-12:10 | 0.00 | 01-JUN-00:10 | 18601.79 | 25-JUN-08:62 | 18601.79 | 25-JUN-08:62 | 2565.64 | 18-JUN-08:63 | 4531.70 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.673632E+10 | 0.180591E+10 | 332.58 | 0.634106E+10 | 0.395255E+09 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:02 | 20362.23 | 24-JUL-07:02 | 19133.34 | 18-JUL-07:02 | 3789.19 | 24-JUL-07:02 | 4727.23 | 16-JUL-08:62 | 0.00 | 01-JUL-00:02 |
August | 0.657734E+10 | 0.174354E+10 | 339.99 | 0.631190E+10 | 0.265434E+09 | 0.00 | 1.00 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 | 19657.77 | 20-AUG-08:62 | 18261.15 | 20-AUG-08:62 | 4524.15 | 04-AUG-07:03 | 4349.43 | 20-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.457053E+10 | 0.118928E+10 | 283.19 | 0.452284E+10 | 47688458.64 | 0.00 | 1.00 | 03-SEP-08:62 | 0.00 | 01-SEP-00:05 | 17525.08 | 11-SEP-07:02 | 17525.08 | 11-SEP-07:02 | 1279.62 | 03-SEP-08:62 | 3710.80 | 11-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.560394E+09 | 0.143671E+09 | 64.58 | 0.560327E+09 | 66259.12 | 0.00 | 0.83 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 | 7172.62 | 11-OCT-14:10 | 7172.62 | 11-OCT-14:10 | 13.55 | 01-OCT-14:20 | 1801.09 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 79912291.79 | 21424768.15 | 18.33 | 79912291.79 | 0.00 | 0.00 | 0.39 | 07-NOV-14:00 | 0.00 | 01-NOV-00:05 | 3061.76 | 07-NOV-14:00 | 3061.76 | 07-NOV-14:00 | 0.00 | 07-NOV-15:20 | 793.72 | 07-NOV-14:00 | 0.00 | 01-NOV-00:05 |
December | 8664631.08 | 2383007.07 | 3.83 | 8664631.08 | -0.0 | 0.00 | 0.21 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 1603.54 | 02-DEC-15:00 | 1603.54 | 02-DEC-15:00 | 0.00 | 02-DEC-14:50 | 435.90 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.260548E+11 | 0.694269E+10 | 1521.18 | 0.250606E+11 | 0.994208E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.673632E+10 | 0.180591E+10 | 339.99 | 0.634106E+10 | 0.395255E+09 | 0.00 | 1.00 | 0.00 | 20362.23 | 19133.34 | 4524.15 | 4727.23 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 430699.18 | 120902.71 | 1.00 | 430699.18 | 0.00 | 0.00 | 0.04 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 271.74 | 20-JAN-14:00 | 271.74 | 20-JAN-14:00 | 0.00 | 20-JAN-13:50 | 76.12 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.122802E+09 | 32884272.68 | 17.67 | 0.122802E+09 | -0.0 | 0.00 | 0.48 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4069.10 | 14-MAR-13:00 | 4069.10 | 14-MAR-13:00 | 0.00 | 14-MAR-13:00 | 1067.02 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 9225384.97 | 2565632.15 | 4.83 | 9225384.97 | 0.00 | 0.00 | 0.19 | 20-APR-13:00 | 0.00 | 01-APR-00:05 | 1522.21 | 20-APR-13:00 | 1522.21 | 20-APR-13:00 | 0.00 | 19-APR-13:00 | 415.96 | 20-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.895903E+09 | 0.244492E+09 | 102.17 | 0.893231E+09 | 2672408.45 | 0.00 | 0.68 | 17-MAY-13:00 | 0.00 | 01-MAY-00:10 | 5928.10 | 17-MAY-13:00 | 5928.10 | 17-MAY-13:00 | 180.67 | 31-MAY-18:40 | 1631.56 | 17-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.647056E+10 | 0.176139E+10 | 322.81 | 0.619706E+10 | 0.273504E+09 | 0.00 | 1.00 | 13-JUN-12:10 | 0.00 | 01-JUN-00:10 | 19661.76 | 25-JUN-08:62 | 19661.76 | 25-JUN-08:62 | 2202.37 | 18-JUN-12:00 | 4789.93 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.688064E+10 | 0.185206E+10 | 325.19 | 0.650889E+10 | 0.371748E+09 | 0.00 | 1.00 | 09-JUL-13:40 | 0.00 | 01-JUL-00:02 | 20764.91 | 23-JUL-08:62 | 19790.37 | 17-JUL-07:02 | 2934.58 | 24-JUL-07:02 | 5008.26 | 16-JUL-08:62 | 0.00 | 01-JUL-00:02 |
August | 0.688293E+10 | 0.182449E+10 | 331.26 | 0.661103E+10 | 0.271894E+09 | 0.00 | 1.00 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 | 15521.29 | 20-AUG-08:62 | 13948.56 | 20-AUG-08:62 | 3367.44 | 05-AUG-14:30 | 3590.88 | 16-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.473514E+10 | 0.123268E+10 | 273.80 | 0.468786E+10 | 47278799.47 | 0.00 | 1.00 | 09-SEP-11:20 | 0.00 | 01-SEP-00:05 | 11772.85 | 11-SEP-07:02 | 11772.85 | 11-SEP-07:02 | 1104.19 | 01-SEP-14:00 | 2850.31 | 09-SEP-13:00 | 0.00 | 01-SEP-00:05 |
October | 0.503762E+09 | 0.129646E+09 | 52.67 | 0.503740E+09 | 21851.96 | 0.00 | 0.80 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 | 7247.28 | 11-OCT-14:10 | 7247.28 | 11-OCT-14:10 | 7.24 | 01-OCT-14:30 | 1834.71 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 56423470.48 | 15263263.32 | 16.00 | 56423470.48 | 0.00 | 0.00 | 0.33 | 07-NOV-14:00 | 0.00 | 01-NOV-00:05 | 2721.62 | 07-NOV-14:00 | 2721.62 | 07-NOV-14:00 | 0.00 | 07-NOV-14:20 | 716.34 | 07-NOV-14:00 | 0.00 | 01-NOV-00:05 |
December | 4236164.98 | 1174770.46 | 2.33 | 4236164.98 | -0.0 | 0.00 | 0.16 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 1231.30 | 02-DEC-15:00 | 1231.30 | 02-DEC-15:00 | 0.00 | 02-DEC-14:40 | 339.61 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.265620E+11 | 0.709677E+10 | 1449.73 | 0.255949E+11 | 0.967120E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.688293E+10 | 0.185206E+10 | 331.26 | 0.661103E+10 | 0.371748E+09 | 0.00 | 1.00 | 0.00 | 20764.91 | 19790.37 | 3367.44 | 5008.26 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 228.22 | 91.62 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 217.77 | 95.12 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 162.37 | 76.53 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 96.07 | 70.19 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 95.38 | 44.19 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.64 | 24.47 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.98 | 22.23 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 147.32 | 25.83 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.70 | 39.31 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 189.16 | 78.77 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 223.83 | 87.92 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 205.12 | 104.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 163.82 | 63.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 95.38 | 22.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 228.22 | 104.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 228.22 | 91.62 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 217.77 | 95.12 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 162.37 | 76.53 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 96.07 | 70.19 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 95.38 | 44.19 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.64 | 24.47 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.98 | 22.23 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 147.32 | 25.83 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.70 | 39.31 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 189.16 | 78.77 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 223.83 | 87.92 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 205.12 | 104.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 163.82 | 63.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 95.38 | 22.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 228.22 | 104.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 228.22 | 91.62 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 217.77 | 95.12 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 162.37 | 76.53 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 96.07 | 70.19 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 95.38 | 44.19 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.64 | 24.47 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.98 | 22.23 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 147.32 | 25.83 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.70 | 39.31 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 189.16 | 78.77 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 223.83 | 87.92 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 205.12 | 104.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 163.82 | 63.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 95.38 | 22.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 228.22 | 104.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 228.22 | 91.62 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 217.77 | 95.12 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 162.37 | 76.53 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 96.07 | 70.19 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 95.38 | 44.19 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.64 | 24.47 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.98 | 22.23 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 147.32 | 25.83 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.70 | 39.31 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 189.16 | 78.77 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 223.83 | 87.92 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 205.12 | 104.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 163.82 | 63.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 95.38 | 22.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 228.22 | 104.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 237.18 | 195.11 | 42.07 | 274.76 | 108.87 | 0.00 | 0.00 | 0.00 |
February | 227.50 | 181.38 | 46.12 | 262.38 | 112.79 | 0.00 | 0.00 | 0.00 |
March | 167.73 | 110.36 | 57.37 | 195.60 | 90.78 | 0.00 | 0.00 | 0.00 |
April | 108.63 | 43.68 | 64.95 | 115.85 | 83.20 | 0.00 | 0.00 | 0.00 |
May | 99.55 | 18.25 | 81.30 | 114.84 | 52.50 | 0.00 | 0.00 | 0.00 |
June | 91.78 | 16.78 | 75.01 | 132.79 | 29.25 | 0.00 | 0.00 | 0.00 |
July | 95.54 | 17.11 | 78.44 | 139.19 | 26.57 | 0.00 | 0.00 | 0.00 |
August | 121.65 | 50.85 | 70.79 | 176.93 | 30.87 | 0.00 | 0.00 | 0.00 |
September | 156.51 | 87.33 | 69.18 | 213.58 | 46.88 | 0.00 | 0.00 | 0.00 |
October | 187.14 | 132.78 | 54.36 | 227.58 | 93.58 | 0.00 | 0.00 | 0.00 |
November | 228.01 | 181.75 | 46.25 | 269.47 | 104.42 | 0.00 | 0.00 | 0.00 |
December | 218.03 | 176.47 | 41.56 | 247.17 | 123.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.23 | 100.53 | 60.70 | 197.14 | 75.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.78 | 16.78 | 41.56 | 114.84 | 26.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.18 | 195.11 | 81.30 | 274.76 | 123.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 237.18 | 195.11 | 42.07 | 274.76 | 108.87 | 0.00 | 0.00 | 0.00 |
February | 227.50 | 181.38 | 46.12 | 262.38 | 112.79 | 0.00 | 0.00 | 0.00 |
March | 167.73 | 110.36 | 57.37 | 195.60 | 90.78 | 0.00 | 0.00 | 0.00 |
April | 108.63 | 43.68 | 64.95 | 115.85 | 83.20 | 0.00 | 0.00 | 0.00 |
May | 99.55 | 18.25 | 81.30 | 114.84 | 52.50 | 0.00 | 0.00 | 0.00 |
June | 91.78 | 16.78 | 75.01 | 132.79 | 29.25 | 0.00 | 0.00 | 0.00 |
July | 95.54 | 17.11 | 78.44 | 139.19 | 26.57 | 0.00 | 0.00 | 0.00 |
August | 121.65 | 50.85 | 70.79 | 176.93 | 30.87 | 0.00 | 0.00 | 0.00 |
September | 156.51 | 87.33 | 69.18 | 213.58 | 46.88 | 0.00 | 0.00 | 0.00 |
October | 187.14 | 132.78 | 54.36 | 227.58 | 93.58 | 0.00 | 0.00 | 0.00 |
November | 228.01 | 181.75 | 46.25 | 269.47 | 104.42 | 0.00 | 0.00 | 0.00 |
December | 218.03 | 176.47 | 41.56 | 247.17 | 123.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.23 | 100.53 | 60.70 | 197.14 | 75.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.78 | 16.78 | 41.56 | 114.84 | 26.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.18 | 195.11 | 81.30 | 274.76 | 123.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 226.19 | 96.81 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 215.70 | 100.17 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 160.70 | 81.14 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 94.51 | 75.17 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 94.02 | 46.42 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.43 | 24.83 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.77 | 22.59 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 147.14 | 26.12 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.32 | 39.96 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 188.08 | 81.95 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 222.05 | 92.54 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 203.32 | 109.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 162.63 | 66.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 94.02 | 22.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 226.19 | 109.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 226.19 | 96.81 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 215.70 | 100.17 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 160.70 | 81.14 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 94.51 | 75.17 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 94.02 | 46.42 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.43 | 24.83 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.77 | 22.59 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 147.14 | 26.12 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.32 | 39.96 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 188.08 | 81.95 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 222.05 | 92.54 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 203.32 | 109.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 162.63 | 66.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 94.02 | 22.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 226.19 | 109.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 237.18 | 195.11 | 42.07 | 272.38 | 114.96 | 0.00 | 0.00 | 0.00 |
February | 227.50 | 181.38 | 46.12 | 259.97 | 118.71 | 0.00 | 0.00 | 0.00 |
March | 167.73 | 110.36 | 57.37 | 193.64 | 96.20 | 0.00 | 0.00 | 0.00 |
April | 108.63 | 43.68 | 64.95 | 114.01 | 89.03 | 0.00 | 0.00 | 0.00 |
May | 99.55 | 18.25 | 81.30 | 113.24 | 55.11 | 0.00 | 0.00 | 0.00 |
June | 91.78 | 16.78 | 75.01 | 132.54 | 29.67 | 0.00 | 0.00 | 0.00 |
July | 95.54 | 17.11 | 78.44 | 138.95 | 26.99 | 0.00 | 0.00 | 0.00 |
August | 121.65 | 50.85 | 70.79 | 176.73 | 31.20 | 0.00 | 0.00 | 0.00 |
September | 156.51 | 87.33 | 69.18 | 213.16 | 47.64 | 0.00 | 0.00 | 0.00 |
October | 187.14 | 132.78 | 54.36 | 226.33 | 97.29 | 0.00 | 0.00 | 0.00 |
November | 228.01 | 181.75 | 46.25 | 267.40 | 109.83 | 0.00 | 0.00 | 0.00 |
December | 218.03 | 176.47 | 41.56 | 245.08 | 129.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.23 | 100.53 | 60.70 | 195.75 | 78.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.78 | 16.78 | 41.56 | 113.24 | 26.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.18 | 195.11 | 81.30 | 272.38 | 129.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 226.64 | 94.62 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 216.13 | 97.87 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 161.01 | 79.50 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 94.85 | 73.26 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 94.13 | 46.58 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.04 | 26.61 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.23 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 146.91 | 28.04 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.13 | 41.62 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 188.24 | 81.49 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 222.53 | 90.81 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 203.71 | 107.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 162.74 | 65.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 94.13 | 24.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 226.64 | 107.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 226.64 | 94.62 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 216.13 | 97.87 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 161.01 | 79.50 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 94.85 | 73.26 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 94.13 | 46.58 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.04 | 26.61 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.23 | 24.51 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 146.91 | 28.04 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.13 | 41.62 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 188.24 | 81.49 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 222.53 | 90.81 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 203.71 | 107.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 162.74 | 65.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 94.13 | 24.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 226.64 | 107.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 235.88 | 194.04 | 41.84 | 271.44 | 111.76 | 0.00 | 0.00 | 0.00 |
February | 226.26 | 180.39 | 45.87 | 259.06 | 115.36 | 0.00 | 0.00 | 0.00 |
March | 166.81 | 109.75 | 57.06 | 192.95 | 93.75 | 0.00 | 0.00 | 0.00 |
April | 108.04 | 43.44 | 64.60 | 113.80 | 86.31 | 0.00 | 0.00 | 0.00 |
May | 99.01 | 18.15 | 80.86 | 112.76 | 54.98 | 0.00 | 0.00 | 0.00 |
June | 91.28 | 16.68 | 74.60 | 131.36 | 31.58 | 0.00 | 0.00 | 0.00 |
July | 95.02 | 17.02 | 78.01 | 137.56 | 29.08 | 0.00 | 0.00 | 0.00 |
August | 120.98 | 50.58 | 70.41 | 175.49 | 33.26 | 0.00 | 0.00 | 0.00 |
September | 155.66 | 86.86 | 68.80 | 211.77 | 49.32 | 0.00 | 0.00 | 0.00 |
October | 186.12 | 132.06 | 54.06 | 225.29 | 96.21 | 0.00 | 0.00 | 0.00 |
November | 226.76 | 180.76 | 46.00 | 266.51 | 107.20 | 0.00 | 0.00 | 0.00 |
December | 216.84 | 175.51 | 41.33 | 244.20 | 126.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.35 | 99.98 | 60.37 | 194.81 | 77.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.28 | 16.68 | 41.33 | 112.76 | 29.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.88 | 194.04 | 80.86 | 271.44 | 126.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 226.95 | 93.56 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 216.41 | 96.84 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 161.24 | 78.62 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 95.11 | 72.25 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 94.33 | 46.11 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.03 | 26.66 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.20 | 24.60 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 146.90 | 28.10 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.14 | 41.60 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 188.38 | 80.87 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 222.82 | 89.86 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 203.97 | 106.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 162.90 | 65.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 94.33 | 24.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 226.95 | 106.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 226.95 | 93.56 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 216.41 | 96.84 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 161.24 | 78.62 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 95.11 | 72.25 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 94.33 | 46.11 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.03 | 26.66 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.20 | 24.60 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 146.90 | 28.10 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.14 | 41.60 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 188.38 | 80.87 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 222.82 | 89.86 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 203.97 | 106.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 162.90 | 65.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 94.33 | 24.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 226.95 | 106.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 235.88 | 194.04 | 41.84 | 271.80 | 110.51 | 0.00 | 0.00 | 0.00 |
February | 226.26 | 180.39 | 45.87 | 259.40 | 114.15 | 0.00 | 0.00 | 0.00 |
March | 166.81 | 109.75 | 57.06 | 193.24 | 92.71 | 0.00 | 0.00 | 0.00 |
April | 108.04 | 43.44 | 64.60 | 114.10 | 85.11 | 0.00 | 0.00 | 0.00 |
May | 99.01 | 18.15 | 80.86 | 113.00 | 54.43 | 0.00 | 0.00 | 0.00 |
June | 91.28 | 16.68 | 74.60 | 131.35 | 31.63 | 0.00 | 0.00 | 0.00 |
July | 95.02 | 17.02 | 78.01 | 137.52 | 29.18 | 0.00 | 0.00 | 0.00 |
August | 120.98 | 50.58 | 70.41 | 175.48 | 33.33 | 0.00 | 0.00 | 0.00 |
September | 155.66 | 86.86 | 68.80 | 211.79 | 49.28 | 0.00 | 0.00 | 0.00 |
October | 186.12 | 132.06 | 54.06 | 225.45 | 95.47 | 0.00 | 0.00 | 0.00 |
November | 226.76 | 180.76 | 46.00 | 266.86 | 106.06 | 0.00 | 0.00 | 0.00 |
December | 216.84 | 175.51 | 41.33 | 244.51 | 124.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.35 | 99.98 | 60.37 | 195.00 | 77.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.28 | 16.68 | 41.33 | 113.00 | 29.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.88 | 194.04 | 80.86 | 271.80 | 124.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 227.31 | 92.61 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 216.73 | 95.97 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 161.57 | 77.75 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 95.47 | 71.23 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 94.71 | 45.43 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.18 | 26.32 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.34 | 24.29 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 147.02 | 27.76 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.28 | 41.21 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 188.62 | 80.14 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 223.18 | 88.96 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 204.28 | 105.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 163.17 | 64.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 94.71 | 24.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 227.31 | 105.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 227.31 | 92.61 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 216.73 | 95.97 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 161.57 | 77.75 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 95.47 | 71.23 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 94.71 | 45.43 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.18 | 26.32 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.34 | 24.29 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 147.02 | 27.76 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.28 | 41.21 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 188.62 | 80.14 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 223.18 | 88.96 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 204.28 | 105.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 163.17 | 64.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 94.71 | 24.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 227.31 | 105.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 235.88 | 194.04 | 41.84 | 272.23 | 109.39 | 0.00 | 0.00 | 0.00 |
February | 226.26 | 180.39 | 45.87 | 259.79 | 113.12 | 0.00 | 0.00 | 0.00 |
March | 166.81 | 109.75 | 57.06 | 193.62 | 91.68 | 0.00 | 0.00 | 0.00 |
April | 108.04 | 43.44 | 64.60 | 114.53 | 83.91 | 0.00 | 0.00 | 0.00 |
May | 99.01 | 18.15 | 80.86 | 113.45 | 53.63 | 0.00 | 0.00 | 0.00 |
June | 91.28 | 16.68 | 74.60 | 131.53 | 31.23 | 0.00 | 0.00 | 0.00 |
July | 95.02 | 17.02 | 78.01 | 137.69 | 28.81 | 0.00 | 0.00 | 0.00 |
August | 120.98 | 50.58 | 70.41 | 175.62 | 32.94 | 0.00 | 0.00 | 0.00 |
September | 155.66 | 86.86 | 68.80 | 211.95 | 48.84 | 0.00 | 0.00 | 0.00 |
October | 186.12 | 132.06 | 54.06 | 225.74 | 94.61 | 0.00 | 0.00 | 0.00 |
November | 226.76 | 180.76 | 46.00 | 267.28 | 105.01 | 0.00 | 0.00 | 0.00 |
December | 216.84 | 175.51 | 41.33 | 244.88 | 123.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.35 | 99.98 | 60.37 | 195.32 | 76.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.28 | 16.68 | 41.33 | 113.45 | 28.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.88 | 194.04 | 80.86 | 272.23 | 123.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 228.52 | 90.21 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 217.95 | 93.46 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 162.61 | 75.30 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 96.46 | 68.53 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 95.61 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.32 | 25.15 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.43 | 23.21 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 147.12 | 26.62 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.51 | 40.03 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 189.25 | 78.19 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 224.20 | 86.71 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 205.52 | 102.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 163.90 | 62.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 95.61 | 23.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 228.52 | 102.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 228.52 | 90.21 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 217.95 | 93.46 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 162.61 | 75.30 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 96.46 | 68.53 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 95.61 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.32 | 25.15 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.43 | 23.21 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 147.12 | 26.62 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.51 | 40.03 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 189.25 | 78.19 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 224.20 | 86.71 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 205.52 | 102.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 163.90 | 62.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 95.61 | 23.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 228.52 | 102.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 228.52 | 90.21 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 217.95 | 93.46 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 162.61 | 75.30 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 96.46 | 68.53 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 95.61 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.32 | 25.15 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.43 | 23.21 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 147.12 | 26.62 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.51 | 40.03 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 189.25 | 78.19 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 224.20 | 86.71 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 205.52 | 102.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 163.90 | 62.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 95.61 | 23.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 228.52 | 102.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 228.52 | 90.21 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 217.95 | 93.46 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 162.61 | 75.30 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 96.46 | 68.53 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 95.61 | 43.63 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.32 | 25.15 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.43 | 23.21 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 147.12 | 26.62 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.51 | 40.03 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 189.25 | 78.19 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 224.20 | 86.71 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 205.52 | 102.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 163.90 | 62.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 95.61 | 23.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 228.52 | 102.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 235.88 | 194.04 | 41.84 | 273.62 | 106.59 | 0.00 | 0.00 | 0.00 |
February | 226.26 | 180.39 | 45.87 | 261.17 | 110.22 | 0.00 | 0.00 | 0.00 |
March | 166.81 | 109.75 | 57.06 | 194.82 | 88.84 | 0.00 | 0.00 | 0.00 |
April | 108.04 | 43.44 | 64.60 | 115.69 | 80.78 | 0.00 | 0.00 | 0.00 |
May | 99.01 | 18.15 | 80.86 | 114.51 | 51.54 | 0.00 | 0.00 | 0.00 |
June | 91.28 | 16.68 | 74.60 | 131.70 | 29.86 | 0.00 | 0.00 | 0.00 |
July | 95.02 | 17.02 | 78.01 | 137.79 | 27.55 | 0.00 | 0.00 | 0.00 |
August | 120.98 | 50.58 | 70.41 | 175.73 | 31.61 | 0.00 | 0.00 | 0.00 |
September | 155.66 | 86.86 | 68.80 | 212.21 | 47.45 | 0.00 | 0.00 | 0.00 |
October | 186.12 | 132.06 | 54.06 | 226.45 | 92.35 | 0.00 | 0.00 | 0.00 |
November | 226.76 | 180.76 | 46.00 | 268.45 | 102.40 | 0.00 | 0.00 | 0.00 |
December | 216.84 | 175.51 | 41.33 | 246.30 | 120.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.35 | 99.98 | 60.37 | 196.16 | 73.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.28 | 16.68 | 41.33 | 114.51 | 27.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.88 | 194.04 | 80.86 | 273.62 | 120.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 235.88 | 194.04 | 41.84 | 273.62 | 106.59 | 0.00 | 0.00 | 0.00 |
February | 226.26 | 180.39 | 45.87 | 261.17 | 110.22 | 0.00 | 0.00 | 0.00 |
March | 166.81 | 109.75 | 57.06 | 194.82 | 88.84 | 0.00 | 0.00 | 0.00 |
April | 108.04 | 43.44 | 64.60 | 115.69 | 80.78 | 0.00 | 0.00 | 0.00 |
May | 99.01 | 18.15 | 80.86 | 114.51 | 51.54 | 0.00 | 0.00 | 0.00 |
June | 91.28 | 16.68 | 74.60 | 131.70 | 29.86 | 0.00 | 0.00 | 0.00 |
July | 95.02 | 17.02 | 78.01 | 137.79 | 27.55 | 0.00 | 0.00 | 0.00 |
August | 120.98 | 50.58 | 70.41 | 175.73 | 31.61 | 0.00 | 0.00 | 0.00 |
September | 155.66 | 86.86 | 68.80 | 212.21 | 47.45 | 0.00 | 0.00 | 0.00 |
October | 186.12 | 132.06 | 54.06 | 226.45 | 92.35 | 0.00 | 0.00 | 0.00 |
November | 226.76 | 180.76 | 46.00 | 268.45 | 102.40 | 0.00 | 0.00 | 0.00 |
December | 216.84 | 175.51 | 41.33 | 246.30 | 120.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.35 | 99.98 | 60.37 | 196.16 | 73.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.28 | 16.68 | 41.33 | 114.51 | 27.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.88 | 194.04 | 80.86 | 273.62 | 120.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 228.21 | 90.29 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 217.55 | 93.77 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 162.36 | 75.42 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 96.30 | 68.58 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 95.63 | 43.49 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.46 | 24.87 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.57 | 22.94 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 147.17 | 26.33 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.45 | 39.77 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 189.08 | 78.20 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 223.91 | 86.79 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 205.11 | 102.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 163.76 | 62.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 95.63 | 22.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 228.21 | 102.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 228.21 | 90.29 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 217.55 | 93.77 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 162.36 | 75.42 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 96.30 | 68.58 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 95.63 | 43.49 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.46 | 24.87 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.57 | 22.94 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 147.17 | 26.33 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.45 | 39.77 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 189.08 | 78.20 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 223.91 | 86.79 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 205.11 | 102.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 163.76 | 62.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 95.63 | 22.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 228.21 | 102.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 235.88 | 194.04 | 41.84 | 273.32 | 106.64 | 0.00 | 0.00 | 0.00 |
February | 226.26 | 180.39 | 45.87 | 260.76 | 110.52 | 0.00 | 0.00 | 0.00 |
March | 166.81 | 109.75 | 57.06 | 194.58 | 88.93 | 0.00 | 0.00 | 0.00 |
April | 108.04 | 43.44 | 64.60 | 115.54 | 80.79 | 0.00 | 0.00 | 0.00 |
May | 99.01 | 18.15 | 80.86 | 114.56 | 51.35 | 0.00 | 0.00 | 0.00 |
June | 91.28 | 16.68 | 74.60 | 131.88 | 29.54 | 0.00 | 0.00 | 0.00 |
July | 95.02 | 17.02 | 78.01 | 137.98 | 27.23 | 0.00 | 0.00 | 0.00 |
August | 120.98 | 50.58 | 70.41 | 175.81 | 31.25 | 0.00 | 0.00 | 0.00 |
September | 155.66 | 86.86 | 68.80 | 212.17 | 47.14 | 0.00 | 0.00 | 0.00 |
October | 186.12 | 132.06 | 54.06 | 226.30 | 92.32 | 0.00 | 0.00 | 0.00 |
November | 226.76 | 180.76 | 46.00 | 268.16 | 102.43 | 0.00 | 0.00 | 0.00 |
December | 216.84 | 175.51 | 41.33 | 245.87 | 121.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.35 | 99.98 | 60.37 | 196.04 | 73.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.28 | 16.68 | 41.33 | 114.56 | 27.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.88 | 194.04 | 80.86 | 273.32 | 121.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 228.39 | 89.88 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 217.70 | 93.42 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 162.53 | 75.03 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 96.47 | 68.12 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 95.90 | 43.11 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.56 | 24.74 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.65 | 22.82 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 147.24 | 26.20 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.53 | 39.62 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 189.23 | 77.84 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 224.07 | 86.42 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 205.24 | 102.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 163.90 | 62.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 95.90 | 22.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 228.39 | 102.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 228.39 | 89.88 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 217.70 | 93.42 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 162.53 | 75.03 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 96.47 | 68.12 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 95.90 | 43.11 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.56 | 24.74 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.65 | 22.82 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 147.24 | 26.20 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.53 | 39.62 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 189.23 | 77.84 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 224.07 | 86.42 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 205.24 | 102.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 163.90 | 62.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 95.90 | 22.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 228.39 | 102.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 235.88 | 194.04 | 41.84 | 273.53 | 106.15 | 0.00 | 0.00 | 0.00 |
February | 226.26 | 180.39 | 45.87 | 260.95 | 110.11 | 0.00 | 0.00 | 0.00 |
March | 166.81 | 109.75 | 57.06 | 194.78 | 88.47 | 0.00 | 0.00 | 0.00 |
April | 108.04 | 43.44 | 64.60 | 115.74 | 80.25 | 0.00 | 0.00 | 0.00 |
May | 99.01 | 18.15 | 80.86 | 114.88 | 50.90 | 0.00 | 0.00 | 0.00 |
June | 91.28 | 16.68 | 74.60 | 131.99 | 29.38 | 0.00 | 0.00 | 0.00 |
July | 95.02 | 17.02 | 78.01 | 138.08 | 27.08 | 0.00 | 0.00 | 0.00 |
August | 120.98 | 50.58 | 70.41 | 175.90 | 31.11 | 0.00 | 0.00 | 0.00 |
September | 155.66 | 86.86 | 68.80 | 212.27 | 46.96 | 0.00 | 0.00 | 0.00 |
October | 186.12 | 132.06 | 54.06 | 226.48 | 91.90 | 0.00 | 0.00 | 0.00 |
November | 226.76 | 180.76 | 46.00 | 268.35 | 102.00 | 0.00 | 0.00 | 0.00 |
December | 216.84 | 175.51 | 41.33 | 246.03 | 120.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.35 | 99.98 | 60.37 | 196.21 | 73.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.28 | 16.68 | 41.33 | 114.88 | 27.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.88 | 194.04 | 80.86 | 273.53 | 120.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 228.90 | 88.54 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 218.16 | 92.12 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 163.02 | 73.68 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 96.91 | 66.68 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 96.60 | 42.02 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.74 | 24.41 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.80 | 22.54 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 147.35 | 25.94 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.68 | 39.25 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 189.61 | 76.81 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 224.49 | 85.31 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 205.62 | 101.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 164.27 | 61.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 96.60 | 22.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 228.90 | 101.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 228.90 | 88.54 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 218.16 | 92.12 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 163.02 | 73.68 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 96.91 | 66.68 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 96.60 | 42.02 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 110.74 | 24.41 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 115.80 | 22.54 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 147.35 | 25.94 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.68 | 39.25 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 189.61 | 76.81 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 224.49 | 85.31 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 205.62 | 101.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 164.27 | 61.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 96.60 | 22.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 228.90 | 101.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 235.88 | 194.04 | 41.84 | 274.14 | 104.57 | 0.00 | 0.00 | 0.00 |
February | 226.26 | 180.39 | 45.87 | 261.50 | 108.57 | 0.00 | 0.00 | 0.00 |
March | 166.81 | 109.75 | 57.06 | 195.36 | 86.88 | 0.00 | 0.00 | 0.00 |
April | 108.04 | 43.44 | 64.60 | 116.28 | 78.55 | 0.00 | 0.00 | 0.00 |
May | 99.01 | 18.15 | 80.86 | 115.72 | 49.62 | 0.00 | 0.00 | 0.00 |
June | 91.28 | 16.68 | 74.60 | 132.21 | 28.99 | 0.00 | 0.00 | 0.00 |
July | 95.02 | 17.02 | 78.01 | 138.25 | 26.75 | 0.00 | 0.00 | 0.00 |
August | 120.98 | 50.58 | 70.41 | 176.03 | 30.80 | 0.00 | 0.00 | 0.00 |
September | 155.66 | 86.86 | 68.80 | 212.45 | 46.53 | 0.00 | 0.00 | 0.00 |
October | 186.12 | 132.06 | 54.06 | 226.93 | 90.68 | 0.00 | 0.00 | 0.00 |
November | 226.76 | 180.76 | 46.00 | 268.86 | 100.69 | 0.00 | 0.00 | 0.00 |
December | 216.84 | 175.51 | 41.33 | 246.49 | 119.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.35 | 99.98 | 60.37 | 196.65 | 72.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.28 | 16.68 | 41.33 | 115.72 | 26.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.88 | 194.04 | 80.86 | 274.14 | 119.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 230.47 | 83.51 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 219.65 | 86.84 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 164.34 | 68.45 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 98.01 | 61.41 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 98.30 | 38.48 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 111.01 | 23.08 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 116.01 | 21.35 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 147.39 | 24.90 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.85 | 37.87 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 190.49 | 73.08 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 225.63 | 81.25 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 206.83 | 96.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 165.19 | 57.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 98.01 | 21.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 230.47 | 96.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.30 | 162.30 | 35.00 | 230.47 | 83.51 | 0.00 | 0.00 | 0.00 |
February | 189.24 | 150.88 | 38.37 | 219.65 | 86.84 | 0.00 | 0.00 | 0.00 |
March | 139.53 | 91.80 | 47.73 | 164.34 | 68.45 | 0.00 | 0.00 | 0.00 |
April | 90.37 | 36.34 | 54.03 | 98.01 | 61.41 | 0.00 | 0.00 | 0.00 |
May | 82.81 | 15.18 | 67.63 | 98.30 | 38.48 | 0.00 | 0.00 | 0.00 |
June | 76.35 | 13.95 | 62.39 | 111.01 | 23.08 | 0.00 | 0.00 | 0.00 |
July | 79.48 | 14.23 | 65.25 | 116.01 | 21.35 | 0.00 | 0.00 | 0.00 |
August | 101.19 | 42.30 | 58.89 | 147.39 | 24.90 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 72.65 | 57.55 | 177.85 | 37.87 | 0.00 | 0.00 | 0.00 |
October | 155.67 | 110.45 | 45.22 | 190.49 | 73.08 | 0.00 | 0.00 | 0.00 |
November | 189.67 | 151.19 | 38.47 | 225.63 | 81.25 | 0.00 | 0.00 | 0.00 |
December | 181.37 | 146.80 | 34.57 | 206.83 | 96.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.12 | 83.63 | 50.49 | 165.19 | 57.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 13.95 | 34.57 | 98.01 | 21.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 162.30 | 67.63 | 230.47 | 96.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 235.88 | 194.04 | 41.84 | 276.03 | 98.62 | 0.00 | 0.00 | 0.00 |
February | 226.26 | 180.39 | 45.87 | 263.29 | 102.35 | 0.00 | 0.00 | 0.00 |
March | 166.81 | 109.75 | 57.06 | 196.95 | 80.70 | 0.00 | 0.00 | 0.00 |
April | 108.04 | 43.44 | 64.60 | 117.60 | 72.34 | 0.00 | 0.00 | 0.00 |
May | 99.01 | 18.15 | 80.86 | 117.75 | 45.46 | 0.00 | 0.00 | 0.00 |
June | 91.28 | 16.68 | 74.60 | 132.54 | 27.43 | 0.00 | 0.00 | 0.00 |
July | 95.02 | 17.02 | 78.01 | 138.51 | 25.36 | 0.00 | 0.00 | 0.00 |
August | 120.98 | 50.58 | 70.41 | 176.07 | 29.58 | 0.00 | 0.00 | 0.00 |
September | 155.66 | 86.86 | 68.80 | 212.64 | 44.91 | 0.00 | 0.00 | 0.00 |
October | 186.12 | 132.06 | 54.06 | 227.98 | 86.28 | 0.00 | 0.00 | 0.00 |
November | 226.76 | 180.76 | 46.00 | 270.22 | 95.89 | 0.00 | 0.00 | 0.00 |
December | 216.84 | 175.51 | 41.33 | 247.94 | 113.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.35 | 99.98 | 60.37 | 197.75 | 68.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.28 | 16.68 | 41.33 | 117.60 | 25.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.88 | 194.04 | 80.86 | 276.03 | 113.57 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.611253E+09 | 0.245407E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.526825E+09 | 0.230103E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.434897E+09 | 0.204973E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.249002E+09 | 0.181933E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.255458E+09 | 0.118361E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.286789E+09 | 63430841.42 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.310644E+09 | 59551467.52 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.394590E+09 | 69184806.95 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.460586E+09 | 0.101885E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.506656E+09 | 0.210987E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.580174E+09 | 0.227898E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.549393E+09 | 0.279680E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.516627E+10 | 0.199340E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.249002E+09 | 59551467.52 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.611253E+09 | 0.279680E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.611253E+09 | 0.245407E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.526825E+09 | 0.230103E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.434897E+09 | 0.204973E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.249002E+09 | 0.181933E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.255458E+09 | 0.118361E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.286789E+09 | 63430841.42 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.310644E+09 | 59551467.52 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.394590E+09 | 69184806.95 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.460586E+09 | 0.101885E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.506656E+09 | 0.210987E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.580174E+09 | 0.227898E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.549393E+09 | 0.279680E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.516627E+10 | 0.199340E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.249002E+09 | 59551467.52 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.611253E+09 | 0.279680E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.611253E+09 | 0.245407E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.526825E+09 | 0.230103E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.434897E+09 | 0.204973E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.249002E+09 | 0.181933E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.255458E+09 | 0.118361E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.286789E+09 | 63430841.42 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.310644E+09 | 59551467.52 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.394590E+09 | 69184806.95 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.460586E+09 | 0.101885E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.506656E+09 | 0.210987E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.580174E+09 | 0.227898E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.549393E+09 | 0.279680E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.516627E+10 | 0.199340E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.249002E+09 | 59551467.52 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.611253E+09 | 0.279680E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.611253E+09 | 0.245407E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.526825E+09 | 0.230103E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.434897E+09 | 0.204973E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.249002E+09 | 0.181933E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.255458E+09 | 0.118361E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.286789E+09 | 63430841.42 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.310644E+09 | 59551467.52 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.394590E+09 | 69184806.95 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.460586E+09 | 0.101885E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.506656E+09 | 0.210987E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.580174E+09 | 0.227898E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.549393E+09 | 0.279680E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.516627E+10 | 0.199340E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.249002E+09 | 59551467.52 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.611253E+09 | 0.279680E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.635265E+09 | 0.522574E+09 | 0.112691E+09 | 0.735911E+09 | 0.291600E+09 |
February | 0.550369E+09 | 0.438789E+09 | 0.111580E+09 | 0.634755E+09 | 0.272863E+09 |
March | 0.449250E+09 | 0.295581E+09 | 0.153669E+09 | 0.523889E+09 | 0.243156E+09 |
April | 0.281582E+09 | 0.113225E+09 | 0.168357E+09 | 0.300273E+09 | 0.215645E+09 |
May | 0.266640E+09 | 48873215.54 | 0.217767E+09 | 0.307600E+09 | 0.140622E+09 |
June | 0.237903E+09 | 43482009.71 | 0.194421E+09 | 0.344190E+09 | 75805748.81 |
July | 0.255907E+09 | 45825760.71 | 0.210081E+09 | 0.372817E+09 | 71154174.82 |
August | 0.325821E+09 | 0.136206E+09 | 0.189616E+09 | 0.473882E+09 | 82669192.81 |
September | 0.405678E+09 | 0.226366E+09 | 0.179312E+09 | 0.553599E+09 | 0.121525E+09 |
October | 0.501242E+09 | 0.355642E+09 | 0.145599E+09 | 0.609561E+09 | 0.250639E+09 |
November | 0.590994E+09 | 0.471108E+09 | 0.119886E+09 | 0.698476E+09 | 0.270658E+09 |
December | 0.583982E+09 | 0.472667E+09 | 0.111315E+09 | 0.662015E+09 | 0.331582E+09 |
Annual Sum or Average | 0.508463E+10 | 0.317034E+10 | 0.191429E+10 | 0.621697E+10 | 0.236792E+10 |
Minimum of Months | 0.237903E+09 | 43482009.71 | 0.111315E+09 | 0.300273E+09 | 71154174.82 |
Maximum of Months | 0.635265E+09 | 0.522574E+09 | 0.217767E+09 | 0.735911E+09 | 0.331582E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.635265E+09 | 0.522574E+09 | 0.112691E+09 | 0.735911E+09 | 0.291600E+09 |
February | 0.550369E+09 | 0.438789E+09 | 0.111580E+09 | 0.634755E+09 | 0.272863E+09 |
March | 0.449250E+09 | 0.295581E+09 | 0.153669E+09 | 0.523889E+09 | 0.243156E+09 |
April | 0.281582E+09 | 0.113225E+09 | 0.168357E+09 | 0.300273E+09 | 0.215645E+09 |
May | 0.266640E+09 | 48873215.54 | 0.217767E+09 | 0.307600E+09 | 0.140622E+09 |
June | 0.237903E+09 | 43482009.71 | 0.194421E+09 | 0.344190E+09 | 75805748.81 |
July | 0.255907E+09 | 45825760.71 | 0.210081E+09 | 0.372817E+09 | 71154174.82 |
August | 0.325821E+09 | 0.136206E+09 | 0.189616E+09 | 0.473882E+09 | 82669192.81 |
September | 0.405678E+09 | 0.226366E+09 | 0.179312E+09 | 0.553599E+09 | 0.121525E+09 |
October | 0.501242E+09 | 0.355642E+09 | 0.145599E+09 | 0.609561E+09 | 0.250639E+09 |
November | 0.590994E+09 | 0.471108E+09 | 0.119886E+09 | 0.698476E+09 | 0.270658E+09 |
December | 0.583982E+09 | 0.472667E+09 | 0.111315E+09 | 0.662015E+09 | 0.331582E+09 |
Annual Sum or Average | 0.508463E+10 | 0.317034E+10 | 0.191429E+10 | 0.621697E+10 | 0.236792E+10 |
Minimum of Months | 0.237903E+09 | 43482009.71 | 0.111315E+09 | 0.300273E+09 | 71154174.82 |
Maximum of Months | 0.635265E+09 | 0.522574E+09 | 0.217767E+09 | 0.735911E+09 | 0.331582E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.605815E+09 | 0.259308E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.521814E+09 | 0.242323E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.430422E+09 | 0.217331E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.244960E+09 | 0.194829E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.251814E+09 | 0.124321E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.286236E+09 | 64361245.84 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.310089E+09 | 60517532.51 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.394090E+09 | 69955877.57 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.459611E+09 | 0.103568E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.503746E+09 | 0.219482E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.575551E+09 | 0.239876E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.544580E+09 | 0.293136E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.512873E+10 | 0.208901E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.244960E+09 | 60517532.51 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.605815E+09 | 0.293136E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.605815E+09 | 0.259308E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.521814E+09 | 0.242323E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.430422E+09 | 0.217331E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.244960E+09 | 0.194829E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.251814E+09 | 0.124321E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.286236E+09 | 64361245.84 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.310089E+09 | 60517532.51 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.394090E+09 | 69955877.57 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.459611E+09 | 0.103568E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.503746E+09 | 0.219482E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.575551E+09 | 0.239876E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.544580E+09 | 0.293136E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.512873E+10 | 0.208901E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.244960E+09 | 60517532.51 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.605815E+09 | 0.293136E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.635265E+09 | 0.522574E+09 | 0.112691E+09 | 0.729534E+09 | 0.307917E+09 |
February | 0.550369E+09 | 0.438789E+09 | 0.111580E+09 | 0.628918E+09 | 0.287171E+09 |
March | 0.449250E+09 | 0.295581E+09 | 0.153669E+09 | 0.518657E+09 | 0.257655E+09 |
April | 0.281582E+09 | 0.113225E+09 | 0.168357E+09 | 0.295506E+09 | 0.230754E+09 |
May | 0.266640E+09 | 48873215.54 | 0.217767E+09 | 0.303296E+09 | 0.147594E+09 |
June | 0.237903E+09 | 43482009.71 | 0.194421E+09 | 0.343549E+09 | 76899870.48 |
July | 0.255907E+09 | 45825760.71 | 0.210081E+09 | 0.372174E+09 | 72291233.37 |
August | 0.325821E+09 | 0.136206E+09 | 0.189616E+09 | 0.473341E+09 | 83570994.52 |
September | 0.405678E+09 | 0.226366E+09 | 0.179312E+09 | 0.552515E+09 | 0.123482E+09 |
October | 0.501242E+09 | 0.355642E+09 | 0.145599E+09 | 0.606195E+09 | 0.260575E+09 |
November | 0.590994E+09 | 0.471108E+09 | 0.119886E+09 | 0.693103E+09 | 0.284687E+09 |
December | 0.583982E+09 | 0.472667E+09 | 0.111315E+09 | 0.656412E+09 | 0.347301E+09 |
Annual Sum or Average | 0.508463E+10 | 0.317034E+10 | 0.191429E+10 | 0.617320E+10 | 0.247990E+10 |
Minimum of Months | 0.237903E+09 | 43482009.71 | 0.111315E+09 | 0.295506E+09 | 72291233.37 |
Maximum of Months | 0.635265E+09 | 0.522574E+09 | 0.217767E+09 | 0.729534E+09 | 0.347301E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.607043E+09 | 0.253428E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.522850E+09 | 0.236756E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.431246E+09 | 0.212941E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.245854E+09 | 0.189896E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.252131E+09 | 0.124750E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.285215E+09 | 68980247.56 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.308631E+09 | 65655048.83 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.393474E+09 | 75092366.91 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.459108E+09 | 0.107886E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.504186E+09 | 0.218261E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.576787E+09 | 0.235386E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.545622E+09 | 0.286738E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.513215E+10 | 0.207577E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.245854E+09 | 65655048.83 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.607043E+09 | 0.286738E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.607043E+09 | 0.253428E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.522850E+09 | 0.236756E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.431246E+09 | 0.212941E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.245854E+09 | 0.189896E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.252131E+09 | 0.124750E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.285215E+09 | 68980247.56 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.308631E+09 | 65655048.83 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.393474E+09 | 75092366.91 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.459108E+09 | 0.107886E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.504186E+09 | 0.218261E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.576787E+09 | 0.235386E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.545622E+09 | 0.286738E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.513215E+10 | 0.207577E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.245854E+09 | 65655048.83 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.607043E+09 | 0.286738E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.631794E+09 | 0.519719E+09 | 0.112075E+09 | 0.727020E+09 | 0.299338E+09 |
February | 0.547362E+09 | 0.436391E+09 | 0.110970E+09 | 0.626720E+09 | 0.279086E+09 |
March | 0.446795E+09 | 0.293966E+09 | 0.152829E+09 | 0.516809E+09 | 0.251101E+09 |
April | 0.280043E+09 | 0.112606E+09 | 0.167437E+09 | 0.294960E+09 | 0.223711E+09 |
May | 0.265183E+09 | 48606148.79 | 0.216577E+09 | 0.302022E+09 | 0.147261E+09 |
June | 0.236603E+09 | 43244403.10 | 0.193359E+09 | 0.340475E+09 | 81855659.34 |
July | 0.254508E+09 | 45575346.72 | 0.208933E+09 | 0.368435E+09 | 77875686.09 |
August | 0.324041E+09 | 0.135461E+09 | 0.188580E+09 | 0.470023E+09 | 89091791.75 |
September | 0.403461E+09 | 0.225129E+09 | 0.178332E+09 | 0.548907E+09 | 0.127829E+09 |
October | 0.498503E+09 | 0.353699E+09 | 0.144804E+09 | 0.603405E+09 | 0.257683E+09 |
November | 0.587764E+09 | 0.468533E+09 | 0.119231E+09 | 0.690785E+09 | 0.277853E+09 |
December | 0.580791E+09 | 0.470084E+09 | 0.110707E+09 | 0.654074E+09 | 0.337921E+09 |
Annual Sum or Average | 0.505685E+10 | 0.315302E+10 | 0.190383E+10 | 0.614363E+10 | 0.245061E+10 |
Minimum of Months | 0.236603E+09 | 43244403.10 | 0.110707E+09 | 0.294960E+09 | 77875686.09 |
Maximum of Months | 0.631794E+09 | 0.519719E+09 | 0.216577E+09 | 0.727020E+09 | 0.337921E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.607852E+09 | 0.250584E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.523537E+09 | 0.234275E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.431873E+09 | 0.210589E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.246513E+09 | 0.187270E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.252661E+09 | 0.123490E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.285196E+09 | 69093032.18 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.308556E+09 | 65896834.15 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.393451E+09 | 75252418.67 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.459145E+09 | 0.107815E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.504549E+09 | 0.216601E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.577553E+09 | 0.232906E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.546303E+09 | 0.283912E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.513719E+10 | 0.205768E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.246513E+09 | 65896834.15 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.607852E+09 | 0.283912E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.607852E+09 | 0.250584E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.523537E+09 | 0.234275E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.431873E+09 | 0.210589E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.246513E+09 | 0.187270E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.252661E+09 | 0.123490E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.285196E+09 | 69093032.18 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.308556E+09 | 65896834.15 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.393451E+09 | 75252418.67 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.459145E+09 | 0.107815E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.504549E+09 | 0.216601E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.577553E+09 | 0.232906E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.546303E+09 | 0.283912E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.513719E+10 | 0.205768E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.246513E+09 | 65896834.15 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.607852E+09 | 0.283912E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.631794E+09 | 0.519719E+09 | 0.112075E+09 | 0.727993E+09 | 0.295978E+09 |
February | 0.547362E+09 | 0.436391E+09 | 0.110970E+09 | 0.627542E+09 | 0.276157E+09 |
March | 0.446795E+09 | 0.293966E+09 | 0.152829E+09 | 0.517561E+09 | 0.248323E+09 |
April | 0.280043E+09 | 0.112606E+09 | 0.167437E+09 | 0.295749E+09 | 0.220611E+09 |
May | 0.265183E+09 | 48606148.79 | 0.216577E+09 | 0.302656E+09 | 0.145776E+09 |
June | 0.236603E+09 | 43244403.10 | 0.193359E+09 | 0.340452E+09 | 81988655.42 |
July | 0.254508E+09 | 45575346.72 | 0.208933E+09 | 0.368345E+09 | 78160251.50 |
August | 0.324041E+09 | 0.135461E+09 | 0.188580E+09 | 0.469995E+09 | 89280649.37 |
September | 0.403461E+09 | 0.225129E+09 | 0.178332E+09 | 0.548951E+09 | 0.127745E+09 |
October | 0.498503E+09 | 0.353699E+09 | 0.144804E+09 | 0.603841E+09 | 0.255720E+09 |
November | 0.587764E+09 | 0.468533E+09 | 0.119231E+09 | 0.691699E+09 | 0.274919E+09 |
December | 0.580791E+09 | 0.470084E+09 | 0.110707E+09 | 0.654888E+09 | 0.334584E+09 |
Annual Sum or Average | 0.505685E+10 | 0.315302E+10 | 0.190383E+10 | 0.614967E+10 | 0.242924E+10 |
Minimum of Months | 0.236603E+09 | 43244403.10 | 0.110707E+09 | 0.295749E+09 | 78160251.50 |
Maximum of Months | 0.631794E+09 | 0.519719E+09 | 0.216577E+09 | 0.727993E+09 | 0.334584E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.608818E+09 | 0.248053E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.524316E+09 | 0.232170E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.432745E+09 | 0.208242E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.247446E+09 | 0.184617E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.253669E+09 | 0.121672E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.285598E+09 | 68209564.34 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.308931E+09 | 65050619.81 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.393781E+09 | 74360052.07 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.459501E+09 | 0.106823E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.505192E+09 | 0.214636E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.578477E+09 | 0.230582E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.547138E+09 | 0.281417E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.514561E+10 | 0.203583E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.247446E+09 | 65050619.81 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.608818E+09 | 0.281417E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.608818E+09 | 0.248053E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.524316E+09 | 0.232170E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.432745E+09 | 0.208242E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.247446E+09 | 0.184617E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.253669E+09 | 0.121672E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.285598E+09 | 68209564.34 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.308931E+09 | 65050619.81 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.393781E+09 | 74360052.07 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.459501E+09 | 0.106823E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.505192E+09 | 0.214636E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.578477E+09 | 0.230582E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.547138E+09 | 0.281417E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.514561E+10 | 0.203583E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.247446E+09 | 65050619.81 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.608818E+09 | 0.281417E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.631794E+09 | 0.519719E+09 | 0.112075E+09 | 0.729150E+09 | 0.292988E+09 |
February | 0.547362E+09 | 0.436391E+09 | 0.110970E+09 | 0.628475E+09 | 0.273671E+09 |
March | 0.446795E+09 | 0.293966E+09 | 0.152829E+09 | 0.518605E+09 | 0.245554E+09 |
April | 0.280043E+09 | 0.112606E+09 | 0.167437E+09 | 0.296865E+09 | 0.217482E+09 |
May | 0.265183E+09 | 48606148.79 | 0.216577E+09 | 0.303863E+09 | 0.143640E+09 |
June | 0.236603E+09 | 43244403.10 | 0.193359E+09 | 0.340936E+09 | 80953387.43 |
July | 0.254508E+09 | 45575346.72 | 0.208933E+09 | 0.368797E+09 | 77169922.53 |
August | 0.324041E+09 | 0.135461E+09 | 0.188580E+09 | 0.470394E+09 | 88233582.61 |
September | 0.403461E+09 | 0.225129E+09 | 0.178332E+09 | 0.549379E+09 | 0.126581E+09 |
October | 0.498503E+09 | 0.353699E+09 | 0.144804E+09 | 0.604610E+09 | 0.253402E+09 |
November | 0.587764E+09 | 0.468533E+09 | 0.119231E+09 | 0.692800E+09 | 0.272173E+09 |
December | 0.580791E+09 | 0.470084E+09 | 0.110707E+09 | 0.655887E+09 | 0.331640E+09 |
Annual Sum or Average | 0.505685E+10 | 0.315302E+10 | 0.190383E+10 | 0.615976E+10 | 0.240349E+10 |
Minimum of Months | 0.236603E+09 | 43244403.10 | 0.110707E+09 | 0.296865E+09 | 77169922.53 |
Maximum of Months | 0.631794E+09 | 0.519719E+09 | 0.216577E+09 | 0.729150E+09 | 0.331640E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.612063E+09 | 0.241611E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.527271E+09 | 0.226093E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.435548E+09 | 0.201690E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.250020E+09 | 0.177640E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.256092E+09 | 0.116869E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.285953E+09 | 65177639.43 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.309156E+09 | 62153805.41 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.394044E+09 | 71309317.35 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.460108E+09 | 0.103747E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.506878E+09 | 0.209419E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.581126E+09 | 0.224754E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.550461E+09 | 0.274181E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.516872E+10 | 0.197465E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.250020E+09 | 62153805.41 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.612063E+09 | 0.274181E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.612063E+09 | 0.241611E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.527271E+09 | 0.226093E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.435548E+09 | 0.201690E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.250020E+09 | 0.177640E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.256092E+09 | 0.116869E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.285953E+09 | 65177639.43 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.309156E+09 | 62153805.41 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.394044E+09 | 71309317.35 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.460108E+09 | 0.103747E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.506878E+09 | 0.209419E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.581126E+09 | 0.224754E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.550461E+09 | 0.274181E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.516872E+10 | 0.197465E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.250020E+09 | 62153805.41 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.612063E+09 | 0.274181E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.612063E+09 | 0.241611E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.527271E+09 | 0.226093E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.435548E+09 | 0.201690E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.250020E+09 | 0.177640E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.256092E+09 | 0.116869E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.285953E+09 | 65177639.43 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.309156E+09 | 62153805.41 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.394044E+09 | 71309317.35 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.460108E+09 | 0.103747E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.506878E+09 | 0.209419E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.581126E+09 | 0.224754E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.550461E+09 | 0.274181E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.516872E+10 | 0.197465E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.250020E+09 | 62153805.41 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.612063E+09 | 0.274181E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.612063E+09 | 0.241611E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.527271E+09 | 0.226093E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.435548E+09 | 0.201690E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.250020E+09 | 0.177640E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.256092E+09 | 0.116869E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.285953E+09 | 65177639.43 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.309156E+09 | 62153805.41 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.394044E+09 | 71309317.35 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.460108E+09 | 0.103747E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.506878E+09 | 0.209419E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.581126E+09 | 0.224754E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.550461E+09 | 0.274181E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.516872E+10 | 0.197465E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.250020E+09 | 62153805.41 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.612063E+09 | 0.274181E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.631794E+09 | 0.519719E+09 | 0.112075E+09 | 0.732873E+09 | 0.285492E+09 |
February | 0.547362E+09 | 0.436391E+09 | 0.110970E+09 | 0.631832E+09 | 0.266638E+09 |
March | 0.446795E+09 | 0.293966E+09 | 0.152829E+09 | 0.521816E+09 | 0.237939E+09 |
April | 0.280043E+09 | 0.112606E+09 | 0.167437E+09 | 0.299862E+09 | 0.209381E+09 |
May | 0.265183E+09 | 48606148.79 | 0.216577E+09 | 0.306699E+09 | 0.138053E+09 |
June | 0.236603E+09 | 43244403.10 | 0.193359E+09 | 0.341364E+09 | 77398378.31 |
July | 0.254508E+09 | 45575346.72 | 0.208933E+09 | 0.369067E+09 | 73776677.18 |
August | 0.324041E+09 | 0.135461E+09 | 0.188580E+09 | 0.470678E+09 | 84656099.99 |
September | 0.403461E+09 | 0.225129E+09 | 0.178332E+09 | 0.550042E+09 | 0.122990E+09 |
October | 0.498503E+09 | 0.353699E+09 | 0.144804E+09 | 0.606516E+09 | 0.247353E+09 |
November | 0.587764E+09 | 0.468533E+09 | 0.119231E+09 | 0.695814E+09 | 0.265413E+09 |
December | 0.580791E+09 | 0.470084E+09 | 0.110707E+09 | 0.659680E+09 | 0.323275E+09 |
Annual Sum or Average | 0.505685E+10 | 0.315302E+10 | 0.190383E+10 | 0.618624E+10 | 0.233237E+10 |
Minimum of Months | 0.236603E+09 | 43244403.10 | 0.110707E+09 | 0.299862E+09 | 73776677.18 |
Maximum of Months | 0.631794E+09 | 0.519719E+09 | 0.216577E+09 | 0.732873E+09 | 0.323275E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.631794E+09 | 0.519719E+09 | 0.112075E+09 | 0.732873E+09 | 0.285492E+09 |
February | 0.547362E+09 | 0.436391E+09 | 0.110970E+09 | 0.631832E+09 | 0.266638E+09 |
March | 0.446795E+09 | 0.293966E+09 | 0.152829E+09 | 0.521816E+09 | 0.237939E+09 |
April | 0.280043E+09 | 0.112606E+09 | 0.167437E+09 | 0.299862E+09 | 0.209381E+09 |
May | 0.265183E+09 | 48606148.79 | 0.216577E+09 | 0.306699E+09 | 0.138053E+09 |
June | 0.236603E+09 | 43244403.10 | 0.193359E+09 | 0.341364E+09 | 77398378.31 |
July | 0.254508E+09 | 45575346.72 | 0.208933E+09 | 0.369067E+09 | 73776677.18 |
August | 0.324041E+09 | 0.135461E+09 | 0.188580E+09 | 0.470678E+09 | 84656099.99 |
September | 0.403461E+09 | 0.225129E+09 | 0.178332E+09 | 0.550042E+09 | 0.122990E+09 |
October | 0.498503E+09 | 0.353699E+09 | 0.144804E+09 | 0.606516E+09 | 0.247353E+09 |
November | 0.587764E+09 | 0.468533E+09 | 0.119231E+09 | 0.695814E+09 | 0.265413E+09 |
December | 0.580791E+09 | 0.470084E+09 | 0.110707E+09 | 0.659680E+09 | 0.323275E+09 |
Annual Sum or Average | 0.505685E+10 | 0.315302E+10 | 0.190383E+10 | 0.618624E+10 | 0.233237E+10 |
Minimum of Months | 0.236603E+09 | 43244403.10 | 0.110707E+09 | 0.299862E+09 | 73776677.18 |
Maximum of Months | 0.631794E+09 | 0.519719E+09 | 0.216577E+09 | 0.732873E+09 | 0.323275E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.611240E+09 | 0.241836E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.526291E+09 | 0.226840E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.434876E+09 | 0.202014E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.249614E+09 | 0.177761E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.256128E+09 | 0.116485E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.286314E+09 | 64470352.99 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.309535E+09 | 61435413.43 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.394168E+09 | 70510646.19 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.459955E+09 | 0.103094E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.506437E+09 | 0.209450E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.580375E+09 | 0.224952E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.549361E+09 | 0.275180E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.516429E+10 | 0.197403E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.249614E+09 | 61435413.43 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.611240E+09 | 0.275180E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.611240E+09 | 0.241836E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.526291E+09 | 0.226840E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.434876E+09 | 0.202014E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.249614E+09 | 0.177761E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.256128E+09 | 0.116485E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.286314E+09 | 64470352.99 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.309535E+09 | 61435413.43 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.394168E+09 | 70510646.19 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.459955E+09 | 0.103094E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.506437E+09 | 0.209450E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.580375E+09 | 0.224952E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.549361E+09 | 0.275180E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.516429E+10 | 0.197403E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.249614E+09 | 61435413.43 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.611240E+09 | 0.275180E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.631794E+09 | 0.519719E+09 | 0.112075E+09 | 0.732058E+09 | 0.285628E+09 |
February | 0.547362E+09 | 0.436391E+09 | 0.110970E+09 | 0.630842E+09 | 0.267373E+09 |
March | 0.446795E+09 | 0.293966E+09 | 0.152829E+09 | 0.521165E+09 | 0.238195E+09 |
April | 0.280043E+09 | 0.112606E+09 | 0.167437E+09 | 0.299479E+09 | 0.209400E+09 |
May | 0.265183E+09 | 48606148.79 | 0.216577E+09 | 0.306826E+09 | 0.137538E+09 |
June | 0.236603E+09 | 43244403.10 | 0.193359E+09 | 0.341825E+09 | 76555580.03 |
July | 0.254508E+09 | 45575346.72 | 0.208933E+09 | 0.369555E+09 | 72920408.42 |
August | 0.324041E+09 | 0.135461E+09 | 0.188580E+09 | 0.470898E+09 | 83702827.43 |
September | 0.403461E+09 | 0.225129E+09 | 0.178332E+09 | 0.549957E+09 | 0.122192E+09 |
October | 0.498503E+09 | 0.353699E+09 | 0.144804E+09 | 0.606118E+09 | 0.247266E+09 |
November | 0.587764E+09 | 0.468533E+09 | 0.119231E+09 | 0.695084E+09 | 0.265510E+09 |
December | 0.580791E+09 | 0.470084E+09 | 0.110707E+09 | 0.658549E+09 | 0.324272E+09 |
Annual Sum or Average | 0.505685E+10 | 0.315302E+10 | 0.190383E+10 | 0.618235E+10 | 0.233055E+10 |
Minimum of Months | 0.236603E+09 | 43244403.10 | 0.110707E+09 | 0.299479E+09 | 72920408.42 |
Maximum of Months | 0.631794E+09 | 0.519719E+09 | 0.216577E+09 | 0.732058E+09 | 0.324272E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.611719E+09 | 0.240723E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.526655E+09 | 0.225994E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.435333E+09 | 0.200956E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.250050E+09 | 0.176573E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.256851E+09 | 0.115456E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.286561E+09 | 64123358.93 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.309762E+09 | 61114338.23 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.394362E+09 | 70185209.79 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.460164E+09 | 0.102687E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.506833E+09 | 0.208499E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.580784E+09 | 0.223990E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.549704E+09 | 0.274264E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.516878E+10 | 0.196457E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.250050E+09 | 61114338.23 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.611719E+09 | 0.274264E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.611719E+09 | 0.240723E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.526655E+09 | 0.225994E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.435333E+09 | 0.200956E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.250050E+09 | 0.176573E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.256851E+09 | 0.115456E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.286561E+09 | 64123358.93 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.309762E+09 | 61114338.23 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.394362E+09 | 70185209.79 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.460164E+09 | 0.102687E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.506833E+09 | 0.208499E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.580784E+09 | 0.223990E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.549704E+09 | 0.274264E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.516878E+10 | 0.196457E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.250050E+09 | 61114338.23 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.611719E+09 | 0.274264E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.631794E+09 | 0.519719E+09 | 0.112075E+09 | 0.732630E+09 | 0.284310E+09 |
February | 0.547362E+09 | 0.436391E+09 | 0.110970E+09 | 0.631278E+09 | 0.266374E+09 |
March | 0.446795E+09 | 0.293966E+09 | 0.152829E+09 | 0.521711E+09 | 0.236945E+09 |
April | 0.280043E+09 | 0.112606E+09 | 0.167437E+09 | 0.300003E+09 | 0.208001E+09 |
May | 0.265183E+09 | 48606148.79 | 0.216577E+09 | 0.307689E+09 | 0.136326E+09 |
June | 0.236603E+09 | 43244403.10 | 0.193359E+09 | 0.342122E+09 | 76146216.26 |
July | 0.254508E+09 | 45575346.72 | 0.208933E+09 | 0.369828E+09 | 72542180.10 |
August | 0.324041E+09 | 0.135461E+09 | 0.188580E+09 | 0.471131E+09 | 83319600.27 |
September | 0.403461E+09 | 0.225129E+09 | 0.178332E+09 | 0.550207E+09 | 0.121713E+09 |
October | 0.498503E+09 | 0.353699E+09 | 0.144804E+09 | 0.606591E+09 | 0.246142E+09 |
November | 0.587764E+09 | 0.468533E+09 | 0.119231E+09 | 0.695574E+09 | 0.264373E+09 |
December | 0.580791E+09 | 0.470084E+09 | 0.110707E+09 | 0.658959E+09 | 0.323188E+09 |
Annual Sum or Average | 0.505685E+10 | 0.315302E+10 | 0.190383E+10 | 0.618772E+10 | 0.231938E+10 |
Minimum of Months | 0.236603E+09 | 43244403.10 | 0.110707E+09 | 0.300003E+09 | 72542180.10 |
Maximum of Months | 0.631794E+09 | 0.519719E+09 | 0.216577E+09 | 0.732630E+09 | 0.323188E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.613076E+09 | 0.237150E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.527776E+09 | 0.222851E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.436625E+09 | 0.197350E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.251201E+09 | 0.172831E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.258740E+09 | 0.112536E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.287033E+09 | 63269090.47 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.310160E+09 | 60358737.25 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.394658E+09 | 69484467.66 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.460550E+09 | 0.101739E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.507850E+09 | 0.205722E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.581875E+09 | 0.221123E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.550745E+09 | 0.271007E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.518029E+10 | 0.193542E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.251201E+09 | 60358737.25 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.613076E+09 | 0.271007E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.613076E+09 | 0.237150E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.527776E+09 | 0.222851E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.436625E+09 | 0.197350E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.251201E+09 | 0.172831E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.258740E+09 | 0.112536E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.287033E+09 | 63269090.47 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.310160E+09 | 60358737.25 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.394658E+09 | 69484467.66 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.460550E+09 | 0.101739E+09 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.507850E+09 | 0.205722E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.581875E+09 | 0.221123E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.550745E+09 | 0.271007E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.518029E+10 | 0.193542E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.251201E+09 | 60358737.25 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.613076E+09 | 0.271007E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.631794E+09 | 0.519719E+09 | 0.112075E+09 | 0.734257E+09 | 0.280083E+09 |
February | 0.547362E+09 | 0.436391E+09 | 0.110970E+09 | 0.632619E+09 | 0.262661E+09 |
March | 0.446795E+09 | 0.293966E+09 | 0.152829E+09 | 0.523256E+09 | 0.232687E+09 |
April | 0.280043E+09 | 0.112606E+09 | 0.167437E+09 | 0.301386E+09 | 0.203592E+09 |
May | 0.265183E+09 | 48606148.79 | 0.216577E+09 | 0.309944E+09 | 0.132894E+09 |
June | 0.236603E+09 | 43244403.10 | 0.193359E+09 | 0.342687E+09 | 75144637.38 |
July | 0.254508E+09 | 45575346.72 | 0.208933E+09 | 0.370302E+09 | 71656592.23 |
August | 0.324041E+09 | 0.135461E+09 | 0.188580E+09 | 0.471486E+09 | 82499547.73 |
September | 0.403461E+09 | 0.225129E+09 | 0.178332E+09 | 0.550670E+09 | 0.120601E+09 |
October | 0.498503E+09 | 0.353699E+09 | 0.144804E+09 | 0.607805E+09 | 0.242865E+09 |
November | 0.587764E+09 | 0.468533E+09 | 0.119231E+09 | 0.696877E+09 | 0.260985E+09 |
December | 0.580791E+09 | 0.470084E+09 | 0.110707E+09 | 0.660207E+09 | 0.319346E+09 |
Annual Sum or Average | 0.505685E+10 | 0.315302E+10 | 0.190383E+10 | 0.620150E+10 | 0.228502E+10 |
Minimum of Months | 0.236603E+09 | 43244403.10 | 0.110707E+09 | 0.301386E+09 | 71656592.23 |
Maximum of Months | 0.631794E+09 | 0.519719E+09 | 0.216577E+09 | 0.734257E+09 | 0.319346E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.617284E+09 | 0.223671E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.531378E+09 | 0.210094E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.440168E+09 | 0.183334E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.254047E+09 | 0.159181E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.263293E+09 | 0.103059E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.287746E+09 | 59816476.90 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.310728E+09 | 57174863.14 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.394759E+09 | 66688846.29 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.460976E+09 | 98167951.62 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.510209E+09 | 0.195751E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.584826E+09 | 0.210594E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.553979E+09 | 0.258152E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.520939E+10 | 0.182569E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.254047E+09 | 57174863.14 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.617284E+09 | 0.258152E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528439E+09 | 0.434698E+09 | 93740998.23 | 0.617284E+09 | 0.223671E+09 |
February | 0.457819E+09 | 0.365002E+09 | 92816803.77 | 0.531378E+09 | 0.210094E+09 |
March | 0.373705E+09 | 0.245876E+09 | 0.127828E+09 | 0.440168E+09 | 0.183334E+09 |
April | 0.234231E+09 | 94185238.87 | 0.140046E+09 | 0.254047E+09 | 0.159181E+09 |
May | 0.221802E+09 | 40654706.08 | 0.181147E+09 | 0.263293E+09 | 0.103059E+09 |
June | 0.197897E+09 | 36170084.27 | 0.161727E+09 | 0.287746E+09 | 59816476.90 |
July | 0.212873E+09 | 38119710.61 | 0.174754E+09 | 0.310728E+09 | 57174863.14 |
August | 0.271031E+09 | 0.113301E+09 | 0.157730E+09 | 0.394759E+09 | 66688846.29 |
September | 0.337459E+09 | 0.188301E+09 | 0.149159E+09 | 0.460976E+09 | 98167951.62 |
October | 0.416953E+09 | 0.295838E+09 | 0.121115E+09 | 0.510209E+09 | 0.195751E+09 |
November | 0.491612E+09 | 0.391886E+09 | 99725935.70 | 0.584826E+09 | 0.210594E+09 |
December | 0.485780E+09 | 0.393184E+09 | 92596250.66 | 0.553979E+09 | 0.258152E+09 |
Annual Sum or Average | 0.422960E+10 | 0.263722E+10 | 0.159239E+10 | 0.520939E+10 | 0.182569E+10 |
Minimum of Months | 0.197897E+09 | 36170084.27 | 92596250.66 | 0.254047E+09 | 57174863.14 |
Maximum of Months | 0.528439E+09 | 0.434698E+09 | 0.181147E+09 | 0.617284E+09 | 0.258152E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.631794E+09 | 0.519719E+09 | 0.112075E+09 | 0.739310E+09 | 0.264147E+09 |
February | 0.547362E+09 | 0.436391E+09 | 0.110970E+09 | 0.636947E+09 | 0.247599E+09 |
March | 0.446795E+09 | 0.293966E+09 | 0.152829E+09 | 0.527509E+09 | 0.216156E+09 |
April | 0.280043E+09 | 0.112606E+09 | 0.167437E+09 | 0.304819E+09 | 0.187516E+09 |
May | 0.265183E+09 | 48606148.79 | 0.216577E+09 | 0.315383E+09 | 0.121771E+09 |
June | 0.236603E+09 | 43244403.10 | 0.193359E+09 | 0.343532E+09 | 71095371.22 |
July | 0.254508E+09 | 45575346.72 | 0.208933E+09 | 0.370974E+09 | 67921641.67 |
August | 0.324041E+09 | 0.135461E+09 | 0.188580E+09 | 0.471597E+09 | 79218476.44 |
September | 0.403461E+09 | 0.225129E+09 | 0.178332E+09 | 0.551173E+09 | 0.116417E+09 |
October | 0.498503E+09 | 0.353699E+09 | 0.144804E+09 | 0.610620E+09 | 0.231103E+09 |
November | 0.587764E+09 | 0.468533E+09 | 0.119231E+09 | 0.700407E+09 | 0.248550E+09 |
December | 0.580791E+09 | 0.470084E+09 | 0.110707E+09 | 0.664095E+09 | 0.304181E+09 |
Annual Sum or Average | 0.505685E+10 | 0.315302E+10 | 0.190383E+10 | 0.623637E+10 | 0.215567E+10 |
Minimum of Months | 0.236603E+09 | 43244403.10 | 0.110707E+09 | 0.304819E+09 | 67921641.67 |
Maximum of Months | 0.631794E+09 | 0.519719E+09 | 0.216577E+09 | 0.739310E+09 | 0.304181E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1462.38 | 584.24 | 1263.55 | 1039.40 | 224.14 | 0.00 | 0.00 |
February | 1395.84 | 606.04 | 1211.98 | 966.26 | 245.71 | 0.00 | 0.00 |
March | 1040.68 | 487.68 | 893.56 | 587.91 | 305.65 | 0.00 | 0.00 |
April | 615.95 | 447.15 | 578.74 | 232.71 | 346.03 | 0.00 | 0.00 |
May | 611.20 | 281.77 | 530.35 | 97.21 | 433.14 | 0.00 | 0.00 |
June | 708.15 | 156.38 | 488.96 | 89.37 | 399.60 | 0.00 | 0.00 |
July | 742.31 | 142.07 | 509.00 | 91.15 | 417.85 | 0.00 | 0.00 |
August | 943.15 | 165.05 | 648.06 | 270.91 | 377.15 | 0.00 | 0.00 |
September | 1137.94 | 251.00 | 833.79 | 465.25 | 368.54 | 0.00 | 0.00 |
October | 1211.82 | 502.25 | 996.97 | 707.38 | 289.60 | 0.00 | 0.00 |
November | 1434.28 | 560.54 | 1214.67 | 968.27 | 246.40 | 0.00 | 0.00 |
December | 1314.81 | 665.28 | 1161.55 | 940.14 | 221.41 | 0.00 | 0.00 |
Annual Sum or Average | 1049.56 | 403.01 | 858.94 | 535.56 | 323.38 | 0.00 | 0.00 |
Minimum of Months | 611.20 | 142.07 | 488.96 | 89.37 | 221.41 | 0.00 | 0.00 |
Maximum of Months | 1462.38 | 665.28 | 1263.55 | 1039.40 | 433.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 724.75 | 308.59 | 631.77 | 519.70 | 112.07 | 0.00 | 0.00 |
February | 691.36 | 319.04 | 605.99 | 483.13 | 122.86 | 0.00 | 0.00 |
March | 515.05 | 258.48 | 446.78 | 293.96 | 152.82 | 0.00 | 0.00 |
April | 303.02 | 239.36 | 289.37 | 116.36 | 173.01 | 0.00 | 0.00 |
May | 301.27 | 147.94 | 265.17 | 48.60 | 216.57 | 0.00 | 0.00 |
June | 353.40 | 79.33 | 244.48 | 44.68 | 199.80 | 0.00 | 0.00 |
July | 370.50 | 72.18 | 254.50 | 45.57 | 208.93 | 0.00 | 0.00 |
August | 471.00 | 83.44 | 324.03 | 135.46 | 188.57 | 0.00 | 0.00 |
September | 567.80 | 127.55 | 416.90 | 232.63 | 184.27 | 0.00 | 0.00 |
October | 602.48 | 261.18 | 498.49 | 353.69 | 144.80 | 0.00 | 0.00 |
November | 711.50 | 294.92 | 607.34 | 484.14 | 123.20 | 0.00 | 0.00 |
December | 651.72 | 348.56 | 580.77 | 470.07 | 110.70 | 0.00 | 0.00 |
Annual Sum or Average | 521.01 | 211.12 | 429.47 | 267.78 | 161.69 | 0.00 | 0.00 |
Minimum of Months | 301.27 | 72.18 | 244.48 | 44.68 | 110.70 | 0.00 | 0.00 |
Maximum of Months | 724.75 | 348.56 | 631.77 | 519.70 | 216.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 724.73 | 301.00 | 630.48 | 518.64 | 111.84 | 0.00 | 0.00 |
February | 691.31 | 311.09 | 604.75 | 482.14 | 122.60 | 0.00 | 0.00 |
March | 514.97 | 252.76 | 445.86 | 293.35 | 152.51 | 0.00 | 0.00 |
April | 303.50 | 232.83 | 288.78 | 116.12 | 172.66 | 0.00 | 0.00 |
May | 301.03 | 148.13 | 264.63 | 48.50 | 216.13 | 0.00 | 0.00 |
June | 351.43 | 84.81 | 243.98 | 44.59 | 199.39 | 0.00 | 0.00 |
July | 368.02 | 78.10 | 253.98 | 45.48 | 208.50 | 0.00 | 0.00 |
August | 469.30 | 89.34 | 323.37 | 135.18 | 188.19 | 0.00 | 0.00 |
September | 566.02 | 132.56 | 416.04 | 232.15 | 183.89 | 0.00 | 0.00 |
October | 601.77 | 259.19 | 497.46 | 352.96 | 144.50 | 0.00 | 0.00 |
November | 711.56 | 288.82 | 606.09 | 483.14 | 122.95 | 0.00 | 0.00 |
December | 651.63 | 340.28 | 579.58 | 469.11 | 110.48 | 0.00 | 0.00 |
Annual Sum or Average | 520.29 | 209.35 | 428.59 | 267.23 | 161.36 | 0.00 | 0.00 |
Minimum of Months | 301.03 | 78.10 | 243.98 | 44.59 | 110.48 | 0.00 | 0.00 |
Maximum of Months | 724.73 | 340.28 | 630.48 | 518.64 | 216.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 725.69 | 297.62 | 630.48 | 518.64 | 111.84 | 0.00 | 0.00 |
February | 692.22 | 307.83 | 604.75 | 482.14 | 122.60 | 0.00 | 0.00 |
March | 515.72 | 249.96 | 445.86 | 293.35 | 152.51 | 0.00 | 0.00 |
April | 304.31 | 229.61 | 288.78 | 116.12 | 172.66 | 0.00 | 0.00 |
May | 301.66 | 146.64 | 264.63 | 48.50 | 216.13 | 0.00 | 0.00 |
June | 351.41 | 84.94 | 243.98 | 44.59 | 199.39 | 0.00 | 0.00 |
July | 367.93 | 78.39 | 253.98 | 45.48 | 208.50 | 0.00 | 0.00 |
August | 469.27 | 89.53 | 323.37 | 135.18 | 188.19 | 0.00 | 0.00 |
September | 566.07 | 132.47 | 416.04 | 232.15 | 183.89 | 0.00 | 0.00 |
October | 602.20 | 257.21 | 497.46 | 352.96 | 144.50 | 0.00 | 0.00 |
November | 712.50 | 285.78 | 606.09 | 483.14 | 122.95 | 0.00 | 0.00 |
December | 652.44 | 336.92 | 579.58 | 469.11 | 110.48 | 0.00 | 0.00 |
Annual Sum or Average | 520.80 | 207.53 | 428.59 | 267.23 | 161.36 | 0.00 | 0.00 |
Minimum of Months | 301.66 | 78.39 | 243.98 | 44.59 | 110.48 | 0.00 | 0.00 |
Maximum of Months | 725.69 | 336.92 | 630.48 | 518.64 | 216.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 726.85 | 294.61 | 630.48 | 518.64 | 111.84 | 0.00 | 0.00 |
February | 693.25 | 305.06 | 604.75 | 482.14 | 122.60 | 0.00 | 0.00 |
March | 516.76 | 247.18 | 445.86 | 293.35 | 152.51 | 0.00 | 0.00 |
April | 305.46 | 226.36 | 288.78 | 116.12 | 172.66 | 0.00 | 0.00 |
May | 302.87 | 144.48 | 264.63 | 48.50 | 216.13 | 0.00 | 0.00 |
June | 351.90 | 83.86 | 243.98 | 44.59 | 199.39 | 0.00 | 0.00 |
July | 368.38 | 77.39 | 253.98 | 45.48 | 208.50 | 0.00 | 0.00 |
August | 469.67 | 88.47 | 323.37 | 135.18 | 188.19 | 0.00 | 0.00 |
September | 566.50 | 131.26 | 416.04 | 232.15 | 183.89 | 0.00 | 0.00 |
October | 602.97 | 254.88 | 497.46 | 352.96 | 144.50 | 0.00 | 0.00 |
November | 713.64 | 282.92 | 606.09 | 483.14 | 122.95 | 0.00 | 0.00 |
December | 653.44 | 333.96 | 579.58 | 469.11 | 110.48 | 0.00 | 0.00 |
Annual Sum or Average | 521.66 | 205.33 | 428.59 | 267.23 | 161.36 | 0.00 | 0.00 |
Minimum of Months | 302.87 | 77.39 | 243.98 | 44.59 | 110.48 | 0.00 | 0.00 |
Maximum of Months | 726.85 | 333.96 | 630.48 | 518.64 | 216.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1461.32 | 574.01 | 1260.96 | 1037.27 | 223.68 | 0.00 | 0.00 |
February | 1394.16 | 594.27 | 1209.49 | 964.28 | 245.21 | 0.00 | 0.00 |
March | 1040.11 | 478.88 | 891.73 | 586.71 | 305.02 | 0.00 | 0.00 |
April | 617.21 | 435.69 | 577.55 | 232.24 | 345.32 | 0.00 | 0.00 |
May | 611.47 | 277.62 | 529.26 | 97.01 | 432.25 | 0.00 | 0.00 |
June | 704.68 | 160.30 | 487.96 | 89.19 | 398.78 | 0.00 | 0.00 |
July | 737.29 | 147.91 | 507.96 | 90.96 | 417.00 | 0.00 | 0.00 |
August | 939.94 | 169.71 | 646.73 | 270.36 | 376.37 | 0.00 | 0.00 |
September | 1134.46 | 255.00 | 832.08 | 464.30 | 367.79 | 0.00 | 0.00 |
October | 1209.88 | 497.45 | 994.93 | 705.92 | 289.00 | 0.00 | 0.00 |
November | 1433.69 | 551.64 | 1212.18 | 966.29 | 245.90 | 0.00 | 0.00 |
December | 1314.66 | 650.86 | 1159.16 | 938.21 | 220.95 | 0.00 | 0.00 |
Annual Sum or Average | 1047.92 | 398.38 | 857.18 | 534.47 | 322.72 | 0.00 | 0.00 |
Minimum of Months | 611.47 | 147.91 | 487.96 | 89.19 | 220.95 | 0.00 | 0.00 |
Maximum of Months | 1461.32 | 650.86 | 1260.96 | 1037.27 | 432.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 729.74 | 287.22 | 630.48 | 518.64 | 111.84 | 0.00 | 0.00 |
February | 695.86 | 298.05 | 604.75 | 482.14 | 122.60 | 0.00 | 0.00 |
March | 519.31 | 239.78 | 445.86 | 293.35 | 152.51 | 0.00 | 0.00 |
April | 308.14 | 217.95 | 288.78 | 116.12 | 172.66 | 0.00 | 0.00 |
May | 305.81 | 138.33 | 264.63 | 48.50 | 216.13 | 0.00 | 0.00 |
June | 352.80 | 79.28 | 243.98 | 44.59 | 199.39 | 0.00 | 0.00 |
July | 369.11 | 73.10 | 253.98 | 45.48 | 208.50 | 0.00 | 0.00 |
August | 470.14 | 83.90 | 323.37 | 135.18 | 188.19 | 0.00 | 0.00 |
September | 567.08 | 126.69 | 416.04 | 232.15 | 183.89 | 0.00 | 0.00 |
October | 604.46 | 248.72 | 497.46 | 352.96 | 144.50 | 0.00 | 0.00 |
November | 715.98 | 276.01 | 606.09 | 483.14 | 122.95 | 0.00 | 0.00 |
December | 656.09 | 326.55 | 579.58 | 469.11 | 110.48 | 0.00 | 0.00 |
Annual Sum or Average | 523.56 | 199.09 | 428.59 | 267.23 | 161.36 | 0.00 | 0.00 |
Minimum of Months | 305.81 | 73.10 | 243.98 | 44.59 | 110.48 | 0.00 | 0.00 |
Maximum of Months | 729.74 | 326.55 | 630.48 | 518.64 | 216.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 730.31 | 285.90 | 630.48 | 518.64 | 111.84 | 0.00 | 0.00 |
February | 696.34 | 296.94 | 604.75 | 482.14 | 122.60 | 0.00 | 0.00 |
March | 519.85 | 238.52 | 445.86 | 293.35 | 152.51 | 0.00 | 0.00 |
April | 308.68 | 216.49 | 288.78 | 116.12 | 172.66 | 0.00 | 0.00 |
May | 306.67 | 137.11 | 264.63 | 48.50 | 216.13 | 0.00 | 0.00 |
June | 353.10 | 78.86 | 243.98 | 44.59 | 199.39 | 0.00 | 0.00 |
July | 369.38 | 72.72 | 253.98 | 45.48 | 208.50 | 0.00 | 0.00 |
August | 470.38 | 83.52 | 323.37 | 135.18 | 188.19 | 0.00 | 0.00 |
September | 567.34 | 126.19 | 416.04 | 232.15 | 183.89 | 0.00 | 0.00 |
October | 604.93 | 247.59 | 497.46 | 352.96 | 144.50 | 0.00 | 0.00 |
November | 716.49 | 274.83 | 606.09 | 483.14 | 122.95 | 0.00 | 0.00 |
December | 656.50 | 325.46 | 579.58 | 469.11 | 110.48 | 0.00 | 0.00 |
Annual Sum or Average | 524.01 | 198.14 | 428.59 | 267.23 | 161.36 | 0.00 | 0.00 |
Minimum of Months | 306.67 | 72.72 | 243.98 | 44.59 | 110.48 | 0.00 | 0.00 |
Maximum of Months | 730.31 | 325.46 | 630.48 | 518.64 | 216.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 731.93 | 281.65 | 630.48 | 518.64 | 111.84 | 0.00 | 0.00 |
February | 697.82 | 292.81 | 604.75 | 482.14 | 122.60 | 0.00 | 0.00 |
March | 521.40 | 234.24 | 445.86 | 293.35 | 152.51 | 0.00 | 0.00 |
April | 310.10 | 211.90 | 288.78 | 116.12 | 172.66 | 0.00 | 0.00 |
May | 308.92 | 133.65 | 264.63 | 48.50 | 216.13 | 0.00 | 0.00 |
June | 353.69 | 77.81 | 243.98 | 44.59 | 199.39 | 0.00 | 0.00 |
July | 369.86 | 71.82 | 253.98 | 45.48 | 208.50 | 0.00 | 0.00 |
August | 470.73 | 82.69 | 323.37 | 135.18 | 188.19 | 0.00 | 0.00 |
September | 567.81 | 125.03 | 416.04 | 232.15 | 183.89 | 0.00 | 0.00 |
October | 606.15 | 244.29 | 497.46 | 352.96 | 144.50 | 0.00 | 0.00 |
November | 717.83 | 271.31 | 606.09 | 483.14 | 122.95 | 0.00 | 0.00 |
December | 657.74 | 321.59 | 579.58 | 469.11 | 110.48 | 0.00 | 0.00 |
Annual Sum or Average | 525.18 | 195.20 | 428.59 | 267.23 | 161.36 | 0.00 | 0.00 |
Minimum of Months | 308.92 | 71.82 | 243.98 | 44.59 | 110.48 | 0.00 | 0.00 |
Maximum of Months | 731.93 | 321.59 | 630.48 | 518.64 | 216.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 736.96 | 265.64 | 630.48 | 518.64 | 111.84 | 0.00 | 0.00 |
February | 702.59 | 276.04 | 604.75 | 482.14 | 122.60 | 0.00 | 0.00 |
March | 525.63 | 217.60 | 445.86 | 293.35 | 152.51 | 0.00 | 0.00 |
April | 313.62 | 195.17 | 288.78 | 116.12 | 172.66 | 0.00 | 0.00 |
May | 314.35 | 122.42 | 264.63 | 48.50 | 216.13 | 0.00 | 0.00 |
June | 354.56 | 73.58 | 243.98 | 44.59 | 199.39 | 0.00 | 0.00 |
July | 370.53 | 68.05 | 253.98 | 45.48 | 208.50 | 0.00 | 0.00 |
August | 470.85 | 79.37 | 323.37 | 135.18 | 188.19 | 0.00 | 0.00 |
September | 568.34 | 120.66 | 416.04 | 232.15 | 183.89 | 0.00 | 0.00 |
October | 608.96 | 232.45 | 497.46 | 352.96 | 144.50 | 0.00 | 0.00 |
November | 721.47 | 258.39 | 606.09 | 483.14 | 122.95 | 0.00 | 0.00 |
December | 661.61 | 306.33 | 579.58 | 469.11 | 110.48 | 0.00 | 0.00 |
Annual Sum or Average | 528.13 | 184.14 | 428.59 | 267.23 | 161.36 | 0.00 | 0.00 |
Minimum of Months | 313.62 | 68.05 | 243.98 | 44.59 | 110.48 | 0.00 | 0.00 |
Maximum of Months | 736.96 | 306.33 | 630.48 | 518.64 | 216.13 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.391683E+10 | 0.156483E+10 | 0.338429E+10 | 0.278394E+10 | 0.600346E+09 | 0.00 | 0.00 |
February | 0.337681E+10 | 0.146614E+10 | 0.293202E+10 | 0.233759E+10 | 0.594427E+09 | 0.00 | 0.00 |
March | 0.278736E+10 | 0.130620E+10 | 0.239332E+10 | 0.157467E+10 | 0.818651E+09 | 0.00 | 0.00 |
April | 0.159654E+10 | 0.115902E+10 | 0.150009E+10 | 0.603191E+09 | 0.896897E+09 | 0.00 | 0.00 |
May | 0.163703E+10 | 0.754686E+09 | 0.142049E+10 | 0.260365E+09 | 0.116012E+10 | 0.00 | 0.00 |
June | 0.183553E+10 | 0.405334E+09 | 0.126740E+10 | 0.231644E+09 | 0.103575E+10 | 0.00 | 0.00 |
July | 0.198821E+10 | 0.380514E+09 | 0.136331E+10 | 0.244130E+09 | 0.111918E+10 | 0.00 | 0.00 |
August | 0.252612E+10 | 0.442077E+09 | 0.173577E+10 | 0.725616E+09 | 0.101015E+10 | 0.00 | 0.00 |
September | 0.294954E+10 | 0.650591E+09 | 0.216119E+10 | 0.120593E+10 | 0.955260E+09 | 0.00 | 0.00 |
October | 0.324574E+10 | 0.134523E+10 | 0.267030E+10 | 0.189464E+10 | 0.775660E+09 | 0.00 | 0.00 |
November | 0.371765E+10 | 0.145291E+10 | 0.314844E+10 | 0.250976E+10 | 0.638676E+09 | 0.00 | 0.00 |
December | 0.352159E+10 | 0.178188E+10 | 0.311108E+10 | 0.251807E+10 | 0.593015E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.330990E+11 | 0.127094E+11 | 0.270877E+11 | 0.168895E+11 | 0.101981E+11 | 0.00 | 0.00 |
Minimum of Months | 0.159654E+10 | 0.380514E+09 | 0.126740E+10 | 0.231644E+09 | 0.593015E+09 | 0.00 | 0.00 |
Maximum of Months | 0.391683E+10 | 0.178188E+10 | 0.338429E+10 | 0.278394E+10 | 0.116012E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.194116E+10 | 0.826532E+09 | 0.169214E+10 | 0.139197E+10 | 0.300173E+09 | 0.00 | 0.00 |
February | 0.167254E+10 | 0.771815E+09 | 0.146601E+10 | 0.116879E+10 | 0.297214E+09 | 0.00 | 0.00 |
March | 0.137950E+10 | 0.692315E+09 | 0.119666E+10 | 0.787334E+09 | 0.409325E+09 | 0.00 | 0.00 |
April | 0.785425E+09 | 0.620409E+09 | 0.750044E+09 | 0.301596E+09 | 0.448448E+09 | 0.00 | 0.00 |
May | 0.806923E+09 | 0.396234E+09 | 0.710244E+09 | 0.130183E+09 | 0.580061E+09 | 0.00 | 0.00 |
June | 0.916020E+09 | 0.205622E+09 | 0.633698E+09 | 0.115822E+09 | 0.517876E+09 | 0.00 | 0.00 |
July | 0.992351E+09 | 0.193326E+09 | 0.681654E+09 | 0.122065E+09 | 0.559588E+09 | 0.00 | 0.00 |
August | 0.126152E+10 | 0.223482E+09 | 0.867884E+09 | 0.362808E+09 | 0.505076E+09 | 0.00 | 0.00 |
September | 0.147174E+10 | 0.330617E+09 | 0.108060E+10 | 0.602967E+09 | 0.477630E+09 | 0.00 | 0.00 |
October | 0.161368E+10 | 0.699538E+09 | 0.133515E+10 | 0.947318E+09 | 0.387830E+09 | 0.00 | 0.00 |
November | 0.184420E+10 | 0.764438E+09 | 0.157422E+10 | 0.125488E+10 | 0.319338E+09 | 0.00 | 0.00 |
December | 0.174557E+10 | 0.933570E+09 | 0.155554E+10 | 0.125903E+10 | 0.296507E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.164306E+11 | 0.665790E+10 | 0.135438E+11 | 0.844477E+10 | 0.509907E+10 | 0.00 | 0.00 |
Minimum of Months | 0.785425E+09 | 0.193326E+09 | 0.633698E+09 | 0.115822E+09 | 0.296507E+09 | 0.00 | 0.00 |
Maximum of Months | 0.194116E+10 | 0.933570E+09 | 0.169214E+10 | 0.139197E+10 | 0.580061E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.194110E+10 | 0.806192E+09 | 0.168867E+10 | 0.138912E+10 | 0.299557E+09 | 0.00 | 0.00 |
February | 0.167242E+10 | 0.752597E+09 | 0.146300E+10 | 0.116640E+10 | 0.296604E+09 | 0.00 | 0.00 |
March | 0.137930E+10 | 0.676980E+09 | 0.119420E+10 | 0.785719E+09 | 0.408486E+09 | 0.00 | 0.00 |
April | 0.786665E+09 | 0.603500E+09 | 0.748505E+09 | 0.300977E+09 | 0.447528E+09 | 0.00 | 0.00 |
May | 0.806283E+09 | 0.396759E+09 | 0.708787E+09 | 0.129916E+09 | 0.578871E+09 | 0.00 | 0.00 |
June | 0.910905E+09 | 0.219816E+09 | 0.632398E+09 | 0.115585E+09 | 0.516813E+09 | 0.00 | 0.00 |
July | 0.985698E+09 | 0.209185E+09 | 0.680255E+09 | 0.121815E+09 | 0.558440E+09 | 0.00 | 0.00 |
August | 0.125697E+10 | 0.239276E+09 | 0.866103E+09 | 0.362064E+09 | 0.504039E+09 | 0.00 | 0.00 |
September | 0.146712E+10 | 0.343600E+09 | 0.107838E+10 | 0.601730E+09 | 0.476650E+09 | 0.00 | 0.00 |
October | 0.161177E+10 | 0.694203E+09 | 0.133241E+10 | 0.945374E+09 | 0.387034E+09 | 0.00 | 0.00 |
November | 0.184436E+10 | 0.748625E+09 | 0.157099E+10 | 0.125231E+10 | 0.318683E+09 | 0.00 | 0.00 |
December | 0.174532E+10 | 0.911396E+09 | 0.155235E+10 | 0.125645E+10 | 0.295899E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.164079E+11 | 0.660213E+10 | 0.135161E+11 | 0.842745E+10 | 0.508861E+10 | 0.00 | 0.00 |
Minimum of Months | 0.786665E+09 | 0.209185E+09 | 0.632398E+09 | 0.115585E+09 | 0.295899E+09 | 0.00 | 0.00 |
Maximum of Months | 0.194110E+10 | 0.911396E+09 | 0.168867E+10 | 0.138912E+10 | 0.578871E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.194370E+10 | 0.797145E+09 | 0.168867E+10 | 0.138912E+10 | 0.299557E+09 | 0.00 | 0.00 |
February | 0.167461E+10 | 0.744706E+09 | 0.146300E+10 | 0.116640E+10 | 0.296604E+09 | 0.00 | 0.00 |
March | 0.138130E+10 | 0.669498E+09 | 0.119420E+10 | 0.785719E+09 | 0.408486E+09 | 0.00 | 0.00 |
April | 0.788772E+09 | 0.595150E+09 | 0.748505E+09 | 0.300977E+09 | 0.447528E+09 | 0.00 | 0.00 |
May | 0.807976E+09 | 0.392755E+09 | 0.708787E+09 | 0.129916E+09 | 0.578871E+09 | 0.00 | 0.00 |
June | 0.910844E+09 | 0.220174E+09 | 0.632398E+09 | 0.115585E+09 | 0.516813E+09 | 0.00 | 0.00 |
July | 0.985456E+09 | 0.209954E+09 | 0.680255E+09 | 0.121815E+09 | 0.558440E+09 | 0.00 | 0.00 |
August | 0.125690E+10 | 0.239785E+09 | 0.866103E+09 | 0.362064E+09 | 0.504039E+09 | 0.00 | 0.00 |
September | 0.146724E+10 | 0.343375E+09 | 0.107838E+10 | 0.601730E+09 | 0.476650E+09 | 0.00 | 0.00 |
October | 0.161294E+10 | 0.688920E+09 | 0.133241E+10 | 0.945374E+09 | 0.387034E+09 | 0.00 | 0.00 |
November | 0.184681E+10 | 0.740730E+09 | 0.157099E+10 | 0.125231E+10 | 0.318683E+09 | 0.00 | 0.00 |
December | 0.174749E+10 | 0.902407E+09 | 0.155235E+10 | 0.125645E+10 | 0.295899E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.164240E+11 | 0.654460E+10 | 0.135161E+11 | 0.842745E+10 | 0.508861E+10 | 0.00 | 0.00 |
Minimum of Months | 0.788772E+09 | 0.209954E+09 | 0.632398E+09 | 0.115585E+09 | 0.295899E+09 | 0.00 | 0.00 |
Maximum of Months | 0.194370E+10 | 0.902407E+09 | 0.168867E+10 | 0.138912E+10 | 0.578871E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.194679E+10 | 0.789094E+09 | 0.168867E+10 | 0.138912E+10 | 0.299557E+09 | 0.00 | 0.00 |
February | 0.167710E+10 | 0.738009E+09 | 0.146300E+10 | 0.116640E+10 | 0.296604E+09 | 0.00 | 0.00 |
March | 0.138409E+10 | 0.662038E+09 | 0.119420E+10 | 0.785719E+09 | 0.408486E+09 | 0.00 | 0.00 |
April | 0.791755E+09 | 0.586715E+09 | 0.748505E+09 | 0.300977E+09 | 0.447528E+09 | 0.00 | 0.00 |
May | 0.811199E+09 | 0.386982E+09 | 0.708787E+09 | 0.129916E+09 | 0.578871E+09 | 0.00 | 0.00 |
June | 0.912131E+09 | 0.217372E+09 | 0.632398E+09 | 0.115585E+09 | 0.516813E+09 | 0.00 | 0.00 |
July | 0.986659E+09 | 0.207271E+09 | 0.680255E+09 | 0.121815E+09 | 0.558440E+09 | 0.00 | 0.00 |
August | 0.125796E+10 | 0.236953E+09 | 0.866103E+09 | 0.362064E+09 | 0.504039E+09 | 0.00 | 0.00 |
September | 0.146838E+10 | 0.340226E+09 | 0.107838E+10 | 0.601730E+09 | 0.476650E+09 | 0.00 | 0.00 |
October | 0.161499E+10 | 0.682674E+09 | 0.133241E+10 | 0.945374E+09 | 0.387034E+09 | 0.00 | 0.00 |
November | 0.184975E+10 | 0.733337E+09 | 0.157099E+10 | 0.125231E+10 | 0.318683E+09 | 0.00 | 0.00 |
December | 0.175016E+10 | 0.894473E+09 | 0.155235E+10 | 0.125645E+10 | 0.295899E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.164510E+11 | 0.647514E+10 | 0.135161E+11 | 0.842745E+10 | 0.508861E+10 | 0.00 | 0.00 |
Minimum of Months | 0.791755E+09 | 0.207271E+09 | 0.632398E+09 | 0.115585E+09 | 0.295899E+09 | 0.00 | 0.00 |
Maximum of Months | 0.194679E+10 | 0.894473E+09 | 0.168867E+10 | 0.138912E+10 | 0.578871E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.391400E+10 | 0.153743E+10 | 0.337734E+10 | 0.277823E+10 | 0.599115E+09 | 0.00 | 0.00 |
February | 0.337275E+10 | 0.143765E+10 | 0.292600E+10 | 0.233279E+10 | 0.593208E+09 | 0.00 | 0.00 |
March | 0.278582E+10 | 0.128264E+10 | 0.238841E+10 | 0.157144E+10 | 0.816971E+09 | 0.00 | 0.00 |
April | 0.159980E+10 | 0.112932E+10 | 0.149701E+10 | 0.601954E+09 | 0.895057E+09 | 0.00 | 0.00 |
May | 0.163776E+10 | 0.743579E+09 | 0.141757E+10 | 0.259831E+09 | 0.115774E+10 | 0.00 | 0.00 |
June | 0.182654E+10 | 0.415507E+09 | 0.126480E+10 | 0.231169E+09 | 0.103363E+10 | 0.00 | 0.00 |
July | 0.197476E+10 | 0.396168E+09 | 0.136051E+10 | 0.243630E+09 | 0.111688E+10 | 0.00 | 0.00 |
August | 0.251753E+10 | 0.454549E+09 | 0.173221E+10 | 0.724128E+09 | 0.100808E+10 | 0.00 | 0.00 |
September | 0.294052E+10 | 0.660969E+09 | 0.215676E+10 | 0.120346E+10 | 0.953300E+09 | 0.00 | 0.00 |
October | 0.324055E+10 | 0.133238E+10 | 0.266482E+10 | 0.189075E+10 | 0.774069E+09 | 0.00 | 0.00 |
November | 0.371613E+10 | 0.142984E+10 | 0.314198E+10 | 0.250461E+10 | 0.637365E+09 | 0.00 | 0.00 |
December | 0.352120E+10 | 0.174327E+10 | 0.310470E+10 | 0.251290E+10 | 0.591798E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.330473E+11 | 0.125633E+11 | 0.270321E+11 | 0.168549E+11 | 0.101772E+11 | 0.00 | 0.00 |
Minimum of Months | 0.159980E+10 | 0.396168E+09 | 0.126480E+10 | 0.231169E+09 | 0.591798E+09 | 0.00 | 0.00 |
Maximum of Months | 0.391400E+10 | 0.174327E+10 | 0.337734E+10 | 0.277823E+10 | 0.115774E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.195454E+10 | 0.769300E+09 | 0.168867E+10 | 0.138912E+10 | 0.299557E+09 | 0.00 | 0.00 |
February | 0.168342E+10 | 0.721052E+09 | 0.146300E+10 | 0.116640E+10 | 0.296604E+09 | 0.00 | 0.00 |
March | 0.139092E+10 | 0.642222E+09 | 0.119420E+10 | 0.785719E+09 | 0.408486E+09 | 0.00 | 0.00 |
April | 0.798703E+09 | 0.564917E+09 | 0.748505E+09 | 0.300977E+09 | 0.447528E+09 | 0.00 | 0.00 |
May | 0.819082E+09 | 0.370507E+09 | 0.708787E+09 | 0.129916E+09 | 0.578871E+09 | 0.00 | 0.00 |
June | 0.914452E+09 | 0.205496E+09 | 0.632398E+09 | 0.115585E+09 | 0.516813E+09 | 0.00 | 0.00 |
July | 0.988623E+09 | 0.195791E+09 | 0.680255E+09 | 0.121815E+09 | 0.558440E+09 | 0.00 | 0.00 |
August | 0.125923E+10 | 0.224723E+09 | 0.866103E+09 | 0.362064E+09 | 0.504039E+09 | 0.00 | 0.00 |
September | 0.146987E+10 | 0.328381E+09 | 0.107838E+10 | 0.601730E+09 | 0.476650E+09 | 0.00 | 0.00 |
October | 0.161899E+10 | 0.666165E+09 | 0.133241E+10 | 0.945374E+09 | 0.387034E+09 | 0.00 | 0.00 |
November | 0.185583E+10 | 0.715412E+09 | 0.157099E+10 | 0.125231E+10 | 0.318683E+09 | 0.00 | 0.00 |
December | 0.175727E+10 | 0.874633E+09 | 0.155235E+10 | 0.125645E+10 | 0.295899E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.165109E+11 | 0.627860E+10 | 0.135161E+11 | 0.842745E+10 | 0.508861E+10 | 0.00 | 0.00 |
Minimum of Months | 0.798703E+09 | 0.195791E+09 | 0.632398E+09 | 0.115585E+09 | 0.295899E+09 | 0.00 | 0.00 |
Maximum of Months | 0.195454E+10 | 0.874633E+09 | 0.168867E+10 | 0.138912E+10 | 0.578871E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.195607E+10 | 0.765757E+09 | 0.168867E+10 | 0.138912E+10 | 0.299557E+09 | 0.00 | 0.00 |
February | 0.168459E+10 | 0.718361E+09 | 0.146300E+10 | 0.116640E+10 | 0.296604E+09 | 0.00 | 0.00 |
March | 0.139237E+10 | 0.638856E+09 | 0.119420E+10 | 0.785719E+09 | 0.408486E+09 | 0.00 | 0.00 |
April | 0.800097E+09 | 0.561142E+09 | 0.748505E+09 | 0.300977E+09 | 0.447528E+09 | 0.00 | 0.00 |
May | 0.821390E+09 | 0.367239E+09 | 0.708787E+09 | 0.129916E+09 | 0.578871E+09 | 0.00 | 0.00 |
June | 0.915244E+09 | 0.204393E+09 | 0.632398E+09 | 0.115585E+09 | 0.516813E+09 | 0.00 | 0.00 |
July | 0.989352E+09 | 0.194770E+09 | 0.680255E+09 | 0.121815E+09 | 0.558440E+09 | 0.00 | 0.00 |
August | 0.125986E+10 | 0.223690E+09 | 0.866103E+09 | 0.362064E+09 | 0.504039E+09 | 0.00 | 0.00 |
September | 0.147053E+10 | 0.327087E+09 | 0.107838E+10 | 0.601730E+09 | 0.476650E+09 | 0.00 | 0.00 |
October | 0.162026E+10 | 0.663138E+09 | 0.133241E+10 | 0.945374E+09 | 0.387034E+09 | 0.00 | 0.00 |
November | 0.185714E+10 | 0.712351E+09 | 0.157099E+10 | 0.125231E+10 | 0.318683E+09 | 0.00 | 0.00 |
December | 0.175837E+10 | 0.871716E+09 | 0.155235E+10 | 0.125645E+10 | 0.295899E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.165253E+11 | 0.624850E+10 | 0.135161E+11 | 0.842745E+10 | 0.508861E+10 | 0.00 | 0.00 |
Minimum of Months | 0.800097E+09 | 0.194770E+09 | 0.632398E+09 | 0.115585E+09 | 0.295899E+09 | 0.00 | 0.00 |
Maximum of Months | 0.195607E+10 | 0.871716E+09 | 0.168867E+10 | 0.138912E+10 | 0.578871E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.196041E+10 | 0.754383E+09 | 0.168867E+10 | 0.138912E+10 | 0.299557E+09 | 0.00 | 0.00 |
February | 0.168817E+10 | 0.708364E+09 | 0.146300E+10 | 0.116640E+10 | 0.296604E+09 | 0.00 | 0.00 |
March | 0.139650E+10 | 0.627387E+09 | 0.119420E+10 | 0.785719E+09 | 0.408486E+09 | 0.00 | 0.00 |
April | 0.803785E+09 | 0.549253E+09 | 0.748505E+09 | 0.300977E+09 | 0.447528E+09 | 0.00 | 0.00 |
May | 0.827421E+09 | 0.357964E+09 | 0.708787E+09 | 0.129916E+09 | 0.578871E+09 | 0.00 | 0.00 |
June | 0.916752E+09 | 0.201683E+09 | 0.632398E+09 | 0.115585E+09 | 0.516813E+09 | 0.00 | 0.00 |
July | 0.990621E+09 | 0.192374E+09 | 0.680255E+09 | 0.121815E+09 | 0.558440E+09 | 0.00 | 0.00 |
August | 0.126080E+10 | 0.221468E+09 | 0.866103E+09 | 0.362064E+09 | 0.504039E+09 | 0.00 | 0.00 |
September | 0.147177E+10 | 0.324078E+09 | 0.107838E+10 | 0.601730E+09 | 0.476650E+09 | 0.00 | 0.00 |
October | 0.162350E+10 | 0.654308E+09 | 0.133241E+10 | 0.945374E+09 | 0.387034E+09 | 0.00 | 0.00 |
November | 0.186063E+10 | 0.703231E+09 | 0.157099E+10 | 0.125231E+10 | 0.318683E+09 | 0.00 | 0.00 |
December | 0.176169E+10 | 0.861356E+09 | 0.155235E+10 | 0.125645E+10 | 0.295899E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.165621E+11 | 0.615585E+10 | 0.135161E+11 | 0.842745E+10 | 0.508861E+10 | 0.00 | 0.00 |
Minimum of Months | 0.803785E+09 | 0.192374E+09 | 0.632398E+09 | 0.115585E+09 | 0.295899E+09 | 0.00 | 0.00 |
Maximum of Months | 0.196041E+10 | 0.861356E+09 | 0.168867E+10 | 0.138912E+10 | 0.578871E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.197388E+10 | 0.711489E+09 | 0.168867E+10 | 0.138912E+10 | 0.299557E+09 | 0.00 | 0.00 |
February | 0.169970E+10 | 0.667787E+09 | 0.146300E+10 | 0.116640E+10 | 0.296604E+09 | 0.00 | 0.00 |
March | 0.140785E+10 | 0.582824E+09 | 0.119420E+10 | 0.785719E+09 | 0.408486E+09 | 0.00 | 0.00 |
April | 0.812910E+09 | 0.505875E+09 | 0.748505E+09 | 0.300977E+09 | 0.447528E+09 | 0.00 | 0.00 |
May | 0.841968E+09 | 0.327889E+09 | 0.708787E+09 | 0.129916E+09 | 0.578871E+09 | 0.00 | 0.00 |
June | 0.919023E+09 | 0.190728E+09 | 0.632398E+09 | 0.115585E+09 | 0.516813E+09 | 0.00 | 0.00 |
July | 0.992430E+09 | 0.182271E+09 | 0.680255E+09 | 0.121815E+09 | 0.558440E+09 | 0.00 | 0.00 |
August | 0.126111E+10 | 0.212596E+09 | 0.866103E+09 | 0.362064E+09 | 0.504039E+09 | 0.00 | 0.00 |
September | 0.147313E+10 | 0.312753E+09 | 0.107838E+10 | 0.601730E+09 | 0.476650E+09 | 0.00 | 0.00 |
October | 0.163104E+10 | 0.622603E+09 | 0.133241E+10 | 0.945374E+09 | 0.387034E+09 | 0.00 | 0.00 |
November | 0.187006E+10 | 0.669738E+09 | 0.157099E+10 | 0.125231E+10 | 0.318683E+09 | 0.00 | 0.00 |
December | 0.177205E+10 | 0.820484E+09 | 0.155235E+10 | 0.125645E+10 | 0.295899E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.166551E+11 | 0.580704E+10 | 0.135161E+11 | 0.842745E+10 | 0.508861E+10 | 0.00 | 0.00 |
Minimum of Months | 0.812910E+09 | 0.182271E+09 | 0.632398E+09 | 0.115585E+09 | 0.295899E+09 | 0.00 | 0.00 |
Maximum of Months | 0.197388E+10 | 0.820484E+09 | 0.168867E+10 | 0.138912E+10 | 0.578871E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.370595E+09 | -247793999.0 | 0.00 | 0.00 | 744.00 | 0.00 | -122801393.4 | 58.99 | 0.00 | 0.00 |
February | 0.339378E+09 | -227796559.4 | 0.00 | 0.00 | 672.00 | 0.00 | -111581784.2 | 58.99 | 0.00 | 0.00 |
March | 0.373855E+09 | -252561115.0 | 0.00 | 0.00 | 744.00 | 0.00 | -121293466.0 | 58.99 | 0.00 | 0.00 |
April | 0.348617E+09 | -231743555.8 | 0.00 | 0.00 | 720.00 | 0.00 | -116873653.5 | 58.99 | 0.00 | 0.00 |
May | 0.341844E+09 | -226497925.9 | 0.00 | 0.00 | 744.00 | 0.00 | -115345726.7 | 58.99 | 0.00 | 0.00 |
June | 0.317368E+09 | -208346221.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109021782.9 | 58.99 | 0.00 | 0.00 |
July | 0.313836E+09 | -201339887.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112496482.9 | 58.99 | 0.00 | 0.00 |
August | 0.314619E+09 | -202215699.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112403373.6 | 58.99 | 0.00 | 0.00 |
September | 0.306604E+09 | -197251743.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109352314.5 | 58.99 | 0.00 | 0.00 |
October | 0.329148E+09 | -211853507.5 | 0.00 | 0.00 | 744.00 | 0.00 | -117294076.1 | 58.99 | 0.00 | 0.00 |
November | 0.334384E+09 | -217272072.0 | 0.00 | 0.00 | 720.00 | 0.00 | -117112367.4 | 58.99 | 0.00 | 0.00 |
December | 0.361795E+09 | -238555854.2 | 0.00 | 0.00 | 744.00 | 0.00 | -123238750.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.405204E+10 | -0.266323E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138882E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.306604E+09 | -252561115.0 | 0.00 | 0.00 | 672.00 | 0.00 | -123238750.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.373855E+09 | -197251743.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109021782.9 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.367517E+09 | -247794558.1 | 0.00 | 0.00 | 744.00 | 0.00 | -119722021.9 | 58.99 | 0.00 | 0.00 |
February | 0.336878E+09 | -227796997.3 | 0.00 | 0.00 | 672.00 | 0.00 | -109081201.6 | 58.99 | 0.00 | 0.00 |
March | 0.371385E+09 | -252568390.8 | 0.00 | 0.00 | 744.00 | 0.00 | -118816757.8 | 58.99 | 0.00 | 0.00 |
April | 0.345950E+09 | -231746258.3 | 0.00 | 0.00 | 720.00 | 0.00 | -114204087.9 | 58.99 | 0.00 | 0.00 |
May | 0.340436E+09 | -226499829.5 | 0.00 | 0.00 | 744.00 | 0.00 | -113936463.1 | 58.99 | 0.00 | 0.00 |
June | 0.317183E+09 | -208350783.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108832401.9 | 58.99 | 0.00 | 0.00 |
July | 0.313665E+09 | -201337573.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112327832.3 | 58.99 | 0.00 | 0.00 |
August | 0.314505E+09 | -202207448.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112297813.6 | 58.99 | 0.00 | 0.00 |
September | 0.306244E+09 | -197252246.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108991815.0 | 58.99 | 0.00 | 0.00 |
October | 0.327342E+09 | -211855628.1 | 0.00 | 0.00 | 744.00 | 0.00 | -115486301.6 | 58.99 | 0.00 | 0.00 |
November | 0.331619E+09 | -217268575.7 | 0.00 | 0.00 | 720.00 | 0.00 | -114350187.9 | 59.00 | 0.00 | 0.00 |
December | 0.359124E+09 | -238552992.3 | 0.00 | 0.00 | 744.00 | 0.00 | -120571337.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.403185E+10 | -0.266323E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.136862E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.306244E+09 | -252568390.8 | 0.00 | 0.00 | 672.00 | 0.00 | -120571337.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.371385E+09 | -197252246.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108832401.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.339409E+09 | -217898958.3 | 0.00 | 0.00 | 744.00 | 0.00 | -121510177.5 | 59.00 | 0.00 | 0.00 |
February | 0.311188E+09 | -200475839.5 | 0.00 | 0.00 | 672.00 | 0.00 | -110712522.3 | 59.00 | 0.00 | 0.00 |
March | 0.345488E+09 | -225415373.1 | 0.00 | 0.00 | 744.00 | 0.00 | -120072397.7 | 58.99 | 0.00 | 0.00 |
April | 0.319467E+09 | -203801210.6 | 0.00 | 0.00 | 720.00 | 0.00 | -115665404.8 | 59.00 | 0.00 | 0.00 |
May | 0.314722E+09 | -200895811.4 | 0.00 | 0.00 | 744.00 | 0.00 | -113826265.6 | 58.99 | 0.00 | 0.00 |
June | 0.292799E+09 | -185537952.4 | 0.00 | 0.00 | 720.00 | 0.00 | -107260598.3 | 59.00 | 0.00 | 0.00 |
July | 0.286485E+09 | -176046469.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110438325.5 | 58.98 | 0.00 | 0.00 |
August | 0.291248E+09 | -180642189.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110606086.0 | 58.98 | 0.00 | 0.00 |
September | 0.281071E+09 | -173385846.5 | 0.00 | 0.00 | 720.00 | 0.00 | -107685042.8 | 58.98 | 0.00 | 0.00 |
October | 0.302253E+09 | -186315370.4 | 0.00 | 0.00 | 744.00 | 0.00 | -115937265.6 | 58.99 | 0.00 | 0.00 |
November | 0.307620E+09 | -191818434.3 | 0.00 | 0.00 | 720.00 | 0.00 | -115801682.0 | 59.00 | 0.00 | 0.00 |
December | 0.330602E+09 | -208223383.6 | 0.00 | 0.00 | 744.00 | 0.00 | -122378616.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.372235E+10 | -0.235046E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.137189E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.281071E+09 | -225415373.1 | 0.00 | 0.00 | 672.00 | 0.00 | -122378616.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.345488E+09 | -173385846.5 | 0.00 | 0.00 | 744.00 | 0.00 | -107260598.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.339942E+09 | -217903252.9 | 0.00 | 0.00 | 744.00 | 0.00 | -122038706.7 | 59.00 | 0.00 | 0.00 |
February | 0.311633E+09 | -200480865.3 | 0.00 | 0.00 | 672.00 | 0.00 | -111151904.9 | 58.99 | 0.00 | 0.00 |
March | 0.345912E+09 | -225418752.9 | 0.00 | 0.00 | 744.00 | 0.00 | -120493526.3 | 58.99 | 0.00 | 0.00 |
April | 0.319920E+09 | -203839541.6 | 0.00 | 0.00 | 720.00 | 0.00 | -116080045.5 | 58.98 | 0.00 | 0.00 |
May | 0.314992E+09 | -200898516.4 | 0.00 | 0.00 | 744.00 | 0.00 | -114092985.7 | 58.99 | 0.00 | 0.00 |
June | 0.292761E+09 | -185563819.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107197623.0 | 58.99 | 0.00 | 0.00 |
July | 0.286442E+09 | -176014610.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110427679.4 | 58.99 | 0.00 | 0.00 |
August | 0.291239E+09 | -180591294.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110647414.4 | 59.00 | 0.00 | 0.00 |
September | 0.281091E+09 | -173351808.4 | 0.00 | 0.00 | 720.00 | 0.00 | -107738792.1 | 59.00 | 0.00 | 0.00 |
October | 0.302547E+09 | -186326724.7 | 0.00 | 0.00 | 744.00 | 0.00 | -116220723.8 | 58.99 | 0.00 | 0.00 |
November | 0.308104E+09 | -191830224.7 | 0.00 | 0.00 | 720.00 | 0.00 | -116273994.2 | 59.00 | 0.00 | 0.00 |
December | 0.331098E+09 | -208205538.7 | 0.00 | 0.00 | 744.00 | 0.00 | -122892138.7 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.372568E+10 | -0.235042E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.137526E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.281091E+09 | -225418752.9 | 0.00 | 0.00 | 672.00 | 0.00 | -122892138.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.345912E+09 | -173351808.4 | 0.00 | 0.00 | 744.00 | 0.00 | -107197623.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.329828E+09 | -205919599.8 | 0.00 | 0.00 | 744.00 | 0.00 | -123908529.8 | 59.01 | 0.00 | 0.00 |
February | 0.302273E+09 | -189589473.6 | 0.00 | 0.00 | 672.00 | 0.00 | -112683885.0 | 58.99 | 0.00 | 0.00 |
March | 0.335518E+09 | -213274058.4 | 0.00 | 0.00 | 744.00 | 0.00 | -122243641.3 | 59.00 | 0.00 | 0.00 |
April | 0.310825E+09 | -192883849.8 | 0.00 | 0.00 | 720.00 | 0.00 | -117940916.8 | 58.99 | 0.00 | 0.00 |
May | 0.305626E+09 | -189992006.4 | 0.00 | 0.00 | 744.00 | 0.00 | -115633625.5 | 58.99 | 0.00 | 0.00 |
June | 0.283665E+09 | -175589022.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108075628.0 | 58.98 | 0.00 | 0.00 |
July | 0.277713E+09 | -166465941.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111247272.0 | 58.99 | 0.00 | 0.00 |
August | 0.282350E+09 | -170894465.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111455777.3 | 58.99 | 0.00 | 0.00 |
September | 0.272579E+09 | -164050660.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108528170.9 | 58.99 | 0.00 | 0.00 |
October | 0.293702E+09 | -176099928.2 | 0.00 | 0.00 | 744.00 | 0.00 | -117602373.5 | 59.00 | 0.00 | 0.00 |
November | 0.299076E+09 | -181175838.8 | 0.00 | 0.00 | 720.00 | 0.00 | -117899973.0 | 59.00 | 0.00 | 0.00 |
December | 0.321590E+09 | -196930684.5 | 0.00 | 0.00 | 744.00 | 0.00 | -124659355.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.361474E+10 | -0.222287E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139188E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.272579E+09 | -213274058.4 | 0.00 | 0.00 | 672.00 | 0.00 | -124659355.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.335518E+09 | -164050660.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108075628.0 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.329921E+09 | -205920737.0 | 0.00 | 0.00 | 744.00 | 0.00 | -124000645.0 | 59.01 | 0.00 | 0.00 |
February | 0.302307E+09 | -189586818.3 | 0.00 | 0.00 | 672.00 | 0.00 | -112719921.8 | 58.99 | 0.00 | 0.00 |
March | 0.335592E+09 | -213270644.5 | 0.00 | 0.00 | 744.00 | 0.00 | -122321418.8 | 59.00 | 0.00 | 0.00 |
April | 0.310926E+09 | -192882599.4 | 0.00 | 0.00 | 720.00 | 0.00 | -118043292.1 | 58.99 | 0.00 | 0.00 |
May | 0.305755E+09 | -189997878.4 | 0.00 | 0.00 | 744.00 | 0.00 | -115757162.1 | 58.99 | 0.00 | 0.00 |
June | 0.283799E+09 | -175573086.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108225738.6 | 58.99 | 0.00 | 0.00 |
July | 0.277834E+09 | -166444784.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111388873.1 | 59.00 | 0.00 | 0.00 |
August | 0.282462E+09 | -170917229.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111544469.0 | 58.98 | 0.00 | 0.00 |
September | 0.272703E+09 | -164058008.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108644823.9 | 58.99 | 0.00 | 0.00 |
October | 0.293798E+09 | -176097941.6 | 0.00 | 0.00 | 744.00 | 0.00 | -117699952.9 | 58.99 | 0.00 | 0.00 |
November | 0.299182E+09 | -181182138.8 | 0.00 | 0.00 | 720.00 | 0.00 | -117999751.0 | 58.99 | 0.00 | 0.00 |
December | 0.321615E+09 | -196926036.6 | 0.00 | 0.00 | 744.00 | 0.00 | -124689007.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.361589E+10 | -0.222286E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139304E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.272703E+09 | -213270644.5 | 0.00 | 0.00 | 672.00 | 0.00 | -124689007.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.335592E+09 | -164058008.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108225738.6 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.330131E+09 | -205925848.8 | 0.00 | 0.00 | 744.00 | 0.00 | -124205495.4 | 59.00 | 0.00 | 0.00 |
February | 0.302469E+09 | -189581579.4 | 0.00 | 0.00 | 672.00 | 0.00 | -112887629.1 | 58.99 | 0.00 | 0.00 |
March | 0.335781E+09 | -213295515.6 | 0.00 | 0.00 | 744.00 | 0.00 | -122485202.8 | 58.99 | 0.00 | 0.00 |
April | 0.311140E+09 | -192868203.6 | 0.00 | 0.00 | 720.00 | 0.00 | -118271727.9 | 58.99 | 0.00 | 0.00 |
May | 0.306021E+09 | -189994336.9 | 0.00 | 0.00 | 744.00 | 0.00 | -116027151.8 | 58.99 | 0.00 | 0.00 |
June | 0.283860E+09 | -175591825.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108268508.3 | 58.99 | 0.00 | 0.00 |
July | 0.277900E+09 | -166446673.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111453034.4 | 58.99 | 0.00 | 0.00 |
August | 0.282523E+09 | -170915903.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111607413.7 | 58.98 | 0.00 | 0.00 |
September | 0.272781E+09 | -164053770.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108727728.7 | 59.00 | 0.00 | 0.00 |
October | 0.293996E+09 | -176103595.6 | 0.00 | 0.00 | 744.00 | 0.00 | -117892521.7 | 58.99 | 0.00 | 0.00 |
November | 0.299361E+09 | -181174002.5 | 0.00 | 0.00 | 720.00 | 0.00 | -118187303.4 | 58.99 | 0.00 | 0.00 |
December | 0.321775E+09 | -196928100.2 | 0.00 | 0.00 | 744.00 | 0.00 | -124847062.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.361774E+10 | -0.222288E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139486E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.272781E+09 | -213295515.6 | 0.00 | 0.00 | 672.00 | 0.00 | -124847062.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.335781E+09 | -164053770.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108268508.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 245.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 415.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 421.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 430.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 394.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 354.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 262.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 257.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 251.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3902.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 245.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 430.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.830180E+10 | 62797.89 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.932256E+10 | 62797.89 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.643899E+10 | 62797.89 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.455277E+10 | 62797.89 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167355E+09 | 62797.89 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20646893.62 | 5495.67 | 22-SEP-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.322569E+10 | 62797.89 | 24-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.507427E+10 | 62797.89 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116371E+11 | 62797.89 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.487412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116371E+11 | 62797.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.200767E+10 | 33234.47 | 05-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244993E+10 | 33234.47 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159058E+10 | 33234.47 | 05-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.999460E+09 | 33234.47 | 03-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11863468.87 | 3715.24 | 02-MAY-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 426699.87 | 711.17 | 22-SEP-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.950787E+09 | 33234.47 | 31-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123065E+10 | 33234.47 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.333069E+10 | 33234.47 | 08-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.333069E+10 | 33234.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.277929E+10 | 34363.73 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.316564E+10 | 34363.73 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213878E+10 | 34363.73 | 05-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143187E+10 | 34363.73 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41197379.54 | 6882.91 | 03-MAY-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1659496.16 | 1017.74 | 22-SEP-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119608E+10 | 34363.73 | 31-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.175520E+10 | 34363.73 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.415453E+10 | 34363.73 | 08-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.415453E+10 | 34363.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.298530E+10 | 34190.73 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.335045E+10 | 34190.73 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.228116E+10 | 34190.73 | 05-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156300E+10 | 34190.73 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 54538986.00 | 10480.99 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2319799.08 | 1107.17 | 22-SEP-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125964E+10 | 34190.73 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190354E+10 | 34190.73 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.435990E+10 | 34190.73 | 08-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.435990E+10 | 34190.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.326468E+10 | 34188.68 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.363731E+10 | 34188.68 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.250272E+10 | 34188.68 | 05-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.176062E+10 | 34188.68 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74887767.77 | 14771.59 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4245241.32 | 2123.17 | 22-SEP-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135240E+10 | 34188.68 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.211262E+10 | 34188.68 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.466018E+10 | 34188.68 | 08-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.466018E+10 | 34188.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.694546E+10 | 60020.47 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.765340E+10 | 60020.47 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.529761E+10 | 60020.47 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.384777E+10 | 60020.47 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202974E+09 | 60020.47 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17010806.31 | 7176.00 | 22-SEP-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.285459E+10 | 60020.47 | 24-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.469021E+10 | 60020.47 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.958265E+10 | 60020.47 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.410917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.958265E+10 | 60020.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.361441E+10 | 30505.48 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.398599E+10 | 30505.48 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.278020E+10 | 30505.48 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.203523E+10 | 30505.48 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110753E+09 | 30505.48 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7948517.27 | 3736.34 | 22-SEP-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148776E+10 | 30505.48 | 24-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.243628E+10 | 30505.48 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.497827E+10 | 30505.48 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.497827E+10 | 30505.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.373123E+10 | 30377.45 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.408878E+10 | 30377.45 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286106E+10 | 30377.45 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.211634E+10 | 30377.45 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121543E+09 | 30377.45 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9251312.52 | 3507.68 | 22-SEP-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152416E+10 | 30377.45 | 24-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.251905E+10 | 30377.45 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.507819E+10 | 30377.45 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.507819E+10 | 30377.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.413065E+10 | 30202.47 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.447404E+10 | 30202.47 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.317502E+10 | 30202.47 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.240822E+10 | 30202.47 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158564E+09 | 30202.47 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13592372.83 | 3316.67 | 22-SEP-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165436E+10 | 30202.47 | 23-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279183E+10 | 30202.47 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.544759E+10 | 30202.47 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.544759E+10 | 30202.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.566117E+10 | 31742.33 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.614233E+10 | 31742.33 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.450434E+10 | 31742.33 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.352196E+10 | 31742.33 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.314929E+09 | 31742.33 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 42290429.86 | 15881.93 | 22-SEP-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223526E+10 | 31742.33 | 23-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.376538E+10 | 31742.33 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.721759E+10 | 31742.33 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.334052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.721759E+10 | 31742.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 24828016.62 | 24828016.62 | 3663.45 | 20-JAN-14:00 | 3663.45 | 0.00 |
February | 0.00 | 0.00 | 7264502.69 | 7264502.69 | 1788.69 | 18-FEB-14:00 | 1788.69 | 0.00 |
March | 0.00 | 0.00 | 0.488296E+09 | 0.488296E+09 | 10144.18 | 14-MAR-13:00 | 10144.18 | 0.00 |
April | 0.00 | 0.00 | 0.145398E+09 | 0.145398E+09 | 5079.59 | 20-APR-13:00 | 5079.59 | 0.00 |
May | 0.00 | 0.00 | 0.320669E+10 | 0.316724E+10 | 13405.09 | 17-MAY-14:00 | 13405.09 | 0.00 |
June | 0.00 | 0.00 | 0.168553E+11 | 0.160259E+11 | 38689.34 | 25-JUN-07:02 | 38689.34 | 0.00 |
July | 0.00 | 0.00 | 0.182197E+11 | 0.170141E+11 | 42582.30 | 24-JUL-07:02 | 33176.01 | 0.00 |
August | 0.00 | 0.00 | 0.173922E+11 | 0.165215E+11 | 41565.26 | 03-AUG-07:02 | 33200.54 | 0.00 |
September | 0.00 | 0.00 | 0.121059E+11 | 0.119395E+11 | 38133.02 | 13-SEP-07:02 | 35523.77 | 0.00 |
October | 0.00 | 0.00 | 0.165352E+10 | 0.165299E+10 | 15446.88 | 11-OCT-14:00 | 15446.88 | 0.00 |
November | 0.00 | 0.00 | 0.331092E+09 | 0.331092E+09 | 8359.55 | 07-NOV-15:00 | 8359.55 | 0.00 |
December | 0.00 | 0.00 | 58006141.54 | 58006141.54 | 4619.96 | 02-DEC-15:00 | 4619.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.704883E+11 | 0.673761E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7264502.69 | 7264502.69 | 1788.69 | 1788.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.182197E+11 | 0.170141E+11 | 42582.30 | 38689.34 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 51736789.62 | 51665687.23 | 3150.83 | 20-JAN-14:00 | 3150.83 | 0.00 |
February | 0.00 | 0.00 | 16157100.42 | 16145578.67 | 2098.13 | 18-FEB-14:00 | 2098.13 | 0.00 |
March | 0.00 | 0.00 | 0.386095E+09 | 0.386078E+09 | 21282.15 | 12-MAR-17:01 | 21282.15 | 0.00 |
April | 0.00 | 0.00 | 0.163662E+09 | 0.163428E+09 | 3600.05 | 20-APR-13:00 | 3600.05 | 0.00 |
May | 0.00 | 0.00 | 0.240041E+10 | 0.235461E+10 | 21456.05 | 31-MAY-20:40 | 17339.94 | 0.00 |
June | 0.00 | 0.00 | 0.102889E+11 | 0.968766E+10 | 22770.18 | 17-JUN-18:40 | 17340.54 | 0.00 |
July | 0.00 | 0.00 | 0.112132E+11 | 0.103220E+11 | 23486.53 | 29-JUL-18:03 | 14580.43 | 0.00 |
August | 0.00 | 0.00 | 0.107183E+11 | 0.100737E+11 | 22990.15 | 03-AUG-22:50 | 13585.44 | 0.00 |
September | 0.00 | 0.00 | 0.761503E+10 | 0.746886E+10 | 21941.60 | 02-SEP-19:58 | 19109.95 | 0.00 |
October | 0.00 | 0.00 | 0.110082E+10 | 0.109963E+10 | 21282.15 | 08-OCT-17:07 | 21282.15 | 0.00 |
November | 0.00 | 0.00 | 0.258423E+09 | 0.258210E+09 | 5091.98 | 07-NOV-14:30 | 5091.98 | 0.00 |
December | 0.00 | 0.00 | 75927396.34 | 75925425.64 | 3437.95 | 02-DEC-15:00 | 3437.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.442887E+11 | 0.419579E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16157100.42 | 16145578.67 | 2098.13 | 2098.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.112132E+11 | 0.103220E+11 | 23486.53 | 21282.15 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 24028503.27 | 24028503.27 | 2327.03 | 20-JAN-14:00 | 2327.03 | 0.00 |
February | 0.00 | 0.00 | 9042512.31 | 9042512.31 | 1580.31 | 18-FEB-14:00 | 1580.31 | 0.00 |
March | 0.00 | 0.00 | 0.297361E+09 | 0.297361E+09 | 6089.71 | 14-MAR-13:00 | 6089.71 | 0.00 |
April | 0.00 | 0.00 | 0.101756E+09 | 0.101756E+09 | 3208.31 | 20-APR-13:00 | 3208.31 | 0.00 |
May | 0.00 | 0.00 | 0.173937E+10 | 0.172326E+10 | 7280.28 | 17-MAY-13:00 | 7280.28 | 0.00 |
June | 0.00 | 0.00 | 0.754562E+10 | 0.719272E+10 | 22022.97 | 25-JUN-07:02 | 22022.97 | 0.00 |
July | 0.00 | 0.00 | 0.805115E+10 | 0.754387E+10 | 23615.69 | 24-JUL-06:02 | 16117.11 | 0.00 |
August | 0.00 | 0.00 | 0.766307E+10 | 0.734619E+10 | 23338.29 | 03-AUG-06:02 | 17274.71 | 0.00 |
September | 0.00 | 0.00 | 0.556141E+10 | 0.550011E+10 | 22255.81 | 03-SEP-07:02 | 19995.13 | 0.00 |
October | 0.00 | 0.00 | 0.856427E+09 | 0.856252E+09 | 8198.65 | 11-OCT-14:00 | 8198.65 | 0.00 |
November | 0.00 | 0.00 | 0.190155E+09 | 0.190155E+09 | 4645.56 | 07-NOV-14:00 | 4645.56 | 0.00 |
December | 0.00 | 0.00 | 42809259.70 | 42809259.70 | 2928.88 | 02-DEC-15:00 | 2928.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.320822E+11 | 0.308275E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 9042512.31 | 9042512.31 | 1580.31 | 1580.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.805115E+10 | 0.754387E+10 | 23615.69 | 22022.97 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 17803251.55 | 17803251.55 | 2090.56 | 20-JAN-14:00 | 2090.56 | 0.00 |
February | 0.00 | 0.00 | 7438073.88 | 7438073.88 | 1403.90 | 18-FEB-14:00 | 1403.90 | 0.00 |
March | 0.00 | 0.00 | 0.282438E+09 | 0.282438E+09 | 5974.36 | 14-MAR-13:00 | 5974.36 | 0.00 |
April | 0.00 | 0.00 | 85629944.30 | 85629943.25 | 3016.91 | 20-APR-13:00 | 3016.91 | 0.00 |
May | 0.00 | 0.00 | 0.168111E+10 | 0.166629E+10 | 7219.98 | 17-MAY-13:00 | 7219.98 | 0.00 |
June | 0.00 | 0.00 | 0.754927E+10 | 0.719639E+10 | 22084.88 | 27-JUN-06:02 | 22084.88 | 0.00 |
July | 0.00 | 0.00 | 0.807168E+10 | 0.756435E+10 | 23463.55 | 24-JUL-06:02 | 16022.42 | 0.00 |
August | 0.00 | 0.00 | 0.767160E+10 | 0.735338E+10 | 23186.60 | 03-AUG-06:02 | 17164.23 | 0.00 |
September | 0.00 | 0.00 | 0.555870E+10 | 0.549655E+10 | 22304.20 | 03-SEP-07:02 | 20047.95 | 0.00 |
October | 0.00 | 0.00 | 0.833854E+09 | 0.833690E+09 | 8153.56 | 11-OCT-14:00 | 8153.56 | 0.00 |
November | 0.00 | 0.00 | 0.172601E+09 | 0.172601E+09 | 4461.89 | 07-NOV-14:00 | 4461.89 | 0.00 |
December | 0.00 | 0.00 | 35984642.85 | 35984642.85 | 2732.91 | 02-DEC-15:00 | 2732.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.319681E+11 | 0.307125E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7438073.88 | 7438073.88 | 1403.90 | 1403.90 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.807168E+10 | 0.756435E+10 | 23463.55 | 22084.88 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 12338715.48 | 12338715.48 | 1753.13 | 20-JAN-14:00 | 1753.13 | 0.00 |
February | 0.00 | 0.00 | 4929649.46 | 4929649.46 | 1100.20 | 18-FEB-14:00 | 1100.20 | 0.00 |
March | 0.00 | 0.00 | 0.250148E+09 | 0.250148E+09 | 5719.04 | 14-MAR-13:00 | 5719.04 | 0.00 |
April | 0.00 | 0.00 | 60454111.16 | 60454111.16 | 2681.25 | 20-APR-13:00 | 2681.25 | 0.00 |
May | 0.00 | 0.00 | 0.154212E+10 | 0.153021E+10 | 7011.70 | 17-MAY-13:00 | 7011.70 | 0.00 |
June | 0.00 | 0.00 | 0.733305E+10 | 0.699670E+10 | 21846.66 | 25-JUN-07:02 | 21846.66 | 0.00 |
July | 0.00 | 0.00 | 0.785372E+10 | 0.736958E+10 | 23456.57 | 24-JUL-06:02 | 15993.37 | 0.00 |
August | 0.00 | 0.00 | 0.746645E+10 | 0.716255E+10 | 23135.40 | 03-AUG-06:02 | 17093.59 | 0.00 |
September | 0.00 | 0.00 | 0.538611E+10 | 0.532766E+10 | 21148.86 | 03-SEP-07:02 | 18964.43 | 0.00 |
October | 0.00 | 0.00 | 0.770507E+09 | 0.770390E+09 | 7987.15 | 11-OCT-14:00 | 7987.15 | 0.00 |
November | 0.00 | 0.00 | 0.146028E+09 | 0.146028E+09 | 4159.59 | 07-NOV-14:00 | 4159.59 | 0.00 |
December | 0.00 | 0.00 | 26602823.71 | 26602823.71 | 2434.50 | 02-DEC-15:00 | 2434.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.308525E+11 | 0.296576E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4929649.46 | 4929649.46 | 1100.20 | 1100.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.785372E+10 | 0.736958E+10 | 23456.57 | 21846.66 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 14006775.01 | 14006775.01 | 2451.47 | 20-JAN-14:00 | 2451.47 | 0.00 |
February | 0.00 | 0.00 | 4755583.77 | 4755583.77 | 1065.37 | 18-FEB-14:00 | 1065.37 | 0.00 |
March | 0.00 | 0.00 | 0.393378E+09 | 0.393378E+09 | 9751.16 | 14-MAR-13:00 | 9751.16 | 0.00 |
April | 0.00 | 0.00 | 76083692.84 | 76083692.84 | 4223.74 | 20-APR-13:00 | 4223.74 | 0.00 |
May | 0.00 | 0.00 | 0.240689E+10 | 0.238984E+10 | 12297.05 | 17-MAY-13:00 | 12297.05 | 0.00 |
June | 0.00 | 0.00 | 0.127955E+11 | 0.122050E+11 | 37114.25 | 26-JUN-07:02 | 37114.25 | 0.00 |
July | 0.00 | 0.00 | 0.135795E+11 | 0.127511E+11 | 39730.48 | 24-JUL-07:02 | 32408.40 | 0.00 |
August | 0.00 | 0.00 | 0.131949E+11 | 0.126442E+11 | 39183.37 | 03-AUG-07:02 | 30970.17 | 0.00 |
September | 0.00 | 0.00 | 0.923937E+10 | 0.913744E+10 | 37151.49 | 11-SEP-07:02 | 37151.49 | 0.00 |
October | 0.00 | 0.00 | 0.127200E+10 | 0.127171E+10 | 14292.16 | 11-OCT-14:10 | 14292.16 | 0.00 |
November | 0.00 | 0.00 | 0.218911E+09 | 0.218911E+09 | 6807.23 | 07-NOV-14:00 | 6807.23 | 0.00 |
December | 0.00 | 0.00 | 32711853.81 | 32711853.81 | 3750.62 | 02-DEC-15:00 | 3750.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.532280E+11 | 0.511391E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4755583.77 | 4755583.77 | 1065.37 | 1065.37 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.135795E+11 | 0.127511E+11 | 39730.48 | 37151.49 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6351898.64 | 6351898.64 | 1182.51 | 20-JAN-14:00 | 1182.51 | 0.00 |
February | 0.00 | 0.00 | 1449140.18 | 1449140.18 | 409.69 | 18-FEB-14:00 | 409.69 | 0.00 |
March | 0.00 | 0.00 | 0.195575E+09 | 0.195575E+09 | 4956.00 | 14-MAR-13:00 | 4956.00 | 0.00 |
April | 0.00 | 0.00 | 32032995.71 | 32032995.71 | 2064.40 | 20-APR-13:00 | 2064.40 | 0.00 |
May | 0.00 | 0.00 | 0.120670E+10 | 0.119879E+10 | 6316.97 | 17-MAY-13:00 | 6316.97 | 0.00 |
June | 0.00 | 0.00 | 0.656985E+10 | 0.627095E+10 | 18875.55 | 27-JUN-07:02 | 18875.55 | 0.00 |
July | 0.00 | 0.00 | 0.698015E+10 | 0.655900E+10 | 20582.68 | 24-JUL-07:02 | 16793.34 | 0.00 |
August | 0.00 | 0.00 | 0.678455E+10 | 0.650535E+10 | 19870.13 | 20-AUG-08:62 | 18489.70 | 0.00 |
September | 0.00 | 0.00 | 0.475243E+10 | 0.470144E+10 | 19242.17 | 11-SEP-07:02 | 19242.17 | 0.00 |
October | 0.00 | 0.00 | 0.645779E+09 | 0.645656E+09 | 7417.57 | 11-OCT-14:10 | 7417.57 | 0.00 |
November | 0.00 | 0.00 | 0.108713E+09 | 0.108713E+09 | 3499.37 | 07-NOV-14:00 | 3499.37 | 0.00 |
December | 0.00 | 0.00 | 14784463.33 | 14784463.33 | 1948.32 | 02-DEC-15:00 | 1948.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.272984E+11 | 0.262401E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1449140.18 | 1449140.18 | 409.69 | 409.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.698015E+10 | 0.655900E+10 | 20582.68 | 19242.17 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 5294680.22 | 5294680.22 | 1065.13 | 20-JAN-14:00 | 1065.13 | 0.00 |
February | 0.00 | 0.00 | 843535.90 | 843535.90 | 295.69 | 18-FEB-14:00 | 295.69 | 0.00 |
March | 0.00 | 0.00 | 0.183678E+09 | 0.183678E+09 | 4792.33 | 14-MAR-13:00 | 4792.33 | 0.00 |
April | 0.00 | 0.00 | 27195147.38 | 27195147.38 | 1949.23 | 20-APR-13:00 | 1949.23 | 0.00 |
May | 0.00 | 0.00 | 0.115195E+10 | 0.114499E+10 | 6213.08 | 17-MAY-13:00 | 6213.08 | 0.00 |
June | 0.00 | 0.00 | 0.648732E+10 | 0.619398E+10 | 18724.75 | 25-JUN-08:62 | 18724.75 | 0.00 |
July | 0.00 | 0.00 | 0.689887E+10 | 0.648523E+10 | 20459.00 | 24-JUL-07:02 | 16683.28 | 0.00 |
August | 0.00 | 0.00 | 0.670935E+10 | 0.643475E+10 | 19750.53 | 20-AUG-08:62 | 18370.55 | 0.00 |
September | 0.00 | 0.00 | 0.468895E+10 | 0.463905E+10 | 19059.58 | 11-SEP-07:02 | 19059.58 | 0.00 |
October | 0.00 | 0.00 | 0.619513E+09 | 0.619408E+09 | 7333.76 | 11-OCT-14:10 | 7333.76 | 0.00 |
November | 0.00 | 0.00 | 99963437.97 | 99963437.97 | 3365.53 | 07-NOV-14:00 | 3365.53 | 0.00 |
December | 0.00 | 0.00 | 12854455.77 | 12854455.77 | 1855.90 | 02-DEC-15:00 | 1855.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.268858E+11 | 0.258472E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 843535.90 | 843535.90 | 295.69 | 295.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.689887E+10 | 0.648523E+10 | 20459.00 | 19059.58 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2824663.15 | 2824663.15 | 765.18 | 20-JAN-14:00 | 765.18 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.157082E+09 | 0.157082E+09 | 4402.96 | 14-MAR-13:00 | 4402.96 | 0.00 |
April | 0.00 | 0.00 | 16578274.67 | 16578274.67 | 1678.79 | 20-APR-13:00 | 1678.79 | 0.00 |
May | 0.00 | 0.00 | 0.102416E+10 | 0.101925E+10 | 5971.76 | 17-MAY-13:00 | 5971.76 | 0.00 |
June | 0.00 | 0.00 | 0.632099E+10 | 0.604014E+10 | 18601.79 | 25-JUN-08:62 | 18601.79 | 0.00 |
July | 0.00 | 0.00 | 0.673632E+10 | 0.634106E+10 | 20362.23 | 24-JUL-07:02 | 16573.05 | 0.00 |
August | 0.00 | 0.00 | 0.657734E+10 | 0.631190E+10 | 19657.77 | 20-AUG-08:62 | 18261.15 | 0.00 |
September | 0.00 | 0.00 | 0.457053E+10 | 0.452284E+10 | 17525.08 | 11-SEP-07:02 | 17525.08 | 0.00 |
October | 0.00 | 0.00 | 0.560394E+09 | 0.560327E+09 | 7172.62 | 11-OCT-14:10 | 7172.62 | 0.00 |
November | 0.00 | 0.00 | 79912291.79 | 79912291.79 | 3061.76 | 07-NOV-14:00 | 3061.76 | 0.00 |
December | 0.00 | 0.00 | 8664631.08 | 8664631.08 | 1603.54 | 02-DEC-15:00 | 1603.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.260548E+11 | 0.250606E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.673632E+10 | 0.634106E+10 | 20362.23 | 18601.79 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 430699.18 | 430699.18 | 271.74 | 20-JAN-14:00 | 271.74 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.122802E+09 | 0.122802E+09 | 4069.10 | 14-MAR-13:00 | 4069.10 | 0.00 |
April | 0.00 | 0.00 | 9225384.97 | 9225384.97 | 1522.21 | 20-APR-13:00 | 1522.21 | 0.00 |
May | 0.00 | 0.00 | 0.895903E+09 | 0.893231E+09 | 5928.10 | 17-MAY-13:00 | 5928.10 | 0.00 |
June | 0.00 | 0.00 | 0.647056E+10 | 0.619706E+10 | 19661.76 | 25-JUN-08:62 | 19661.76 | 0.00 |
July | 0.00 | 0.00 | 0.688064E+10 | 0.650889E+10 | 20764.91 | 23-JUL-08:62 | 19721.86 | 0.00 |
August | 0.00 | 0.00 | 0.688293E+10 | 0.661103E+10 | 15521.29 | 20-AUG-08:62 | 13948.56 | 0.00 |
September | 0.00 | 0.00 | 0.473514E+10 | 0.468786E+10 | 11772.85 | 11-SEP-07:02 | 11772.85 | 0.00 |
October | 0.00 | 0.00 | 0.503762E+09 | 0.503740E+09 | 7247.28 | 11-OCT-14:10 | 7247.28 | 0.00 |
November | 0.00 | 0.00 | 56423470.48 | 56423470.48 | 2721.62 | 07-NOV-14:00 | 2721.62 | 0.00 |
December | 0.00 | 0.00 | 4236164.98 | 4236164.98 | 1231.30 | 02-DEC-15:00 | 1231.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.265620E+11 | 0.255949E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.688293E+10 | 0.661103E+10 | 20764.91 | 19721.86 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.218401E+10 | 0.48 | 2712.05 | 02-JAN-08:61 | 1.08 |
February | 0.202417E+10 | 0.49 | 2712.05 | 01-FEB-08:61 | 1.08 |
March | 0.214387E+10 | 0.47 | 2712.05 | 01-MAR-08:61 | 1.08 |
April | 0.202447E+10 | 0.46 | 2712.05 | 02-APR-07:01 | 1.08 |
May | 0.197263E+10 | 0.44 | 2712.05 | 01-MAY-07:01 | 1.08 |
June | 0.193525E+10 | 0.45 | 2712.05 | 14-JUN-07:02 | 1.08 |
July | 0.198216E+10 | 0.44 | 2712.05 | 16-JUL-07:02 | 1.08 |
August | 0.198904E+10 | 0.44 | 2712.05 | 03-AUG-07:02 | 1.07 |
September | 0.191326E+10 | 0.44 | 2579.75 | 13-SEP-07:02 | 1.05 |
October | 0.205240E+10 | 0.46 | 2712.05 | 24-OCT-07:01 | 1.08 |
November | 0.203409E+10 | 0.46 | 2712.05 | 01-NOV-07:01 | 1.08 |
December | 0.227915E+10 | 0.49 | 2712.05 | 01-DEC-08:61 | 1.08 |
Annual Sum or Average | 0.245345E+11 | 0.46 | |||
Minimum of Months | 0.191326E+10 | 0.44 | 2579.75 | 1.05 | |
Maximum of Months | 0.227915E+10 | 0.49 | 2712.05 | 1.08 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.892278E+09 | 0.40 | 1512.57 | 05-JAN-08:61 | 1.12 |
February | 0.837979E+09 | 0.41 | 1512.57 | 01-FEB-08:61 | 1.12 |
March | 0.947501E+09 | 0.41 | 1512.57 | 05-MAR-08:61 | 1.12 |
April | 0.897488E+09 | 0.42 | 1512.57 | 03-APR-07:01 | 1.11 |
May | 0.103668E+10 | 0.45 | 706.48 | 02-MAY-08:10 | 0.75 |
June | 0.968446E+09 | 0.44 | 1512.57 | 14-JUN-07:02 | 1.12 |
July | 0.983711E+09 | 0.44 | 1512.57 | 16-JUL-07:02 | 1.12 |
August | 0.984661E+09 | 0.44 | 1512.57 | 03-AUG-07:02 | 1.11 |
September | 0.966248E+09 | 0.44 | 1512.57 | 13-SEP-07:02 | 1.11 |
October | 0.101407E+10 | 0.44 | 1512.57 | 31-OCT-07:01 | 1.12 |
November | 0.883001E+09 | 0.42 | 1512.57 | 01-NOV-07:01 | 1.12 |
December | 0.935155E+09 | 0.41 | 1512.57 | 08-DEC-08:61 | 1.12 |
Annual Sum or Average | 0.113472E+11 | 0.43 | |||
Minimum of Months | 0.837979E+09 | 0.40 | 706.48 | 0.75 | |
Maximum of Months | 0.103668E+10 | 0.45 | 1512.57 | 1.12 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.958041E+09 | 0.37 | 1526.98 | 05-JAN-07:01 | 1.09 |
February | 0.884785E+09 | 0.38 | 1526.98 | 02-FEB-07:01 | 1.08 |
March | 0.958554E+09 | 0.38 | 1526.98 | 05-MAR-08:61 | 1.08 |
April | 0.895730E+09 | 0.36 | 1526.98 | 03-APR-06:01 | 1.08 |
May | 0.893834E+09 | 0.36 | 794.30 | 03-MAY-07:06 | 0.77 |
June | 0.876502E+09 | 0.36 | 1526.98 | 14-JUN-06:02 | 1.08 |
July | 0.883519E+09 | 0.35 | 1526.98 | 16-JUL-07:02 | 1.08 |
August | 0.905737E+09 | 0.36 | 1526.98 | 03-AUG-06:02 | 1.07 |
September | 0.858176E+09 | 0.35 | 1511.28 | 03-SEP-07:02 | 1.07 |
October | 0.915830E+09 | 0.36 | 1526.98 | 31-OCT-06:01 | 1.08 |
November | 0.904351E+09 | 0.37 | 1526.98 | 01-NOV-06:01 | 1.08 |
December | 0.990309E+09 | 0.38 | 1526.98 | 08-DEC-07:01 | 1.09 |
Annual Sum or Average | 0.109254E+11 | 0.37 | |||
Minimum of Months | 0.858176E+09 | 0.35 | 794.30 | 0.77 | |
Maximum of Months | 0.990309E+09 | 0.38 | 1526.98 | 1.09 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.957639E+09 | 0.37 | 1517.01 | 05-JAN-07:01 | 1.09 |
February | 0.884349E+09 | 0.38 | 1517.01 | 02-FEB-07:01 | 1.08 |
March | 0.956370E+09 | 0.38 | 1517.01 | 05-MAR-08:61 | 1.08 |
April | 0.893561E+09 | 0.37 | 1517.01 | 03-APR-06:01 | 1.08 |
May | 0.888356E+09 | 0.36 | 885.82 | 02-MAY-06:03 | 0.83 |
June | 0.871365E+09 | 0.36 | 1517.01 | 14-JUN-06:02 | 1.08 |
July | 0.878323E+09 | 0.35 | 1517.01 | 16-JUL-07:02 | 1.08 |
August | 0.900185E+09 | 0.36 | 1517.01 | 03-AUG-06:02 | 1.07 |
September | 0.852707E+09 | 0.35 | 1517.01 | 03-SEP-07:02 | 1.07 |
October | 0.911699E+09 | 0.36 | 1517.01 | 30-OCT-06:01 | 1.08 |
November | 0.902627E+09 | 0.37 | 1517.01 | 01-NOV-06:01 | 1.08 |
December | 0.989863E+09 | 0.38 | 1517.01 | 08-DEC-07:01 | 1.09 |
Annual Sum or Average | 0.108870E+11 | 0.37 | |||
Minimum of Months | 0.852707E+09 | 0.35 | 885.82 | 0.83 | |
Maximum of Months | 0.989863E+09 | 0.38 | 1517.01 | 1.09 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.965006E+09 | 0.38 | 1516.89 | 01-JAN-08:62 | 1.08 |
February | 0.891922E+09 | 0.38 | 1516.89 | 01-FEB-07:02 | 1.08 |
March | 0.962197E+09 | 0.38 | 1516.89 | 05-MAR-08:61 | 1.08 |
April | 0.898755E+09 | 0.37 | 1516.89 | 02-APR-07:01 | 1.08 |
May | 0.888828E+09 | 0.36 | 999.99 | 02-MAY-06:03 | 0.89 |
June | 0.870243E+09 | 0.36 | 1516.89 | 25-JUN-07:02 | 1.08 |
July | 0.877298E+09 | 0.35 | 1516.89 | 16-JUL-07:02 | 1.08 |
August | 0.899245E+09 | 0.36 | 1516.89 | 20-AUG-07:02 | 1.07 |
September | 0.852459E+09 | 0.35 | 1423.76 | 03-SEP-07:02 | 1.04 |
October | 0.914099E+09 | 0.36 | 1516.89 | 30-OCT-06:01 | 1.08 |
November | 0.908125E+09 | 0.37 | 1516.89 | 01-NOV-06:01 | 1.08 |
December | 0.997787E+09 | 0.38 | 1516.89 | 08-DEC-07:01 | 1.09 |
Annual Sum or Average | 0.109260E+11 | 0.37 | |||
Minimum of Months | 0.852459E+09 | 0.35 | 999.99 | 0.89 | |
Maximum of Months | 0.997787E+09 | 0.38 | 1516.89 | 1.09 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154053E+10 | 0.35 | 2551.93 | 01-JAN-09:01 | 1.08 |
February | 0.142997E+10 | 0.36 | 2551.93 | 01-FEB-08:61 | 1.08 |
March | 0.152789E+10 | 0.35 | 2551.93 | 01-MAR-08:61 | 1.08 |
April | 0.142108E+10 | 0.34 | 2551.93 | 02-APR-08:61 | 1.08 |
May | 0.138322E+10 | 0.33 | 2551.93 | 01-MAY-07:01 | 1.08 |
June | 0.136365E+10 | 0.33 | 2551.93 | 14-JUN-07:02 | 1.08 |
July | 0.137027E+10 | 0.32 | 2551.93 | 16-JUL-08:62 | 1.08 |
August | 0.140663E+10 | 0.33 | 2551.93 | 03-AUG-07:02 | 1.07 |
September | 0.132562E+10 | 0.33 | 2551.93 | 11-SEP-07:02 | 1.08 |
October | 0.143617E+10 | 0.34 | 2551.93 | 24-OCT-07:01 | 1.08 |
November | 0.144257E+10 | 0.35 | 2551.93 | 01-NOV-07:01 | 1.08 |
December | 0.160045E+10 | 0.36 | 2551.93 | 01-DEC-08:61 | 1.08 |
Annual Sum or Average | 0.172481E+11 | 0.34 | |||
Minimum of Months | 0.132562E+10 | 0.32 | 2551.93 | 1.07 | |
Maximum of Months | 0.160045E+10 | 0.36 | 2551.93 | 1.08 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.827840E+09 | 0.37 | 1367.58 | 01-JAN-09:01 | 1.12 |
February | 0.768909E+09 | 0.37 | 1367.58 | 01-FEB-08:61 | 1.12 |
March | 0.821156E+09 | 0.37 | 1367.58 | 01-MAR-08:61 | 1.12 |
April | 0.763700E+09 | 0.35 | 1367.58 | 02-APR-08:61 | 1.12 |
May | 0.741474E+09 | 0.34 | 1367.58 | 01-MAY-07:01 | 1.12 |
June | 0.730700E+09 | 0.35 | 1367.58 | 14-JUN-07:02 | 1.12 |
July | 0.734201E+09 | 0.34 | 1367.58 | 16-JUL-08:62 | 1.12 |
August | 0.753669E+09 | 0.35 | 1367.58 | 20-AUG-08:62 | 1.11 |
September | 0.710312E+09 | 0.34 | 1367.58 | 11-SEP-07:02 | 1.12 |
October | 0.770636E+09 | 0.35 | 1367.58 | 24-OCT-07:01 | 1.12 |
November | 0.774488E+09 | 0.36 | 1367.58 | 01-NOV-07:01 | 1.12 |
December | 0.860587E+09 | 0.37 | 1367.58 | 01-DEC-08:61 | 1.12 |
Annual Sum or Average | 0.925767E+10 | 0.35 | |||
Minimum of Months | 0.710312E+09 | 0.34 | 1367.58 | 1.11 | |
Maximum of Months | 0.860587E+09 | 0.37 | 1367.58 | 1.12 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.826486E+09 | 0.37 | 1359.49 | 01-JAN-09:01 | 1.12 |
February | 0.767568E+09 | 0.37 | 1359.49 | 01-FEB-08:61 | 1.12 |
March | 0.818781E+09 | 0.37 | 1359.49 | 01-MAR-08:61 | 1.12 |
April | 0.761588E+09 | 0.36 | 1359.49 | 02-APR-08:61 | 1.12 |
May | 0.737389E+09 | 0.34 | 1359.49 | 01-MAY-07:01 | 1.12 |
June | 0.726282E+09 | 0.35 | 1359.49 | 14-JUN-07:02 | 1.12 |
July | 0.729746E+09 | 0.34 | 1359.49 | 16-JUL-08:62 | 1.12 |
August | 0.749106E+09 | 0.35 | 1359.49 | 20-AUG-08:62 | 1.11 |
September | 0.706114E+09 | 0.34 | 1353.64 | 11-SEP-07:02 | 1.12 |
October | 0.767221E+09 | 0.35 | 1359.49 | 24-OCT-07:01 | 1.12 |
November | 0.772402E+09 | 0.36 | 1359.49 | 01-NOV-07:01 | 1.12 |
December | 0.858739E+09 | 0.37 | 1359.49 | 01-DEC-08:61 | 1.12 |
Annual Sum or Average | 0.922142E+10 | 0.35 | |||
Minimum of Months | 0.706114E+09 | 0.34 | 1353.64 | 1.11 | |
Maximum of Months | 0.858739E+09 | 0.37 | 1359.49 | 1.12 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.834168E+09 | 0.37 | 1353.51 | 01-JAN-09:01 | 1.12 |
February | 0.775184E+09 | 0.38 | 1353.51 | 01-FEB-08:61 | 1.12 |
March | 0.824065E+09 | 0.37 | 1353.51 | 01-MAR-08:61 | 1.12 |
April | 0.766414E+09 | 0.36 | 1353.51 | 02-APR-08:61 | 1.12 |
May | 0.735160E+09 | 0.34 | 1353.51 | 01-MAY-07:01 | 1.12 |
June | 0.722539E+09 | 0.35 | 1353.51 | 25-JUN-08:62 | 1.12 |
July | 0.726088E+09 | 0.34 | 1353.51 | 16-JUL-08:62 | 1.12 |
August | 0.745357E+09 | 0.35 | 1353.51 | 20-AUG-08:62 | 1.11 |
September | 0.703000E+09 | 0.34 | 1224.22 | 11-SEP-07:02 | 1.07 |
October | 0.767583E+09 | 0.35 | 1353.51 | 23-OCT-07:01 | 1.12 |
November | 0.776729E+09 | 0.36 | 1353.51 | 01-NOV-07:01 | 1.12 |
December | 0.865752E+09 | 0.38 | 1353.51 | 01-DEC-08:61 | 1.12 |
Annual Sum or Average | 0.924204E+10 | 0.36 | |||
Minimum of Months | 0.703000E+09 | 0.34 | 1224.22 | 1.07 | |
Maximum of Months | 0.865752E+09 | 0.38 | 1353.51 | 1.12 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.913370E+09 | 0.39 | 1423.51 | 01-JAN-09:01 | 1.12 |
February | 0.857576E+09 | 0.43 | 1423.51 | 01-FEB-08:61 | 1.12 |
March | 0.899236E+09 | 0.39 | 1423.51 | 01-MAR-08:61 | 1.12 |
April | 0.833197E+09 | 0.37 | 1423.51 | 01-APR-07:01 | 1.12 |
May | 0.777168E+09 | 0.34 | 1423.51 | 01-MAY-07:01 | 1.12 |
June | 0.759550E+09 | 0.35 | 1423.51 | 25-JUN-08:62 | 1.12 |
July | 0.764224E+09 | 0.34 | 1423.51 | 16-JUL-08:62 | 1.12 |
August | 0.784327E+09 | 0.35 | 994.19 | 20-AUG-08:62 | 0.93 |
September | 0.740190E+09 | 0.34 | 996.74 | 22-SEP-07:03 | 0.94 |
October | 0.820639E+09 | 0.35 | 1423.51 | 23-OCT-07:01 | 1.12 |
November | 0.839445E+09 | 0.37 | 1423.51 | 01-NOV-07:01 | 1.12 |
December | 0.955759E+09 | 0.43 | 1423.51 | 01-DEC-08:61 | 1.12 |
Annual Sum or Average | 0.994468E+10 | 0.37 | |||
Minimum of Months | 0.740190E+09 | 0.34 | 994.19 | 0.93 | |
Maximum of Months | 0.955759E+09 | 0.43 | 1423.51 | 1.12 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.219084E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.202622E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.227300E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.206470E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.283492E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.650647E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.689385E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.662046E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.508639E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.248115E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.212246E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.229520E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.433957E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.202622E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.689385E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.906118E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.842345E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.104593E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.941320E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.164738E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.362990E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.386722E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.370392E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.286919E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.129046E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.949851E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.955467E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.226491E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.842345E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.386722E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.964542E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.887253E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.103556E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.923280E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.135364E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.291196E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.303744E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.293466E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.230327E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.113521E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.954270E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.100187E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.194429E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.887253E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.303744E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.962457E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.886388E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.102957E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.916815E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.133349E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.290588E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.303496E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.292906E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.229573E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.112534E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.948091E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.999614E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.193674E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.886388E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.303496E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.968361E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.893282E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.102723E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.915262E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.129956E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.285494E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.298432E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.288181E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.225638E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.111206E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.946819E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.100503E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.191451E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.893282E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.298432E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.154437E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.143130E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.163000E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.144195E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.202535E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.481406E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.499436E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.489169E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.372091E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.176120E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.150072E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.160941E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.313653E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.143130E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.499436E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.829586E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.769314E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.871984E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.772512E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.106397E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.250456E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.259920E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.254741E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.194318E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.935615E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.803383E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.864635E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.165053E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.769314E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.259920E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.827945E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.767805E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.866672E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.769087E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.104604E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.247950E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.257444E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.252417E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.192349E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.925629E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.799038E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.862262E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.163661E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.767805E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.257444E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.834951E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.775184E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.865407E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.771008E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.101154E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.243591E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.253200E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.248889E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.189228E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.911255E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.798154E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.868135E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.161847E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.771008E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.253200E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.913491E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.857576E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.932121E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.835763E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.102166E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.252094E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.261628E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.260882E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.197287E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.950286E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.854708E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.956934E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.170415E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.835763E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.261628E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.218401E+10 | 24828016.62 | 0.830180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202417E+10 | 7264502.69 | 0.932256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.214387E+10 | 0.488296E+09 | 0.643899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202447E+10 | 0.145398E+09 | 0.455277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197263E+10 | 0.320669E+10 | 0.167355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.193525E+10 | 0.168553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.198216E+10 | 0.182197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.198904E+10 | 0.173922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.191326E+10 | 0.121059E+11 | 20646893.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205240E+10 | 0.165352E+10 | 0.322569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.203409E+10 | 0.331092E+09 | 0.507427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227915E+10 | 58006141.54 | 0.116371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245345E+11 | 0.704883E+11 | 0.487412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.191326E+10 | 7264502.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.227915E+10 | 0.182197E+11 | 0.116371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.892278E+09 | 51736789.62 | 0.200767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.837979E+09 | 16157100.42 | 0.244993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.947501E+09 | 0.380669E+09 | 0.159058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.897488E+09 | 0.163662E+09 | 0.999460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103668E+10 | 0.231236E+10 | 11863468.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.968446E+09 | 0.980709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.983711E+09 | 0.107103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.984661E+09 | 0.101661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.966248E+09 | 0.722627E+10 | 426699.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101407E+10 | 0.108734E+10 | 0.950787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.883001E+09 | 0.258423E+09 | 0.123065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.935155E+09 | 75927396.34 | 0.333069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113472E+11 | 0.422561E+11 | 0.125720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.837979E+09 | 16157100.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103668E+10 | 0.107103E+11 | 0.333069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.958041E+09 | 24028503.27 | 0.277929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.884785E+09 | 9042512.31 | 0.316564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.958554E+09 | 0.297361E+09 | 0.213878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.895730E+09 | 0.101756E+09 | 0.143187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.893834E+09 | 0.173937E+10 | 41197379.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.876502E+09 | 0.754562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.883519E+09 | 0.805115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.905737E+09 | 0.766307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.858176E+09 | 0.556141E+10 | 1659496.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.915830E+09 | 0.856427E+09 | 0.119608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.904351E+09 | 0.190155E+09 | 0.175520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.990309E+09 | 42809259.70 | 0.415453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109254E+11 | 0.320822E+11 | 0.166642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.858176E+09 | 9042512.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.990309E+09 | 0.805115E+10 | 0.415453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.957639E+09 | 17803251.55 | 0.298530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.884349E+09 | 7438073.88 | 0.335045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.956370E+09 | 0.282438E+09 | 0.228116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.893561E+09 | 85629944.30 | 0.156300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.888356E+09 | 0.168111E+10 | 54538986.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.871365E+09 | 0.754927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.878323E+09 | 0.807168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.900185E+09 | 0.767160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.852707E+09 | 0.555870E+10 | 2319799.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.911699E+09 | 0.833854E+09 | 0.125964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.902627E+09 | 0.172601E+09 | 0.190354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.989863E+09 | 35984642.85 | 0.435990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108870E+11 | 0.319681E+11 | 0.177599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.852707E+09 | 7438073.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.989863E+09 | 0.807168E+10 | 0.435990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.965006E+09 | 12338715.48 | 0.326468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.891922E+09 | 4929649.46 | 0.363731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.962197E+09 | 0.250148E+09 | 0.250272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.898755E+09 | 60454111.16 | 0.176062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.888828E+09 | 0.154212E+10 | 74887767.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.870243E+09 | 0.733305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.877298E+09 | 0.785372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.899245E+09 | 0.746645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.852459E+09 | 0.538611E+10 | 4245241.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.914099E+09 | 0.770507E+09 | 0.135240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.908125E+09 | 0.146028E+09 | 0.211262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.997787E+09 | 26602823.71 | 0.466018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109260E+11 | 0.308525E+11 | 0.193697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.852459E+09 | 4929649.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.997787E+09 | 0.785372E+10 | 0.466018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154053E+10 | 14006775.01 | 0.694546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142997E+10 | 4755583.77 | 0.765340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152789E+10 | 0.393378E+09 | 0.529761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142108E+10 | 76083692.84 | 0.384777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138322E+10 | 0.240689E+10 | 0.202974E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136365E+10 | 0.127955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137027E+10 | 0.135795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140663E+10 | 0.131949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132562E+10 | 0.923937E+10 | 17010806.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143617E+10 | 0.127200E+10 | 0.285459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144257E+10 | 0.218911E+09 | 0.469021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160045E+10 | 32711853.81 | 0.958265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172481E+11 | 0.532280E+11 | 0.410917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132562E+10 | 4755583.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160045E+10 | 0.135795E+11 | 0.958265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.827840E+09 | 6351898.64 | 0.361441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.768909E+09 | 1449140.18 | 0.398599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.821156E+09 | 0.195575E+09 | 0.278020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.763700E+09 | 32032995.71 | 0.203523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.741474E+09 | 0.120670E+10 | 0.110753E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.730700E+09 | 0.656985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.734201E+09 | 0.698015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.753669E+09 | 0.678455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.710312E+09 | 0.475243E+10 | 7948517.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.770636E+09 | 0.645779E+09 | 0.148776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.774488E+09 | 0.108713E+09 | 0.243628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.860587E+09 | 14784463.33 | 0.497827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.925767E+10 | 0.272984E+11 | 0.214368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.710312E+09 | 1449140.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.860587E+09 | 0.698015E+10 | 0.497827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.826486E+09 | 5294680.22 | 0.373123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.767568E+09 | 843535.90 | 0.408878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.818781E+09 | 0.183678E+09 | 0.286106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.761588E+09 | 27195147.38 | 0.211634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.737389E+09 | 0.115195E+10 | 0.121543E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.726282E+09 | 0.648732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.729746E+09 | 0.689887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.749106E+09 | 0.670935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.706114E+09 | 0.468895E+10 | 9251312.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.767221E+09 | 0.619513E+09 | 0.152416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.772402E+09 | 99963437.97 | 0.251905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.858739E+09 | 12854455.77 | 0.507819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.922142E+10 | 0.268858E+11 | 0.220496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.706114E+09 | 843535.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.858739E+09 | 0.689887E+10 | 0.507819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.834168E+09 | 2824663.15 | 0.413065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.775184E+09 | 0.00 | 0.447404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.824065E+09 | 0.157082E+09 | 0.317502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.766414E+09 | 16578274.67 | 0.240822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.735160E+09 | 0.102416E+10 | 0.158564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.722539E+09 | 0.632099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.726088E+09 | 0.673632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.745357E+09 | 0.657734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.703000E+09 | 0.457053E+10 | 13592372.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.767583E+09 | 0.560394E+09 | 0.165436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.776729E+09 | 79912291.79 | 0.279183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.865752E+09 | 8664631.08 | 0.544759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.924204E+10 | 0.260548E+11 | 0.242539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.703000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.865752E+09 | 0.673632E+10 | 0.544759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.913370E+09 | 430699.18 | 0.566117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.857576E+09 | 0.00 | 0.614233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.899236E+09 | 0.122802E+09 | 0.450434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.833197E+09 | 9225384.97 | 0.352196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.777168E+09 | 0.895903E+09 | 0.314929E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.759550E+09 | 0.647056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.764224E+09 | 0.688064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.784327E+09 | 0.688293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.740190E+09 | 0.473514E+10 | 42290429.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.820639E+09 | 0.503762E+09 | 0.223526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.839445E+09 | 56423470.48 | 0.376538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.955759E+09 | 4236164.98 | 0.721759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.994468E+10 | 0.265620E+11 | 0.334052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.740190E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.955759E+09 | 0.688293E+10 | 0.721759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.218401E+10 | 0.00 | 0.00 | 0.00 | 6830967.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202417E+10 | 0.00 | 0.00 | 0.00 | 2045854.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.214387E+10 | 0.00 | 0.00 | 0.00 | 0.129135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202447E+10 | 0.00 | 0.00 | 0.00 | 40225415.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197263E+10 | 0.00 | 0.00 | 0.00 | 0.862291E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.193525E+10 | 0.00 | 0.00 | 0.00 | 0.457122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.198216E+10 | 0.00 | 0.00 | 0.00 | 0.491169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.198904E+10 | 0.00 | 0.00 | 0.00 | 0.463143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.191326E+10 | 0.00 | 0.00 | 0.00 | 0.317312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205240E+10 | 0.00 | 0.00 | 0.00 | 0.428750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.203409E+10 | 0.00 | 0.00 | 0.00 | 88371779.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227915E+10 | 0.00 | 0.00 | 0.00 | 16047254.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245345E+11 | 0.00 | 0.00 | 0.00 | 0.188612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.191326E+10 | 0.00 | 0.00 | 0.00 | 2045854.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.227915E+10 | 0.00 | 0.00 | 0.00 | 0.491169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.892278E+09 | 0.00 | 0.00 | 0.00 | 13839737.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.837979E+09 | 0.00 | 0.00 | 0.00 | 4366120.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.947501E+09 | 0.00 | 0.00 | 0.00 | 98425856.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.897488E+09 | 0.00 | 0.00 | 0.00 | 43832281.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103668E+10 | 0.00 | 0.00 | 0.00 | 0.610697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.968446E+09 | 0.00 | 0.00 | 0.00 | 0.266146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.983711E+09 | 0.00 | 0.00 | 0.00 | 0.288351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.984661E+09 | 0.00 | 0.00 | 0.00 | 0.271926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.966248E+09 | 0.00 | 0.00 | 0.00 | 0.190294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101407E+10 | 0.00 | 0.00 | 0.00 | 0.276393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.883001E+09 | 0.00 | 0.00 | 0.00 | 66850400.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.935155E+09 | 0.00 | 0.00 | 0.00 | 20312486.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113472E+11 | 0.00 | 0.00 | 0.00 | 0.113019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.837979E+09 | 0.00 | 0.00 | 0.00 | 4366120.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103668E+10 | 0.00 | 0.00 | 0.00 | 0.288351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.958041E+09 | 0.00 | 0.00 | 0.00 | 6501078.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.884785E+09 | 0.00 | 0.00 | 0.00 | 2468607.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.958554E+09 | 0.00 | 0.00 | 0.00 | 77005260.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.895730E+09 | 0.00 | 0.00 | 0.00 | 27550481.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.893834E+09 | 0.00 | 0.00 | 0.00 | 0.459808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.876502E+09 | 0.00 | 0.00 | 0.00 | 0.203546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.883519E+09 | 0.00 | 0.00 | 0.00 | 0.215392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.905737E+09 | 0.00 | 0.00 | 0.00 | 0.202892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.858176E+09 | 0.00 | 0.00 | 0.00 | 0.144509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.915830E+09 | 0.00 | 0.00 | 0.00 | 0.219375E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.904351E+09 | 0.00 | 0.00 | 0.00 | 49918977.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.990309E+09 | 0.00 | 0.00 | 0.00 | 11562296.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109254E+11 | 0.00 | 0.00 | 0.00 | 0.851758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.858176E+09 | 0.00 | 0.00 | 0.00 | 2468607.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.990309E+09 | 0.00 | 0.00 | 0.00 | 0.215392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.957639E+09 | 0.00 | 0.00 | 0.00 | 4817832.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.884349E+09 | 0.00 | 0.00 | 0.00 | 2038565.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.956370E+09 | 0.00 | 0.00 | 0.00 | 73199956.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.893561E+09 | 0.00 | 0.00 | 0.00 | 23253668.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.888356E+09 | 0.00 | 0.00 | 0.00 | 0.445133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.871365E+09 | 0.00 | 0.00 | 0.00 | 0.203452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.878323E+09 | 0.00 | 0.00 | 0.00 | 0.215664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.900185E+09 | 0.00 | 0.00 | 0.00 | 0.202887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.852707E+09 | 0.00 | 0.00 | 0.00 | 0.144303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.911699E+09 | 0.00 | 0.00 | 0.00 | 0.213636E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.902627E+09 | 0.00 | 0.00 | 0.00 | 45464685.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.989863E+09 | 0.00 | 0.00 | 0.00 | 9750611.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108870E+11 | 0.00 | 0.00 | 0.00 | 0.848035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.852707E+09 | 0.00 | 0.00 | 0.00 | 2038565.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.989863E+09 | 0.00 | 0.00 | 0.00 | 0.215664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.965006E+09 | 0.00 | 0.00 | 0.00 | 3354800.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.891922E+09 | 0.00 | 0.00 | 0.00 | 1360393.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.962197E+09 | 0.00 | 0.00 | 0.00 | 65036232.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.898755E+09 | 0.00 | 0.00 | 0.00 | 16507380.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.888828E+09 | 0.00 | 0.00 | 0.00 | 0.410728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.870243E+09 | 0.00 | 0.00 | 0.00 | 0.198470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.877298E+09 | 0.00 | 0.00 | 0.00 | 0.210702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.899245E+09 | 0.00 | 0.00 | 0.00 | 0.198256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.852459E+09 | 0.00 | 0.00 | 0.00 | 0.140393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.914099E+09 | 0.00 | 0.00 | 0.00 | 0.197958E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.908125E+09 | 0.00 | 0.00 | 0.00 | 38693814.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.997787E+09 | 0.00 | 0.00 | 0.00 | 7247787.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109260E+11 | 0.00 | 0.00 | 0.00 | 0.821909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.852459E+09 | 0.00 | 0.00 | 0.00 | 1360393.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.997787E+09 | 0.00 | 0.00 | 0.00 | 0.210702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.154053E+10 | 0.00 | 0.00 | 0.00 | 3839880.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142997E+10 | 0.00 | 0.00 | 0.00 | 1325159.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152789E+10 | 0.00 | 0.00 | 0.00 | 0.102108E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142108E+10 | 0.00 | 0.00 | 0.00 | 20872755.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138322E+10 | 0.00 | 0.00 | 0.00 | 0.642129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136365E+10 | 0.00 | 0.00 | 0.00 | 0.345041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137027E+10 | 0.00 | 0.00 | 0.00 | 0.362409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140663E+10 | 0.00 | 0.00 | 0.00 | 0.348506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132562E+10 | 0.00 | 0.00 | 0.00 | 0.239529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143617E+10 | 0.00 | 0.00 | 0.00 | 0.325033E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144257E+10 | 0.00 | 0.00 | 0.00 | 58148448.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160045E+10 | 0.00 | 0.00 | 0.00 | 8956664.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172481E+11 | 0.00 | 0.00 | 0.00 | 0.141173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132562E+10 | 0.00 | 0.00 | 0.00 | 1325159.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160045E+10 | 0.00 | 0.00 | 0.00 | 0.362409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.827840E+09 | 0.00 | 0.00 | 0.00 | 1745927.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.768909E+09 | 0.00 | 0.00 | 0.00 | 405391.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.821156E+09 | 0.00 | 0.00 | 0.00 | 50827972.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.763700E+09 | 0.00 | 0.00 | 0.00 | 8811633.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.741474E+09 | 0.00 | 0.00 | 0.00 | 0.322491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.730700E+09 | 0.00 | 0.00 | 0.00 | 0.177386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.734201E+09 | 0.00 | 0.00 | 0.00 | 0.186499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.753669E+09 | 0.00 | 0.00 | 0.00 | 0.179374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.710312E+09 | 0.00 | 0.00 | 0.00 | 0.123287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.770636E+09 | 0.00 | 0.00 | 0.00 | 0.164978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.774488E+09 | 0.00 | 0.00 | 0.00 | 28895316.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.860587E+09 | 0.00 | 0.00 | 0.00 | 4047514.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.925767E+10 | 0.00 | 0.00 | 0.00 | 0.724767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.710312E+09 | 0.00 | 0.00 | 0.00 | 405391.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.860587E+09 | 0.00 | 0.00 | 0.00 | 0.186499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.826486E+09 | 0.00 | 0.00 | 0.00 | 1459229.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.767568E+09 | 0.00 | 0.00 | 0.00 | 236643.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.818781E+09 | 0.00 | 0.00 | 0.00 | 47891014.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.761588E+09 | 0.00 | 0.00 | 0.00 | 7498352.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.737389E+09 | 0.00 | 0.00 | 0.00 | 0.308654E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.726282E+09 | 0.00 | 0.00 | 0.00 | 0.175322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.729746E+09 | 0.00 | 0.00 | 0.00 | 0.184469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.749106E+09 | 0.00 | 0.00 | 0.00 | 0.177506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.706114E+09 | 0.00 | 0.00 | 0.00 | 0.121738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.767221E+09 | 0.00 | 0.00 | 0.00 | 0.158408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.772402E+09 | 0.00 | 0.00 | 0.00 | 26636831.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.858739E+09 | 0.00 | 0.00 | 0.00 | 3522962.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.922142E+10 | 0.00 | 0.00 | 0.00 | 0.714465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.706114E+09 | 0.00 | 0.00 | 0.00 | 236643.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.858739E+09 | 0.00 | 0.00 | 0.00 | 0.184469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.834168E+09 | 0.00 | 0.00 | 0.00 | 783123.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.775184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.824065E+09 | 0.00 | 0.00 | 0.00 | 41341908.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.766414E+09 | 0.00 | 0.00 | 0.00 | 4594151.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.735160E+09 | 0.00 | 0.00 | 0.00 | 0.276381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.722539E+09 | 0.00 | 0.00 | 0.00 | 0.171337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.726088E+09 | 0.00 | 0.00 | 0.00 | 0.180591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.745357E+09 | 0.00 | 0.00 | 0.00 | 0.174354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.703000E+09 | 0.00 | 0.00 | 0.00 | 0.118928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.767583E+09 | 0.00 | 0.00 | 0.00 | 0.143671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.776729E+09 | 0.00 | 0.00 | 0.00 | 21424768.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.865752E+09 | 0.00 | 0.00 | 0.00 | 2383007.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.924204E+10 | 0.00 | 0.00 | 0.00 | 0.694269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.703000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.865752E+09 | 0.00 | 0.00 | 0.00 | 0.180591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.913370E+09 | 0.00 | 0.00 | 0.00 | 120902.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.857576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.899236E+09 | 0.00 | 0.00 | 0.00 | 32884272.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.833197E+09 | 0.00 | 0.00 | 0.00 | 2565632.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.777168E+09 | 0.00 | 0.00 | 0.00 | 0.244492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.759550E+09 | 0.00 | 0.00 | 0.00 | 0.176139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.764224E+09 | 0.00 | 0.00 | 0.00 | 0.185206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.784327E+09 | 0.00 | 0.00 | 0.00 | 0.182449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.740190E+09 | 0.00 | 0.00 | 0.00 | 0.123268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.820639E+09 | 0.00 | 0.00 | 0.00 | 0.129646E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.839445E+09 | 0.00 | 0.00 | 0.00 | 15263263.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.955759E+09 | 0.00 | 0.00 | 0.00 | 1174770.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.994468E+10 | 0.00 | 0.00 | 0.00 | 0.709677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.740190E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.955759E+09 | 0.00 | 0.00 | 0.00 | 0.185206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.990168E+10 | 0.00 | 0.00 | 481127.95 | 0.00 | 0.375357E+10 | 0.491560E+09 | 0.00 | 0.55 |
February | 0.798049E+10 | 0.00 | 0.00 | 343355.34 | 0.00 | 0.489578E+10 | 0.363989E+09 | 0.00 | 0.54 |
March | 0.670000E+10 | 0.00 | 0.00 | 3615316.47 | 0.00 | 0.322061E+10 | 0.237071E+10 | 0.00 | 0.64 |
April | 0.676327E+10 | 0.00 | 0.00 | 2141292.23 | 0.00 | 0.212479E+10 | 0.192861E+10 | 0.00 | 0.62 |
May | 0.210727E+10 | 59454247.98 | 0.00 | 12581988.22 | 0.00 | 45440925.89 | 0.610182E+10 | 0.00 | 0.89 |
June | 6093737.14 | 0.170441E+10 | 0.00 | 17752120.36 | 294240.39 | 0.00 | 0.297634E+10 | 0.00 | 0.93 |
July | 9122694.90 | 0.199755E+10 | 0.00 | 16548713.50 | 124762.47 | 0.00 | 0.263678E+10 | 0.00 | 0.92 |
August | 4533215.22 | 0.147543E+10 | 0.00 | 21875730.64 | 0.00 | 0.00 | 0.350173E+10 | 0.00 | 0.99 |
September | 0.600414E+09 | 0.540545E+09 | 0.00 | 24163630.39 | 0.00 | 0.00 | 0.523426E+10 | 0.00 | 1.05 |
October | 0.495247E+10 | 4066655.05 | 0.00 | 9824748.79 | 0.00 | 0.165651E+10 | 0.580087E+10 | 0.00 | 0.77 |
November | 0.923920E+10 | 0.00 | 0.00 | 2266920.65 | 0.00 | 0.203404E+10 | 0.155653E+10 | 0.00 | 0.60 |
December | 0.827475E+10 | 0.00 | 0.00 | 650964.56 | 0.00 | 0.669402E+10 | 0.616479E+09 | 0.00 | 0.56 |
Annual Sum or Average | 0.565393E+11 | 0.578146E+10 | 0.00 | 0.112246E+09 | 419002.87 | 0.244248E+11 | 0.335797E+11 | 0.00 | 0.76 |
Minimum of Months | 4533215.22 | 0.00 | 0.00 | 343355.34 | 0.00 | 0.00 | 0.363989E+09 | 0.00 | 0.54 |
Maximum of Months | 0.990168E+10 | 0.199755E+10 | 0.00 | 24163630.39 | 294240.39 | 0.669402E+10 | 0.610182E+10 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.373866E+10 | 0.00 | 0.00 | 1069148.82 | 0.00 | 0.770089E+09 | 0.883774E+09 | 0.00 | 0.44 |
February | 0.297870E+10 | 0.00 | 0.00 | 689227.66 | 0.00 | 0.142713E+10 | 0.589621E+09 | 0.00 | 0.43 |
March | 0.260562E+10 | 0.00 | 0.00 | 2887138.34 | 0.00 | 0.766598E+09 | 0.180625E+10 | 0.00 | 0.60 |
April | 0.229249E+10 | 0.00 | 0.00 | 2384740.23 | 0.00 | 0.492048E+09 | 0.180389E+10 | 0.00 | 0.58 |
May | 0.448339E+09 | 30500629.55 | 0.00 | 8078277.98 | 0.00 | 1055771.09 | 0.407410E+10 | 0.00 | 0.98 |
June | 1337740.10 | 0.846990E+09 | 0.00 | 7004473.67 | 0.00 | 0.00 | 0.121460E+10 | 0.00 | 0.82 |
July | 500803.11 | 0.103130E+10 | 0.00 | 6119241.81 | 0.00 | 0.00 | 0.970647E+09 | 0.00 | 0.78 |
August | 576017.27 | 0.760987E+09 | 0.00 | 8407607.13 | 0.00 | 0.00 | 0.141585E+10 | 0.00 | 0.85 |
September | 0.168786E+09 | 0.267955E+09 | 0.00 | 10768950.55 | 0.00 | 0.00 | 0.255842E+10 | 0.00 | 0.98 |
October | 0.150230E+10 | 2175359.36 | 0.00 | 6684548.51 | 0.00 | 0.569598E+09 | 0.394534E+10 | 0.00 | 0.79 |
November | 0.317138E+10 | 0.00 | 0.00 | 2347311.24 | 0.00 | 0.464665E+09 | 0.165378E+10 | 0.00 | 0.53 |
December | 0.316922E+10 | 0.00 | 0.00 | 986372.70 | 0.00 | 0.189897E+10 | 0.748634E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.200779E+11 | 0.293991E+10 | 0.00 | 57427038.66 | 0.00 | 0.639015E+10 | 0.216649E+11 | 0.00 | 0.69 |
Minimum of Months | 500803.11 | 0.00 | 0.00 | 689227.66 | 0.00 | 0.00 | 0.589621E+09 | 0.00 | 0.43 |
Maximum of Months | 0.373866E+10 | 0.103130E+10 | 0.00 | 10768950.55 | 0.00 | 0.189897E+10 | 0.407410E+10 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.346556E+10 | 0.00 | 0.00 | 526685.45 | 0.00 | 0.137439E+10 | 0.472032E+09 | 0.00 | 0.45 |
February | 0.290806E+10 | 0.00 | 0.00 | 254320.00 | 0.00 | 0.179824E+10 | 0.236642E+09 | 0.00 | 0.43 |
March | 0.259585E+10 | 0.00 | 0.00 | 1748804.31 | 0.00 | 0.111566E+10 | 0.106902E+10 | 0.00 | 0.56 |
April | 0.237275E+10 | 0.00 | 0.00 | 1256423.45 | 0.00 | 0.750192E+09 | 0.100031E+10 | 0.00 | 0.54 |
May | 0.793484E+09 | 32333287.35 | 0.00 | 4283343.38 | 0.00 | 5699744.39 | 0.230826E+10 | 0.00 | 0.79 |
June | 52998138.74 | 0.811941E+09 | 0.00 | 2917071.75 | 24332023.51 | 0.00 | 0.806543E+09 | 0.00 | 0.71 |
July | 52242968.23 | 0.935413E+09 | 0.00 | 2584325.78 | 35383862.87 | 0.00 | 0.642151E+09 | 0.00 | 0.69 |
August | 57954892.54 | 0.707621E+09 | 0.00 | 3740420.08 | 10983981.17 | 0.00 | 0.116650E+10 | 0.00 | 0.74 |
September | 0.308622E+09 | 0.263346E+09 | 0.00 | 5265026.29 | 5387272.73 | 0.00 | 0.152375E+10 | 0.00 | 0.82 |
October | 0.177177E+10 | 2641545.76 | 0.00 | 3781202.00 | 0.00 | 0.780226E+09 | 0.226416E+10 | 0.00 | 0.67 |
November | 0.319454E+10 | 0.00 | 0.00 | 1232460.53 | 0.00 | 0.820450E+09 | 0.870330E+09 | 0.00 | 0.51 |
December | 0.281045E+10 | 0.00 | 0.00 | 441643.80 | 0.00 | 0.260661E+10 | 0.359222E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.203843E+11 | 0.275330E+10 | 0.00 | 28031726.81 | 76087140.28 | 0.925147E+10 | 0.127189E+11 | 0.00 | 0.62 |
Minimum of Months | 52242968.23 | 0.00 | 0.00 | 254320.00 | 0.00 | 0.00 | 0.236642E+09 | 0.00 | 0.43 |
Maximum of Months | 0.346556E+10 | 0.935413E+09 | 0.00 | 5265026.29 | 35383862.87 | 0.260661E+10 | 0.230826E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.329345E+10 | 0.00 | 0.00 | 430373.57 | 0.00 | 0.157623E+10 | 0.404306E+09 | 0.00 | 0.45 |
February | 0.280533E+10 | 0.00 | 0.00 | 202736.65 | 0.00 | 0.191835E+10 | 0.192790E+09 | 0.00 | 0.43 |
March | 0.244534E+10 | 0.00 | 0.00 | 1640350.93 | 0.00 | 0.127373E+10 | 0.101370E+10 | 0.00 | 0.56 |
April | 0.233825E+10 | 0.00 | 0.00 | 1110872.88 | 0.00 | 0.805793E+09 | 0.917690E+09 | 0.00 | 0.53 |
May | 0.794714E+09 | 32315065.40 | 0.00 | 4078856.84 | 0.00 | 21168210.33 | 0.222969E+10 | 0.00 | 0.78 |
June | 52892612.99 | 0.811815E+09 | 0.00 | 2918220.42 | 24332072.69 | 0.00 | 0.801794E+09 | 0.00 | 0.71 |
July | 52099398.69 | 0.935015E+09 | 0.00 | 2605716.32 | 35368265.11 | 0.00 | 0.639997E+09 | 0.00 | 0.69 |
August | 57817159.87 | 0.707599E+09 | 0.00 | 3751771.99 | 11007896.19 | 0.00 | 0.116163E+10 | 0.00 | 0.74 |
September | 0.313018E+09 | 0.263406E+09 | 0.00 | 5244951.03 | 5392688.82 | 0.00 | 0.150636E+10 | 0.00 | 0.82 |
October | 0.177247E+10 | 2637585.64 | 0.00 | 3624695.80 | 0.00 | 0.829204E+09 | 0.215739E+10 | 0.00 | 0.66 |
November | 0.317799E+10 | 0.00 | 0.00 | 1097599.84 | 0.00 | 0.917846E+09 | 0.745709E+09 | 0.00 | 0.50 |
December | 0.267783E+10 | 0.00 | 0.00 | 371217.31 | 0.00 | 0.276208E+10 | 0.306874E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.197812E+11 | 0.275279E+10 | 0.00 | 27077363.58 | 76100922.81 | 0.101044E+11 | 0.120779E+11 | 0.00 | 0.61 |
Minimum of Months | 52099398.69 | 0.00 | 0.00 | 202736.65 | 0.00 | 0.00 | 0.192790E+09 | 0.00 | 0.43 |
Maximum of Months | 0.329345E+10 | 0.935015E+09 | 0.00 | 5244951.03 | 35368265.11 | 0.276208E+10 | 0.222969E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.312508E+10 | 0.00 | 0.00 | 306402.64 | 0.00 | 0.179536E+10 | 0.300721E+09 | 0.00 | 0.44 |
February | 0.265611E+10 | 0.00 | 0.00 | 145888.68 | 0.00 | 0.208781E+10 | 0.144766E+09 | 0.00 | 0.43 |
March | 0.225120E+10 | 0.00 | 0.00 | 1436323.45 | 0.00 | 0.148853E+10 | 0.914094E+09 | 0.00 | 0.54 |
April | 0.227058E+10 | 0.00 | 0.00 | 875952.55 | 0.00 | 0.932784E+09 | 0.764102E+09 | 0.00 | 0.51 |
May | 0.895833E+09 | 32285496.00 | 0.00 | 3586423.19 | 0.00 | 33655501.26 | 0.198445E+10 | 0.00 | 0.75 |
June | 53705836.24 | 0.807880E+09 | 0.00 | 2738112.62 | 24679669.68 | 0.00 | 0.787613E+09 | 0.00 | 0.70 |
July | 52682811.89 | 0.927694E+09 | 0.00 | 2456822.05 | 35786183.22 | 0.00 | 0.636751E+09 | 0.00 | 0.68 |
August | 57187663.05 | 0.704322E+09 | 0.00 | 3563734.56 | 11226411.21 | 0.00 | 0.114311E+10 | 0.00 | 0.74 |
September | 0.324139E+09 | 0.263311E+09 | 0.00 | 4972254.07 | 5528427.76 | 0.00 | 0.145699E+10 | 0.00 | 0.81 |
October | 0.174480E+10 | 2637677.76 | 0.00 | 3286333.00 | 0.00 | 0.914858E+09 | 0.199348E+10 | 0.00 | 0.65 |
November | 0.309158E+10 | 0.00 | 0.00 | 926637.92 | 0.00 | 0.107396E+10 | 0.618515E+09 | 0.00 | 0.50 |
December | 0.250766E+10 | 0.00 | 0.00 | 286845.57 | 0.00 | 0.294967E+10 | 0.251448E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.190306E+11 | 0.273813E+10 | 0.00 | 24581730.29 | 77220691.87 | 0.112766E+11 | 0.109960E+11 | 0.00 | 0.60 |
Minimum of Months | 52682811.89 | 0.00 | 0.00 | 145888.68 | 0.00 | 0.00 | 0.144766E+09 | 0.00 | 0.43 |
Maximum of Months | 0.312508E+10 | 0.927694E+09 | 0.00 | 4972254.07 | 35786183.22 | 0.294967E+10 | 0.199348E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.505506E+10 | 0.00 | 0.00 | 314163.87 | 0.00 | 0.419289E+10 | 0.370583E+09 | 0.00 | 0.39 |
February | 0.421696E+10 | 0.00 | 0.00 | 159267.73 | 0.00 | 0.467950E+10 | 0.174603E+09 | 0.00 | 0.39 |
March | 0.377685E+10 | 0.00 | 0.00 | 1972771.61 | 0.00 | 0.324544E+10 | 0.139924E+10 | 0.00 | 0.47 |
April | 0.400138E+10 | 0.00 | 0.00 | 921446.38 | 0.00 | 0.215694E+10 | 0.970971E+09 | 0.00 | 0.43 |
May | 0.183099E+10 | 29140659.03 | 0.00 | 5245672.56 | 0.00 | 74902944.81 | 0.307577E+10 | 0.00 | 0.61 |
June | 16159365.06 | 0.134182E+10 | 0.00 | 4546350.45 | 15536821.29 | 0.00 | 0.122527E+10 | 0.00 | 0.58 |
July | 8598391.35 | 0.151763E+10 | 0.00 | 4069185.34 | 39716791.07 | 0.00 | 0.101901E+10 | 0.00 | 0.56 |
August | 31805396.00 | 0.110207E+10 | 0.00 | 5744734.33 | 4318381.89 | 0.00 | 0.166797E+10 | 0.00 | 0.61 |
September | 0.465537E+09 | 0.356341E+09 | 0.00 | 9104771.65 | 5592275.40 | 1608907.20 | 0.248452E+10 | 0.00 | 0.68 |
October | 0.303375E+10 | 324952.38 | 0.00 | 5106801.05 | 0.00 | 0.193134E+10 | 0.321158E+10 | 0.00 | 0.54 |
November | 0.523645E+10 | 0.00 | 0.00 | 1219028.02 | 0.00 | 0.260787E+10 | 0.909327E+09 | 0.00 | 0.43 |
December | 0.418136E+10 | 0.00 | 0.00 | 336607.08 | 0.00 | 0.603871E+10 | 0.345189E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.318549E+11 | 0.434733E+10 | 0.00 | 38740800.05 | 65164269.65 | 0.249292E+11 | 0.168540E+11 | 0.00 | 0.51 |
Minimum of Months | 8598391.35 | 0.00 | 0.00 | 159267.73 | 0.00 | 0.00 | 0.174603E+09 | 0.00 | 0.39 |
Maximum of Months | 0.523645E+10 | 0.151763E+10 | 0.00 | 9104771.65 | 39716791.07 | 0.603871E+10 | 0.321158E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.239012E+10 | 0.00 | 0.00 | 133372.65 | 0.00 | 0.224215E+10 | 0.159764E+09 | 0.00 | 0.39 |
February | 0.202766E+10 | 0.00 | 0.00 | 66465.29 | 0.00 | 0.241279E+10 | 80918232.75 | 0.00 | 0.39 |
March | 0.174723E+10 | 0.00 | 0.00 | 943342.92 | 0.00 | 0.177130E+10 | 0.673293E+09 | 0.00 | 0.47 |
April | 0.189490E+10 | 0.00 | 0.00 | 405824.27 | 0.00 | 0.119544E+10 | 0.446813E+09 | 0.00 | 0.43 |
May | 0.948245E+09 | 15581598.59 | 0.00 | 2533958.55 | 0.00 | 41477518.51 | 0.148589E+10 | 0.00 | 0.61 |
June | 6781223.53 | 0.681366E+09 | 0.00 | 2263319.88 | 8152772.33 | 0.00 | 0.625834E+09 | 0.00 | 0.59 |
July | 5109999.81 | 0.769358E+09 | 0.00 | 2022398.53 | 20474491.47 | 0.00 | 0.523824E+09 | 0.00 | 0.57 |
August | 16139281.17 | 0.562997E+09 | 0.00 | 2865708.33 | 2385399.35 | 0.00 | 0.854298E+09 | 0.00 | 0.62 |
September | 0.236864E+09 | 0.184122E+09 | 0.00 | 4533510.94 | 3112168.62 | 802437.35 | 0.125811E+10 | 0.00 | 0.69 |
October | 0.150769E+10 | 232219.87 | 0.00 | 2528252.44 | 0.00 | 0.988802E+09 | 0.159133E+10 | 0.00 | 0.55 |
November | 0.256360E+10 | 0.00 | 0.00 | 598527.83 | 0.00 | 0.135219E+10 | 0.449703E+09 | 0.00 | 0.43 |
December | 0.195204E+10 | 0.00 | 0.00 | 154979.60 | 0.00 | 0.315353E+10 | 0.162940E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.152964E+11 | 0.221366E+10 | 0.00 | 19049661.21 | 34124831.77 | 0.131585E+11 | 0.831272E+10 | 0.00 | 0.51 |
Minimum of Months | 5109999.81 | 0.00 | 0.00 | 66465.29 | 0.00 | 0.00 | 80918232.75 | 0.00 | 0.39 |
Maximum of Months | 0.256360E+10 | 0.769358E+09 | 0.00 | 4533510.94 | 20474491.47 | 0.315353E+10 | 0.159133E+10 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.230966E+10 | 0.00 | 0.00 | 109194.70 | 0.00 | 0.233995E+10 | 0.129322E+09 | 0.00 | 0.39 |
February | 0.197237E+10 | 0.00 | 0.00 | 55845.55 | 0.00 | 0.247184E+10 | 70748518.10 | 0.00 | 0.39 |
March | 0.169408E+10 | 0.00 | 0.00 | 863804.91 | 0.00 | 0.184871E+10 | 0.619697E+09 | 0.00 | 0.46 |
April | 0.183736E+10 | 0.00 | 0.00 | 358376.99 | 0.00 | 0.127321E+10 | 0.403190E+09 | 0.00 | 0.43 |
May | 0.100358E+10 | 15540116.48 | 0.00 | 2349625.06 | 0.00 | 45171138.33 | 0.137535E+10 | 0.00 | 0.60 |
June | 7148451.61 | 0.679818E+09 | 0.00 | 2203044.91 | 8199955.47 | 0.00 | 0.617759E+09 | 0.00 | 0.59 |
July | 5163551.39 | 0.766464E+09 | 0.00 | 1975505.96 | 20556768.26 | 0.00 | 0.520075E+09 | 0.00 | 0.56 |
August | 16164881.05 | 0.561586E+09 | 0.00 | 2809924.34 | 2407440.55 | 0.00 | 0.845865E+09 | 0.00 | 0.62 |
September | 0.243995E+09 | 0.184110E+09 | 0.00 | 4436627.74 | 3153514.30 | 802090.72 | 0.123579E+10 | 0.00 | 0.69 |
October | 0.153424E+10 | 232046.15 | 0.00 | 2384760.91 | 0.00 | 0.101137E+10 | 0.150070E+10 | 0.00 | 0.54 |
November | 0.250143E+10 | 0.00 | 0.00 | 552678.19 | 0.00 | 0.141745E+10 | 0.430235E+09 | 0.00 | 0.43 |
December | 0.188497E+10 | 0.00 | 0.00 | 138294.16 | 0.00 | 0.322212E+10 | 0.150971E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.150102E+11 | 0.220775E+10 | 0.00 | 18237683.42 | 34317678.58 | 0.136306E+11 | 0.789969E+10 | 0.00 | 0.51 |
Minimum of Months | 5163551.39 | 0.00 | 0.00 | 55845.55 | 0.00 | 0.00 | 70748518.10 | 0.00 | 0.39 |
Maximum of Months | 0.250143E+10 | 0.766464E+09 | 0.00 | 4436627.74 | 20556768.26 | 0.322212E+10 | 0.150070E+10 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.196944E+10 | 0.00 | 0.00 | 73107.66 | 0.00 | 0.269651E+10 | 85300962.54 | 0.00 | 0.39 |
February | 0.166605E+10 | 0.00 | 0.00 | 38965.31 | 0.00 | 0.278233E+10 | 51272038.16 | 0.00 | 0.38 |
March | 0.150889E+10 | 0.00 | 0.00 | 694994.55 | 0.00 | 0.208137E+10 | 0.505839E+09 | 0.00 | 0.45 |
April | 0.160454E+10 | 0.00 | 0.00 | 259434.36 | 0.00 | 0.154102E+10 | 0.317027E+09 | 0.00 | 0.42 |
May | 0.108677E+10 | 15428056.77 | 0.00 | 1935336.57 | 0.00 | 60314869.74 | 0.115131E+10 | 0.00 | 0.57 |
June | 16960426.07 | 0.676007E+09 | 0.00 | 2047944.08 | 8404044.80 | 0.00 | 0.589269E+09 | 0.00 | 0.58 |
July | 8654425.95 | 0.760089E+09 | 0.00 | 1861809.18 | 20703285.37 | 0.00 | 0.510747E+09 | 0.00 | 0.56 |
August | 18021383.84 | 0.559280E+09 | 0.00 | 2653793.44 | 2446531.33 | 0.00 | 0.826421E+09 | 0.00 | 0.61 |
September | 0.255271E+09 | 0.184073E+09 | 0.00 | 4223043.06 | 3219250.33 | 806076.33 | 0.119206E+10 | 0.00 | 0.68 |
October | 0.157429E+10 | 231998.19 | 0.00 | 2081025.92 | 0.00 | 0.106711E+10 | 0.131059E+10 | 0.00 | 0.52 |
November | 0.230836E+10 | 0.00 | 0.00 | 444452.81 | 0.00 | 0.163276E+10 | 0.375214E+09 | 0.00 | 0.43 |
December | 0.167548E+10 | 0.00 | 0.00 | 98322.86 | 0.00 | 0.343930E+10 | 0.118925E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.136927E+11 | 0.219511E+10 | 0.00 | 16412229.78 | 34773111.84 | 0.153015E+11 | 0.703397E+10 | 0.00 | 0.50 |
Minimum of Months | 8654425.95 | 0.00 | 0.00 | 38965.31 | 0.00 | 0.00 | 51272038.16 | 0.00 | 0.38 |
Maximum of Months | 0.230836E+10 | 0.760089E+09 | 0.00 | 4223043.06 | 20703285.37 | 0.343930E+10 | 0.131059E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101206E+10 | 0.00 | 0.00 | 25004.79 | 0.00 | 0.364608E+10 | 34361988.15 | 0.00 | 0.38 |
February | 0.794733E+09 | 0.00 | 0.00 | 17542.90 | 0.00 | 0.362937E+10 | 27671181.51 | 0.00 | 0.38 |
March | 0.882638E+09 | 0.00 | 0.00 | 461407.25 | 0.00 | 0.273399E+10 | 0.363295E+09 | 0.00 | 0.44 |
April | 0.104988E+10 | 0.00 | 0.00 | 142719.35 | 0.00 | 0.212434E+10 | 0.195709E+09 | 0.00 | 0.41 |
May | 0.107478E+10 | 15538211.38 | 0.00 | 1395980.69 | 0.00 | 0.161483E+09 | 0.855602E+09 | 0.00 | 0.54 |
June | 27950252.07 | 0.675542E+09 | 0.00 | 1926674.63 | 8471876.25 | 0.00 | 0.561730E+09 | 0.00 | 0.58 |
July | 19598802.89 | 0.750760E+09 | 0.00 | 1639571.84 | 20952135.14 | 0.00 | 0.488703E+09 | 0.00 | 0.56 |
August | 29567564.38 | 0.568125E+09 | 0.00 | 2501467.89 | 2367012.55 | 0.00 | 0.820241E+09 | 0.00 | 0.62 |
September | 0.273754E+09 | 0.184450E+09 | 0.00 | 4076655.55 | 3064315.99 | 12888316.97 | 0.114268E+10 | 0.00 | 0.69 |
October | 0.141386E+10 | 260064.76 | 0.00 | 1747941.89 | 0.00 | 0.131573E+10 | 0.110303E+10 | 0.00 | 0.51 |
November | 0.161568E+10 | 0.00 | 0.00 | 338436.29 | 0.00 | 0.237187E+10 | 0.271351E+09 | 0.00 | 0.43 |
December | 0.828560E+09 | 0.00 | 0.00 | 48865.51 | 0.00 | 0.426904E+10 | 74891840.38 | 0.00 | 0.38 |
Annual Sum or Average | 0.902305E+10 | 0.219468E+10 | 0.00 | 14322268.60 | 34855339.94 | 0.202648E+11 | 0.593927E+10 | 0.00 | 0.49 |
Minimum of Months | 19598802.89 | 0.00 | 0.00 | 17542.90 | 0.00 | 0.00 | 27671181.51 | 0.00 | 0.38 |
Maximum of Months | 0.161568E+10 | 0.750760E+09 | 0.00 | 4076655.55 | 20952135.14 | 0.426904E+10 | 0.114268E+10 | 0.00 | 0.69 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:34:29
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.234618E+12 | 0.255604E+11 | 0.00 | 0.658716E+11 | 0.110584E+11 |
February | 0.307382E+12 | 0.265623E+11 | 0.00 | 0.618418E+11 | 0.121337E+11 |
March | 0.402278E+12 | 0.235501E+11 | 0.00 | 0.579780E+11 | 0.118673E+11 |
April | 0.433637E+12 | 0.218040E+11 | 0.00 | 0.496536E+11 | 0.697304E+10 |
May | 0.534692E+12 | 0.103500E+11 | 0.00 | 0.359758E+11 | 0.221527E+11 |
June | 0.583055E+12 | -0.216857E+10 | 0.00 | 0.138676E+10 | 0.111956E+12 |
July | 0.539678E+12 | -0.298500E+10 | 0.00 | -0.172829E+10 | 0.119689E+12 |
August | 0.529489E+12 | -0.141343E+10 | 0.00 | 0.603792E+10 | 0.115074E+12 |
September | 0.388854E+12 | 0.343929E+10 | 0.00 | 0.202422E+11 | 0.808791E+11 |
October | 0.311670E+12 | 0.196585E+11 | 0.00 | 0.573227E+11 | 0.155096E+11 |
November | 0.257420E+12 | 0.233409E+11 | 0.00 | 0.597072E+11 | 0.917164E+10 |
December | 0.179873E+12 | 0.325013E+11 | 0.00 | 0.722024E+11 | 0.155093E+11 |
Annual Sum or Average | 0.470265E+13 | 0.180200E+12 | 0.00 | 0.486492E+12 | 0.531974E+12 |
Minimum of Months | 0.179873E+12 | -0.298500E+10 | 0.00 | -0.172829E+10 | 0.697304E+10 |
Maximum of Months | 0.583055E+12 | 0.325013E+11 | 0.00 | 0.722024E+11 | 0.119689E+12 |